Upload
fennsen
View
366
Download
21
Embed Size (px)
Citation preview
Vitotronic 050, type HK1W
Vitotronic 050, type HK3W
VITOTRONIC 050
Installation and
service instructionsfor heating engineers
Vitotronic050
Type HK1W and HK3W
Weather−compensated, digital heating circuit controls
See applicability on the last page.
5862739GB3/2005 Please keep safe
2
Safety instructions
Safety instructions
¨ Please follow these safety instructions closely to prevent accidents and
material losses.
Safety instructions explained
¨Danger
This symbol warns against the
risk of injury.
!Please note
This symbol warns against the
risk of material losses and
environmental pollution.
Note
Details identified by the word "Note"
contain additional information.
Target group
These instructions are exclusively
designed for qualified personnel.
Work on gas equipment must only
be carried out by a registered gas
fitter.
Electrical work must only be
carried out by a qualified
electrician.
The system must be
commissioned by the system
installer or a qualified person
authorised by the installer.
Regulations
Observe the following when working
on this system
all legal instructions regarding the
prevention of accidents,
all legal instructions regarding
environmental protection,
regulations issued by professional
bodies,
all current safety regulations as
defined by DIN, EN, DVGW, TRGI,
TRF, VDE and all locally applicable
standards.
If you notice the smell of gas
¨Danger
Escaping gas can lead to
explosions which may lead to
serious injury.
Do not smoke! Prevent
naked flames and sparks.
Never switch electrical lights
or equipment.
Open windows and doors.
Close the gas shut−off valve.
Shut down the heating
system.
Remove all people from the
danger zone.
Observe the safety
regulations of your local gas
supplier found on the gas
meter.
58
62
73
9G
B
3
Safety instructions
Safety instructions (cont.)
If you smell flue gas
¨Danger
Flue gas can lead to
life−threatening poisoning.
Shut down the heating
system.
Ventilate the boiler room.
Close all doors leading to the
living space.
Working on the heating system
Isolate the system from the mains
power supply and check that it is
no longer ’live’, e.g. by removing a
separate fuse or by means of a
mains isolator.
Safeguard the system against
unauthorised reconnection.
When using gas as fuel, also close
the main gas shut−off valve and
safeguard against unauthorised
reopening.
Repair work
!Please note
Repairing components which
fulfil a safety function can
compromise the safe operation
of your heating system.
Replace faulty components
only with original Viessmann
spare parts.
Ancillary components, spare and
wearing parts
!Please note
Spare and wearing parts which
have not been tested together
with the heating system can
compromise its function.
Installing non−authorised
components and
non−approved modifications/
conversions can compromise
safety and may infringe our
warranty conditions.
For replacements, use only
original spare parts from
Viessmann or those which are
approved by Viessmann.
58
62
73
9G
B
4
Index
Index
Heating system designs
System versions 1 to 3 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installation
Summary of electrical connections 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installing the mounting bracket and control unit back 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Inserting cables and applying strain relief 14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Sensor connection 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Pump connection 16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connecting the actuator drives 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connecting the central fault messages to pluggÖ 18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
External connections on plugaVD 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Power supply 20. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installing the control unit front 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Opening the control unit 22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Commissioning
Controls and display elements 23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Checking the heating circuit allocation 24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Changing the display language 24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connecting control unit to LON system 24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Carrying out a user check 26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connecting the control unit to the Viessmann 2−wire BUS system 27. . . . . . . . . . . . . . . . .
Matching the coding addresses to the system version 28. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Checking outputs (actuators) and sensors 29. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Adjusting heating curves 30. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Service scans
Service level summary 33. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Temperatures and brief scans 34. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Scanning operating conditions 36. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Troubleshooting
Faults which are displayed at the programming unit 37. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Downloading fault codes from the fault memory (fault history) 46. . . . . . . . . . . . . . . . . . . . . . .
Function description
Heating circuit control 47. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cylinder temperature control 51. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5
Index
Index (cont.)
Components
Components from the parts list 55. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Radio clock receiver 60. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Mixer circuit extension kit 61. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Mixer motors 62. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installation examples 64. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Temperature limiter for maximum temperature limiting 65. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Remote control 66. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Room temperature sensor 72. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Function extension 0−10V 73. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Coding
Resetting codes into the delivered condition 74. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Code 1 74. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Code 2 77. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Screed function diagrams 99. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parts lists
Parts list type HK1W 102. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parts list type HK3W 104. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connecting and wiring diagrams
Summary 106. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Main PCB low voltage 107. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Main PCB 230V~ 108 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Mixer extension PCB 109. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Specification 110. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Declaration of conformity 111. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Keyword index 112. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
58
62
73
9G
B
6
Heating system designs
System version 1
A Vitotronic 050
B DHW cylinder
C Mixer circuit
(for typeHK1W only one mixer
circuit can be connected)
D LON or Viessman 2−wire BUS
connection
Plug
! Outside temperature sensor
? Flow temperature sensor
% Cylinder temperature sensor
sÖ Heating circuit pump
sA Cylinder primary pump
sK DHW circulation pump
fÖ Power supply 230V/50 Hz
gS Mixer motor
aVD External hook−up
(see page 19)
Coding
For systems with a DHW cylinder and for additional mixer circuits for type
HK3W, coding addresses "00:2" to "00:10" are automatically set.
58
62
73
9G
B
C
2
20
52
M2
C
2
20
52
M2
C
401
52
20 2
143 5
21
28
B
282
20
52
M1
A
21
5
D
2M1
2
20
52
M22
20
52
M2
401
52 20 214
3 5 21 28
2820
52
21
5
17B
G
20
E H
20
LN
7
Heating system designs
System version 2
System with underfloor heating system
The underfloor heating mixer circuit must be M1 if the underfloor heating
system is regulated with flow and return temperature sensors (optimised
control).
Pumps with underfloor heating circuit:
A Vitotronic050
B DHW cylinder
C Mixer circuit,
only for typeHK3W
D Underfloor heating circuit
E Temperature limiter (max. limit)
F LON or Viessmann 2−wire BUS
connection
G Primary pump
H Secondary pump
(after system separation)
58
62
73
9G
B
8
Heating system designs
System version 2 (cont.)
Plug
! Outside temperature sensor
? Flow temperature sensor
% Cylinder temperature sensor
aJB Return temperature sensor
sÖ Heating circuit pump
(Primary pump)
sA Cylinder primary pump
sK DHW circulation pump
fÖ Power supply 230V/50 Hz
gS Mixer motor
aVD External hook−up
Coding
For systems with a DHW cylinder and for additional mixer circuits for type
HK3W, coding addresses "00:2" to "00:10" are automatically set.
Observe coding addresses "C7" and "C9" in conjunction with the optimised
underfloor heating circuit control.
58
62
73
9G
B
9
Heating system designs
System version 3
System with cylinder storage systemConnections for the cylinder storage system are always %, aJB, sÖM1 and
gSM1. A mixer circuit M1 cannot be connected under these circumstances.
For typeHK1W:
Insert plug ! for outside temperature sensor and plug ? for flow
temperature sensor (plugs supplied with Vitotrans 222) into the sockets. This
prevents fault messages being generated. When scanning via keyc the
actual temperatures from 8ºC upwards are displayed.
A Vitotronic050
B VitocellL100
C Vitotrans222
D Mixer circuit,
only for typeHK3W
E LON or Viessmann 2−wire BUS
connection
58
62
73
9G
B
D
2
20
52
M3
D
2
20
52
M2
C
52
20
21
B
5
5
28
52
20 2
143 5 21
28
17B
A140E
10
Heating system designs
System version 3 (cont.)
Plug
! Outside temperature
sensor
? Flow temperature sensor
% Cylinder temperature
sensor 1 and 2
aJB Temperature sensor
Vitotrans222
sÖ Primary pump
Cylinder storage system
sÖM2/M3 Heating circuit pump
Mixer circuit
sA Cylinder primary pump
sK DHW circulation pump
fÖ Power supply 230V/50 Hz
gS 3−way mixing valve
cylinder storage system
gSM2/M3 Mixer motor
Mixer circuit
aVD External hook−up
Required coding
4C : 1 Primary pump connection to plugsÖ
4E : 1 3−way mixing valve connection to pluggS
55 : 3 Cylinder thermostat cylinder storage system
58
62
73
9G
B
11
Installation
Summary of electrical connections
58
62
73
9G
B
52522020
22
M3M2M3M2M3M2
145145
117 B
52/3 M1
143
28215220 M1
M1
5040
156
12
Installation
Summary of electrical connections (cont.)
Mixer extension PCB
(only for type HK3W)
?M2/M3 Flow temperature sensor
sÖM2/M3 Heating circuit pump
gSM2/M3 Mixer motor
Main PCB low voltage
! Outside temperature sensor
?M1Flow temperature sensor
% Cylinder temperature sensor 1/
Cylinder temperature sensor2
for cylinder storage system
(accessories)
aJB Return temperature sensor or
temperature sensor cylinder
storage system (accessories)
aVD External hook−up
aVG KM BUS user
(accessories),
for typeHK1W only one
required per system
Main PCB 230V~
sÖM1 Heating circuit pump
or
Primary pump
Cylinder storage system
sA Cylinder primary pump
(accessories)
sK DHW circulation pump (on
site)
fÖ Power supply
gÖ Central fault message
gSM1 Mixer motor
or
Motor for 3−way mixing valve
cylinder storage system
aBH Power supply for accessories
When connecting external switching
contacts or components to the low
voltage of the control unit (aVD and
aVG), observe the safety
requirements of protection class II,
i.e. maintain an 8.0mm air
gap/creeping distance or a 2.0 mm
insulation thickness from ’live’
components.
For all on−site components (incl.
PC/laptops) ensure a safe electrical
separation in accordance with EN 60
335 or IEC 65.
58
62
73
9G
B
13
Installation
Installing the mounting bracket and control unit back
58
62
73
9G
B
1.
2.
14
Installation
Inserting cables and applying strain relief
A Cables with moulded strain relief
B On−site cables
Strip a maximum of 100 mm off
the cable insulation
58
62
73
9G
B
A
B
15
Installation
Sensor connection
A Flow temperature sensor mixer
circuit 3
(only for type HK3W)
B Flow temperature sensor mixer
circuit 2
(only for type HK3W)
C Outside temperature sensor
D Return temperature sensor
or
Temperature sensor cylinder
storage system (accessories)
E Cylinder temperature sensor
F Cylinder temperature sensor 2 in
conjunction with a cylinder
storage system (accessories)
G Flow temperature sensor
Mixer circuit1
Installation point for outside
temperature sensor
North or north−western wall,
2 to 2.5m above ground level; in
multi−storey buildings, in the upper
half of the second floor
Not above windows, doors or
ventilation outlets
Not immediately below balconies
or gutters
Do not render over
Connection
2−core cable with a maximum length
of 35m and a cross−section of
1.5mm2 (copper)
58
62
73
9G
B
17B 5 3/2
1 2 3 1 2 3 1 2 3
E F G
1
1 2 3
C D
2
1 2 3
B
2
1 2 3
A
16
Installation
Pump connection
Available pump connections
sÖM1 Heating circuit pump mixer circuitM1
or
Primary pump cylinder storage system
sÖM2/M3 Heating circuit pump mixer circuitM2/M3
(only for typeHK3W)
sA Cylinder primary pump
sK DHW circulation pump
Pumps 230 V~
A Contactor
B Pump
C Mains supply in accordance with
manufacturer’s instructions
Rated current: 4 (2) A~
Recommended
connecting
cable: H05VVF3G 0.75 mm2
or
H05RNF3G 0.75 mm2
58
62
73
9G
B
LN
ExternalON/OFF
L N PE
CB
A
B
L N PE
17
Installation
Pump connections (cont.)
Pumps 400 V~
A Contactor
B Pump
For controlling the contactor
Rated voltage: 230 V~
Rated current: 4 (2) A~
Recommended
connecting
cable: H05VVF3G 0.75 mm2
or
H05RNF3G 0.75 mm2
Connecting the actuator drives
| Open
~ Closed
Application:
Mixer motor mixer circuits
Motor for 3−way mixing valve for
cylinder storage system
Rated voltage: 230 V~
Rated current: max. 0.2 (0.1)A~
Recommended
connecting
cable: H05VVF3G 0.75 mm2
or
H05RNF3G 0.75 mm2
Run time: adjustable via coding
address "C3"
58
62
73
9G
B
LN L1 L2 L3 N PE
M3~
B
A
52
18
Installation
Connecting the central fault messaging to plug gÖ
Rated voltage: 230V~
Rated current: 4 (2) A~
Recommended
connecting
cable: H05VVF3G 0.75 mm2
or
H05RNF3G 0.75 mm2
58
62
73
9G
B
50
19
Installation
External connections on plug aVD
Zero volt contacts
A External heating program
changeover/
Extern. "Mixer open"
B Extern "Mixer closed"
External heating program
changeover/ Extern. "Mixer open"
The manually preselected heating
program can be modified via this
contact (see table below), and the
mixer can be opened.
Allocation to the heating circuits via
coding addresses "91" and "9A".
Extern. "Mixer closed"
Closing the zero volt contact closes
the mixer.
Allocation to the heating circuits via
coding address "99".
The function "mixer closed" has
priority over "mixer open".
!Please note
The heating circuit is no longer
protected from frost when the
mixer closes.
Manually preselectedheating program (with contact open)
Code 2 Changed heating program(with closed contact)
9
or
Central heating
OFF/DHW OFF
d5:0
(as delivered
condition)
<> Permanent operation with
reduced room
temperature/DHW OFF
w
or
Central heating
OFF/DHW ON
d5:1 <> Constant operation with
standard room
temperature/DHW in
rw Central heating
ON/DHW ON
p
accordance with coding
address "64"
58
62
73
9G
B
143
B
A
20
Installation
Power supply
RegulationsMake the mains connection and all required earthing (e.g fault current circuit)in accordance with IEC 364, the requirements of your local electricity supplier,
VDE regulations or all local and national regulations. Secure the control unit
supply with an appropriate fuse.
Mains isolator requirements (if necessary)
For combustion equipment to DIN VDE 0116, the mains isolator fitted on site
must comply with the requirements of DIN VDE 0116 "Section 6" [or localregulations]. Install the mains isolator outside the installation area. It must
simultaneously isolate all non−earthed conductors with at least 3 mm contact
separation.
Replacing the mains connecting cable3core cable selected from the following options: H05VVF3G 1.5 mm2
H05RNF3G 1.5 mm2
A Mains voltage 230 V~
B Fuse
C Mains isolator, 2−pole (on site)D Junction box (on site)
1. Check whether the mains power
cable to the control unit is fittedwith the correct fuse.
2. Connect the mains supply cableinside the junction box (on site)
and in plugfÖ.
¨DangerIncorrect core terminations can
cause severe injuries anddamage to the equipment.
Do not interchange cores "L1"
and "N":L1: brown
N: blue
PE: green/yellow
3. Insert plug fÖ into the control unit.
Colour coding to DIN IEC60757BN brown
BU blueGNYE green/yellow
58
62
73
9G
BD
L1PEN
A
B
C
21
Installation
Installing the control unit front
58
62
73
9G
B
22
Installation
Opening the control unit
58
62
73
9G
B
First key 1,2 or 3
C
BA H
D E
FG
23
Commissioning
Controls and display elements
A ON indicator (green)
B Fault indicator (red)
C Heating circuit selection keys
D User interface
A Central heating time
program
B DHW heating time
program
C DHW circulation pump
time program
H Holiday program
F DHW temperature
E Reduced room
temperature
I Heating curve slope
J Heating curve level
D Time/date
K Standby mode
L DHW only
G Heating and DHW
N Economy mode
M Party mode
a/b Adjusting values
d Confirmation
c Information
e Standard setting
E Rotary selector"ts" for
"Standard room temperature"
F ON/OFF switch
G Fuse
H Open flap
58
62
73
9G
B
24
Commissioning
Checking the heating circuit allocation
Check whether the label for the
heating circuit allocation has been
affixed to the corresponding array
of the programming unit.
Select the corresponding heating
circuit before making any
adjustments.
Changing the display language
1. Press c.
2. Selected the required language
with b.
3. Confirm with d.
Connecting control unit to LON system
The LON communication module (accessories) must be plugged in (see parts
list).
Note
Data transfer via the LON system can take several minutes.
Setting up LON user numbers
In code 1 via coding address "77".
In a LON system, the same number
cannot be allocated twice.
Updating LON users
Only possible if all users are
connected and the control unit is
programmed to be fault manager
(code "79:1").
1. Press L and d simultaneously
for approx. 2 s.
User check initiated (see page 26).
2. Press e.
The user list is updated after
approx. 2 minutes.
User check completed.
58
62
73
9G
B
25
Commissioning
Integrating the control unit into the LON system (cont.)
Single boiler system with Vitotronic 050 and Vitocom 300 downstream
User no. 1
Code "77:1"
User no. 10
Code "77:10"
User no. 11
Set code "77:11"
User no. 99
(fixed)
Control unit is
fault manager*1
Code "79:1"
Control unit is not
fault manager*1
Code "79:0"
Control unit is not
fault manager*1
Code "79:0"
Device is
fault manager
(fixed)
Send time via
LON
Code "7b:1"
Time received via
LON
Set code "81:3"
Time received via
LON
Set code "81:3"
Time received
via LON
(fixed)
Receive outside
temperature via
LON
Code "97:2"
Outside
temperature is
received via LON
Set code "97:1"
Outside
temperature is
received via LON
Set code "97:1"
Viessman system
number coding
"98:1"
Viessman system
number coding
"98:1"
Viessman system
number coding
"98:1"
Fault monitoring
LON user
Set code
"9C:20"
Fault monitoring
LON user
Set code
"9C:20"
Fault monitoring
LON user
Set code
"9C:20"
*1In each heating system, only one Vitotronic may be programmed as fault manager.
58
62
73
9G
B
LON
Vitotronic 200 Vitotronic 050 Vitotronic 050 Vitocom
LON LON
26
Commissioning
Carrying out a user check (in conjunction with LON System)
Communication with the system devices connected to the fault manager is
tested with a user check.
Preconditions:
The control unit must be programmed as fault manager (code "79:1")
The LON user number must be encoded in all control units (see page 24).
The fault manager user list must be up to date (see page24).
1. Press L and d simultaneously
for approx. 2 s.
User check initiated.
2. Select the required user with a or
b.
3. Activate check with d.
"Check" flashes until its
completion. The display and all
key illuminations of the selected
user flash for approx. 60 s.
During communication between
both devices
"Check OK" flashes
"Check not OK" flashes if there
is no communication between
both devices. Check the LON
connection and encoding (see
page25).
4. For checking further users,
proceed as described under items
2 and 3.
5. Press L and d simultaneously
for approx. 1 s.
User check completed.
58
62
73
9G
B
Participant check
1F01 : 01
User
number
Consecutive
list number
27
Commissioning
Connecting control unit to Viessmann 2−wire BUS system
The Viessmann 2−wire BUS communication module (accessories) must be
plugged in (see parts list).
A Communication module
B Rotary selector
1. Set the rotary selector on the
communication module in
accordance with the system
version between 4 and C (the
rotary selector must not be set the
same as the rotary selector of
another control unit).
2. In conjunction with a boiler
control unit
Adjust the differential
temperature at the above control
unit.
On the Vitotronic 050, set code
"9F:0".
Set code "97:1" if the outside
temperature is to be taken from
an outside temperature sensor
which is already connected.
Examples
A Vitotronic300, type KW3
B Vitotronic050
C Viessmann 2−wire BUS
58
62
73
9G
B
B
A
C C
BA B
5
S1
4
S1
28
Commissioning
Matching the coding addresses to the system version
In code1 adjust the following coding
addresses :
"00" System design
"A2"Cylinder priority
"A5"Heating circuit pump logic
function (economy mode)
"C5" Flow temperature minimum
limit
"C6" Flow temperature maximum
limit
In code2 set the following coding
address:
"4C" Function plugsÖ M1
"4E" Function pluggS M1
"55" Buffer cylinder system
"77" LON user number
"7F" Detached house or apartment
block
"98" Viessmann system number
Note
Further optional adjustments are listed in code1 and 2.
58
62
73
9G
B
29
Commissioning
Checking outputs (actuators) and sensors
Relay test
1. Press K and d simultaneously
for approx. 2 s.
Relay test is activated.
2. Control relay outputs
with a or b.
3. Press d. Relay test is completed.
The following relay outputs may be selected:
Output20 ON
Output52 OPEN,
Output52 Ntr.,
Output52 Closed
Cylinder primary pump ON
DHW circulation pump ON
Heating circuit pump M2 ON
Heating circuit pump M3 ON
MixerM2 OPEN
MixerM2 CLOSED
MixerM3 OPEN
MixerM3 CLOSED
Central fault messaging ON
Notes
The illuminated heating circuit
selector indicates the corresponding
heating circuit.
Changing the rotational direction of
the mixer motor, see page64.
Checking sensors
1. Press c.
Scanning operating conditions is
activated, see page 36.
2. Scan the actual temperatures with
a or b.
3. Press c. Scanning is completed.
58
62
73
9G
B
30
Commissioning
Adjusting heating curves
Heating curves represent the
relationship between the outside
temperature and the flow
temperature. To put it simply:
The lower the outside temperature,
the higher the flow temperature. The
room temperature again depends on
the flow temperature.
Settings in the delivered condition:
Slope "n"=1,4
Level "N"=0
A Underfloor heating
B Low temperature heating systems ([German] Energy Savings Order)
C Heating system with boiler water temperatures in excess of 75ºC
58
62
73
9G
B
Flo
w t
em
pera
ture
in
ºC
Outside temperature in ºC
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
2.2
2.4
2.6
2.8
3.0
3.2
3.4
Slope
31
Commissioning
Adjusting heating curves (cont.)
Changing slope and level (for each heating circuit separately)
1. I for slope, value adjustable
from 0.2 to 3.5;
J for level, value adjustable from
13 to +40 K.
2. a/b for the required value.
3. d to confirm.
A Change slope
B Change level
Changing the maximum limit for the flow temperature
(for each heating circuit separately)
Delivered condition 75ºC, change via
coding address "C6".
Note
For underfloor heating circuits, you
can select a maximum limit, e.g.
45ºC ; for this, observe the
system−specific maximum
permissible flow temperature.
The maximum limit does not replace
the maximum limit temperature
limiter.
58
62
73
9G
B
110
+20 −20Outside temperature in °C
3.5
1.4
0.2
A
B
Flo
w t
em
pera
ture
in
°C
32
Commissioning
Adjusting heating curves (cont.)
Adjust the set room temperature (for each heating circuit separately)
Standard room temperature:
Adjust the set temperature with
rotary selector"ts".
The value will automatically be
accepted after approx. 2s.
Reduced room temperature:
1. E for "Reduced room
temperature".
2. a/b for the required set
temperature.
3. d to confirm.
Example 1:
Adjustment of the standard room
temperature from 20 ºC to 26 ºC
Example 2:
Adjustment of the reduced room
temperature from 5 ºC to 14 ºC
AFlow temperature in ºC
BOutside temperature in ºC
CSet room temperature in ºC
DHeating circuit pump OFF
EHeating circuit pump ON
Accordingly, the heating curve is
adjusted along the set room
temperature axis, which results in
modified start−up/shutdown
characteristics of the heating circuit
pumps, if heating circuit pump logic
is activated.
58
62
73
9G
B
33
Service scans
Service level summary
Function Key combination Exit Page
Adjusting the display
contrast
Press d and asimultaneously; the display will darken
Press d and bsimultaneously;the display will getlighter
User check
(in conjunction with
LON system)
Press L and dsimultaneously for
approx. 2 s
Press L and dsimultaneously for
approx. 1 s
26
Relay test Press K and dsimultaneously for
approx. 2s
Press d 29
Temperatures and
brief scans
Press K and Gsimultaneously for
approx. 2s
Press d 34
Operating condition Press c Press c 36
Troubleshooting Press c Press d 37
Calling up
acknowledged fault
messages
Press d for approx. 2 s Press d NO TAG
Fault history Press G and dsimultaneously for
approx. 2 s
Press d 46
Resetting codes into
the delivered
condition
Press L and Gsimultaneously for
approx. 2 s; press econfirm with d
74
Code 1 Press K and Lsimultaneously for
approx. 2 s
Press K and Lsimultaneously for
approx.
1s
74
Code 2 Press L and Gsimultaneously for
approx. 2 s;
confirm with d
Press K and Gsimultaneously for
approx. 1s
77
58
62
73
9G
B
34
Service scans
Temperatures and brief scans
1. Press K and G simultaneously
for approx. 2 s.
2. Select the required scan with aor b.
3. Press d. Scanning is completed.
The following values can be scanned, subject to the actual equipment level:
Slope M1/M2/M3
Level M1/M2/M3
Outside temp. adj.
Outside temp. actual
Sensor 17B
Set DHW temp.
Actual DHW temp.
DHW Temp.1. actual
DHW temp.2. actual
Flow temperature, set
Flow temperature, actual
Room temp. set
Room temp. actual
Brief scan 1
to
Brief scan9
The adjusted outside temperature
can be reset to the current outside
temperature with e.
If a sensor is connected.
If a cylinder temperature sensor is
connected.
If two cylinder temperature
sensors are connected.
If a remote control unit is
connected.
See page 35.
58
62
73
9G
B
35
Service scans
Temperatures and brief scans (cont.)
8ssm
an
n 2
−wir
e
N/A
So
ftw
are
vers
ion
Rem
ote
co
ntr
ol
Mix
er
cir
cu
itM
3
N/A
So
lar
co
ntr
ol
un
it s
oft
ware
8N
um
ber
of
Vie
ss
BU
S u
sers
So
ftw
are
vers
ion
Mix
er
exte
nsio
nM
2/M
3 P
CB
Op
era
tin
g m
od
eM
ixer
circ
uitM
30
w/o
rem
ote
co
ntr
ol
1w
ith
Vito
tro
l200
2w
ith
Vito
tro
l300
No
de a
dd
ress
Nu
mb
er
LO
N u
ser
N/A
8N
um
ber
of
KM
BU
S u
sers
So
ftw
are
vers
ion
Co
mm
un
ica
tio
nm
od
ule
So
ftw
are
vers
ion
Rem
ote
co
ntr
ol
Mix
er
circ
uit
M2
N/A
s/s
yste
m n
o.
on
N/A
N/A
8N
/A
N/A
Op
era
tng
mo
de
Mix
er
circ
uitM
2
0w
/o r
em
ote
co
ntr
ol
1w
ith
Vit
otr
ol200
2w
ith
Vit
otr
ol300
Su
bn
et
ad
dre
ss/
So
ftw
are
vers
ioN
eu
ron
ch
ip
N/A
ef scan
8
s "
00")
So
ftw
are
vers
ion
Pro
gra
mm
ing
un
it
So
ftw
are
vers
ion
Rem
ote
co
ntr
ol
Mix
er
cir
cu
it M
1
So
ftw
are
vers
ion
co
mm
un
icati
on
co
−pro
cesso
r
see c
od
ing
de2
Brie
8
Syste
m d
esig
n
(see c
od
ing
ad
dre
ss
So
ftw
are
vers
ion
Co
ntr
ol
un
it
Op
era
tin
g m
od
e
Mix
er
cir
cu
it M
1
0w
/o r
em
ote
co
ntr
ol
1w
ith
Vit
otr
ol200
2w
ith
Vit
otr
ol300
LO
N u
ser
no
.
SN
VT
co
nfi
gu
rati
on
0 =
Au
to1 =
To
ol
Devic
e r
eco
gn
itio
n s
ad
dre
ss "
92" i
n c
od
N/A
Bri
ef
scan
1 2 3 4 5 6 7 8 9
58
62
73
9G
B
36
Service scans
Scanning operating conditions
1. Press c.
2. Select the required operating
condition scan with a or b.
3. Press c. Scanning is completed.
The following operating conditions can be scanned subject to the actual
equipment level:
User no.
Holiday program with departure
and return date
Actual outside temperature
Sensor17B (actual value)
Actual DHW temperature
Actual DHW temperature 1
Actual DHW temperature 2
Flow temperature
Standard room temperature (set
value)
Actual room temperature
Actual solar DHW temperature
Collector temperature (actual value)
Solar energy (kWh)
Time
Date
Output20 ON/OFF
Output52 OPEN/CLOSED
Cylinder pump ON/OFF
DHW circulation pump ON/OFF
Central heating circuit pump ON/OFF
Mixer open/closed
Solar circuit pump ON/OFF
Hours run solar circuit pump
Various languages
If a LON communication module is
installed.
If a holiday program has been
entered.
If a sensor is connected.
If a cylinder temperature sensor is
connected.
If two cylinder temperature
sensors are connected.
If a remote control unit is
connected.
In conj. with solar heating system.
In conj. with solar heating system.
In conj. with solar heating system.
Position detail in %
Position detail in %
In conj. with solar heating system.
In conj. with solar heating system.
Each language can be selected as
the permanent display language
with d.
58
62
73
9G
B
37
Troubleshooting
Faults which are displayed at the programming unit
The red fault indicatorflashes for all faults.
If a fault message is issued, the display flashes
"Fault".
A central fault messaging facility connected to plug gÖ will be started.
Troubleshooting
Note
A new fault message will be shown
in the display if an acknowledged
fault is not removed by 07:00 h the
following day.
1. Press c.
2. Call up further fault codes
with a or b.
3. The fault can be acknowledged
with d. The fault message in the
display will be hidden, but the red
fault indicator continues to flash.
Fault display
Fault code
(for explanations, see page 39)
Fault number (1 to 10)
Fault symbol
58
62
73
9G
B
Fault
1Mo 57
w ºC
Outdoor sensor
1DBG− 101
38
Troubleshooting
Faults which are displayed at the programming unit (cont.)
Plain text fault display
Outside temperature sensor
Flow sensor
Cylinder sensor 1 or 2
Will only be displayed if a second
cylinder temperature sensor is
connected.
Sensor 17B
Room temperature sensor
Collector sensor
Solar DHW sensor
User number
Fault user
Display only if the control unit is
programmed as fault manager.
Calling up acknowledged fault
messages
1. Press d for approx. 2 s.
The fault will then be displayed.
2. Select an acknowledged fault
with a or b.
58
62
73
9G
B
39
Troubleshooting
Faults which are displayed at the programming unit (cont.)
Fault
codeSystem
characteristics
Cause Remedy
10 Activates after 0 ºC
outside
temperature
Short circuit
Outside
temperature sensor
Check outside
temperature sensor
(see page 59)
18
p
Lead broken
Outside
temperature sensor
( p g )
20 Mixer is "Closed" Short circuit
Flow temperature
sensor
Mixer circuitM1
Check flow
temperature sensor
(see page 58)
28 Lead broken
Flow temperature
sensor
Mixer circuitM1
40 Short circuit
Flow temperature
sensor
Mixer circuitM2
44Short circuit
Flow temperature
sensor
Mixer circuitM3
48 Lead broken
Flow temperature
sensor
Mixer circuitM2
4cLead broken
Flow temperature
sensor
Mixer circuitM3
58
62
73
9G
B
40
Troubleshooting
Faults which are displayed at the programming unit (cont.)
Fault
codeSystem
characteristics
Cause Remedy
50 Cylinder primary
pump ON:
Set DHW
temperature=set
boiler water
temperature, priority
is cancelled
or
With cylinder
storage system:
Cylinder heating is
started and stopped
by cylinder
temperature sensor
2
Short circuit
Cylinder
temperature
sensor1
Check cylinder
temperature sensor
(see page 57)
51 With cylinder
storage system:
Cylinder heating is
started and stopped
by cylinder
temperature sensor
1
Short circuit
Cylinder
temperature
sensor2
58 Cylinder primary
pump "ON":
Set DHW
temperature=set
boiler water
temperature, priority
is cancelled
or
With cylinder
storage system:
Cylinder heating is
started and stopped
by cylinder
temperature sensor
2
Lead broken
Cylinder
temperature
sensor1
58
62
73
9G
B
41
Troubleshooting
Faults which are displayed at the programming unit (cont.)
Fault
codeSystem
characteristics
Cause Remedy
59 With cylinder storage
system:
Cylinder heating is
started and stopped
by cylinder temp.
sensor 1
Lead broken
Cylinder
temperature sensor
2
Check cylinder
temperature sensor
(see page57)
70 Weather−compensated
control unit without
return temp. sensor
Short circuit
Temperature
sensoraJB
Check temperature
sensor
(see page 58).
78
p
or
Primary circuit mixer
closed
Lead broken
Temperature
sensoraJB
( p g )
Without
temperature sensor:
Set code "4B:0"
92 Control mode
Only the solar control
unit fault codes will
be displayed
Short circuit
Collector
temperature sensor,
connects to
Vitosolic S1
Check solar control
unit sensor
93 Short circuit
Cylinder
temperature sensor,
connects to
Vitosolic S2
94 Short circuit
Temperature
sensor, connects to
Vitosolic S3
9a Lead broken
Collector
temperature sensor,
connects to
Vitosolic S1
9b Lead broken
Cylinder
temperature sensor,
connects to
Vitosolic S2
58
62
73
9G
B
42
Troubleshooting
Faults which are displayed at the programming unit (cont.)
Fault
codeSystem
characteristics
Cause Remedy
9c Control mode
Only the solar
control unit fault
codes will be
Lead broken
Temperature sensor,
connects to Vitosolic
S3
Check solar control
unit sensor
9fdisplayed Fault
Solar control unit;
displayed if an error
without fault code
occurs at the solar
control unit
Check solar control
unit
AAab Controlled
operation, perhaps
DHW cylinder cold
Code "55:3" has
been set, but
plugaJB is not
plugged in
and/or
Code"4C:1" and
code "4E:1" have
not been set
Insert plugaJB and
check coding
b1 Control mode Communication
error
Programming unit
Check connections
and replace
programming unit, if
required
b4 Undefined control
characteristics
Internal electronics
fault
Replace electronics
PCB
b5 Control mode
b6 Undefined control
characteristics
Invalid hardware
recognised
Check coding
address "92"
(see page 84)
ba Mixer closed Mixer extension
PCB
communication
error
Replace the PCB
(see parts list)
58
62
73
9G
B
43
Troubleshooting
Faults which are displayed at the programming unit (cont.)
Fault
codeSystem
characteristics
Cause Remedy
bc Control mode
without remote
control
Communication error
Vitotrol remote
control,
Mixer circuitM1
Check connections,
cable and coding
address "A0" as well
as the remote control
bd Communication error
Vitotrol remote
control,
Mixer circuitM2
DIP switches
(see page67 and 69)
be Communication error
Vitotrol remote
control,
Mixer circuitM3
bf Control mode Incorrect LON
communication
module
Replace
communication
module (see parts list)
c2 Lead broken
KM BUS to solar
control unit
Check KM BUS cable
and the solar control
unit.
Without solar control
unit:
Set code "54:0"
c4 Communication with
function extension
0−10V faulty
Check connections,
cables/leads; if
required, replace the
function extension
(see page73).
Without function
extension:
Set code "9d:0"
cEf LON communication
module fault
Replace
communication
module (see parts list)
58
62
73
9G
B
44
Troubleshooting
Faults which are displayed at the programming unit (cont.)
Fault
codeSystem
characteristics
Cause Remedy
dEa Control mode
without room
influence
Short circuit
Room temperature
sensor,
Mixer circuitM1
Check room
temperature sensor
(see
page 72) and DIP
dEb Short circuit
Room temperature
sensor,
Mixer circuitM2
p g )
switch setting on
the Vitotrol (see
page67 and 69).
dEc Short circuit
Room temperature
sensor,
Mixer circuitM3
dEd Lead broken
Room temperature
sensor,
Mixer circuitM1
dEe Lead broken
Room temperature
sensor,
Mixer circuitM2
dEf Lead broken
Room temperature
sensor,
Mixer circuitM3
e0 Control modeR Communication
break Viessmann
2−wire BUS
Check connection
58
62
73
9G
B
45
Troubleshooting
Faults which are displayed at the programming unit (cont.)
LON users fault messages
Preconditions:
The control unit must be encoded as fault manager (code "79:1").
Fault
codeSystem
characteristics
Cause Remedy
01to
98
Control mode A user fault has
occurred e.g. 12
(Vitotronic050)
Download fault code
to user
Installation
and service
instructions
of the
relevant
control unit
No connection to
the user
Check coding (see
page25)
Check connecting
LON cable
Update user list
(see page24)
Carry out a user
check (see
page26)
58
62
73
9G
B
Participant
1U 12F1
46
Troubleshooting
Faults which are displayed at the programming unit (cont.)
Fault
codeSystem
characteristics
Cause Remedy
99 Control mode Fault message
active at Vitocom
300
Check external
connections at
Vitocom 300
No connection to
Vitocom 300
Check coding (see
page25)
Check connecting
LON cable
Update user list
(see page24)
Carry out a user
check (see
page26)
Downloading fault codes from the fault memory (fault history)
The most recent 10 faults are saved
and may be called up.
Faults are sorted by date. The most
recent fault is thus fault number 1.
1. Press G and d simultaneously
for approx. 2 s.
2. Call up the individual fault codes
with a/b.
Note
All saved fault codes can be
deleted with e.
3. Press d.
58
62
73
9G
BFault history
1F1 18
47
Function description
Heating circuit control unit
Brief description
The set flow temperature of every
heating circuit is selected by the
following parameters:
Outside temperature
Set room temperature
Operating mode
Heating curve
The flow temperature of the mixer
circuits is regulated by the stepped
opening or closing of the mixers.
The mixer motor control changes the
actuating and pause times subject to
the control difference
(control deviation).
Coding addresses which influence
the heating circuit control
9F, A0 to Fb.
For a description, see the coding
overview.
Functions
Time program
The control unit time switch changes
in accordance with the programmed
times in the central heating program
between the central heating with
standard temperature and central
heating with reduced temperature
operating modes.
Every operating mode has its own
set value level.
Outside temperature
A heating curve must be set up for
matching the control unit to the
building and the heating system.
The heating curve characteristics
determine the set flow temperature
subject to outside temperature. An
average outside temperature is used
for control purposes. This comprises
the actual and the adjusted outside
temperature.
Domestic hot water temperature
With priority control:
The set flow temperature will be
set to 0 ºC whilst the cylinder is
being heated up.
The mixer closes, and the heating
circuit pump is switched OFF.
Without priority control:
The heating circuit control unit
continues to operate with the same
set value.
58
62
73
9G
B
48
Function description
Heating circuit control (cont.)
Room temperature
in conjunction with remote control
and room temperature hook−up
(observe coding address "b0")
Compared to the outside
temperature, the room temperature
has a greater influence on the set
flow temperature. This influence
may be changed via coding address
"b2".
For control differences (actual value
deviation) above 2 K room
temperature, the influence can be
increased again (via coding address
"b6", quick heat−up/quick setback).
Quick heat−up:
The set room temperature must be
raised by a minimum of 2 K by
pressing party key M changing from central heating with
reduced temperature to central
heating with standard temperature
start−up optimisation
Quick heat−up will stop when the set
room temperature has been reached.
Quick setback:
The set room temperature must be
reduced by a minimum of 2 K by
pressing economy key N changing from central heating with
standard temperature to central
heating with reduced temperature
Shutdown time optimisation
Quick setback will stop when the set
room temperature has been reached.
Heating circuit pump logic (economy
mode)
The heating circuit pump is switched
OFF (set flow temperature set to
0ºC), when the outside temperature
exceeds the value selected via
coding address "A5".
Extended economy mode
The heating circuit pump is switched
OFF and the set flow temperature is
set to 0ºC, if:
the outside temperature exceeds
the value selected via coding
address "A6"
the set room temperature is
reduced via coding address "A9"
the mixer has been closed for 12
min (mixer economy function,
coding address "A7")
the actual room temperature
exceeds the value selected via
coding address "b5"
Screed function
Note
Observe DIN 4725 part 4.
Four different temperature profiles
can be selected for drying the
screed. These profiles are activated
via coding address "F1".
When the screed drying function is
activated, the heating circuit pump is
switched ON and the flow
temperature will be held at the
selected profile. After completion (30
days), the mixer circuit will again be
regulated automatically via the set
parameters.
58
62
73
9G
B
49
Function description
Heating circuit control (cont.)
Underfloor heating
(only mixer circuitM1)
An additional return temperature
sensor can be connected to achieve
an optimum underfloor heating
system. The control unit calculates a
set return temperature. Changes are
implemented if the actual return
temperature deviates from the set
return temperature.
The temperature differential may be
changed via coding address "C7".
When changing from central heating
with reduced temperature to central
heating with standard temperature,
the set flow temperature can be
raised by 20 % for one hour via code
"C9:1".
System dynamics mixer circuit
You can influence the control
characteristics of the mixer via
coding address "C4".
Frost protection
When the outside temperature falls
below +1ºC, a flow temperature of at
least 10ºC will be safeguarded.
For changes see coding address
"A3", variable frost limit.
Flow temperature control
Differential temperature:
The differential temperature can be
adjusted via
coding address "9F",
Delivered condition 8 K.
The differential temperature is the
minimum value by which the boiler
water temperature should be higher
than the current highest required
flow temperature of the mixer
circuits.
A Max. boiler water temperature
B Slope=1.8 mixer circuitM1
C Slope=0.6 mixer circuitM2
Level=10
D Boiler water temperature
(at a differential temperature of
8K)
E Lower boiler water temperature
58
62
73
9G
B
Flo
w t
em
pera
ture
in
°C
8K
50
110
87
+20 −20Outside temperature in C
B
A
C
E
D
50
Function description
Heating circuit control (cont.)
Upper control limit
Electronic maximum limit
Setting range: 10 to 127 ºC
Changes via coding address "C6"
Note
The maximum limit is no
replacement for the underfloor
heating system temperature limiter
(see page65).
Temperature limiter for underfloor
heating:
The temperature limiter switches the
heating circuit pump OFF if the set
value has been exceeded. In such
cases, the flow temperature reduces
only slowly, i.e. it may be several
hours before the system restarts
again automatically.
Lower control range limit
Electronic minimum limit (only
active in operation with standard
room temperature)
Setting range: 1 to 127 ºC
Changes via coding address "C5"
Control sequence
Mixer circuit
Inside the "neutral zone"
(±1 K) the mixer motor will not be
controlled.
Flow temperature drops
(set value −1 K)
The mixer motor receives the signal
"Mixer open".
The signal duration lengthens with
an increasing control differential.
The duration of pauses reduces with
an increasing control differential.
Flow temperature rises
(set value +1 K)
The mixer motor receives the signal
"Mixer closed".
The signal duration lengthens with
an increasing control differential.
The duration of pauses reduces with
an increasing control differential.
58
62
73
9G
B
51
Function description
Cylinder temperature control
Brief description
The cylinder thermostat operates
with a constant temperature. It is the
result of starting and stopping the
cylinder primary pump.
The switching differential is ±2.5K.
During cylinder heating, a constant
upper boiler water temperature will
be set (20 K higher than the set
cylinder temperature, adjustable via
coding address "60") and central
heating is switched OFF (optional
cylinder priority).
Coding addresses which influence
the cylinder thermostat
54, 55, 56, 58 to 62, 64, 66, 67,
70 to 75, 7F, A2.
For a description, see the coding
overview.
Functions
Time program
An automatic program or an
individual time program may be
selected for DHW heating and the
control of the DHW circulation pump.
Compared with the heating circuit
heat−up phase, DHW heating starts
30minutes earlier in automatic
mode.
The individual time program enables
up to four time phases per day to be
set via the time switch to control the
DHW heating and four time phases
per day for the DHW circulation
pump.
Any cylinder heating sequence will
be completed, independent of the
time program.
In conjunctionwithcodingaddress"7F"
"7F:1" Detached house:
Automatic mode
The heating times for heating
circuit 1 are applied to systems
with two or three heating circuits.
Individual time program
The switching times for DHW
heating and the DHW circulation
pump have the same effect on all
heating circuits.
"7F:0" Apartment block:
Automatic mode
The heating times for the
respective heating circuit will be
applied to systems with two or
three heating circuits.
Individual time program
The switching times for DHW
heating can be adjusted separately
for each heating circuit.
58
62
73
9G
B
52
Function description
Cylinder temperature control (cont.)
DHW priority
With DHW priority:
(code "A2:2"):
The set flow temperature will be
set to 0 ºC during cylinder heating.
The mixer closes, and the heating
circuit pump is switched OFF.
Without DHW priority:
The heating circuit control unit
continues to operate with the same
set value.
Frost protection
The DHW cylinder will be heated to
20 ºC if the DHW temperature falls
below 5ºC.
Auxiliary function for DHW heating
This function is activated by
providing a second set DHW
temperature via coding address
"58", and activating the fourth DHW
phase for DHW heating.
Set DHW temperature
The set DHW temperature can be
adjusted between 10 and 60 ºC. The
set range can be extended to 95 ºC
via coding address "56".
The set default value of the
programming unit and/or the Vitotrol
300 remote control (if installed) can
be allocated via coding address
"66".
DHW circulation pump
The DHW circulation pump delivers
hot water to the draw−off points at
adjustable times.
Up to four time phases can be set at
the time switch.
Auxiliary circuits
DHW heating can be blocked or
enabled by changing over the
heating program (see coding
address "b5").
System with cylinder storage system
These functions also apply
in conjunction with the cylinder
storage system.
Set the following codes:
"4C:1", "4E:1", "55:3" (see coding
overview).
Systems with Vitosolic
A third set DHW temperature can be
defaulted via coding address "67".
Re−heating will be suppressed above
the selected temperature. The DHW
cylinder will only be heated by the
solar heating system.
58
62
73
9G
B
53
Function description
Cylinder temperature control (cont.)
DHW demand to central cylinder
(Only in conjunction with LON
communication module)
The DHW demand can optionally be
applied to a central DHW cylinder
(coding address "57"). The cylinder
temperature control of the Vitotronic
050 is inactive, i.e. no DHW
temperature can be set and no DHW
circulation pump can be controlled.
However, the time phases for DHW
heating remain active.
Control sequence
Pump run−on
The cylinder primary pump runs on
after cylinder heating until the
following criteria have been met:
The weather−compensated set
boiler water temperature has
been reached
or
The set DHW temperature has
been exceeded by 5 K
or
The maximum run−on time
(adjustable via coding
address"62") has been reached
Without the cylinder primary pump
running on (code "62:0")
Code "55:0"
Cylinder heating
DHW cylinder goes cold
(set value −2.5K; adjustable via
coding address "59")
The set boiler water temperature is
adjusted 20 K higher than the set
DHW (adjustable via coding address
"60").
The DHW cylinder is hot
(set value +2.5 K)
The set boiler water temperature is
returned to the weather−compensated
value.
58
62
73
9G
B
54
Function description
Cylinder temperature control (cont.)
Code "55:2":
Cylinder temperature control with 2
cylinder temperature sensors
Cylinder temperature sensor 1
enables the cylinder primary pump
and is evaluated for termination
conditions during the pump run−on
time (see page53). Cylinder
temperature sensor 2 (inside the cold
water inlet) is designed to start
cylinder heating prematurely when
large volumes of DHW are drawn off
as well as to stop cylinder heating
prematurely, if no DHW is drawn.
Select starting and stopping points
via coding addresses "68" and "69".
Code "55:3"
Cylinder thermostat cylinder
storage system
DHW cylinder goes cold
(Set value 2.5K; adjustable via
coding address "59")
The set boiler water temperature is
adjusted 20K higher than the set
DHW (adjustable via coding
address"60")
The cylinder primary pump is
switched ON
The three−way mixing valve opens
and then regulates to the defaulted
set value
The cylinder primary pump cycles
(short term ON and OFF) until the
set flow temperature has been
reached (set DHW temperature
+ 5 K), then it runs constantly.
Then it runs constantly.
If, during cylinder heating, the
actual value stays below the
required set temperature, then the
cylinder primary pump will
temporarily cycle again.
The DHW cylinder is hot
(Cylinder temperature sensor 1:
Actual value Set value
and
Cylinder temperature sensor 2:
Actual value > Set value −1.5K)
The set boiler water temperature is
reset to the weather−compensated
value,
The cylinder primary pump is
switched OFF:
Immediately, if the three−way
mixing valve is open
or
after expiry of a run−on time,
which is adjustable via code
"62".5
86
27
39
GB
55
Components
Components from the parts list
For parts list, see page 102.
Main PCB 230V~
The main PCB comprises:
Relays and outputs for controlling
pumps and actuators
Slot for power supply unit
Main PCB low voltage
The main PCB comprises:
Connection plug for sensors,
communication connections and
external hook−ups
Slot for electronics PCB, power
supply unit, LON communication
module, Viessmann 2−wire BUS
communication module, 2−wire
BUS, programming unit and
Optolink PCB
Electronics PCB
Microprocessor with software
When replacing the PCB:
1. Record the codes and adjustments
made at the control unit.
2. Replace the PCB.
3. Set code "8A: 176" and coding
address "92" to
"92 : 170" for type HK1W,
"92 : 171" for type HK3W.
Power supply unit PCB
The power supply unit PCB
comprises the low voltage supply for
all electronic equipment.
Mixer extension PCB
Only for type HK3W
The PCB comprises the relays for
controlling the mixer motor and the
heating circuit pumps.
Supplementary mixer
extension PCB
Only for type HK3W
This is plugged into the mixer
extension PCB.
All data is processed and the outputs
(relay) are selected.
Optolink PCB
The PCB comprises:
Burner standby display
Fault display
Optolink laptop interface
Front cover
Only for type HK1W
58
62
73
9G
B
56
Components
Components from the parts list (cont.)
Front panel with heating
circuit selector keys
Only for type HK3W
Display and selection of the heating
circuit.
Programming unit
Settings:
Heating program
Set values
Switching times
Heating curve
(slope and level)
Date
Time
Economy and party mode
Displaying:
Temperatures
Operating conditions
Faults
Programming unit ON/OFF
switch
Including fuse and mains isolator.
Fuse
F1: 6.3 A (slow), 250 V,
max. power loss 2.5 W,
to protect the total device, the
pumps, the actuators and all
electronics.
Viessmann 2−wire BUS
communication module
Electronics PCB for data exchange
with Vitotronic 300, type KW3
The communication interruption will
be displayed.
The rotary selector is set at the
factory to 4.
Communication module LON
PCB for data exchange.
A Control unit or Vitocom 300
B Connecting cable for data
exchange between control units,
part no.7143495
C Terminators,
part no.7143497
The communication interruption will
be displayed.
58
62
73
9G
B
B BC C
A AA
LON LON LON LON LON LON
57
Components
Components from the parts list (cont.)
Cylinder temperature sensor
Connection
See page 15.
Check sensor
1. Pull plug %.
2. Check the sensor resistance at
terminals 1 and 2 or 2 and 3 (if a
second cylinder temperature
sensor has been connected).
3. Compare the measurement with
the actual temperature displayed
(for scanning, see page 34).
Check the installation and replace
sensor, if necessary, in case of
severe deviation.
Specification
Protection: IP 32
Permiss. ambient
temperature
in operation 0 to +90ºC
during storage
and transport: 20 to +70ºC
58
62
73
9G
B
Resis
tan
ce i
n
Cylinder temperature in °C
540
560
580
600
620
640
660
680
0 20 40 60 80
58
Components
Components from the parts list (cont.)
Contact temperature sensor and immersion temperature
sensor
For recording the flow and return temperature.
Connection
See page 15.
Check sensor
1. Pull plug ? or aJ.
2. Check the sensor resistance at
terminals "1" and "2" of the plug.
3. Compare the test result with the
actual temperature (for scanning,
see page 34).
Check the installation and replace
sensor, if necessary, in case of
severe deviation.
Specification
Protection: IP 32
Permiss. ambient
temperature
in operation: 0 to +100 ºC
in storage and
transport: 20 to +70ºC
58
62
73
9G
B
30 40 50 60 70 80 90 100540
560
580
600
620
640
660
680
700
720
740
20
Resis
tan
ce in
Flow temperature orreturn temperature in ºC
59
Components
Components from the parts list (cont.)
Outside temperature sensor
Connection
See page 15.
Checking the outside temperature
sensor
1. Pull plug !.
2. Check the sensor resistance at
terminals "1" and "2" of the plug.
3. Where actual values strongly
deviate from the curve values,
repeat the sensor test and
compare with the actual
temperature (for scanning, see
page 34).
4. Depending on the result, replace
cable or outside temperature
sensor.
5. Scan actual temperature
(see page 34).
Specification
Protection: IP43
Permissible ambient
temperature for
operation, storage
and transport: 40 to +70ºC
58
62
73
9G
B
400
420
440
460
480
500
520
540
560
580
600
−40 −30 −20 −10 0 10 20 30
Outside temperature in °C
Resis
tan
ce i
nΩ
60
Components
Radio clock receiver, part no. 7450 563
The radio clock receiver provides a fully automatic time setting for the control
unit and remote control unit (if connected).
A Outside temperature sensor
B Radio clock receiver
C Green LED
D Red LED
E Aerial
Connection
2−core cable with a maximum length
of 35 m and a cross section of 1.5
mm2 (copper).
Check reception
During reception, the green LED on
the radio clock receiver flashes.
When the red LED flashes, rotate the
aerial until reception is confirmed by
the flashing green LED.
Specification
Protection: IP43
Permissible ambient
temperature for
operation, storage
and transport: 40 to +70ºC
58
62
73
9G
B
1
EA
B
C D
61
Components
Mixer circuit extension kit, Part no. 7450650
Comprising:
Flow temperature sensor as contact temperature sensor to record the flow
temperature, see page 58
Mixer motor with connecting cable, 4 m long, and plug for connecting the
heating circuit pump.
Mixer motor, part no. 7450 657
A Plug in the mixer motor
Mixer open
Mixer closed
Changing the rotational direction
(see page64).
Remove the cover and reinsert the
3−pole plug A turned by 180º.
Checking the direction of rotation
The relay test of the control unit
moves the mixer to "Open" and
"Closed".
SpecificationRated voltage: 230V~
Rated frequency: 50Hz
Power consumption: 4WProtection: IP 42
Torque: 3Nm
Run−time for 90º: 120s
58
62
73
9G
B
A
62
Components
Mixer motor, part no. 9522 487
for central heating mixers DN40 and 50
A Mixer motor
Mixer open
Mixer closed
B Coupling switch
Changing the rotational direction
(see page64)
Interchange both cores at terminals
"Y1" and "Y2".
Checking the direction of rotation
The relay test of the control unit
moves the mixer to "Open" and
"Closed".
Manual mixer adjustment
Clutch switch B set to "MAN".
Specification
Rated voltage: 230V~
Rated frequency: 50Hz
Power consumption: 3W
Protection: IP 42
Torque: 5Nm
Run−time for 90º: 135s
58
62
73
9G
B
AUTO
MAN
BM
1~
A
NY1Y2
63
Components
Mixer motor, part no. 9522 488
for central heating mixer DN 65 and 100
A Mixer motor
Mixer open
Mixer closed
B Coupling switch
Changing the rotational direction
(see page64).
Interchange both cores at terminals
"Y1" and "Y2".
Checking the direction of rotation
The relay test of the control unit
moves the mixer to "Open" and
"Closed".
Manual mixer adjustment
Clutch switch B set to "MAN".
Specification
Rated voltage: 230V~
Rated frequency: 50Hz
Power consumption: 4W
Protection: IP 42
Torque: 12Nm
Run−time for 90º: 125s
58
62
73
9G
B
AUTO
MAN
B
M
1~
100%0%
A
NY1Y21112
KR
HV
KV HR
HR
KV
HVKR
HV
KV
HR
KR
HV
KV
HR
KV
HV
HR
HR
HVKR
KV
HV
HR
KR
KV
HV
KVHR
KR
64
Components
Installation examples
Mixer insert conversion (if required); see mixer installation instructions.
Note
For system with ModularDivicon, reverse the rotational direction.
Delivered condition
of the mixer motor rotational
direction
Change the mixer motor rotational
direction for these installation
examples
HR Heating return
HV Heating flow
KR Boiler return
KV Boiler flow
58
62
73
9G
B
65
Components
Temperature limiter for maximum temperature limiting
Immersion thermostat, part no. 7151 728
Contact thermostat, part no. 7151 729
A Heating circuit pump
B Control thermostat (temp. limiter)
C Plug sÖ of the thermostat
(temperature limiter) to the
control unit
Electro−mechanical temperature
limiter according to the liquid
expansion principle.
Switches the heating circuit pump
OFF, when the set value has been
exceeded.
In such cases, the flow temperature
reduces only slowly, i.e it may be
several hours before the system
restarts again automatically.
Specification
Setting range: 0 to 80ºC
Terminals: Screw terminals
for 1.5mm2
Switching differential
Immersion
thermostat: max. 11K
Contact
thermostat: max. 14 K
58
62
73
9G
B
C
B
A M1~
66
Components
Remote control
Vitotrol 200, part no. 7450 017
(incl. integral room temperature sensor for room temperature hook−up)
Settings:
Day temperature
Heating program
Economy and party mode
Function changes can be made via coding addresses "A0", "b0" to "b9",
"C0" to "C2", "C8", "E1", "E2" and "F2" (see overview).
A Wall mounting base for
Vitotrol 200
B To the control unit
C Separate room temperature
sensor
Connection
2−core lead (total length max. 50 m).
Room temperature sensor
connection
2−core cable with a maximum length
of 35 m and a cross−section of
1.5 mm2 (copper).
58
62
73
9G
B
B
145
13b
9
C
A
67
Components
Remote control (cont.)
D DIP switches on the PCB
(back of the remote control)
Remote controlaffects
DIP switchsetting
Mixer circuit M1(heating circuitselection key !)
Delivered condition
ON
1 2 3 4
Mixer circuit M2(heating circuitselection key ?)
ON
1 2 3 4
Mixer circuit M3(heating circuitselection key §)
ON
1 2 3 4
Specification
Power supply via KM BUS.
Safety class: III
Protection: IP30
Permiss. ambient
temperature
in operation: 0 to +40ºC
in storage and
in transport: 20 to +65ºC
Setting range
Standard set
room temp.: 10 to 30ºC;
adjustable to
3 to 23ºC
or
17 to 37ºC via
coding
address"E1"
Reduced set room temperature
adjustment at the control unit.
When connecting a separate room
temperature sensor, set DIP switch
"S6.3" to ON.
58
62
73
9G
B
ONS6
1 2 3 4
D
ON
1 2 3 4
68
Components
Remote control (cont.)
Vitotrol 300, part no. 7179 060
(incl. integral room temperature sensor for room temperature hook−up)
Settings:
Day and night temperature
Domestic hot water temperature
Heating program
Holiday program
Switching times
Economy and party mode
Function changes can be made via coding addresses "A0", "b0" to "b9",
"C0" to "C2", "C8", "E1" and "E2" and "F8" (see overview).
A Wall mounting base for
Vitotrol300
B To the control unit
C Separate room temperature
sensor
Connection
2−core lead (total length max. 50 m).
Room temperature sensor
connection
2−core cable with a maximum length
of 35 m and a cross−section of
1.5 mm2 (copper).
58
62
73
9G
B
13b
9
A
B
145
C
12
34
ON
69
Components
Remote control (cont.)
A PCB DIP switches (back of the top
casing).
Remote controlaffects
DIP switchsetting
Mixer circuit M1(heating circuitselection key !)
Delivered condition
12
34
ON
Mixer circuit M2(heating circuitselection key ?) 1
23
4
ON
Mixer circuit M3(heating circuitselection key §) 1
23
4
ON
When connecting a separate room
temperature sensor, set DIP switch
"S3.3" to ON.
Specification
Power supply via KM BUS.
Safety class: III
Protection: IP 30
Permiss. ambient temperature
in operation: 0 to +40 ºC
during storage
and transport: 20 to + 65 ºC
Setting range for
set standard
room temp.: 10 to 30 ºC;
adjustable from
3 to 23 ºC
or
17 to 37 ºC
via coding
address "E1"
Reduced room
temp.: 3 to 37 ºC
58
62
73
9G
B
A
12
34
ONS3
3 2 1RTSint. ext.
12
34
S3
70
Components
Remote control (cont.)
Connecting several remote control units
When connecting several remote controls to the control unit, install a socket
on site.
Version 1
A To control unit
B Socket (on site)
C Vitotrol 1
D Vitotrol 2
E Vitotrol 3
On−site connection via socket:
Connect in accordance with the
diagram above.
The total length of all KM BUS
cables should be limited to 50 m.
58
62
73
9G
B
145A
B
max.15 m
D
max.15 m
E
max.15 m
C
71
Components
Remote control (cont.)
Version 2
A To control unit
B Socket (on site)
C Vitotrol 1
D Vitotrol 2
E Vitotrol 3
F Additional BUS users
If several remote control units and
additional KM BUS users are
connected, make the connections
via a socket (on−site) as shown in
the diagram above.
The total length of all KM BUS
cables should be limited to 50 m.
58
62
73
9G
B
145A
max.15 m
B
C D
F
E
max. 15 mmax. 15 m
72
Components
Room temperature sensor, part no. 7408 012
The room temperature sensor measures the actual room temperature, if the
remote control unit cannot be installed in a suitable location.
Connection
See pages66 and 68.
Check the room temperature sensor
1. Disconnect the wires from the
sensor.
2. Check the sensor resistance at
terminals 9 and 13b.
3. Compare the measurement with
the actual temperature displayed
(for scanning, see page34).
Check the installation and replace
sensor, if necessary, in case of
severe deviation.
Specification
Protection: IP 30
Permiss. ambient
temperature
in operation 0 to +40ºC
during storage
and transport: 20 to +65ºC5
86
27
39
GB
Resis
tan
ce i
n
0Room temperature in °C
5005 10 15 20 25 30 35 40
510
520
530
540
550
560
570
580
600
590
73
Components
Functions extension 0 to 10V, part no 7174 718
To control a feed pump, e.g in a sub−station
or
for signalling reduced mode.
fÖ Power supply
aVF 0−10 V input
aVG KM BUS
aBJ Zero volt contact
A Mains isolator (if required)
B DIP switch (see table)
DIP switch Function
1 to 3 OFF Controlling the feed pump
1 ON Mixer circuit reduced mode M1
2 ON Mixer circuit reduced mode M2
3 ON Mixer circuit reduced mode M3
Note
Set only one switch to ON.
58
62
73
9G
B
OFF
A
Electronics24V
5V
L1
40
230V~
157 144 145
N S Ö P 1 2 3 1 2 3
1 2 3 4
ONF1T250mA
B
+
74
Coding
Resetting codes to the delivered condition
1. Press L and G simultaneously
for approx. 2 s.
2. Press e.
Confirm "Standard setting? Yes"
with d.
With a or b, "Standard setting?
Yes" or "Standard setting? No"
can be selected.
Code 1
Calling up code 1
1. Press K and L simultaneously
for approx. 2 s.
2. Select the required coding address
with a or b,
the address flashes;
confirm with d,
the value flashes.
3. Change the value with a or b;
confirm with d.
The display briefly shows
"Accepted", then the address
flashes again.
Call up further addresses
with a or b.
4. Press K and L simultaneously
for approx. 1 s.
58
62
73
9G
B
75
Coding
Code 1 (cont.)
Summary
Coding in the delivered condition Possible change
System design
00 : 1 Mixer circuitM1
without DHW heating
00 : 2 Mixer circuitM1
with DHW heatingg
Only for typeHK3W
00 : 3 Mixer circuitM2
without DHW heating
00 : 4 Mixer circuitM2
with DHW heating
00 : 5 Mixer circuitM1 and M2
without DHW heating
00 : 6 Mixer circuitM1 and M2
with DHW heating
00 : 7 Mixer circuit M2 and M3
without DHW heating
00 : 8 Mixer circuit M2 and M3
with DHW heating
00 : 9 Mixer circuitM1, M2 and M3
without DHW heating
00 : 10 Mixer circuitM1, M2 and M3
with DHW heating
User no.
77 : 10 LON user number 77 : 1
to
77 : 99
LON user number,
adjustable from 1 to 99
Note
Allocate each number only
once
58
62
73
9G
B
76
Coding
Code 1 (cont.)
Coding in the delivered condition Possible change
DHW priority M1/M2/M3
A2 : 2 Cylinder priority control for
heating circuit pump and
A2 : 0 Without DHW priority for
heating circuit pumpg p p
mixer A2 : 1 The mixer is closed and the
heating circuit pump runs
whilst the cylinder is being
loaded
A2 : 3
to
A2 : 15
No function
Summer econ. M1/M2/M3
A5 : 5 With heating circuit pump
logic function
A5 : 0 Without heating circuit
pump logic function
Flow min. temp. M1/M2/M3
C5: 20 Electronic minimum flow
temperature limit 20 ºC
C5: 1
to
C5 : 127
Minimum limit adjustable
from 1 to 127ºC (only for
operation with standard
room temperature)
Flow max. temp. M1/M2/M3
C6: 75 Electronic maximum flow
temperature limit set to
75 ºC
C6: 10
to
C6 : 127
Maximum limit
adjustable from
10 to 127 ºC5
86
27
39
GB
77
Coding
Code 2
The summary from page 78 lists all possible coding addresses.
The coding addresses are grouped as follows.
Initially the possible coding
addresses "A0" to "FF" for the mixer
circuit M1 are scanned, then those
for mixer circuits M2 and M3, again
starting with coding address "A0".
Calling up code 2
1. Press L and G simultaneously
for approx. 2 s;
confirm with d.
2. Select the required coding address
with a or b,
the address flashes;
confirm with d,
the value flashes.
3. Change the value with a or b;
confirm with d.
The display briefly shows
"Accepted", then the address
flashes again.
Call up further addresses
with a or b.
4. Press L and G simultaneously
for approx. 1 s.
58
62
73
9G
B
System designCod. 00
GeneralCod. 4b to 54
DHWCod. 55 to 75
GeneralCod. 76 to 9F
Heating circuit M1Cod. A0 to FF
Heating circuit M2Cod. A0 to FF
Heating circuit M3Cod. A0 to FF
78
Coding
Code 2 (cont.)
Overall summary
Coding in the delivered condition Possible change
System design (see page 75)
General
4b:0 SensoraJB not installed 4b:1 SensoraJB installed (e.g.
return temperature sensor);
automatic recognition
4C:0 Connection on plugsÖM1:
Heating circuit pump 4C:1 Primary pump cylinder
storage system
4C:2
and
4C:3
No function
4E:2 Connection at pluggSM1:
Mixer motor 4E:1 Three−way mixing valve
cylinder storage system
54:0 Without solar control unit 54:1 With Vitosolic100;
automatic recognition
54:2 With Vitosolic200;
automatic recognition
DHW
55:0 Cylinder heating,
hysteresis±2.5K
55:2 Cylinder temperature
control
with 2 cylinder temperature
sensors
55:3 Cylinder temperature
control
cylinder storage system
58
62
73
9G
B
79
Coding
Code 2 (cont.)
Coding in the delivered condition Possible change
DHW (cont.)
56:0 DHW temperature setting
range
10 to 60 ºC
56:1 DHW temperature setting
range
10 to 95 ºC
Notes
Observe the max.
permissible DHW
temperature
Change control
thermostat "R" on the
boiler control unit (if
required)
57:0 With LON communication
module;
No DHW demand to central
cylinder
57 : 1 DHW demand to central
cylinder
58:0 Without auxiliary function
for DHW heating
58 : 1
to
58 : 95
Input of a secondset DHW
temperature; adjustable
from 1 to 95ºC (observe
coding address"56" and
section "Auxiliary function"
on page52).
59:0 Cylinder heating:
Starting point −2.5K
Stopping point +2.5K
59 : 1
to
59 : 10
Starting point adjustable
from 1 to 10 K below the set
value
5A:0 No function 5A : 1 Flow temperature demand
of DHW cylinder is
maximum system value
60:20 During DHW heating, boiler
water temperature is max.
20K higher than the set
DHW temperature
60 : 10
to
60 : 50
The difference between the
boiler water temperature
and the set DHW
temperature is adjustable
from 10 to 50K
62:10 The circulation pump will
run on for a max. of 10min
62:0 Circulation pump without
run−on
62:1
to
62:15
Max. run−on time
adjustable from 1 to 15 min
58
62
73
9G
B
80
Coding
Code 2 (cont.)
Coding in the delivered condition Possible change
DHW (cont.)
64:2 During party mode and after
external changeover during
operation with permanently
standard room temperature:
Enable constant DHW
heating and DHW circulation
64:0 No DHW heating, DHW
circulation pump OFFg
pump ON 64:1 DHW heating and DHW
circulation pump according
to time program
66:4 Input of set DHW
temperature:
at the programming unit 66:0 at the programming unitp g g
and all Vitotrol 300 remote
control units66:1 at the programming unit
and the remote control
mixer circuit M1
66:2 at the programming unit
and remote control unit,
mixer circuit M2
66:3 at the programming unit
and remote control unit,
mixer circuit M3
66:5 at the remote control,
mixer circuit M1
66:6 at the remote control,
mixer circuit M2
66:7 at the remote control,
mixer circuit M3
67:40 With Vitosolic:
Set third DHW temperature
67:0 Without third set
temperaturep
40ºC (see page52) 67:1
to
67:95
Set temperature adjustable
from 1 to 95ºC (subject to
the input of coding
address"56")
58
62
73
9G
B
81
Coding
Code 2 (cont.)
Coding in the delivered condition Possible change
DHW (cont.)
68:8 With 2 cylinder temperature
sensors
(code "55:2"):
cylinder heating switch−off
point with set value×0.8
68:2
to
68:10
Factor adjustable
from 0.2 to 1;
1step 0.1
69:7 With 2 cylinder temperature
sensors
(Code"55 : 2"):
cylinder heating starting
point with set value×0.7
69:1
to
69:9
Factor adjustable
from 0.1 to 0.9;
1step 0.1
70:0 DHW circulation pump ON
according to time program
when DHW heating is
enabled
70:1 DHW circulation pump ON
according to time program
71:0 DHW circulation pump:
ON according to time
program
71:1 OFF during DHW heating to
set value 1p g
71:2 ON during DHW heating to
set value 1
72:0 72:1 OFF during DHW heating to
set value 2
72:2 ON during DHW heating to
set value 2
73:0
73:1
to
73:6
During time program
1x/h for 5min ON
to
6 x/h for 5min ON
73:7 Permanently ON
58
62
73
9G
B
82
Coding
Code 2 (cont.)
Coding in the delivered condition Possible change
DHW (cont.)
75:0 DHW circulation pump
during economy mode or
standby mode:
ON according to time
program
75:1 OFF
General
76:0 Without communication
module
76:1 With LON communication
module;
automatic recognition
76:2 With Viessmann 2−wire BUS
communication module;
automatic recognition
77:10 LON user number 77:1
to
77:99
LON user number,
adjustable from 1 to 99
Note
Allocate each number only
once.
78:1 With LON communication
module:
LON communication
enabled
78:0 LON communication
disabled
79:0 Control unit is not fault
manager
79:1 Control unit is fault
manager
7b:0 With LON communication
module:
Do not transmit time via
BUS
7b:1 Transmit time via BUS
7F:1 Detached house 7F:0 Apartment block
(see page 51)
80:1 A fault message is 80:0 Immediate fault messageg
displayed, providing a fault
is active for at least 5s80:2
to
80:199
The minimum fault
duration, until a message is
displayed, is adjustable
from 10 to 995s;
1 step5s
58
62
73
9G
B
83
Coding
Code 2 (cont.)
Coding in the delivered condition Possible change
General
81:1 Automatic summer/winter
time changeover
81:0 Manual summer/winter
time changeoverg
Note
Coding addresses "82" to
81:2 Incl. radio clock module;
automatic recognitionCoding addresses "82" to
"87" only possible if code
"81:1" is installed.
81:3 Accept time via LON
82:3 Summer starts: March 82:1
to
82:12
January
to
December
83:5 Summer starts:
last week of the month 83:1
to
83:5
Week 1
to
Week 5
84:7 Summer starts:
last day of the week
(Sunday)
84:1
to
84:7
Monday
to
Sunday
85:10 Winter starts:
October 85:1
to
85:12
January
to
December
86:5 Winter starts:
last week of the month 86:1
to
86:5
Week 1
to
Week 5
87:7 Winter starts:
last day of the week
(Sunday)
87:1
to
87:7
Monday
to
Sunday
88:0 Temperature displayed in ºC
(Celsius)
88:1 Temperature displayed in ºF
(Fahrenheit)
8A:175 Do not adjust
58
62
73
9G
B
84
Coding
Code 2 (cont.)
Coding in the delivered condition Possible change
General (cont.)
8E:4 Displaying and
acknowledging faults:
at the programming unit 8E:0 at the programming unitp g g
and the remote control units
(if installed)8E:1 at the programming unit
and the remote control
mixer circuit M1
8E:2 at the programming unit
and remote control unit,
mixer circuit M2
8E:3 at the programming unit
and remote control unit,
mixer circuit M3
90:128 Time constant for
calculating adjusted outside
temperature 21.3h
90:0
to
90:199
Fast (low values) or slow
(high values) matching of
flow temperature subject to
set value if the outside
temperature changes;
1 step10min
91:0 Connection at terminals 1
and 2 in plug aVD (external 91: 1
Contact affects:
Mixer circuitM1p g aVD (
heating program) inactive 91 : 2 Mixer circuitM2
91 : 3 Mixer circuitM1, M2
91 : 4 Mixer circuitM3
91 : 5 Mixer circuitM1,M3
91 : 6 Mixer circuit M2, M3
91 : 7 Mixer circuitM1, M2, M3
92:170
(HK1W)
or
92:171
(HK3W)
Do not adjust
Will only be displayed, if "8A:176" has been adjusted.
58
62
73
9G
B
85
Coding
Code 2 (cont.)
Coding in the delivered condition Possible change
General (cont.)
94:0 Without plug−in adaptor for
external safety equipment
94 : 1 With plug−in adaptor, e.g.
for external fault hook−ups;
automatic recognition
96:1 With mixer extension PCB,
delivered condition for type
HK3W
96 : 0 Without mixer extension
PCB, delivered condition for
type HK1W
97:0 With communication
module:
Outside temperature from
97:1 Outside temperature is
accepted from the BUSp
the installed sensor will be
used97:2 The outside temperature of
the sensor connected to the
control unit will be used
and transmitted via the
LON BUS
98:1 LON communication
module
Viessmann system number
(in conjunction with
monitoring several systems)
98 : 2
to
98 : 5
System number
adjustable from 2 to 5
99:0 Connection at terminals 2
and 3 in plug aVD 99:1Contact affects:
Mixer circuitM1p g aVD(External "Mixer closed")
inactive99:2 Mixer circuitM2
inactive99:3 Mixer circuitM1, M2
99:4 Mixer circuitM3
99:5 Mixer circuitM1,M3
99:6 Mixer circuit M2, M3
99:7 Mixer circuitM1, M2, M3
58
62
73
9G
B
86
Coding
Code 2 (cont.)
Coding in the delivered condition Possible change
General (cont.)
9A:0 Connection at terminals 1
and 2 in plug aVD 9A:1Contact affects:
Mixer circuitM1p g aVD(External mixer open)
inactive9A:2 Mixer circuitM2
inactive9A:3 Mixer circuitM1, M2
9A:4 Mixer circuitM3
9A:5 Mixer circuitM1, M3
9A:6 Mixer circuit M2, M3
9A:7 Mixer circuitM1, M2, M3
9C:20 With LON communication
module:
LON user monitoring
When there is no response
from a user, values
9C:0 No monitoring
from a user, values
defaulted by the control unit
continue to be used for a
further 20min. Only then
will a fault message be
triggered.
9C:5
to
9C:60
Time adjustable
from 5 to 60min
9d:0 Without function extension
0−10V
9d:1 With function extension;
automatic recognition
9F:8 Differential temperature 8 K,
this is added to the highest
flow temperature
9F:0
to
9F:40
Differential temperature
adjustable from 0 to 40K
Mixer circuit
A0:0 Without remote control A0:1 With Vitotrol200
A0:2 With Vitotrol300
58
62
73
9G
B
87
Coding
Code 2 (cont.)
Coding in the delivered condition Possible change
Mixer circuit (cont.)
A2:2 Cylinder priority control for
heating circuit pump and mixer
A2:0 Without cylinder priority
controlg p p
A2:1 With cylinder priority
applied to mixer:
The mixer will be closed
whilst the cylinder is
being heated up; the
heating circuit pump
operates
A2:3
to
A3 : 15
No function
A3:2 Outside temp. below 1ºC:
Heating circuit pump ON
Outside temp. above 3ºC:
Heating circuit pump OFF
Please note
When selecting a value
below 1 ºC, there is a risk
of pipes outside the
thermal insulation of the
house freezing up.
Particularly the standby
mode should be taken
into consideration, e.g.
during holidays.
!
A3 : 9
A3 : 8
A3 : 7
A3 : 6
A3 : 5
A3 : 4
A3 : 3
A3 : 2
A3 : 1
A3 : 0
A3 : 1
A3 : 2
to
A3 : 15
Heating circuit pump
ON at OFF at
10 ºC 8 ºC
19 ºC 7 ºC
8 ºC 6 ºC
7 ºC 5 ºC
6 ºC 4 ºC
5 ºC 3 ºC
4 ºC 2 ºC
3 ºC 1 ºC
2 ºC 0 ºC
1 ºC 1 ºC
0 ºC 2 ºC
1 ºC 3 ºC
to
14 ºC 16 ºC
A4:0 With frost protection A4:1 No frost protection,
Adjustment only possible
if code "A3 :9" has been
programmed.
Please note:
Observe the
information
regarding coding
address "A3".
!
58
62
73
9G
B
88
Coding
Code 2 (cont.)
Coding in the delivered condition Possible change
Mixer circuit (cont.)
A5:5 With heating circuit pump
logic function (economy
A5:0 Without heating circuit
pump logic functiong ( y
mode):
Heating circuit pump OFF, if
the outside temperature (AT)
is 1 K higher than the set
room temperature (RTset)
AT > RTset + 1K
A5:1
A5:2
A5:3
A5:4
A5:5
A5:6
A5:7
to
A5:15
With heating circuit pump
logic function:
Heating circuit pump OFF, if
AT > RTset +5 K
AT > RTset +4 K
AT > RTset +3 K
AT > RTset +2 K
AT > RTset +1 K
AT >RTset
AT > RTset 1 K
to
AT > RTset 9 K
A6:36 Extended economy mode
not active
A6:5
to
A6:35
Extended economy circuit
active, i.e. the burner and
heating circuit pump will be
switched OFF at a variable
value, adjustable between 5
and 35 ºC plus 1ºC.
This value is based on the
adjusted outside
temperature, comprising
the actual outside
temperature and a time
constant.
The time constant takes the
cooling down of an average
building into account.
58
62
73
9G
B
89
Coding
Code 2 (cont.)
Coding in the delivered condition Possible change
Mixer circuit (cont.)
A7:0 Without mixer economy
function
A7:1 With mixer economy
function
(extended heating circuit
pump logic):
Heating circuit pump also
OFF, if the mixer was closed
longer than 12min.
Heating circuit pump ON
Mixer changes to control
function
or
After the cylinder has
been heated up
(for 20 min)
or
If there is a risk of frost
A9:7 With pump idle period:
heating circuit pump OFF in
case of set value
A9:0 Without pump idle time
case of set value
modification (by changing
the operating mode or
changing the set room
temperature)
A9:1
to
A9:15
Pump idle time adjustable
from 1 to 15
AA:2 With LON communication
module:
With output reduction
through temperature
AA:0 Without output reduction
through temperature
sensoraJA of the boiler
control unitAA:1 No function
58
62
73
9G
B
90
Coding
Code 2 (cont.)
Coding in the delivered condition Possible change
Mixer circuit (cont.)
b0:0 With remote control:
Heating mode/red. mode:
weather−compensated
b0:1 Heating mode:
weather−compensated
Red. mode:
with room temperature
hook−up
b0:2 Heating mode:
with room temperature
hook−up
Red. mode:
weather−compensated
b0:3 Heating mode/ red. mode:
with room temperature
hook−up
b2:8 With remote control unit
and for the heating circuit,
operation with room
temperature hook−up must
be encoded: b2:0 Excluding room influence
Room influence factor 8 b2:1
to
b2:31
Room influence factor
adjustable from 1 to 31
b5:0 With remote control:
Without room
temperature−dependent
heating circuit pump logic
function
b5:1
Heating circuit pump
ON at RTactual < RTset + T
OFF at RTactual > RTset + T
T for ON T for OFF
+4K +5K
b5:2 +3K +4K
b5:3 +2K +3K
b5:4 +1K +2K
b5:5 +0K +1K
b5:6 1K +0K
b5:7 2K 1K
b5:8 2K 1K
58
62
73
9G
B
91
Coding
Code 2 (cont.)
Coding in the delivered condition Possible change
Mixer circuit (cont.)
b6:0 With remote control unit
and for the heating circuit,
operation with room
temperature hook−up must
be encoded:
Without quick heat−up/quick
setback
b6:1 With quick heat−up/quick
setback
(see page 48)
b7:0 With remote control unit
and for the heating circuit,
operation with room
temperature hook−up must
be encoded:
Without start−up time
optimisation
b7:1 With start−up time
optimisation (max. offset
2h 30min)
b7:2 With start−up time
optimisation (max. offset
15h 50min)
b8:10 With remote control unit
and for the heating circuit,
heating with room
temperature hook−up must
be encoded:
Heat−up gradient
Start−up time optimisation
10 min/K
b8:11
to
b8:255
Heat−up gradient start−up
time optimisation
adjustable from
11 to 255 min/K
b9:0 With remote control unit
and for the heating circuit,
heating with room
temperature hook−up must
be encoded:
Without learning start−up
time optimisation
b9:1 With learning start−up time
optimisation
58
62
73
9G
B
92
Coding
Code 2 (cont.)
Coding in the delivered condition Possible change
Mixer circuit (cont.)
C0:0 With remote control unit
and for the heating circuit,
operation with room
temperature hook−up must
be encoded:
Without shutdown time
optimisation
C0:1 With shutdown optimisation
(max. offset 1h)p
C0:2 With shutdown optimisation
(max. offset 2h)
C1:0 With remote control unit
and for the heating circuit,
heating with room
temperature hook−up must
be encoded:
Without shutdown time
optimisation
C1:1
to
C1:12
With shutdown time
optimisation (max. offset 10
to 120 min)
1 step10min
C2:0 With remote control unit
and for the heating circuit,
heating with room
temperature hook−up must
be encoded:
Without learning shutdown
time optimisation
C2:1 With learning shutdown
time optimisation
C3:125 Mixer operating time
125s
C3:10
to
C3:255
Adjustable operating time
from 10 to 255 s
58
62
73
9G
B
93
Coding
Code 2 (cont.)
Coding in the delivered condition Possible change
Mixer circuit (cont.)
C4:1 Mixer algorithm
Standard
C4:0
C4:2
and
C4:3
Controller responds too
quickly
(cycles between "Open"
and "Closed"):
Select a lower value
Controller responds too
slowly (temperature is not
held sufficiently):
Select a higher value
C5:20 Electronic minimum flow
temperature limit 20 ºC
C5:1
to
C5:127
Minimum limit adjustable
from 1 to 127 ºC
(only during operation with
standard room temperature)
C6:75 Electronic maximum flow
temperature limit 75ºC
C6:10
to
C6:127
Maximum limit adjustable
from 10to 127 ºC
C7:0 With return temperature
sensor:
Without return temperature
sensor influence
C7:1
to
C7:31
Spread adjustable
from 1 to 31K
Spread = temperature
differential between the
flow and return
temperature at the design
point 10 ºC
C8:31 With remote control unit
and for the heating circuit,
operation with room
temperature hook−up must
be encoded:
Without limiting room
influence
C8:1
to
C8:30
Room influence limit
adjustable from 1 to 30 K
58
62
73
9G
B
94
Coding
Code 2 (cont.)
Coding in the delivered condition Possible change
Mixer circuit (cont.)
C9:0 Control of an underfloor
heating system by flow and
return temperature sensor:
Without heat−up phase C9:1 With optimisation during
the heat−up phase (operates
with coding address "C7")
d5:0 The heating program
changes to "Constant
operation with reduced
room temperature"
d5 : 1 The heating program
changes to "Constant
central heating with
standard room
temperature"
E1:1 With remote control:
Set day temperature
adjustable at the remote
control
E1:0 Set day temperature
adjustable
from 3 to 23 ºC
from 10 to 30 ºC E1:2 Set day temperature
adjustable
from 17 to 37 ºC
E2:50 With remote control:
No display correction of the
actual room temperature
E2:0
to
E2:49
Display correction 5 K
to
Display correction 0.1 K
E2:51
to
E2:99
Display correction +0.1 K
to
Display correction +4.9 K
58
62
73
9G
B
95
Coding
Code 2 (cont.)
Coding in the delivered condition Possible change
Mixer circuit (cont.)
F1:0 Screed function inactive F1:1
to
F1:4
Screed function adjustable
in accordance with four
optional temperature time
profiles (see page 99)
Note
Observe the screed
supplier’s instructions.
Observe DIN 47252 (or
local regulations).
The report to be provided
by the heating contractor
must contain the following
heat−up details:
Heat−up data with
respective flow
temperatures
Actual max. flow
temperature achieved
Operating condition and
outside temperature
during handover
The function continues after
power failure or after the
control unit has been
switched OFF.
Heating program "Heating
and DHW" will be started,
after the screed function
has been terminated or if
the address is manually set
to 0.
F2:8 Time limit for party mode*1
F2:0 No time limit *1p y
8h *1F2:1
to
F2:12
Time limit adjustable from
1 to 12h*1
*1Party mode ends automatically in program "Heating and DHW" when the systemchanges over to operation with standard room temperature.5
86
27
39
GB
96
Coding
Code 2 (cont.)
Coding in the delivered condition Possible change
Mixer circuit (cont.)
F8:5 For operation in reduced
room temperature mode,
the set room temperature
will be raised (up to the
temperature limit set by
coding address "F9") to a
value subject to the outside
temperature if the outside
F8:+10
to
F8:60
Temperature limit for
cancelling reduced mode,
adjustablefrom +10 to 60ºC
temperature, if the outside
temperature falls below
5ºC. See example1 on
page97.
Observe the setting of
coding address "A3".
F8:61 Function is not active
F9:14 If the outside temperature
is under 14ºC, the set
reduced room temperature
will be raised to the value
of the set standard room
temperature.
See example1 on page97.
F9:+10
to
F9:60
Temperature limit for
raising set reduced room
temperature, adjustable
from +10 to 60ºC
FA:20 Raising the set boiler water
temperature when
changing from operation
with reduced temperature
to operation with standard
room temperature by about
20%.
See example2 on page98.
FA:0
to
F9:50
Temperature increase
adjustable from 0 to 50%
Fb:30 Duration for the increase of
the set flow temperature
(see coding address "FA")
60 min.
See example 2 on page98
Fb:0
to
Fb:150
Duration adjustable from
0 to 300min;
1 step2min
58
62
73
9G
B
97
Coding
Code 2 (cont.)
Example1 ("F8:5", "F9:14")
A Set standard room temperature 20ºC
B Set reduced room temperature 3ºC
C Temperature limit 14ºC in accordance with coding address "F9"
D Temperature limit5ºC in accordance with coding address "F8"
58
62
73
9G
B
5
10
0
15
20
−30 −25 −20 −15 −10 −5 0 5
Set
roo
m t
em
pera
ture
in
°C
Outside temperature in °C
B
A
C D
98
Coding
Code 2 (cont.)
Example2 ("FA:20", "Fb:30")
A Start of operation with standard room temperature
B Set flow temperature in accordance with the set heating curve
C Raised set flow temperature in accordance with coding address"FA":
50ºC + 20% = 60ºC
D Duration of operation with raised set flow temperature in accordance with
coding address "Fb": 60min5
86
27
39
GB
Set
flo
w t
em
pera
ture
in
°C
Time in h
99
Coding
Screed function diagrams
Coding, see page 95.
Temperature time profile 1 ("F1:1")
Temperature time profile 2 ("F1:2")
Temperature time profile 3 ("F1:3")
Temperature time profile 4 ("F1:4")
58
62
73
9G
B
Flo
wte
mp
era
ture
°C
1 5 10 15 20 25 30Days
50
40
30
2010
Flo
wte
mp
era
ture
°C
Days
50
40
30
2010
1 5 10 15 20 25 30
Flo
wte
mp
era
ture
°C
Days
50
40
30
2010
1 5 10 15 20 25 30
Flo
wte
mp
era
ture
°C
Days
50
40
30
2010
1 5 10 15 20 25 30
100
Coding
58
62
73
9G
B
101
Parts lists
Parts list typeHK1W and HK3W
When ordering spare parts
Quote the type and serial no. (see
type plate) and the item no. of the
required part (as per parts list).
Obtain standard parts from your
local supplier.
Parts
001 Hinge
008 Support stay
011 Programming unit ON/OFF
switch
013 Housing front with frame
(with item 001)
014 PCB cover
015 Front flap
016 Casing back
017 Mounting panel
018 Programming unit
019 Programming unit flap
020 Fascia cover
021 Ribbon cable, 14pole,
only for typeHK3W
024 Fuse holder cap for control fuse
025 Fuse holder for control fuse
038 Switch, 2−pole
(ON/OFF switch"8")
040 Outside temperature sensor !
043 Cylinder temperature sensor
with plug%
047 LON communication module
048 Electronics PCB mixer extension,
only for type HK3W
049 Main PCB low voltage
050 Electronics PCB
051 Optolink
052 Main PCB 230V~
054 Power supply unit PCB
055 Mixer extension PCB, only for
type HK3W
056 Viessman 2−wire BUS
communication module
067 Immersion temperature sensor
068 Contact temperature sensor
074 Connecting cable
092 Fuse 6.3A/250V~(slow)
Parts not shown
081 Operating instructions
084 Installation and service
instructions
093 LON connecting cable
094 Terminator (2 pieces)
100 Plugs for sensors (3 pieces)
101 Plugs for pumps (3 pieces)
102 Plugs gS (3 pieces)
103 Plugs aBH (3 pieces)
104 Mains supply plugs fÖ
(3 pieces)
106 Plugs gÖ (3 pieces)
108 PlugaVD, plugaVG and plugaVH
A Type plate
58
62
73
9G
B
102
Parts lists
Parts list type HK1W
58
62
73
9G
B
015
001
001
013 008
043 067
068
040
018051
020
038
025
092024
011074
019
103
Parts lists
Parts list typeHK1W (cont.)
58
62
73
9G
B
016
014
A
013
014
049
017
054
052
050
056 047
104
Parts lists
Parts list type HK3W
58
62
73
9G
B
043 067040
015
001
001
013 008018021051
020
038
025
092024
011074
019
068
105
Parts lists
Parts list type HK3W (cont.)
58
62
73
9G
B
016
014
A
013
014
049
017
054
052
050
056 047
048 055
106
Connection and wiring diagrams
Summary
A1 Mixer extension PCB only for
typeHK3W
A2 Low voltage main PCB
A3 Main PCB 230 V~
A4 Mixer extension electronics
PCB, only for typeHK3W
A5 PCB heating circuit selection
keys, only for typeHK3W
A6 Programming unit
A7 Optolink PCB
A8 Electronics PCB
A10 LON/Viessman 2−wire BUS
communication module
(accessories)
A11 Power supply unit PCB
A12 ON/OFF switch
58
62
73
9G
B
107
Connection and wiring diagrams
Main PCB low voltage
! Outside temperature sensor/
Radio clock receiver
? Flow temperature sensor
mixer circuit M1
% Cylinder temperature sensor/
Cylinder temperature sensor 2
for cylinder storage system
aJB Return temperature sensor
or
Temperature sensor
cylinder storage system
aVD External hook−up
aVG KM BUS user, for type HK1W,
only one required per system
58
62
73
9G
B
..
108
Connection and wiring diagrams
Main PCB 230 V~
sÖ Heating circuit pump
Mixer circuitM1
or
Primary pump
Cylinder storage system
sA Cylinder primary pump
(accessories)
sK DHW circulation pump (on site)
fÖ Mains supply, 50 Hz
gÖ Central fault message (on site)
gS Mixer motor mixer circuitM1
or
Motor for three−way mixing valve
Cylinder storage system
aBH Power supply for accessories
F Fuse
K Relay
S1 ON/OFF switch "8"
58
62
73
9G
B
F1
6,3
A(s
low
)250V
109
Connection and wiring diagrams
Mixer extension PCB
? Flow temperature sensors
mixer circuits M2/M3
sÖ Heating circuit pumps
Mixer circuits M2/M3
gS Mixer motors
Mixer circuits M2/M3
K1 K6 Relay
58
62
73
9G
B
110
Specification
Specification
Rated voltage: 230V~
Rated frequency: 50Hz
Rated current: 6A~
Power
consumption: 10W
Safety class: I
Protection level: IP 20 D to EN60529,
safeguard through
appropriate design
and installation
Function: Type 1 B to
EN607301
Permissible
ambient
temperature
in operation: 0 to 40 ºC
Use in living space
and boiler rooms
(standard ambient
conditions)
during storage
and transport: 20 to 65 ºC
Rated relay output breaking capacity
at 230V~:
Heating circuit
pump sÖor
Primary pump
cylinder storage
system: 4 (2)A~*1
Cylinder primary
pumpsA: 4 (2)A~*1
DHW circulation
pumpsK: 4 (2)A~*1
Central fault
messagegÖ: 4 (2)A~*1
Mixer motors
or
Motor three−way
mixing valve
cylinder storage
systemgS: 0.2 (0.1)A*1
*1 Total max. 6 A~.
58
62
73
9G
B
111
Declaration of conformity
Declaration of conformity
We, Viessmann Werke GmbH&CoKG, D35107 Allendorf, declare as sole
responsible body, that the products
Vitotronic 050, type HK1W and Vitotronic 050, type HK3W
conform to the following standards:
EN550141
EN550142
EN500902
EN50165
EN603351
This product is designated according to the specifications of Directive
89/336/EEC: _
Allendorf, 11March2005 Viessmann Werke GmbH&CoKG
pp. Manfred Sommer
58
62
73
9G
B
112
Keyword index
Keyword index
A
Actual room temperature,
display correction, 94
Actuators, checking, 29
Additional function for
DHW heating, 52, 79
Adjusted outside
temperature, 34, 47, 88
Apartment building, 51
Applicability, 116
Automatic mode, 51
Auxiliary control for
DHW heating, 52
B
Brief scan, 34
C
Central cylinder, 53, 79
Central fault message, 18, 29, 37
Changing the display language, 24
Communication module Viessman
2−wire BUS, 56, 85
Components, 55
Connecting control unit to
Viessman 2−wire BUS system, 27
Connection and
wiring diagram, 106
Connections, summary 11
Contact temperature sensor, 58
Control unit for
wall mounted boilers, 27
Code1
calling up, 74
summary, 75
Code2
calling up, 77
overview, 78
Coding
overview, 78
resetting codes to
the delivered condition, 74
Coding summary, 78
Cylinder primary pump, 34
Cylinder priority control, 47, 52, 76, 87
Cylinder storage system, 52
Cylinder temperature control, 51
Cylinder temperature
sensor, 15, 40, 57
D
Date, 36
Declaration of conformity, 111
Detached house, 51
Diagnosis, 37
DHW circulation pump, 52
DHW heating, 51
DHW heating time program, 51
Differential temperature, 27, 86
Display contrast, 33
Display correction actual room
temperature, 94
58
62
73
9G
B
113
Keyword index
Keyword index (cont.)
E
Economy mode, 48, 88
Electrical connections summary, 11
Electronics PCB, 55
Equipment recognition, 35, 55
Extended economy mode, 48, 88
External connections, 19
External heating program
changeover, 19, 84
External "Mixer open", 19, 86
External "Mixer closed", 19, 85
F
Fault codes, 39
Fault history, 46
Fault manager, 25, 26
Fault memory, 46
Fault message, calling up, 37
Fault messages, LON users,45
Faults with fault display, 37
Flow temperature control, 49
Flow temperature sensor, 15, 58
Front cover, 55
Frost protection, 49, 87
Function extension, 73, 86
Fuses, 56
H
Heating circuit allocation, 24
Heating circuit control unit, 47
Heating circuit pump
logic function, 48, 88
Heating curves, 30
Heating program changeover, 19, 84
Heating system version, 6
Heat−up phase, 94
Hiding a fault display, 37
I
Immersion temperature sensor, 58
Initial start−up, 23
Inserting cables and applying strain
relief, 14
Installation examples,
mixer motor, 64
Installing the control unit, 13
L
Level (heating curve), 31
LON communication
module, 24, 56, 85
LON connecting cable, 25
LON user fault messages,45
LON user no. fault codes, 45
LON system, 24
M
Main PCB, 55, 106
Mains electrical isolator, 3, 20
Maximum limit, 50, 76
Minimum limit, 50, 76
Mixer algorithm, 49, 93
Mixer circuit extension kit, 61
Mixer circuit,
system dynamics, 49, 93
Mixer economy function, 89
Mixer motors
changing rotational
direction, 61, 62, 63
connection, 61, 62, 63
installation examples, 64
Mixer, run time, 92
Motor for three−way
mixing valve, 12, 17
58
62
73
9G
B
114
Keyword index
Keyword index (cont.)
O
Optimised mixer control, 49, 94
Optolink (PCB), 55
Outputs, checking, 29
Outside temperature
actual, 88, 47
adjusted, 34, 47, 88
Outside temperature sensor, 11, 59
P
Parts lists, 102
Party mode, 80, 95
PCBs, 55, 106
PluggÖ, 18
Plug aVD, 19
Power supply, 20
Priority control, 47, 52, 76, 87
Programming unit, 56
Pumps, 16
Pump idle time, 89
Q
Quick heat−up/
setback, 48, 91
R
Radio clock receiver, 60
Relay test, 29
Remote control units, 66, 68, 86
Return temperature
sensor, 49, 58, 93, 94
Room influence, 48, 90
Room temperature hook−up, 90
Room temperature sensor, 66, 68, 72
Rotary selector, 27
Rotational direction,
mixer motor, 61, 62, 63
Run−time, mixer, 92
S
Safety, 2
Scanning, 34
Scanning actual temperatures, 34
Scanning collector
temperature, 24, 56, 85
Scanning holiday programs, 36
Scanning operating conditions, 36
Scanning set temperatures, 34
Scanning set values, 34
Scanning temperatures, 34
Screed function, 48, 95, 99
Sensors
connecting, 15
checking, 29
Service level summary, 33
Set DHW temperature, 52
Set room temperature adjustment, 32
Setting LON user no., 24
Shutdown time optimisation, 48, 92
Slope (heating curve), 31
Solar circuit pump, 56
Solar control unit, 52
Specification, 110
Start−up time optimisation, 91
System versions, 6, 75
System dynamics, 49, 93
Summer/winter changeover, 83
58
62
73
9G
B
115
Keyword index
Keyword index (cont.)
T
Temperature limiter, 65
Time, 36
Time program, 47
U
Underfloor heating, 49, 94
Updating LON user list, 24
User check, 26
Users, fault messages,45
User list, 24
V
Viessmann 2−wire BUS, 27, 56, 85
Vitocom300, 25
Vitotronic300, 56
Vitotrol 200, 66, 86
Vitotrol 300, 68, 86
W
Weather−compensated mode, 90
Winter/summer, 83
Wiring diagram, 106
Working on the equipment, 3
Working with an open control unit, 2
58
62
73
9G
B
Viessmann Werke GmbH&Co KGD35107 AllendorfTel: +49 6452 700Fax: +49 6452 702780www.viessmann.de
Viessmann LimitedHortonwood 30, TelfordShropshire, TF1 7YP, GBTel: +44 1952 675000Fax: +44 1952 675040E−mail: info−[email protected]
116
Applicability
Applicability
Valid for control units
Vitotronic050, typeHK1W
Part no. 7187105
Vitotronic050, typeHK3W
Part no. 7187109
Pri
nte
d o
n e
nvir
on
men
tally f
rien
dly
,
chlo
rin
e−f
ree b
leach
ed
pap
er
58627
39G
BS
ub
ject
to t
ech
nic
al m
od
ific
ati
on
s.