Solenoid Valves

• Solenoid Valves are a mechanical/electrical valve. – The mechanical part is in the refrigeration

or water line.– The electrical portion is a coil that is

attached to the top of the valve.

Page 3: 1 HVACR317 – Core for Refrigeration Solenoid Valves Pump Down Systems Solenoid Valves Pump Down Systems

3

Solenoid Valves

Page 4: 1 HVACR317 – Core for Refrigeration Solenoid Valves Pump Down Systems Solenoid Valves Pump Down Systems

4

Solenoid Valve

• The valve in the closed position is not powered and the flow of liquid is being blocked by the plunger in the DOWN position.

• In the closed position the coil does not produce any magnetic field as it is not powered.

Page 5: 1 HVACR317 – Core for Refrigeration Solenoid Valves Pump Down Systems Solenoid Valves Pump Down Systems

5

Solenoid Valve - Closed

Valve is blockingflow of liquid.

Page 6: 1 HVACR317 – Core for Refrigeration Solenoid Valves Pump Down Systems Solenoid Valves Pump Down Systems

6

Solenoid Valve - Open

• The valve opens when the coil is powered.

• The coil generates a magnetic field and pulls the plunger into the up position.

• This allows fluid flow through the central passage of the valve.

Page 7: 1 HVACR317 – Core for Refrigeration Solenoid Valves Pump Down Systems Solenoid Valves Pump Down Systems

7

Solenoid Valve - Opening

Page 8: 1 HVACR317 – Core for Refrigeration Solenoid Valves Pump Down Systems Solenoid Valves Pump Down Systems

8

Solenoid Valve - Open

Page 9: 1 HVACR317 – Core for Refrigeration Solenoid Valves Pump Down Systems Solenoid Valves Pump Down Systems

9

Solenoid Valves

• In refrigeration solenoid valves mainly have two uses– Hot Gas By-Pass Defrost– Pump Down Systems

Page 10: 1 HVACR317 – Core for Refrigeration Solenoid Valves Pump Down Systems Solenoid Valves Pump Down Systems

10

Pump Down System

• The solenoid in the pump down system is used in the liquid line prior to the metering device and after the receiver.

• The solenoid is in the normally closed position.

• When the thermostat calls for cooling the solenoid opens.

Page 11: 1 HVACR317 – Core for Refrigeration Solenoid Valves Pump Down Systems Solenoid Valves Pump Down Systems

11

Pump Down System

• This releases refrigerant into the liquid line and raises the pressure of the system.

• A pressure switch senses this pressure increase and turns on the compressor.

• When the call for cooling is complete the thermostat de-energizes the solenoid

Page 12: 1 HVACR317 – Core for Refrigeration Solenoid Valves Pump Down Systems Solenoid Valves Pump Down Systems

12

Pump Down System

• The solenoid closes and blocks the flow of refrigerant into the liquid line.

• The refrigerant gets pumped into the receiver which is mounted after the condenser coil.

• Once the refrigerant is pumped down into the receiver the pressure on the system drops.

Page 13: 1 HVACR317 – Core for Refrigeration Solenoid Valves Pump Down Systems Solenoid Valves Pump Down Systems

13

Pump Down System

• Once the pressure has dropped to a pre-determined point the pressure switch opens and shuts off the compressor.

Page 14: 1 HVACR317 – Core for Refrigeration Solenoid Valves Pump Down Systems Solenoid Valves Pump Down Systems

14

Pump down system

• The thermostat controls the solenoid - not the compressor.

• The pressure switch controls the compressor.

• The purpose of a pump down system is to prevent liquid refrigerant from migrating to the evaporator on off cycles.

Page 15: 1 HVACR317 – Core for Refrigeration Solenoid Valves Pump Down Systems Solenoid Valves Pump Down Systems

15

Pump down system

• If liquid refrigerant is in the evaporator it will be sucked as a liquid into the compressor on start up.

• Liquid refrigerant in the compressor can break valves, crank shafts and cause premature compressor failure.

Page 16: 1 HVACR317 – Core for Refrigeration Solenoid Valves Pump Down Systems Solenoid Valves Pump Down Systems

16

Pump Down Systems

• Pump down systems are most often found on commercial freezers and low temp refrigerators. – Low temp systems–Medium temp systems

Page 17: 1 HVACR317 – Core for Refrigeration Solenoid Valves Pump Down Systems Solenoid Valves Pump Down Systems

17

Pump Down OFF Cycle

C

MD

CONDENSER

EVAPORATOR

OFF

20100

OFF

`

Page 18: 1 HVACR317 – Core for Refrigeration Solenoid Valves Pump Down Systems Solenoid Valves Pump Down Systems

18

Pump Down Starting Cycle

C

MD

CONDENSER

EVAPORATOR

ON

35100

OFF

Page 19: 1 HVACR317 – Core for Refrigeration Solenoid Valves Pump Down Systems Solenoid Valves Pump Down Systems

19

Pump Down On Cycle

C

MD

CONDENSER

EVAPORATOR

ON

40150

ON

Page 20: 1 HVACR317 – Core for Refrigeration Solenoid Valves Pump Down Systems Solenoid Valves Pump Down Systems

20

Pump Down Satisfied Cycle

C

MD

CONDENSER

EVAPORATOR

OFF

30150

ON

Page 21: 1 HVACR317 – Core for Refrigeration Solenoid Valves Pump Down Systems Solenoid Valves Pump Down Systems

21

Pump Down OFF Cycle

C

MD

CONDENSER

EVAPORATOR

OFF

20100

OFF

`

Page 22: 1 HVACR317 – Core for Refrigeration Solenoid Valves Pump Down Systems Solenoid Valves Pump Down Systems

22

NSSL1

C

S

R

Setpoint: 35 degrees F. Temp is 55 Degree F.

C1

Pump Down Schematic