1 HVACR317 – Core for Refrigeration System Recovery

1 HVACR317 – Core for Refrigeration System Recovery

Embed Size (px)

Citation preview

Page 1: 1 HVACR317 – Core for Refrigeration System Recovery

1

HVACR317 – Core for Refrigeration

HVACR317 – Core for Refrigeration

System RecoverySystem Recovery

Page 2: 1 HVACR317 – Core for Refrigeration System Recovery

2

Recovery

• All recovery machines are different. Make sure you read the operation manual for the machine you are using.

• Using a machine in the wrong manner can cause equipment damage and personal injury.

• Safety glasses must be worn at all times.

Page 3: 1 HVACR317 – Core for Refrigeration System Recovery

3

THE 3 R’S

• The three R’s of protecting the environment are:– Recovery– Recycling– Reclamation

Page 4: 1 HVACR317 – Core for Refrigeration System Recovery

4

Recovery Guidelines

• Refrigerant should be recovered from a system as a liquid.– This is quicker and easier.– Recovering as a vapor will take

considerably longer.

• Refrigerant hoses should be good quality and have good sealing gaskets.

Page 5: 1 HVACR317 – Core for Refrigeration System Recovery

5

Recovery Guidelines

• Some recovery units may require a warm-up period of up to 10 minutes.

• Read all information regarding the recovery units you are using.

Page 6: 1 HVACR317 – Core for Refrigeration System Recovery

6

Recovery

• Recovery is defined by the EPA as:– To remove refrigerant in any condition

from a system and store it in an external container without necessarily testing or processing it in any way.

• Refrigerant recovered can be re-used in the same system.

• Refrigerant recovered can be re-used in a different system if owned by the same owner.

Page 7: 1 HVACR317 – Core for Refrigeration System Recovery

7

Recovery

• Per the EPA refrigerant that has been recovered can not be sold to another customer unless it meets new refrigerant specifications under ARI-700.

Page 8: 1 HVACR317 – Core for Refrigeration System Recovery

8

Recycling

• Recycling Refrigerant is defined as:– To clean the refrigerant by oil separation

and single or multiple passes through devices such as replaceable core filter dryers.

• The filter dryers reduce moisture, acid, and particulate matter.

• Recycling means to clean up the refrigerant.

Page 9: 1 HVACR317 – Core for Refrigeration System Recovery

9

Reclaim

• Reclaiming refrigerant is defined as:– Processing refrigerant to new product

specifications by means that may include distillation.

• This requires chemical analysis of the refrigerant.

• The refrigerant is processed to new refrigerant standards.

Page 10: 1 HVACR317 – Core for Refrigeration System Recovery

10

Reclaim

• Refrigerant that is reclaimed may be sold without hefty excise taxes. This is an incentive to save and reclaim old refrigerant.

Page 11: 1 HVACR317 – Core for Refrigeration System Recovery

11

Recovery Techniques

• Active Recovery– Uses a dedicated compressor in the

machine to move the refrigerant.– Can be done on a system with a bad or

missing compressor.

Page 12: 1 HVACR317 – Core for Refrigeration System Recovery

12

Recovery Techniques

• Passive Recovery– System dependent - systems compressor

must be operational.– Passive recovery uses the systems

compressor to move the refrigerant.

Page 13: 1 HVACR317 – Core for Refrigeration System Recovery

13

Recovery Techniques

• Piercing Valves– You are required to recover refrigerant

even in a hermetic (sealed) system with no access valves or fittings.

–When servicing a sealed system you can not just cut the pipe and let the refrigerant out.

Page 14: 1 HVACR317 – Core for Refrigeration System Recovery

14

Recovery Techniques

• Piercing Valves (cont)– A piercing valve will clamp onto the line

and allow you to recover refrigerant so the system can be serviced.

– Piercing valves are temporary and can not be left on a system as they leak.

– Install a permanent valve while system is empty.

Page 15: 1 HVACR317 – Core for Refrigeration System Recovery

15

Recovery Steps

• Step 1:– Get all equipment together.– You need:• Gauges• Recovery Cylinder• Scale• Recovery Machine

Page 16: 1 HVACR317 – Core for Refrigeration System Recovery

16

Recovery Steps

• Step 1 (Continued)– Net Refrigerant is found with the following

formula:

W.C.___X 0.8 = ____80% Liquid level                       +____ T.W.                 ____ Total Capacity weight

–W.C. and T.W. is stamped on the handle of the cylinder

– Do not overfill. These cylinders can explode.

Page 17: 1 HVACR317 – Core for Refrigeration System Recovery

17

Recovery Steps

• Step 2:– Connect your gauges to the equipment.– Red Hose (High Side) goes to the high

side of the equipment (Liquid Line)– Blue Hose (Low Side) goes to the low side

of the equipment (Suction Line)–Make sure all gauge valves are closed.

Page 18: 1 HVACR317 – Core for Refrigeration System Recovery

18

Recovery Steps

• Step 3– Connect the recovery machine.–Middle hose (most often white) from your

gauge manifold will connect to the inlet port of the recovery machine.

– Additional hose from the recovery machine will go to the liquid side of the recovery cylinder.

Page 19: 1 HVACR317 – Core for Refrigeration System Recovery

19

Recovery Steps

• Step 4– Starting from the hoses connected to the

equipment you are recovering from purge all the air out of the hoses.

– Once you get to the gauges open both side handles and the valve that goes to the white hose. If you have an extra hose, leave that one closed.

Page 20: 1 HVACR317 – Core for Refrigeration System Recovery

20

Recovery Steps

• Step 4 (Continued)– At the recovery machine turn the inlet

valve to ON and the discharge valve to ON.

– Bleed the air out of the line at the recovery cylinder.

– Open the valve on the recovery cylinder.

Page 21: 1 HVACR317 – Core for Refrigeration System Recovery

21

Recovery Steps

• Step 5:– Turn the recovery machine ON and wait

until all the gauges show 0 PSI. (can go as low as 5 inches vacuum).

Page 22: 1 HVACR317 – Core for Refrigeration System Recovery

22

Recovery Steps

• Step 6:– Once system is empty then:– Close all gauge handles– Turn off recovery machine– Turn off recovery cylinder valve.

Page 23: 1 HVACR317 – Core for Refrigeration System Recovery

23

Recovery Steps

• Step 7:– Disconnect recovery cylinder and

machine – put them aside.–Weigh the recovery cylinder – record the

weight and the net refrigerant recovered.

Page 24: 1 HVACR317 – Core for Refrigeration System Recovery

24

Recovery Rules

• Recovered refrigerant can not change ownership.

• Refrigerant must be reclaimed to change ownership.

• The refrigerant is the property of the person who owns the equipment.

Page 25: 1 HVACR317 – Core for Refrigeration System Recovery

25

Recovery Rules

• Recovered refrigerant can not be mixed.

• Recovery containers must be DOT (department of transportation) approved and color coded gray with a yellow top.

Page 26: 1 HVACR317 – Core for Refrigeration System Recovery

26

Recovery Rules

• All newly manufactured recovery and recycling machines must be certified by an EPA approved organization to meet the requirements of the evacuation table (standards).

• Always evacuate the machine before each use.

Page 27: 1 HVACR317 – Core for Refrigeration System Recovery

27

Recovery Rules

• When recovering R134A use a machine dedicated to that refrigerant.– The oil requirements are different.

• Recover as a liquid when possible. –Most recovery machines will first get the

liquid and then the vapor on their own.

Page 28: 1 HVACR317 – Core for Refrigeration System Recovery

28

Do your repair work

• Now the system is empty. You can do whatever repair work you need to accomplish.

• Make sure that you do not leave any leaks or braze near your gauges while they are connected.

• Remove any schraeder cores while you are brazing. They are rubber and will burn.