    T&D Service SolutionsT&D Service SolutionsSiemens Power Technologies InternationalSiemens Power Technologies International

    PSSE V32 Part I

  • 7/25/2019 14 00 Hs Sptius_pssev32_part1

    2/55

  • 7/25/2019 14 00 Hs Sptius_pssev32_part1

    3/55

    2009 Siemens Energy, Inc. All rights reservedSiemens Power Technologies InternationalOctober 10Page 3

    Power Flow Interface

    2009 Siemens Energy, Inc. Al l r ights reserved.

  • 7/25/2019 14 00 Hs Sptius_pssev32_part1

    4/55

    2009 Siemens Energy, Inc. All rights reservedSiemens Power Technologies InternationalOctober 10Page 4

    Views in the Power Flow Interface

    TreeView

    SpreadsheetView

    Toolbars

    DiagramView

    Report/ProgressWindow

    StatusBar

    Menu Bar

    Multiple

    Tabs

  • 7/25/2019 14 00 Hs Sptius_pssev32_part1

    5/55

    2009 Siemens Energy, Inc. All rights reservedSiemens Power Technologies InternationalOctober 10Page 5

    Use menu bar File>New or toolbar button

    Choose New Network Case

    Enter Base MVA, frequency, rating options

    To Create a New Case

  • 7/25/2019 14 00 Hs Sptius_pssev32_part1

    6/55

    2009 Siemens Energy, Inc. All rights reservedSiemens Power Technologies InternationalOctober 10Page 6

    Network Data Editing (V30, V31 & V32)

    This row of data being edited. In V30or V31, must move cursor to anotherrow or click on pencil to confirm data

    change. In V32, press afterdata entry in cell is enough.

    One tab for each

    data category

  • 7/25/2019 14 00 Hs Sptius_pssev32_part1

    7/55

    2009 Siemens Energy, Inc. All rights reservedSiemens Power Technologies InternationalOctober 10Page 7

    Revised Spreadsheet/Tree View Organization

    (V32.0)

    Tabs and folders in Spreadsheet & Tree View re-ordered and synchronized.

    Tab labels fully exposed.

    Excel-like tools and Context-menu allow easy selection of tabs.

  • 7/25/2019 14 00 Hs Sptius_pssev32_part1

    8/55

    2009 Siemens Energy, Inc. All rights reservedSiemens Power Technologies InternationalOctober 10Page 8

    Configurable Spreadsheets (V32.0)

    Change precision for any column

    Change font / style / color for any column

  • 7/25/2019 14 00 Hs Sptius_pssev32_part1

    9/55

    2009 Siemens Energy, Inc. All rights reservedSiemens Power Technologies InternationalOctober 10Page 9

    Regional Settings (V32.0)

    Preference for displaying numbers in cells according to Regional and LanguageOptions in Control Panel.

  • 7/25/2019 14 00 Hs Sptius_pssev32_part1

    10/55

    2009 Siemens Energy, Inc. All rights reservedSiemens Power Technologies InternationalOctober 10Page 10

    Configuration Resets (V31)

    Version 30.3 introduced the ability tomemorize spreadsheet customizations.

    Added two new functionsto reset the spreadsheets todefault configurations.

    Reset the active spreadsheet

    Reset all spreadsheets

    Added new function to reset mostapplication dialogs to their defaultconfigurations.

  • 7/25/2019 14 00 Hs Sptius_pssev32_part1

    11/55

    2009 Siemens Energy, Inc. All rights reservedSiemens Power Technologies InternationalOctober 10Page 11

    After Editing,

    Save the Data

    File > SAVE or Show > Case Data - Saves a power flow model (working case) inbinary or raw data format

  • 7/25/2019 14 00 Hs Sptius_pssev32_part1

    12/55

    2009 Siemens Energy, Inc. All rights reservedSiemens Power Technologies InternationalOctober 10Page 12

    Toolbars

    Tools > Customize Toolbars

  • 7/25/2019 14 00 Hs Sptius_pssev32_part1

    13/55

    2009 Siemens Energy, Inc. All rights reservedSiemens Power Technologies InternationalOctober 10Page 13

    Automation Toolbar

    Command line input

    Start / stop recording (PYTHON, IDEV file)

    Run automation file (PYTHON, IDEV, IPLAN file)

    Re-run automation file (V32)

    Edit last recorded automation file

    Edit last run automation file

  • 7/25/2019 14 00 Hs Sptius_pssev32_part1

    14/55

    2009 Siemens Energy, Inc. All rights reservedSiemens Power Technologies InternationalOctober 10Page 14

    Analysis Toolbar

    Solution settings

    Solve

    PV analysis

    PV analysis using previous results

    QV analysis

    QV analysis using previous results

    AC contingency solution (ACCC)

    Multi-level AC contingency solution

    AC corrective action

    Reliability assessment

    Substation reliability assessment

    Network connectivity check (TREE)

    Solve for switching

    Inertial power flow

    N-1-1 analysis

  • 7/25/2019 14 00 Hs Sptius_pssev32_part1

    15/55

    2009 Siemens Energy, Inc. All rights reservedSiemens Power Technologies InternationalOctober 10Page 15

    To Create a New Diagram

    Use menu bar File>Open or toolbar button

    Choose New Diagram

  • 7/25/2019 14 00 Hs Sptius_pssev32_part1

    16/55

    2009 Siemens Energy, Inc. All rights reservedSiemens Power Technologies InternationalOctober 10Page 16

    Contour Plotting (V30.3)

  • 7/25/2019 14 00 Hs Sptius_pssev32_part1

    17/55

    2009 Siemens Energy, Inc. All rights reservedSiemens Power Technologies InternationalOctober 10Page 17

    Bus Location File

    File>Open (*.loc)

    Controlled through Preferencesdialog

    Can also update existing diagram: Diagram>Update bus locations

    Bus locations can be specified in either CARTESIAN or GEOPHYSICALcoordinates

  • 7/25/2019 14 00 Hs Sptius_pssev32_part1

    18/55

    2009 Siemens Energy, Inc. All rights reservedSiemens Power Technologies InternationalOctober 10Page 18

    Diagram View Results Toolbar

    Toggle labels

    Diagram annotation

    Power flow solution results

    Power flow impedance data

    Graphical case comparison

    ASCC fault analysis

    IEC analysis

    Reliability analysis

    Dynamic simulation models

    Flow animation

    Current loading bar chart

    Multi-section line reporting

    Lock diagram (but not from deleting or moving equipment)

    Also activated from Menu Bar

    (Diagram>Results)

  • 7/25/2019 14 00 Hs Sptius_pssev32_part1

    19/55

    2009 Siemens Energy, Inc. All rights reservedSiemens Power Technologies InternationalOctober 10Page 19

    Current Loading Bar Chart

    I: % rating based on currentS: % rating based on MVA

    Properties can be changed in: Diagram Annotation Diagram Properties Diagram Range Checking

  • 7/25/2019 14 00 Hs Sptius_pssev32_part1

    20/55

    2009 Siemens Energy, Inc. All rights reservedSiemens Power Technologies InternationalOctober 10Page 20

    Editing Network Data From Diagram (V32.0)

    Select item in diagram and right click to bring up property sheet

    Edit > Preference

  • 7/25/2019 14 00 Hs Sptius_pssev32_part1

    21/55

    2009 Siemens Energy, Inc. All rights reservedSiemens Power Technologies InternationalOctober 10Page 21

    GRPG-Style Report Node (V32.0)

    Present results of a Python function on a diagram Arguments may be passed Python functions

    Sample file usegrpg.py has some GRPG functions

  • 7/25/2019 14 00 Hs Sptius_pssev32_part1

    22/55

    2009 Siemens Energy, Inc. All rights reservedSiemens Power Technologies InternationalOctober 10Page 22

    Diagram Templates (V32.0)

    Common network equipment configurations can be created and reused.

  • 7/25/2019 14 00 Hs Sptius_pssev32_part1

    23/55

    2009 Siemens Energy, Inc. All rights reservedSiemens Power Technologies InternationalOctober 10Page 23

    Saving the Slider Diagram

    In Diagram view, under File > Save, or File > Save as

    Two formats:

    Slider binary file (*.sld) Slider XML file (*.sldxml, text file)

    Power flow case not saved simultaneously when slider diagram is saved, andvice versa.

  • 7/25/2019 14 00 Hs Sptius_pssev32_part1

    24/55

    2009 Siemens Energy, Inc. All rights reservedSiemens Power Technologies InternationalOctober 10Page 24

    Navigating Between Views

    Mouse click on item to go between different views:

    Double click toedit data

    Doubleclick toedit data

    Rightclick tolocate

    Progress

    Window

    Spreadsheet View

    Diagram View

    Tree View

    Report

    Window

    Doubleclick for

    GOUTSelectdiagramwindow

    Doubleclick for

    GOUT

  • 7/25/2019 14 00 Hs Sptius_pssev32_part1

    25/55

    2009 Siemens Energy, Inc. All rights reservedSiemens Power Technologies InternationalOctober 10Page 25

    Configuration Resets (V31)

    Version 30.3 introduced the ability tomemorize spreadsheet customizations.

    Added two new functionsto reset the spreadsheets todefault configurations.

    Reset the active spreadsheet

    Reset all spreadsheets

    Added new function to reset mostapplication dialogs to their defaultconfigurations.

  • 7/25/2019 14 00 Hs Sptius_pssev32_part1

    26/55

    2009 Siemens Energy, Inc. All rights reservedSiemens Power Technologies InternationalOctober 10Page 26

    More Program Settings in V31

    (Misc > OPTN)

    % branch loadings reportedaccording to MVA or current

    Print winding buses of 3-winding transformers inPOUT, LOUT, LAMP

    Print outaged branches in

    POUT, LOUT and LAMP

  • 7/25/2019 14 00 Hs Sptius_pssev32_part1

    27/55

    2009 Siemens Energy, Inc. All rights reservedSiemens Power Technologies InternationalOctober 10Page 27

    Newton Solution Convergence Parameters (V30.3)

    Two new solution parameters in Version 30.3: Controlled bus Q mismatch convergence tolerance

    (VCTOLQ = 0.1 MW/Mvar) Controlled bus voltage error convergence tolerance

    (VCTOLV = 0.00001 pu)

    Ensure voltage at controlled bus is being controlled if at least one of its

    controlling devices is not at var limit.

    Compatibility with convergence test in previous releases: Version 28 or earlier, set VCTOLQ = 1000, VCTOLV = TOLN/SBASE Version 29.0 through 29.5.1, set VCTOLQ=TOLN, VCTOLV =10 Version 30.0 through 30.2.2, set VCTOLQ=TOLN, VCTOLV=0.0001

  • 7/25/2019 14 00 Hs Sptius_pssev32_part1

    28/55

    2009 Siemens Energy, Inc. All rights reservedSiemens Power Technologies InternationalOctober 10Page 28

    Allows Multiple Voltage Controlling Devices (V30.1)

    Multiple set-point mode voltage controlling devices are allowed on the samebus or on buses connected by zero impedance lines, such as

    Generators Switched shunts Shunt elements at the sending end of FACTS devices VSC dc line converters

    An RMPCT data item is now associated with switched shunts and FACTSdevices.

  • 7/25/2019 14 00 Hs Sptius_pssev32_part1

    29/55

    2009 Siemens Energy, Inc. All rights reservedSiemens Power Technologies InternationalOctober 10Page 29

    Switched Shunt Adjustment (V31)

    Switched shunts which control voltage to a band can oscillate due to: Multiple devices electrically close to each other

    Large admittance blocks Narrow voltage bands

    New solution parameter SWVBND specifies the percentage (population) of

    such switched shunts whose controlled voltage is outside of the desiredvoltage band which can be adjusted on any single adjustment cycle.

  • 7/25/2019 14 00 Hs Sptius_pssev32_part1

    30/55

    2009 Siemens Energy, Inc. All rights reservedSiemens Power Technologies InternationalOctober 10Page 30

    Switched Shunt Adjustments (V32.0)

    Previous adjustment method: Pre-defined switching sequence based on input order

    Reactor & capacitor components cannot be on simultaneously

    New features: Status attribute Both reactors and capacitors can be on at the same time

    Optional adjustment method to find a combination of reactors and/orcapacitors with the next larger/smaller total admittance.

  • 7/25/2019 14 00 Hs Sptius_pssev32_part1

    31/55

    2009 Siemens Energy, Inc. All rights reservedSiemens Power Technologies InternationalOctober 10Page 31

    Multiple Fixed Shunts at a Bus (V31)

    Similar in data structure to loads and machines

    Identified by bus and 2-character ID

    Can be switched in/out

    Inherits area, zone and owner attributes of bus

    Negative sequence same as positive sequence

    Can enter separate zero sequence admittance

  • 7/25/2019 14 00 Hs Sptius_pssev32_part1

    32/55

    2009 Siemens Energy, Inc. All rights reservedSiemens Power Technologies InternationalOctober 10Page 32

    New Transformer Code (V31)

    When CW = 3, transformer turn ratios (WINDV) and limits (RMAX andRMIN) for voltage or MVAR controlling transformer windings are

    specified in pu of nominal winding voltage (NOMV)

    (When CW = 1, items are specified in pu of winding bus base voltage)

  • 7/25/2019 14 00 Hs Sptius_pssev32_part1

    33/55

    2009 Siemens Energy, Inc. All rights reservedSiemens Power Technologies InternationalOctober 10Page 33

    FACTS Devices (V31)

    Shunt element may control voltage at remote bus

    A switched shunt can control reactive power setting of the shunt element of aFACTS device

    Maximum number of FACTS devices is increased:

    From 20 to 50 at 4,000 through 11,000 buses From 40 to 100 at 12,000 through 49,000 buses From 99 to 250 at 50,000 buses and above

  • 7/25/2019 14 00 Hs Sptius_pssev32_part1

    34/55

    2009 Siemens Energy, Inc. All rights reservedSiemens Power Technologies InternationalOctober 10Page 34

    FACTS Devices & DC Lines Identif iers (V31)

    Identify FACTS devices, two-terminal dc lines, and multi-terminal dc lines bya 12 character device name

    Same approach as VSC dc lines

    When old Saved Case File is read, device names are set to old device

    number, left justified

    Old Response Files, Python programs, and IPLAN programs referencingdevice numbers will continue to work

  • 7/25/2019 14 00 Hs Sptius_pssev32_part1

    35/55

    2009 Siemens Energy, Inc. All rights reservedSiemens Power Technologies InternationalOctober 10Page 35

    Wind Machines (V31)

    Wind machine explicitly identified in power flow data

    Control Mode:

    0 = non-wind machine1 = specified var limits (same as non-wind machines)2 = use var limits from MW output and specified PF3 = fix var output determined from MW output and specified PF

  • 7/25/2019 14 00 Hs Sptius_pssev32_part1

    36/55

    2009 Siemens Energy, Inc. All rights reservedSiemens Power Technologies InternationalOctober 10Page 36

    Non-Conforming Loads (V32.0)

    Each load is characterized as either conforming (i.e., scalable) or non-conforming (i.e., fixed)

    Only conforming subsystem loads:

    Are modified during load scaling

    using SCAL API

    Participate in transfer incrementin P-V analysis

  • 7/25/2019 14 00 Hs Sptius_pssev32_part1

    37/55

    2009 Siemens Energy, Inc. All rights reservedSiemens Power Technologies InternationalOctober 10Page 37

    Zero-Impedance-Line Loops (V32.0)

    Branches for breakers and switches can be modeled as zero impedance lines.

    Restriction which prohibited zero impedance line-connected loops removed.

  • 7/25/2019 14 00 Hs Sptius_pssev32_part1

    38/55

    2009 Siemens Energy, Inc. All rights reservedSiemens Power Technologies InternationalOctober 10Page 38

    Transformer Phase Shift Angle Adjustment (V32.1)

    For some European transformers, a change in phase shift angle results in achange of turns ratio.

    Transformer control mode (5) to select asymmetric phase shift angleadjustment to control active power flow.

    For regular (symmetrical) phase shifter,

    control mode is 3,

    as before,

    andwinding connection angle is not used.

  • 7/25/2019 14 00 Hs Sptius_pssev32_part1

    39/55

    2009 Siemens Energy, Inc. All rights reservedSiemens Power Technologies InternationalOctober 10Page 39

    Report of Load Reduction in Power Flow Solution

    (V32.0)

    Constant MVA loads which have been reduced due to bus voltages belowPQBRAK.

    Constant current loads which have been reduced due to bus voltages below0.5 pu.

  • 7/25/2019 14 00 Hs Sptius_pssev32_part1

    40/55

    2009 Siemens Energy, Inc. All rights reservedSiemens Power Technologies InternationalOctober 10Page 40

    Expanded AREA and ZONE Reporting (V32.0)

    AREA report tabulates 3 categories of load: Area load at area buses, Area load at non-area buses, Non-area load at

    area buses

    AREA report tabulates 2 categories of net interchange: Tie flows, Tie flows plus loads

    Similar options for ZONE reporting

  • 7/25/2019 14 00 Hs Sptius_pssev32_part1

    41/55

    2009 Siemens Energy, Inc. All rights reservedSiemens Power Technologies InternationalOctober 10Page 41

    Area, Owner and Zone Numbering (V32.0)

    4 digit zone number at any program size level

    Allow area, owner and zone numbers of 1 through 9,999 at all program sizelevels

    Limits remain on the number of area, owners and zones that may be

    represented in a power flow case These continue to be dependent on the dimensional capacity of PSSEwhich is running

  • 7/25/2019 14 00 Hs Sptius_pssev32_part1

    42/55

    2009 Siemens Energy, Inc. All rights reservedSiemens Power Technologies InternationalOctober 10Page 42

    Subsystem Loads in RAWD Output (V32.0)

    Option in RAWD indicating which loads are to be included in output:

    All loads at subsystem

    buses

    Subsystem loads at allbuses

    All loads at subsystem

    buses and subsystemloads at non-subsystembuses

  • 7/25/2019 14 00 Hs Sptius_pssev32_part1

    43/55

    2009 Siemens Energy, Inc. All rights reservedSiemens Power Technologies InternationalOctober 10Page 43

    Contingency Analysis

    2009 Siemens Energy, Inc. Al l r ights reserved.

  • 7/25/2019 14 00 Hs Sptius_pssev32_part1

    44/55

    2009 Siemens Energy, Inc. All rights reservedSiemens Power Technologies InternationalOctober 10Page 44

    Contingency Analysis Setup

    Prepare base case (N-0)

    Prepare and input data files:

    Study area (Subsystem Description file *.sub) Equipment to be monitored (Monitored Element File *.mon) Contingencies to be tested (Contingency description File *.con) Other auxiliary data files

    Read basic input data files (DFAX)

    Perform contingency analysis DC analysis AC analysis

    Multi-level AC analysis

    Review results in tables or diagrams

  • 7/25/2019 14 00 Hs Sptius_pssev32_part1

    45/55

    2009 Siemens Energy, Inc. All rights reservedSiemens Power Technologies InternationalOctober 10Page 45

    Build Distribution Factor Data File (DFAX)

    (Power Flow > Linear Network >Build Distribution Factor Data File)

    Pre-processor for contingencyand transfer limit calculations:

    Reads data from:

    SUBsystem description file

    MONitored element file

    CONtingency description FileCalculates line outage distribution factors for

    linear analysis

    Stores information in binary output file (DFX)

    SUB MON CON

    DFAX

    DFX

  • 7/25/2019 14 00 Hs Sptius_pssev32_part1

    46/55

    2009 Siemens Energy, Inc. All rights reservedSiemens Power Technologies InternationalOctober 10Page 46

    Subsystem Description File

    SYSTEM MONITOR6AREAS 6 10 ------->

    Areas 6 to 10 inclusive

    END

    SYSTEM WESTBUSES 3001 3008 ------->

    Buses 3001 through 3008 inclusive.

    ENDSUBSYSTEM CONT2 ------->

    Subsystem means the same as System

    JOIN

    AREA 2 ------->

    JOIN defines elements between 230 & 500 kV

    KVRANGE 230 500 AND within Area 2END

    END

    END

    Specify generator/load buses participating in generator/load shift for transfer limit analysis:

    PARTICIPATEBUS 123 0.4BUS 456 0.6

    END

  • 7/25/2019 14 00 Hs Sptius_pssev32_part1

    47/55

    2009 Siemens Energy, Inc. All rights reservedSiemens Power Technologies InternationalOctober 10Page 47

    Monitored Element File

    MONITOR BRANCHES3004 1523006 1533008 154

    201 151202 152203 154205 154

    ENDMONITOR INTERFACE WEST RATING 200 MW

    3004 1523006 1533008 154

    ENDMONITOR INTERFACE EAST RATING 350 MW

    MONITOR TIES FROM AREA 1 TO AREA 2

    ENDEND

    Interfaces can be input asas individual branches oras a group. E.g., Interface

    East is all tie lines fromAREA 1 to AREA 2.

  • 7/25/2019 14 00 Hs Sptius_pssev32_part1

    48/55

    2009 Siemens Energy, Inc. All rights reservedSiemens Power Technologies InternationalOctober 10Page 48

    Contingency Description File

    CONTINGENCY TRIP1NUCLEARREMOVE UNIT 1 FROM BUS 101 dispatchbus 3001 .2bus 3008 .1bus 201 .2

    bus 206 .2bus 102 .3end

    ENDCONTINGENCY EASTLINE1

    TRIP LINE FROM BUS 3004 TO BUS 152

    ENDCONTINGENCY EASTLINE2TRIP LINE FROM BUS 3006 TO BUS 153

    ENDCONTINGENCY DOUBLE1

    TRIP LINE FROM BUS 153 TO BUS 154 CKT 1

    TRIP LINE FROM BUS 153 TO BUS 154 CKT 2ENDEND

    Number of contingency

    elements per event

    increased from 16 to 32

    in V32.

  • 7/25/2019 14 00 Hs Sptius_pssev32_part1

    49/55

    2009 Siemens Energy, Inc. All rights reservedSiemens Power Technologies InternationalOctober 10Page 49

    Shunt Contingencies in V32

    New command to trip in-service switched shunt

    REMOVE SWSHUNT FROM BUS 1234

    ALTER /SET /INCREASE /DECREASE ... SHUNT commands recognize the MVAR

    keyword, in addition to MW and PERCENT

    SET BUS 5678 SHUNT TO -200 MVAR

    ADD & REMOVE commands allow status change of an individual load or fixed shuntADD SHUNT 2 TO BUS 7890

  • 7/25/2019 14 00 Hs Sptius_pssev32_part1

    50/55

    2009 Siemens Energy, Inc. All rights reservedSiemens Power Technologies InternationalOctober 10Page 50

    More Contingency File Options (V32.0)

    Command to change current or power demand or scheduled compounded dc voltageof two-terminal dc lines, e.g.

    SET TWOTERMDC XYZ-DC TO 500 MW

    Command to generate single machine contingencies (At buses with multiple machines,the one with largest PGEN selected), e.g.

    SINGLE MACHINE IN SUBSYSTEM ABC

    Command to disconnect in-service buses, e.g.

    SINGLE BUS IN KV 345

    Number of contingency elements per event increased from 16 to 32.

  • 7/25/2019 14 00 Hs Sptius_pssev32_part1

    51/55

    2009 Siemens Energy, Inc. All rights reservedSiemens Power Technologies InternationalOctober 10Page 51

    Breakers & Switches in Configuration Files (V32.0)

    Breakers and switches introduced as non-transformer branches with @ or * in branchID.

    Use keyword breakers to include breaker and switch branches in MON file, e.g.

    Monitor breakers in area 1

    Use keyword breaker to include breaker and switch branches in CON file, e.g.

    Single breaker in zone 2Double breaker from bus 5000

  • 7/25/2019 14 00 Hs Sptius_pssev32_part1

    52/55

    2009 Siemens Energy, Inc. All rights reservedSiemens Power Technologies InternationalOctober 10Page 52

    Configuration File Builder (V30.3)

    Build contingency analysis files byselecting options

    SUB Choose bus subsystem by picking

    name from existing subsystem definitionsor by using bus subsystem selector andgiving new name

    MON Monitor bus voltages and/or

    branch flows within subsystem

    CON Define contingency groups withinsubsystem

  • 7/25/2019 14 00 Hs Sptius_pssev32_part1

    53/55

    2009 Siemens Energy, Inc. All rights reservedSiemens Power Technologies InternationalOctober 10Page 53

    Defining Configuration File Text Editor

    Edit> Preferences

    Edit file

    Define text

    editor

  • 7/25/2019 14 00 Hs Sptius_pssev32_part1

    54/55

    2009 Siemens Energy, Inc. All rights reservedSiemens Power Technologies InternationalOctober 10Page 54

    Bus Renumbering for Contingency

    Analysis Input Data Files (V32.0)

    Bus renumbering (RNFI) can now be applied to: Subsystem description data file

    Monitored description data file Contingency description data file Tripping data file Load throwover data file