29
Product Data Publication 1771Ć2.183 - May 1996 1771 Analog Input and Output Modules Interfaces your analog devices to AllenĆBradley programmable controllers within the 1771 Universal I/O structure. Allen–Bradley analog I/O modules interface to analog devices such as speed sensors, temperature and pressure sensors, tire and printing presses, and flow meters. The modules are compatible with all current Allen-Bradley programmable controllers. Allen-Bradley analog modules perform the required A/D and D/A conversions to directly interface analog signals to programmable controller data table values using up to 16-bit resolution. Analog I/O can be user-configured for the desired fault-response state in the event that I/O communication is disrupted. This feature provides a safe reaction/response in case of a fault, limits the extent of the fault and provides a predictable fault response. Photo/Slide #

1771 Analog Input and Output Modules

Embed Size (px)

Citation preview

Page 1: 1771 Analog Input and Output Modules

Product Data

Publication 17712.183 - May 1996

1771 Analog Input and Output Modules

Interfaces your analog devices to AllenBradley programmable

controllers within the 1771 Universal I/O structure.

Allen–Bradley analog I/O modules interface to analog devices suchas speed sensors, temperature and pressure sensors, tire and printingpresses, and flow meters. The modules are compatible with allcurrent Allen-Bradley programmable controllers.

Allen-Bradley analog modules perform the required A/D and D/Aconversions to directly interface analog signals to programmablecontroller data table values using up to 16-bit resolution.

Analog I/O can be user-configured for the desired fault-responsestate in the event that I/O communication is disrupted. This featureprovides a safe reaction/response in case of a fault, limits the extentof the fault and provides a predictable fault response.

Photo/Slide #

Page 2: 1771 Analog Input and Output Modules

1771 Analog Input and Output Modules 1. . . . . . . . . . . . . . .

Interfaces your analog devices to AllenBradley programmable controllers within the 1771 Universal I/O structure. 1. . . . . . . . . .

Analog Module Features 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Overview of the 1771 Analog I/O Modules 2. . . . . . . . . . . . . . . . . .

1771 Analog I/O Modules 2. . . . . . . . . . . . . . . . . . . . . . . . . . . .

System Compatibility 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Status Indicators 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Keying 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Power Supply Requirements 3. . . . . . . . . . . . . . . . . . . . . . . . . .

Module Placement Guidelines 3. . . . . . . . . . . . . . . . . . . . . . . . .

Addressing Modes 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Analog Input Modules 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Input Filtering 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Analog Output Modules 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

High Resolution NSeries Analog Modules 5. . . . . . . . . . . . . . . . . .

Conformal Coating 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Compliance to European Union Directives 5. . . . . . . . . . . . . . . . . .

EMC Directive 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Low Voltage Directive 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Agency Certification 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Where to Look 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Analog Input Module (Cat. No. 1771IFE Series C) 8 differential, or 16 singleended inputs 8. . . . . . . . . . . . . . . . . . . . . . . . . . .

Analog Input Module (Cat. No. 1771IFE Series C) 8 differential, or 16 singleended inputs 7. . . . . . . . . . . . . . . . . . . . . . . . . . .

Support Services 27. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Technical Support 27. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Engineering and Field Services 27. . . . . . . . . . . . . . . . . . . . . . . .

Technical Training 27. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Repair and Exchange Services 27. . . . . . . . . . . . . . . . . . . . . . . .

Table of Contents

Page 3: 1771 Analog Input and Output Modules

2 1771 Analog Input and Output Modules

Overview

Publication 17712.183 - May 1996

Analog I/O modules feature:

• a wide range of signal levels including standard analog inputs andoutputs, and direct thermocouple and RTD temperature inputs

• software selectable features including digital filtering for noisytransmitters and environments, and range selections per I/O pointfor added flexibility

• comprehensive self-diagnostic test: over/underrange, high/lowrate-of-change alarming, open input/open loop detection, onboard error checking

• scaling to engineering units makes incoming signals easy to workwith

• I/O chassis-supplied power eliminates the cost of external powersupplies

• inputs isolated from power source noise

• isolation between individual output circuits

• user-configurable output response (min, mid, max range or lastvalue) for safe reaction to a module fault

• a status block provides information to the processor for alarmingand troubleshooting

Allen-Bradley offers a full line of analog modules to accommodateyour specific needs. The varied selection of the analog I/O familyallows you the flexibility to purchase modules with the features andperformance capabilities that you need. Refer to the table below fora list of analog I/O family modules.

1771 Analog I/O Modules

Catalog Number Series Module Type

1771IFE C Analog Input

1771IFF A Fast Analog Input

1771IFMS A Fast Millivolt Input

1771IL C Isolated Analog Input

1771IR C Resistance Temperature Detector Input

1771IXE C Thermocouple Millivolt Input

1771IXHR B High Resolution Thermocouple /Millivolt Input

1771OFE1 B Analog Output (voltage)

1771OFE2 B Analog Output (4 to 20mA)

1771OFE3 B Analog Output (0 to 50mA)

1771N seriesHigh Resolution Analog Modules are alsoavailable. Refer to publication 17712.193

System Compatibility

Refer to the individual specification sheets included in this documentfor compatibility and use of each module.

Analog Module Features

Overview of the 1771Analog I/O Modules

Page 4: 1771 Analog Input and Output Modules

3 1771 Analog Input and Output Modules

Overview

Publication 17712.183 - May 1996

Status Indicators

The front panel of each analog I/O module contains status indicators.Refer to the individual specification sheets included in this documentfor each module’s status indicators and meanings.

Keying

Plastic keying bands shipped with each I/O chassis let you key yourI/O slots to accept only one type of module. You can key anybackplane connector in an I/O chassis to receive your module exceptfor the leftmost connector, which is reserved for adapter or processormodules.

Power Supply Requirements

The analog modules do not require any external power. Power issupplied through the 1771 I/O chassis backplane from the associatedchassis power supply. Refer to the table below for individual modulepower requirements.

Catalog Number Module TypeCurrent

Requirement

1771IFE/C Analog Input 500mA

1771IFF/A Fast Analog Input 500mA

1771IFMS/A Intrinsically Safe Fast Millivolt Input 750mA

1771IL/C Isolated Analog Input 1.0mA

1771IR/C Resistance Temperature Detector Input 850mA

1771IXE/C Thermocouple Millivolt Input 750mA

1771IXHR/B High Resolution Thermocouple /Millivolt Input 750mA

1771OFE1/B Analog Output (voltage) 1.5A

1771OFE2/B Analog Output (4 to 20mA) 1.5A

1771OFE3/B Analog Output (0 to 50mA) 2.5A

Total the current requirements for all the modules in the chassis toavoid overloading the power supply or the I/O chassis backplane.

Module Placement Guidelines

Group your modules to minimize adverse effects from radiatedelectrical noise and/or heat.

• Group analog I/O modules away from other modules in thechassis to minimize electrical noise interference.

• Place analog input modules and other I/O modules that aresensitive to heat away from slot power supplies to minimizeadverse heat effects.

RUN

FLT

Page 5: 1771 Analog Input and Output Modules

4 1771 Analog Input and Output Modules

Overview

Publication 17712.183 - May 1996

Addressing Modes

Your Allen-Bradley processor can address its I/O in 2-slot, 1-slot or1/2-slot I/O groups. You select the addressing method for the chassisin which a processor or I/O adapter resides with the I/O chassisbackplane switch assembly. You make the selection for each chassisindependently, choosing one method of addressing for each chassis.

The 1771 analog input modules are intelligent modules that useblock transfer programming to interface analog inputs withAllen-Bradley programmable controllers. Typical analogapplications include:

• temperature and pressure sensing

• level sensing

• flow metering

Allen-Bradley analog input modules are available with a wide rangeof input terminals per module.

Catalog Number Module TypeNumber of

InputsType of Inputs

1771IFE/C Analog Input 16/8 16 singleended/8 differential

1771IFF/A Fast Analog Input 16/8 16 singleended/8 differential

1771IFMS Intrinsically Safe Fast Millivolt Input 8 differential low level

1771IL/C Isolated Analog Input 8 fully isolated differential

1771IR/C RTD Input 6 RTD, fully isolated differential

1771IXE/C Thermocouple Millivolt Input 8 thermocouple/mV, fully isolateddifferential

1771IXHR/B High Resolution Thermocouple/Millivolt Input 8 high resolution thermocouple/mV,fully isolated differential

Input Filtering

Input filtering limits the effect of voltage transients caused bycontact bounce and/or electrical noise. If not filtered, voltagetransients could produce false data.

Backplane circuits, module logic circuits, and the rest of the systemare protected from possible damage due to electrical transients byopto-electrical isolation.

The1771 analog output modules are intelligent block transfermodules that convert binary or four-digit BCD values (from yourprocessor) to analog signals at module outputs. The modules useblock transfer programming to accomplish data transfer. Typicaloutput devices include:

• motor speed controllers

• signal amplifiers

• valve positioners

Analog Input Modules

Analog Output Modules

Page 6: 1771 Analog Input and Output Modules

5 1771 Analog Input and Output Modules

Overview

Publication 17712.183 - May 1996

Output modules include:

Catalog Number Module TypeNumber of

OutputsType of Outputs

1771OFE1/B Analog Output 4 individually isolated voltage

1771OFE2/B Analog Output 4 individually isolated 4-20mA current

1771OFE3/B Analog Output 4 individually isolated 0-50mA current

1771-N series high resolution analog modules come in a variety ofcombinations of inputs and outputs. Input/output connections to theN-series modules are made to remote termination panels, tailored tothe type of module. The remote termination panels are thencable-connected to the actual module.

In addition, 1771-N series modules can be custom-ordered with inputand output combinations not normally offered. Consult your localAllen-Bradley district office for more information.

1771-N series modules are not covered in this publication. Refer topublication 1771-2.193, “High Resolution Isolated Analog ModulesProduct Data” for detailed information on the N-series modules.

Many products are available conformally coated. Conformal coatingsare polymeric films which cover or encapsulate printed circuitassemblies. They protect the assembly by sealing out contaminantsand humidity.

The catalog number of a conformally coated product will include thedesignation “K ” in the last position before the series identifier. Forexample, a 1771-IFE C module with conformal coating would have acatalog number of 1771-IFEK C.

All analog modules, except for the 1771-IXHR and 1771-IFMSmodules, are available conformally coated.

If this product has the CE mark it is approved for installation withinthe European Union and EEA regions. It has been designed andtested to meet the following directives.

EMC Directive

This product is tested to meet Council Directive 89/336/EECElectromagnetic Compatibility (EMC) and the following standards,in whole or in part, documented in a technical construction file:

• EN 50081-2EMC – Generic Emission Standard, Part 2 –Industrial Environment

• EN 50082-2EMC – Generic Immunity Standard, Part 2 –Industrial Environment

This product is intended for use in an industrial environment.

High Resolution NSeriesAnalog Modules

Conformal Coating

Compliance to European Union Directives

Page 7: 1771 Analog Input and Output Modules

6 1771 Analog Input and Output Modules

Overview

Publication 17712.183 - May 1996

Low Voltage Directive

This product is tested to meet Council Directive 73/23/EECLow Voltage, by applying the safety requirements of EN 61131–2Programmable Controllers, Part 2 – Equipment Requirements andTests.

For specific information required by EN 61131-2, see the appropriatesections in this publication, as well as the following Allen-Bradleypublications:

• Industrial Automation Wiring and Grounding Guidelines ForNoise Immunity, publication 1770-4.1

• Guidelines for Handling Lithium Batteries, publication AG-5.4

• Automation Systems Catalog, publication B111

Individual discrete I/O modules can also comply with various otheragency requirements when product or packaging is so marked.

Agency Certification(when product or packaging ismarked)

• CSA certified

• CSA Class I, Division 2, Groups A, B, C, D certified

• UL listed

• CE marked for all applicable directives

The following table shows you where to go in this publication for thespecifications, wiring, and application information specific to eachanalog input and output module.

CatalogNumber

Module TypeFor specifications,

refer to:

1771IFE/C Analog Input page 7

1771IFF/A Fast Analog Input page 11

1771IFMS/A Intrinsically Safe Fast Millivolt Input page 15

1771IL/C Isolated Analog Input page 17

1771IR/C RTD Input page 19

1771IXE/C Thermocouple/Millivolt Input page 21

1771IXHR/B High Resolution Thermocouple/Millivolt Input page 23

1771OFE1/B Analog Output

1771OFE2/B Analog Output page 25

1771OFE3/B Analog Output

p g

1771N series High Resolution Analog ModulesRefer to publication

17712.193

Agency Certification

Where to Look

Page 8: 1771 Analog Input and Output Modules

71771 Analog Input and Output Modules

Analog Input Module (Cat. No. 1771IFE Series C) 8 differential, or 16 singleended inputs

Publication 17712.183 - May 1996

Simplified Schematic

A/DConverter

Optoisolation +

_250Ω

Channel1 (+)Multi

plexer

MultiplexerOpto

isolation

SystemCircuitry

Channel1 (-)

1 of 8 differential channels

Control

Analog Switch

VIN-

VIN+

A/DConverter

Optoisolation +

_250Ω

Channel1Multi

plexer

Optoisolation

SystemCircuitry

1 of 16 singleended channels

Control

Analog Switch

VIN-

VIN+ Multiplexer

Ch 3Ch 5Ch 7

Ch 2Ch 4Ch 6Ch 8

Channel 1 shown

Channel 1 shown

470pF

200KΩ

470pF

200KΩ

470pF

200KΩ

Configurable Features -

• 16 singleended or 8 differential inputs

• userprogrammable selectable input ranges

• selectable realtime sampling

• selectable digital filtering

• selectable data format

• selectable scaling to engineering units

Application Notes

Wiring - Wiring to the analog input module is connected tothe 1771WG field wiring arm. The wiring arm pivots upwardand connects with the module so that you can install orremove it without disconnecting the wires. Recommendedmaximum cable length for voltage input devices is 50 feet.

Status Indicators - The front panel of the input module contains agreen RUN and a red FAULT indicator. At powerup an initial moduleselfcheck occurs. If there is no fault, the red indicator turns off. Thegreen indicator will blink until the processor completes a successfulwrite block transfer to the module.

Product Compatibility - The module is compatible with 1771A1Bthrough -A4B or later I/O chassis only. Insert the module in any slot inthe chassis except the leftmost slot, which is reserved for processorsor adapter modules.

The green indicator remains on while the module is powered. Any timea fault occurs, the red FAULT indicator lights up.

Note: Configuring the module for differential inputs does notprovide channeltochannel isolation. To prevent commonmode voltage problems, we recommend the use of commonpower supplies and careful wiring and grounding practices(refer to publication 17704.1, Industrial Automation Wiringand Grounding Guidelines for Noise Immunity"). If isolationis required, signal conditioners must be added.

Page 9: 1771 Analog Input and Output Modules

8 1771 Analog Input and Output Modules

Analog Input Module (Cat. No. 1771IFE Series C) 8 differential, or 16 singleended inputs

Publication 17712.183 - May 1996

Channel 1+

Channel 1

Channel 2+

Channel 2

Channel 3+

Channel 3

Channel 4+

Channel 4

Channel 5+

Channel 5

Channel 6+

Channel 6

Channel 7+

Channel 7

Channel 8+

Channel 8

Module Common

Common

Common

Common

Module Common

Source Ground

1771WGField Wiring Arm

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

Channel 1+

Channel 1

Channel 2+

Channel 2

Channel 3+

Channel 3

Channel 4+

Channel 4

Channel 5+

Channel 5

Channel 6+

Channel 6

Channel 7+

Channel 7

Channel 8+

Channel 8

Module Common

Common

Common

Common

Module Common

1771WGField Wiring Arm

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

+

-

2WireTransmitter

PowerSupply

+

_

2WireTransmitter

PowerSupply

The sensor cable must be shielded. The shield must:

• extend the length of the cable, but be connected only at the 1771 I/O chassis

• extend up to the point of termination

Important: The shield should extend to the termination point, exposing just enoughcable to adequately terminate the inner conductors. Use heat shrink oranother suitable insulation where the wire exits the cable jacket.

Source Ground

+

-

PowerSupply

4WireTransmitter

+

-

PowerSupply

4WireTransmitter

Connection Diagram - 8 Differential Inputs and 2wire Transmitter

Connection Diagram - 8 Differential Inputs and 4wire Transmitter

1. Unused channels must have their+ and inputs jumpered togetherand tied to module common toreduce noise.

Attention: Analog input signals must be within +14.25V referenced to modulecommon. If an input channel exceeds this range, channeltochannel crosstalkcan cause invalid input readings and invalid underrange or overrange bits.

Note:

The 1771IFE module does not supply loop power for the input device. The user mustsupply loop power for looppowered input devices.

Configuring the module for differential inputs does not provide isolation.

2. Tie power supply grounds togetherto minimize ground loops.

Note: Refer to transmitter manufacturers specifications for power supply connections.

1. Unused channels must havetheir + and inputs jumperedtogether and tied to modulecommon to reduce noise.

Attention: Analog input signals must be within +14.25V referenced to module common. Ifan input channel exceeds this range, channeltochannel crosstalk can cause invalid inputreadings and invalid underrange or overrange bits.

Note:

The 1771IFE module does not supply loop power for the input device. The user mustsupply loop power for looppowered input devices.

Configuring the module for differential inputs does not provide isolation.

2. Tie power supply grounds togetherto minimize ground loops.

The sensor cable must be shielded. The shield must:

• extend the length of the cable, but be connected only at the 1771 I/O chassis

• extend up to the point of termination

Important: The shield should extend to the termination point, exposing just enoughcable to adequately terminate the inner conductors. Use heat shrink oranother suitable insulation where the wire exits the cable jacket.

Note: Refer to transmitter manufacturers specifications for power supply connections.

Page 10: 1771 Analog Input and Output Modules

91771 Analog Input and Output Modules

Analog Input Module (Cat. No. 1771IFE Series C) 8 differential, or 16 singleended inputs

Publication 17712.183 - May 1996

Channel 1

Channel 2

Channel 3

Channel 4

Channel 5

Channel 6

Channel 7

Channel 8

Channel 9

Channel 10

Channel 11

Channel 12

Channel 13

Channel 14

Channel 15

Channel 16

Module Common

Module Common

Module Common

Module Common

Module Common

Source Ground

1771WGField Wiring Arm

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

Channel 1

Channel 2

Channel 3

Channel 4

Channel 5

Channel 6

Channel 7

Channel 8

Channel 9

Channel 10

Channel 11

Channel 12

Channel 13

Channel 14

Channel 15

Channel 16

Module Common

Module Common

Module Common

Module Common

Module Common

Source Ground

1771WGField Wiring Arm

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

Connection Diagram - 16 Singleended Inputs and 2wire Transmitter

Connection Diagram - 16 Singleended Inputs and 4wire Transmitter

1. All commons are electrically tiedtogether inside the module.

2. Jumper all unused channels tomodule common to reduce noise.

Attention: Analog input signals must be within +14.25V referenced to module common.This input signal includes any common mode voltage present between either input terminaland module common. If an input terminal exceeds this range, channeltochannel crosstalkcan cause invalid input readings and invalid underrange or overrange bits.

The 1771IFE module does not supply loop power for the input device. The usermust supply loop power for looppowered input devices.

3. Tie power supply grounds togetherto minimize ground loops.

Note: Refer to transmitter manufacturers specifications for power supply connections.

The sensor cable must be shielded. The shield must:

• extend the length of the cable, but be connected only at the 1771 I/O chassis

• extend up to the point of termination

Important: The shield should extend to the termination point, exposing just enoughcable to adequately terminate the inner conductors. Use heat shrink oranother suitable insulation where the wire exits the cable jacket.

The sensor cable must be shielded. The shield must:

• extend the length of the cable, but be connected only at the 1771 I/O chassis

• extend up to the point of termination

Important: The shield should extend to the termination point, exposing just enoughcable to adequately terminate the inner conductors. Use heat shrink oranother suitable insulation where the wire exits the cable jacket.

Attention: Analog input signals must be within +14.25V referenced to module common.This input signal includes any common mode voltage present between either input terminaland module common. If an input terminal exceeds this range, channeltochannel crosstalkcan cause invalid input readings and invalid underrange or overrange bits.

The 1771IFE module does not supply loop power for the input device. The user mustsupply loop power for looppowered input devices.

Note: Refer to transmitter manufacturers specifications for power supply connections.

+

-

2WireTransmitter

PowerSupply

+

_

2WireTransmitter

PowerSupply

+

-

PowerSupply

4WireTransmitter

+

-

PowerSupply

4WireTransmitter

Note:

Note:1. All commons are electrically tied

together inside the module.

2. Jumper all unused channels tomodule common to reduce noise.

3. Tie power supply grounds togetherto minimize ground loops.

Page 11: 1771 Analog Input and Output Modules

10 1771 Analog Input and Output Modules

Analog Input Module (Cat. No. 1771IFE Series C) 8 differential, or 16 singleended inputs

Publication 17712.183 - May 1996

Specifications (Cat. No. 1771IFE/C)

Inputs per module 16 singleended; 8 differential low level

Module location 1771 I/O chassis - 1 slot

Nominal input voltage +1 to +5V dc0 to 5V dc5 to + 5V dc10 to +10V dc0 to 10V dc

Nominal input current +4 to +20mA0 to +20mA20 to +20mA

Resolution 12bit binary,12 bits plus sign in bipolar ranges

Accuracy 0.1% of full scale range @ 25oC

Linearity +1LSB

Repeatability +1LSB

Isolation voltage Isolation meets or exceeds UL Standard508, and CSA Standard C22.2 No. 142.

Input overvoltage protection(current ranges)

200V (voltage mode)1

8V (current mode)2

Common mode voltage +14.25 Volts

Input impedance >10 megohms for voltage ranges;250 ohms for current ranges

Common mode rejection 80 db, dc120Hz

Backplane current 500mA @ +5V

Power dissipation 2.5 Watts (maximum)

Thermal dissipation 8.52 BTU/hr (maximum)

Unscaled BCD and binary outputto processor

0000 to +409510 for polar ranges (0 to 5V, +1 to +5V, 0 to +20mA, and +4 to20mA)409510 to 409510 for bipolar ranges (+5V,+10V, +20mA)

Engineering units sent toprocessor

+9999 with selectable scaling

Internal scan rate 13.7ms for 8 differential inputs (no digitalfiltering) add 0.3ms for filtering27.4ms for 16 singleended input (nodigital filtering) add 0.3ms for filtering

Specifications (Cat. No. 1771IFE/C)

Environmental conditions:Operational temperatureStorage temperatureRelative humidity

OperatingStorage

0o to 60oC (32o to 140oF)-40o to 85oC (-40o to 185oF)

5 to 95% (noncondensing)5 to 90% (noncondensing)

Conductors Wire size

Category

14 gauge (2mm2) stranded maximum3/64 inch (1.2mm) insulation maximum23

Keying Between 10 and 12Between 24 and 26

Field wiring arm Catalog number 1771WG

Wiring arm screw torque 79 inchpounds

PublicationsUser manualInstallation Instructions

Publication 17716.5.115Publication 17715.45

Agency Certification(when product or packaging ismarked)

• CSA certified

• CSA Class I, Division 2, Groups A, B,C, D certified

• UL listed

• CE marked for all applicable directives

1 The inputs are protected to 200V. However, if an input terminal's voltage exceeds+14.25 as referenced to module common,channeltochannel crosstalk can cause invalid input readings and nvalidunderrange/overrange bits.

2 Only 8 volts can be placed directly across the input when configured in the currentmode.

3 Refer to publication 17704.1, Industrial Automation Wiring and GroundingGuidelines."

RUN

FAULT

10528I

ANALOGIN

(12 BIT)

Green Run indicator

Red Fault indicator

Status Indicators

Page 12: 1771 Analog Input and Output Modules

111771 Analog Input and Output Modules

Analog Input Module (Cat. No. 1771IFF Series A) 8 differential, or 16 differential inputs

Publication 17712.183 - May 1996

Simplified Schematic

A/DConverter

Optoisolation +

_250Ω

Channel1 (+)Multi

plexer

MultiplexerOpto

isolation

SystemCircuitry

Channel1 (-)

1 of 8 differential channels

Control

Analog Switch

VIN-

VIN+

A/DConverter

Optoisolation +

_250Ω

Channel1Multi

plexer

Optoisolation

SystemCircuitry

1 of 16 singleended channels

Control

Analog Switch

VIN-

VIN+ Multiplexer

Ch 3Ch 5Ch 7

Ch 2Ch 4Ch 6Ch 8

Channel 1 shown

Channel 1 shown

470pF

200KΩ

470pF

200KΩ

470pF

200KΩ

Configurable Features -

• 16 singleended or 8 differential inputs

• userprogrammable selectable input ranges

• selectable realtime sampling

• selectable digital filtering

• selectable data format

• selectable scaling to engineering units

Application Notes

Wiring - Wiring to the analog input module is connected tothe 1771WG field wiring arm. The wiring arm pivots upwardand connects with the module so that you can install orremove it without disconnecting the wires. Recommendedmaximum cable length for voltage input devices is 50 feet.

Status Indicators - The front panel of the input module contains agreen RUN and a red FAULT indicator. At powerup an initial moduleselfcheck occurs. If there is no fault, the red indicator turns off. Thegreen indicator will blink until the processor completes a successfulwrite block transfer to the module.

Product Compatibility - The module is compatible with 1771A1Bthrough -A4B or later I/O chassis only. Insert the module in any slot inthe chassis except the leftmost slot, which is reserved for processorsor adapter modules.

The green indicator remains on while the module is powered. Any timea fault occurs, the red FAULT indicator lights up.

Note: Configuring the module for differential inputs does notprovide channeltochannel isolation. To prevent commonmode voltage problems, we recommend the use of commonpower supplies and careful wiring and grounding practices(refer to publication 17704.1, Industrial Automation Wiringand Grounding Guidelines for Noise Immunity"). If isolationis required, signal conditioners must be added.

Page 13: 1771 Analog Input and Output Modules

12 1771 Analog Input and Output Modules

Analog Input Module (Cat. No. 1771IFF Series A) 8 differential, or 16 differential inputs

Publication 17712.183 - May 1996

Channel 1+

Channel 1

Channel 2+

Channel 2

Channel 3+

Channel 3

Channel 4+

Channel 4

Channel 5+

Channel 5

Channel 6+

Channel 6

Channel 7+

Channel 7

Channel 8+

Channel 8

Module Common

Common

Common

Common

Module Common

Source Ground

1771WGField Wiring Arm

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

Channel 1+

Channel 1

Channel 2+

Channel 2

Channel 3+

Channel 3

Channel 4+

Channel 4

Channel 5+

Channel 5

Channel 6+

Channel 6

Channel 7+

Channel 7

Channel 8+

Channel 8

Module Common

Common

Common

Common

Module Common

1771WGField Wiring Arm

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

+

-

2WireTransmitter

PowerSupply

+

_

2WireTransmitter

PowerSupply

The sensor cable must be shielded. The shield must:

• extend the length of the cable, but be connected only at the 1771 I/O chassis

• extend up to the point of termination

Important: The shield should extend to the termination point, exposing just enoughcable to adequately terminate the inner conductors. Use heat shrink oranother suitable insulation where the wire exits the cable jacket.

Source Ground

+

-

PowerSupply

4WireTransmitter

+

-

PowerSupply

4WireTransmitter

Connection Diagram - 8 Differential Inputs and 2wire Transmitter

Connection Diagram - 8 Differential Inputs and 4wire Transmitter

The 1771IFF module does not supply loop power for the input device. The user mustsupply loop power for looppowered input devices.

Configuring the module for differential inputs does not provide isolation.

Note: Refer to transmitter manufacturers specifications for power supply connections.

The 1771IFF module does not supply loop power for the input device. The user mustsupply loop power for looppowered input devices.

Configuring the module for differential inputs does not provide isolation.

The sensor cable must be shielded. The shield must:

• extend the length of the cable, but be connected only at the 1771 I/O chassis

• extend up to the point of termination

Important: The shield should extend to the termination point, exposing just enoughcable to adequately terminate the inner conductors. Use heat shrink oranother suitable insulation where the wire exits the cable jacket.

Note: Refer to transmitter manufacturers specifications for power supply connections.

1. Unused channels must have their+ and inputs jumpered togetherand tied to module common toreduce noise.

Note:

2. Tie power supply grounds togetherto minimize ground loops.

1. Unused channels must have their+ and inputs jumpered togetherand tied to module common toreduce noise.

Note:

2. Tie power supply grounds togetherto minimize ground loops.

Page 14: 1771 Analog Input and Output Modules

131771 Analog Input and Output Modules

Analog Input Module (Cat. No. 1771IFF Series A) 8 differential, or 16 differential inputs

Publication 17712.183 - May 1996

Channel 1

Channel 2

Channel 3

Channel 4

Channel 5

Channel 6

Channel 7

Channel 8

Channel 9

Channel 10

Channel 11

Channel 12

Channel 13

Channel 14

Channel 15

Channel 16

Module Common

Module Common

Module Common

Module Common

Module Common

Source Ground

1771WGField Wiring Arm

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

Channel 1

Channel 2

Channel 3

Channel 4

Channel 5

Channel 6

Channel 7

Channel 8

Channel 9

Channel 10

Channel 11

Channel 12

Channel 13

Channel 14

Channel 15

Channel 16

Module Common

Module Common

Module Common

Module Common

Module Common

Source Ground

1771WGField Wiring Arm

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

Connection Diagram - 16 Singleended Inputs and 2wire Transmitter

Connection Diagram - 16 Singleended Inputs and 4wire Transmitter

The 1771IFE module does not supply loop power for the input device. The usermust supply loop power for looppowered input devices.

Note: Refer to transmitter manufacturers specifications for power supply connections.

The sensor cable must be shielded. The shield must:

• extend the length of the cable, but be connected only at the 1771 I/O chassis

• extend up to the point of termination

Important: The shield should extend to the termination point, exposing just enoughcable to adequately terminate the inner conductors. Use heat shrink oranother suitable insulation where the wire exits the cable jacket.

The sensor cable must be shielded. The shield must:

• extend the length of the cable, but be connected only at the 1771 I/O chassis

• extend up to the point of termination

Important: The shield should extend to the termination point, exposing just enoughcable to adequately terminate the inner conductors. Use heat shrink oranother suitable insulation where the wire exits the cable jacket.

The 1771IFE module does not supply loop power for the input device. The user mustsupply loop power for looppowered input devices.

Note: Refer to transmitter manufacturers specifications for power supply connections.

+

-

2WireTransmitter

PowerSupply

+

_

2WireTransmitter

PowerSupply

+

-

PowerSupply

4WireTransmitter

+

-

PowerSupply

4WireTransmitter

1. All commons are electrically tiedtogether inside the module.

2. Jumper all unused channels tomodule common to reduce noise.

3. Tie power supply grounds togetherto minimize ground loops.

Note:

1. All commons are electrically tiedtogether inside the module.

2. Jumper all unused channels tomodule common to reduce noise.

3. Tie power supply grounds togetherto minimize ground loops.

Note:

Page 15: 1771 Analog Input and Output Modules

14 1771 Analog Input and Output Modules

Analog Input Module (Cat. No. 1771IFF Series A) 8 differential, or 16 differential inputs

Publication 17712.183 - May 1996

Specifications (Cat. No. 1771IFF/A)

Inputs per module 16 singleended; 8 differential low level

Module location 1771 I/O chassis - 1 slot

Nominal input voltage +1 to +5V dc0 to 5V dc5 to + 5V dc10 to +10V dc0 to 10V dc

Nominal input current +4 to +20mA0 to +20mA20 to +20mA

Resolution 12bit binary,12 bits plus sign in bipolar ranges

Accuracy 0.1% of full scale range @ 25oC

Linearity +1LSB

Repeatability +1LSB

Isolation voltage Isolation meets or exceeds UL Standard508, and CSA Standard C22.2 No. 142.

Input overvoltage protection(current ranges)

35V (voltage mode)1

8V (current mode)2

Common mode voltage +35 Volts

Input impedance >10 megohms for voltage ranges;250 ohms for current ranges

Common mode rejection 80 db, dc120Hz

Backplane current 500mA @ +5V

Power dissipation 2.5 Watts (maximum)

Thermal dissipation 8.52 BTU/hr (maximum)

Unscaled BCD and binary outputto processor

0000 to +409510 for polar ranges (0 to 5V, +1 to +5V, 0 to +20mA, and +4 to20mA)409510 to 409510 for bipolar ranges (+5V,+10V, +20mA)

Engineering units sent toprocessor

+9999 with selectable scaling

Fastest internal scan rate 8 channels in less than 2ms (Depends onnumber of oversamples, number ofchannels, and active teatures.)

Specifications (Cat. No. 1771IFF/A)

Environmental conditions:Operational temperatureStorage temperatureRelative humidity

OperatingStorage

0o to 60oC (32o to 140oF)-40o to 85oC (-40o to 185oF)

5 to 95% (noncondensing)5 to 90% (noncondensing)

Conductors Wire size

Category

14 gauge (2mm2) stranded maximum3/64 inch (1.2mm) insulation maximum23

Keying Between 10 and 12Between 24 and 26

Field wiring arm Catalog number 1771WG

Wiring arm screw torque 79 inchpounds

PublicationsUser manualInstallation Instructions

Publication 17716.5.116Publication 17715.46

Agency Certification(when product or packaging ismarked)

• CSA certified

• CSA Class I, Division 2, Groups A, B,C, D certified

• UL listed

• CE marked for all applicable directives

1 The inputs are protected to 35V. 2 Only 8 volts can be placed directly across the input when configured in the current

mode.3 Refer to publication 17704.1, Industrial Automation Wiring and Grounding

Guidelines."

RUN

FAULT

10528I

FASTANALOG(12 BIT)

Green Run indicator

Red Fault indicator

Status Indicators

Page 16: 1771 Analog Input and Output Modules

151771 Analog Input and Output Modules

Intrisically Safe Fast Millivolt Input Module (Cat. No 1771IFMS Series A)

Publication 17712.183 - May 1996

Simplified Schematic

A/DConverter

Optoisolation +

_

1MΩ

Channel1 (+)

Multiplexer

Optoisolation

Channel1 (-)

Ch 2

Ch 3

Ch 4

VIN-

VIN+SystemCircuitry

SampleandHold

0.1µF0.39µF

1KΩ

1KΩ

1MΩ0.1µF0.39µF

To next multiplexer for channels 5 through 8

Control

DataCommon

Ch 1

Status Indicators - The front panel of the inputmodule contains a green RUN and a red FLT (fault)indicator. At powerup an initial module selfcheckoccurs. If there is no fault, the red indicator turns off. The green indicator will blink until the processorcompletes a successful write block transfer to themodule. The green indicator remains on while themodule is powered. Any time a fault is detected, thered FLT indicator lights up.

Wiring - Wiring to the analog input module connectsto the 1771WG field wiring arm. The wiring armpivots upward and connects with the module so thatyou can install or remove the module withoutdisconnecting the wiring. Recommended maximumcable length for voltage input devices is 50 feet.

Application Notes

Configurable Features - • 8 differential inputs on one card• selectable real time sampling• selectable scaling to engineering units• selectable digital filtering• 0 to 50mV input range with extended linear range above 50mV and below 0mV

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

Channel 3+Channel 3

Channel 4+

Channel 4

Common 3 and 4

Channel 5+

Channel 5

Channel 6+

Channel 6

Common 5 and 6

Channel 7+Channel 7

Channel 8+

Channel 8

Common 7 and 8

Not used

AnalogSource

AnalogSource

+

+

Unused channels must have their + and inputsjumpered together and tied to module common.

Analog signals must be within the +10V commonmode voltage range which is referenced to the analogsystem common.

NOTE:

1.

2.

Connection DiagramProduct Compatibility - The Fast Millivolt InputModule can be used with any 1771 I/O chassis. Insertthe module in any slot in the I/O chassis except for theleftmost slot which is reserved for the processor oradapter. You can put two input modules, or an inputmodule and an output module, in the same modulegroup. Do not put this module in the same modulegroup as a digital high density module unless you areusing 1 or 1/2slot addressing.

Field Wiring ArmCat. No. 1771WG

Channel 1+

Channel 1

Channel 2+

Channel 2

Common 1 and 2

Page 17: 1771 Analog Input and Output Modules

RUN

FLT

Status Indicators

Green RUN indicator

Red FLT indicator

16 1771 Analog Input and Output Modules

Intrisically Safe Fast Millivolt Input Module (Cat. No 1771IFMS Series A)

Publication 17712.183 - May 1996

Specifications (Cat. No. 1771IFMS/A)

Inputs per module 8 differential, low level

Module location 1771 I/O rack - 1 slot

Input voltage range 0 to 50mV

Resolution 12bit binary

Accuracy 0.1% of full range @ 25oC

Linearity +1 LSB

Repeatability +1 LSB

Isolation Voltage Isolation meets or exceeds UL Standard508, and CSA Standard C22.2 No. 142.

Input overvoltageprotection

32V

Maximum input voltage +10V

Input impedance 1 megohm

Common moderejection

100db dc 60Hz

BCD and unscaledoutput to processor

0000 to 409510

Engineering units sentto processor

9999 BCD with selectable scaling32767 Binary

A/D converterResolutionAbsolute accuracyQuantizing errorTemperature coefficient

monotonic output with no missing codes12-bit binary +0.1% of full scale+1/2 LSB+50ppm/oC of full scale range for 0 to 60oCambient

Internal scan rate 14.5ms for 8 differential inputs (no digitalfiltering ) - add 2.5ms for filtering, 0.25msfor BCD format

Recalibration time check calibration at 6 month intervals tomaintain specified accuracy

Backplane current 0.75A @ +5V

Power dissipation 3.75 Watts (maximum)

Thermal dissipation 12.8 BTU/hr (maximum)

Environmentalconditions

Operational temp.:Storage temperature:Relative humidity:

OperatingStorage

0o to 60oC (32o to 140oF)-40o to 85oC (-40o to 185oF)

5 to 95% (noncondensing)5 to 95% (noncondensing)

Specifications (Cat. No. 1771IFMS/A)

ConductorsWire size

Category

14 gauge (2mm2) stranded maximum3/64 inch (1.2mm) insulation maximum 21

Keying Between 20 and 22Between 28 and 30

Field wiring arm Catalog number 1771WG

Wiring arm screwtorque

79 inchpounds

Agency Certification(when product orpackaging is marked)

• CSA certified

• CSA Class I, Division 2, Groups A, B, C, D certified

• UL listed

• CE marked for all applicable directives

User manual 17716.5.571 Refer to publication 17704.1, Industrial Automation Wiring and Grounding

Guidelines."

Page 18: 1771 Analog Input and Output Modules

Status Indicators - The front panel of the input module contains agreen RUN and a red FLT (fault) indicator. At powerup an initialmodule selfcheck occurs. If there is no fault, the red indicator turnsoff. The green indicator will blink until the processor completes asuccessful write block transfer to the module. The green indicatorremains on while the module is powered. Any time a fault isdetected, the red FLT indicator lights up.

Configurable Features -

• 8 software configurable differential inputs

• user selectable input ranges

• selectable real time sampling

• selectable scaling to engineering units

• selectable digital filtering

• +1000V input isolation, channeltochannel, channeltoground

+

+

Channel 3

Channel 2

Channel 1

Channel 4

Channel 7

Channel 6

Channel 5

Channel 8

Analog Source

Analog Source

Ground

Ground

Field Wiring ArmCat. No. 1771WF

18

17

16

1

15

14

13

12

11

10

9

8

7

6

5

4

3

2

11846I

NOTE: The 1771IL/C module does not supply looppower for loop powered analog sources(transmitters, transducers, etc.). Loop powermust be supplied by the user.

Product Compatibility - This module is compatible with all 1771 I/Ochassis. Insert the module in any chassis slot except the leftmost,which is reserved for the processor or adapter module.

18

16

14

12

10

8

6

4

2

Do not useWiring - Wiring to the analog input module connects to the1771WF field wiring arm. The wiring arm pivots upward andconnects with the module so that you can install or remove themodule without disconnecting the wiring. Recommended maximumcable length for voltage input devices is 50 feet.

Application Notes Connection Diagram

171771 Analog Input and Output Modules

Isolated Input Module (Cat. No. 1771IL Series C)

Publication 17712.183 - May 1996

Simplified Schematic

A/DConverter

Optoisolation

Microprocessor

+

_+2.5V

+15V

-12V

+12V

250Ω

20MΩ

AnalogIn

AnalogReturn

1 of 8 circuits shown

1.5KΩ1KΩ

0.01µF 0.1µF

A/DConverter

Optoisolation

2 of 8 circuits,and so on

Page 19: 1771 Analog Input and Output Modules

18 1771 Analog Input and Output Modules

Isolated Input Module (Cat. No. 1771IL Series C)

Publication 17712.183 - May 1996

Specifications (Cat. No. 1771IL/C)

Inputs per module 8 fully isolated differential

Module location 1771 I/O rack 1 slot

Input voltage ranges(nominal)

+1 to +5V DC0 to 5V DC 5 to +5V DC10 to +10V DC

Input current ranges(nominal)

+4 to +20mA0 to +20mA20 to +20mA

Resolution 16bit binary over full range (+10.7V);0.33mV/bit, 1.3µA/bit

Accuracy Voltage

Current

Typical 0.01% of full scale range @ 25oCMaximum 0.05% of full scale range @ 25oCTypical 0.06% of full scale range @ 25oCMaximum 0.1% of full scale range @ 25oC (Includes 0.05% with internal current resistor)

Linearity +1 LSB

Repeatability +1 LSB

Isolation voltage Isolation meets or exceeds UL Standard 508, andCSA Standard C22.2 No. 142.

Input overvoltageprotection

voltage mode: 140V ac (rms) continuous; current mode: 8V dc continuous

Unscaled BCD and binaryoutput data to theprocessor

0000 to +409510 for unipolar ranges (0 to 5V, +1to +5V, 0 to +20mA, and +4 to +20mA)409510 to 409510 for bipolar ranges +5V, +10V,+20mA input

Input impedance >10 megohms for voltage ranges; 250 ohms forcurrent ranges

Common mode rejection >150db typical @ 60Hz and 1K ohm sourceimbalance

Common mode impedence >50 megohms shunted by <5nF

Normal mode rejection >60db @ 60Hz

Open circuit detection Voltage mode: Open input produces upscalereading.Current mode: Open input produces zeroreading.

Time to detect open circuit 10 seconds maximum

Calibration AutoInterval

Autocalibration for offset and gainVerify every 6 months to maintain absoluteaccuracy

Backplane current 1.1A @ +5V from I/O chassis backplane

Power dissipation 5.5 Watts maximum

Thermal dissipation 18.75 BTU/hr maximum

Engineering units sent toprocessor

+9999 BCD with selectable scaling; +32767binary

Internal scan rate 50ms for 8 channels

Environmental conditionsOperational temp.:Storage temperature:Relative humidity

0 to 600C (32 to 1400F) 40 to 850C (40 to 1850FOperating: 5 to 95% (noncondensing)Nonoperating: 5 to 80% (noncondensing)

Specifications (Cat. No. 1771IL/C)

Conductors Wiring

Category

14 gauge (2mm2) stranded (max.); 3/64 inch (1.2mm) insulation (max.)21

Keying between 10 and 12 and between 32 and 34

Wiring arm Catalog number 1771WF

Wiring arm screw torque 79 inchpounds

Agency Certification(when product orpackaging is marked)

• CSA certified

• CSA Class I, Division 2, Groups A, B, C, Dcertified

• UL listed

• CE marked for all applicable directives

User manual Publication 17716.5.911 Refer to publication 17704.1, Industrial Automation Wiring and Grounding Guidelines."

RUN

FLT

10528I

ISOLATEDANALOG

INPUT

Green RUN indicator

Red FLT indicator

Status Indicators

Page 20: 1771 Analog Input and Output Modules

191771 Analog Input and Output Modules

RTD Input Module (Cat. No 1771IR Series C)

Publication 17712.183 - May 1996

Filteringand

OvervoltageProtection

A/DConverter

Optoisolation

Microprocessor

+

_

= Analog Input Common

+

_

+

_

Return (C)

Excite (A)

Simplified Schematic

20KΩ

0.22µF

20KΩ

0.22µF 11.0V

11.0V

LeadCompensation

(B)

Channel 1 of 6

A/DConverter

Optoisolation

Channel 2 of 6

1mACurrentSource

18

16

14

12

10

8

6

4

2

C

B

A

C

B

A

C

B

A

C

B

A

C

B

A

C

B

A

RTD

Product Compatibility - The RTD Input Module can be usedwith any 1771 I/O chassis. Insert the module in any slot of theI/O chassis except for the leftmost slot reserved for theprocessor or adapter. You can put two input modules, or an inputmodule and an output module, in the same module group. Donot put this module in the same module group as a digital highdensity module unless you are using 1 or 1/2slot addressing.Avoid placing this module close to ac modules, or high voltagedc modules.

Status Indicators - The front panel of the input module containsa green RUN and a red FLT (fault) indicator. At powerup an initialmodule selfcheck occurs. If there is no fault, the red indicatorturns off. The green indicator will blink until the processorcompletes a successful write block transfer to the module. Thegreen indicator remains on while the module is powered. Any timea fault is detected, the red FLT indicator lights up.

Configurable Features

• 6 resistance temperature detector inputs

• reports ohms for other types of sensors

• software configurable

• autocalibration

• open wire detection

Application Notes Connection Diagram

Channel 5

Channel 4

Channel 3

Channel 2

Channel 1

Channel 6

TerminalIdentification

Ground

18

17

16

15

14

13

11

10

9

8

7

6

54

3

2

1

12

Wiring - Wiring to the analog input module connects to the1771WG field wiring arm. The wiring arm pivots upward andconnects with the module so that you can install or remove themodule without disconnecting the wiring. Recommended maximumcable length for voltage input devices is 50 feet.

Field Wiring ArmCat. No. 1771WG

Page 21: 1771 Analog Input and Output Modules

20 1771 Analog Input and Output Modules

RTD Input Module (Cat. No 1771IR Series C)

Publication 17712.183 - May 1996

Specifications (Cat. No. 1771IR/C)

Module capacity 6 RTD Input Channels

Module location 1771 I/O Chassis

Sensor type 100 ohm platinum (alpha = 0.00385) or 10 ohm copper (alpha = 0.00386)Other types may be used with report inohms only

Units of measure Temperature in oCTemperature in oFRTD resistance in ohms (10 milliohms or30 milliohms resolution)

Temperature range Platinum: -200 to +870oC (-328 to+1598oF)Copper: -200 to +260oC (-328 to +500oF)

Resistance range 1.00 to 600.00 ohms

Resolution Platinum: 0.1oC (0.1oF)Copper: 0.3oC (0.5oF)

Sensor excitation 1mA constant current source supplied bymodule

Isolation Voltage Isolation meets or exceeds UL Standard508, and CSA Standard C22.2 No. 142.

Common mode rejection 120db @ 60Hz, up to 1000V peak

Common mode impedance Greater than 10 megohms

Normal mode rejection 60dB at 60Hz

Input overvoltage protection 120V rms, continuous

Open RTD response time Open excitation (terminal A ) overerrange:<0.5sOpen Common (terminal C) to underrange:<0.5sOpen Sense (terminal B ): drift high

Scan time 50ms for all 6 channels

Specifications (Cat. No. 1771IR/C)

Backplane current 950mA maximum

Power dissipation 4.75 Watts

Thermal dissipation 16.2 BTU/hr

Environmental conditionsOperational temperature:Rate of change:

Storage temperature:Relative humidity:

OperatingStorage

0o to 60oC (32o to 140oF)Ambient changes greater than 01.0oC perminute may temporarily degradeperformance during periods of change.-40o to 85oC (-40o to 185oF)

5 to 95% (noncondensing)5 to 95% (noncondensing)

Keying Between 10 and 12Between 28 and 30

Field wiring arm Catalog number 1771WF

Field wiring arm screw torque 79 inchpounds

Agency Certification(when product or packaging ismarked)

• CSA certified

• CSA Class I, Division 2, Groups A, B, C,D certified

• UL listed

• CE marked for all applicable directives

User manual Publication 17716.5.761 Refer to publication 17704.1, Industrial Automation Wiring and Grounding Guidelines."

RTD Type Range Error @ Calibration Temperature (25oC) (over range) Drift oC/oC or oF/oF

Copper -200 to +260oC (-328 to +500oF) +0.344oC/+0.564oF +0.1306

Platinum -200 to +870oC (-328 to 1598oF) +0.100oC/+0.152oF +0.0717

RTD Type Resistance Error @ 25oC (over range) Resistance Drift Ohm/oC

Copper +0.074 ohm +0.0213

Platinum +0.075 ohm +0.0213

RUN

FLT

ANALOGIN

(12 BIT)

Red FLT indicator

Green RUN indicator

Status Indicators

Page 22: 1771 Analog Input and Output Modules

211771 Analog Input and Output Modules

Thermocouple/Millivolt Input (Cat. No.1771IXE Series C)

Publication 17712.183 - May 1996

Simplified Schematic Filtering and OvervoltageProtection

A/DConverter

Optoisolation

Systemlogic +

_

+15V

Analog Input+105mV

= Analog Input Common

0.22µF

>30MΩ

50Ω

20KΩ

A/DConverter

Optoisolation

Input 2 of 8

Input 1 of 8

+

+–

Do not use

Short circuitunused pins

Channel 1

Channel 2

18 Input 1 (+ lead)

17 Input 1 (- lead)

16 Input 2 (+ lead)

15 Input 2 (- lead)

14 Input 3 (+ lead)

13 Input 3 (- lead)

12 Input 4 (+ lead)

11 Input 4 (- lead)

10 Not Used

9 Not used

8 Input 5 (+ lead)

7 Input 5 (- lead)

6 Input 6 (+ lead)

5 Input 6 (- lead)

4 Input 7 (+ lead)

3 Input 7 (- lead)

2 Input 8 (+ lead)

1 Input 8 (- lead)

Terminal Identification

Terminal Function

Field Wiring ArmCat. No. 1771-WI

• Ground cable shield to I/O chassis mounting bolt.

10527-I

• Connect positive thermocoupleleads to evennumbered terminals,negative leads to oddnumbered terminals.

Product Compatibility - The module is compatible with all1771-A1B through A4B or later I/O chassis. Insert the module inany slot in the chassis except the leftmost slot, which is reserved fora processor or adapter module.

Status Indicators - The front panel of the input module contains agreen RUN and a red FLT (fault) indicator. At powerup the red andgreen indicators are on. If there is no fault, the red indicator turns off.The green indicator will blink until the processor completes asuccessful write block transfer to the module. Any time a fault isdetected, the red FLT indicator lights up.

Configurable Features -

• 8 input channels configurable for thermocouple inputranges or millivolt: Types E,J,K,T,R and Sthermocouples and +100 millivolts (full range is +105mV)

• two types of inputs allowed at the same time: 4 of one type and 4 of another

• cold junction compensation

• user selectable high and low temperature alarms

Application Notes Connection Diagram

18

16

14

12

10

8

6

4

2

Wiring - Wiring to the analog input module is connected to the1771WI field wiring arm. The wiring arm pivots upward andconnects with the module so that you can install or remove themodule without disconnecting the wiring. Recommended maximumcable length for voltage input devices is 50 feet.

Page 23: 1771 Analog Input and Output Modules

22 1771 Analog Input and Output Modules

Thermocouple/Millivolt Input (Cat. No.1771IXE Series C)

Publication 17712.183 - May 1996

Specifications (Cat. No. 1771IXE/C)

Number of inputs 8, all of the same type, or 4 each of 2 different types

I/O chassis location Any single I/O module slot

Type of input Type E, chromel/constantan (-270 to 1000oC)Type J, iron/constantan (-210 to 1200oC)Type K, chromel/alumel (-270 to 1380oC)Type R, Pt/Pt13% Rh (-50 to 1770oC)Type S, Pt/Pt10% Rh (-50 to 1770oC)Type T, copper/constantan (-270 to 400oC)Millivolt (-105 to =105mV dc)

Thermocouplelinearization

IPTSstandard, NBS MN125

Cold junctioncompensation

Range: 0 to 60oCAccuracy: + 0.5oC

Temperature scale(selectable)

oC or oF

Input resolution 1oC, 1oF, or 10uV

Common mode rejection 120db @ 60Hz, up to 1000V peak

Common modeimpedance

Greater than 10 megohms

Normal mode rejection 60dB at 60Hz

Input overvoltageprotection

120V rms, continuous

Open input detection Open input produces maximum value reading inless than 10s

Isolation voltage Isolation meets or exceeds UL Standard 508, and CSA Standard C22.2 No. 142.

Backplane current 850mA @ 5V

Power dissipation 4.25 Watts (maximum)

Thermal dissipation 14.5 BTU/hr (maximum)

Data format (selectable) 4digit BCD2's compliment binarysigned magnitude binary

CalibrationAutoManual

Check

Autocalibration for offset and gainZero, offset and gain adjustment for each channelvia programming terminalVerify every six months for maintaining absoluteaccuracy

Specifications (Cat. No. 1771IXE/C)

Environmentalconditions

Operating temp.:Rate of change:

Storage temp.:Relative humidity:

OperatingStorage

0o to 60oC (32o to 140oF)Ambient changes greater than 0.5oC per minutemay temporarily degrade performance duringperiods of change-40o to 85oC (-40o to 185oF)

5 to 95% (noncondensing)5 to 95% (noncondensing)

Processor compatibility Any AB processor using 1771 I/O structure blocktransfer

Keying Between 20 and 22Between 24 and 26

Field wiring arm Catalog number 1771WI

Wiring arm screw torque 79 inchpounds

Agency Certification(when product orpackaging is marked)

• CSA certified

• CSA Class I, Division 2, Groups A, B, C, Dcertified

• UL listed

• CE marked for all applicable directives

User manual Publication 17716.5.771 Refer to publication 17704.1, Industrial Automation Wiring and Grounding Guidelines."

RUN

FLT

10528I

ANALOGIN

(12 BIT)

Green RUN indicator

Red FLT indicator

Status Indicators

Page 24: 1771 Analog Input and Output Modules

231771 Analog Input and Output Modules

High Resolution Thermocouple/Millivolt Input (Cat. No. 1771IXHR)

Publication 17712.183 - May 1996

Simplified Schematic Filtering and OvervoltageProtection

A/DConverter

Optoisolation

Systemlogic +

_

+15V

Analog Input+105mV

= Analog Input Common

0.22µF

>30MΩ

50Ω

20KΩ

A/DConverter

Optoisolation

Input 2 of 8

Input 1 of 8

+

+

Do not use

Short circuitunused pins

Channel 1

Channel 2

18 Input 1 (+ lead)

17 Input 1 (- lead)

16 Input 2 (+ lead)

15 Input 2 (- lead)

14 Input 3 (+ lead)

13 Input 3 (- lead)

12 Input 4 (+ lead)

11 Input 4 (- lead)

10 Not Used

9 Not used

8 Input 5 (+ lead)

7 Input 5 (- lead)

6 Input 6 (+ lead)

5 Input 6 (- lead)

4 Input 7 (+ lead)

3 Input 7 (- lead)

2 Input 8 (+ lead)

1 Input 8 (- lead)

Field Wiring ArmCat. No. 1771-WI

• Ground cable shield to I/O chassis mounting bolt.

10527-I

• Connect positive thermocoupleleads to evennumbered terminals,negative leads to oddnumbered terminals.

Product Compatibility - The module is compatible with1771A1B through A4B or later I/O chassis. Insert themodule in any slot in the chassis except the leftmost slot,which is reserved for the processor or adapter module.

Status Indicators - The front panel of the input modulecontains a green RUN and a red FLT (fault) indicator. Atpowerup the red and green indicators are on. If there is nofault, the red indicator turns off. The green indicator will blinkuntil the processor completes a successful write blocktransfer to the module. Any time a fault is detected, the redFLT indicator lights up.

Wiring - Wiring to the analog input module is connected tothe 1771WI field wiring arm. The wiring arm pivots upwardand connects with the module so that you can install orremove the module without disconnecting the wiring.Recommended maximum cable length for voltage inputdevices is 50 feet.

Configurable Features

• 8 input channels configurable for thermocouple inputranges (Types B, E, J, K, T, R and S thermocouples)and +100 millivolts (full range is +105V)

• two types of input allowed at one time: 4 of one typeand 4 of another

• cold junction compensation• user selectable high and low temperature alarms

Application Notes Connection Diagram

18

16

14

12

10

8

6

4

2

Page 25: 1771 Analog Input and Output Modules

24 1771 Analog Input and Output Modules Product Data

High Resolution Thermocouple/Millivolt Input (Cat. No. 1771IXHR)

Publication 17712.183 - May 1996

Specifications (Cat. No. 1771IXHR)

Number of inputs 8, all of the same type or 4 each of 2 different types

I/O chassis location Any single I/O module slot

Type of input See table below.

Thermocouplelinearization

IPTSstandard, NBS MN125

Cold junctioncompensation

Range: 0 to 60oCAccuracy: + 0.5oC

Temperature scaleselectable

oC or oF

Input resolution 3.2328µV

Display resolution 0.1oC, 0.1oF, or 1.0µV, 10µV

Input isolation Isolation meets or exceeds UL Standard 508, and CSA Standard C22.2 No. 142.

Common mode rejection 120db @ 60Hz, up to 1000V peak

Common modeimpedance

Greater than 10 megohms

Normal mode rejection 60dB at 60Hz

Input overvoltageprotection

120V rms, continuous

Open input detection Open input produces an overrange in less than 10s

Data format 2's complement binary

Backplane current 850mA @ 5V

Thermal dissipation 4.255 Watts (maximum)

Power dissipation 14.5 BTU/hr (maximum)

CalibrationAutoManual

Check

Autocalibration for offset and gainZero offset and gain adjustment for each channelvia programming terminalVerify every six months to maintain absoluteaccuracy

Specifications (Cat. No. 1771IXHR)

Environmentalconditions:

Operational temp.Rate of change:

Storage temp.:Relative humidity:

OperatingStorage

0o to 60oC (32o to 140oF)Ambient changes greater than 0.5oC per minutemay temporarily degrade performance duringperiods of change-40o to 85oC (-40o to 185oF)

5 to 95% (noncondensing) 5 to 95% (noncondensing)

Keying Between 20 and 22Between 24 and 26

Field wiring arm Catalog number 1771WI

Wiring arm screw torque 79 inchpounds

Processor compatibility PLC3 or PLC5 family processor using the 1771I/Ostructure and block transfer. (Not recommended foruse with the PLC2 family processors.)

Agency Certification(when product orpackaging is marked)

• CSA certified

• CSA Class I, Division 2, Groups A, B, C, Dcertified

• UL listed

• CE marked for all applicable directives

User manual 17716.5.801 Refer to publication 17704.1, Industrial Automation Wiring and Grounding Guidelines."

RUN

FLT

10528I

ANALOGIN

(12 BIT)

Green RUN indicator

Red FLT indicator

Status Indicators

Types of Inputs for the 1771IXHR Module

Input Type Type B, Pt 30% Rh/Pt6% Rh (320 to 1800oC)Type E, chromel/constantan (-270 to 1000oC)Type J, iron/constantan (-210 to 1200oC)Type K, chromel/alumel (-270 to 1380oC)Type R, Pt/Pt13% Rh (-50 to 1770oC)Type S, Pt/Pt10% Rh (-50 to 1770oC)Type T, copper/constantan (-270 to 400oC)Millivolt (-105 to +105mV dc)

Page 26: 1771 Analog Input and Output Modules

251771 Analog Input and Output Modules

Analog Output Module (Cat. No. 1771OFE1, OFE2 and OFE3, Series B)

Publication 17712.183 - May 1996

Simplified Schematic

+

_

+

_D/A

ConverterSystemCircuitry

Optoisolation

10V

+15V

5KΩ

25KΩ

12.5KΩ

287ΩV+

V-

15V

10V

287Ω

12.5KΩ25KΩ

12.5KΩ

J9

J10

J5

J8

J6

J7

OutputRanges+10V010V1-5V

Voltage Output

+

_D/A

ConverterSystemCircuitry

Optoisolation

V+

V-

4.7KΩ

2.4KΩ

40KΩ

Current Output

+

_

+

_

15V

10V

+15V

150Ω

10KΩ

Output

Ranges420mA050mA

(60Ω for OFE3)

(omit forOFE3)

0.047µF

10V MOV

0.0047µF

D/AConverter

Optoisolation

D/AConverter

Optoisolation

Channel 1 shown

Channel 1 shown

Channel 2 of 4, etc.

Channel 2 of 4, etc.

Status Indicators - The front panel of the input module contains agreen RUN and a red FLT (fault) indicator. At powerup an initialmodule selfcheck occurs. If there is no fault, the red indicator turnsoff and the green indicator turn on. The green indicator remains onwhile the module is powered. Any time a fault occurs, the red FLTindicator lights up.

Wiring - Wiring to the analog input module connects to the 1771WCfield wiring arm. The wiring arm pivots upward and connects with themodule so that you can install or remove it without disconnecting thewires. Recommended maximum cable length for voltage input devicesis 50 feet.

Configurable Features -

• 4 individually isolated differential outputs• selectable scaling to engineering units• selectable data formats• selectable voltage ranges (1771OFE1 only)• requires only one I/O slot

A

0

1

2

3

4

5

6

7

B

Channel 1 (+)

Channel 1 ()

Channel 2 (+)

Channel 2 ()

Channel 3 (+)

Channel 3 ()

Channel 4 (+)

Channel 4 ()

Not used

Not used

Ground

Field Wiring ArmCat. No 1771WC

UserAnalogDevice

Application Notes Connection DiagramProduct Compatibility - The analog output module can be usedwith any 1771 I/O chassis. Insert the module in any slot of the I/Ochassis except for the leftmost slot reserved for the processor oradapter. You can put two input modules, or an input module and anoutput module, in the same module group. Do not put this modulein the same module group as a discrete high density module unlessyou are using 1 or 1/2slot addressing. Avoid placing this moduleclose to ac modules, or high voltage dc modules.

Page 27: 1771 Analog Input and Output Modules

26 1771 Analog Input and Output Modules

Analog Output Module (Cat. No. 1771OFE1, OFE2 and OFE3, Series B)

Publication 17712.183 - May 1996

Specifications (Cat. No. 1771OFE1,2,3)

Outputs per module 4 individually isolated

Module location Bulletin 1771 I/O chassis - 1 slot

Output voltage ranges(nominal) - 1771OFE1 only

+1 to +5V dc-10 to +10V dc0 to +10V dc

Output current (maximum)- 1771OFE1 only

10mA per channel in voltage mode(1771-OFE1)

Output current ranges(nominal)

+4 to +20mA (1771-OFE2)0 to +50mA (1771-OFE3)

Digital resolution 12Bit Binary - 1 part in 4095

Output capacitance 0.01µF (voltage outputs)0.022µF (current outputs)

Output impedance <0.25 ohms for voltage outputs exclusive ofcontact wiring resistance >1.5 megohms for current outputs

Maximum loop impedancein the current mode

1771OFE2 - Up to 1200 ohms load resistance1771OFE3 - Up to 450 ohms load resistance

Output overload protection All outputs are protected against short circuitload conditions not to exceed one minute.

Backplane power 1771OFE1 1.50A1771OFE2 1.50A1771OFE3 2.50A

Power dissipation 1771OFE1 7.9W1771OFE2 7.9W1771OFE3 13.1W

Thermal dissipation 1771OFE1 26.9 BTU/hr1771OFE2 26.9 BTU/hr1771OFE3 44.5 BTU/hr

Isolation voltage Isolation meets or exceeds UL Standard 508, and CSA Standard C22.2 No. 142.

D/A converter settling time 0.8ms maximum for a resistive load

Internal scan rate 8.0ms for all channels using BCD data, scaling 1.6ms for all channels using binary data, noscaling

Accuracy (includinglinearity, gain, and offset at25oC)

+0.1% of full scale+1/2 LSD (BCD Mode)+1/2 LSB (BINARY Mode)

Temperature coefficient +50 ppm/oC of full scale range

Specifications (Cat. No. 1771OFE1,2,3)

Environmental conditionsOperational temp.:Storage temp.: Relative himidity:

OperatingStorage

0oC to +60oC (+32oF to +140oF) -40oC to +85oC (-40oF to +185oF)

5% to 95% (noncondensing)5% to 95% (noncondensing)

Field wiring arm Catalog number 1771WC

Field wiring arm screwtorque

79 inchpounds

Agency Certification(when product orpackaging is marked)

• CSA certified

• CSA Class I, Division 2, Groups A, B,C, D certified

• UL listed

• CE marked for all applicable directives

PublicationsUser manualInstallation Instruction

Publication 17716.5.30Publication 17715.44

1 Refer to publication 17704.1, Industrial Automation Wiring and GroundingGuidelines."

R U N

FLT

Status Indicators

Green RUN indicator

Red Fault Indicator

10 20 30 40 50 60

35

Ambient Temperature (oC)

Ou

tpu

t C

urr

ent

(mA

)

10

20

30

40

50

0Ω load

150-450Ω load100Ω load50Ω load

40o 47o 53o

1771OFE3 Loop Impedance vs. Temperature

Page 28: 1771 Analog Input and Output Modules

271771 Analog Input and Output Modules Product Data

Support Services

Publication 17712.183 - May 1996

At Allen-Bradley, customer service means experiencedrepresentatives at Customer Support Centers in key cities throughout the world for sales service and support. Our value-addedservices include:

Technical Support

• SupportPlus programs

• telephone support and 24-hour emergency hotline

• software and documentation updates

• technical subscription services

Engineering and Field Services

• application engineering assistance

• integration and start-up assistance

• field service

• maintenance support

Technical Training

• lecture and lab courses

• self-paced computer and video-based training

• job aids and workstations

• training needs analysis

Repair and Exchange Services

• your only “authorized” source

• current revisions and enhancements

• worldwide exchange inventory

• local support

Support Services

Page 29: 1771 Analog Input and Output Modules

AllenBradley, a Rockwell Automation Business, has been helping its customers improveproductivity and quality for more than 90 years. We design, manufacture and support a broadrange of automation products worldwide. They include logic processors, power and motioncontrol devices, operator interfaces, sensors and a variety of software. Rockwell is one of theworld's leading technology companies.

Worldwide representation.

Argentina • Australia • Austria • Bahrain • Belgium • Brazil • Bulgaria • Canada • Chile • China, PRC • Colombia • Costa Rica • Croatia • Cyprus • Czech Republic •Denmark • Ecuador • Egypt • El Salvador • Finland • France • Germany • Greece • Guatemala • Honduras • Hong Kong • Hungary • Iceland • India • Indonesia •

Ireland • Israel • Italy • Jamaica • Japan • Jordan • Korea • Kuwait • Lebanon • Malaysia • Mexico • Netherlands • New Zealand • Norway • Pakistan • Peru •Philippines • Poland • Portugal • Puerto Rico • Qatar • Romania • Russia-CIS • Saudi Arabia • Singapore • Slovakia • Slovenia • South Africa, Republic • Spain •Sweden • Switzerland • Taiwan • Thailand • Turkey • United Arab Emirates • United Kingdom • United States • Uruguay • Venezuela • Yugoslavia

AllenBradley Headquarters, 1201 South Second Street, Milwaukee, WI 53204 USA, Tel: (1) 414 3822000 Fax: (1) 414 3824444

Publication 17712.183 - May 1996Copyright 1996 AllenBradley Company, Inc. Printed in USA