1.OPEN CIRCUIT AND SHORT CIRCUIT TEST OF TRANSFORMER AIM:- To conduct open circuit and short circuit test in given transformer. Predetermine the following 1. Efficiencies at various loads and power factors 2. Regulation at various power factor and loads MACHINE DETAILS :- METERIALS REQUIRED :- 1. Ammeter (0-2.5A) MI 1NO 2. Ammeter (0-15A)MI 1NO 3. Volt meter (0-250v) 1no 4. Voltmeter (0-50v) MI 1NO 5. Wattmeter (150V,5A,LPF) 1NO 6. Wattmeter (150V,15A,UPF) 1NO THEORY:- The purpose of the OC test to determine the no load loss (core loss) at rated voltage and frequency. Shunt branch parameters of equalent circuit r0&x0 and the no load current of the transformer on winding of the transformer. In the open circuit test the primary load current is very small(2.6% of rated current )copper loss is negligibly small in the primary and is nil in the secondary is opened. The equalent circuit parameters r0&xo referred to LV side can be calculated from the test result. The no load power loss, Pi=V0*I0*COS φ0 COSφ0=Pi/V0*I0 Magnetising component of I 0 =I m =I 0 SIN φ 0 Energy component of I 0 =Ie=I 0 COS φ 0 The noload resistance R 0 =V 0 /I e and the no load reactance X 0 = V 0 /I m These values can be transferred to hv side as R 0 =R 0 (V 2 /V 1 ) 2 and X 0 =X 0 (V 2 /V 1 ) 2 SC Test is to conduct for determining the full load copper loss and the equalent resistance and resistance of the transformer as refferd to the metering side. In this test one winding usually LV side is solidly short circuited and a low voltage (2-12% of primary voltage ) is applied to the HV side such that rated current flows through the winding since applied voltage is very low ,iron losses are very small and may be neglected. Hence the wattmeter shows the full load copper loss

1.OPEN CIRCUIT AND SHORT CIRCUIT TEST OF … lab1.pdf · 1.OPEN CIRCUIT AND SHORT CIRCUIT TEST OF TRANSFORMER AIM:- To conduct open circuit and short circuit test in given transformer

  • Upload
    trandan

  • View
    277

  • Download
    3

Embed Size (px)

Citation preview

Page 1: 1.OPEN CIRCUIT AND SHORT CIRCUIT TEST OF … lab1.pdf · 1.OPEN CIRCUIT AND SHORT CIRCUIT TEST OF TRANSFORMER AIM:- To conduct open circuit and short circuit test in given transformer

1.OPEN CIRCUIT AND SHORT CIRCUIT TEST OF TRANSFORMER

AIM:-

To conduct open circuit and short circuit test in given transformer. Predetermine the

following

1. Efficiencies at various loads and power factors

2. Regulation at various power factor and loads

MACHINE DETAILS:-

METERIALS REQUIRED:-

1. Ammeter (0-2.5A) MI 1NO

2. Ammeter (0-15A)MI 1NO

3. Volt meter (0-250v) 1no

4. Voltmeter (0-50v) MI 1NO

5. Wattmeter (150V,5A,LPF) 1NO

6. Wattmeter (150V,15A,UPF) 1NO

THEORY:-

The purpose of the OC test to determine the no load loss (core loss) at rated voltage and

frequency. Shunt branch parameters of equalent circuit r0&x0 and the no load current of the

transformer on winding of the transformer. In the open circuit test the primary load current is very

small(2.6% of rated current )copper loss is negligibly small in the primary and is nil in the

secondary is opened. The equalent circuit parameters r0&xo referred to LV side can be calculated

from the test result.

The no load power loss, Pi=V0*I0*COS φ0

COSφ0=Pi/V0*I0

Magnetising component of I0 =Im=I0SIN φ0

Energy component of I0=Ie=I0COS φ0

The noload resistance R0=V0/Ie and the no load reactance X0= V0/Im

These values can be transferred to hv side as R0’=R0(V2/V1)

2 and X0’=X0(V2/V1)

2

SC Test is to conduct for determining the full load copper loss and the equalent resistance and

resistance of the transformer as refferd to the metering side. In this test one winding usually LV

side is solidly short circuited and a low voltage (2-12% of primary voltage ) is applied to the HV

side such that rated current flows through the winding since applied voltage is very low ,iron

losses are very small and may be neglected. Hence the wattmeter shows the full load copper loss

Page 2: 1.OPEN CIRCUIT AND SHORT CIRCUIT TEST OF … lab1.pdf · 1.OPEN CIRCUIT AND SHORT CIRCUIT TEST OF TRANSFORMER AIM:- To conduct open circuit and short circuit test in given transformer

Pcu for the bwhole transformer. If VSC is the voltage required to circulate the rated current I2(KVA X

1000/V1) Then the equavalent circuit parameters can be found as Z02=VSC/I2 and R02=PCu

Then X02= 𝒁𝟎𝟐𝟐 + 𝑹𝟎𝟐 These parameters can be transferred to the LV side as

R2’=R2(V2/V1)

2 and X2’=X2(V2/V1)

2 secondary side R02 and X02 the regulation at any PF and loading

factor(x) can be predetermind as regulation= XI2(R02 COS φ0+- X02 SIN φ0)/V2 Where (+) for lagging

and(-) for leading power factors) from the full load copper loss and iron loss the efficiency at any

loading factor and pf can be pre determind as

Efficiency= 𝑿𝟏𝟎𝟎𝟎𝑲𝑽𝑨𝑿.𝑷𝑭

𝑿𝟏𝟎𝟎𝟎𝑲𝑽𝑨𝑿𝑷𝑭+𝑿𝟐𝑷𝒄𝒖+𝑷𝒊

Page 3: 1.OPEN CIRCUIT AND SHORT CIRCUIT TEST OF … lab1.pdf · 1.OPEN CIRCUIT AND SHORT CIRCUIT TEST OF TRANSFORMER AIM:- To conduct open circuit and short circuit test in given transformer

PROCEDURE:-

OC TEST

1. Collect the materials for the given work.

2. Connection are done as shown in connection diagram.

3. Keep auto transformer at zero position.

4. Adjust the auto transformer up to rated voltage.

5. Take voltmeter, ammeter and wattmeter reading.

PROCEDURE:-

SC TEST

1. Collect the materials for the given work.

2. Connection are done as shown in connection diagram.

3. Keep auto transformer at zero position.

4. Adjust the auto transformer up to rated current

Page 4: 1.OPEN CIRCUIT AND SHORT CIRCUIT TEST OF … lab1.pdf · 1.OPEN CIRCUIT AND SHORT CIRCUIT TEST OF TRANSFORMER AIM:- To conduct open circuit and short circuit test in given transformer

5.Take voltmeter, ammeter and wattmeter reading.

𝑽𝑶𝑪

𝑰𝑶𝑪

𝑾𝑶𝑪

𝑽𝑺𝑪

𝑰𝑺𝑪

𝑾𝑺𝑪

MODEL CALCULATION

OC TEST

𝑽𝑶𝑪=

𝑰𝑶𝑪=

𝑾𝑶𝑪=

𝑾𝑶𝑪==𝑽𝑶𝑪 𝑰𝑶𝑪 𝑪𝑶𝑺∅𝟎

∅𝟎=𝒄𝒐𝒔−𝟏(𝑾𝑶𝑪

𝑽𝑶𝑪 𝑰𝑶𝑪)

Wattles component 𝒊𝒘 = 𝒊𝟎𝒄𝒐𝒔∅𝟎

Magnetizing component 𝒊µ = 𝒊𝟎𝒔𝒊𝒏∅𝟎

𝑹𝟎=𝑽𝑶𝑪

𝑰𝑾

𝑿𝟎=𝑽𝑶𝑪

𝑰µ

These values can be transferred to hv side

R0’=R0 x K2 X0

’=X0 x K2

SC TEST

Page 5: 1.OPEN CIRCUIT AND SHORT CIRCUIT TEST OF … lab1.pdf · 1.OPEN CIRCUIT AND SHORT CIRCUIT TEST OF TRANSFORMER AIM:- To conduct open circuit and short circuit test in given transformer

𝑽𝑺𝑪=

𝑰𝑺𝑪=

𝑾𝑺𝑪=

Zsc=Vsc/Isc

𝑹𝒔𝒄 = 𝑽𝒔𝒄/𝑰𝒔𝒄𝟐

Xsc= (𝒁𝒔𝒄²− 𝑹𝒔𝒄²)

Z02=Vsc/ISC

R02=PCU/ISC2

X02= 𝒁𝟎𝟐𝟐 + 𝑹𝟎𝟐

These values can be transferred in to LV

R01=R02/K2

X01=X02/K2

Page 6: 1.OPEN CIRCUIT AND SHORT CIRCUIT TEST OF … lab1.pdf · 1.OPEN CIRCUIT AND SHORT CIRCUIT TEST OF TRANSFORMER AIM:- To conduct open circuit and short circuit test in given transformer

TO DRAW EFFICIENCY CURVE FOR A GIVEN P.F

Out put at X times F.L=X(rated KVA x 1000) cos∅

Core loss Wi= W0

Copper loss Wcs= X²Wsc

Efficiency=(Output /output+losses) x100.

KVA Curresponding to maximum efficiency=KVArated X 𝑪𝒐𝒓𝒆 𝒍𝒐𝒔𝒔

𝑪𝒐𝒑𝒑𝒆𝒓 𝒍𝒐𝒔𝒔 then find efficiency as usual.

Page 7: 1.OPEN CIRCUIT AND SHORT CIRCUIT TEST OF … lab1.pdf · 1.OPEN CIRCUIT AND SHORT CIRCUIT TEST OF TRANSFORMER AIM:- To conduct open circuit and short circuit test in given transformer

Sl no Load Output(Watt) Wi(watt) Wcx(watt) Input %efficiency

TO DRAW REGULATION V/S PF CURVE

% regulation at F.L for a given P.F= 𝑰𝒓𝒂𝒕𝒆𝒅(𝑹𝟎𝟐𝒄𝒐𝒔∅±𝑿𝟎𝟐𝒔𝒊𝒏∅

𝑽𝟐

Sl No cos∅ sin∅ % Regulation

Procedure:-

OC Test

1. Make connection as per the circuit diagram

2. Keep the autotransformer in minimum position

3. Adjust the auto transformer upto rated voltage of the transformer

4. Take the meter readings and tabulate the readings

5. Finish the work

SC Test

1. Make connection as per the circuit diagram

2. Keep the autotransformer in minimum position

3. Adjust the auto transformer upto rated current of the transformer

4. Take the meter readings and tabulate the readings

5. Finish the work

RESULT:-Conducted the OC and SC test on the given single phase transformer and predetrermine

the following

1. Efficiencies at various loads and power factors

2. Regulation at various loads and power factors

3. Equavalent circuit reffered to hv and lv side

4. Maximum efficiencies at unity PF=

5. Maximum efficiencies at 0.8PF=

Page 8: 1.OPEN CIRCUIT AND SHORT CIRCUIT TEST OF … lab1.pdf · 1.OPEN CIRCUIT AND SHORT CIRCUIT TEST OF TRANSFORMER AIM:- To conduct open circuit and short circuit test in given transformer

2.LOAD TEST ON SINGLE PHASE TRANSFORMER

AIM:-

To conduct a no load test on given SINGLE PHASE TRANSFORMER and determine the

regulation for defferent load.

MACHINE DETAILS:-

METERIALS REQUIRED:-

1. Ammeter (0-15A) MI 1NO

2. Voltmeter (0-150v) MI 1NO

3. Wattmeter (300v,15A,upf) 1NO

4. Ammeter (0-5A) MI 1NO

5. Voltmeter (0-250v) MI 1NO

6. Wattmeter (300v,30A,upf) 1NO

THEORY:-

In this test the efficiencies and regulation are detrermind by direct loading of the given single

phase transformer . this test is very often carried out in practice excepting for small sizes ,owing to

the difficulty of obtaining a suitable load and the loss of power involved.

When ever a transformer is loaded its secondary terminal voltage changes with increased load ,if

the supplied primary voltage is held constent.the change in secondary voltage from no load to full

load expressed ias percentage of no load voltage is known a voltage is known as voltage regulatin

of a transformer (ie, secondary voltage at noload –secondary voltage at full load) 𝑬𝟐−𝑽𝟐

𝑬𝟐 (the

secondary rated voltage of a transformer is equal to the secondary voltage at no load,ie,E2

The efficienciy of a transformer is defaind as the ratio of output power to input power,thus

efficeiency=output power/input power

In this experiment input power is measured directly from the wattmeter connected in the primary

side and output power is obtained by multiplying the volt meter reading and ammeter reading in

the secondary side.

Page 9: 1.OPEN CIRCUIT AND SHORT CIRCUIT TEST OF … lab1.pdf · 1.OPEN CIRCUIT AND SHORT CIRCUIT TEST OF TRANSFORMER AIM:- To conduct open circuit and short circuit test in given transformer

PROCEDURE:-

1. Connect the circuit diagram as per the circuit diagram

2. Adjust the autotransformer till the voltmeter reads rated voltage.

3. Note the no load readings and enter them as first set of readings in tabular column.

4. Load the transformer gradually and take all meter readings each time till the secondary

current reaches rated value.

5. Tabulate the readings. And finish the work

TABULATION

Sl No

I1 in Amps

V1 in volts

W in watts

I2 in Amps

V2 in volts

Input in watts

Output=V2xI2 %efficiency % Regulation

CALCULATION

Output=V2xI2.

Input= W

%efficiency=𝑶/𝒑

𝒊/𝒑 x100.

Regulation= 𝒐𝑽𝟐−𝑽𝟐

𝒐𝑽𝟐 x100.

RESULT:-

Load test on single phase transformer is conducted and efficiency and regulation curve were

plotted.

Page 10: 1.OPEN CIRCUIT AND SHORT CIRCUIT TEST OF … lab1.pdf · 1.OPEN CIRCUIT AND SHORT CIRCUIT TEST OF TRANSFORMER AIM:- To conduct open circuit and short circuit test in given transformer

3.SWIMBERN’S TEST

AIM:-

Conduct no load test on dc shunt motor and [predetermine the efficiency of the machine under

the following working conditions.

a)machine working as a generator

b) Machine working as a motor

c) plot efficiency vs output

MACHINE DETAILS:-

METERIALS REQUIRED:-

1) Ammeter 0-5A MC 2NO

2) Ammeter 0-3A MC 1NO

3) voltmeter 0-300v MC 1NO

4) voltmeter 0-30v MC 1NO

5) Rheostat 100Ω,5A 1NO

6) Rheostat 370Ω,1.1A 1NO

7) Tachometer 1NO

THEORY:-

This is a no load test to determine the losses of the machine. the losses in the motors are

Iron loss or core losses, frictional losses, windage losses, arm copper losses

Work as generator

Efficiency= 𝒐𝒖𝒕𝒑𝒖𝒕

𝒐𝒖𝒕𝒑𝒖𝒕−𝒍𝒐𝒔𝒔𝒆𝒔

Work as motor

Efficiency = 𝒊𝒏𝒑𝒖𝒕−𝒍𝒐𝒔𝒆𝒔

𝒊𝒏𝒑𝒖𝒕

Page 11: 1.OPEN CIRCUIT AND SHORT CIRCUIT TEST OF … lab1.pdf · 1.OPEN CIRCUIT AND SHORT CIRCUIT TEST OF TRANSFORMER AIM:- To conduct open circuit and short circuit test in given transformer

PROCEDURE:-

1. Connection are as shown in connection diagram.

2. Armature rheostat at maximum position.

3. Field rheostat at minimum position.

4. Switch on the supply and run the motor at no load.

5. Adjust the field rheostat bring motor speed to rated speed.

6. Note the readings and tabulate the readings

TABULATION

Si

no

Voltage V

(in volts)

𝑰𝑺𝑯

AMPS

𝑰𝑨𝟎

AMPS

𝑰𝟎=𝑰𝑨𝟎 + 𝑰𝑺𝑯

Page 12: 1.OPEN CIRCUIT AND SHORT CIRCUIT TEST OF … lab1.pdf · 1.OPEN CIRCUIT AND SHORT CIRCUIT TEST OF TRANSFORMER AIM:- To conduct open circuit and short circuit test in given transformer

AS MOTOR:

Sl No Fraction of load(X)

Voltage(v) Current Ia in Amps

Total loss= X²Ia²Ra+Wc

Input power

o/p power

efficiency

AS GENERATOR

Sl No Fraction of load(X)

Voltage(v) Current Ia in Amps

Total loss= X²Ia²Ra+Wc

Input power

o/p power

efficiency

CALCULATIUON:

Constant losses Wc= V ( Iao+ Ish)-Iao²Ra.

AS MOTOR:

I/p power=F.L o/p Power+Ia²Ra+Wc.,O/p power= V𝑰𝑳, 𝑰𝑳=Ia+ Ish.

Total loss= Ia²Ra+Wc.

O/p=I/p-Losses.

Efficiency=𝑶/𝒑

𝒊/𝒑 x100.

AS GENERATOR:

Full load o/p power=Vx𝑰𝑳.

I/p=o/p+ losses.

%efficiency=𝑶/𝒑

𝒊/𝒑 x100.

RESULT Efficiency of the DC shunt machine when work as

1)Motor 2) Generator are pre-determined also efficiency curves are plotted.

Page 13: 1.OPEN CIRCUIT AND SHORT CIRCUIT TEST OF … lab1.pdf · 1.OPEN CIRCUIT AND SHORT CIRCUIT TEST OF TRANSFORMER AIM:- To conduct open circuit and short circuit test in given transformer

4.LOAD TEST ON A DC SERIES MOTOR AIM;

To conduct a load test on DC series motor and plot the following graph.

1) Torque v/s armature current

2) Speed v/s armature current

3) Speed v/s torque

4) Efficiency v/s o/p

MACHINE DETAILS:

APPARATUS REQUIRED:

1) Voltmeter 0-250V(MC) 1No

2) Ammeter 0-15A(MC) 1 No

3) Tachometer

THEORY:

In series motor the torque is directly proportional to armature current. Speed N is

proportional to Ed/∅. In a series motor the field carries same current as the armature ie, ∅

∝Ia. The series motor cannot be started without load.

Toque= (S1-S2)xgr

Output= 𝟐П𝑵𝑻

𝟔𝟎.

Input=VI.

%efficiency=𝑶/𝒑

𝒊/𝒑 x100.

Page 14: 1.OPEN CIRCUIT AND SHORT CIRCUIT TEST OF … lab1.pdf · 1.OPEN CIRCUIT AND SHORT CIRCUIT TEST OF TRANSFORMER AIM:- To conduct open circuit and short circuit test in given transformer

TABULATION:

Sl No

Voltage(V)

Speed(RPM)

Spring balance Torque= (S1-s2)rg

Output(W)

Input(W)

Efficiency(%)

S1

S2

S1~s2

CALCULATION:

V= ………………..

Speed,N=………………………….

Spring balance, S1=…………………………….

S2=……………………………………………..

Torque,T= (s1~s2)rg, r=Radius of break drum

g= 9.8

Output= 𝟐П𝑵𝑻

𝟔𝟎.

%efficiency=𝑶/𝒑

𝒊/𝒑 x100.

Page 15: 1.OPEN CIRCUIT AND SHORT CIRCUIT TEST OF … lab1.pdf · 1.OPEN CIRCUIT AND SHORT CIRCUIT TEST OF TRANSFORMER AIM:- To conduct open circuit and short circuit test in given transformer

PROCEDURE:

1) Connections are made as per diagram.

2) Apply a small load to the motor and start the motor.

3) Note the meter readings

4) Vary the spring balance at different load.

5) Note the corresponding readings.

6) Tabulate the reading and plot the graph.

RESULT:

The load test on series motor is conducted and plotted the graphs.

Page 16: 1.OPEN CIRCUIT AND SHORT CIRCUIT TEST OF … lab1.pdf · 1.OPEN CIRCUIT AND SHORT CIRCUIT TEST OF TRANSFORMER AIM:- To conduct open circuit and short circuit test in given transformer

5.LOAD TEST ON A DC SHUNT MOTOR AIM;

To conduct a load test on DCshunt motor and plot the following graph.

5) Torque v/s armature current

6) Speed v/s armature current

7) Speed v/s torque

8) Efficiency v/s o/p

MACHINE DETAILS:

APPARATUS REQUIRED:

1) Voltmeter 0-250V(MC) 1No

2) Ammeter 0-15A(MC) 1 No

3) Ammeter 0-3A (MC) 1No

4) Rheostat 500Ω,3A 1No

5) Tachometer

THEORY:

A load test is direct method,and this method is used only for small motors, because in the case

of large motors it is difficult to dissipate large amount of heat generation

Toque= (S1-S2)xgr

Output= 𝟐П𝑵𝑻

𝟔𝟎.

Input=VI.

%efficiency=𝑶/𝒑

𝒊/𝒑 x100.

Page 17: 1.OPEN CIRCUIT AND SHORT CIRCUIT TEST OF … lab1.pdf · 1.OPEN CIRCUIT AND SHORT CIRCUIT TEST OF TRANSFORMER AIM:- To conduct open circuit and short circuit test in given transformer

TABULATION:

Sl No

Voltage(V) Speed(RPM)

Ish Ia IL=Ia+ Ish

Spring balance Torque= (S1-s2)rg

Output(W)

Input(W)

Efficiency(%)

S1 S2 S1~s2

CALCULATION:

V= ………………..

Speed,N=………………………….

Spring balance, S1=…………………………….

S2=……………………………………………..

Torque,T= (s1~s2)rg, r=Radius of break drum

g= 9.8

Output= 𝟐П𝑵𝑻

𝟔𝟎.

%efficiency=𝑶/𝒑

𝒊/𝒑 x100.

Page 18: 1.OPEN CIRCUIT AND SHORT CIRCUIT TEST OF … lab1.pdf · 1.OPEN CIRCUIT AND SHORT CIRCUIT TEST OF TRANSFORMER AIM:- To conduct open circuit and short circuit test in given transformer

PROCEDURE:

1) Connections are made as per diagram.

2) Rheostat kept in min. position

4) Start the motor using 4 point starter

5)Note the meter readings

6) Vary the spring balance at different load.

7) Note the corresponding readings.

8) Tabulate the reading and plot the graph.

RESULT:

The load test on shunt motor is conducted and plotted the graphs.

Page 19: 1.OPEN CIRCUIT AND SHORT CIRCUIT TEST OF … lab1.pdf · 1.OPEN CIRCUIT AND SHORT CIRCUIT TEST OF TRANSFORMER AIM:- To conduct open circuit and short circuit test in given transformer

6.POLARITY TEST AND TURN`S RATIO TEST ON SINGLE PHASE T RANSFORMER

Aim : To conduct polarity test, and determine turn`s ratio, transformation ratio, and magnetizing

component of No Load current of single phase transformer. (115/ 220 V, 5 KVA)

Apparatus required :

Theory:- Turns ratio of a transformer = No of turns of primary/No of turns of secondary.

Transformation ratio K = Secondary induced EMF/ Primary induced EMF= E2/E1

E1 = 4.444 φm.f.N1Volts., and E2 = 4.444 φm.f.N2Volts ... K= E2/E1

K =4.444 φm.f.N2/4.444 φm.f.N1 , =N2/N1

...Turns ratio, N1/N2=E1/E2

No load input power, W0= V0 I0 Cosφ0, Cosφ0= W0/ V0 I0, ... φ0 =Cos-1(W0/ V0 I0)

Magnetizing component of no load current Iµ = I0 Sinφ0

Page 20: 1.OPEN CIRCUIT AND SHORT CIRCUIT TEST OF … lab1.pdf · 1.OPEN CIRCUIT AND SHORT CIRCUIT TEST OF TRANSFORMER AIM:- To conduct open circuit and short circuit test in given transformer

Procedure:- 1) Polarity test.

1 Connections are made as shown in figure (1)

2. Checked the connections and given a specified voltage to primary.

3. Noted the volt meter reading and verified the polarity of the transformer.ie If the

voltmeter reading in the inter connected voltmeter is greater than the input voltage, then

the polarity is additive , So Opposite polarity on the other adjacent terminal on secondary.

4. Interchanged the connections to confirm first determined polarity.

Page 21: 1.OPEN CIRCUIT AND SHORT CIRCUIT TEST OF … lab1.pdf · 1.OPEN CIRCUIT AND SHORT CIRCUIT TEST OF TRANSFORMER AIM:- To conduct open circuit and short circuit test in given transformer

Turn`s ration and transformation ratio;

1. Connections are made as in figure (2)

2. Checked the connections and given the supply gradually from minimum voltage to

rated voltage of primary using autotransformer.

3. Noted the V/m readings on primary and secondary and the A/m and W/m reading

when applying the rated primary voltage.

4. Completed the experiment neatly and correctly.

Result:- Checked the polarity and determined the turns ratio transformation ratio, and

magnetizing component of no load current of 115/220/V 5 KVA transformer.

Turns ratio= Transformation ratio=

Magnetizing component of no load current Iµ =

Determined the polarity of the transformer also.

Sl No Prim V/m

reading E1

Sec V/m

reading E2

Watt meter

reading W0

A/m

reading I0

Turns ratio Transf.

ratio =K

Page 22: 1.OPEN CIRCUIT AND SHORT CIRCUIT TEST OF … lab1.pdf · 1.OPEN CIRCUIT AND SHORT CIRCUIT TEST OF TRANSFORMER AIM:- To conduct open circuit and short circuit test in given transformer