Sentron 3WT Circuit Breaker –The Art of Simplicity.

During the last decade, with the introduction of 3WN and3WL Circuit Breakers, Siemens introduced a new perspectivein the field of Switching technology and Intelligentcommunication. The standards of Performance, Reliability,and Safety were further raised through the Sentron series andoffered an “Art of Intelligent Simplicity”.

Siemens Sentron family of Air circuit breaker grows furtherand now offers an additional range of 3WT Circuit breakers for greater choice and optimized selection in LVpower system.

Sentron 3WT is available with Siemens hallmark of Performance, Reliability, Safety, Ease of operation andMaintenance, and accurate protections under the banner:

Sentron 3WT Circuit Breaker “The Art of Simplicity”.

3WT is available from 630 A to 3200 A in two frame sizes with thefollowing advantages:

3WT conforms following standards:

• IEC 60947 –2, IS 13947 -2

• VDE 0660 Part 101

• GB 14048.2

• Climate proof to IEC 60 068 –2-30

• Approval according to maritime classification on request.

Safety Plus:

• Interchangeable Line- Load terminals.

• Front cover can’t be removed if the circuit breaker is in closedcondition.

• “SAFE OFF” Suitable for isolation. Castell key can be removedonly when contacts are separated.

• Locking of withdrawable circuit breaker against moving, asstandard.

• Locking of the guide frame with the circuit breaker removed,as standard.

• Trip signalling switch for overload and short circuit trippingwith mechanical closing lock out.

• Distinct “Ready to Close” interlocking is provided as inherentsafety features. This ensures safe switching ON of ACB andeases the diagnosis.

• 3WT conforms to positive isolation requirement as per IEC 60-947- 2.

Easy Plus:

Ease of Operation, Maintenance and Upgradation:

• Unambiguous ON- OFF indicator with auxiliary switch forsignal.

• Click-fit front mounted accessories e.g. Shunt, Under Voltage,etc can be replaced without removing the breaker from thepanel and needs no calibrations.

• High electrical life reduces frequency of replacement ofcontacts.

• Permits last minute up-gradation. e.g converting from Manualto Motorized or from fixed to draw-out.

• Built-in test features of the release permit testing of thebreakers and trip circuitry without additional test kit.

• Contact erosion indicator for predictive maintenance.

Compact and Power Saver:

• Continuous rated low consumption accessories like shunt,Motor, Under Voltage bring down the cost and size of thecontrol transformer.

• Low power loss improves the inpanel rating of the circuitbreaker without increasing the circuit breaker width.

2

Page 3: 2) Sentron 3WT ACB

3

Technical specifications that blends with Indian environment:

3WT Technical Specification Sheet

Frame Size I II

Type 3WT8 06 3WT8 08 3WT8 10 3WT8 12 3WT8 16 3WT8 20 3WT8 25 3WT8 32

Rated Current In at 50°C Main Conductor A 630 800 1000 1250 1600 2000 2500 3200

at 50/60 Hz Neutral Conductor A 100%(only for 4-pole version)

Rated operational voltage Ue V AC upto 500at 50/60 Hz

Rated insulation voltage Ui V AC 1000at 50/60 Hz

Rated impulse withstand Main Circuits kV 8

voltage, Uimp Auxiliary Circuits kV 4

Utilization category B

Rated short-circuit makingcapacity Icm

upto 500 V AC kA 145

Rated ultimate short-circuitbreaking capacity, Icu

upto 500 V AC kA 66

Rated service short-circuitbreaking capacity, Ics

upto 500 V AC kA 66

Rated short time withstandcapacity, Icw at 50/60 Hz

1 sec kA 50 60

Permissible service temperature °C -20 ... +70

Power Loss at In Fixed W 40 60 90 120 140 170 325 420

(with 3 phase symmetrical load) Withdrawable W 80 130 205 255 310 310 535 760

Service Life Mechanical cycles 16000 12000

Electrical cycles 10000 4000

Operating frequency opn/hr 60

Degree of Protection IP 40*

Dimensions A mm 3P / 4P 320 / 420 410 / 540

B mm 470 470

C mm Fix / 00 330 / 398 330 / 398

Weight (3P / 4P) Fixed kg 34 / 47 36 / 49 57 / 70 61 / 74

Withdrawable kg 58 / 76 61 / 79 94 / 118 100 / 124

*IP 54 available on request

Page 4: 2) Sentron 3WT ACB

4

Secondary isolating contacts

Mechanical reclosing lockout

‘Ready to close’ interlock

Closing Coil

Shunt Release

Racking window Motorised mechanism

Microprocessor based trip unitU/V Release

Front accessible terminals for panels withoutrear access

Rear horizontal terminals for horizontal busconnections & bus couplers

Rear vertical terminals for multiple cableterminations and vertical droppers

Slot for Phase barrier to prevent arc propogationin the ACB in the event of line side fault

Easy Terminations:Simplified busbar and cableconnections through differentterminal orientation

Sentron 3WT –The Art of SimplicityModular accessories enables easymodification at site

4

Page 5: 2) Sentron 3WT ACB

5

Simplicity of inspection and operational safety

Keyless Mechanical Interlocking

• Two or three breakers can bemechanically interlocked

• Ideal for auto change oversystems

• The breakers can be mountedside by side or above each other

Easily approachableprotection C.Ts

• Fire retardant insulatingmaterial

Contact erosion indicator

• No adjustments requiredafter replacing powercontacts

Insulating enclosure segregatesphases completely and isolatesthe power contacts from thefront accessible operatingmechanism/auxiliaries/trip unitcompartments

Front accessible secondaryisolating contacts permitinspection and retrofitting ofauxiliaries without removingthe breaker from the guideframe

Metallic guide rails hold thebreaker in maintenanceposition for inspection andretrofitting of auxiliaries

Racking window blocks accessto the racking mechanism.The window opens only whenthe ‘OFF’ push button is keptdepressed, preventing rackingof the breaker in ‘ON’condition.

Interlocking Mechanism

Mechanical Cord

5

Page 6: 2) Sentron 3WT ACB

6

Reliability Plus:Microprocessor Based Release for Ultra Accurate Protections:

Trip units The Microprocessor based releases which measures TRUE RMScurrent are provided with following standard features:

• Integrated Test Features:The test button test the healthiness of microprocessor basedtrip units, trip solenoid and breaker mechanism with orwithout tripping of the circuit breaker. This eliminates externaltest unit to check the healthiness of the protection measuringsystem.

• Active LED to show healthiness of ETU:Correct operation of the trip unit is indicated by the“heartbeat” of a green flashing LED. Rapid flashing of LED willindicate whenever load current exceeds the threshold value ofoverload protections.

• Fault Clarity and Fault History:The LEDs shows the reason for tripping of the breaker. Faulthistory is also recorded and can be recovered by QUERYbutton.

6

• Microprocessor Bypass circuit:If a microprocessor fault occur, the alarm will activate redLED “MP”. This alarm indicates that the overloadprotection functions are not currently active. However,with the internal bypass circuit, trip unit guaranteesprotection against short-circuit.

Page 7: 2) Sentron 3WT ACB

7

Comprehensive additional functions for high uptime:

Comprehensive additional functions – in accordance with thedesign of the trip unit, e.g.:

• Short time-delay short-circuit release with I2t-dependent delayfor improved discrimination to the downstream fuses

• Thermal memory

Ground-fault protection

• Description

Ground-fault releases “G” sense fault currents that flow toground and that can cause fire in the plant. Multiple circuit-breakers connected in series can have their delay timesadjusted so as to provide time-graded discrimination.

The reason for tripping is indicated by means of an LED whenthe query button is activated.

• Measurement methods

– Vectorial summation formation with current transformer inneutral conductor

The neutral conductor current is measured directly and isevaluated for neutral conductor overload protection.

The trip unit determines the ground-fault current by meansof vectorial summation of current in all three phases andthe N-conductor current.

Trip unit version Current transformer T5 must beconnected to auxiliary current connection

• ETU5WT, ETU8WT 400.13400.14

For 4-pole circuit-breakers, the fourth current transformerfor the N-conductor is installed internally.

7

Functional overview of the microprocessor based trip unit system

Function Trip unit versionETU2WT ETU8WT ETU5WT

Basic functions

Overload protection Inverse-time delayed Adjustment of the current setting IR from 40 % to 100 % Inoverload release “L” Graduation 5 %for the phases Graduation freely programmable

Time-lag class tR = opening time at 6 × IR, setting tR 10 s 10 s 2–30 s

“Phase-failure sensitivity” (reversible)

for the neutral conductor 1) Adjustment of the current setting In 50 or 50 orTime-lag class tR of the neutral conductor as for the phases 100 % 100 %

Short-circuit protection Short-time delayed Setting the operating current Isd 1.5–12×IR 1.25–12×IR 1.25–12×IRshort-circuit release “S” Setting the delay time tsd 0; 20–400 ms 0; 20–400 ms 20–400 ms

With I2tsd-dependent delay, delay time tsd 80–300 ms

Instantaneous short-circuit Setting the operating current Ii >15×In >15×In >1.5–12×Inrelease “I” and Ii = ∞

with settingIi = ∞ thenIcu = Ics = Icw

(lowest valuedecisive)

Ground-fault protection Ground-fault release “G” 1) Setting the operating current Ig 0.2–0.6×In

Setting the delay time tg 100–500 ms

LCD display Operating current indication

LED display Status indication Flashing LED when trip unit activated

“Tripped” indication “L” release

“S/I” release

“S” release

“I” release

“N” release

“G” release

Alarm indication T. U. ERROR

Test Internal self-test and display via LED

Connection of the test device to test connector X3

Basic configuration

Signal by Ready-to-close Circuit-breaker can be safely closedsignaling switch (1 NO) “Tripped” switch Latching; active after “L”, “S”, “I”, “G” 2) release

with/without mechanical closing lockout

Three-pole circuit-breakers,current transformers in theneutral conductor suitable forasymmetrical loading of thephases.

1) With 3-pole circuit-breakers a current transformer is required if there is asymmetrical loadingof the phases. In the case of 4-pole circuit-breakers a current transformer in the neutralconductor is fitted internally in the circuit-breaker.

2) “G” release occurs with “Trip” setting on the trip unit.

Function available as standard

Function active when td is set to 20 ms.

Page 8: 2) Sentron 3WT ACB

8

3WT Characteristics

The characteristics show the behavior of the trip unit when it isactivated by a current that is already flowing before the trippingoperation.

Tripping characteristics “L” and “S”: “S” = definite-time delayed

Tripping characteristics of trip units – version ETU2WT

Key to illustrations above:

Inverse-time delayed electronic trip unit “L” Short-time delayed short-circuit release “S”IR Current setting (adjustable) Isd Operating current (adjustable)IN Current setting (50 or 100 % IR) for the N conductor tsd Delay time (adjustable)tR Time-lag class (permanently set to 10 s)

Tripping characteristics “I”

Tripping characteristics of trip units – version ETU8WT

Tripping characteristics of trip units – versions ETU2WT andETU8WT

In Transformer primary rated current

Instantaneous short-circuit release “I”Ii Operating current (permanently set)

Tripping characteristic “G”: definite-time delayed

Tripping characteristics of trip units – version ETU8WT

In Transformer primary rated current

Ground-fault release “G”Ig Operating current (adjustable)tg Delay time (adjustable)

Page 9: 2) Sentron 3WT ACB

9

Rated Short-circuitcurrent breaking capacity, 3 pole, ETU2WT: 3 pole, ETU8WT: 4 pole, ETU2WT: 4 pole, ETU8WT:

Size In 500VAC, protection function LSI protection function protection function LSI protection function

(Amps) Ics=100% Icu, LSING 1) LSING

Motorised operating mechanism, drawout type with guide frame (EDO), horizontal main circuit connection 2) 4)

I 630 3WT80 61-1UG04-5AB2 3WT80 61-2UG04-5AB2 3WT80 65-1UG04-5AB2 3WT80 65-2UG04-5AB2

I 800 3WT80 81-1UG04-5AB2 3WT80 81-2UG04-5AB2 3WT80 85-1UG04-5AB2 3WT80 85-2UG04-5AB2

I 1000 3WT81 01-1UG04-5AB2 3WT81 01-2UG04-5AB2 3WT81 05-1UG04-5AB2 3WT81 05-2UG04-5AB2

I 1250 66 kA 3WT81 21-1UG04-5AB2 3WT81 21-2UG04-5AB2 3WT81 25-1UG04-5AB2 3WT81 25-2UG04-5AB2

I 1600 3WT81 61-1UG04-5AB2 3WT81 61-2UG04-5AB2 3WT81 65-1UG04-5AB2 3WT81 65-2UG04-5AB2

II 2000 3WT82 02-1UG04-5AB2 3WT82 02-2UG04-5AB2 3WT82 06-1UG04-5AB2 3WT82 06-2UG04-5AB2

II 2500 3WT82 52-1UG04-5AB2 3WT82 52-2UG04-5AB2 3WT82 56-1UG04-5AB2 3WT82 56-2UG04-5AB2

II 3200 3WT83 22-1UG04-5AB2 3WT83 22-2UG04-5AB2 3WT83 26-1UG04-5AB2 3WT83 26-2UG04-5AB2

Manual operating mechanism, drawout type with guide frame (MDO), horizontal main circuit connection 2)

I 630 3WT80 61-1AA04-5AB2 3WT80 61-2AA04-5AB2 3WT80 65-1AA04-5AB2 3WT80 65-2AA04-5AB2

I 800 3WT80 81-1AA04-5AB2 3WT80 81-2AA04-5AB2 3WT80 85-1AA04-5AB2 3WT80 85-2AA04-5AB2

I 1000 3WT81 01-1AA04-5AB2 3WT81 01-2AA04-5AB2 3WT81 05-1AA04-5AB2 3WT81 05-2AA04-5AB2

I 1250 66 kA 3WT81 21-1AA04-5AB2 3WT81 21-2AA04-5AB2 3WT81 25-1AA04-5AB2 3WT81 25-2AA04-5AB2

I 1600 3WT81 61-1AA04-5AB2 3WT81 61-2AA04-5AB2 3WT81 65-1AA04-5AB2 3WT81 65-2AA04-5AB2

II 2000 3WT82 02-1AA04-5AB2 3WT82 02-2AA04-5AB2 3WT82 06-1AA04-5AB2 3WT82 06-2AA04-5AB2

II 2500 3WT82 52-1AA04-5AB2 3WT82 52-2AA04-5AB2 3WT82 56-1AA04-5AB2 3WT82 56-2AA04-5AB2

II 3200 3WT83 22-1AA04-5AB2 3WT83 22-2AA04-5AB2 3WT83 26-1AA04-5AB2 3WT83 26-2AA04-5AB2

Motorised operating mechanism, fixed type (EF), horizontal main circuit connection 3) 4)

I 630 3WT80 61-1UG00-0AA2 3WT80 61-2UG00-0AA2 3WT80 65-1UG00-0AA2 3WT80 65-2UG00-0AA2

I 800 3WT80 81-1UG00-0AA2 3WT80 81-2UG00-0AA2 3WT80 85-1UG00-0AA2 3WT80 85-2UG00-0AA2

I 1000 3WT81 01-1UG00-0AA2 3WT81 01-2UG00-0AA2 3WT81 05-1UG00-0AA2 3WT81 05-2UG00-0AA2

I 1250 66 kA 3WT81 21-1UG00-0AA2 3WT81 21-2UG00-0AA2 3WT81 25-1UG00-0AA2 3WT81 25-2UG00-0AA2

I 1600 3WT81 61-1UG00-0AA2 3WT81 61-2UG00-0AA2 3WT81 65-1UG00-0AA2 3WT81 65-2UG00-0AA2

II 2000 3WT82 02-1UG00-0AA2 3WT82 02-2UG00-0AA2 3WT82 06-1UG00-0AA2 3WT82 06-2UG00-0AA2

II 2500 3WT82 52-1UG00-0AA2 3WT82 52-2UG00-0AA2 3WT82 56-1UG00-0AA2 3WT82 56-2UG00-0AA2

II 3200 3WT83 22-1UG00-0AA2 3WT83 22-2UG00-0AA2 3WT83 26-1UG00-0AA2 3WT83 26-2UG00-0AA2

Manual operating mechanism, fixed type (MF), horizontal main circuit connection 3)

I 630 3WT80 61-1AA00-0AA2 3WT80 61-2AA00-0AA2 3WT80 65-1AA00-0AA2 3WT80 65-2AA00-0AA2

I 800 3WT80 81-1AA00-0AA2 3WT80 81-2AA00-0AA2 3WT80 85-1AA00-0AA2 3WT80 85-2AA00-0AA2

I 1000 3WT81 01-1AA00-0AA2 3WT81 01-2AA00-0AA2 3WT81 05-1AA00-0AA2 3WT81 05-2AA00-0AA2

I 1250 66 kA 3WT81 21-1AA00-0AA2 3WT81 21-2AA00-0AA2 3WT81 25-1AA00-0AA2 3WT81 25-2AA00-0AA2

I 1600 3WT81 61-1AA00-0AA2 3WT81 61-2AA00-0AA2 3WT81 65-1AA00-0AA2 3WT81 65-2AA00-0AA2

II 2000 3WT82 02-1AA00-0AA2 3WT82 02-2AA00-0AA2 3WT82 06-1AA00-0AA2 3WT82 06-2AA00-0AA2

II 2500 3WT82 52-1AA00-0AA2 3WT82 52-2AA00-0AA2 3WT82 56-1AA00-0AA2 3WT82 56-2AA00-0AA2

II 3200 3WT83 22-1AA00-0AA2 3WT83 22-2AA00-0AA2 3WT83 26-1AA00-0AA2 3WT83 26-2AA00-0AA2

Selection and Ordering data

1) Current transformer for overload protection in the neutral conductor and ground fault protection must be ordered separately.2) Standard Accessories included for draw out type ACB (EDO/MDO) = Safety shutter, sealing cap over Off button, door sealing frame, release transparent cover, trip signaling

contact, ready to close electrical contacts, auxiliary contacts 2 NO + 2NC3) Standard accessories included for fixed type ACB (EF/MF) = Door sealing frame, release transparent cover, trip signaling contact, ready to close electrical contacts, auxiliary

contacts 2 NO + 2NC4) Standard accessories included for electrical ACB (EDO/EF) = Motor operated mechanism, with mechanical and electrical closing, motor and closing solenoid of 220-240V AC/

DC and shunt release of 220-240V AC/DC.

9

Page 10: 2) Sentron 3WT ACB

10

Dimension Drawings3WT 8 fixed-mounted circuit-breakers, 3-pole

Top and Bottom Horizontal connection

1.) Clearance for removing of the arc chute2.) Clearance for auxiliary connector3.) Arcing space4.) Auxiliary connector5.) Cubicle door6.) Recessed grip7.) M8 Nut8.) Slots (4 mm deep)

for phase separating barriers; (not included in the scope ofsupply)

9.) Axis of the circuit-breaker

Note : The clearance between the connections point and thesupport for the busbars must not exceed 250mm

Rated current A a b c d e f j k l

630 to 1250 300 320 90 8 60 30 530 18 40

1600 300 320 90 15 60 30 530 18 40

2000 to 2500 400 420 120 15 80 40 560 22 44

3200 400 420 120 30 80 50 560 22 44

Main conductor connections

Terminal screws with clamping washers (inner diameter = 12 mm acc. DIN 6769-Fst) M 12

Recommended tightening torque Nm 70

Required screw strength 8.8 acc. DIN 267

Page 11: 2) Sentron 3WT ACB

11

a Disconnected positionb Test positionc Connected position1.) Auxiliary wiring connection system2.) Guide frame3.) Cubicle door4.) Slots (6 mm deep), for phase separating barriers (not included

in the scope of suply)5.) Holes for fixing screws (for the draw out-frame)6.) Axis of the circuit-breaker

Note : The clearance between the connections point and thesupport for the busbars must not exceed 250mm

Dimension Drawings3WT 8 draw out circuit-breakers, 3-pole

Top Horizontal – Bottom Horizontal connection

Rated current A a b c d e f h j k l m n

630 to 1250 280 320 90 8 60 30 455 470 157,5 115 37 90

1600 280 320 90 15 60 30 455 470 157,5 115 37 90

2000 to 2500 380 420 120 15 80 40 465 480 157,5 115 37 140

3200 380 420 120 30 100 50 465 480 150 130 37 140

Top Horizontal – Bottom Vertical connection

Page 12: 2) Sentron 3WT ACB

12

1.) Clearance for removing the arc chute2.) Clearance for auxiliary connector3.) Arcing space4.) Auxiliary connector5.) Cubicle door6.) Recessed grip7.) Nut M 88.) Slots (4 mm deep), for phase separating barriers, (not included

in the scope of supply)9.) Axis of the operating panel

Note : The clearance between the connections point and thesupport for the busbars must not exceed 250mm

Top and Bottom Horizontal connection

Rated current A a b c d e f j k l p

630 to 1250 390 410 90 8 60 30 530 18 40 150

1600 390 410 90 15 60 30 530 18 40 150

2000 to 2500 520 540 120 15 80 40 560 22 44 200

3200 520 540 120 30 80 40 560 22 44 200

Dimension Drawings3WT 8 fixed-mounted circuit-breakers, 4-pole

Page 13: 2) Sentron 3WT ACB

13

a Disconnected positionb Test positionc Connected position1.) Auxiliary wiring connection system2.) Guide frame3.) Cubicle door4.) Slots (6 mm deep), for phase separating barriers, (not included

in the scope of supply5.) Holes for fixing screws6.) Axis of the operating panel

Note : The clearance between the connections point and thesupport for the busbars must not exceed 250mm

Dimension Drawings3WT 8 draw out circuit-breakers, 4-pole

Top Horizontal – Bottom Horizontal connection

Top Horizontal – Bottom Vertical connection

Rated current A a b c d e f h j k l m n n1 p

630 to 1250 370 410 90 8 60 30 455 470 157,5 115 37 90 90 140

1600 370 410 90 15 60 30 455 470 157,5 115 37 90 90 140

2000 to 2500 500 540 120 15 80 40 465 480 157,5 115 37 140 120 190

3200 500 540 120 30 100 50 465 480 150 130 37 140 120 190

Page 14: 2) Sentron 3WT ACB

14

Door cut-out for operator panel using the door sealing frame

Dimension Drawings3WT circuit-breakers, 3- and 4-pole

Mounting surface * 3 holes, dia. ∅ 5.5 mm; only drill when using door interlocking

Accessories for 3WT circuit-breakers, 3- and 4-poleMutual mechanical interlocking (1)/locking device to prevent closing (2),consisting of lock in the control cabinet door and interlock module with Bowden wire

Clearance for interlock module(without Bowden wire)

For withdrawable circuit-breakers

Current transformer for neutral conductor overload protection and ground-fault protection

Cut-out when the circuit-breaker is installed in a switchgear cabinet andwith the door arranged centrally.

Section width Fixed-mounted Withdrawableb b

400 275 292

500 275 290

600 275 288

Clearance for a b c d e

(1) 90 90 50 65 270

(2) 58 215 10 250 115

Current Current Size A B C D E Ftransformer transformer approx.

primary ratedcurrent In

3WT98 43-1..00 A

CD 630 I 92 60 86.5 140 5...15 107CE 800CF 1000CG 1250CH 1600

FJ 2000 II 128 80 99 167 5...35 136FK 2500FM 3200

For fixed-mounted circuit-breakers

Page 15: 2) Sentron 3WT ACB

15

Connection of the neutral-conductor current transformers 3WT9843-1..00 with 3WT8 circuit-breakers

3WT8/Size I

Example of an overall circuit diagramMotor/manual operating mechanism, with ready-to-close signalingswitch, with trip unit version ETU2WT “LSI”, with undervoltage

3WT8063WT8083WT8103WT8123WT816

3WT8203WT8253WT832

3WT8/Size II

Circuit DrawingSchematics

A1 Trip unitS1/S2 1st auxiliary switch blockS3/S4 2nd auxiliary switch blockS7 Ready-to-close signaling switchS8 Storage spring contactS11 “Tripped” switchF1 1st shunt release “F”F2 2nd shunt release “F”F3 Undervoltage release “r”

release “r” (F3) or shunt release “f” (F1), with shunt release“f” (F2), with “tripped” signaling switch, with auxiliary switch2 NO + 2 NC + 2 CO, with motor switch

F5 Trip solenoidM1 Motor for “charging store”P Storage springQ01 Hand-operated lever for “charging store”Q1 Main contactsT1/T2/T3 Current transformerX100/X200 TerminalsY1 Closing solenoidR Indication and reset button for overcurrent tripping

Page 16: 2) Sentron 3WT ACB

Siemens Ltd.Automation and Drives DivisionLV Control & Distribution ProductsThane Belapur RoadThane 400601Fax: +91 22 27623729E-mail: [email protected]

Siemens Ltd.SGR-01-115-020This replaces SGR-01-115-012

‘Product development is a continuous process. Consequently,the data indicated in this Catalogue is subject to change withoutprior notice. For latest issue contact our Sales Offices.’

Sales offices:

• Bhubaneswar - 751002109, Harapriya ApartmentVivekananda Marg

: +91 674 3200627Mobile: +91 9937009749E-mail: [email protected]

• Cochin - 682016K.G. Oxford Business Centre39/4609, 3rd FloorSreekandath Road, Ravipuram

: +91 484 4028611/22/33/44Fax: +91 484 2371564E-mail: [email protected]

• Durgapur - 71321693, Pranabananda Avenue, 1st FloorSAIL Housing Complex, City Center

: +91 343 2605286Mobile: +91 9830185007E-mail: [email protected]

• Gurgaon - 122001117-C, First Floor, Sector-30Behind Jalvayu ViharMobile: +91 99710 91588Email: [email protected]

• Guwahati - 781003G1, Hill View ApartmentNavagraha Path, Chenikuthi Hill Side

: +91 361 2663988Mobile: +91 9864037562E-mail: [email protected]

• Hardwar - 249407758, 1st Floor, Model ColonyAwas Vikas, Jwalapur, Uttaranchal

& Fax: +91 1334 265491Mobile: +91 9897070133E-mail: [email protected]

• Haryana - 121006House No.237, sector 8, Faridabad

: +91 9990265226Mobile: +91 9873696350E-mail: [email protected], [email protected]

• Indore - 452001521 Suniket ApartmentsShri Nagar Extension, Main Khajrana RoadMobile: +91 98266 41970E-mail: [email protected]

• Jaipur - 3020066, Park Street, Opp. Pink City Petrol PumpM.I. Road, Rajasthan

: +91 141 2370274, 2377956Fax: +91 141 2370482Mobile: +91 9829244313E-mail: [email protected]

• Jallandhar - 144002635L, 1st Floor, Model Town

& Fax: +91 181 2460547Mobile: +91 9915526636E-mail: [email protected]

• Jamshedpur - 8310051511, Kirthar ApartmentVijaya Heritage, Uliyan, Kadma

: +91 657 6451637Mobile: +91 99343 11352E-mail: [email protected]

• Kanpur - 208001Flat No.19-B, 4th Floor, Prabhu Vatika7/109, Swarup Nagar, U.P.

& Fax: +91 512 2423348Mobile: +91 9839102434E-mail: [email protected]

• Kolhapur - 416001B-7, Mahagaonkar Complex1147/E, Rajaram RoadOpp. Kamala College

: +91 231 2536626Mobile: +91 9822558876E-mail: [email protected]

• Ludhiana - 141009H.No. 3127, First Floor, Sector 38Urban Estate, Chandigarh RoadMobile : 09876047929E-mail : [email protected]

• Ludhiana - 141004House No. 281, 1st Floor, E Block, B.R.S. NagarMobile: +91 9872000936E-Mail: [email protected]

• Ludhiana - 141004House No. 766, 1st FloorSector 39, Chandigarh RoadMobile: +91 9815130172E-Mail: [email protected]

• Madurai - 625006Arun Illam, Plot No 4, Lion City, Thirunagar

& Fax: +91 452 2484085Mobile: +91 9443369375E-Mail: [email protected]

• Nashik - 4221018B, Shubhmangal ApartmentChavan Mala, Nasik RoadMobile: +91 9822193204E-mail: [email protected]

• Pondicherry - 60500132, Second Floor, St. Theresa Street

& Fax: +91 413 4500101Mobile: +91 9840472727E-mail: [email protected]

• Raipur - 492007Flat no -103, First Floor, Block-B, Shilp EnclaveNear I A S Colony, Shankar NagarMobile: +91 9425057945E-mail: [email protected]

• Rajkot - 360005Maushmi, Nr. Sadguru Vandana Dham-IIOpp. Raiya Telephone ExchangeMobile: +91 98258 18864E-mail: [email protected]

• Ranchi - 834001Flat No. 403, Rishab TowersNear Line Tank, Behind Firayalals

: +91 651 6450812Mobile: +91 99343 52756E-mail: [email protected]

• Rourkela - 769004T-15 Civil Town

: +91 661 2400880Mobile: +91 9437041724E-mail: [email protected]

• Renukoot - 231217Sector 1/1653, Plant II ColonyHindalco Industries Ltd.P.O. Murdhawa, Distt. Sonebhadra, U.P.Mobile: +91 9838007897E-mail: [email protected]

• Tiruchirappalli - 620017T3, III rd Floor, Vishranthi Daffodils ApartmentsOpp: Friends Eye Hospital, Puthur

: +91 431 4030390Fax: +91 431 4030390Mobile: +91 9444911221E-mail: [email protected]

• Udaipur - 313001Oasis Park, Flat No.303P.P. Singhal Marg, Ambavgarh

: +91 294 2430345Mobile: +91 9829039120E-mail: [email protected]

• Vapi - 396195Flat No. 302, Samrajaya IVRoyal Residency, Charwada Road

: +91 260 6451156Mobile: +91 98251 47957E-Mail: [email protected]

• Vijayawada - 520010G-2, Shreya Towers, MoghalrajapuramNear Jammichettu Centre

: +91 866 6629933Mobile: +91 9866463639E-mail: [email protected]

• Visakhapatnam - 530003B4, Mount Moriah Residency, Waltair Uplands

: +91 891 6637344Fax: +91 2519762Mobile: +91 98492 12555E-mail: [email protected]

Sales offices:• Ahmedabad - 380009

1st Floor, Shanti Chamber,Terapanth Marg, Opp. Dinesh HallNear I.T. Cross Road, Navrangpura

: +91 79 27546803, 27546172Fax: +91 79 27546711

• Bangalore - 5600011st Floor, Jyothimahal, #49, St. Marks Road

: +91 80 22042000Fax: +91 80 22224131, 41120735

• Chandigarh - 160019SCO - 188-190, 2nd Floor,Sector 34A, Gurunanak Complex

: +91 172 2666189, 2666190Fax: +91 172 2666654

• Chennai - 6000344, Mahatma Gandhi Road

: +91 44 28334000Fax: +91 44 28334088

• Coimbatore - 6410187th Floor, East Wing, Global Towers1057, Avinashi Road

: +91 422 4336300Fax: +91 422 4336310

• Hyderabad - 5000045-9-19, Lakshmi Narsinh Estate, 4th FloorSecretariat Road, Opp. Secretariat, Saifabad

: +91 40 23482500 (10 Lines)Fax: +91 40 23243145 / 23243146

• Kolkata - 70004243 Shanti Palli, R B Connector, Eastern Metropolitan Bypass

: +91 33 24449000, 24428641-47Fax: +91 33 24449010 / 13

• Lucknow - 22600128/45, Ashok Marg, Post Box No. 246, U.P.

: +91 522 4031000, 4031039Fax : +91 522 4031019

• Mumbai - 400018130, Pandurang Budhkar Marg, Worli

: +91 22 24987000-02Fax: +91 22 24987312

• Nagpur - 4400105th Floor, Landmark Building, Ramdas Peth

: +91 712 6633000Fax: +91 712 6633111

• New Delhi - 1100024A, Ring Road, I.P. Estate

: +91 11 42995000-09Fax: +91 11 42995030

• Pune - 411016Tower B / 701 - 705, ICC Trade Tower403A, Senapati Bapat Road

: +91 20 2570 6000Fax: +91 20 2570 6060

Territory managers :• Aurangabad

Mobile: +91 9822193204E-mail: [email protected]

• Bareilly - 243001Flat no. T1, 129, Civil LinesMobile: +91 9897019061E-mail: [email protected]

• Baroda - 3900071st Floor Vanijya Bhavan, Race Course Road

: +91 265 2325810 / 12, 6692110Mobile: +91 98255 06963E-mail: [email protected]

• Belgaum - 590005C/o “Shrihari”, 1st Floor, Plot No. 615th Cross, Bhagya Nagar

& Fax: +91 831 2495156Mobile: +91 9880290835E-mail: [email protected]

• Bhilai - 490001C/o. Mr. S. H. SiddiquiSector -1, Street- 9, Quarter No.1AMobile: +91 9826127525E-mail: [email protected]