12
Features Basic system includes: Capacity for up to 1000 addressable IDNet points, up to 127 VESDA Air Aspiration Systems interface points and up to 254 addressable notification appliances with up to 2000 points of Annunciation; and up to 20 internal and external card addresses Color-coded operator interface with membrane keypad includes 2 x 40 Super-twist LCD display, 3 programmable control keys and 6 programmable LEDs CPU assembly includes dedicated compact flash memory for on-site system information storage and convenient Ethernet service port access Includes an Enhanced System Supply (ESS) that provides power and battery charging (6 A output): Dual 3 A on-board IDNAC SLCs (signaling line circuit) provide enhanced power delivery to addressable notification appliances With an IDNAC SLC, a constant 29 VDC source voltage is maintained during alarm, even during battery operation, allowing strobes to operate at higher voltage with lower current and ensuring a consistent current draw and voltage drop margin under both primary power and secondary battery standby Efficiencies include lower strobe currents, wiring distances up to 2 to 3 times farther than with conventional notification, support for more appliances per IDNAC SLC, ability to use smaller gauge wiring, all providing installation and maintenance savings with high assurance that appliances that operate during normal system testing will operate during worst case alarm conditions IDNAC SLCs are compatible with both TrueAlert ES and TrueAlert addressable notification appliances, and remote 4009 IDNAC Repeaters to extend power and wiring distance even farther and extends supervisory capacity by up to 139 additional unit loads or 3 A Addressable initiating device control is provided by on-board IDNet 2 dual loop SLCs that provide two electrically isolated channels that support TrueAlarm analog sensors and IDNet communications monitoring and control devices with an electrically isolated output channel allowing use with either shielded or unshielded, twisted or untwisted single pair wiring; and providing dual short circuit isolating output loops Battery charger for up to 110 Ah batteries (UL) or up to 50 Ah batteries (ULC) (33 Ah max in control panel cabinet) 2 A programmable function auxiliary output Remote annunciator module support via RUI (Remote Unit Interface) communications port, supports either Class B or Class A operation 48 LED panel mount annunciation provides 40 Red and 8 Yellow pluggable LEDs (select models, meets ULC requirements), optional LED kits are available to change individual LED color to Green or Blue to meet specific site requirements 1-Bay Cabinet 2-Bay Cabinet 1-Bay Cabinet with LED Annunciation 4010ES Panel Type Reference Optional ESS mounted modules, door mounted modules, and other options include: City Connect (with or without disconnect switches) Alarm Relay Module Battery brackets for seismic area protection (see page 2) Optional block space modules include: Fire Alarm Network Interface Card for Peer-to-Peer fire alarm network communications, supports either Class B or Class X operation Ethernet connectivity options include Building Network Interface Module (BNIC), SafeLINC Internet Interface, and BACpac Ethernet Portal Dual Class A IDNAC Isolator (DCAI) Dual RS-232 Module (for printer, PC annunciator or third party interface) VESDA Air Aspiration High Level Interface Serial DACT and Physical Bridge Network Modules 8 Zone IDC Modules Class A or B 4 Point Auxiliary Relay Module Compatible with Simplex ® remotely located: 4098-9757 QuickConnect2 and legacy 4098-9710 QuickConnect TrueAlarm smoke sensors 4003EC Small Voice Panels 4081 Series, 110 Ah Battery Chargers 4100-7400 Series Graphic Annunciators 4190 Series PC Annunciator 4190 Series Fiber Modems and Physical Bridges 4606-9102 Remote LCD Annunciator, 4100-9400 Series Remote InfoAlarm Command Centers, and 4602 Series Status Command Units (SCU) and Remote Command Units (RCU) Annunciators IP communicator compatibility * See page 6 for additional listing information. Additional listings may be applicable; contact your local Simplex product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. are the property of Tyco Fire Protection Products. S4010-0012-4 11/2015 Fire Control Panels UL, ULC Listed, Addressable Fire Detection and Control FM Approved* Basic Panel Modules and Accessories

4010 ES Series 4010 ES Fire Control Panels

Embed Size (px)

Citation preview

Page 1: 4010 ES Series 4010 ES Fire Control Panels

Features

Basic system includes: Capacity for up to 1000 addressable IDNet points, up

to 127 VESDA Air Aspiration Systems interface points and up to 254 addressable notification appliances with up to 2000 points of Annunciation; and up to 20 internal and external card addresses

Color-coded operator interface with membrane keypad includes 2 x 40 Super-twist LCD display, 3 programmable control keys and 6 programmable LEDs

CPU assembly includes dedicated compact flash memory for on-site system information storage and convenient Ethernet service port access

Includes an Enhanced System Supply (ESS) that provides power and battery charging (6 A output): Dual 3 A on-board IDNAC SLCs (signaling line circuit)

provide enhanced power delivery to addressable notification appliances

With an IDNAC SLC, a constant 29 VDC source voltage is maintained during alarm, even during battery operation, allowing strobes to operate at higher voltage with lower current and ensuring a consistent current draw and voltage drop margin under both primary power and secondary battery standby

Efficiencies include lower strobe currents, wiring distances up to 2 to 3 times farther than with conventional notification, support for more appliances per IDNAC SLC, ability to use smaller gauge wiring, all providing installation and maintenance savings with high assurance that appliances that operate during normal system testing will operate during worst case alarm conditions

IDNAC SLCs are compatible with both TrueAlert ES and TrueAlert addressable notification appliances, and remote 4009 IDNAC Repeaters to extend power and wiring distance even farther and extends supervisory capacity by up to 139 additional unit loads or 3 A

Addressable initiating device control is provided by on-board IDNet 2 dual loop SLCs that provide two electrically isolated channels that support TrueAlarm analog sensors and IDNet communications monitoring and control devices with an electrically isolated output channel allowing use with either shielded or unshielded, twisted or untwisted single pair wiring; and providing dual short circuit isolating output loops

Battery charger for up to 110 Ah batteries (UL) or up to 50 Ah batteries (ULC) (33 Ah max in control panel cabinet)

2 A programmable function auxiliary output Remote annunciator module support via RUI (Remote

Unit Interface) communications port, supports either Class B or Class A operation

48 LED panel mount annunciation provides 40 Red and 8 Yellow pluggable LEDs (select models, meets ULC requirements), optional LED kits are available to change individual LED color to Green or Blue to meet specific site requirements

1-Bay Cabinet

2-Bay Cabinet

1-Bay Cabinet with LED Annunciation

4010ES Panel Type Reference

Optional ESS mounted modules, door mounted modules, and other options include: City Connect (with or without disconnect switches) Alarm Relay Module Battery brackets for seismic area protection (see page 2) Optional block space modules include: Fire Alarm Network Interface Card for Peer-to-Peer fire

alarm network communications, supports either Class B or Class X operation

Ethernet connectivity options include Building Network Interface Module (BNIC), SafeLINC Internet Interface, and BACpac Ethernet Portal

Dual Class A IDNAC Isolator (DCAI) Dual RS-232 Module (for printer, PC annunciator or

third party interface) VESDA Air Aspiration High Level Interface Serial DACT and Physical Bridge Network Modules 8 Zone IDC Modules Class A or B 4 Point Auxiliary Relay Module Compatible with Simplex® remotely located: 4098-9757 QuickConnect2 and legacy 4098-9710

QuickConnect TrueAlarm smoke sensors 4003EC Small Voice Panels 4081 Series, 110 Ah Battery Chargers 4100-7400 Series Graphic Annunciators 4190 Series PC Annunciator 4190 Series Fiber Modems and Physical Bridges 4606-9102 Remote LCD Annunciator, 4100-9400

Series Remote InfoAlarm Command Centers, and 4602 Series Status Command Units (SCU) and Remote Command Units (RCU) Annunciators

IP communicator compatibility * See page 6 for additional listing information. Additional listings may be applicable;

contact your local Simplex product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. are the property of Tyco Fire Protection Products.

S4010-0012-4 11/2015

Fire Control Panels UL, ULC Listed, Addressable Fire Detection and Control FM Approved* Basic Panel Modules and Accessories

Page 2: 4010 ES Series 4010 ES Fire Control Panels

Features

4010ES Agency listings: UL 864, Fire Detection and Control (UOJZ), and

Smoke Control Service (UUKL) UL 2017, Process Management Equipment (QVAX) UL 1076, Proprietary Alarm Units-Burglar (APOU) UL 1730, Smoke Detector Monitor (UULH) ULC S527-99, Fire Detection and Control (UOJZC)

Introduction

4010ES Series Fire Detection and Control Panels provide leading edge installation, operator, and service features for customer applications in the mid-range addressable fire alarm systems market. An on-board Ethernet port provides fast external system communications to expedite installation and service activity. Dedicated compact flash memory archiving provides secure on-site system information storage of electronic job configuration files to meet NFPA 72 (National Fire Alarm and Signaling Code) requirements.

Modular design. A variety of functional modules are available to meet specific system requirements. Selections allow panels to be configured for either Stand-Alone or Networked fire control operation.

Mechanical Description

Mounting box provides convenient stud markers for drywall thickness and nail-hole knockouts for quicker mounting

Smooth box surfaces are provided for locally cutting conduit entrance holes exactly where required

The hinged User Interface panel easily opens for internal access

Modules are power-limited (except as noted, such as relay modules)

Doors include tempered glass inserts, boxes and doors are available in platinum or red

Box and door/retainer assemblies are included with Basic Panel assemblies

Cabinet assemblies are rated NEMA 1 and IP 30 Cabinet assembly design has been seismic tested and

is certified to IBC and CBC standards as well as to ASCE 7 categories A through F, requires battery brackets as detailed on data sheet S2081-0019

Panel Hardware

4010ES Block Space Option Cards mount to the left of the 4010ES ESS. There are 3 available 4” x 5” blocks for mounting 4010ES hardware options.

Other 4010ES Options: The 4010ES City Connect module or the optional Alarm Relay module mount directly to the ESS. These options are mutually exclusive.

Network Media modules mount directly to the 4010ES Network Interface Card.

The Battery Compartment located in the bottom of the 4010ES cabinet accepts two batteries, up to 33 Ah, without interfering with expansion module space.

The illustrations at the bottom of this page identify mounting locations available for optional 4010ES modules. (refer to page 7 for additional information)

Software Feature Summary

TrueAlarm individual analog sensing with front panel information and selection access

“Dirty” TrueAlarm sensor maintenance alerts, service and status reports including “almost dirty”

TrueAlarm magnet test indication appears as distinct “test abnormal” message on display when in test mode

TrueAlarm sensor peak value performance report

“Install Mode” allows grouping of multiple troubles for uninstalled modules and devices into a single trouble condition (typical with future phased expansion); with future equipment and devices grouped into a single trouble, operators can more clearly identify events from the commissioned and occupied areas

Module level ground fault searching assists installation and service by locating and isolating modules with grounded wiring

“Recurring Trouble Filtering” allows the panel to recognize, process, and log recurring intermittent troubles (such as external wiring ground faults), but only sends a single outbound system trouble to avoid nuisance communications

WALKTEST silent or audible system test performs an automatic self-resetting test cycle

2 S4010-0012-4 11/2015

4" x 5" Block A

4" x 5"

Block B

4" x 5"

Block D

Main System Supply

3 available 4”x5” block spaces for option cards

2nd bay of two-bay cabinet has 8 additional 4” x 5” block spaces for option cards (2 horizontal rows of 4 block spaces)

Note: Some block spaces may be used by basic panel features (see pages 5 and 6 for available space)

Mounting Locations for Optional Modules, One-Bay Cabinet

Page 3: 4010 ES Series 4010 ES Fire Control Panels

Operator Interface Features

Convenient and extensive operator information is provided using a logical, menu-driven display

Multiple automatic and manual diagnostics for maintenance reduction

Convenient PC programmer label editing

Password access control

Alarm and Trouble History Logs (up to 2000 total events) are available for viewing from the LCD, or capable of being printed to a connected printer, or downloaded to a service computer

Convenient Status Information. With the locking door closed, the glass window allows viewing of the display, status LEDs, and available operator switches. Features include a two-line by 40-character, wide viewing angle (super-twist) LCD with status LEDs and switches as shown in the illustration below.

LED indicators describe the general category of activity being displayed with the LCD providing more detail. For the authorized user, unlocking the door provides access to the control switches and allows further inquiry by scrolling the display for additional detail.

The following illustration identifies the primary functions of the operator interface.

6 SYSTEM STATUS INDICATOR LEDs provide system status indications, LEDs flash to indicate a change in status and remain on-steady after acknowledged until reset

3 PROGRAMMABLE FUNCTION SWITCHESwith yellow LED indicators

POINT STATUS CONTROL KEYS:Point Enable and DisableForce On or ArmForce Off or DisarmReturn On/Off or Arm/Disarm to Auto Mode

NUMERIC KEYPAD for point category and point selection (alphabet characters are not used at this time)

ADDITIONAL FUNCTION KEYS:Event Time RequestMore Information RequestLamp Test

Elevator Bypass

City Disconnect

Ground Fault

Waterflow-West

Waterflow-East

Custom label insert

LCD NAVIGATION CONTROL:Menu selectionVertical and Horizontal position selection buttons

2 X 40 LCD READOUT, LCD is backlighted during normal conditions, provides up to 40 characters for custom label information

FIRST ALARM DISPLAY operation can be selected for maintained display of first alarm until acknowledged

3 PROGRAMMABLE LEDs two selectable as Red or Yellow, one selectable as Green or Yellow

Ground Fault Latch

FIRE ALARM ACK acknowledges a Fire Alarm condition, logs the acknowledge, and silences the operator panel and all annunciator tone-alerts

PRIORITY 2 ACK acknowledges a Priority 2 Alarm condition, logs the acknowledge, and silences the operator panel and all annunciator tone-alerts

SUPV ACK acknowledges system supervisory conditions, logs the acknowledge, and silences the operator panel and all annunciator tone-alerts

TROUBLE ACK acknowledges system trouble conditions, logs the acknowledge, and silences the operator panel and all annunciator tone-alerts

ALARM SILENCE causes audible notification appliances to be silenced (depending on panel programming) typically after evacuation is complete and while alarm source is being investigated; may allow visible notification to continue (strobes still flashing)

SYSTEM RESET restores control panel to normal when all alarmed inputs are returned to normal

ULC SYSTEMS require designating a Ground Fault indicator

3 S4010-0012-4 11/2015

Page 4: 4010 ES Series 4010 ES Fire Control Panels

Overview. The 4010ES with ESS provides dual IDNet (IDNet 2) addressable initiating device Signaling Line Circuits (SLCs) that supervise wiring connections and the individual device communications status on the SLC. With 2-wire IDNet 2 SLCs, initiation, monitoring, and control devices such as manual fire alarm stations, TrueAlarm sensors, control relays, and sprinkler waterflow switches can communicate their identity and status and receive fire alarm system control. Additional addressable interface modules include circuit isolators, conventional IDC zone adapters, and interface to other system circuits such as fans, dampers, and elevator controls.

IDNet 2 Addressable Device Operation

Each addressable device on the IDNet communication channel is continuously interrogated for status condition such as: normal, off-normal, alarm, supervisory, or trouble. Both Class B and Class A operation is available. Sophisticated poll and response communication techniques ensure supervision integrity and allow for "T-tapping" of the circuits for Class B operation. Devices with LEDs pulse the LED to indicate receipt of a communications poll and can be turned on steady from the panel. With addressable devices, the location and status of the connected device is monitored, logged, and displayed on the operator interface LCD with each device having its own 40 character custom label for precise identification.

TrueAlarm Addressable Sensor Operation

Addressable initiating device communications include operation of TrueAlarm smoke and temperature sensors. Smoke sensors transmit an output value based on their smoke chamber condition and the CPU maintains a current value, peak value, and an average value for each sensor. Status is determined by comparing the current sensor value to its average value. Tracking this average value as a continuously shifting reference point filters out environmental factors that cause shifts in sensitivity.

TrueAlarm Addressable Sensor Reference

TrueAlarm Photo Sensor with Base

TrueAlarm Photo/Heat

Sensor in CO Base

Programmable sensitivity of each sensor can be selected at the control panel for different levels of smoke obscuration (shown directly in percent) or for specific heat detection levels. To evaluate whether the sensitivity should be revised, the peak value is stored in memory and can be easily read (or downloaded as a report) and compared to the alarm threshold directly in percent.

CO sensor bases combine an electrolytic CO sensing module with a TrueAlarm analog sensor to provide a single multiple sensing assembly using one system address. The CO sensor can be enabled/disabled, and can be used in LED/Switch modes and custom control. (refer to data sheet S4098-0052 for details)

TrueAlarm heat sensors can be selected for fixed temperature detection, with or without rate-of-rise detection. Utility temperature sensing is also available, typically to provide freeze warnings or alert to HVAC system problems. Readings can selected as either Fahrenheit or Celsius.

TrueSense Early Fire Detection. Multi-sensor 4098-9754 provides photoelectric and heat sensor data using a single 4010ES IDNet address. The panel evaluates smoke activity, heat activity, and their combination, to provide TrueSense early detection. For more details on this operation, refer to data sheet S4098-0024.

Diagnostics and Default Device Type

Sensor Status. TrueAlarm operation allows the control panel to automatically indicate when a sensor is almost dirty, dirty, and excessively dirty. The NFPA 72 requirement for a test of the sensitivity range of the sensors is fulfilled by the ability of TrueAlarm operation to maintain the sensitivity level of each sensor. CO Sensors track their 10 year active life status providing indicators to assist with service planning. Indicators occur at: 1 year, 6 months, and end of life.

Modular TrueAlarm sensors use the same base and different sensor types (smoke or heat sensor) and can be easily interchanged to meet specific location requirements. This allows intentional sensor substitution during building construction when conditions are temporarily dusty. Instead of covering smoke sensors (causing them to be disabled), heat sensors may be installed without reprogramming the control panel. The control panel will indicate an incorrect sensor type, but the heat sensor will operate at a default sensitivity to provide heat detection for building protection at that location.

IDNet Device Wiring Reference

IDNet Addressable Channel Capacity. The ESS provides dual electrically isolated IDNet 2 signaling line circuits (SLCs) that support up to 250 addressable monitor and control points intermixed on the same pair of wires. IDNet 2 SLCs are isolated from other system reference voltages to reduce common mode noise interaction with adjacent system wiring.

IDNet 2 SLC Wiring Specifications

Maximum Distance from Control Panel per Device Load

0 to 125 4000 ft (1219 m); 50 ohms

126-250 2500 feet (762 m); 35 ohms

Total Wire Length Allowed With “T” Taps for Class B Wiring

Up to 12,500 ft (3.8 km); 0.60 µF

Maximum Capacitance Between IDNet Channels

1 µF

Loading per device 0.8 mA supv., 1 mA alarm; 2 mA per activated device LED

Wire Type and Connections Shielded or unshielded, twisted or untwisted wire*

Connections Terminal blocks for 18 to 12 AWG

Compatibility includes: IDNet communicating devices and TrueAlarm sensors including QuickConnect and QuickConnect2 sensors; see data sheet S4090-0011 for additional reference

* Some applications may require shielded wiring. Review your system with your local Simplex product supplier.

4 S4010-0012-4 11/2015

IDNet Addressable Device Control

Page 5: 4010 ES Series 4010 ES Fire Control Panels

Addressable notification appliance communications include operation of TrueAlert and TrueAlert ES Visible only (V/O, strobe), Audible only (A/O, horn), Audible/Visible (A/V, horn/strobe), and strobes of Speaker/Visible (S/V) notification appliances. (S/V appliances require separate speaker wiring.) IDNAC SLC addressable communications allow each horn and strobe to be individually controlled using a single two-wire circuit, confirms the wiring connections to the individual notification appliance’s electronic circuit, and confirms communications between each appliance and the fire alarm control panel. Addressable communications increases supervision integrity versus conventional notification systems by providing supervision beyond the circuit wiring to each individual appliance and by constantly verifying the ability of each appliance to communicate with the control panel. Individual Appliance Status and Settings. The fire alarm control panel monitors and records each addressable notification appliance status, type of appliance, and its configured appliance settings. A fault in any individual appliance automatically reports a trouble condition to the control panel.

TrueAlert ES Addressable Appliance Reference

A/O (horn) V/O (strobe) A/V (horn/strobe)

Virtual NACs Provide Control Convenience. For control convenience, IDNAC notification appliances can be grouped into Virtual NACS (VNACs) for group control, grouping that can be made across SLCs, not defined by their wiring connection.

Panel Control Convenience. Applicable operation settings for each appliance can be programmed without having to replace appliances or remove them from the wall or ceiling. An appliance’s VNAC notification zone can be easily changed through programming without having to add additional circuits, conduit, and wiring. Audible and visible appliances for non-Fire Emergency Communications notification can be programmed to operate separately on the same pair of wires as the fire alarm notification appliances. The result is lower installation, retrofit, and overall life-cycle cost of ownership compared with traditional conventional notification systems.

Installation, Retrofit, and Life-Cycle Cost Benefits. With each addressable appliance capable of being controlled separately on the same two-wire IDNAC SLC, installation time and expense for both retrofit and new construction can be significantly reduced. When Class B wiring is used, wiring can be “T-tapped” allowing more savings in distance, wire, conduit (size and utilization), and overall installation efficiency.

Location Information, Diagnostics and Troubleshooting. Each addressable notification appliance has its own 40 character custom label to identify the location of the appliance and to aid in troubleshooting fault conditions. In conventional notification systems, conventional appliances are not capable of communicating with the control panel. Fault reporting on a conventional system is limited to the circuit wiring and the entire area (zone) covered by appliances on the notification appliance circuit (NAC) making it much more difficult and costly to locate and correct the source of a

problem. Using the TrueAlert magnet test allows each appliance to individually identify its candela setting and address and to briefly operate if desired, and using the TrueAlert ES Appliance Self-Test feature provides detailed performance verification per appliance.

TrueAlert ES Appliance Self-Test Operation

On-Board Test Sensors. TrueAlert ES appliances are equipped with on-board sensors to detect strobe and/or horn output allowing efficient and unobtrusive Self-Testing. When Automatic Self-Test is initiated from the control panel, each appliance within the selected VNAC group will briefly operate and then report its Self-Test status to the control panel, all within several seconds. Silent Self-Test can be selected to test only visible appliance if desired. The control panel is in a trouble condition during testing and in the event of an alarm, Self-Test is automatically terminated. Additionally, Automatic Self-Test can be scheduled to occur at a convenient time on a regular basis.

Automatic Self-Test results are communicated to the control panel with a time and date stamp and are stored in memory. Results are viewable at the front panel display and printed reports can be generated from the panel service port.

Individual Self-Test is selected from the control panel when individual appliances need to be observed to operate. Each appliance in the selected VNAC group will turn on its LED until individually activated by applying a magnet. After performing the individual test, the appliance LED turns off to indicate completion. Results are recorded the same as during the automatic test.

IDNAC SLC Hardware Reference

The Enhanced System Supply provides two, 3 A IDNAC SLCs for control and power to TrueAlert ES and TrueAlert addressable notification appliances. Both power supplies incorporate an efficient switching design that provides a regulated output of 29 VDC, even during battery operation. With 29 VDC minimum output at the panel, addressable notification SLCs can support wiring distances 2 to 3 times farther than available with conventional notification, or support more appliances per SLC, or work with smaller gauge wiring, or combinations of these benefits. The result is installation and maintenance savings with high assurance that appliances that operate during normal system testing will operate during worst case alarm conditions.

IDNAC SLC Appliance Wiring Reference

IDNAC SLC Capacity: Up to 127 addresses and up to 139 unit loads (appliances are typically one unit load, devices such as Isolators may require more than one load, refer to individual device data sheet for specific information)

Recommended Wire Type UTP, unshielded twisted pair

Maximum wire length allowed with “T-Taps” for Class B wiring, per SLC

10,000 ft (3048 m)

Maximum wire length per SLC to any appliance

4000 ft (1219 m)

Appliance Supervisory Current

1 unit load = 0.8 mA per appliance

Wiring Connections Terminals for 20 to 12 AWG (0.52 mm2 to 3.31 mm2)

5 S4010-0012-4 11/2015

IDNAC SLC Control of TrueAlert and TrueAlert ES Addressable Notification

Page 6: 4010 ES Series 4010 ES Fire Control Panels

Master Controller (CPU)

The 4010ES Master Controller includes dedicated 2GB compact flash Mass Storage memory for on-site system information storage and convenient Ethernet service port access

Convenient front panel accessed Ethernet port for quick and easy download of site-specific programming

AND, firmware enhancements are made via software downloads to the on-board flash memory

Every downloaded job is automatically stored to Compact flash without overwriting earlier versions providing a means for recovering previous configurations

Downtime is reduced because the system stays running during download

Modifications can be uploaded as well as downloaded for greater service flexibility

Mass Storage allows job specific files to be stored in the control panel such as test and inspection reports, record drawings, specifications, and more...

Ethernet connectivity options include Building Network Interface Module (BNIC) and SafeLINC Internet Interface

RUI (Remote Unit Interface) communications port supports either Class B or Class A operation for remote annunciation equipment

Basic Panel Description

4010ES panels with ESS include:

An Operator Interface, Master Controller with 2 GB Compact Flash, IDNet 2 dual loop communications that provides Class B or Class A operation for up to 250 addressable IDNet points, with dual short circuit isolating loop outputs, and 6 A Enhanced System Supply (ESS)

RUI Class B or Class A communications port for remote annunciation devices

Support for up to 20 internal and external card addresses

Other standard features may be provided depending on model (see model selection below for additional details on specific models)

Cabinet and door

6 A Enhanced System Supply details:

Two, 3 A Class B IDNAC SLCs for up to 254 addressable notification appliances; Class A operation is available using the 4010-9930 Dual Class A IDNAC Isolator (DCAI) module

Up to 2 A of auxiliary power

110 Ah (UL)/50 Ah (ULC) battery charger (33 Ah maximum in the control panel cabinet)

Low Battery Voltage Cutout is selectable when required (required for ULC listing applications)

2 A for Regulated 24 DC operation; 1 programmable auxiliary relay rated for 2 A @ 32 VDC

6 S4010-0012-4 11/2015

Model Panel Color

Language & Voltage

Listings Features Supv.

Current Alarm

Current Available

Option Blocks (see notes below)

4010-9601 Red English

120 VAC UL, CSFM,

FM

Basic 1- Bay Panel with 2x40 LCD Operator Interface, 6 A ESS/battery charger, (1) Two-loop Isolated IDNet 2 Communications Channel, Class A or Class B, with support for up to 250 addressable IDNet points; and two, 3 A, Class B, IDNAC SLCs with support for up to 254 addressable notification appliances

256 mA 390 mA 3

4“x5” blocks

4010-9602

4010-9602BA* Platinum

4010-9701 Red English 220 - 240

VAC UL, FM

4010-9702 Platinum

4010-9603 Red English

120 VAC UL, ULC,

CSFM, FM

Same features as above with 48 LED annunciation; alarm current includes 24 annunciator LEDs activated

276 mA 455 mA 4010-9604 Platinum

4010-9722 Platinum English

220 - 240 VAC

UL, FM

Basic 2- Bay Panel with 2x40 LCD Operator Interface, 6 A ESS/battery charger, (1) Two-loop Isolated IDNet 2 Communications Channel and (1) Four-loop Isolated IDNet 2+2 Communications Module, Class A or Class B, with support for up to 500 addressable IDNet points; and two, 3 A, Class B, IDNAC SLCs with support for up to 254 addressable notification appliances

256 mA 390 mA 9

4“x5” blocks

* BA model is assembled in the USA. Current Notes: 1. Basic panel current does not subtract from the 6 A output rating. 2. Supervisory and alarm current specifications are for determining battery standby requirements. 3. Current specifications include an active RUI channel. 4. IDNet channel device current is not included, refer to page 7 for details. 5. IDNAC channel notification appliance current is not included, calculate separately per connected devices.

Basic Panel Model Selection

Page 7: 4010 ES Series 4010 ES Fire Control Panels

7 S4010-0012-4 11/2015

Single Block Option Modules, Select Three (3) Maximum if No Dual Block Module is Selected; Select One (1) Maximum if a Dual Block Module or the Module Bracket is Selected

Model Features Supervisory

Current Alarm

Current Option Block

Usage

4010-9912 Serial DACT, includes 2, 2080-9047 cables, 14 ft (4.3 m) long, RJ45 plug and spade lugs

30 mA 40 mA

1 Block (must mount

in block D under ESS)

4010-9908 4 Point Aux Relay Module 15 mA 60 mA 1 Block

4010-9916 Voltage Regulator Module, 22.8 to 26.4 VDC (25 VDC nominal); isolated and resettable output; includes earth detection circuit and trouble relay for status monitoring

3 A maximum with 2.5 A load

4.9 A maximum

with 4 A load1 Block

4010-9918 Dual RS-232 Module 60 mA 60 mA 1 Block

4010-9930

Dual Class A IDNAC Isolator (DCAI); converts a single Class B IDNAC SLC input to two Class A or two Class B SLC outputs; provides short circuit isolation between each Class A or B output circuit; requires one IDNAC address; the total current remains controlled by the Class B input source SLC at 3 A maximum; select up to 2 per IDNAC SLC

8.3 mA 18.5 mA

1 Block

Note: One DCAI module

can be mounted on

the ESS

4010-9915 BACpac Ethernet Portal Module; requires 4010-9918 RS-232 Module (no address required)

123 mA 123 mA 1 Block

4010-9901 VESDA HLI 60 mA 60 mA 1 Block

4010-9929

IDNet 2+2 Module, 250 point capacity; electrically isolated output with four short circuit isolating Class B or Class A output loops; alarm currents for 50 and above devices includes 20 device LEDs in alarm; see above for individual device currents

No device 50 mA 60 mA

1 Block 50 devices 90 mA 150 mA

125 devices 150 mA 225 mA

250 devices 250 mA 350 mA

Dual Vertical Block (Flat) Modules, Select One, or Two with 4010-9928 Bracket Kit (except for Media Cards)

Model Features Option Block Usage Supervisory

Current Alarm

Current

4010-9928 For 1-Bay Panels Only: Dual Vertical Block Card Mounting Kit, allows selecting two, dual Vertical Block (flat) modules from the list below

2 Vertical Blocks NA NA

4010-9922 Modular Network Interface Card (requires two media modules, see below)

2 Vertical Blocks 30 mA 30 mA

4010-9818 Network Media Card Wired N/A (mounts to 4010-9922)

55 mA 55 mA

4010-9819 Network Media Card Fiber Optic 25 mA 25 mA

4010-9914 Building Network Interface Card 2 Vertical Blocks 236 mA 236 mA

4010-9923* SafeLINC Internet Interface 2 Vertical Blocks 115 mA 115 mA

4010-9924* Modem Physical Bridge Class B Requires one of the 2 Vertical Block spaces on the

4010-9928 Mounting Kit

193 mA 193 mA

4010-9925* Modem Physical Bridge Class X 246 mA 246 mA

4010-9926** TCP/IP Physical Bridge Class B 3 Block “L” Shape, requires one of the 2 Vertical Block spaces on the 4010-9928

Mounting Kit, plus Block D

196 mA 196 mA

4010-9927** TCP/IP Physical Bridge Class X 236 mA 236 mA

*UL, ULC, and CSFM listed. Continued on next page ** FM Approved only.

Addressable Channel Loading Reference Device LoadSupervisory

Current Alarm Current

IDNet 2 and IDNet 2+2 Communications Channel Output

for every 50 Devices 40 mA 1 mA per device in alarm; 2 mA per activated device LED

IDNAC Communications Channel Output for every 50 Appliances 40 mA calculate per selected appliances

Addressable Device Load Specifications for Battery Standby

Block Space Option Card Selection

Note: Refer to diagrams on pages 2 and 9 for Option Module availability. Supervisory and Alarm current specifications are for determining battery standby requirements.

Page 8: 4010 ES Series 4010 ES Fire Control Panels

8 S4010-0012-4 11/2015

Door thickness4-3/4"(121 mm)

Exposed cabinet for semi-flush mounting

1/2" (12.7 mm)minimum

24" (610 mm)

Total depth, box and door

11-11/16"(296 mm)

Box depth,6-29/32"(175 mm)

4" stud

6" stud

Knockout screw/nail holes (for semi-flush mounting)

Stud alignment markers, each side

Front view, box outline without door Side view with door attached

1 Bay height =22" (559 mm)

2 Bay height = 40" (1016 mm)

Reserved for Batteries

16" (406 mm)

Use 4 holes to Secure box to wall

Dual Vertical Block (Slot) Modules, Select One if no Dual Vertical (Flat) Modules are Selected

Model Features Option Block Usage Supervisory

Current Alarm

Current

4010-9920 8 Zone Initiating Device Circuit - Class B 2 Vertical Blocks (mother/daughter card)

75 mA 195 mA 4010-9921 8 Zone Initiating Device Circuit - Class A

Model Features Supervisory

Current Alarm

Current Mounting Requirements

4010-9909 City Connect Module w/ disconnect switches 20 mA 36 mA Select one maximum, mounts on ESS

4010-9910 City Connect Module 20 mA 36 mA

4010-9911 Alarm Relay Module 15 mA 37 mA

4100-5128 Battery Distribution Terminal Block, mounts to side of box, required when battery connection leaves the 4010ES box (also used in the 4100ES fire alarm control panel)

Cabinet Dimension Reference

Additional Panel Option Selection (block space is not used)

Additional Block Space Option Card Selections (Continued)

Page 9: 4010 ES Series 4010 ES Fire Control Panels

LED Kits (LEDs are pluggable, use to change color for local application requirements)

Model Description

4100-9843 8 Yellow LED Kit

4100-9844 8 Green LED Kit

4100-9845 8 Red LED Kit

4100-9855 8 Blue LED Kit

End User Programming Tools

Model Description

4100-8802 End User Programming Unit Software

4100-0292 Custom Label Editing (USB Dongle)

4100-0295 Port Vectoring Setup and Control (USB Dongle)

4100-0296 Access Level/Passcode Editing (USB Dongle)

4100-0298 WalkTest Configuration Setup and Control (USB Dongle)

Factory Programming Options

Model Description

4010-8810 Factory Programming (select)

4010-0831 Custom Labels and Programming (requires 4010-8810)

4" x 5" Block A

Main System Supply

4" x 5" Block B

4" x 5" Block D

4" x 5" Block B

4" x 5" Block D

4" x 5" Block F

4" x 5" Block H

4" x 5" Block A

4" x 5" Block C

4" x 5" Block E

4" x 5" Block G

First bay of two-bay cabinet has 3 available 4”x5” block spaces for additional option cards

Second bay of two-bay cabinet has 8 additional 4” x 5” block spaces for additional option cards (2 horizontal rows of 4 blocks) Note: Some spaces may be used by basic panel, see pages 5 and 6 for available space

4" x 5" Block A

4" x 5"

Block B

4" x 5"

Block D

Main System Supply

First bay of one-bay cabinet has 3 available 4”x5” block spaces for additional option cards

Note: Some spaces may be used by basic

panel, see pages 5 and 6 for available space

9 S4010-0012-4 11/2015

Miscellaneous Accessories

Cabinet One and Two Bay Loading Reference

Page 10: 4010 ES Series 4010 ES Fire Control Panels

10 S4010-0012-4 11/2015

Model Description Card Address Consumption

Card Address Allocation

Notes

Control Panels (Select One)

4010-9601 4010-9602 4010-9701 4010-9702

2x40 Display, (1) IDNet 2 Communications Channel, Single Bay Box

2

4010-9603 4010-9604

2x40 Display, (1) IDNet 2 Communications Channel; 48 Pluggable LED Module, Single Bay Box

3

4010-9722 2x40 Display, (1) IDNet 2 Communications Channel and (1) IDNet 2+2 Communications Channel, Two-Bay Box

3

Panel Option Cards (Select As Required)

4010-9901 Flat VESDA HLI Card 1

4010-9922 Flat Network Card 1

4010-9908 4 Point Flat Aux Relay Module 1

4010-9912 Serial DACT 1

4010-9923 SafeLINC Internet Interface Card 1

4010-9914 Building Network Interface Card 1

4010-9918 Dual RS-232 Module 1

4010-9920 8 Zone Initiating Device Circuit - Class B 1

4010-9921 8 Zone Initiating Device Circuit - Class A 1 4010-9929 IDNet 2+2 Communications Module 1

Remote Annunciation (Select As Required)

4100-9401 Red Cabinet, English

Remote InfoAlarm Command Center

2

4100-9403 Platinum Cabinet, English 2

4100-9441 Red Cabinet, with blank inserts for key labels

2

4100-9443 Platinum Cabinet, with blank inserts for key labels

2

4606-9102 4010ES RUI LCD Annunciator, English 1

4602-9101 Status Command Unit (SCU) LED Annunciator 1

4602-9102 Remote Command Unit (RCU) LED Annunciator w/control 1

4602-9150 Graphic I/O RCU/SCU Assembly for custom annunciator panels 1

4602-7101 Graphic I/O RCU/SCU Assembly for custom annunciator panels 1

4602-7001 RCU for cabinet mount 1

4602-6001 SCU for cabinet mount 1

4100-7401 24 Point I/O Graphic Module for custom annunciator panels 1

4100-7402 64/64 LED Switch Controller for custom annunciator panels 1

4100-7403 32 Point LED Driver Module for custom annunciator panels 1

4100-7404 32 Point Switch Input Module for custom annunciator panels 1

Total Card Addresses (Not to Exceed 20) TOTAL

4010ES Card Address Allocation

The 4010ES has a maximum Internal and External Card Address Limit of 20 Card Addresses. Use the Table below to calculate 4010ES card address allocation.

INSTRUCTIONS: Below is a list of 4010ES equipment and the quantity of card addresses they consume

1. For the applicable control panel, write in the Card Address Consumption value in the Card Address Allocation column. (Note: Only select 1 control panel)

2. For the option cards to be installed on the 4010ES, write in the Card Address Consumption value in the Card Address Allocation column.

3. Total the Card Address Allocation column (total must not exceed 20).

Page 11: 4010 ES Series 4010 ES Fire Control Panels

11 S4010-0012-4 11/2015

Input Current AC 4 A maximum, 120 VAC @ 60 Hz nominal

Battery 9 A maximum @ 24 VDC (during battery operation)

ESS Power Supply Output Ratings

Power Supply Output Rating

6 A output for “Special Application” appliances Note: The 6 A output rating of the ESS was determined such that optional module currents, and external device and appliance currents can be directly added together, not to exceed 6 A total.

Output switches to battery backup during mains AC failure or brownout conditions

IDNAC SLC Ratings 3 A, regulated 29 VDC during Alarm, 127 addresses, 139 unit loads; DC-DC converter circuit is >92% efficient over operating range

IDNAC SLC Wiring

Output terminals are rated for 20 to 12 AWG with duplicate output terminals rated for two wires each, allowing up to four (4) Class B branch circuit T-taps to be made in the cabinet; additional T-taps may be made in external wiring junction cabinets or boxes

Auxiliary Power Tap 2 A maximum, rated 19.1 to 31.1 VDC

Compatible Special Application Appliances

Simplex TrueAlert ES and TrueAlert addressable notification appliances; contact your Simplex product representative for compatible appliances

Battery Charger Rating (sealed lead acid batteries)

Battery capacity range UL listed for battery charging of 6.2 Ah up to 110 Ah; ULC listed for charging up to 50 Ah batteries; batteries above 33 Ah require separate cabinet

Charger characteristics and performance

Temperature compensated, dual rate, recharges depleted batteries within 48 hours per UL Standard 864; to 70% capacity in 12 hours per ULC Standard S527

Environmental Operating Temperature 32° to 120°F (0° to 49° C)

Operating Humidity Up to 93% RH, non-condensing @ 90° F (32° C) maximum

Additional Technical Reference

Installation Instructions 579-1150

Operating Instructions 579-969

Subject Data Sheet Subject Data Sheet

4010ES Agent Release Applications and Accessories

S4010-0005 Network Communications S4100-0056

Agent Release Accessories S2080-0010 Multi-Signal Fiber Optics S4100-0049

Building Network Interface S4100-0061 4602 Series SCU/RCU S4602-0001

SafeLINC Internet Interface S4100-0062 PC Annunciator S4190-0013

Interface to VESDA Air Aspiration Detection Systems

S4100-0026Addressable Device Compatibility, IDNet Communication Sensors and Devices

S4090-0011

Serial DACT (SDACT) S2080-0009 4009 IDNAC Repeater S4009-0004

Fire Alarm Network Overview S4100-0055 4003EC Voice Control Panel S4003-0002

4606-9102 Remote LCD Annunciator S4606-0002 120 VAC Desktop Remote Printer S4190-0011

Graphic I/O Modules S4100-0005 110 Ah Batteries and Cabinets S2081-0012

Remote InfoAlarm Command Center S4010-0008 Remote 110 Ah Battery Chargers and Cabinets S4081-0002

PC Annunciator S4190-0013 BACpac Ethernet Portal Module S4100-0051

TCP/IP Physical Bridge S4100-0029 Network Physical Bridge S4100-0057

Additional Compatible Equipment and Reference

General Specifications

Page 12: 4010 ES Series 4010 ES Fire Control Panels

TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. VESDA is a trademark of Xtralis Pty Ltd. NFPA 72 and National Fire Alarm and Signaling Code are trademarks of the National Fire Protection Association (NFPA). ASHRAE and BACnet are trademarks of ASHRAE, American Society of Heating, Refrigeration, and Air Conditioning Engineers.

Tyco Fire Protection Products • Westminster, MA • 01441-0001 • USA S4010-0012-4 11/2015

www.simplex-fire.com © 2015 Tyco Fire Protection Products. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.