September 9, 2013 ECS File No. 08-220832.00 Ms. Sandy Dooley 44 East Terrace South Burlington, VT 05403 Re: Fuel Oil UST removal Dooley Residence 44 East Terrace, South Burlington, Vermont Dear Ms. Dooley: On 3 September 2013, Environmental Compliance Services (ECS) completed a Closure Assessment for one 275-gallon #2 fuel oil underground storage tank (UST) at the above-referenced site. Enclosed are UST closure assessment reports, a site sketch with PID readings and photographs. A copy of this report will be submitted to the Vermont Department of Environmental Conservation (VT DEC) on your behalf. Findings: One 275-gallon fuel oil UST was removed. The tank was in poor condition with several small holes and rust. The UST is greater than 25 years old and has been out of use since the installation of natural gas at the site. Photoionization detector (PID) soil headspace readings were detected at values ranging from 0.0 to 916 parts per million (ppm), above the VT DEC soil threshold value for fuel oil of 10 ppm. Olfactory evidence of fuel oil contamination was noted. ECS field personnel and Enpro Services Inc., used the onsite mini-excavator in an attempt to define the limits of the contamination. Due to space limitations and the proximity of the UST to the foundation of the house, the limits of contamination were not defined. The excavation stopped at approximately 6 feet below the ground surface (bgs) where the footer of the foundation wall was encountered. Groundwater was not encountered in the excavation however; due to the groundwater intrusion near the bottom of the foundation wall in the basement, ECS believes that the depth to groundwater may be as high as 7 feet bgs during seasonal water table fluctuations. The soil consisted of very dry fine sand with trace silt. All soils were backfilled into the excavation.

44 East Terrace Re: Fuel Oil UST removal - … · Re: Fuel Oil UST removal Dooley Residence 44 East Terrace, South Burlington, Vermont ... used the onsite mini-excavator in an attempt

  • Upload
    votu

  • View
    212

  • Download
    0

Embed Size (px)

Citation preview

September 9, 2013

ECS File No. 08-220832.00

Ms. Sandy Dooley

44 East Terrace

South Burlington, VT 05403

Re: Fuel Oil UST removal

Dooley Residence

44 East Terrace, South Burlington, Vermont

Dear Ms. Dooley:

On 3 September 2013, Environmental Compliance Services (ECS) completed a Closure Assessment for

one 275-gallon #2 fuel oil underground storage tank (UST) at the above-referenced site. Enclosed are

UST closure assessment reports, a site sketch with PID readings and photographs. A copy of this report

will be submitted to the Vermont Department of Environmental Conservation (VT DEC) on your behalf.

Findings: One 275-gallon fuel oil UST was removed. The tank was in poor condition with

several small holes and rust. The UST is greater than 25 years old and has been

out of use since the installation of natural gas at the site. Photoionization

detector (PID) soil headspace readings were detected at values ranging from 0.0

to 916 parts per million (ppm), above the VT DEC soil threshold value for fuel

oil of 10 ppm. Olfactory evidence of fuel oil contamination was noted.

ECS field personnel and Enpro Services Inc., used the onsite mini-excavator in

an attempt to define the limits of the contamination. Due to space limitations and

the proximity of the UST to the foundation of the house, the limits of

contamination were not defined. The excavation stopped at approximately 6 feet

below the ground surface (bgs) where the footer of the foundation wall was

encountered. Groundwater was not encountered in the excavation however; due

to the groundwater intrusion near the bottom of the foundation wall in the

basement, ECS believes that the depth to groundwater may be as high as 7 feet

bgs during seasonal water table fluctuations. The soil consisted of very dry fine

sand with trace silt. All soils were backfilled into the excavation.

The basement of the residence was inspected and screened with a PID along the

west wall were the UST was located. The copper feed line had previously been

cut and capped in place. The PID readings in the gap of the foundation where the

feed line came in was 0.2 ppm. The ambient air in the basement was 0.7 ppm.

No petroleum related odors were observed in the basement by ECS during the

screening or historically by the homeowner.

Recommendations: ECS recommends an Initial Site Investigation at the site to determine the extent

of contamination and if groundwater has been impacted. Based on the Vermont

Department of Environmental Conservation (VT DEC) “Investigation and

Remediation of Contaminated Properties Procedure” updated April 2012, an

additional vapor intrusion evaluation will be necessary due to PID readings

>10ppm within 5 feet of the house.

ECS has appreciated the opportunity to assist you with this work. Please contact me at (802) 241-4131 if

you have any questions or need additional information.

Sincerely,

ENVIRONMENTAL COMPLIANCE SERVICES, INC.

Jeff Girard Tom Murphy

Environmental Scientist Senior Scientist

cc: Ms. Sue Thayer, VTDEC (upon client approval)

Scott Buckley, Enpro Services, Inc.

Attachments: ECS Closure Assessment Report

VT DEC UST Permanent Closure Form

Site Sketch With PID Readings

Photographs

Environmental Compliance Services

UST Closure Assessment Report

Site Name: Dooley Residence Date: 9/3/13

Site Address: 44 East Terrace On-Site ECS Staff: Jeff Girard

Site Town, State, Zip: South Burlington, Vermont 05403 Weather: 65 degrees F

UST Facility ID #: 5554131 ECS Client: Enpro Services, Inc.

Cleaning Contractor: Enpro Services, Inc.

Removal Contractor: Enpro Services, Inc.

Setting: Residential home

Closed UST Info:

UST

#

Capacity

(gallons)

Contents Condition Backfill Materials Native Soils Depth to

Ground

Water

Depth to

Bedrock

Comments

1 275 #2 Fuel Oil poor Native soils and

clean fill

Very dry fine sand,

trace silt

N/A N/A Tank installed greater than 25

years ago, in poor condition,

with several small holes in the

bottom

Closed Piping/Dispenser Information:

Location Condition Backfill Materials Native Soils Depth to

water

Depth to

Bedrock

Comments

Fill and vent

pipes located

directly above

tank

good Native soils and clean

fill

Very dry fine sand,

trace silt

N/A N/A Piping in good condition

Environmental Observations

Location Range of PID Readings

(ppm)*

Visual Evidence of Contamination

(odors, sheens, discoloration)

Comments

excavation 0.0 – 916 ppm Odors, approximately 2” crusty, stained soil

directly under tank

Bottom of excavation was 6 feet bgs and had a PID reading

of 402 ppm.

Highest PID reading detected at 5 feet bgs (bottom of tank)

was 916 ppm.

PID Make: Rae Model: MiniRAE 3000 Screening Method: Sealed in Ziploc, Agitated, Headspace Screened

Calibration: 100 ppm isobutylene

Environmental Compliance Services

UST Closure Assessment Report

Soil and Groundwater Sampling N/A

Remedial Activities: NA - all soils were backfilled into the excavation.

Stockpile Information: NA - all soils were backfilled into the excavation.

VT DEC Contact Info: On 3 September 2013, Beth Erickson of ECS contacted Jaymi Cleland of the VT DEC UST Program.

Potential receptors:

Type Description Distance Direction Position rel

to USTs

Type Description Distance Direction Position rel

to USTs

Surface Water NA NA NA NA Stormwater Stormdrain

along East

Terrace

131 ft North Cross-

gradient

Drinking

Water

Municipal NA NA NA Underground

Utilities

Underground

power

10 feet South Cross-

gradient

Septic Municipal NA NA NA Manholes NA NA NA NA

Basements 44 East Terrace < 1’ East Cross-

gradient

Special Notes: Groundwater was not encountered in the excavation. PID readings ranged from 0.2 – 0.7 ppm in the basement at 44 East Terrace. No

petroleum related odors were observed in the basement by ECS during the screening or historically by the homeowner.

Underground Storage Tank and Piping Closure Form Page 1 of 3

Vermont Agency of Natural Resources, Department of Environmental Conservation Waste Management and Prevention Division

http://www.anr.state.vt.us/dec/wastediv/index.htm_________________________________________________________________________________________________

Important: All closures must be scheduled with the Underground Storage Tank Program at least 5 business daysprior to the commencement of closure. Please call 802-828-1138

Section A. Facility/Ownership Information

Facility ID #: _______________________ SMS # (if applicable) : _________________________

To find if a facility has an ID # and/or SMS# please use WMID: http://www.anr.state.vt.us/wmid/. If there is no Facility ID then please contact the UST Program 802-828-1138.

Facility Name: ____________________________________________________ # of employee’s _________

Street Address: _____________________________________ City/Town: ___________________________

Type of Facility: ____Commercial/industrial; ____ Retail ____Residential; ____ Service Station; ____ Institutional; ____Farm; ____ Federal; ____ Bulk; ____ Fish Hatchery

Owner of UST(s) to be closed: _________________________ Owner Telephone: _____________________

Owner mailing address: ___________________________________________________________________

Owner Email: ___________________________________________________________________________

Contact (if different from owner):__________________________Contact Telephone: __________________

Contact Email: _________________________________________________

Landowner (if different than tank owner):_____________________________________________________________

Section B. Closure Information

What components will be closed/removed? UST system____; Tanks only_____; Piping only ____ .

Reason for closure/removal? Liability: ___; Replacement: _____; Abandoned: _____; Suspected leak: _____.

UST # Product Tank Age Size (gal)

Tank condition(excellent, good, fair, poor) Piping Age

Piping condition(excellent, good, fair,poor)

Proximity (ft.)of tanks to buildings / structures

Have any tanks been closed in-place? UST #______ Authorized by: ________________ Date: _______

Type of material used to closed tank in place (Water is not allowed):______________________________________

Disposal/destruction of removed UST(s) Location: __________________ Method: _________ Date: _______

Amount (gal) and type of waste generated from USTs: ____________________________________________

(Tank contents are hazardous wastes and must be handled as such unless recovered as usable product; sludge and solids are not usable/recyclable products and must be handled as hazardous waste. Please contact the Hazardous Waste program with any questions 802-828-1138).

Tank cleaning company (must be trained in confined space entry): __________________________________

5554131 NA

Ms. Sandy Dooley Residence NA

44 East Terrace South Burlington

X

Ms. Sandy Dooley NA

44 East Terrace, South Burlington, VT 05403

[email protected]

NA NA

NA

NA

X

1 heating oil >25 years 275 poor >25 years good <1 foot

NA NA NA

NA

Burnett Scrap Metal Recycling 9/4/13

5 gallons

Enpro Services, Inc.

UST and Piping Closure Form Page 2 of 3 Facility ID #_______________________

Certified hazardous waste hauler: _________________________________________________________

Generator ID #: ________________________________________________________________________

Section C. Initial Site Characterization (Work in this section must be completed by a professional environmental

consultant or hydro geologist with experience in environmental sampling for the presence of hazardous materials. A full report from the consultant must accompany this form.

Excavation Information. Some removals require more than one excavation. Identify as A, B, C, etc.

Tank #, excavation

A,B,CDepth

(ft.)

Excavation size

(sq. ft.)Peak PIDreading

Depth ofPeak (ft.)

Avg. PIDreading

Bedrockdepth (ft.)

Groundwater?(Y/N) and depth Soil type

Locate all readings and samples on a site diagram and submit with this form and site assessment

Dig Safe # ________________________

PID Make: ____________________ Model: ____________ Calibration (date/time/gas) __________________

Have any soils been polyencapsulated on site? _____NO; ____YES # cubic yds: _____

PID range > zero: ________ppm to_____________ppm

Have any soils been transported off site? _____NO; _____YES # cubic yds: _________

Location transported to: __________________________________ Approved by: _______________________

Amount of soil backfilled (cubic yds.): ___________________ PID range > zero: ______ppm to_________ppm

Have limits of contamination been defined? ____NO; ____YES. Other on-site contamination? ____NO; ____YES

Is contamination in contact with building foundation? _____No; _____Yes, If Yes, PID reading; ________ppm

Number of soil samples collected for laboratory analysis: __________ Results due date: ______________

Free Phase product encountered? _____NO; _____YES Thickness: ____________ Sheen: ________________

Groundwater encountered? _____NO; _____YES Depth: ______

Are there existing monitoring wells on-site? _____NO; _____YES How many? ______ (Locate on site diagram)

Have new monitoring wells been installed? _____NO; _____YES (Locate on site diagram)

Samples obtained from monitoring wells for lab analysis? _____NO; _____YES Results due date: _________

Is there a water supply well on site? ____NO; _____YES Type: ____Shallow; _____Rock; _____Spring

Number of public water supply wells located within 0.5-mile radius: _____ Min. distance (ft); _____

Receptors impacted:

____Soil; _____Indoor Air; ____ Ambient Air; ____Groundwater; ____Surface Water; ____Water Supply

5554131

Enpro Services, Inc.

NA

1 6 45 916 5 249 NA not encountered very dry fine sand, trace silt

Rae MiniRAE 3000 9/3/13 @7:00 100 ppm isobutylene

X NA

0.6 916

X NA

NA NA

10 0.6 916

X X

X 727

NA NA

X NA NA

X NA

X

X

X

X

0 NA

X X

UST and Piping Closure Form Page 3 of 3 Facility ID________________________

Any release must be reported immediately by calling 802-828-1138 (if after hours please call 800-641-5005)

Name of WMPD staff that the release was reported to: ______________________ Date: ___________

Spill # (issued by WMPD staff when release is reported):_______________________________________

Section D: Tanks and Piping Remaining or to be Installed. Regardless of size or use, list all USTs and ASTs currently at facility or to be installed at facility. For "Tank Status," indicate "abandoned," "in use," or "to be installed*." This includes any UST/ASTs used to store fuel for heat at a public building (propane tanks do not need to be listed)

Tank #UST or AST? Product

Size (gallons)

Tank Use(heat, backup

generator, etc) Tank age Tank Status Piping age

Piping Status

*Note: Some installations may require permits and advance notice to the UST Program. Please call the UST Program with any questions 802-828-1138

Section E. Statements of UST closure compliance

I, _____________________________________________, as the environmental consultant on-site, I hereby (Please print name)

certify that the site assessment requirements were performed in accordance with DEC policy and regulations, and that information which I have provided on this form is true and correct to the best of my knowledge.

Signature: __________________________________________________________________________

Company: _________________________________ Telephone#:_____________________________

Date of Assessment: ____________________________ Date of Closure: _________________________

Return this form along with complete narrative report and photographs to the Department of Environmental Conservation (DEC), Underground Storage Tank Program within 10 days of closure. Do not delay submission of the site assessment if waiting for lab analysis results. Labs can be emailed separately.

An electronic version of the report from an environmental consultant covering all aspects of closure and site

assessment, complete with photographs and any other relevant data, must accompany this form and be emailed to

WMPD or uploaded on the WMPD FTP server. Please DO NOT SUBMIT PAPER COPIES.

All procedures must be conducted by qualified personnel, to include training required by 29 CFR 1910.120.

Documentation of all methods and materials used must be adequate. All work must be performed in compliance with

DEC policy "UST Closure and Site Assessment Requirements" as well as all applicable statutes, regulations, and

additional policies. The DEC may reject inadequate closure forms and reports.

5554131

Jaymi Cleland 9/3/13

NA

NA

Jeff Girard

Environmental Compliance Services, Inc. (ECS) 802-241-4131

9/3/13 9/3/13

Site Sketch With PID Readings

44 East Terrace, South Burlington, VT

1 7 3 6 ↑

4 2

← ← underground power

North

Location Depth (ft) PID (ppm) Location Depth (ft) PID (ppm)

1 0.5 0.6 4 2.5 0.6

2 0.5 0 4 3.0 0.7

3 1.0 0 5 3.0 2.6

3 4.5 269 6 5.0 727

3 5.0 916 7 5.0 671

4 1.5 0 7 6.0 402

House

concrete

stairs

East Terrace

main entrance

ECS 08-220832.00

PHOTOGRAPHIC LOG Environmental Compliance Services, Inc.

1 Elm St., Suite 3

Waterbury, Vermont 05676

Client Name: Enpro Services

Site Location: 44 East Terrace

South Burlington, Vermont

ECS Project #: 08-220832.00

Photograph #1

Description:

Front of house. UST

to the left of stake.

Photograph #2

Description:

Fill and vent pipes.

PHOTOGRAPHIC LOG Environmental Compliance Services, Inc.

1 Elm St., Suite 3

Waterbury, Vermont 05676

Client Name: Enpro Services

Site Location: 44 East Terrace

South Burlington, Vermont

ECS Project #: 08-220832.00

Photograph #3

Description:

Removing abandoned

concrete stairs to

access side of tank.

Photograph #4

Description:

Access to tank for

cleaning.

PHOTOGRAPHIC LOG Environmental Compliance Services, Inc.

1 Elm St., Suite 3

Waterbury, Vermont 05676

Client Name: Enpro Services

Site Location: 44 East Terrace

South Burlington, Vermont

ECS Project #: 08-220832.00

Photograph #5

Description:

Removing tank from

ground.

Photograph #6

Description:

Bottom of excavation.

PHOTOGRAPHIC LOG Environmental Compliance Services, Inc.

1 Elm St., Suite 3

Waterbury, Vermont 05676

Client Name: Enpro Services

Site Location: 44 East Terrace

South Burlington, Vermont

ECS Project #: 08-220832.00

Photograph #7

Description:

Pits and holes in

bottom of tank.

Photograph #8

Description: Capped feed line in

basement.