9-Generator Performance Curves and Static Exciation

Embed Size (px)

Citation preview

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    1/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 1

    AnsaldoEnergia Una Societ Finmeccanica

    .

    DPT. ELECTRICAL MACHINES

    _____________________________________

    PRESENTATION

    PERFORMANCES CURVES OF THE ALTERNATOR

    +

    STATIC EXCITATION SYSTEM

    _____________________________________

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    2/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 2

    AnsaldoEnergia Una Societ Finmeccanica

    Summary

    1st PART (sh. 3)

    PERFORMANCES CURVES OF THE ALTERNATOR

    2nd PART (sh. 39)STATIC EXCITATION SYSTEM

    .

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    3/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 3

    1st PART

    AnsaldoEnergia Una Societ Finmeccanica

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    4/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 4

    PERFORMANCES CURVES

    OF THE ALTERNATOR

    AnsaldoEnergia Una Societ Finmeccanica

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    5/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 5

    The performances given by a generation groupof electric energy (type turbogenerator,hydrogenerator, etc.) they are essentiallysynthesized by the following types of curves,that represent an useful tool to support theexercise and maintenance operators of a

    production plant.

    1a - Saturation and short circuit curves

    1b - Capability diagram

    1c - V curve

    1d - Power vs. temperature curve (for GT)

    AnsaldoEnergia Una Societ Finmeccanica

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    6/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 6

    1 a SATURATION AND SHORT

    CIRCUIT CURVES

    AnsaldoEnergia Una Societ Finmeccanica

    G

    T

    25C

    Iexc

    nom

    Vstator

    Main Breaker

    OPEN

    At no-load

    At nominal

    speed

    Temperature

    The saturation curve of analternator shows the behavior of

    the stator voltage versus the

    variations of the excitation

    current Iexc injected in the rotorwindings.

    This curve is done at no-load

    conditions, at nominal speed

    revolution and at a defined

    ambient temperature.

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    7/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 7

    ( 1 a Saturation and

    short circuit curves )

    AnsaldoEnergia Una Societ Finmeccanica

    The a) diagram shows that,

    when the excitation current

    increases, after a certain linear

    trait, appears a knee of the

    voltage V due to a saturationphenomenon of the magnetic-

    iron material of which the

    laminated core of the stator is

    composed.

    a)

    Vstator

    Iexc

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    8/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 8

    The diagram also showsthe short circuit straight

    line b) obtained

    measuring the statorcurrent versus variations

    of excitation current,

    when the main terminals

    of the stator have been

    short circuited.

    AnsaldoEnergia Una Societ Finmeccanica

    ( 1 a Saturation and

    short circuit curves )

    b)

    Iexc

    Istator

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    9/141

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    10/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 10

    1 b CAPABILITY DIAGRAM

    AnsaldoEnergia Una Societ Finmeccanica

    It is a particularly important diagram because it

    synthetically represents by a close surface all the

    possible working points of the generation group

    (turbine + alternator) in terms of MW and MVAR

    delivered for the external loads.

    This diagram therefore is valid if the generator is on

    load only [i.e. when it is synchronised to the grid or

    it is loaded locally (in island)].

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    11/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 11

    ( 1 b Capability diagram )

    AnsaldoEnergia Una Societ Finmeccanica

    MW

    +

    -

    MVAR

    Over

    Under

    Mw are in abscissa and MVAR are in

    ordinate.

    Each segment of the star having origininto zero is composed by working points

    having same ratio between MW-MVAR

    and therefore the same cos .

    Every half-circumference with center in theorigin is composed by working points at

    constant MVA, but with different cos .

    The curves are at Vstator= constant.

    In this case the capability are three and

    each of them corresponds to a generator

    cooling more or less intense (here done

    with hydrogen at different pressures).

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    12/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 12

    The overexcitation quadrant is atpositive MVAR (positive cos).

    The underexcitation one is at

    negative MVAR (negative cos).

    In the example at side, the nominalworking point (on which the whole

    group is sized) is at cos= + 0,85

    in overexcitation.

    The boundaries of the curves are

    due to the limits of the machine

    project.

    AnsaldoEnergia Una Societ Finmeccanica

    ( 1 b Capability diagram )

    Nominal

    working point

    +

    -

    MVAR

    Over

    Under

    MW

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    13/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 13

    At side, the boundaries of the

    capability, imposed by the sizingand by the characteristics of themachine, are highlighted withcolored lines.

    More in detail:

    green line: limitation due to themax thermal ability of the stator

    blue line: limitation due to themax thermal ability of the rotor

    red line: limitations due toproblems of dynamic stability andto heating of parts situated in theextreme zones of the statorpackage.

    AnsaldoEnergia Una Societ Finmeccanica

    ( 1 b Capability diagram )

    Nominal

    working point

    +

    -

    MVAR

    Over

    Under

    MW

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    14/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 14

    This curve is particularly meaningful for the exerciseoperators and therefore it deserves further details in

    order to explain the manner by which it is gotten and

    the reasons for which some limitations are applied to it.

    The following images go through the sequence of all thephases of the capability construction and they focus,

    particularly, the phenomena that converge to establish

    its boundaries in the plan of the active (MW+) and

    reactive (MVAR +/-) powers.

    AnsaldoEnergia Una Societ Finmeccanica

    ( Appendix to the item 1b )

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    15/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 15

    AnsaldoEnergia Una Societ Finmeccanica( Appendix to the item 1b )

    .

    Now we go back through the notes on the capability already seen, starting from the

    origin and using the physical considerations that have contributed to produce it..

    ------------------------------The capability diagram is represented on the Active/Reactive

    Powers and it includes all possible working points of the

    generator (each point is defined by its active/reactive values).

    It is applicable to thesynchronized machine only and it dependsby the size of turbine and alternator,

    Some limitations are applicable due to the materials temperatures

    and to the dynamic performances of the group (stability).

    The following images show in sequence the main considerationsthat produce, as final result, the definition of the capability.

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    16/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 16

    AnsaldoEnergia Una Societ Finmeccanica

    .

    1 step (pls. see next image)

    On the surface Active/Reactive Power the portion at MW < 0

    is not considered [because we are talking of generators MWdelivered to the grid(MW with sign > 0) and not motors

    MW absorbed from the grid(MW with sign < 0)].

    The size imposed by the Client (apparent power MVA) defines

    on this plan an half-circle including all working points having

    MVA the size required (its limit is just the half-circumferenceat max MVA).

    The nominal cos required, together with the apparent powerrequired, define the nominal working point of the whole

    group turbine-generator.

    ( Appendix to the item 1b )

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    17/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 17

    AnsaldoEnergia Una Societ Finmeccanica

    .

    ( Appendix to the item 1b )

    Nominal apparent power

    (MVA) of the alternator

    Active Power

    Positive reactive

    power

    Negative reactive

    powerUnder-

    excitationLEADING

    Over-

    excitationLAGGING

    0

    Motor

    Nominal working point

    (nominal power at nominalcos )

    (+)

    (

    -)

    Generic working point

    (MVA corrispondent to a

    generic MW / MVAR)

    MVAR

    MW

    MVA nominal

    MVA

    Doc. n 196 W 429 Rev.1 Oct. 2008

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    18/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 18

    2 step (pls. see the following image)

    The nominal working point (MVA, MW, MVAR, cos)is the main reference for turbine and generator sizing.

    Consequently, the turbine is designed to deliver, as its maxpower, the MW correspondent to the nom. working point.

    This is the first limitation that cuts the upper part of thecapability diagram.

    It will be physically impossible to over-exceed that MWand, therefore, the upper highlighted area will be erased

    because inaccessible (forbidden working conditions of thegroup).

    AnsaldoEnergia Una Societ Finmeccanica( Appendix to the item 1b )

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    19/141

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    20/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 20

    3 STEP (pls. see the following image)

    The nominal working point (MVA, MW, MVAR, cos)is the main reference for turbine and generator sizing.

    The generator will have the stator size designed on theMVA of the nominal working point and, similarly, therotor size.

    The outlined half-circumference (MVA=constant)represents all points at the same MVA of the nominal

    working point.The rotor is sized for the steady field current correspondentto the nominal working point and this size limits theworking conditions up to the points correspondent to the

    red line.Consequently, the blue area also (at right end of diagram)is cutted and inaccessible, because of the rotor size.

    AnsaldoEnergia Una Societ Finmeccanica( Appendix to the item 1b )

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    21/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 21

    .

    .

    AnsaldoEnergia Una Societ Finmeccanica

    Nominal working point

    Active powerNominal apparent power

    (MVA) of the alternator

    and stator size (+)

    Inaccessible area due to the

    rotor size of the generator

    Limitation due to

    the rotor size

    0

    Positive reactive

    power

    Negative reactive

    powerUnder-

    excitationLEADING

    Over-

    excitationLAGGINGMotor

    (

    -)

    Doc. n 196 W 429 Rev.0 March 2005

    ( Appendix to the item 1b )

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    22/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 22

    Just for example, eacharc of circumference inblue in the figure,

    corresponds to workingpoints having all thesame excitation current.

    In particular, the design ofthe rotor is sized on theexcitation currentcorresponding to thenominal working point Pn.

    The center of these arcsis found in a specific pointsituated on the MVAR

    axis in underexcitation atabout 1/Xd from thezero.

    AnsaldoEnergia Una Societ Finmeccanica

    MW

    MVAR

    0

    Nominal workingpoint Pn

    1 / Xd

    Overexc.

    Underexc.

    ( Appendix to the item 1b )

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    23/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 23

    4 STEP (pls. see the following image)

    The last limitation on the capability diagram (the blue

    area at left end) is due to stability problems of thegenerator and to overheating of some parts at the statorcore ends.

    The risk of instability is mainly due to weak flux inside the

    machine air-gap that makes feeble the magnetic connectionbetween rotor and stator, with consequent its easy tear.

    The overheating on the extreme parts of the statorwindings, due to a particular magnetic flux disposition in

    that zone, is the second reason of limitation on this under-excitation area of the capability diagram.

    AnsaldoEnergia Una Societ Finmeccanica( Appendix to the item 1b )

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    24/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 24

    .

    AnsaldoEnergia Una Societ Finmeccanica

    Inaccessible area due to stability

    problems and overheating of

    some parts at the stator core ends.

    Active power

    MW

    0

    Positive reactivepower MVAR

    Negative reactivepower MVAR

    Under-excitation

    LEADING

    Over-excitation

    LAGGINGMotor

    (-)

    (+)

    Limitation

    Nominal working pointHeating

    problems

    Stability problems

    ( Appendix to the item 1b )

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    25/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 25

    The final configuration of the capability diagram for theturbo-generator set is shown on the following image.

    All permissible working points (at steady state) for the group

    ( if synchronized ) are included into the green area only.

    The protection to avoid the MW over-exceeding (to shift toordinates higher than the max allowed) is intrinsic due tothe turbine size.

    On the contrary, the protections against working attempts

    out of the above mentioned limitations at right or left ends,are foreseen and performed by the excitation system.

    AnsaldoEnergia Una Societ Finmeccanica( Appendix to the item 1b )

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    26/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 26

    Capability diagram of generator

    Nominal working point

    Inaccessible area due to the

    turbine power limitation

    Inaccessible area due to therotor size of the generator

    Inaccessible area due to stability

    problems and overheating of some

    part at the stator core ends.

    Max apparent power of the

    generator

    Active power

    Positive reactive

    power

    Negative reactive power Under-excitation

    LEADING

    Over-excitation

    LAGGING

    0

    Motor

    Under-excitation limit Max rotor current limit

    Max turbine

    power

    AnsaldoEnergia Una Societ Finmeccanica( Appendix to the item 1b )

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    27/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 27

    CAPABILITY DIAGRAM OF GENERATOR

    Movements of the working points

    AnsaldoEnergia Una Societ Finmeccanica

    MW

    MVAR

    Over-excitation

    Under-excitation

    AVR

    AVR

    EHC EHC

    Zone

    MOTOR

    ( Appendix to the item 1b )

    From the point of view of the machineconduction, we remember that any

    change of the working point on the

    capability is done by commands on

    the EHC (turbine regulation) and/or on

    the AVR (voltage regulation into theexciter).

    In particular, as shown at side, the

    variations of MW are obtained by

    actions on the EHC only, while the

    variations of MVAR are produced by

    commands on the AVRonly.

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    28/141

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    29/141

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    30/141

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    31/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 31

    AnsaldoEnergia Una Societ Finmeccanica.

    V curve of the generator

    I excitation

    P apparent

    0

    Nominal

    working point

    P app nom

    Iexc at no-loadA

    B

    E

    I exc nom

    Limitation dueto the max

    power of theturbine

    .% Iexc

    at no-load

    D C

    OverUnder

    ( 1 c V curve )

    The following image shows the correspondence of some working points

    both on the capability diagram and on the V curve.

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    32/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 32

    AnsaldoEnergia Una Societ Finmeccanica

    .

    ( 1 c V curve )

    Correspondence between Capability and V curves

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    33/141

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    34/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 34

    AnsaldoEnergia Una Societ Finmeccanica

    .

    MW

    MVAR

    cos = 0.85

    MVA

    0

    Sovraecc.

    Sottoecc.

    ( 1 d Power vs. temperature )

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    35/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 35

    GENERATOR SYNCHRONIZED :

    OVER-EXCITATION &

    UNDER-EXCITATION

    AnsaldoEnergia Una Societ Finmeccanica

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    36/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 36

    AnsaldoEnergia Una Societ Finmeccanica.

    The image at side represents, symbolically and from the reactive

    power point of view only, the generator synchronized on the

    national grid.

    GX

    ReteVa Vr

    The interconnecting reactance X

    allows the reactive power exchange

    between generator and grid.

    In the synchronizing instant Va=Vr : no flux of reactive current

    through the reactance is there ( I = (Va-Vr) / X ---> I = 0 = Q ).

    If Vr remains constant and Va changes, reactive current increases.

    If Va > Vr I and Q go from G to grid (over-excitation).

    If Va < Vr I and Q go from grid to G (under-excitation).

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    37/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 37

    AnsaldoEnergia Una Societ Finmeccanica.

    In over-excitation Ia flows from G to the grid and produces on X a

    voltage drop with sign + at G side.

    In under-excitation, on the contrary, Ia flows from the grid to G

    and produces on X a drop voltage with sign + at grid side.

    Being Ia always 90 delaied on Vt, in over-excitation the Va-Ia

    vectorial diagram says that G sees an inductive load, while in

    under-excitation G sees on the contrary a capacitive load (pls.see this images).

    GX

    GridVa Vr

    Ia

    Vt

    Over-excitation

    +_

    GX

    GridVa Vr

    Ia

    Vt

    Under-excitation

    +_

    Inductive load Capacitive load

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    38/141

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    39/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 39

    AnsaldoEnergia Una Societ Finmeccanica.

    2nd PART

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    40/141

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    41/141

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    42/141

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    43/141

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    44/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 44

    When the generator is synchronized, the grid creates on its

    stator winding a strong rotating electromagnetic field (like

    magnet), which finds in front the rotor magnet with correct

    polarities and their attraction is consequent.

    But their magnetic connection is strictly dependent by the air

    gap magnetic flux, which is strong if the rotor magnet is

    powerful and fragile if the rotor magnet is feeble.The energy exchange between generator and grid is controlled

    through the regulation of that flux.

    Consequently, a rotating permanent magnet could not control

    that exchange, while a rotating magnet produced by field

    excitation (d.c. current) can properly regulate that exchange.

    AnsaldoEnergia Una Societ Finmeccanica

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    45/141

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    46/141

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    47/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 47

    A machine is ageneratorif its rotor magnet, powered by

    the mechanical couple of the turbine, rotates ahead of the

    stator magnet (of the grid) and pulls and drags it.

    On the contrary, a machine is a motorif the stator magnet

    (of the grid) rotates ahead and pulls and drags the

    rotor magnet.

    The angle displacement between the axes of the rotor and

    stator magnets is called load angle.

    We are always speaking aboutgenerators .

    AnsaldoEnergia Una Societ Finmeccanica

    AnsaldoEnergia Una Societ Finmeccanica

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    48/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 48

    In order to deliver big amounts of energy to the grid, the

    turbine gives high torque couples to the generator shaft.

    But that high couples, applied to the rotor body/magnet,

    succeed to drag the stator magnet if only the magnetic flux

    inside the air gap is very strong ( rotor-stator link, in thiscase, must be very solid to do it). Strong flux means

    high intensities of excitation current on the rotor winding

    (this is the over-excitation status).

    On the contrary, when the excitation current is reduced, thepossibility to transmit energy to the grid is correspondingly

    reduced because the flux is reduced.

    In that conditions it is hazardous have strong couples onthe shaft because it becomes easier to tear the magnetic

    link between rotor and stator magnets (under-excitation

    status).

    AnsaldoEnergia Una Societ Finmeccanica

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    49/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 49

    The previous general introduction clarifies the necessity

    and the advantages to create an artificial magnet on the

    rotor through d.c. currents flowing into windings mountedon the rotor body.

    The excitation systems was conceived just with the main

    purpose to supply d.c. currents for the rotor windings.

    Nevertheless this is not the unique goal of the exciters and,

    taking advantage of the control facilities on the fieldcurrent, other important functions can be performed.

    AnsaldoEnergia Una Societ Finmeccanica

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    50/141

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    51/141

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    52/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 52

    .

    AnsaldoEnergia Una Societ Finmeccanica

    +_

    Alternator

    Rotor rings

    Dynamo

    +

    _

    Alternator and

    rectifier bridge(the electrical scheme

    is for brushless too)

    +

    _

    +

    _

    Static

    Various types of

    excitation system

    AnsaldoEnergia Una Societ Finmeccanica

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    53/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 53

    ADVANTAGES OF FULLY STATIC EXCITER______________________

    HIGH RELIABILITY SHORT TIMES TO RESTORE EVENTUAL FAULTS(due to the static components only) (economic advantages for reduction of production loss)

    COMPLETE REDUNDANCY SIMPLIFIED MAINTENANCE

    (ex. brushless is not doubled) (practically nothing)

    DYNAMIC RESPONSE FAST FIELD DE-EXCITATION

    (negligible delays and negative ceiling) (direct on the machine field)

    GLOBAL EFFICIENCY SHORTER LENGTH OF THE SHAFT

    (reduced losses) (reduced dimensions)

    For all that reasons the plant strongly gains on its economical balance.

    AnsaldoEnergia Una Societ Finmeccanica

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    54/141

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    55/141

    AnsaldoEnergia Una Societ Finmeccanica

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    56/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 56

    +

    EXCITATION

    CUBICLE

    MAIN

    GENERATOR

    EXCITATION

    TRANSFORMER

    ENERGY FOR

    EXCITATION

    SYSTEM

    STATIC EXCITATION SYSTEMSTATIC EXCITATION SYSTEM

    ENERGY FORTHE ROTOR

    WINDING

    AnsaldoEnergia Una Societ Finmeccanica

    AnsaldoEnergia Una Societ Finmeccanica

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    57/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 57

    Typical parameters for evaluation

    of the excitation systems performances______________________

    CEILING

    REGULATION ACCURACY

    SYSTEM RESPONSE

    SYSTEM SETTLING TIME

    g

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    58/141

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    59/141

    AnsaldoEnergia Una Societ Finmeccanica

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    60/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 60

    .

    t [sec]

    V stat. generat.

    The regulation accuracy is evaluated by the displacement, at steady, between

    Vg2 (final value after oscillation) and Vg1 (previous value).

    Vg2Vg1

    ACCURACY

    displacement

    O

    AnsaldoEnergia Una Societ Finmeccanica

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    61/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 61

    RESPONSE

    It is a parameter that gives the idea of the promptness by which theexcitation system responds to the variations, mainly in automatic

    regulation mode.The international Standards define this evaluation method asshown into the following image (find the compensation line, markthe intersection point at 0.5s and apply the indicated formula).

    Starting from the nominal excitation voltage, the ceiling voltage isimposed by the regulator and the resulting excitation voltage shapeon the field is a curve significant of the exciter response.

    The response measure has meaning for rotating exciters onlybecause for the static exciters it is directly proportional to the

    ceiling.

    g

    AnsaldoEnergia Una Societ Finmeccanica

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    62/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 62

    .

    t [s]

    V excitation

    O

    A

    BC

    V ceiling

    A

    R = AB / (BC*OC)R = AB / (BC*OC)

    0.5 s

    RESPONSE

    V nominal excitation

    Rotating exc. RED AREAS

    Static exc. GREY AREAS

    AC = compensation line

    considering instant t=0.5 s, area ABC must be equal

    to the area under the real curve (the exponential for

    rotating exciter and the step for static)

    01

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    63/141

    AnsaldoEnergia Una Societ Finmeccanica

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    64/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 63

    .

    t [sec]

    V stat. generat.

    Time t0 is defined as the interval from t=0 to the instant in which the oscillation returns and

    remains contained into a certain band up to the steady state.

    The width of this band (. %) has to be defined in order to be able consequently to define t0 .

    Vg2

    Vg1

    t0

    Band ( . %)

    SETTLING TIME

    O

    AnsaldoEnergia Una Societ Finmeccanica

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    65/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 64

    STATIC EXCITER

    g

    AnsaldoEnergia Una Societ Finmeccanica

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    66/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 65

    .

    STATIC EXCITATION SYSTEMONE LINE BLOCK DIAGRAM

    STATIC EXCITATION SYSTEMONE LINE BLOCK DIAGRAM

    G

    AVR 1

    AVR 2

    CB

    RES

    EXCITATION

    TRANSFORMER

    Ref. 1

    2

    EXCITATION

    BOARD

    MAIN

    GENERATOR

    Commands

    and signals

    from remote

    Bridge 1

    Bridge 2

    +

    _

    Signals

    to remote

    AnsaldoEnergia Una Societ Finmeccanica

    .

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    67/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 66

    g

    TYPICAL INTERFACE OF THE EXCITATION BOARD

    INPUT OUTPUT

    Excitation

    board

    3 LV power line

    from excitation transformer

    Analogical signals from remote

    Commands from remote

    Permissives from remote

    Trip from remote

    d.c. power output (+ and -)

    to the rotor of the machine

    Analogical signals to remote

    State signals to remote

    Alarms to remote

    Trip request to remote

    Aux feeding voltages

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    68/141

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    69/141

    AnsaldoEnergia Una Societ Finmeccanica

    .

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    70/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 69

    A particular feeding system taken from the generator terminals, now nomore used, is with a voltage transformer (TRE) and a current transformer

    (TAT). The TRE feeds a thyristors bridge which is in series with a diodes

    bridge fed, on the contrary, by the TAT. In this case too it is necessary the

    use of the pre-excitation circuit.

    When the generator is at no-load, the

    machine is excited by the contribution of

    the TRE only (in fact the stator current

    I=0). If the generator is in short circuit

    (also permanent) it is the TAT alone that

    contributes to excite it (in fact the stator

    voltage V=0). In any other working

    condition (between these two extreme)

    both the transformers contribute to excite

    the machine. The quick intervention on

    the line faults of the actual digital

    protections has made useless this systemwhose principal characteristic was just to

    succeed in sustaining for long time the

    short-circuits prolonged.

    Static

    exciterGen

    Voltagetransformer(TRE)

    Currenttransformerwith air-gap (TAT)

    V of the

    machine

    I of the

    machine

    From

    TRE

    From

    TAT

    +

    -

    +

    -

    Thyristors

    Diodes

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    71/141

    AnsaldoEnergia Una Societ Finmeccanica

    .

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    72/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 71

    UPS or plant Battery

    Feeder

    To regulation

    system 1

    To regulation

    system 2

    Feeder

    Exciter

    Each regulation system is fed with security and with the possibility to becompletely deactivated for eventual maintenances during the normal

    service also, while the alternator produces energy under the control of the

    other regulation system.

    Since the feeders of the electronics (1 for regulator) can be fed both in

    a.c. and in d.c., it can be chosen, as energy source for them, both the UPS

    and the battery of the plant.

    AnsaldoEnergia Una Societ Finmeccanica

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    73/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 72

    POWER SECTION

    RECTIFIER BRIDGES

    AnsaldoEnergia Una Societ Finmeccanica

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    74/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 73

    The 3phase power rectifier bridge Graetz type can be madeby diodes or by thyristors.

    Diodes rectifier bridge .

    Diode is a non-controlledsemiconductor

    having 2 poles: anode and cathode.

    Its conduction is conditioned by 1 status

    only: potential of anode Va higher than the

    potential of cathode Vc.

    In this condition the current I can flow through the diode.

    A Graetz rectifier bridge with 6 diodes (next image) has its

    output directly proportional to its feeding voltage only.

    +

    _

    I

    Va

    Vc

    anode

    cathode

    AnsaldoEnergia Una Societ Finmeccanica

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    75/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 74

    DIODES BRIDGE

    RS

    T

    +

    --

    i

    i

    iexc

    VRVS

    VT

    Vexc

    Time

    Vexc

    VR VT

    VR

    VS

    VT

    VS

    VR

    V

    RV

    TV

    S

    VRS VRT VST VSR VTR VTS

    1 period of the fundamental

    [ 20 ms (50Hz) 16.6 ms (60Hz) ]

    The output excitation voltage

    Vexc (left side) is, in anyinstant, the highest amongthe actual differencesamong the 3 phase voltagesVR - VS - VT at that instant(phase-to-phase values).The result is a regular

    sequence of the 6 typicalondulating peaks duringeach 20 ms (cycle 50Hz).Its average value is directlyproportional to VR VS VTfeeding values only.

    V

    R

    V

    S

    V

    T

    V

    R

    V

    S

    V

    T

    V

    R

    V

    S

    V

    T

    R+

    R -

    S+

    S -

    T+

    T -

    Phase voltages

    Vexc

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    76/141

    AnsaldoEnergia Una Societ Finmeccanica

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    77/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 76

    THYRISTORS BRIDGE

    The output average value of Vexc isnot directly proportional to the supplyvoltages VR VS VT , as per the diodes

    bridge, but it is function of thecontrolling signal on the gate of thethyristors.Changing the delay of their firing

    instant (changing the firing angle )referred to the natural firing instant, itis possible to change the output bridge.

    This kind of bridge has the possibility toproduce a rectified voltage withvariable average value, being constantits feeding voltage.Theoretically, changing the control, theoutput voltage Vexc could be changed

    from + VC to VC , where Vc is theceiling voltage (posit.), correspondent

    to the output voltage with = 0 (whichis the condition where the thyristorsbridge becomes like a diodes bridge).

    RS

    T

    +

    --

    i

    i

    iecc

    VR

    VS

    VT

    Vecc

    R+ S+ T+

    R - S - T -

    R+ means thyristor of the

    phase R, sidepositive (+)

    Vexc

    Time

    - VCeiling (=180)

    0

    Permanent times( Vexc > 0 )Voutput

    (average value)

    Zone used for

    transient timesonly ( Vexc < 0 )

    + VCeiling

    (=0)

    AnsaldoEnergia Una Societ Finmeccanica

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    78/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 77

    THYRISTORS BRIDGE

    RS

    T

    +iecc

    VRVS

    VT

    Vecc

    R+ S+ T+

    R - S - T -

    --

    R+

    S+

    T+

    R -

    S -

    T -

    60 60 60 60 60 60

    R+S- R+T- S+T- S+R- T+R- T+S-

    In the thyristors bridges, the

    sequence of the commutations is

    identical to that of the diodes

    bridges (pls. see the image).

    They are :

    R+ S- for 60 electric

    R+ T- for 60 electric

    S+ T- for 60 electric

    S+ R- for 60 electric

    T+ R- for 60 electric

    T+ S- for 60 electric

    Each of the 6 thyristors conducts

    for 120 electric, in couplealternatively with the two

    thyristors of opposite sign of the

    other phases.

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    79/141

    AnsaldoEnergia Una Societ Finmeccanica

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    80/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 79

    THYRISTORS BRIDGE

    Delay angle 0

    =180

    60 60 60 60 60

    R+ R-T- S+ T+ S-

    Delay angle =180

    R+ R-T- S+ T+ S-

    60 60 60 60 60

    Average = 0

    Working conditions with 90 ,and consequently with average voltage negative,

    can be for transient times only

    Averagenegative

    Time

    Time

    Vexc

    Vexc

    Natural

    instant of firing

    of the thyristor

    R+

    They move

    Bridge voltage

    output for = 90

    Bridge voltageoutput for = 140They move

    0

    Delay

    on R+= 90

    Delay

    on R+= 140

    AnsaldoEnergia Una Societ Finmeccanica

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    81/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 80

    The thyristors bridge has the particular possibility to deliveroutput voltages with negative sign, even if the semiconductors arecontrolled diodes (unidirectional).

    This is possible because the bridge feeds a big inductive load

    (field of generator) and any voltage variation on it produceschanges in current very slow, compared with the voltage changes(inside an inductance any current variation is braked).

    Consequently, with the thyristors impulses delayed at >90, the

    voltage transmitted to the field is negative but the thyristorsremain alive and in conduction until the current inside remainsalways positive (current is decreasing because of the V< 0).

    If the current would reach zero the thyristors and the bridge wouldbe switched-off : this is why the time to deliver V< 0 on theoutput bridge is limitedby the time of decreasing to zero of thecurrent.

    AnsaldoEnergia Una Societ Finmeccanica

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    82/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 81

    The static exciter are normally provided with twoidentical Graetz thyristors rectifier bridgesworking in alternative.

    Each of them can be commanded by its own AVRonly or by both AVRs, operating in alternative.

    Any malfunction of the main bridge produce theautomatic change-over to the other, in order toguarantee the continuity of the generator service.

    The cooling of the rectifier bridge is normallydone by forced air in open cycle, except for the

    exciters at small sizes (natural air) or at big sizes(treated water in closed cycle).

    AnsaldoEnergia Una Societ Finmeccanica

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    83/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 82

    EXAMPLE OF CONVERTER COOLEDBY AIR IN OPEN CYCLE

    3phase a.c. line from

    excitation transformer

    2phase d.c. line for therotor of the alternator

    3phase Graetz bridge

    with thyristors and fuses

    3phase Graetz bridge

    with thyristors and fuses

    Warm air

    Air

    filters

    Air

    filtersFresh air

    AnsaldoEnergia Una Societ Finmeccanica

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    84/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 83

    EXAMPLE OF CONVERTERS COOLEDBY AIR IN OPEN CYCLE

    Fresh

    air

    Warm air

    Hot

    components

    Lateral section of the cubicle

    Path of the air that

    cools a

    compartment by

    natural convection.

    Filters

    Path of the air that

    cools a

    compartment by

    forced cooling.

    Fresh

    air

    Warm

    air

    Hot

    components

    Lateral section of the cubicle

    Extractor

    Filters

    AnsaldoEnergia Una Societ Finmeccanica

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    85/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 84

    EXAMPLE OF CONVERTERS COOLED

    BY AIR IN CLOSED CYCLE

    Air-to-water exchangerWater

    Fresh air

    Warm air

    Extractor

    Bridge

    Sealed

    room

    AnsaldoEnergia Una Societ Finmeccanica

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    86/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 85

    EXEMPLE OF CONVERTER COOLED BY WATER

    Schematic representation of the converter and its cooling system done

    with treated water in closed loop

    (in the figure, the representation of the water that flows in the bridge,

    obviously, is indicative only, for explanatory purpose)

    FUS

    +

    Cooling water coming from an

    external hydraulic circuit for the

    internal water-to-water exchangers

    Ex Ex

    P

    Tk

    P

    T

    P = circulation pump

    Ex = water-to-water exchangerTk= treated water tank

    T = cells of water treatment

    FUS= fuses of the bridge

    3phase Graetz bridgewith 12 thyristors

    (100% series redundance)and 3 fuses at input side

    Excitation board

    AnsaldoEnergia Una Societ Finmeccanica

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    87/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 86

    DE - EXCITATION

    AND

    PRE - EXCITATION

    AnsaldoEnergia Una Societ Finmeccanica

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    88/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 87

    The de-excitation of the generator reduces its stator voltage

    at about zero (except the effect of the magnetic residual).

    This condition is obtained with the discharge of the internal

    flux, dissipating the field current through a passiveresistance circuit, composed by the rotor resistance and an

    aux discharge resistance connected in series.

    This is obtained by the crow bar positive (pls. see image)which can be fired by the logic with two voltage thresholds:

    higher used when CB is operated as overvoltage protection

    and lower used only when CB is actuated as field breaker.

    Its ON state allows the field current flow through RES andthe consequent electromagnetic flux discharge.

    Crow bar positive

    AnsaldoEnergia Una Societ Finmeccanica

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    89/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 88

    .

    Crow-bar positivefiring voltage 1 threshold

    Overvoltage

    protection

    2 threshold

    De-excitation

    function0 Volt

    Iexc

    Rotor

    Field

    resistanceDischarge

    resistor

    Crow-bar

    positive

    Power

    converter

    De-excitation circuit or

    Static field breaker

    RES

    0 time

    Stator voltage

    Being RES about double of field

    resistance, the complete discharging

    time is approx. equivalent to Tdo.

    = Lfield / (RES + Rfield) = Tdo / 3

    Tdo = Lfield /Rfield

    CROW BAR

    AnsaldoEnergia Una Societ Finmeccanica

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    90/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 89

    CROW - BARThe crow-bar is made by 2 thyristors in antiparallel (v. figure), one called positive crow-bar and the

    other negative crow-bar.

    Both has the function of protection against the overvoltages (+ and -) but the positive one has the

    function also to de-excite the field of the alternator.

    Its two functions are discriminated by two different thresholds of intervention that are him imposedaccording to the situations and of the moments in which it has to intervene (v. figure).

    The thyristors firing is produced by the same overvoltages that directly activate the firing circuits,

    which are totally redounded, to guarantee the certainty of the primer.

    Crow-bar

    positive

    Crow-bar

    negative

    Dischargeresistor

    Iexc

    Iexc

    +

    _

    CB

    RotorIexc

    RES

    Primer thresholds of

    the positive crow-bar 1 threshold

    Protection

    against the

    overvoltages

    2 thresholdFunction of

    de-excitation0 Volt

    Mechanism of de excitation by crow bar

    AnsaldoEnergia Una Societ Finmeccanica

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    91/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 90

    Mechanism of de-excitation by crow-bar

    IexcRotor

    Dischargeresistor

    Crow-bar

    positive

    Power converter

    De-excitation circuit or

    Static field breaker

    Excitation voltage (for example) before

    the de-excitation command

    Negative ceiling

    voltage

    Instant where the de-excitation

    order is done and it is ordered

    the negative ceiling

    Voltage on the

    discherge resistor

    and on the field

    Instant where the output voltage of the bridge

    equalizes the voltage on the discherge resistor.

    After this point the bridge goes OFF because its

    thyristors become inversely polarized

    time

    Voltage

    0

    Instant of command

    of the impulses

    suppression

    Phase-to-phase

    voltage

    It is shown the mechanismby which the de-excitation ofthe generator is done by thecrow-bar.

    PRE EXCITATION

    AnsaldoEnergia Una Societ Finmeccanica

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    92/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 91

    PRE-EXCITATION

    To the generator field

    Pre-excitation circuit

    Feeding from the

    battery of the plant

    +

    _

    Res+

    _

    To the generator field

    Pre-excitation circuit

    Feeding from an a.c.

    aux line of the plant

    +

    _

    When the feeding of the power converter is directly absorbed from themain terminals of the generator, at any starting it is always temporarilyactuated a dedicated pre-excitation system in order to give a first voltageramp sufficient to make the group independent from its own excitation.

    The feeding source for the pre-excitation circuit can be a 3phase aux lineof the plant or the d.c. services (battery system) of the plant.

    A dedicated logic automatically activates and deactivates this circuit andcontemporarily oversees the correct behaviour of this phase.

    .

    AnsaldoEnergia Una Societ Finmeccanica

    During the pre-excitation phase the feeding(f l b tt ) d

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    93/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 92

    Excitation

    transformer

    Generator

    Main breaker

    of the machine

    Rotor

    Stator

    Bloc diode

    Battery of

    the plant Circuit of

    pre-excitation

    Resistor of adaptation

    and limitation

    +

    _

    Exciter

    Generator circuitry during the pre-excitation

    0

    time

    Iexc

    Tdo

    Typical time

    of the pre-

    excitation

    Max time allowed

    to the pre-excitation

    30% Iexc at no-load

    During the pre excitation phase the feedingsource (for example battery) produces anexcitation current having an exponentialshape, with a steady state value of about 30%of the machine field current at no-load and atime constant equal to about Tdo of thegenerator.

    Typical duration of the pre-excitation is someseconds (pls. see the diagram at bottom).

    In case of problems, the logic of overseeingasks for the electric trip if the max timeallowed to this phase is expired (this time is

    previously adjusted into the system).

    AnsaldoEnergia Una Societ Finmeccanica

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    94/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 93

    PROTECTION CIRCUITS

    PASSIVE PROTECTIONS ON THE POWER CIRCUITS

    AnsaldoEnergia Una Societ Finmeccanica

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    95/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 94

    PASSIVE PROTECTIONS ON THE POWER CIRCUITS

    Fuses

    Excitation

    transformer

    Voltage limiters

    Bridge

    +

    _

    The exciter foresees two types of passive protections on the power circuits: fuses in

    series to each thyristor and voltage limiters on the 3phase feeding line of the power

    converter.

    The fuses, obviously, protect the corresponding thyristors, having their I2t lower than the

    I2t of the correspondent semiconductors.

    The limiters (i.e. varistors) are three, connected triangle, and they limit the possible

    overvoltages on that 3phase feeding line.

    PROTECTION AGAINST SHORT CIRCUIT ON THE D.C. LINE

    AnsaldoEnergia Una Societ Finmeccanica

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    96/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 95

    A.C. Protection

    +

    _

    Gen

    Fuses

    Crow-bar

    Excitationtransformer

    Rotor

    RES

    Rectifier bridge

    Short

    circuit

    This electronic protection has the purpose to avoid damages to the powerconverter against occasional possible short-circuits on its output bars (alongthe whole two-phase line that connects the power converter to the rotor of themachine).

    Its intervention consists of sending the immediate command to the firingcircuits of the thyristors for their max impulses delay and contemporarily toproduce the electric trip of the generator.

    PROTECTION AGAINST CURRENT UNBALANCE A.C. SIDE

    AnsaldoEnergia Una Societ Finmeccanica

    Thi l t i t ti h th t d t t ibl b l th

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    97/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 96

    Anomalous current

    due to the fault

    The current in the central phase S is greater than the

    current in T, because S feeds T and the fault in R too.

    The currents in the phases S and T should be equal

    but, in this case, this in not true and this is detected.

    R

    S

    T

    Iexc normal

    Iexc normal

    Rotor

    This electronic protection has the purpose to detect possible unbalances among the

    currents values flowing into the three conductors (R-S-T) of the a.c. line that feeds

    the power converter.

    Such condition can occur in case of an internal fault of the rectifier bridge.

    Its intervention consists of actuating the logic of bridges commutation, in order to

    try to maintain the generator in service through the use of the backup rectifier

    bridge.

    If this was not possible it would be required the electric trip of the generator.

    PROTECTION AGAINST MAX OVERLOAD CURRENT

    AnsaldoEnergia Una Societ Finmeccanica

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    98/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 97

    Example of 2 points on the

    curve overload limitZone (green) of

    overload allowed

    by this protection

    0

    Iexc

    time

    t2

    I2

    I1

    t1

    Inom

    This electronic protection has the purpose to avoid damages to the power

    converter due to possible thermal overloads.

    It allows the bridge to deliver also currents higher than the nominal, but only if

    they are contained within a threshold-limit following the quadratic law at inversetime shown in figure (higher overcurrents for brief times and lower overcurrents

    for longer times).

    Its intervention produces the request of electric trip of the generator.

    CURVE IMPLEMENTED

    IN THE AVR

    AnsaldoEnergia Una Societ Finmeccanica

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    99/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 98

    AUXILIARY ACCESSORIES OF

    THE EXCITATION SYSTEM

    ROTOR EARTH FAULT RELAYhi d i i i i f h

    AnsaldoEnergia Una Societ Finmeccanica

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    100/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 99

    This device guarantees a continuous monitoring of the

    insulation level of the rotor winding, referred to the earth

    potential (normally the rotor body).

    In normal conditions this insulation level must be very high

    (M), while, if it drops (some K), it is significant of somefault into the rotor winding, which is generated by

    insulation loss between the winding copper and the rotor

    body (i.e. insulation material of the rotor winding damaged

    in some point).

    This kind of fault, if occurred in one point only of the rotor

    winding, does not produce, from the electrical point of

    view, any visible immediate effect, but always it stronglysuggests to stop the generator service as soon as possible, in

    order to avoid any further fault in other different points.

    In fact this situation could produce injurious effects to the

    system.

    This device can be chosen with one or two monitoring

    thresholds on the rotor winding insulation level and thecorresponding operations are the following:

    - with one threshold its action is an alarm only

    - with two thresholds its actions are alarm (step 1) and trip

    (step 2)

    GEN

    Rotor winding

    Rotor earthfault relay

    +

    -

    Eventual fault

    ROTOR TEMPERATURE CALCULATOR

    AnsaldoEnergia Una Societ Finmeccanica

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    101/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 100

    GEN

    Rotor winding

    +

    -

    Vexc

    Iexc

    Rotortemperature

    calculator

    Iexc Vexc

    Excitation board

    Output signal

    for remote

    C

    This device guarantees a constant monitoring of the rotor winding temperature, during the exercise of the

    generator.

    Its working principle is based on the continuous measure of the excitation voltage and current in order to

    calculate the actual temperature of the winding by the ratio Vexc/Iexc at any time interval of some

    milliseconds (cycle time of the digital program).

    Of course the function is programmed considering the high thermal inertia of the rotor winding, compared

    with the variation times of the excitation voltage and current (i.e. the ceiling voltage impulses are notaffecting the calculations because too fast for a possible influence on the temperature winding).

    This function is performed by a dedicated software (subroutine) implemented into the main AVR program.

    The digital regulation system gives an output signal significant of the rotor winding temperature for remote

    uses (typically for a recorder in control room or for the DCS system).

    AnsaldoEnergia Una Societ Finmeccanica

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    102/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 101

    REGULATION

    The generator is provided with a regulation system which is

    AnsaldoEnergia Una Societ Finmeccanica

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    103/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 102

    The generator is provided with a regulation system which is

    the main responsible for the correct conduction of the

    machine.

    This system primarily operates in automatic mode, in order tohave the best dynamic performances and securities, but it is

    possible the operation in manual mode too (next image).

    The first of the possible regulations is on the stator voltage,which normally has to be maintained constant or regulated

    following particular logic useful for the plant exercise.

    Other types of regulation can be done (i.e. cos of machine).The regulation system is digital and normally fully redundant,

    in order to be classified as fault tolerant.

    Automatic and Manual regulation modes

    AnsaldoEnergia Una Societ Finmeccanica

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    104/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 103

    Automatic regulation

    mode

    GENRegulation

    & Excitationsystems

    Stator

    voltageElectric

    feed-back

    Set-point

    selection

    Automatic

    correctionManual regulationmode

    GEN

    Stator voltageindicator

    Human visualfeed-back

    Continuous human

    correction

    Regulation

    & Excitationsystems

    CLASSIC REGULATION LOOPOF THE STATOR VOLTAGE

    AnsaldoEnergia Una Societ Finmeccanica

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    105/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 104

    OF THE STATOR VOLTAGE

    GErr.

    Feedback

    Reference

    VT feedback

    Bridge

    +

    -

    Exciter

    Next image shows the equivalent internal circuit of generator. Itincludes an ideal generator E and its synchronous reactance Xd1,

    AnsaldoEnergia Una Societ Finmeccanica

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    106/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 105

    g y d1,

    and it is connected to the grid by Xe1 (external reactance).

    The diagram shows the voltages E1-V1-VGRID in two situations

    - at no-load, just synchronized ---> E10 = V10 = VGRID- loaded, delivering positive MVAR to the grid (inductive load)

    In last case, supposing VGRID=constant, increasing field current Iexc ,

    E1 increases too (E10 --> E1A) and consequently V1 too (V10 -->

    V1A), delivering to the grid an inductive (+) reactive current I1 ,and a consequent power rate QA , proportional to the difference

    V between the voltages (E1A-VGRID).

    Being Xd1>>Xe1 , large part of that V is on Xd1 and, consequently,

    V1 will be always very close to the VGRID (transferred to thegenerator side) : this is the reason way, when the generator is

    synchronized, the stator voltage is blocked on the grid value.

    .- Generator synchronized -Blocks representation

    - Generator synchronized -Equivalent electrical

    representation

    AnsaldoEnergia Una Societ Finmeccanica

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    107/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 106

    VGRID

    xe1

    G

    Generator

    Stepuptransformer

    iexc1E

    Generator

    xd1

    xe1

    iexc1

    E1 V1I1

    V GRID

    G

    Stepuptransformer

    representation

    Internal gen.voltage E1Terminals gen.

    voltage V1 V GRID

    AT NO LOAD : E10=V10=VGRID

    Command to increase iexc1in order to change

    from E10 (at no load)

    to E1A

    (Q (+) delivered)

    V1A

    V10V

    GRIDE10

    E1 A

    QA

    E1A

    - VGRID

    QA

    E1A

    - VGRID

    xe1xd1

    G

    .

    AnsaldoEnergia Una Societ Finmeccanica

    In case of increasing of the external reactance Xe of the transformer, from

    Xe1 to Xe2 (pls. see diagram below), with same voltages E1 and VGRID, thereactive current exchanged Ireact and also Q decrease because they are

    always proportional to the PENDENCY of the segment (E1-VGRID) - and not

    - Generator synchronized -Equivalent electrical

    representation

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    108/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 107

    always proportional to thePENDENCYof the segment (E1 VGRID) and not

    only to the level difference among these two voltages - according to the

    relationship:

    Ireact Q (E1-VGRID) / (Xd1+Xe)

    which, being calculated as ratio among the 2 cathetus of the triangle

    E1-E10-VGRID, it represents just the pendency of its hypotenuse, that is thependency of the aforesaid segment (E1-VGRID).

    The pendency of (E1-VGRID 1) is greater of (E1-VGRID 2) therefore, with the

    external reactance Xe2 > Xe1 Ireact/Q are smaller (smaller pendency).

    E

    Generator

    xd1xe

    iexc1

    E1 V1I1

    V GRID

    G

    Stepuptransformer

    p

    Internal volt.generatorE1

    21

    E10

    E1

    Ireact Q (E1 V

    GRID) / (Xd1 + Xe)

    Ireact Q (E1 VGRID) / (Xd1 + Xe)

    xe1xd1

    Inside the Generator

    xe2unchanged but is Xe that changes

    Xe2 > Xe1

    Xd1 obviously remains

    V GRID

    The automatic regulation operates as explained in the followingimage.

    AnsaldoEnergia Una Societ Finmeccanica

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    109/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 108

    If, for example, the grid voltage drops (VGRID A --> VGRID B), the

    generator terminals voltage V1 drops too (V1A --> V1B) being

    still unchanged the field current Iexc and the internal voltage E1A(pls. see the upper diagram of the image).

    In that moment the delivered reactive power increases because

    increases V between E1A and VGRID B .

    The AVR sees V1 drop and corrects it increasing the field currentIexc [and consequently E1 (E1A --> E1C)] up to the condition in

    which V1 come back from V1B to V1A (pls. see the second

    diagram of the image).

    Due to this, the reactive power increases more up to QC .

    Same sequence, but inverted, if VGRID A jumps higher.

    .

    AnsaldoEnergia Una Societ Finmeccanica

    GRID VARIATION AND REGULATOR REACTION

    GRID VARIATION AND REGULATOR REACTION

    D lt th

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    110/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 109

    Correction due to the

    automatic regulation

    to bring back V1

    from V1B to V1A( which is the original

    value )

    Internal gen.voltage E1

    Terminals gen.voltage V1 V GRID

    V1AE1 A

    xe1

    xd1

    Inside the Generator V1B

    VGRID B

    QC E1C - VGRID B

    IC ,QC > IB ,QB > IA,QA

    QC E1C - VGRID B

    IC ,QC > IB ,QB > IA,QA

    E1 C

    iexc

    Representative straight lines of the voltage drop on the

    reactances Xd1 (yellow part) and Xe1 (white part)

    QA E1A - VGRID A

    QB E1A - VGRID B

    IB ,QB > IA,QA

    QA

    E1A

    - VGRID A

    QB E1A - VGRID B

    IB ,QB > IA,QAV GRID A

    Internal gen.voltage E1

    Terminals gen.voltage V1 V GRID

    V1AE1 A

    xe1xd1

    Inside the

    Generator V1B V GRID B

    Drop voltage on the

    grid with consequent

    drop voltage on V1( from V1A to V1B )

    1

    2

    Behaviour on a near short circuit

    AnsaldoEnergia Una Societ Finmeccanica

    During a strong and near short circuit on the grid, the voltage at generator terminals strongly lowers while,

    on the contrary, the statoric current increases correspondingly.

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    111/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 110

    Forcing of the automatic

    regulator in the attempt to

    sustain the voltage at the

    terminals of the generator

    Internal voltage ofgeneratorE1

    V GRID

    V1AE1 A

    xe1

    xd1

    Inside the Gen.

    V1B

    VGRID B

    QC E1C - VGRID B

    IC

    ,QC

    > IB

    ,QB

    > IA,Q

    A

    QC

    E1C

    - VGRID B

    IC

    ,QC

    > IB

    ,QB

    > IA,Q

    AE1 C

    iexc

    Voltage drop on

    the grid due to the

    short cicuit

    Voltage at gener.terminals V1

    on the contrary, the statoric current increases correspondingly.

    The electromagnetic flux in machine [ total = rotor - stator] strongly decreases a lot immediately,

    therefore the magnetic connection between rotor and stator becomes very weak and so the mechanical couple

    of the turbine, still strong because slower to be reduced, can cause the tear of the weak magneticconnection and it can produce the so-called out of step.

    This is avoided, at times, if the short circuit duration is so brief that the excitation current, quickly increased

    due to the ceiling, has had time to create a flux in machine such to be still able to withhold rotor and stator

    connected among them.

    V GRID ACorrection on the

    terminals voltage due

    to the ceiling

    Electric grid systemEach generator synchronised to the grid contributes to supply the grid load by its

    own stator current (I1,, In) ----> Itot = i IiIncreasing the generators number, both the total current Itot and the global grid

    AnsaldoEnergia Una Societ Finmeccanica

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    112/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 111

    E

    G 1

    xd1 xe1ie1

    E1 V1

    E

    G 2xd2 xe2ie2

    E2 V2

    E

    G n

    xdn xenien

    En Vn

    I1

    I2

    In

    Grid loads

    Z tot = very low

    n generatorssynchronised on

    the grid

    I tot

    V GRID

    E

    G AxdAxeA ieA

    EAVAIA

    g g , tot g g

    power increase consequently P = 3 * VGRID * I tot .The total grid impedence Ztot can be difined as ratio between the grid voltage

    VGRID divided by the total grid current Itot in order to satisfy the relation

    VGRID = Z tot * I tot .

    When an other new generator is connected to the grid, its contribution IA to feed

    the grid loads is added to the preexistent Itot

    and the grid voltage will be modified

    by that contribution with the same rate by which IA modifies Itot --> IA / Itot gives

    V on the grid.VGRID = Z tot * (Itot + IA) if IA

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    113/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 112

    E

    G 1

    xd1 xe1ie1

    E1 V1

    E

    G 2xd2 xe2ie2

    E2 V2

    E

    G n

    xdn xenien

    En Vn

    I1

    I2

    In

    Grid loads

    Z tot = very low

    n generatorssynchronised on

    the grid

    I tot

    V GRID

    E

    G AxdAxeA ieA

    EAVAIA

    G 1G 2G 3G nG A

    Grid

    loadsabsorption

    The tank level is mainly due and maintained by

    the big set of sources G1Gn balanced by the

    grid loads absorption.

    The new source GA is influent on the tank level as

    far as its contribution is relevant compared with

    the global contribution of all other sources.

    The electro-hydraulic comparison is significant inorder to emphatise the influence of a single generatorcontribution on the grid voltage alteration, when it isconnected to a powerful national grid.

    The regulation system provided into the exciter is normallycomposed by two identical digital automatic voltage

    AnsaldoEnergia Una Societ Finmeccanica

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    114/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 113

    composed by two identical digital automatic voltage

    regulator (AVR) operating in alternative (master & slave).

    At starting, each AVR can be selected as master.Being the stand-by regulator automatic type too (not manual)

    all functions of the main one are again available for the

    best dynamic control of the generator behaviour.

    The generator voltage feedback is doubled (one each AVR)

    and the feeders too in order to have 100% redundancy.

    A logic system (pls. see the following image) oversees the

    good operation of the AVRs and, in case of problems ofAVR master, decides to switch-over to the second AVR.

    Regulation and Control

    AnsaldoEnergia Una Societ Finmeccanica

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    115/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 114

    A V R

    Automatic regulator

    AVR 1

    Stator voltage and currentfeed-back (for channel 1)

    V stator

    I stator

    A V R

    Automatic regulator

    AVR 2

    Feeding

    V stator

    I stator

    Control/Protection Logic

    I/O to

    remote

    Converter 1

    Converter 2

    Plant

    Stator voltage and current

    feed-back (for channel 2)

    Feedbacks of the regulators

    AnsaldoEnergia Una Societ Finmeccanica

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    116/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 115

    VT1

    VT2

    CT-U

    CT-W

    For the

    regulator1

    For theregulator2

    For regulators

    1 e 2

    Generator

    Vc

    tensione

    statorica

    concatenata

    Set of 3 VTssingle phase for

    the voltage

    feedback of the

    machine

    Set of 3 VTs

    single phase for

    the voltagefeedback of the

    machine

    CTs for the

    current feedback

    of the machine

    Main breaker of

    the machineEvery regulator works correctly if only

    it is constantly informed on the

    actual values of voltage and currentproduced on the stator.

    For this purpose there are VTs and CTsconnected as in the figure.

    Every set of 3 VTs feeds its own

    regulator making in this way twoloops of stator voltage regulation

    completely independent.

    The CTs feed in series both the

    regulators and they are used to

    perform auxiliary functions(compound, limits, etc.).

    The following image shows a list of the main functions

    normally foreseen into each AVR (with optional too)

    AnsaldoEnergia Una Societ Finmeccanica

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    117/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 116

    normally foreseen into each AVR (with optional too).

    Some note on them.

    - Each of the two AVRs has the possibility to operate, locally,in manual mode too (commissioning phase) through the

    display and the keyboard mounted on the cubicle front.

    - The function called Power System Stabilizer (PSS) is usedto strongly reduce the oscillations (amplitude and time) on

    the stator machine variables, due to sudden load changes.

    - The best tuning of the PSS parameters have to be found by a

    complex plant/grid study, normally not given by theexciter supplier, but produced by the plant designer only.

    Typical functions of the automatic voltage regulation

    AnsaldoEnergia Una Societ Finmeccanica

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    118/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 117

    Automatic stator voltage regulation

    Manual field voltage regulation

    Reactive current compensation (pos. and neg.)

    Stabilizing signals function (PSS)

    Automatic reduction to zero of reactive power

    Automatic cos regulation

    Automatic reactive power regulation

    Voltage calibrator Max field current limit

    Underexcitation limit

    Voltage/frequency limit

    Automatic alignment with the other AVR

    Field winding temperature

    Max stator current limit

    Operating functions

    of the AVR regulator

    The green functions are optional and

    applicable in certain cases only.

    SFC interface and logic

    AUTOMATIC VOLTAGE REGULATOR

    AnsaldoEnergia Una Societ Finmeccanica

    F db k f t t

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    119/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 118

    + -Ref.

    Feedback of stator

    voltage

    Error

    +

    -

    Ref.

    Feedback

    of stator

    voltage

    K11 + s T1

    s

    +

    -

    K31 + s T3

    s

    Feedback of

    field voltage

    Thyristors

    firing angleA B

    Regulator Firingcircuits

    Regulation systemOperator

    interfaceG

    Feedback of stator

    voltage

    Bridge

    Transfer functions

    AUTOMATIC VOLTAGE REGULATOR

    AnsaldoEnergia Una Societ Finmeccanica

    The automatic regulation has the main purpose to maintain constant the voltage at

    the alternator terminals even if the load varies casually.

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    120/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 119

    Vstator

    time

    V0 V0

    transitory

    0

    Reference

    Error negative

    ( reduce Iexc)

    Errors positive

    (increase Iexc)

    Feedback

    time

    Error Error = Reference - Feedback

    Error = 0

    0

    The figure at left shows, for instance, the behaviour of the stator voltage of a

    machine that sees a load disconnection and reacts with its regulation.

    The voltage increases but the regulator reacts and brings it back to the previousvalue V0 after some oscillation (for simplicity in this example the contribution of

    the function compound is not considered pls. see next image).

    When the feedback changes the error on the reference corrects the Iexc.

    COMPOUND AND COMPENSATION

    AnsaldoEnergia Una Societ Finmeccanica

    This function automatically corrects the set-point of the regulation loop of the stator

    voltage in proportion to the actual current reactive delivered by the generator Such

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    121/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 120

    voltage, in proportion to the actual current reactive delivered by the generator. Such

    correction can be in increases (straight line in rise- compensation) or in decreases

    (straight line in descent-compound) but it is always done in automatic and transparent

    way for the operator.

    It is an additional signal injected in the comparison point that corrects the reference of the

    regulator.

    The compensation allows to maintain constant the voltage after the step-up transformer.

    The compound contributes to the automatic reactive load division among more groups

    of the same plant in parallel on the same bar (v. figures in the following slide).

    +-

    Ref.

    Feedback ofstator voltage

    +

    Compound Other

    signals

    1 p.u. di Ireact =

    I nom statoric

    Ireactiva

    Vstator

    1 p.u. Band

    0 22%

    Band

    0 22%

    Compensation

    Compound

    0

    Error

    DIVISION OF LOAD

    AnsaldoEnergia Una Societ Finmeccanica

    High voltage V0

    The load connection produces arapid lowering of the high voltage

    V0 that goes from here (V01) to

    here (V02)IB1IA1

    V1 V2

    V

    Generator 1 Generator 2

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    122/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 121

    In this case both the reactive currents IA1 and IB1 increase up

    to IA2 and IB2, but in different rate if the inclinations of the

    segments orange and blue (the compound) are different.

    In this case the load is not divided equally.Ireact

    Ireact

    The load connection produces a rapid loweringof the high voltage V0 that goes from here

    (V01) to here (V02)

    IB1

    IB2

    IA1

    IA2

    V1 V2

    V01

    V02

    Ireact1Ireact2

    G1 G2

    T1 T2

    V1 (M.V.) V2 (M.V.)

    IreactIreact

    In the orange diagrams the Ireact increases to the

    right from left, while in those blues the Ireact

    increases to the left from right

    Ireact

    Ireact

    B1

    IB2

    A1

    IA2

    The reactive currents IA1 and IB1 increase equally up to IA2 and IB2 if the

    inclinations of the segments orange and blue (the compound) are the same.

    In this way the load is equally divided.

    V01

    V02

    Ireact1 Ireact2

    STABILIZING SIGNALS ( PSS )

    AnsaldoEnergia Una Societ Finmeccanica

    Purpose of this function is to reduce the electromechanical oscillations of the machine

    due to consistent load variations and this favors the stability of the group and of the grid

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    123/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 122

    Apex of theoscillation

    Pendulum

    to it connected.

    Its intervention is transitory (just for the strong load variations only) and the principle of

    its operation is to add brief corrective impulses to the field current in the mostopportune instants of the oscillations: in such way the damping action will be favorite.

    An intuitive comparison that can clarify the mechanism concept of

    this function operation is illustrated in figure. In the moments near

    to those in which the pendulum reaches the apex of its oscillation

    it is possible to influence its future run giving new touches of

    push, also of modest entity, but in well precise instants. If such

    touches of push are applied, every time, immediately after the

    pendulum has already reached and overcome the apex of every

    run, the ampleness of its oscillations will increase more always.

    Contrarily, if that touches of push are applied, every time,

    immediately before the pendulum has reached the apex of everyrun, the ampleness of its oscillations will find contrast and it will

    decreaseprogressively.

    This is the same principle of action of the stabilizing signals.

    STABILIZING SIGNALS ( PSS )

    AnsaldoEnergia Una Societ Finmeccanica

    The two following figures show what is the effectiveness of the

    bili i i l h d h i ill i

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    124/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 123

    -1 0 1 2 3 4 5 6 7 80

    0.5

    1

    1.5

    P

    -1 0 1 2 3 4 5 6 7 80

    0.5

    1

    1.5

    P

    Without PSS With PSS

    stabilizing signals on the process to reduce the statoric oscillations

    produced by a strong transitory of power on the grid (for instance

    short circuit).

    The setting of the PSS parameters for a generator connected to a particular electric grid can

    normally be optimized with specific SW simulations, given by the Manager of the Grid.

    REGULATION OF THE REACTIVE POWER

    AnsaldoEnergia Una Societ Finmeccanica

    The regulation of the reactive power Q is done with the help of the regulation loop of the statoric voltage,

    through which, regulating the field current (and therefore the internal voltage Ei), it is possible vary the

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    125/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 124

    Internal voltage E1

    Grid voltage VGRID

    (E1 VGRID ) Q

    Time

    Voltages

    0

    Correcting E1 in order to recopy VGRID, the Q will be maintained constant

    through which, regulating the field current (and therefore the internal voltage Ei), it is possible vary the

    reactive power that the generator exchanges with the load (as already seen previously).

    With this type of regulation, Q is maintained constant maintaining constant the difference between the

    internal voltage Ei and the grid voltage VGRID.Practically there is a regulation loop in which the wished reference Q* is continuously compared with the

    real reactive power currently delivered: the possible error corrects the reference of the voltage loop to vary

    Ei in such way that the generator will produce a Q (= Ei-VGRID) equal to the wished reference Q*.

    REGULATION OF THE POWER FACTOR

    AnsaldoEnergia Una Societ Finmeccanica

    The regulation of the power factor (cos ) is done with the help of the regulation loop

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    126/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 125

    MW

    MVAROver-excitation

    Under-excitation

    MW2

    MVAR2

    MVAR1

    MW1

    P1

    P2

    P1

    0

    g p ( ) p g pof statoric voltage, through which it is possible vary the reactive power exchanged by

    the generator with the load (as already seen previously) and consequently its cos .

    The working principle of this type of regulation is

    the following.

    Continuously it is measured the active power

    value that the machine is delivering now and,

    based on it, it is calculated the consequent

    reactive power that maintains constant thewanted relationship among these two powers

    (active and reactive) and therefore the cos .

    The automatic regulator will act to maintain this

    calculated reactive power until there will be a

    successive variation of the active power.

    The figure shows that, if the MW changes (from

    MW1 to MW2), the exciter will vary the MVAR

    (from MVAR1 to MVAR2) and P1 P2.

    LIMITS IN OVER AND UNDEREXCITATION ZONES

    AnsaldoEnergia Una Societ Finmeccanica

    MW Action curve of the

    overexcitation limit

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    127/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 126

    LIMIT IN OVEREXCITATION

    This function protects the generator against

    prolonged trespasses out of the capabilityzone hazardous for the integrity of the field

    windings.

    LIMIT IN UNDEREXCITATION

    This function protects the generator against

    prolonged trespasses out of the capability

    zone hazardous for the stability of the group

    and for the integrity of terminal parts of the

    stator.

    MVAR

    0

    Overexc.Underexc.

    +

    overexcitation limit

    MVAR

    Nominal workingpoint Pn

    MW

    0

    Overexc.Undrexc.

    _

    Action curve of the

    underexcitation limit

    LIMIT OF FLUX

    AnsaldoEnergia Una Societ Finmeccanica

    Th fl i id h hi i i b h i V/f

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    128/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 127

    f (%)

    V (%)

    100%95%

    95%

    105%

    105%

    98%

    103%

    102%

    Flux V/f == 105% nom

    Flux V/f == 95% nom

    The flux inside the machine is given by the ratio V/f .

    The colored area represents the surface of the normal

    working points allowed indefinitely by the project,while the outlined areas adjacent to it, are always

    representative of working points allowed for the

    machine, but with more stressful conditions of those

    in the colored zone.

    For this reason the permanent exercise of the group

    outside the colored area is unadvisable, in order to

    limit, as far as possible, the "loss of life" of the

    generator.

    The flux limit of the exciter acts along the highest

    oblique segment and it adapts the stator voltage on the

    foreseen relationship V/f, when the frequencydecreases.

    .

    AnsaldoEnergia Una Societ Finmeccanica

    V (%)

    In this diagram V/f the limitations are

    due to:

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    129/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 128

    A

    D

    B

    C

    f (%)

    100%95%

    95%

    105%

    105%

    98% 103%102%

    Flux V/f == 105% nom

    Flux V/f == 95% nom

    in A

    max flux (V/f) , max voltage (gen.)

    and min frequency (turbine)

    in B

    max voltage and max frequency

    in C

    max frequency, min voltage (max

    current) and min flux (instability)

    in D

    min frequency and min voltage

    (max current)

    The reactive power and power factor regulations can be only

    AnsaldoEnergia Una Societ Finmeccanica

    NOTES

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    130/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 129

    - The reactive power and power factor regulations can be only

    actuated when the generator is synchronized to the grid.

    Its disconnection automatically produces a change-over to

    the stator voltage regulation (in island configuration too).

    - Any change-over to the other regulator is bumpless in

    order to avoid any dynamic and thermal machine variation.

    Typical exercise sequence of a generator

    AnsaldoEnergia Una Societ Finmeccanica

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    131/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 130

    Predisposition completed

    Turbine at nominal speed

    Exciter fed and in automatic

    voltage regulation

    Exc

    ON

    Exc

    OFF

    Soft-start

    Voltageequalization

    First loading

    (few MW)

    INCR / DECR

    EHC and EXCLOADING

    Reduction of

    Reactive

    Power to 0

    Reduction of

    Active

    Power to 0

    Disconnection

    from the grid

    LOADINGVOLTAGE

    Regulation

    Synchronization

    Reg. COS orReg. REACT.

    Generator

    de-excited

    FRONT VIEW OF A TYPICAL EXCITATION BOARD

    AnsaldoEnergia Una Societ Finmeccanica

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    132/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 131

    AnsaldoEnergia Una Societ Finmeccanica

    INTERNAL VIEW OF TYPICAL POWER CUBICLES

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    133/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 132

    AnsaldoEnergia Una Societ Finmeccanica

    TYPICAL MODULE WITH THYRISTORS AND RADIATORS

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    134/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 133

    AnsaldoEnergia Una Societ Finmeccanica

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    135/141

    Doc. n 196 W 429 Rev.1 Oct. 2008 134

    EXCITATION

    TRANSFORMERS

    EXCITATION TRANSFORMERS

    AnsaldoEnergia Una Societ Finmeccanica

    The feeding transformers of the excitation systems are substantially

  • 7/29/2019 9-Generator Performance Curves and Static Exciation

    136/141

    Doc.