Upload
nabil160874
View
234
Download
0
Embed Size (px)
Citation preview
7/29/2019 9-Generator Performance Curves and Static Exciation
1/141
Doc. n 196 W 429 Rev.1 Oct. 2008 1
AnsaldoEnergia Una Societ Finmeccanica
.
DPT. ELECTRICAL MACHINES
_____________________________________
PRESENTATION
PERFORMANCES CURVES OF THE ALTERNATOR
+
STATIC EXCITATION SYSTEM
_____________________________________
7/29/2019 9-Generator Performance Curves and Static Exciation
2/141
Doc. n 196 W 429 Rev.1 Oct. 2008 2
AnsaldoEnergia Una Societ Finmeccanica
Summary
1st PART (sh. 3)
PERFORMANCES CURVES OF THE ALTERNATOR
2nd PART (sh. 39)STATIC EXCITATION SYSTEM
.
7/29/2019 9-Generator Performance Curves and Static Exciation
3/141
Doc. n 196 W 429 Rev.1 Oct. 2008 3
1st PART
AnsaldoEnergia Una Societ Finmeccanica
7/29/2019 9-Generator Performance Curves and Static Exciation
4/141
Doc. n 196 W 429 Rev.1 Oct. 2008 4
PERFORMANCES CURVES
OF THE ALTERNATOR
AnsaldoEnergia Una Societ Finmeccanica
7/29/2019 9-Generator Performance Curves and Static Exciation
5/141
Doc. n 196 W 429 Rev.1 Oct. 2008 5
The performances given by a generation groupof electric energy (type turbogenerator,hydrogenerator, etc.) they are essentiallysynthesized by the following types of curves,that represent an useful tool to support theexercise and maintenance operators of a
production plant.
1a - Saturation and short circuit curves
1b - Capability diagram
1c - V curve
1d - Power vs. temperature curve (for GT)
AnsaldoEnergia Una Societ Finmeccanica
7/29/2019 9-Generator Performance Curves and Static Exciation
6/141
Doc. n 196 W 429 Rev.1 Oct. 2008 6
1 a SATURATION AND SHORT
CIRCUIT CURVES
AnsaldoEnergia Una Societ Finmeccanica
G
T
25C
Iexc
nom
Vstator
Main Breaker
OPEN
At no-load
At nominal
speed
Temperature
The saturation curve of analternator shows the behavior of
the stator voltage versus the
variations of the excitation
current Iexc injected in the rotorwindings.
This curve is done at no-load
conditions, at nominal speed
revolution and at a defined
ambient temperature.
7/29/2019 9-Generator Performance Curves and Static Exciation
7/141
Doc. n 196 W 429 Rev.1 Oct. 2008 7
( 1 a Saturation and
short circuit curves )
AnsaldoEnergia Una Societ Finmeccanica
The a) diagram shows that,
when the excitation current
increases, after a certain linear
trait, appears a knee of the
voltage V due to a saturationphenomenon of the magnetic-
iron material of which the
laminated core of the stator is
composed.
a)
Vstator
Iexc
7/29/2019 9-Generator Performance Curves and Static Exciation
8/141
Doc. n 196 W 429 Rev.1 Oct. 2008 8
The diagram also showsthe short circuit straight
line b) obtained
measuring the statorcurrent versus variations
of excitation current,
when the main terminals
of the stator have been
short circuited.
AnsaldoEnergia Una Societ Finmeccanica
( 1 a Saturation and
short circuit curves )
b)
Iexc
Istator
7/29/2019 9-Generator Performance Curves and Static Exciation
9/141
7/29/2019 9-Generator Performance Curves and Static Exciation
10/141
Doc. n 196 W 429 Rev.1 Oct. 2008 10
1 b CAPABILITY DIAGRAM
AnsaldoEnergia Una Societ Finmeccanica
It is a particularly important diagram because it
synthetically represents by a close surface all the
possible working points of the generation group
(turbine + alternator) in terms of MW and MVAR
delivered for the external loads.
This diagram therefore is valid if the generator is on
load only [i.e. when it is synchronised to the grid or
it is loaded locally (in island)].
7/29/2019 9-Generator Performance Curves and Static Exciation
11/141
Doc. n 196 W 429 Rev.1 Oct. 2008 11
( 1 b Capability diagram )
AnsaldoEnergia Una Societ Finmeccanica
MW
+
-
MVAR
Over
Under
Mw are in abscissa and MVAR are in
ordinate.
Each segment of the star having origininto zero is composed by working points
having same ratio between MW-MVAR
and therefore the same cos .
Every half-circumference with center in theorigin is composed by working points at
constant MVA, but with different cos .
The curves are at Vstator= constant.
In this case the capability are three and
each of them corresponds to a generator
cooling more or less intense (here done
with hydrogen at different pressures).
7/29/2019 9-Generator Performance Curves and Static Exciation
12/141
Doc. n 196 W 429 Rev.1 Oct. 2008 12
The overexcitation quadrant is atpositive MVAR (positive cos).
The underexcitation one is at
negative MVAR (negative cos).
In the example at side, the nominalworking point (on which the whole
group is sized) is at cos= + 0,85
in overexcitation.
The boundaries of the curves are
due to the limits of the machine
project.
AnsaldoEnergia Una Societ Finmeccanica
( 1 b Capability diagram )
Nominal
working point
+
-
MVAR
Over
Under
MW
7/29/2019 9-Generator Performance Curves and Static Exciation
13/141
Doc. n 196 W 429 Rev.1 Oct. 2008 13
At side, the boundaries of the
capability, imposed by the sizingand by the characteristics of themachine, are highlighted withcolored lines.
More in detail:
green line: limitation due to themax thermal ability of the stator
blue line: limitation due to themax thermal ability of the rotor
red line: limitations due toproblems of dynamic stability andto heating of parts situated in theextreme zones of the statorpackage.
AnsaldoEnergia Una Societ Finmeccanica
( 1 b Capability diagram )
Nominal
working point
+
-
MVAR
Over
Under
MW
7/29/2019 9-Generator Performance Curves and Static Exciation
14/141
Doc. n 196 W 429 Rev.1 Oct. 2008 14
This curve is particularly meaningful for the exerciseoperators and therefore it deserves further details in
order to explain the manner by which it is gotten and
the reasons for which some limitations are applied to it.
The following images go through the sequence of all thephases of the capability construction and they focus,
particularly, the phenomena that converge to establish
its boundaries in the plan of the active (MW+) and
reactive (MVAR +/-) powers.
AnsaldoEnergia Una Societ Finmeccanica
( Appendix to the item 1b )
7/29/2019 9-Generator Performance Curves and Static Exciation
15/141
Doc. n 196 W 429 Rev.1 Oct. 2008 15
AnsaldoEnergia Una Societ Finmeccanica( Appendix to the item 1b )
.
Now we go back through the notes on the capability already seen, starting from the
origin and using the physical considerations that have contributed to produce it..
------------------------------The capability diagram is represented on the Active/Reactive
Powers and it includes all possible working points of the
generator (each point is defined by its active/reactive values).
It is applicable to thesynchronized machine only and it dependsby the size of turbine and alternator,
Some limitations are applicable due to the materials temperatures
and to the dynamic performances of the group (stability).
The following images show in sequence the main considerationsthat produce, as final result, the definition of the capability.
7/29/2019 9-Generator Performance Curves and Static Exciation
16/141
Doc. n 196 W 429 Rev.1 Oct. 2008 16
AnsaldoEnergia Una Societ Finmeccanica
.
1 step (pls. see next image)
On the surface Active/Reactive Power the portion at MW < 0
is not considered [because we are talking of generators MWdelivered to the grid(MW with sign > 0) and not motors
MW absorbed from the grid(MW with sign < 0)].
The size imposed by the Client (apparent power MVA) defines
on this plan an half-circle including all working points having
MVA the size required (its limit is just the half-circumferenceat max MVA).
The nominal cos required, together with the apparent powerrequired, define the nominal working point of the whole
group turbine-generator.
( Appendix to the item 1b )
7/29/2019 9-Generator Performance Curves and Static Exciation
17/141
Doc. n 196 W 429 Rev.1 Oct. 2008 17
AnsaldoEnergia Una Societ Finmeccanica
.
( Appendix to the item 1b )
Nominal apparent power
(MVA) of the alternator
Active Power
Positive reactive
power
Negative reactive
powerUnder-
excitationLEADING
Over-
excitationLAGGING
0
Motor
Nominal working point
(nominal power at nominalcos )
(+)
(
-)
Generic working point
(MVA corrispondent to a
generic MW / MVAR)
MVAR
MW
MVA nominal
MVA
Doc. n 196 W 429 Rev.1 Oct. 2008
7/29/2019 9-Generator Performance Curves and Static Exciation
18/141
Doc. n 196 W 429 Rev.1 Oct. 2008 18
2 step (pls. see the following image)
The nominal working point (MVA, MW, MVAR, cos)is the main reference for turbine and generator sizing.
Consequently, the turbine is designed to deliver, as its maxpower, the MW correspondent to the nom. working point.
This is the first limitation that cuts the upper part of thecapability diagram.
It will be physically impossible to over-exceed that MWand, therefore, the upper highlighted area will be erased
because inaccessible (forbidden working conditions of thegroup).
AnsaldoEnergia Una Societ Finmeccanica( Appendix to the item 1b )
7/29/2019 9-Generator Performance Curves and Static Exciation
19/141
7/29/2019 9-Generator Performance Curves and Static Exciation
20/141
Doc. n 196 W 429 Rev.1 Oct. 2008 20
3 STEP (pls. see the following image)
The nominal working point (MVA, MW, MVAR, cos)is the main reference for turbine and generator sizing.
The generator will have the stator size designed on theMVA of the nominal working point and, similarly, therotor size.
The outlined half-circumference (MVA=constant)represents all points at the same MVA of the nominal
working point.The rotor is sized for the steady field current correspondentto the nominal working point and this size limits theworking conditions up to the points correspondent to the
red line.Consequently, the blue area also (at right end of diagram)is cutted and inaccessible, because of the rotor size.
AnsaldoEnergia Una Societ Finmeccanica( Appendix to the item 1b )
7/29/2019 9-Generator Performance Curves and Static Exciation
21/141
Doc. n 196 W 429 Rev.1 Oct. 2008 21
.
.
AnsaldoEnergia Una Societ Finmeccanica
Nominal working point
Active powerNominal apparent power
(MVA) of the alternator
and stator size (+)
Inaccessible area due to the
rotor size of the generator
Limitation due to
the rotor size
0
Positive reactive
power
Negative reactive
powerUnder-
excitationLEADING
Over-
excitationLAGGINGMotor
(
-)
Doc. n 196 W 429 Rev.0 March 2005
( Appendix to the item 1b )
7/29/2019 9-Generator Performance Curves and Static Exciation
22/141
Doc. n 196 W 429 Rev.1 Oct. 2008 22
Just for example, eacharc of circumference inblue in the figure,
corresponds to workingpoints having all thesame excitation current.
In particular, the design ofthe rotor is sized on theexcitation currentcorresponding to thenominal working point Pn.
The center of these arcsis found in a specific pointsituated on the MVAR
axis in underexcitation atabout 1/Xd from thezero.
AnsaldoEnergia Una Societ Finmeccanica
MW
MVAR
0
Nominal workingpoint Pn
1 / Xd
Overexc.
Underexc.
( Appendix to the item 1b )
7/29/2019 9-Generator Performance Curves and Static Exciation
23/141
Doc. n 196 W 429 Rev.1 Oct. 2008 23
4 STEP (pls. see the following image)
The last limitation on the capability diagram (the blue
area at left end) is due to stability problems of thegenerator and to overheating of some parts at the statorcore ends.
The risk of instability is mainly due to weak flux inside the
machine air-gap that makes feeble the magnetic connectionbetween rotor and stator, with consequent its easy tear.
The overheating on the extreme parts of the statorwindings, due to a particular magnetic flux disposition in
that zone, is the second reason of limitation on this under-excitation area of the capability diagram.
AnsaldoEnergia Una Societ Finmeccanica( Appendix to the item 1b )
7/29/2019 9-Generator Performance Curves and Static Exciation
24/141
Doc. n 196 W 429 Rev.1 Oct. 2008 24
.
AnsaldoEnergia Una Societ Finmeccanica
Inaccessible area due to stability
problems and overheating of
some parts at the stator core ends.
Active power
MW
0
Positive reactivepower MVAR
Negative reactivepower MVAR
Under-excitation
LEADING
Over-excitation
LAGGINGMotor
(-)
(+)
Limitation
Nominal working pointHeating
problems
Stability problems
( Appendix to the item 1b )
7/29/2019 9-Generator Performance Curves and Static Exciation
25/141
Doc. n 196 W 429 Rev.1 Oct. 2008 25
The final configuration of the capability diagram for theturbo-generator set is shown on the following image.
All permissible working points (at steady state) for the group
( if synchronized ) are included into the green area only.
The protection to avoid the MW over-exceeding (to shift toordinates higher than the max allowed) is intrinsic due tothe turbine size.
On the contrary, the protections against working attempts
out of the above mentioned limitations at right or left ends,are foreseen and performed by the excitation system.
AnsaldoEnergia Una Societ Finmeccanica( Appendix to the item 1b )
7/29/2019 9-Generator Performance Curves and Static Exciation
26/141
Doc. n 196 W 429 Rev.1 Oct. 2008 26
Capability diagram of generator
Nominal working point
Inaccessible area due to the
turbine power limitation
Inaccessible area due to therotor size of the generator
Inaccessible area due to stability
problems and overheating of some
part at the stator core ends.
Max apparent power of the
generator
Active power
Positive reactive
power
Negative reactive power Under-excitation
LEADING
Over-excitation
LAGGING
0
Motor
Under-excitation limit Max rotor current limit
Max turbine
power
AnsaldoEnergia Una Societ Finmeccanica( Appendix to the item 1b )
7/29/2019 9-Generator Performance Curves and Static Exciation
27/141
Doc. n 196 W 429 Rev.1 Oct. 2008 27
CAPABILITY DIAGRAM OF GENERATOR
Movements of the working points
AnsaldoEnergia Una Societ Finmeccanica
MW
MVAR
Over-excitation
Under-excitation
AVR
AVR
EHC EHC
Zone
MOTOR
( Appendix to the item 1b )
From the point of view of the machineconduction, we remember that any
change of the working point on the
capability is done by commands on
the EHC (turbine regulation) and/or on
the AVR (voltage regulation into theexciter).
In particular, as shown at side, the
variations of MW are obtained by
actions on the EHC only, while the
variations of MVAR are produced by
commands on the AVRonly.
7/29/2019 9-Generator Performance Curves and Static Exciation
28/141
7/29/2019 9-Generator Performance Curves and Static Exciation
29/141
7/29/2019 9-Generator Performance Curves and Static Exciation
30/141
7/29/2019 9-Generator Performance Curves and Static Exciation
31/141
Doc. n 196 W 429 Rev.1 Oct. 2008 31
AnsaldoEnergia Una Societ Finmeccanica.
V curve of the generator
I excitation
P apparent
0
Nominal
working point
P app nom
Iexc at no-loadA
B
E
I exc nom
Limitation dueto the max
power of theturbine
.% Iexc
at no-load
D C
OverUnder
( 1 c V curve )
The following image shows the correspondence of some working points
both on the capability diagram and on the V curve.
7/29/2019 9-Generator Performance Curves and Static Exciation
32/141
Doc. n 196 W 429 Rev.1 Oct. 2008 32
AnsaldoEnergia Una Societ Finmeccanica
.
( 1 c V curve )
Correspondence between Capability and V curves
7/29/2019 9-Generator Performance Curves and Static Exciation
33/141
7/29/2019 9-Generator Performance Curves and Static Exciation
34/141
Doc. n 196 W 429 Rev.1 Oct. 2008 34
AnsaldoEnergia Una Societ Finmeccanica
.
MW
MVAR
cos = 0.85
MVA
0
Sovraecc.
Sottoecc.
( 1 d Power vs. temperature )
7/29/2019 9-Generator Performance Curves and Static Exciation
35/141
Doc. n 196 W 429 Rev.1 Oct. 2008 35
GENERATOR SYNCHRONIZED :
OVER-EXCITATION &
UNDER-EXCITATION
AnsaldoEnergia Una Societ Finmeccanica
7/29/2019 9-Generator Performance Curves and Static Exciation
36/141
Doc. n 196 W 429 Rev.1 Oct. 2008 36
AnsaldoEnergia Una Societ Finmeccanica.
The image at side represents, symbolically and from the reactive
power point of view only, the generator synchronized on the
national grid.
GX
ReteVa Vr
The interconnecting reactance X
allows the reactive power exchange
between generator and grid.
In the synchronizing instant Va=Vr : no flux of reactive current
through the reactance is there ( I = (Va-Vr) / X ---> I = 0 = Q ).
If Vr remains constant and Va changes, reactive current increases.
If Va > Vr I and Q go from G to grid (over-excitation).
If Va < Vr I and Q go from grid to G (under-excitation).
7/29/2019 9-Generator Performance Curves and Static Exciation
37/141
Doc. n 196 W 429 Rev.1 Oct. 2008 37
AnsaldoEnergia Una Societ Finmeccanica.
In over-excitation Ia flows from G to the grid and produces on X a
voltage drop with sign + at G side.
In under-excitation, on the contrary, Ia flows from the grid to G
and produces on X a drop voltage with sign + at grid side.
Being Ia always 90 delaied on Vt, in over-excitation the Va-Ia
vectorial diagram says that G sees an inductive load, while in
under-excitation G sees on the contrary a capacitive load (pls.see this images).
GX
GridVa Vr
Ia
Vt
Over-excitation
+_
GX
GridVa Vr
Ia
Vt
Under-excitation
+_
Inductive load Capacitive load
7/29/2019 9-Generator Performance Curves and Static Exciation
38/141
7/29/2019 9-Generator Performance Curves and Static Exciation
39/141
Doc. n 196 W 429 Rev.1 Oct. 2008 39
AnsaldoEnergia Una Societ Finmeccanica.
2nd PART
7/29/2019 9-Generator Performance Curves and Static Exciation
40/141
7/29/2019 9-Generator Performance Curves and Static Exciation
41/141
7/29/2019 9-Generator Performance Curves and Static Exciation
42/141
7/29/2019 9-Generator Performance Curves and Static Exciation
43/141
7/29/2019 9-Generator Performance Curves and Static Exciation
44/141
Doc. n 196 W 429 Rev.1 Oct. 2008 44
When the generator is synchronized, the grid creates on its
stator winding a strong rotating electromagnetic field (like
magnet), which finds in front the rotor magnet with correct
polarities and their attraction is consequent.
But their magnetic connection is strictly dependent by the air
gap magnetic flux, which is strong if the rotor magnet is
powerful and fragile if the rotor magnet is feeble.The energy exchange between generator and grid is controlled
through the regulation of that flux.
Consequently, a rotating permanent magnet could not control
that exchange, while a rotating magnet produced by field
excitation (d.c. current) can properly regulate that exchange.
AnsaldoEnergia Una Societ Finmeccanica
7/29/2019 9-Generator Performance Curves and Static Exciation
45/141
7/29/2019 9-Generator Performance Curves and Static Exciation
46/141
7/29/2019 9-Generator Performance Curves and Static Exciation
47/141
Doc. n 196 W 429 Rev.1 Oct. 2008 47
A machine is ageneratorif its rotor magnet, powered by
the mechanical couple of the turbine, rotates ahead of the
stator magnet (of the grid) and pulls and drags it.
On the contrary, a machine is a motorif the stator magnet
(of the grid) rotates ahead and pulls and drags the
rotor magnet.
The angle displacement between the axes of the rotor and
stator magnets is called load angle.
We are always speaking aboutgenerators .
AnsaldoEnergia Una Societ Finmeccanica
AnsaldoEnergia Una Societ Finmeccanica
7/29/2019 9-Generator Performance Curves and Static Exciation
48/141
Doc. n 196 W 429 Rev.1 Oct. 2008 48
In order to deliver big amounts of energy to the grid, the
turbine gives high torque couples to the generator shaft.
But that high couples, applied to the rotor body/magnet,
succeed to drag the stator magnet if only the magnetic flux
inside the air gap is very strong ( rotor-stator link, in thiscase, must be very solid to do it). Strong flux means
high intensities of excitation current on the rotor winding
(this is the over-excitation status).
On the contrary, when the excitation current is reduced, thepossibility to transmit energy to the grid is correspondingly
reduced because the flux is reduced.
In that conditions it is hazardous have strong couples onthe shaft because it becomes easier to tear the magnetic
link between rotor and stator magnets (under-excitation
status).
AnsaldoEnergia Una Societ Finmeccanica
7/29/2019 9-Generator Performance Curves and Static Exciation
49/141
Doc. n 196 W 429 Rev.1 Oct. 2008 49
The previous general introduction clarifies the necessity
and the advantages to create an artificial magnet on the
rotor through d.c. currents flowing into windings mountedon the rotor body.
The excitation systems was conceived just with the main
purpose to supply d.c. currents for the rotor windings.
Nevertheless this is not the unique goal of the exciters and,
taking advantage of the control facilities on the fieldcurrent, other important functions can be performed.
AnsaldoEnergia Una Societ Finmeccanica
7/29/2019 9-Generator Performance Curves and Static Exciation
50/141
7/29/2019 9-Generator Performance Curves and Static Exciation
51/141
7/29/2019 9-Generator Performance Curves and Static Exciation
52/141
Doc. n 196 W 429 Rev.1 Oct. 2008 52
.
AnsaldoEnergia Una Societ Finmeccanica
+_
Alternator
Rotor rings
Dynamo
+
_
Alternator and
rectifier bridge(the electrical scheme
is for brushless too)
+
_
+
_
Static
Various types of
excitation system
AnsaldoEnergia Una Societ Finmeccanica
7/29/2019 9-Generator Performance Curves and Static Exciation
53/141
Doc. n 196 W 429 Rev.1 Oct. 2008 53
ADVANTAGES OF FULLY STATIC EXCITER______________________
HIGH RELIABILITY SHORT TIMES TO RESTORE EVENTUAL FAULTS(due to the static components only) (economic advantages for reduction of production loss)
COMPLETE REDUNDANCY SIMPLIFIED MAINTENANCE
(ex. brushless is not doubled) (practically nothing)
DYNAMIC RESPONSE FAST FIELD DE-EXCITATION
(negligible delays and negative ceiling) (direct on the machine field)
GLOBAL EFFICIENCY SHORTER LENGTH OF THE SHAFT
(reduced losses) (reduced dimensions)
For all that reasons the plant strongly gains on its economical balance.
AnsaldoEnergia Una Societ Finmeccanica
7/29/2019 9-Generator Performance Curves and Static Exciation
54/141
7/29/2019 9-Generator Performance Curves and Static Exciation
55/141
AnsaldoEnergia Una Societ Finmeccanica
7/29/2019 9-Generator Performance Curves and Static Exciation
56/141
Doc. n 196 W 429 Rev.1 Oct. 2008 56
+
EXCITATION
CUBICLE
MAIN
GENERATOR
EXCITATION
TRANSFORMER
ENERGY FOR
EXCITATION
SYSTEM
STATIC EXCITATION SYSTEMSTATIC EXCITATION SYSTEM
ENERGY FORTHE ROTOR
WINDING
AnsaldoEnergia Una Societ Finmeccanica
AnsaldoEnergia Una Societ Finmeccanica
7/29/2019 9-Generator Performance Curves and Static Exciation
57/141
Doc. n 196 W 429 Rev.1 Oct. 2008 57
Typical parameters for evaluation
of the excitation systems performances______________________
CEILING
REGULATION ACCURACY
SYSTEM RESPONSE
SYSTEM SETTLING TIME
g
7/29/2019 9-Generator Performance Curves and Static Exciation
58/141
7/29/2019 9-Generator Performance Curves and Static Exciation
59/141
AnsaldoEnergia Una Societ Finmeccanica
7/29/2019 9-Generator Performance Curves and Static Exciation
60/141
Doc. n 196 W 429 Rev.1 Oct. 2008 60
.
t [sec]
V stat. generat.
The regulation accuracy is evaluated by the displacement, at steady, between
Vg2 (final value after oscillation) and Vg1 (previous value).
Vg2Vg1
ACCURACY
displacement
O
AnsaldoEnergia Una Societ Finmeccanica
7/29/2019 9-Generator Performance Curves and Static Exciation
61/141
Doc. n 196 W 429 Rev.1 Oct. 2008 61
RESPONSE
It is a parameter that gives the idea of the promptness by which theexcitation system responds to the variations, mainly in automatic
regulation mode.The international Standards define this evaluation method asshown into the following image (find the compensation line, markthe intersection point at 0.5s and apply the indicated formula).
Starting from the nominal excitation voltage, the ceiling voltage isimposed by the regulator and the resulting excitation voltage shapeon the field is a curve significant of the exciter response.
The response measure has meaning for rotating exciters onlybecause for the static exciters it is directly proportional to the
ceiling.
g
AnsaldoEnergia Una Societ Finmeccanica
7/29/2019 9-Generator Performance Curves and Static Exciation
62/141
Doc. n 196 W 429 Rev.1 Oct. 2008 62
.
t [s]
V excitation
O
A
BC
V ceiling
A
R = AB / (BC*OC)R = AB / (BC*OC)
0.5 s
RESPONSE
V nominal excitation
Rotating exc. RED AREAS
Static exc. GREY AREAS
AC = compensation line
considering instant t=0.5 s, area ABC must be equal
to the area under the real curve (the exponential for
rotating exciter and the step for static)
01
7/29/2019 9-Generator Performance Curves and Static Exciation
63/141
AnsaldoEnergia Una Societ Finmeccanica
7/29/2019 9-Generator Performance Curves and Static Exciation
64/141
Doc. n 196 W 429 Rev.1 Oct. 2008 63
.
t [sec]
V stat. generat.
Time t0 is defined as the interval from t=0 to the instant in which the oscillation returns and
remains contained into a certain band up to the steady state.
The width of this band (. %) has to be defined in order to be able consequently to define t0 .
Vg2
Vg1
t0
Band ( . %)
SETTLING TIME
O
AnsaldoEnergia Una Societ Finmeccanica
7/29/2019 9-Generator Performance Curves and Static Exciation
65/141
Doc. n 196 W 429 Rev.1 Oct. 2008 64
STATIC EXCITER
g
AnsaldoEnergia Una Societ Finmeccanica
7/29/2019 9-Generator Performance Curves and Static Exciation
66/141
Doc. n 196 W 429 Rev.1 Oct. 2008 65
.
STATIC EXCITATION SYSTEMONE LINE BLOCK DIAGRAM
STATIC EXCITATION SYSTEMONE LINE BLOCK DIAGRAM
G
AVR 1
AVR 2
CB
RES
EXCITATION
TRANSFORMER
Ref. 1
2
EXCITATION
BOARD
MAIN
GENERATOR
Commands
and signals
from remote
Bridge 1
Bridge 2
+
_
Signals
to remote
AnsaldoEnergia Una Societ Finmeccanica
.
7/29/2019 9-Generator Performance Curves and Static Exciation
67/141
Doc. n 196 W 429 Rev.1 Oct. 2008 66
g
TYPICAL INTERFACE OF THE EXCITATION BOARD
INPUT OUTPUT
Excitation
board
3 LV power line
from excitation transformer
Analogical signals from remote
Commands from remote
Permissives from remote
Trip from remote
d.c. power output (+ and -)
to the rotor of the machine
Analogical signals to remote
State signals to remote
Alarms to remote
Trip request to remote
Aux feeding voltages
7/29/2019 9-Generator Performance Curves and Static Exciation
68/141
7/29/2019 9-Generator Performance Curves and Static Exciation
69/141
AnsaldoEnergia Una Societ Finmeccanica
.
7/29/2019 9-Generator Performance Curves and Static Exciation
70/141
Doc. n 196 W 429 Rev.1 Oct. 2008 69
A particular feeding system taken from the generator terminals, now nomore used, is with a voltage transformer (TRE) and a current transformer
(TAT). The TRE feeds a thyristors bridge which is in series with a diodes
bridge fed, on the contrary, by the TAT. In this case too it is necessary the
use of the pre-excitation circuit.
When the generator is at no-load, the
machine is excited by the contribution of
the TRE only (in fact the stator current
I=0). If the generator is in short circuit
(also permanent) it is the TAT alone that
contributes to excite it (in fact the stator
voltage V=0). In any other working
condition (between these two extreme)
both the transformers contribute to excite
the machine. The quick intervention on
the line faults of the actual digital
protections has made useless this systemwhose principal characteristic was just to
succeed in sustaining for long time the
short-circuits prolonged.
Static
exciterGen
Voltagetransformer(TRE)
Currenttransformerwith air-gap (TAT)
V of the
machine
I of the
machine
From
TRE
From
TAT
+
-
+
-
Thyristors
Diodes
7/29/2019 9-Generator Performance Curves and Static Exciation
71/141
AnsaldoEnergia Una Societ Finmeccanica
.
7/29/2019 9-Generator Performance Curves and Static Exciation
72/141
Doc. n 196 W 429 Rev.1 Oct. 2008 71
UPS or plant Battery
Feeder
To regulation
system 1
To regulation
system 2
Feeder
Exciter
Each regulation system is fed with security and with the possibility to becompletely deactivated for eventual maintenances during the normal
service also, while the alternator produces energy under the control of the
other regulation system.
Since the feeders of the electronics (1 for regulator) can be fed both in
a.c. and in d.c., it can be chosen, as energy source for them, both the UPS
and the battery of the plant.
AnsaldoEnergia Una Societ Finmeccanica
7/29/2019 9-Generator Performance Curves and Static Exciation
73/141
Doc. n 196 W 429 Rev.1 Oct. 2008 72
POWER SECTION
RECTIFIER BRIDGES
AnsaldoEnergia Una Societ Finmeccanica
7/29/2019 9-Generator Performance Curves and Static Exciation
74/141
Doc. n 196 W 429 Rev.1 Oct. 2008 73
The 3phase power rectifier bridge Graetz type can be madeby diodes or by thyristors.
Diodes rectifier bridge .
Diode is a non-controlledsemiconductor
having 2 poles: anode and cathode.
Its conduction is conditioned by 1 status
only: potential of anode Va higher than the
potential of cathode Vc.
In this condition the current I can flow through the diode.
A Graetz rectifier bridge with 6 diodes (next image) has its
output directly proportional to its feeding voltage only.
+
_
I
Va
Vc
anode
cathode
AnsaldoEnergia Una Societ Finmeccanica
7/29/2019 9-Generator Performance Curves and Static Exciation
75/141
Doc. n 196 W 429 Rev.1 Oct. 2008 74
DIODES BRIDGE
RS
T
+
--
i
i
iexc
VRVS
VT
Vexc
Time
Vexc
VR VT
VR
VS
VT
VS
VR
V
RV
TV
S
VRS VRT VST VSR VTR VTS
1 period of the fundamental
[ 20 ms (50Hz) 16.6 ms (60Hz) ]
The output excitation voltage
Vexc (left side) is, in anyinstant, the highest amongthe actual differencesamong the 3 phase voltagesVR - VS - VT at that instant(phase-to-phase values).The result is a regular
sequence of the 6 typicalondulating peaks duringeach 20 ms (cycle 50Hz).Its average value is directlyproportional to VR VS VTfeeding values only.
V
R
V
S
V
T
V
R
V
S
V
T
V
R
V
S
V
T
R+
R -
S+
S -
T+
T -
Phase voltages
Vexc
7/29/2019 9-Generator Performance Curves and Static Exciation
76/141
AnsaldoEnergia Una Societ Finmeccanica
7/29/2019 9-Generator Performance Curves and Static Exciation
77/141
Doc. n 196 W 429 Rev.1 Oct. 2008 76
THYRISTORS BRIDGE
The output average value of Vexc isnot directly proportional to the supplyvoltages VR VS VT , as per the diodes
bridge, but it is function of thecontrolling signal on the gate of thethyristors.Changing the delay of their firing
instant (changing the firing angle )referred to the natural firing instant, itis possible to change the output bridge.
This kind of bridge has the possibility toproduce a rectified voltage withvariable average value, being constantits feeding voltage.Theoretically, changing the control, theoutput voltage Vexc could be changed
from + VC to VC , where Vc is theceiling voltage (posit.), correspondent
to the output voltage with = 0 (whichis the condition where the thyristorsbridge becomes like a diodes bridge).
RS
T
+
--
i
i
iecc
VR
VS
VT
Vecc
R+ S+ T+
R - S - T -
R+ means thyristor of the
phase R, sidepositive (+)
Vexc
Time
- VCeiling (=180)
0
Permanent times( Vexc > 0 )Voutput
(average value)
Zone used for
transient timesonly ( Vexc < 0 )
+ VCeiling
(=0)
AnsaldoEnergia Una Societ Finmeccanica
7/29/2019 9-Generator Performance Curves and Static Exciation
78/141
Doc. n 196 W 429 Rev.1 Oct. 2008 77
THYRISTORS BRIDGE
RS
T
+iecc
VRVS
VT
Vecc
R+ S+ T+
R - S - T -
--
R+
S+
T+
R -
S -
T -
60 60 60 60 60 60
R+S- R+T- S+T- S+R- T+R- T+S-
In the thyristors bridges, the
sequence of the commutations is
identical to that of the diodes
bridges (pls. see the image).
They are :
R+ S- for 60 electric
R+ T- for 60 electric
S+ T- for 60 electric
S+ R- for 60 electric
T+ R- for 60 electric
T+ S- for 60 electric
Each of the 6 thyristors conducts
for 120 electric, in couplealternatively with the two
thyristors of opposite sign of the
other phases.
7/29/2019 9-Generator Performance Curves and Static Exciation
79/141
AnsaldoEnergia Una Societ Finmeccanica
7/29/2019 9-Generator Performance Curves and Static Exciation
80/141
Doc. n 196 W 429 Rev.1 Oct. 2008 79
THYRISTORS BRIDGE
Delay angle 0
=180
60 60 60 60 60
R+ R-T- S+ T+ S-
Delay angle =180
R+ R-T- S+ T+ S-
60 60 60 60 60
Average = 0
Working conditions with 90 ,and consequently with average voltage negative,
can be for transient times only
Averagenegative
Time
Time
Vexc
Vexc
Natural
instant of firing
of the thyristor
R+
They move
Bridge voltage
output for = 90
Bridge voltageoutput for = 140They move
0
Delay
on R+= 90
Delay
on R+= 140
AnsaldoEnergia Una Societ Finmeccanica
7/29/2019 9-Generator Performance Curves and Static Exciation
81/141
Doc. n 196 W 429 Rev.1 Oct. 2008 80
The thyristors bridge has the particular possibility to deliveroutput voltages with negative sign, even if the semiconductors arecontrolled diodes (unidirectional).
This is possible because the bridge feeds a big inductive load
(field of generator) and any voltage variation on it produceschanges in current very slow, compared with the voltage changes(inside an inductance any current variation is braked).
Consequently, with the thyristors impulses delayed at >90, the
voltage transmitted to the field is negative but the thyristorsremain alive and in conduction until the current inside remainsalways positive (current is decreasing because of the V< 0).
If the current would reach zero the thyristors and the bridge wouldbe switched-off : this is why the time to deliver V< 0 on theoutput bridge is limitedby the time of decreasing to zero of thecurrent.
AnsaldoEnergia Una Societ Finmeccanica
7/29/2019 9-Generator Performance Curves and Static Exciation
82/141
Doc. n 196 W 429 Rev.1 Oct. 2008 81
The static exciter are normally provided with twoidentical Graetz thyristors rectifier bridgesworking in alternative.
Each of them can be commanded by its own AVRonly or by both AVRs, operating in alternative.
Any malfunction of the main bridge produce theautomatic change-over to the other, in order toguarantee the continuity of the generator service.
The cooling of the rectifier bridge is normallydone by forced air in open cycle, except for the
exciters at small sizes (natural air) or at big sizes(treated water in closed cycle).
AnsaldoEnergia Una Societ Finmeccanica
7/29/2019 9-Generator Performance Curves and Static Exciation
83/141
Doc. n 196 W 429 Rev.1 Oct. 2008 82
EXAMPLE OF CONVERTER COOLEDBY AIR IN OPEN CYCLE
3phase a.c. line from
excitation transformer
2phase d.c. line for therotor of the alternator
3phase Graetz bridge
with thyristors and fuses
3phase Graetz bridge
with thyristors and fuses
Warm air
Air
filters
Air
filtersFresh air
AnsaldoEnergia Una Societ Finmeccanica
7/29/2019 9-Generator Performance Curves and Static Exciation
84/141
Doc. n 196 W 429 Rev.1 Oct. 2008 83
EXAMPLE OF CONVERTERS COOLEDBY AIR IN OPEN CYCLE
Fresh
air
Warm air
Hot
components
Lateral section of the cubicle
Path of the air that
cools a
compartment by
natural convection.
Filters
Path of the air that
cools a
compartment by
forced cooling.
Fresh
air
Warm
air
Hot
components
Lateral section of the cubicle
Extractor
Filters
AnsaldoEnergia Una Societ Finmeccanica
7/29/2019 9-Generator Performance Curves and Static Exciation
85/141
Doc. n 196 W 429 Rev.1 Oct. 2008 84
EXAMPLE OF CONVERTERS COOLED
BY AIR IN CLOSED CYCLE
Air-to-water exchangerWater
Fresh air
Warm air
Extractor
Bridge
Sealed
room
AnsaldoEnergia Una Societ Finmeccanica
7/29/2019 9-Generator Performance Curves and Static Exciation
86/141
Doc. n 196 W 429 Rev.1 Oct. 2008 85
EXEMPLE OF CONVERTER COOLED BY WATER
Schematic representation of the converter and its cooling system done
with treated water in closed loop
(in the figure, the representation of the water that flows in the bridge,
obviously, is indicative only, for explanatory purpose)
FUS
+
Cooling water coming from an
external hydraulic circuit for the
internal water-to-water exchangers
Ex Ex
P
Tk
P
T
P = circulation pump
Ex = water-to-water exchangerTk= treated water tank
T = cells of water treatment
FUS= fuses of the bridge
3phase Graetz bridgewith 12 thyristors
(100% series redundance)and 3 fuses at input side
Excitation board
AnsaldoEnergia Una Societ Finmeccanica
7/29/2019 9-Generator Performance Curves and Static Exciation
87/141
Doc. n 196 W 429 Rev.1 Oct. 2008 86
DE - EXCITATION
AND
PRE - EXCITATION
AnsaldoEnergia Una Societ Finmeccanica
7/29/2019 9-Generator Performance Curves and Static Exciation
88/141
Doc. n 196 W 429 Rev.1 Oct. 2008 87
The de-excitation of the generator reduces its stator voltage
at about zero (except the effect of the magnetic residual).
This condition is obtained with the discharge of the internal
flux, dissipating the field current through a passiveresistance circuit, composed by the rotor resistance and an
aux discharge resistance connected in series.
This is obtained by the crow bar positive (pls. see image)which can be fired by the logic with two voltage thresholds:
higher used when CB is operated as overvoltage protection
and lower used only when CB is actuated as field breaker.
Its ON state allows the field current flow through RES andthe consequent electromagnetic flux discharge.
Crow bar positive
AnsaldoEnergia Una Societ Finmeccanica
7/29/2019 9-Generator Performance Curves and Static Exciation
89/141
Doc. n 196 W 429 Rev.1 Oct. 2008 88
.
Crow-bar positivefiring voltage 1 threshold
Overvoltage
protection
2 threshold
De-excitation
function0 Volt
Iexc
Rotor
Field
resistanceDischarge
resistor
Crow-bar
positive
Power
converter
De-excitation circuit or
Static field breaker
RES
0 time
Stator voltage
Being RES about double of field
resistance, the complete discharging
time is approx. equivalent to Tdo.
= Lfield / (RES + Rfield) = Tdo / 3
Tdo = Lfield /Rfield
CROW BAR
AnsaldoEnergia Una Societ Finmeccanica
7/29/2019 9-Generator Performance Curves and Static Exciation
90/141
Doc. n 196 W 429 Rev.1 Oct. 2008 89
CROW - BARThe crow-bar is made by 2 thyristors in antiparallel (v. figure), one called positive crow-bar and the
other negative crow-bar.
Both has the function of protection against the overvoltages (+ and -) but the positive one has the
function also to de-excite the field of the alternator.
Its two functions are discriminated by two different thresholds of intervention that are him imposedaccording to the situations and of the moments in which it has to intervene (v. figure).
The thyristors firing is produced by the same overvoltages that directly activate the firing circuits,
which are totally redounded, to guarantee the certainty of the primer.
Crow-bar
positive
Crow-bar
negative
Dischargeresistor
Iexc
Iexc
+
_
CB
RotorIexc
RES
Primer thresholds of
the positive crow-bar 1 threshold
Protection
against the
overvoltages
2 thresholdFunction of
de-excitation0 Volt
Mechanism of de excitation by crow bar
AnsaldoEnergia Una Societ Finmeccanica
7/29/2019 9-Generator Performance Curves and Static Exciation
91/141
Doc. n 196 W 429 Rev.1 Oct. 2008 90
Mechanism of de-excitation by crow-bar
IexcRotor
Dischargeresistor
Crow-bar
positive
Power converter
De-excitation circuit or
Static field breaker
Excitation voltage (for example) before
the de-excitation command
Negative ceiling
voltage
Instant where the de-excitation
order is done and it is ordered
the negative ceiling
Voltage on the
discherge resistor
and on the field
Instant where the output voltage of the bridge
equalizes the voltage on the discherge resistor.
After this point the bridge goes OFF because its
thyristors become inversely polarized
time
Voltage
0
Instant of command
of the impulses
suppression
Phase-to-phase
voltage
It is shown the mechanismby which the de-excitation ofthe generator is done by thecrow-bar.
PRE EXCITATION
AnsaldoEnergia Una Societ Finmeccanica
7/29/2019 9-Generator Performance Curves and Static Exciation
92/141
Doc. n 196 W 429 Rev.1 Oct. 2008 91
PRE-EXCITATION
To the generator field
Pre-excitation circuit
Feeding from the
battery of the plant
+
_
Res+
_
To the generator field
Pre-excitation circuit
Feeding from an a.c.
aux line of the plant
+
_
When the feeding of the power converter is directly absorbed from themain terminals of the generator, at any starting it is always temporarilyactuated a dedicated pre-excitation system in order to give a first voltageramp sufficient to make the group independent from its own excitation.
The feeding source for the pre-excitation circuit can be a 3phase aux lineof the plant or the d.c. services (battery system) of the plant.
A dedicated logic automatically activates and deactivates this circuit andcontemporarily oversees the correct behaviour of this phase.
.
AnsaldoEnergia Una Societ Finmeccanica
During the pre-excitation phase the feeding(f l b tt ) d
7/29/2019 9-Generator Performance Curves and Static Exciation
93/141
Doc. n 196 W 429 Rev.1 Oct. 2008 92
Excitation
transformer
Generator
Main breaker
of the machine
Rotor
Stator
Bloc diode
Battery of
the plant Circuit of
pre-excitation
Resistor of adaptation
and limitation
+
_
Exciter
Generator circuitry during the pre-excitation
0
time
Iexc
Tdo
Typical time
of the pre-
excitation
Max time allowed
to the pre-excitation
30% Iexc at no-load
During the pre excitation phase the feedingsource (for example battery) produces anexcitation current having an exponentialshape, with a steady state value of about 30%of the machine field current at no-load and atime constant equal to about Tdo of thegenerator.
Typical duration of the pre-excitation is someseconds (pls. see the diagram at bottom).
In case of problems, the logic of overseeingasks for the electric trip if the max timeallowed to this phase is expired (this time is
previously adjusted into the system).
AnsaldoEnergia Una Societ Finmeccanica
7/29/2019 9-Generator Performance Curves and Static Exciation
94/141
Doc. n 196 W 429 Rev.1 Oct. 2008 93
PROTECTION CIRCUITS
PASSIVE PROTECTIONS ON THE POWER CIRCUITS
AnsaldoEnergia Una Societ Finmeccanica
7/29/2019 9-Generator Performance Curves and Static Exciation
95/141
Doc. n 196 W 429 Rev.1 Oct. 2008 94
PASSIVE PROTECTIONS ON THE POWER CIRCUITS
Fuses
Excitation
transformer
Voltage limiters
Bridge
+
_
The exciter foresees two types of passive protections on the power circuits: fuses in
series to each thyristor and voltage limiters on the 3phase feeding line of the power
converter.
The fuses, obviously, protect the corresponding thyristors, having their I2t lower than the
I2t of the correspondent semiconductors.
The limiters (i.e. varistors) are three, connected triangle, and they limit the possible
overvoltages on that 3phase feeding line.
PROTECTION AGAINST SHORT CIRCUIT ON THE D.C. LINE
AnsaldoEnergia Una Societ Finmeccanica
7/29/2019 9-Generator Performance Curves and Static Exciation
96/141
Doc. n 196 W 429 Rev.1 Oct. 2008 95
A.C. Protection
+
_
Gen
Fuses
Crow-bar
Excitationtransformer
Rotor
RES
Rectifier bridge
Short
circuit
This electronic protection has the purpose to avoid damages to the powerconverter against occasional possible short-circuits on its output bars (alongthe whole two-phase line that connects the power converter to the rotor of themachine).
Its intervention consists of sending the immediate command to the firingcircuits of the thyristors for their max impulses delay and contemporarily toproduce the electric trip of the generator.
PROTECTION AGAINST CURRENT UNBALANCE A.C. SIDE
AnsaldoEnergia Una Societ Finmeccanica
Thi l t i t ti h th t d t t ibl b l th
7/29/2019 9-Generator Performance Curves and Static Exciation
97/141
Doc. n 196 W 429 Rev.1 Oct. 2008 96
Anomalous current
due to the fault
The current in the central phase S is greater than the
current in T, because S feeds T and the fault in R too.
The currents in the phases S and T should be equal
but, in this case, this in not true and this is detected.
R
S
T
Iexc normal
Iexc normal
Rotor
This electronic protection has the purpose to detect possible unbalances among the
currents values flowing into the three conductors (R-S-T) of the a.c. line that feeds
the power converter.
Such condition can occur in case of an internal fault of the rectifier bridge.
Its intervention consists of actuating the logic of bridges commutation, in order to
try to maintain the generator in service through the use of the backup rectifier
bridge.
If this was not possible it would be required the electric trip of the generator.
PROTECTION AGAINST MAX OVERLOAD CURRENT
AnsaldoEnergia Una Societ Finmeccanica
7/29/2019 9-Generator Performance Curves and Static Exciation
98/141
Doc. n 196 W 429 Rev.1 Oct. 2008 97
Example of 2 points on the
curve overload limitZone (green) of
overload allowed
by this protection
0
Iexc
time
t2
I2
I1
t1
Inom
This electronic protection has the purpose to avoid damages to the power
converter due to possible thermal overloads.
It allows the bridge to deliver also currents higher than the nominal, but only if
they are contained within a threshold-limit following the quadratic law at inversetime shown in figure (higher overcurrents for brief times and lower overcurrents
for longer times).
Its intervention produces the request of electric trip of the generator.
CURVE IMPLEMENTED
IN THE AVR
AnsaldoEnergia Una Societ Finmeccanica
7/29/2019 9-Generator Performance Curves and Static Exciation
99/141
Doc. n 196 W 429 Rev.1 Oct. 2008 98
AUXILIARY ACCESSORIES OF
THE EXCITATION SYSTEM
ROTOR EARTH FAULT RELAYhi d i i i i f h
AnsaldoEnergia Una Societ Finmeccanica
7/29/2019 9-Generator Performance Curves and Static Exciation
100/141
Doc. n 196 W 429 Rev.1 Oct. 2008 99
This device guarantees a continuous monitoring of the
insulation level of the rotor winding, referred to the earth
potential (normally the rotor body).
In normal conditions this insulation level must be very high
(M), while, if it drops (some K), it is significant of somefault into the rotor winding, which is generated by
insulation loss between the winding copper and the rotor
body (i.e. insulation material of the rotor winding damaged
in some point).
This kind of fault, if occurred in one point only of the rotor
winding, does not produce, from the electrical point of
view, any visible immediate effect, but always it stronglysuggests to stop the generator service as soon as possible, in
order to avoid any further fault in other different points.
In fact this situation could produce injurious effects to the
system.
This device can be chosen with one or two monitoring
thresholds on the rotor winding insulation level and thecorresponding operations are the following:
- with one threshold its action is an alarm only
- with two thresholds its actions are alarm (step 1) and trip
(step 2)
GEN
Rotor winding
Rotor earthfault relay
+
-
Eventual fault
ROTOR TEMPERATURE CALCULATOR
AnsaldoEnergia Una Societ Finmeccanica
7/29/2019 9-Generator Performance Curves and Static Exciation
101/141
Doc. n 196 W 429 Rev.1 Oct. 2008 100
GEN
Rotor winding
+
-
Vexc
Iexc
Rotortemperature
calculator
Iexc Vexc
Excitation board
Output signal
for remote
C
This device guarantees a constant monitoring of the rotor winding temperature, during the exercise of the
generator.
Its working principle is based on the continuous measure of the excitation voltage and current in order to
calculate the actual temperature of the winding by the ratio Vexc/Iexc at any time interval of some
milliseconds (cycle time of the digital program).
Of course the function is programmed considering the high thermal inertia of the rotor winding, compared
with the variation times of the excitation voltage and current (i.e. the ceiling voltage impulses are notaffecting the calculations because too fast for a possible influence on the temperature winding).
This function is performed by a dedicated software (subroutine) implemented into the main AVR program.
The digital regulation system gives an output signal significant of the rotor winding temperature for remote
uses (typically for a recorder in control room or for the DCS system).
AnsaldoEnergia Una Societ Finmeccanica
7/29/2019 9-Generator Performance Curves and Static Exciation
102/141
Doc. n 196 W 429 Rev.1 Oct. 2008 101
REGULATION
The generator is provided with a regulation system which is
AnsaldoEnergia Una Societ Finmeccanica
7/29/2019 9-Generator Performance Curves and Static Exciation
103/141
Doc. n 196 W 429 Rev.1 Oct. 2008 102
The generator is provided with a regulation system which is
the main responsible for the correct conduction of the
machine.
This system primarily operates in automatic mode, in order tohave the best dynamic performances and securities, but it is
possible the operation in manual mode too (next image).
The first of the possible regulations is on the stator voltage,which normally has to be maintained constant or regulated
following particular logic useful for the plant exercise.
Other types of regulation can be done (i.e. cos of machine).The regulation system is digital and normally fully redundant,
in order to be classified as fault tolerant.
Automatic and Manual regulation modes
AnsaldoEnergia Una Societ Finmeccanica
7/29/2019 9-Generator Performance Curves and Static Exciation
104/141
Doc. n 196 W 429 Rev.1 Oct. 2008 103
Automatic regulation
mode
GENRegulation
& Excitationsystems
Stator
voltageElectric
feed-back
Set-point
selection
Automatic
correctionManual regulationmode
GEN
Stator voltageindicator
Human visualfeed-back
Continuous human
correction
Regulation
& Excitationsystems
CLASSIC REGULATION LOOPOF THE STATOR VOLTAGE
AnsaldoEnergia Una Societ Finmeccanica
7/29/2019 9-Generator Performance Curves and Static Exciation
105/141
Doc. n 196 W 429 Rev.1 Oct. 2008 104
OF THE STATOR VOLTAGE
GErr.
Feedback
Reference
VT feedback
Bridge
+
-
Exciter
Next image shows the equivalent internal circuit of generator. Itincludes an ideal generator E and its synchronous reactance Xd1,
AnsaldoEnergia Una Societ Finmeccanica
7/29/2019 9-Generator Performance Curves and Static Exciation
106/141
Doc. n 196 W 429 Rev.1 Oct. 2008 105
g y d1,
and it is connected to the grid by Xe1 (external reactance).
The diagram shows the voltages E1-V1-VGRID in two situations
- at no-load, just synchronized ---> E10 = V10 = VGRID- loaded, delivering positive MVAR to the grid (inductive load)
In last case, supposing VGRID=constant, increasing field current Iexc ,
E1 increases too (E10 --> E1A) and consequently V1 too (V10 -->
V1A), delivering to the grid an inductive (+) reactive current I1 ,and a consequent power rate QA , proportional to the difference
V between the voltages (E1A-VGRID).
Being Xd1>>Xe1 , large part of that V is on Xd1 and, consequently,
V1 will be always very close to the VGRID (transferred to thegenerator side) : this is the reason way, when the generator is
synchronized, the stator voltage is blocked on the grid value.
.- Generator synchronized -Blocks representation
- Generator synchronized -Equivalent electrical
representation
AnsaldoEnergia Una Societ Finmeccanica
7/29/2019 9-Generator Performance Curves and Static Exciation
107/141
Doc. n 196 W 429 Rev.1 Oct. 2008 106
VGRID
xe1
G
Generator
Stepuptransformer
iexc1E
Generator
xd1
xe1
iexc1
E1 V1I1
V GRID
G
Stepuptransformer
representation
Internal gen.voltage E1Terminals gen.
voltage V1 V GRID
AT NO LOAD : E10=V10=VGRID
Command to increase iexc1in order to change
from E10 (at no load)
to E1A
(Q (+) delivered)
V1A
V10V
GRIDE10
E1 A
QA
E1A
- VGRID
QA
E1A
- VGRID
xe1xd1
G
.
AnsaldoEnergia Una Societ Finmeccanica
In case of increasing of the external reactance Xe of the transformer, from
Xe1 to Xe2 (pls. see diagram below), with same voltages E1 and VGRID, thereactive current exchanged Ireact and also Q decrease because they are
always proportional to the PENDENCY of the segment (E1-VGRID) - and not
- Generator synchronized -Equivalent electrical
representation
7/29/2019 9-Generator Performance Curves and Static Exciation
108/141
Doc. n 196 W 429 Rev.1 Oct. 2008 107
always proportional to thePENDENCYof the segment (E1 VGRID) and not
only to the level difference among these two voltages - according to the
relationship:
Ireact Q (E1-VGRID) / (Xd1+Xe)
which, being calculated as ratio among the 2 cathetus of the triangle
E1-E10-VGRID, it represents just the pendency of its hypotenuse, that is thependency of the aforesaid segment (E1-VGRID).
The pendency of (E1-VGRID 1) is greater of (E1-VGRID 2) therefore, with the
external reactance Xe2 > Xe1 Ireact/Q are smaller (smaller pendency).
E
Generator
xd1xe
iexc1
E1 V1I1
V GRID
G
Stepuptransformer
p
Internal volt.generatorE1
21
E10
E1
Ireact Q (E1 V
GRID) / (Xd1 + Xe)
Ireact Q (E1 VGRID) / (Xd1 + Xe)
xe1xd1
Inside the Generator
xe2unchanged but is Xe that changes
Xe2 > Xe1
Xd1 obviously remains
V GRID
The automatic regulation operates as explained in the followingimage.
AnsaldoEnergia Una Societ Finmeccanica
7/29/2019 9-Generator Performance Curves and Static Exciation
109/141
Doc. n 196 W 429 Rev.1 Oct. 2008 108
If, for example, the grid voltage drops (VGRID A --> VGRID B), the
generator terminals voltage V1 drops too (V1A --> V1B) being
still unchanged the field current Iexc and the internal voltage E1A(pls. see the upper diagram of the image).
In that moment the delivered reactive power increases because
increases V between E1A and VGRID B .
The AVR sees V1 drop and corrects it increasing the field currentIexc [and consequently E1 (E1A --> E1C)] up to the condition in
which V1 come back from V1B to V1A (pls. see the second
diagram of the image).
Due to this, the reactive power increases more up to QC .
Same sequence, but inverted, if VGRID A jumps higher.
.
AnsaldoEnergia Una Societ Finmeccanica
GRID VARIATION AND REGULATOR REACTION
GRID VARIATION AND REGULATOR REACTION
D lt th
7/29/2019 9-Generator Performance Curves and Static Exciation
110/141
Doc. n 196 W 429 Rev.1 Oct. 2008 109
Correction due to the
automatic regulation
to bring back V1
from V1B to V1A( which is the original
value )
Internal gen.voltage E1
Terminals gen.voltage V1 V GRID
V1AE1 A
xe1
xd1
Inside the Generator V1B
VGRID B
QC E1C - VGRID B
IC ,QC > IB ,QB > IA,QA
QC E1C - VGRID B
IC ,QC > IB ,QB > IA,QA
E1 C
iexc
Representative straight lines of the voltage drop on the
reactances Xd1 (yellow part) and Xe1 (white part)
QA E1A - VGRID A
QB E1A - VGRID B
IB ,QB > IA,QA
QA
E1A
- VGRID A
QB E1A - VGRID B
IB ,QB > IA,QAV GRID A
Internal gen.voltage E1
Terminals gen.voltage V1 V GRID
V1AE1 A
xe1xd1
Inside the
Generator V1B V GRID B
Drop voltage on the
grid with consequent
drop voltage on V1( from V1A to V1B )
1
2
Behaviour on a near short circuit
AnsaldoEnergia Una Societ Finmeccanica
During a strong and near short circuit on the grid, the voltage at generator terminals strongly lowers while,
on the contrary, the statoric current increases correspondingly.
7/29/2019 9-Generator Performance Curves and Static Exciation
111/141
Doc. n 196 W 429 Rev.1 Oct. 2008 110
Forcing of the automatic
regulator in the attempt to
sustain the voltage at the
terminals of the generator
Internal voltage ofgeneratorE1
V GRID
V1AE1 A
xe1
xd1
Inside the Gen.
V1B
VGRID B
QC E1C - VGRID B
IC
,QC
> IB
,QB
> IA,Q
A
QC
E1C
- VGRID B
IC
,QC
> IB
,QB
> IA,Q
AE1 C
iexc
Voltage drop on
the grid due to the
short cicuit
Voltage at gener.terminals V1
on the contrary, the statoric current increases correspondingly.
The electromagnetic flux in machine [ total = rotor - stator] strongly decreases a lot immediately,
therefore the magnetic connection between rotor and stator becomes very weak and so the mechanical couple
of the turbine, still strong because slower to be reduced, can cause the tear of the weak magneticconnection and it can produce the so-called out of step.
This is avoided, at times, if the short circuit duration is so brief that the excitation current, quickly increased
due to the ceiling, has had time to create a flux in machine such to be still able to withhold rotor and stator
connected among them.
V GRID ACorrection on the
terminals voltage due
to the ceiling
Electric grid systemEach generator synchronised to the grid contributes to supply the grid load by its
own stator current (I1,, In) ----> Itot = i IiIncreasing the generators number, both the total current Itot and the global grid
AnsaldoEnergia Una Societ Finmeccanica
7/29/2019 9-Generator Performance Curves and Static Exciation
112/141
Doc. n 196 W 429 Rev.1 Oct. 2008 111
E
G 1
xd1 xe1ie1
E1 V1
E
G 2xd2 xe2ie2
E2 V2
E
G n
xdn xenien
En Vn
I1
I2
In
Grid loads
Z tot = very low
n generatorssynchronised on
the grid
I tot
V GRID
E
G AxdAxeA ieA
EAVAIA
g g , tot g g
power increase consequently P = 3 * VGRID * I tot .The total grid impedence Ztot can be difined as ratio between the grid voltage
VGRID divided by the total grid current Itot in order to satisfy the relation
VGRID = Z tot * I tot .
When an other new generator is connected to the grid, its contribution IA to feed
the grid loads is added to the preexistent Itot
and the grid voltage will be modified
by that contribution with the same rate by which IA modifies Itot --> IA / Itot gives
V on the grid.VGRID = Z tot * (Itot + IA) if IA
7/29/2019 9-Generator Performance Curves and Static Exciation
113/141
Doc. n 196 W 429 Rev.1 Oct. 2008 112
E
G 1
xd1 xe1ie1
E1 V1
E
G 2xd2 xe2ie2
E2 V2
E
G n
xdn xenien
En Vn
I1
I2
In
Grid loads
Z tot = very low
n generatorssynchronised on
the grid
I tot
V GRID
E
G AxdAxeA ieA
EAVAIA
G 1G 2G 3G nG A
Grid
loadsabsorption
The tank level is mainly due and maintained by
the big set of sources G1Gn balanced by the
grid loads absorption.
The new source GA is influent on the tank level as
far as its contribution is relevant compared with
the global contribution of all other sources.
The electro-hydraulic comparison is significant inorder to emphatise the influence of a single generatorcontribution on the grid voltage alteration, when it isconnected to a powerful national grid.
The regulation system provided into the exciter is normallycomposed by two identical digital automatic voltage
AnsaldoEnergia Una Societ Finmeccanica
7/29/2019 9-Generator Performance Curves and Static Exciation
114/141
Doc. n 196 W 429 Rev.1 Oct. 2008 113
composed by two identical digital automatic voltage
regulator (AVR) operating in alternative (master & slave).
At starting, each AVR can be selected as master.Being the stand-by regulator automatic type too (not manual)
all functions of the main one are again available for the
best dynamic control of the generator behaviour.
The generator voltage feedback is doubled (one each AVR)
and the feeders too in order to have 100% redundancy.
A logic system (pls. see the following image) oversees the
good operation of the AVRs and, in case of problems ofAVR master, decides to switch-over to the second AVR.
Regulation and Control
AnsaldoEnergia Una Societ Finmeccanica
7/29/2019 9-Generator Performance Curves and Static Exciation
115/141
Doc. n 196 W 429 Rev.1 Oct. 2008 114
A V R
Automatic regulator
AVR 1
Stator voltage and currentfeed-back (for channel 1)
V stator
I stator
A V R
Automatic regulator
AVR 2
Feeding
V stator
I stator
Control/Protection Logic
I/O to
remote
Converter 1
Converter 2
Plant
Stator voltage and current
feed-back (for channel 2)
Feedbacks of the regulators
AnsaldoEnergia Una Societ Finmeccanica
7/29/2019 9-Generator Performance Curves and Static Exciation
116/141
Doc. n 196 W 429 Rev.1 Oct. 2008 115
VT1
VT2
CT-U
CT-W
For the
regulator1
For theregulator2
For regulators
1 e 2
Generator
Vc
tensione
statorica
concatenata
Set of 3 VTssingle phase for
the voltage
feedback of the
machine
Set of 3 VTs
single phase for
the voltagefeedback of the
machine
CTs for the
current feedback
of the machine
Main breaker of
the machineEvery regulator works correctly if only
it is constantly informed on the
actual values of voltage and currentproduced on the stator.
For this purpose there are VTs and CTsconnected as in the figure.
Every set of 3 VTs feeds its own
regulator making in this way twoloops of stator voltage regulation
completely independent.
The CTs feed in series both the
regulators and they are used to
perform auxiliary functions(compound, limits, etc.).
The following image shows a list of the main functions
normally foreseen into each AVR (with optional too)
AnsaldoEnergia Una Societ Finmeccanica
7/29/2019 9-Generator Performance Curves and Static Exciation
117/141
Doc. n 196 W 429 Rev.1 Oct. 2008 116
normally foreseen into each AVR (with optional too).
Some note on them.
- Each of the two AVRs has the possibility to operate, locally,in manual mode too (commissioning phase) through the
display and the keyboard mounted on the cubicle front.
- The function called Power System Stabilizer (PSS) is usedto strongly reduce the oscillations (amplitude and time) on
the stator machine variables, due to sudden load changes.
- The best tuning of the PSS parameters have to be found by a
complex plant/grid study, normally not given by theexciter supplier, but produced by the plant designer only.
Typical functions of the automatic voltage regulation
AnsaldoEnergia Una Societ Finmeccanica
7/29/2019 9-Generator Performance Curves and Static Exciation
118/141
Doc. n 196 W 429 Rev.1 Oct. 2008 117
Automatic stator voltage regulation
Manual field voltage regulation
Reactive current compensation (pos. and neg.)
Stabilizing signals function (PSS)
Automatic reduction to zero of reactive power
Automatic cos regulation
Automatic reactive power regulation
Voltage calibrator Max field current limit
Underexcitation limit
Voltage/frequency limit
Automatic alignment with the other AVR
Field winding temperature
Max stator current limit
Operating functions
of the AVR regulator
The green functions are optional and
applicable in certain cases only.
SFC interface and logic
AUTOMATIC VOLTAGE REGULATOR
AnsaldoEnergia Una Societ Finmeccanica
F db k f t t
7/29/2019 9-Generator Performance Curves and Static Exciation
119/141
Doc. n 196 W 429 Rev.1 Oct. 2008 118
+ -Ref.
Feedback of stator
voltage
Error
+
-
Ref.
Feedback
of stator
voltage
K11 + s T1
s
+
-
K31 + s T3
s
Feedback of
field voltage
Thyristors
firing angleA B
Regulator Firingcircuits
Regulation systemOperator
interfaceG
Feedback of stator
voltage
Bridge
Transfer functions
AUTOMATIC VOLTAGE REGULATOR
AnsaldoEnergia Una Societ Finmeccanica
The automatic regulation has the main purpose to maintain constant the voltage at
the alternator terminals even if the load varies casually.
7/29/2019 9-Generator Performance Curves and Static Exciation
120/141
Doc. n 196 W 429 Rev.1 Oct. 2008 119
Vstator
time
V0 V0
transitory
0
Reference
Error negative
( reduce Iexc)
Errors positive
(increase Iexc)
Feedback
time
Error Error = Reference - Feedback
Error = 0
0
The figure at left shows, for instance, the behaviour of the stator voltage of a
machine that sees a load disconnection and reacts with its regulation.
The voltage increases but the regulator reacts and brings it back to the previousvalue V0 after some oscillation (for simplicity in this example the contribution of
the function compound is not considered pls. see next image).
When the feedback changes the error on the reference corrects the Iexc.
COMPOUND AND COMPENSATION
AnsaldoEnergia Una Societ Finmeccanica
This function automatically corrects the set-point of the regulation loop of the stator
voltage in proportion to the actual current reactive delivered by the generator Such
7/29/2019 9-Generator Performance Curves and Static Exciation
121/141
Doc. n 196 W 429 Rev.1 Oct. 2008 120
voltage, in proportion to the actual current reactive delivered by the generator. Such
correction can be in increases (straight line in rise- compensation) or in decreases
(straight line in descent-compound) but it is always done in automatic and transparent
way for the operator.
It is an additional signal injected in the comparison point that corrects the reference of the
regulator.
The compensation allows to maintain constant the voltage after the step-up transformer.
The compound contributes to the automatic reactive load division among more groups
of the same plant in parallel on the same bar (v. figures in the following slide).
+-
Ref.
Feedback ofstator voltage
+
Compound Other
signals
1 p.u. di Ireact =
I nom statoric
Ireactiva
Vstator
1 p.u. Band
0 22%
Band
0 22%
Compensation
Compound
0
Error
DIVISION OF LOAD
AnsaldoEnergia Una Societ Finmeccanica
High voltage V0
The load connection produces arapid lowering of the high voltage
V0 that goes from here (V01) to
here (V02)IB1IA1
V1 V2
V
Generator 1 Generator 2
7/29/2019 9-Generator Performance Curves and Static Exciation
122/141
Doc. n 196 W 429 Rev.1 Oct. 2008 121
In this case both the reactive currents IA1 and IB1 increase up
to IA2 and IB2, but in different rate if the inclinations of the
segments orange and blue (the compound) are different.
In this case the load is not divided equally.Ireact
Ireact
The load connection produces a rapid loweringof the high voltage V0 that goes from here
(V01) to here (V02)
IB1
IB2
IA1
IA2
V1 V2
V01
V02
Ireact1Ireact2
G1 G2
T1 T2
V1 (M.V.) V2 (M.V.)
IreactIreact
In the orange diagrams the Ireact increases to the
right from left, while in those blues the Ireact
increases to the left from right
Ireact
Ireact
B1
IB2
A1
IA2
The reactive currents IA1 and IB1 increase equally up to IA2 and IB2 if the
inclinations of the segments orange and blue (the compound) are the same.
In this way the load is equally divided.
V01
V02
Ireact1 Ireact2
STABILIZING SIGNALS ( PSS )
AnsaldoEnergia Una Societ Finmeccanica
Purpose of this function is to reduce the electromechanical oscillations of the machine
due to consistent load variations and this favors the stability of the group and of the grid
7/29/2019 9-Generator Performance Curves and Static Exciation
123/141
Doc. n 196 W 429 Rev.1 Oct. 2008 122
Apex of theoscillation
Pendulum
to it connected.
Its intervention is transitory (just for the strong load variations only) and the principle of
its operation is to add brief corrective impulses to the field current in the mostopportune instants of the oscillations: in such way the damping action will be favorite.
An intuitive comparison that can clarify the mechanism concept of
this function operation is illustrated in figure. In the moments near
to those in which the pendulum reaches the apex of its oscillation
it is possible to influence its future run giving new touches of
push, also of modest entity, but in well precise instants. If such
touches of push are applied, every time, immediately after the
pendulum has already reached and overcome the apex of every
run, the ampleness of its oscillations will increase more always.
Contrarily, if that touches of push are applied, every time,
immediately before the pendulum has reached the apex of everyrun, the ampleness of its oscillations will find contrast and it will
decreaseprogressively.
This is the same principle of action of the stabilizing signals.
STABILIZING SIGNALS ( PSS )
AnsaldoEnergia Una Societ Finmeccanica
The two following figures show what is the effectiveness of the
bili i i l h d h i ill i
7/29/2019 9-Generator Performance Curves and Static Exciation
124/141
Doc. n 196 W 429 Rev.1 Oct. 2008 123
-1 0 1 2 3 4 5 6 7 80
0.5
1
1.5
P
-1 0 1 2 3 4 5 6 7 80
0.5
1
1.5
P
Without PSS With PSS
stabilizing signals on the process to reduce the statoric oscillations
produced by a strong transitory of power on the grid (for instance
short circuit).
The setting of the PSS parameters for a generator connected to a particular electric grid can
normally be optimized with specific SW simulations, given by the Manager of the Grid.
REGULATION OF THE REACTIVE POWER
AnsaldoEnergia Una Societ Finmeccanica
The regulation of the reactive power Q is done with the help of the regulation loop of the statoric voltage,
through which, regulating the field current (and therefore the internal voltage Ei), it is possible vary the
7/29/2019 9-Generator Performance Curves and Static Exciation
125/141
Doc. n 196 W 429 Rev.1 Oct. 2008 124
Internal voltage E1
Grid voltage VGRID
(E1 VGRID ) Q
Time
Voltages
0
Correcting E1 in order to recopy VGRID, the Q will be maintained constant
through which, regulating the field current (and therefore the internal voltage Ei), it is possible vary the
reactive power that the generator exchanges with the load (as already seen previously).
With this type of regulation, Q is maintained constant maintaining constant the difference between the
internal voltage Ei and the grid voltage VGRID.Practically there is a regulation loop in which the wished reference Q* is continuously compared with the
real reactive power currently delivered: the possible error corrects the reference of the voltage loop to vary
Ei in such way that the generator will produce a Q (= Ei-VGRID) equal to the wished reference Q*.
REGULATION OF THE POWER FACTOR
AnsaldoEnergia Una Societ Finmeccanica
The regulation of the power factor (cos ) is done with the help of the regulation loop
7/29/2019 9-Generator Performance Curves and Static Exciation
126/141
Doc. n 196 W 429 Rev.1 Oct. 2008 125
MW
MVAROver-excitation
Under-excitation
MW2
MVAR2
MVAR1
MW1
P1
P2
P1
0
g p ( ) p g pof statoric voltage, through which it is possible vary the reactive power exchanged by
the generator with the load (as already seen previously) and consequently its cos .
The working principle of this type of regulation is
the following.
Continuously it is measured the active power
value that the machine is delivering now and,
based on it, it is calculated the consequent
reactive power that maintains constant thewanted relationship among these two powers
(active and reactive) and therefore the cos .
The automatic regulator will act to maintain this
calculated reactive power until there will be a
successive variation of the active power.
The figure shows that, if the MW changes (from
MW1 to MW2), the exciter will vary the MVAR
(from MVAR1 to MVAR2) and P1 P2.
LIMITS IN OVER AND UNDEREXCITATION ZONES
AnsaldoEnergia Una Societ Finmeccanica
MW Action curve of the
overexcitation limit
7/29/2019 9-Generator Performance Curves and Static Exciation
127/141
Doc. n 196 W 429 Rev.1 Oct. 2008 126
LIMIT IN OVEREXCITATION
This function protects the generator against
prolonged trespasses out of the capabilityzone hazardous for the integrity of the field
windings.
LIMIT IN UNDEREXCITATION
This function protects the generator against
prolonged trespasses out of the capability
zone hazardous for the stability of the group
and for the integrity of terminal parts of the
stator.
MVAR
0
Overexc.Underexc.
+
overexcitation limit
MVAR
Nominal workingpoint Pn
MW
0
Overexc.Undrexc.
_
Action curve of the
underexcitation limit
LIMIT OF FLUX
AnsaldoEnergia Una Societ Finmeccanica
Th fl i id h hi i i b h i V/f
7/29/2019 9-Generator Performance Curves and Static Exciation
128/141
Doc. n 196 W 429 Rev.1 Oct. 2008 127
f (%)
V (%)
100%95%
95%
105%
105%
98%
103%
102%
Flux V/f == 105% nom
Flux V/f == 95% nom
The flux inside the machine is given by the ratio V/f .
The colored area represents the surface of the normal
working points allowed indefinitely by the project,while the outlined areas adjacent to it, are always
representative of working points allowed for the
machine, but with more stressful conditions of those
in the colored zone.
For this reason the permanent exercise of the group
outside the colored area is unadvisable, in order to
limit, as far as possible, the "loss of life" of the
generator.
The flux limit of the exciter acts along the highest
oblique segment and it adapts the stator voltage on the
foreseen relationship V/f, when the frequencydecreases.
.
AnsaldoEnergia Una Societ Finmeccanica
V (%)
In this diagram V/f the limitations are
due to:
7/29/2019 9-Generator Performance Curves and Static Exciation
129/141
Doc. n 196 W 429 Rev.1 Oct. 2008 128
A
D
B
C
f (%)
100%95%
95%
105%
105%
98% 103%102%
Flux V/f == 105% nom
Flux V/f == 95% nom
in A
max flux (V/f) , max voltage (gen.)
and min frequency (turbine)
in B
max voltage and max frequency
in C
max frequency, min voltage (max
current) and min flux (instability)
in D
min frequency and min voltage
(max current)
The reactive power and power factor regulations can be only
AnsaldoEnergia Una Societ Finmeccanica
NOTES
7/29/2019 9-Generator Performance Curves and Static Exciation
130/141
Doc. n 196 W 429 Rev.1 Oct. 2008 129
- The reactive power and power factor regulations can be only
actuated when the generator is synchronized to the grid.
Its disconnection automatically produces a change-over to
the stator voltage regulation (in island configuration too).
- Any change-over to the other regulator is bumpless in
order to avoid any dynamic and thermal machine variation.
Typical exercise sequence of a generator
AnsaldoEnergia Una Societ Finmeccanica
7/29/2019 9-Generator Performance Curves and Static Exciation
131/141
Doc. n 196 W 429 Rev.1 Oct. 2008 130
Predisposition completed
Turbine at nominal speed
Exciter fed and in automatic
voltage regulation
Exc
ON
Exc
OFF
Soft-start
Voltageequalization
First loading
(few MW)
INCR / DECR
EHC and EXCLOADING
Reduction of
Reactive
Power to 0
Reduction of
Active
Power to 0
Disconnection
from the grid
LOADINGVOLTAGE
Regulation
Synchronization
Reg. COS orReg. REACT.
Generator
de-excited
FRONT VIEW OF A TYPICAL EXCITATION BOARD
AnsaldoEnergia Una Societ Finmeccanica
7/29/2019 9-Generator Performance Curves and Static Exciation
132/141
Doc. n 196 W 429 Rev.1 Oct. 2008 131
AnsaldoEnergia Una Societ Finmeccanica
INTERNAL VIEW OF TYPICAL POWER CUBICLES
7/29/2019 9-Generator Performance Curves and Static Exciation
133/141
Doc. n 196 W 429 Rev.1 Oct. 2008 132
AnsaldoEnergia Una Societ Finmeccanica
TYPICAL MODULE WITH THYRISTORS AND RADIATORS
7/29/2019 9-Generator Performance Curves and Static Exciation
134/141
Doc. n 196 W 429 Rev.1 Oct. 2008 133
AnsaldoEnergia Una Societ Finmeccanica
7/29/2019 9-Generator Performance Curves and Static Exciation
135/141
Doc. n 196 W 429 Rev.1 Oct. 2008 134
EXCITATION
TRANSFORMERS
EXCITATION TRANSFORMERS
AnsaldoEnergia Una Societ Finmeccanica
The feeding transformers of the excitation systems are substantially
7/29/2019 9-Generator Performance Curves and Static Exciation
136/141
Doc.