Air Circuit Breaker

HiAN 630 ~ 1600AF

HiAN 2000 ~ 3200AF

02 | HiAN & HiAS Type

SafetyConvenience

SmallLight Weight

High BreakingCapacity

High AbilityDigital APR

04 - Feature

06 - Rating

08 - Selection of Specification

09 - Type of Mounting

10 - Derating Table

11 - Internal Resistance

12 - Spring Charging Operation

13 - Electrical Tripping Device

HiAN Type

14 - Accessory

19 - ACB Protection Relay

28 - Characteristic Curve

30 - Outline Dimension

44 - Circuit Diagram

46 - APR Wiring Diagram

48 - Ordering Information

53 - ACB Operation Environment

56 - Feature

57 - Rating

58 - Selection of Specification

59 - Type of Mounting

60 - Outline Dimension

64 - Circuit Diagram

66 - Ordering Information

HiAS Type

CONTENTS

Page 3: Air Circuit Breaker - HUỲNH LAI · PDF fileAir Circuit Breaker HiAN 630 ~ 1600AF ... Easy maintenance and inspection mechanism ... Type HiAN 08 HiAN 12 HiAN 16 HiAN 20 HiAN 25 HiAN

[ Basic Standard ]IEC60947-2 International Electrotechnical Commission

EN 60947-2 European Standard

AS 3972-2 Australian Standard

NEMA PUB NO.SG3 National Electrical Manufactures Association

ANSI C37.13 American National Standard Institute

GOST R 50030.2-99 9 Government Standard of Russia

GOST R 50030.1-2000 Government Standard of Russia

[ Authorization ]KR/KOREA Korean Register of Shipping

GL/GERMANY Germanischer Lloyd

LR/U.K Lloyd’s Register of Shipping

ABS/U.S.A American Bureau of Shipping

BV/FRANCE Bureau Veritas

NK/JAPAN Nippon Kaiji Kyokai

Introduction of the compact and up-graded

HiAN Type ACB, providing the perfect solution of

highly reliable, space-saving and the advanced

safe systems.

HiAN Type

HiAN Air Circuit Breaker | 03

Page 4: Air Circuit Breaker - HUỲNH LAI · PDF fileAir Circuit Breaker HiAN 630 ~ 1600AF ... Easy maintenance and inspection mechanism ... Type HiAN 08 HiAN 12 HiAN 16 HiAN 20 HiAN 25 HiAN

Feature

HiAN type ACB expanded interruption range (up to 120 kA)

with increased short-time withstand current (up to 100 kA)

and short-circuit current (up to 85 kA).

Long Service LifeThe mechanical endurance of all types are 10,000 cycles.

Zero Arc SpaceNo extra arc space will drastically reduce the height of the

switchboard.

Expanded Selective Interruption Range

HiAN 2000 ~ 3200AF

410 388

Space Saving DesignHiAN type ACBs have two frame sizes. The height and depth dimensions are identical in all sizes up to 3200AF Draw-out type (up to 1600AF): 490 mm (H)×320 mm (W)×388 mm (D) Draw-out type (From 2000AF up to 3200AF): 490 mm (H)×410 mm (W)×388 mm (D)

The panel cutout size for all ACBs is the same, so it is convenient to standardize the switchboard design.

The fully molded body of the ACBs increases the safety for all application.

HiAN 25~32 85 kA

HiAN 06~20 70 kA

HiAN 50~63 120 kA

HiAN 40 100 kA

04 | HiAN & HiAS Type

Air Circuit BreakerHiAN Type

HiAN 630 ~ 1600AF

490

320

Page 5: Air Circuit Breaker - HUỲNH LAI · PDF fileAir Circuit Breaker HiAN 630 ~ 1600AF ... Easy maintenance and inspection mechanism ... Type HiAN 08 HiAN 12 HiAN 16 HiAN 20 HiAN 25 HiAN

Early make, late break neutral pole contact.The neutral pole contact closes earlier than the main circuit contacts, and opens later.

This effectively prevents the occurrence of the abnormal voltages between the phase lines and the neutral line,

thus ensures safety.

Safety and Convenience Easy access to control circuit Easy maintenance and inspection mechanism All out-going parts are molded Auxiliary contacts (4a+4b standard)

Various AccessoryAll accessory is easy to install and maintain Key interlock system Cycle counter Safety shutter Fixing blocks Door flange Position switchMal-insertion prevention device Arc shield.Mechanical interlock device Automatic transfer switch

Front View Designed for the HiAN ACB

➊ Front cover

➋ Charging handle

➌ Position lock device

➍ Close button

➎ Trip button

➏ Charged / Dischargedindicator

➐ Close and open indicator

➑ Cycle counter option

➒ Control circuit

➓ Fault reset button

Digital protection relay

Name plate

Key lock device option

Fixing blocks option

HiAN Air Circuit Breaker | 05

HiAN Type

Page 6: Air Circuit Breaker - HUỲNH LAI · PDF fileAir Circuit Breaker HiAN 630 ~ 1600AF ... Easy maintenance and inspection mechanism ... Type HiAN 08 HiAN 12 HiAN 16 HiAN 20 HiAN 25 HiAN

Ratings for Industrial Plant Applications

Type HiAN 06 HiAN 08 HiAN 10 HiAN 12 HiAN 16 HiAN 20 HiAN 25 HiAN 32 HiAN 40 HiAN 50 HiAN 63

HiAN 32HiAN 25HiAN 20HiAN 16HiAN 12HiAN 10HiAN 08630 800 1000 1250 1600 2000 2500 3200 4000 5000 6300

630 800 1000 1250 1600 2000 2500 3200 4000 2500 3200

3, 4 Poles

320 320 320 320 320 2000 2000 2000 4000 4000 4000

630 630 630 630 630 2500 2500 5000 5000

800 800 800 800 3200 6300

1000 1000 1000

1250 1250

1600

AC 1000 V

AC 690 V

50 50 50 50 50 65 65 65 85 100 100

70 70 70 70 70 70 85 85 100 120 120

70 70 70 70 70 85 85 85 100 120 120

50 50 50 50 50 65 65 65 85 100 100

70 70 70 70 70 70 85 85 100 120 120

105 105 105 105 105 143 143 143 187 220 220

154 154 154 154 154 154 187 187 220 291 291

154 154 154 154 154 187 187 187 220 291 291

105 105 105 105 105 143 143 143 187 220 220

154 154 154 154 154 154 187 187 220 291 291

8

65 65 65 65 65 70 85 85 75 100 100

65 65 65 65 65 70 85 85 75 100 100

B

0.03 0.04

10

0.04 0.06

43 43 43 49 49 60 63 65 - - -

65 65 65 72 72 87 92 96 115 210 230

51 51 51 58 58 69 76 83 - - -

76 76 76 85 85 100 110 120 135 230 250

490 478

320 410 480 984

461.2 481

※ - Value is open air at 40- ⊙ : CESI Type Test- : GOST R Certifications- For 2 poles use both opposite ends poles of 3 poles ACBs.

IEC

VDE

BS

AS

IEC

VDE

BS

AS

ClosingOperatingTime

Weight(kg)

1 sec

with Inst.

Icu=100 % lcs

with Inst.

Icu=100 % lcs

without Inst.

(MCR)

without Inst.

(MCR)

Rated Current (A)

Neutral Phase Current (A)

Poles

Rated Primary Current of OCR [ICT] (A)

Rated Insulation Voltage (Ui) (V)

Rated Operation Voltage (Ue) (V)

Rated Breaking Capacity (kA sym) [lcu]

AC 690 V

AC 500 V

AC 415 V below

AC 600 V

AC 500 V below

Rated Making Capacity (kA peak) [lcm]

AC 690 V

AC 500 V

AC 415 V below

AC 600 V

AC 500 V below

Rated Impulse Withstand Voltage. (Uimp) [kV]

Rated Short-time Withstand

Current [lcw] (rms)

Rated Latching Current (kA)

Utilisation Category

Total Breaking Time (sec)

Charging Time (sec) max.

Closing Time (sec) max.

3 Poles, Fixed Type

3 Poles, Draw-out Type

4 Poles, Fixed Type

4 Poles, Draw-out Type

Dimension (mm) H

(3 Poles, Draw-out Type) W

D

Rating

⊙ ⊙ ⊙ ⊙ ⊙ ⊙

06 | HiAN & HiAS Type

Air Circuit BreakerHiAN Type

Page 7: Air Circuit Breaker - HUỲNH LAI · PDF fileAir Circuit Breaker HiAN 630 ~ 1600AF ... Easy maintenance and inspection mechanism ... Type HiAN 08 HiAN 12 HiAN 16 HiAN 20 HiAN 25 HiAN

Ratings for Generator Applications

Type HiAN 08 HiAN 12 HiAN 16 HiAN 20 HiAN 25 HiAN 32 HiAN 40 HiAN 50 HiAN 63

HiAN 32HiAN 25HiAN 20HiAN 16HiAN 12HiAN 10HiAN 08800 1250 1600 2000 2500 3200 4000 5000 6300

160≤Io≤320 160≤Io≤320 160≤Io≤320 1000≤Io≤2000 1000≤Io≤2000 1000≤Io≤2000 2000≤Io≤4000 2000≤Io≤4000 2000≤Io≤4000

320≤Io≤630 320≤Io≤630 320≤Io≤630 1250≤Io≤2500 1250≤Io≤2500 2500≤Io≤5000 2500≤Io≤5000

400≤Io≤800 400≤Io≤800 400≤Io≤800 1600≤Io≤3200 3200≤Io≤6300

500≤Io≤1000 500≤Io≤1000

630≤Io≤1250 630≤Io≤1250

800≤Io≤1600

AC 1000 V

AC 690 V

70/154 70/154 70/154 70/154 85/187 85/187 100/220 120/291 120/291

70/154 70/154 70/154 70/154 85/187 85/187 100/220 120/291 120/291

70/154 70/154 70/154 70/154 85/187 85/187 100/220 120/291 120/291

70/154 - 70/154 70/154 85/187 85/187 100/220 120/291 120/291

70/154 70/154 70/154 70/154 85/187 85/187 100/220 120/291 120/291

70/154 70/154 70/154 70/154 85/187 85/187 100/220 120/291 120/291

65 65 65 70 85 85 75 100 100

65 65 65 70 85 85 75 100 100

B

0.03 0.04

10

0.04 0.06

65 72 72 87 92 96 115 210 230

KR

LR

ABS

GL

BV

NK

ClosingOperatingTime

1 sec

Icu=100 % Ics

Amperes Rating (A)

Rated Current of OCR (A)

[Io] is Generator Rated Current

Rated Insulation Voltage (Ui) (V)

Rated Operation Voltage (Ue) (V)

Rated Breaking Capacity (kA, sym) [Icu] / Rated Making Capacity (kA peak) [Icm]

AC 480 V

AC 500 V

AC 480 V

AC 480 V

AC 480 V

AC 480 V

Other Ratings

Rated Short-time Withstand

Current [lcw] (rms)

Rated Latching Current (kA)

Utilisation Category

Total Breaking Time (sec)

Charging Time (sec) max.

Closing Time (sec) max.

Weight (kg) (3 Poles, Draw-out Type)

HiAN Air Circuit Breaker | 07

HiAN Type

Page 8: Air Circuit Breaker - HUỲNH LAI · PDF fileAir Circuit Breaker HiAN 630 ~ 1600AF ... Easy maintenance and inspection mechanism ... Type HiAN 08 HiAN 12 HiAN 16 HiAN 20 HiAN 25 HiAN

A wide choice of specifications to suit your particular application

“HiAN ACB” classified into eight categories.

We are sure that our custom-built specification of “HiAN ACB” will contribute to your system design.

Selection of Specification

08 | HiAN & HiAS Type

Air Circuit BreakerHiAN Type

Page 9: Air Circuit Breaker - HUỲNH LAI · PDF fileAir Circuit Breaker HiAN 630 ~ 1600AF ... Easy maintenance and inspection mechanism ... Type HiAN 08 HiAN 12 HiAN 16 HiAN 20 HiAN 25 HiAN

Fixed TypeThis type of ACB has no draw-out cradle and is designed to be directly mounted in the switchboard.

Control Circuit TerminalsControl circuit terminals are front located to allow easy wiring/access.

Connection MethodsMain circuit terminals

Two types of main circuit terminal arrangements are available: vertical terminals, horizontal terminals.

Different types of terminal arrangements can be specified for the line and load sides. Unless otherwise specified by

the user, horizontal terminals are given to all types.

Horizontal terminals

ex) HiAN 12, 16

Vertical terminals

ex) HiAN 12, 16

Type of Mounting

Draw-out TypeThis type of ACB consists of a breaker body and a draw-out cradle. The breaker body can be moved within or removed

from the draw-out cradle that is fixed in the switchboard. There are four breaker body positions: CONNECTED, TEST,

ISOLATED, and Removed. The switchboard panel door can be kept closed the CONNECTED, TEST, and ISOLATED positions

(“shut-in three positions”)

TEST positionThe main circuit is isolated and the controlcircuits are connected. This positionpermits operation tests without the needfor opening the switchboard panel door.

ISOLATED positionBoth the main and control circuits aredisconnected. The switchboard panel door does notneed to be opened.

CONNECTED positionBoth the main and control circuits areconnected for normal service.

HiAN Air Circuit Breaker | 09

HiAN Type

Page 10: Air Circuit Breaker - HUỲNH LAI · PDF fileAir Circuit Breaker HiAN 630 ~ 1600AF ... Easy maintenance and inspection mechanism ... Type HiAN 08 HiAN 12 HiAN 16 HiAN 20 HiAN 25 HiAN

Derating Table

TypeRated

Current(A)

Bus-bar Size(mm3)

Derated Current(max.)(A)

30 40 50 60Remark

HiAN 06

HiAN 08

630

800

1000HiAN 10

HiAN 12 1250

HiAN 16 1600

HiAN 20

HiAN 25

2000

2500

HiAN 32

HiAN 40

HiAN 50

HiAN 63

4000

5000

6300

3200

1×40×10

1×60×10

1×60×10

1×60×10

2×40×10

2×40×10

2×60×10

2×60×10

2×100×10

3×100×10

4×100×10

3×140×10

4×140×10

6×140×10

630

800

1000

1250

1250

1600

1600

2000

2500

3200

3200

4000

5000

6300

630

800

1000

1250

1250

1600

1600

2000

2500

3200

3200

4000

5000

6300

630

800

1000

1250

1250

1600

1600

2000

2500

3020

3200

3880

5000

6300

630

800

1000

1250

1250

1560

1600

2000

2350

2760

3160

3560

4800

6048

Fixed Type(Horizontal Mounting Bus-bar)

TypeRated

Current(A)

Bus-bar Size(mm3)

Derated Current(max.)(A)

30 40 50 60Remark

HiAN 06

HiAN 08

630

800

HiAN 10 1000

HiAN 12 1250

HiAN 16 1600

HiAN 20 2000

HiAN 25 2500

HiAN 32

HiAN 40

HiAN 50

HiAN 63

3200

4000

5000

6300

1×40×10

1×60×10

1×50×10

1×60×10

1×60×10

2×40×10

2×40×10

2×50×10

2×60×10

2×60×10

2×80×10

2×100×10

2×80×10

2×100×10

3×100×10

4×100×10

3×140×10

4×140×10

6×140×10

630

800

1000

1000

1250

1250

1600

1600

1600

2000

2000

2000

2500

2500

3190

3200

4000

5000

6300

630

800

1000

1000

1250

1250

1480

1600

1600

1980

2000

2000

2430

2500

3010

3120

4000

5000

6300

630

800

1000

1000

1140

1250

1330

1560

1600

1770

2000

2000

2180

2500

2830

2930

3880

5000

6000

630

800

900

990

990

1150

1150

1350

1540

1540

1890

2000

1890

2220

2590

2740

3560

4800

5800

Draw-out Type(Horizontal Mounting Bus-bar)

10 | HiAN & HiAS Type

Air Circuit BreakerHiAN Type

Page 11: Air Circuit Breaker - HUỲNH LAI · PDF fileAir Circuit Breaker HiAN 630 ~ 1600AF ... Easy maintenance and inspection mechanism ... Type HiAN 08 HiAN 12 HiAN 16 HiAN 20 HiAN 25 HiAN

HiAN 06/08/10 HiAN 12/16 HiAN 40 HiAN 50 HiAN 63

Internal Resistance(μΩ)

Draw-out Type

Fixed Type

Draw-out Type

Fixed Type

Draw-out Type

Fixed Type

PowerConsumption (W)

Reactance (mΩ)

66

38

26/42/66

15/24/38

0.12

0.12

48

20

75/123

31/51

0.1/0.085

0.1/0.085

20

-

320

-

0.045

-

15

-

375

-

0.035

-

10

-

397

-

0.03

-

Draw-out Type(Vertical Mounting Bus-bar)

RatedCurrent

(A)Type

60504030

1×40×10

1×60×10

1×50×10

1×60×10

1×60×10

2×40×10

2×40×10

2×50×10

2×60×10

2×60×10

2×80×10

2×100×10

2×80×10

2×100×10

3×80×10

2×100×10

3×100×10

4×100×10

3×140×10

4×140×10

6×140×10

630

800

1000

1000

1250

1250

1600

1600

1600

2000

2000

2000

2500

2500

3200

3190

3200

3200

4000

5000

6300

630

800

1000

1000

1250

1250

1600

1600

1600

2000

2000

2000

2500

2500

3150

3010

3200

3200

4000

5000

6300

630

800

1000

1000

1250

1250

1600

1600

1600

2000

2000

2000

2500

2500

2950

2830

3070

3200

3880

5000

6000

630

800

950

1000

1100

1250

1440

1580

1600

1920

2000

2000

2360

2500

2750

2650

2860

3120

3560

4800

5800

HiAN 06

HiAN 08

630

800

1000

1250

1600

2000

2500

3200

4000

5000

6300

HiAN 10

HiAN 12

HiAN 16

HiAN 20

HiAN 25

HiAN 32

HiAN 40

HiAN 50

HiAN 63

RemarkDerated Current(max.)(A)Bus-bar Size

(mm3)

Internal Resistance

HiAN 20 HiAN 25 HiAN 32

30

16

120

64

0.080

0.080

24

14

150

87.5

0.065

0.065

22

13

225

133

0.055

0.055

HiAN Air Circuit Breaker | 11

HiAN Type

Page 12: Air Circuit Breaker - HUỲNH LAI · PDF fileAir Circuit Breaker HiAN 630 ~ 1600AF ... Easy maintenance and inspection mechanism ... Type HiAN 08 HiAN 12 HiAN 16 HiAN 20 HiAN 25 HiAN

Spring Charging Operation

Rating of motor charge type

Rated Voltage (V)

OperatingVoltage (V)

Inrush Current (Peak Value)(A)

Steady-StateCurrent (RMS)(A)

Charging Time (s)

ClosingCurrent (Peak)(A)

AC 220

AC 110

DC 200 ~ 220

DC 125

DC 100 ~ 110

DC 24

~ 246

~ 123

~ 246

~ 140

~ 126

~ 27

187

93.5

170

106

85

20

2.5 (220 V)

2.5 (110 V)

2.5 (220 V)

3.0 (125 V)

3.5 (110 V)

3.0 (24 V)

0.5

1.0

0.5

0.7

1.0

1.0

5

5

5

5

5

5

1.5 (220 V)

3.2 (110 V)

1.5 (220 V)

3.6 (125 V)

3.2 (110 V)

8.0 (24 V)

Motor Charging TypeFor this type of ACB, the closing springs are charged by a

motor. ON/OFF operation of the ACB can be performed

remotely.

The control circuits provide optimum control to the spring

charging and ACB ON/OFF operation.

A manual charging mechanism is also fitted to facilitate

inspection or maintenance work.

Charging the closing springs

A motor is used to charge the closing springs. When the

closing springs are released to close the ACB, they are

automatically charged again by the motor for the next ON

operation.

Closing the ACB

Turning on “remote” ON switch enables the ACB to be

remotely closed.

Opening the ACB

For opening the ACB remotely, specify the shunt trip device

or the undervoltage trip.

Manual Charging TypeFor this type of ACB, the closing springs are charged by the

spring charging handle.

ON/OFF operation of the ACB is performed by ON/OFF

buttons on the ACB.

Charging the closing springs

The closing springs can be charged by spring charging handle.

Closing the ACB

Press “CLOSE” button in the front cover to close ACB.

Opening the ACB

Press “OPEN” button in the front cover to open ACB.

Anti-pumping FunctionEven if the ON switch is kept on, ACB closing operation is

performed only once. To close the ACB again, turn off the

ON switch to charge the closing springs, and then turn on the

ON switch.

If ON and OFF signals are simultaneously given of the ACB,

the ON signal is ignored.

Anti-pumping Circuit

12 | HiAN & HiAS Type

Air Circuit BreakerHiAN Type

Page 13: Air Circuit Breaker - HUỲNH LAI · PDF fileAir Circuit Breaker HiAN 630 ~ 1600AF ... Easy maintenance and inspection mechanism ... Type HiAN 08 HiAN 12 HiAN 16 HiAN 20 HiAN 25 HiAN

Electrical Tripping Device

Rated Input Voltage

Stored Voltage

Rated Current

Rated frequency

Delay time

Standard

Order No. HVFS-T7 HVFS-T9

AC 110 V

DC 145 V

AC 220 V

DC 290 V

DC 2 A

50 / 60 Hz

1.5 sec

IEC 60694

Shunt Trip (SHT)The shunt trip is used to electrically open the breaker from

a remote place(s).

The shunt trip may be used to open the breaker by means

of external protective devices, such as over-current relays

or reverse power relays.

Both shunt trip and undervoltage trip may be fitted in a

single breaker.

Capacitor TripThe capacitor trip is used in conjunction with a shunt trip,

to ensure normal operation of the latter with in 30 seconds

after the control power (AC) is out or in a low voltage

condition.

A combination of capacitor trip and shunt trip work as a

normal AC-rated shunt trip, and may be used to open the

breaker by an external protective device.

Undervoltage Trip (UVT)The undervoltage trip (UVT) automatically opens the Air

Circuit Breaker when control power voltage drops below a

predetermined value.

When the voltage is restored to a value higher then the

pick-up voltage, the Air Circuit Breaker can be closed, The

undervoltage trip consists of a tripping coil and a trip

control device.

Two types of UVT are available: An instantaneous trip, which trip the Air Circuit Breaker

immediately, its circuit voltage drops below a

predetermined value. A time-delay trip, which operates with a time-delay of

500ms, thus providing coordination with the short time-

delay characteristic.

The UVT device is also available for DC applications in

conjunction with a current limiting resister (installed

externally to the breaker)

Shunt Trip Rating

Rating

Type ofUVT

Rated Voltage (V) Pick-up Voltage

Operating Voltage (V)

Drop-out VoltageExciting CoilCurrent (A)

IANS-T(Time-delayType)

IANS-U(Instan-taneous

Type)

480~500430~470360~400200~240100~120

480~500430~470360~400200~240100~120

200~220100~125

367.2~448.8329~402

275.4~336.6153~18776.5~93.5

153~18776.5~93.5

175~336164.5~301140~25284~14042~70

77~14043.8~70

0.15 (480 V)0.15 (450 V)0.15 (380 V)0.15 (220 V)0.15(110 V)

0.1 (200 V)0.1 (100 V)

367.2~448.8329~402

275.4~336.6153~18776.5~93.5

175~336164.5~301140~25284~14042~70

0.15 (480 V)0.15 (450 V)0.15 (380 V)0.15 (220 V)0.15 (110 V)

AC

AC

DC

BreakerType

Rated Voltage (V)

OperationalVoltage (V)

PeakExcitationCurent (A)

CurrentPassage

Time (ms)

HiAN 06HiAN 08HiAN 10HiAN 12HiAN 16

HiAN 20HiAN 25HiAN 32

HiAN 40HiAN 50HiAN 60

421~480380~420180~250100~150

100~150150~23090~125

4824

60~16590~27654~15029~5714~28

3.7 (125 V)1.3 (220 V)3.2 (110 V)4.8 (48 V)8.8 (24 V)

2530303029

252~528228~462108~27560~165

1.2 (450 V)1.3 (380 V)1.5 (220 V)3.1 (110 V)

25252525

AC

421~480380~420180~250100~150

252~528228~462108~27560~165

1.3 (450 V)1.4 (380 V)1.6 (220 V)3.2 (110 V)

25232424

421~480380~420180~250100~150

252~528228~462108~27560~165

0.6 (450 V)0.7 (380 V)1.0 (220 V)1.5 (110 V)

27272727

AC

DC

100~150150~23090~125

4824

60~16590~27654~15029~5714~28

3.7 (125 V)1.4 (220 V)3.2 (110 V)4.9 (48 V)8.8 (24 V)

2528302928

DC

100~150150~23090~125

4824

60~16590~27654~15029~5714~28

1.5 (125 V)1.0 (220 V)1.5 (110 V)2.5 (48 V)3.0 (24 V)

2728302928

DC

AC

HiAN Air Circuit Breaker | 13

HiAN Type

Page 14: Air Circuit Breaker - HUỲNH LAI · PDF fileAir Circuit Breaker HiAN 630 ~ 1600AF ... Easy maintenance and inspection mechanism ... Type HiAN 08 HiAN 12 HiAN 16 HiAN 20 HiAN 25 HiAN

Accessory

Main Circuit Safety ShuttersThe Main circuit safety shutters auto-matically conceal the main circuitcontacts on the draw-out cradle whenthe ACB is drawn out.

The top and bottom shutters operatesimultaneously.

Breaker Fixing BoltsThe breaker fixing bolts hold thebreaker body securely to the draw-outcradle in connected position.

Use them if the ACB is subject tostrong vibration.

Position Padlock The position padlock lever preventsthe breaker body from inadvertentlybeing drawn out.

The position padlock lever in thepulled-out position locks the breakerbody in the CONNECTED, TEST, orISOLATED position.

Padlock is not supplied(shacklediameter 6 mm below).

Arc ShieldAttached to the draw-out cradle, thiscover eliminate the safety clearancerequirement above the breaker.

Test JumperThe test jumper is a plug-in type, andallows ON-OFF tests on all the HiANACBs with the breaker body drawn outfrom the draw-out cradle.

The standard jumper cable is 3.5 m long.

Wrong Inserting Prevention DeviceInterchangeability exists within the HiAN type ACBs.

Because of this feature, there is apossibility for an ACB of a differentspecification being placed into the draw-out cradle.

Using the wrong inserting preventiondevice eliminates such a possibility.

This device is capable of distinguishingnine different breaker bodies.

ON-OFF Cycle CounterThe ON-OFF cycle counter is amechanical 5-digit readout that showsthe number of ON-OFF cycles of the ACB.Counter readings serve as a guide formaintenance or inspection.

ON-OFF Button CoverAn ON-OFF button cover preventsinadvertent or unauthorized operation ofthe ON or OFF button.

14 | HiAN & HiAS Type

Air Circuit BreakerHiAN Type

Page 15: Air Circuit Breaker - HUỲNH LAI · PDF fileAir Circuit Breaker HiAN 630 ~ 1600AF ... Easy maintenance and inspection mechanism ... Type HiAN 08 HiAN 12 HiAN 16 HiAN 20 HiAN 25 HiAN

Mechanical InterlockMechanical interlocks for interlocking 2 or 3ACBs in any arrangement is available.

Interlocking is possible between any framesize within the HiAN-ACB range.

Contact HHI for the details of any type with 3ACBs.

For example at vertical type, minimum pitch(575 mm) is possible if the proper insulatingdistance is obtained.

For large pitch, consult with HHI (maximum 1000 mm).

Auxiliary switch ratings

Category

Voltage ResistiveLoad (A)

ResistiveLoad (A) Min. applicable LoadInductive AC: cosØ≧0.3

Load (A) DC: L/R≧0.01Inductive AC: cosØ≧0.6Load (A) DC: L/R≧0.007

For General Service ➊ For Microload ➋

AC 100~250 V

AC 251~500 V

DC 30 V

DC 125~250 V

5

5

1

1

0.1

-

0.1

-

DC5 V 1 mA

0.1

-

0.1

-

5

5

1

1

➊ The chattering of b-contacts due to ON-OFF operation of the ACB lasts for less than 20 ms.➋ Do not supply different voltages to contacts of a switch.

Auxiliary SwitchesThe auxiliary switches operate during theACB ON-OFF operation. Connections to theswitches are made via ring terminals. The auxiliary switches for draw-out typeACBs operate in the all positions. The auxiliary switches are available forgeneral service and for microload. (4a 4b, standard)

Lifting LugLifting lugs are detachable tools that can beused to lift a draw-out cradle.Lifting lugs for body are available as an option.

PNL Cut-out

HiAN Air Circuit Breaker | 15

HiAN Type

Page 16: Air Circuit Breaker - HUỲNH LAI · PDF fileAir Circuit Breaker HiAN 630 ~ 1600AF ... Easy maintenance and inspection mechanism ... Type HiAN 08 HiAN 12 HiAN 16 HiAN 20 HiAN 25 HiAN

Current Transformer for Neutral Line(Separate Type)When using a 3-pole ACB with the ground faultprotection function to protect a 3-phase, 4-wiresystem against ground fault, it is required toinstall an appropriate current transformer (CT) tothe neutral line of the system.

HHI can provide this neutral line CT as an option. For the 4-pole ACB, a measuring CT instead of theneutral line CT is already built into the neutralphase of the ACB when the ground faultprotection is fitted.

AC220 V, 50/60 Hz

10 W

220 (W)×90 (H)×150 (D) mm

5 kg

Ratings and specifications

Power Supply

Power Consumption

Dimensions

Weight

Door FlangeA door flange can be used as adecoration panel that covers thecutout on the switchboard panel, andprovides IP20 protection.

Door Flange Cutting

APR Checker, Type IANS-HOC5The APR checker allows easy checking of thelong time-delay trip, short time-delay trip,instantaneous trip, and ground fault tripfunctions and the pre-trip alarm function of theAPR in the field.

Connection Diagram for Neutral CT

Accessory

16 | HiAN & HiAS Type

Air Circuit BreakerHiAN Type

Page 17: Air Circuit Breaker - HUỲNH LAI · PDF fileAir Circuit Breaker HiAN 630 ~ 1600AF ... Easy maintenance and inspection mechanism ... Type HiAN 08 HiAN 12 HiAN 16 HiAN 20 HiAN 25 HiAN

Key Lock(Lock-In-Open)An option of key lock is available in lock-in-open type that locks the ACB in theopen position. When this option is installed on a ACB, operators cannot operate theACB without matched key.

Key Interlock(Lock-In-Open)key interlock is a system of interlocking between ACBs, fitted with a key lock oflock-in-open type.

The key must be inserted to release the lock before closing ACB.The key can be removed when the ACB is opened and locked

After utilizing the lock-in-open type key lock, limited keys as default provides aneffective and reliable interlock system.Using the same keys also allows interlocking between an ACB and other devices(such as a switchboard door).A cylinder-type lock is supplied to ACB. (with angular movement 90°£ clockwise to trap key).

Example: Interlock for prevention of parallel feeding from two lines

ACB 3 cannot be closed ACB 2 cannot be closed ACB 1 cannot be closed

HiAN Air Circuit Breaker | 17

HiAN Type

Page 18: Air Circuit Breaker - HUỲNH LAI · PDF fileAir Circuit Breaker HiAN 630 ~ 1600AF ... Easy maintenance and inspection mechanism ... Type HiAN 08 HiAN 12 HiAN 16 HiAN 20 HiAN 25 HiAN

Accessory

Position switch, Operating sequence

Load Resistive Lamp Inductive Motor

AC 250 V

DC 30 V

DC 125 V

DC 250 V

10 A

6 A

0.6 A

0.30 A

1.5 A

3 A

0.1 A

0.05 A

6 A

6 A

0.6 A

0.30 A

2 A

3 A

0.1 A

0.05 A

The following table lists the available types of the switches.(1) CONNECTED position, indicator switches (2C)(2) TEST position, indicator switches (2C)(3) CONNECTED and TEST position, indicator switches (1C each)(4) ISOLATED position, indicator switches (1C)(5) INSERTED position, indicator switches (1C)(6) ISOLATED and INSERTED position, indicator switches (1C each)

Short " b" Contact

Position SwitchesThe position switches operate to give indication of breaker positions: CONNECTED, TEST, ISOLATED. There are two contact arrangements: 2cConnections to the switches are made via screw terminals.

Short Circuit b ContactWhen the ACB is in the test position or further out positions, the Short Circuit b Contact makes [b] signalwith regardless the ACB status; Close or Open.The Short Circuit b Contact output [a] signal when the breaker is in the connected position only.This contact is to prevent wrong operation in test position in the case of the interlock with another ACB inthe system.

18 | HiAN & HiAS Type

Air Circuit BreakerHiAN Type

Page 19: Air Circuit Breaker - HUỲNH LAI · PDF fileAir Circuit Breaker HiAN 630 ~ 1600AF ... Easy maintenance and inspection mechanism ... Type HiAN 08 HiAN 12 HiAN 16 HiAN 20 HiAN 25 HiAN

ACB Protection Relay

Step3

Determine the base current (lo) which is the reference

current for the AL, AS, AI and AP pick-up current settings.

Select one of the four base current values (lo)=(ICT)×0.5 or

0.63 or 0.8 or 1.0

Step4

Determine the long time-delay trip (AL), short time-delay

trip (AS), instantaneous trip (AI), Pre-trip alarm (AP) and

ground fault trip (AG) characteristics.

NOTE: The ground fault trip function is not available when the ratedprimary current (ICT) of the OCR is 160.

Step3Determine the long time-delay trip (AL), short time-delay trip(AS), instantaneous trip (AI), and pre-trip (AP) characteristics.

Determine the protective characteristics appropriate for your application

Type APR multi-protective device, the base current (lo) serves as the base to determine the long time-delay trip, short time-delay

trip, instantaneous trip and pre-trip alarm characteristics. The following steps show how to determine the optimum base current

(lo) that will provide the most appropriate characteristic to suit your application.

320, 630320, 630, 800320, 630, 800, 1000320, 630, 800, 1000, 1250320, 630, 800, 1000, 1250, 160020002000, 25002000, 2500, 320040004000, 50004000, 5000, 6300

※ The rated secondary current of all current transformers (CT) is 0.2 A.

160 ≦ [lo] ≦ 800160 ≦ [lo] ≦ 1250160 ≦ [lo] ≦ 1600

1000 ≦ [lo] ≦ 20001000 ≦ [lo] ≦ 25001000 ≦ [lo] ≦ 32002000 ≦ [lo] ≦ 40002000 ≦ [lo] ≦ 50002000 ≦ [lo] ≦ 6300

Step1

Determine the largest normal

load current (ILOAD) that will pass

through the Air Circuit Breaker.

Step2

Select the rated primary current

(ICT) of the multi-protective

device. The table below lists the

values of (ICT) available for the

respective breaker types.

Select (ICT) according to the

following criteria (ICT)≥(ILOAD)

Step1

Determine the rated generator

current (lGEN)

Step2

Determine the base current (lo)

which is the reference current

for the AL, AS, AI, AP pick-up

current settings of the multi-

protective device.

For General Feeder Circuits For Generator Protection

HiAN 06HiAN 08HiAN 10HiAN 12HiAN 16HiAN 20HiAN 25HiAN 32HiAN 40HiAN 50HiAN 63

Rated Primary Current (lCT) in (A) of OCRBreaker

HiAN 08HiAN 12HiAN 16HiAN 20HiAN 25HiAN 32HiAN 40HiAN 50HiAN 63

Breaker Rated Current (lo) in (A)

HiAN & HiAS Type ACB

HiAN Air Circuit Breaker | 19

HiAN Type

Page 20: Air Circuit Breaker - HUỲNH LAI · PDF fileAir Circuit Breaker HiAN 630 ~ 1600AF ... Easy maintenance and inspection mechanism ... Type HiAN 08 HiAN 12 HiAN 16 HiAN 20 HiAN 25 HiAN

Type APR Multi-protective DeviceThis device is a high-reliability, multi-function protection relay, utilizing a 8-bit microprocessor.

In addition to three over-current protective functions, (long time-delay, short time-delay and instantaneous),

a pre-trip alarm and / or ground fault protective function can also be incorporated within one device.

Indication for long time-delay trip and pick-up, via the LED and terminals for field checking (APR checker

required), are included in the device.

Furthermore, two additional operation indication functions can be included.

By using these functions, simplified checking becomes possible.

APR Characteristics

Application Type Protective Function Indicating Function Optional Function

General Feeder

Generator

APR-1L-AL

APR-1L-AS

APR-1L-AM

APR-1L-GL

APR-1L-GS

APR-1L-GM

APR-2L-GS

APR-1D-GM

APR-1S-AL

APR-1S-AS

APR-2S-AS

AL

AL

AL

AL

AL

AL

AL

AL

AL

AL

AL

AS

AS

AS

AS

AS

AS

AS

AS

AS

AS

AS

AI

AI

AI

AI

AI

AI

AI

AI

AI

AI

AI

AP

AP

AP

AP

AP

AP

AP

AP

AG

AG

AG

AG

AG

MCR

MCR

MCR

MCR

MCR

MCR

MCR

NP

NP

NP

NP

NP

IU

IU

IU

IUt 2)

IUt 2)

CP/I 1)

CP/I 3)

CP/I 3)

CP/I 4)

CP/I 1)

CP/I 1)

LED 5)

LED 5)

LED 5)

LED 5)

LED 6)

LED 6)

LED

LED 6)

LCD

LCD

LCD

FT

FT

FT

FT

FT

FT

FT

FT

CV

CV

CV

CV

CV

CV

CV

CV

AMS

AL Adjustable Long Time Delay Trip

AS Adjustable Short Time Delay Trip

AI Adjustable Instantaneous Trip

AP Adjustable Pre-trip Alarm

AG Adjustable Ground Fault Trip

MCR Making Current Release Function

NP Neutral Phase Protection Function

IU Integrated Indicating Operation LED & Contact1a contact makes the signal during 80 ms when aprotective function operates.Insulation level from earth is 1500 V.

IUt Integrated Indicating Operation LED & Contact2a contacts make the signal until the RESET button ispushed when protective function operates.Insulation level from earth is 1500 V.

CP/I Individual Indicationg Operation Contact2a contacts make the signal until the RESET button ispushed which protective function operates.Insulation level from earth is 1500 V.

LED Individual Indicating Operation LED.Each LED indicates until the RESET button is pushedwhich protective function operates.

1) 1a for AL, AS & AI / 1a for AP2) 2a for AL, AS, AI & AG3) 1a for AL, AS & AI / 1a for AP / 1a for AG

4)1a for AL, AS, AI & AG / 1a for AP5) The abonormal CPU status is indicated6) The operating function is indicated on the LCD.

Protective Function Indicating Function

ACB Protection Relay

20 | HiAN & HiAS Type

Air Circuit BreakerHiAN Type

Page 21: Air Circuit Breaker - HUỲNH LAI · PDF fileAir Circuit Breaker HiAN 630 ~ 1600AF ... Easy maintenance and inspection mechanism ... Type HiAN 08 HiAN 12 HiAN 16 HiAN 20 HiAN 25 HiAN

AMS Network Diagram

LCD Displaying the Protective Function and the Additional Function

FT Field Test Function

CV External Control Voltage is required

AMS APR Monitoring System

Pre-trip Alarm (AP)When the current reached the settingvalue, this function operates. If thecurrent drops below the pick-upcurrent [IP], the function resetsautomatically.

Neutral Phase Protection (NP)This function protects the neutralconductor from the damage due to alarge current. The current and timesetting is the same as LTD.

APR Monitoring System (AMS)APR-1D-GM has the RS-485communication port, which can beapplied to the APR MonitoringSystem. Throught the interface unit,the ACB can be directly operated, andthe power and the load condition canbe supervised and monitored.

Making Current Release (MCR)The instantaneous trip function is thedefault, and the MCR function can beactive by switching the INST/MCRknob.This MCR function trips the ACB, ifthe current exceeds the pick-upcurrent setting only during the closingoperation. After the ACB completesthe closing, this function getsdisabled.

Field Test (FT)AL, AS and AL function can be testedby the APR itself.If detailed field test is required, theAPR Checker is available for all APRs.

RS-485

APR 1 APR 2 APR 3 APR 4 APR 5 APR N

AMS Server

TCP/IP (Ethernet)

HiCM360/860

Precise Protection CoordinationNon Position for Pick-up Current

The pick-up current setting dials for the long time-delay,

short time-delay, instantaneous trip and ground fault trip

functions have a NON position to make the associated

function inoperative, there by permitting a quick change or

selection of the required functions.

Fail-safe Function for System Security

In the event of a fault current exceeding ten times the

setting of the base current (lo) (five times for generator

protection) while the AL, AS and AI functions are set to the

NON position, the circuit breaker

“Fail-Safe” function will interrupt the fault current in a time

equal to the short-time delay setting (T2)

Optional Function

HiAN Air Circuit Breaker | 21

HiAN Type

Page 22: Air Circuit Breaker - HUỲNH LAI · PDF fileAir Circuit Breaker HiAN 630 ~ 1600AF ... Easy maintenance and inspection mechanism ... Type HiAN 08 HiAN 12 HiAN 16 HiAN 20 HiAN 25 HiAN

ACB Protection Relay

I1 : LTD cur.

I2 : STD cur.

I3 : INST cur.

IG : INST cur.

T1 : GFT TIME

T2 : STD TIME

TG : GFT TIME

Characteristic

APR-1L-AL / APR-1L-GL

Type

Protectionfunction

LTD

Base Current (l0) ICT×0.5, 0.63, 0.8, 1.0

±15%

±15%

±20%

±7.5%

±15%

at I1×600% (0.5-1.25-2.5-5-10-15-20-25-30 sec)

I0×(Non-2-2.5-3-4-6-8-10)

80-160-240-320-400-480-560 msec I2t ON/OFF

I0×(Non-4-6-8-10-12-14-16 8 steps)

ICT×(Non-0.1-0.15-0.2-0.25-0.3-0.35-0.4)

80-160-240-320-400-480-560 msec

LTD, STD, INST, GFT (1a during 40 ms ON)

LTD Pick-up LED

-

I0×(Non-0.8-0.85-0.9-0.95-1.0-1.05-1.1 8 steps)

I1×1.05 Non Trip, I1×1.2 TripCurrent (l1)

Time (T1)

Current (l2)

Time (T2)

Current (l3)

Contact

LED

Control Voltage

STD

INST

GFT 1)Current (lG)

Time (TG)

FaultIndication

Additionalfunction

APR-1L-AL1) / APR-1L-GL Tolerance

※ 1) APR-1L-AL does not have the GFT function.

22 | HiAN & HiAS Type

Air Circuit BreakerHiAN Type

Page 23: Air Circuit Breaker - HUỲNH LAI · PDF fileAir Circuit Breaker HiAN 630 ~ 1600AF ... Easy maintenance and inspection mechanism ... Type HiAN 08 HiAN 12 HiAN 16 HiAN 20 HiAN 25 HiAN

I1 : LTD cur.I2 : STD cur.I3 : INST cur.

IG : GFT cur.Ip : PTA cur.T1 : LTD TIME

T2 : STD TIMETG : GFT TIMETp : PTA TIME

Characteristic

APR-1L-AS / APR-1L-AM / APR-1L-GS / APR-1L-GM

※ 1) APR-1L-AS and APR-1L-AM do not have the GFT function.

HiAN Air Circuit Breaker | 23

HiAN Type

Page 24: Air Circuit Breaker - HUỲNH LAI · PDF fileAir Circuit Breaker HiAN 630 ~ 1600AF ... Easy maintenance and inspection mechanism ... Type HiAN 08 HiAN 12 HiAN 16 HiAN 20 HiAN 25 HiAN

ACB Protection Relay

※ 1) APR-2S-AS does not have GFT function.2) LCD displays the current when it becomes 20% over than the rated current.

I1 : LTD cur.I2 : STD cur.I3 : INST cur.

IG : GFT cur.Ip : PTA cur.T1 : LTD TIME

T2 : STD TIMETG : GFT TIMETp : PTA TIME

APR-2L-GS / APR-2S-AS

Type

Protectionfunction

LTD

Base Current (l0) ICT×0.5, 0.63, 0.8, 1.0

±15%

±2%

±15%

±20%±7.5%±15%±20%

at I1×600% (0.5-1.25-2.5-5-10-15-20-25-30 sec)I0×(Non-2-2.5-3-4-6-8-10)80-160-240-320-400-480-560 msec I2t ON/OFFI0×(Non-4-6-8-10-12-14-16 8 steps) INST/MCR ON/OFFI0×(0.75-0.8-0.85-0.9-0.95-1.0-1.05-1.1)60-80-100-120-140-160-180-200 secICT×(Non-0.1-0.15-0.2-0.25-0.3-0.35-0.4)80-160-240-320-400-480-560 msec

LTD, STD, INST, PTA, GFT, System Alarm LEDAC/DC 100~250 VLTD, STD, INST TestR, S, T, N phase current2)

LTD, STD, INST (1a)PTA (1a)GFT (1a)

I0×(Non-0.8-0.85-0.9-0.95-1.0-1.05-1.1 8 steps)I1×1.05 Non Trip, I1×1.2 TripTime (T1)

Current (l2)Time (T2)

Current (l3)Current (lP)Time (TP)

Current (lG)Time (TG)

Contact

LEDControl Voltage

Field TestMonitoring

STD

INST

PTA

GFT1)

FaultIndicationAdditional

function

APR-2L-GS / APR-2S-AS1) Tolerance

Characteristic

24 | HiAN & HiAS Type

Air Circuit BreakerHiAN Type

Page 25: Air Circuit Breaker - HUỲNH LAI · PDF fileAir Circuit Breaker HiAN 630 ~ 1600AF ... Easy maintenance and inspection mechanism ... Type HiAN 08 HiAN 12 HiAN 16 HiAN 20 HiAN 25 HiAN

APR-1D-GM

I1 : LTD cur.I2 : STD cur.I3 : INST cur.

IG : GFT cur.Ip : PTA cur.T1 : LTD TIME

T2 : STD TIMETG : GFT TIMETp : PTA TIME

Characteristic

HiAN Air Circuit Breaker | 25

HiAN Type

Page 26: Air Circuit Breaker - HUỲNH LAI · PDF fileAir Circuit Breaker HiAN 630 ~ 1600AF ... Easy maintenance and inspection mechanism ... Type HiAN 08 HiAN 12 HiAN 16 HiAN 20 HiAN 25 HiAN

ACB Protection Relay

I1 : LTD cur.

I2 : STD cur.

I3 : INST cur.

T1 : LTD TIME

T2 : STD TIME

Characteristic

APR-1S-AL

Type

Protectionfunction

LTD

Base Current (l0) ICT×(0.5-1.0) 1% unit

±5%

±15%

±20%

at I1×120% (15-20-25-30-40-50-60 sec)

I0×(Non-2-2.5-2.7-3-3.5-4-4.5-5)

80-160-240-320-400-480-560 msec I2t ON/OFF

I0×(Non-4-6-8-10-12-14-16 8 steps) INST/MCR ON/OFF

LTD, STD, INST (1a during 40 ms ON)

LTD Pick-up LED

-

I0×(Non-0.8-0.9-1.0-1.05-1.1-1.15-1.2-1.25)

I1×1.0 TripCurrent (l1)

Time (T1)

Current (l2)

Time (T2)

Current (l3)

Contact

LED

Control Voltage

STD

INST

FaultIndication

Additionalfunction

APR-1S-AL Tolerance

26 | HiAN & HiAS Type

Air Circuit BreakerHiAN Type

Page 27: Air Circuit Breaker - HUỲNH LAI · PDF fileAir Circuit Breaker HiAN 630 ~ 1600AF ... Easy maintenance and inspection mechanism ... Type HiAN 08 HiAN 12 HiAN 16 HiAN 20 HiAN 25 HiAN

APR-1S-AS

I1 : LTD cur.

I2 : STD cur.

I3 : INST cur.

Ip : PTA cur.

T1 : LTD TIME

T2 : STD TIME

Tp : PTA TIME

Characteristic

Type

Protectionfunction

LTD

Base Current (l0) ICT×(0.5-1.0) 1% unit

±5%

±10%

±20%

±5%

±15%

at I1×120% (15-20-25-30-40-50-60 sec)

I0×(Non-2-2.5-2.7-3-3.5-4-4.5-5)

80-160-240-320-400-480-560 msec I2t ON/OFF

I0×(Non-4-6-8-10-12-14-16 8 steps) INST/MCR ON/OFF

I0×(0.75-0.8-0.85-0.9-0.95-1.0-1.05-1.1)

at IP×120% (5-10-15-20-25-30-35-40-45 sec)

LTD, STD, INST (1a) / PTA (1a)

LTD, STD, INST, PTA, System Alarm LED

AC / DC 100~250 V

LTD, STD, INST Test

I0×(Non-0.8-1.0-1.05-1.1-1.15-1.2-1.25)

I1×1.0 TripCurrent (l1)

Time (T1)

Current (l2)

Time (T2)

Current (l3)

Current (lp)

Time (Tp)

Contact

LED

Control Voltage

STD

INST

PTA

FaultIndication

Field Test

Additionalfunction

APR-1S-AS Tolerance

HiAN Air Circuit Breaker | 27

HiAN Type

Page 28: Air Circuit Breaker - HUỲNH LAI · PDF fileAir Circuit Breaker HiAN 630 ~ 1600AF ... Easy maintenance and inspection mechanism ... Type HiAN 08 HiAN 12 HiAN 16 HiAN 20 HiAN 25 HiAN

➊ GFT current setting range(10~40%)➋ LTD current setting range(80~110%)

➌ PTA current setting range(75~110%)➍ STD current setting range(200~1000%)

➎ INST current setting range(400~1600%)

General Feeder

Characteristic Curve

28 | HiAN & HiAS Type

Air Circuit BreakerHiAN Type

Page 29: Air Circuit Breaker - HUỲNH LAI · PDF fileAir Circuit Breaker HiAN 630 ~ 1600AF ... Easy maintenance and inspection mechanism ... Type HiAN 08 HiAN 12 HiAN 16 HiAN 20 HiAN 25 HiAN

➊ LTD current setting range(80~125%)➋ PTA current setting range(75~110%)

➌ STD current setting range(200~500%)➍ INST current setting range(400~1600%)

Generator

HiAN Air Circuit Breaker | 29

HiAN Type

Page 30: Air Circuit Breaker - HUỲNH LAI · PDF fileAir Circuit Breaker HiAN 630 ~ 1600AF ... Easy maintenance and inspection mechanism ... Type HiAN 08 HiAN 12 HiAN 16 HiAN 20 HiAN 25 HiAN

Outline Dimension

Draw-out Type

Fixed Type

Panel Cut-out

Panel Cut-out

Horizontal Bus-bar Type (Standard) | HiAN 06~32

270

4-R5

284

33.5

12-Ø

4

334

CONTROL CIRCUIT TERMINALS

(FOR MARINE)

FIXING BLOCKS

X

40.5

320

100100 100

5.5

2-Ø

12

T

V W

FH

J

IG

K

115

115

115

Y

383.

2

45

4-R5

284

33.5

12-Ø

4

334

CONTROL CIRCUIT TERMINALS

(SCREWLESS TYPE)

25150

T10

016

5.5

71

98.8

320

100100 100

5.5

456.

4

L

270

ON

40.9 134

353.5M

(3P)

T

115

115

115

30 | HiAN & HiAS Type

Air Circuit BreakerHiAN Type

Page 31: Air Circuit Breaker - HUỲNH LAI · PDF fileAir Circuit Breaker HiAN 630 ~ 1600AF ... Easy maintenance and inspection mechanism ... Type HiAN 08 HiAN 12 HiAN 16 HiAN 20 HiAN 25 HiAN

60

60

80

100

100

HiAN 06~

HiAN 10

HiAN 12~

HiAN 16

HiAN 20

HiAN 25

HiAN 32

Dimension(mm)

Type A

Draw-out Fixed Draw-out Fixed Draw-out Fixed

B CD E F G H I J K L M N O T V W X Y

60

60

80

80

80

30

30

50

60

60

30

30

50

50

50

15

15

15

20

20

15

15

15

15

15

12.5

12.5

12.5

12.5

12.5

90

90

120

120

120

105

105

150

150

150

105

105

150

150

150

160

160

205

205

205

160

160

205

205

205

167.3

167.3

212.3

212.3

212.3

167.3

167.3

209.3

209.3

209.3

154.3

154.3

199.3

199.3

199.3

154.3

154.3

199.3

199.3

199.3

168.5

168.5

213.5

213.5

213.5

168.5

168.5

213.5

213.5

213.5

8

15

15

22

30

204

204

249

249

249

204

204

249

249

249

216

216

261

261

261

216

216

261

261

261

3 Pole

60

60

80

100

100

Dimension(mm)

Type A

Draw-out Fixed Draw-out Fixed Draw-out Fixed

B CD E F G H I J K L M N O T V W X Y

60

60

80

80

80

30

30

50

60

60

30

30

50

50

50

15

15

15

20

20

15

15

15

15

15

12.5

12.5

12.5

12.5

12.5

90

90

120

120

120

105

105

150

150

150

195

195

270

270

270

160

160

205

205

205

250

250

325

325

325

167.3

167.3

212.3

212.3

212.3

257.3

257.3

332.3

332.3

332.3

154.3

154.3

199.3

199.3

199.3

244.3

244.3

319.3

319.3

319.3

168.5

168.5

213.5

213.5

213.5

258.5

258.5

333.5

333.5

333.5

8

15

15

22

30

204

204

249

249

249

294

294

369

369

369

216

216

261

261

261

306

306

381

381

381

4 Pole

HiAN 06~

HiAN 10

HiAN 12~

HiAN 16

HiAN 20

HiAN 25

HiAN 32

EEE

293.6

490

ISOLATED

TEST

CONNECTED

AA

312.

2

216

EARTH TERMINAL MOUNT’G

70.5

4-Ø14 HOLEs

C

2-ØD

B

C

2-ØD

B

1515

T 10

0

30

15

29.9

25050

358

45

73.3

164

420

N

HiAN Air Circuit Breaker | 31

HiAN Type

P : Front PNL Center LineC

Page 32: Air Circuit Breaker - HUỲNH LAI · PDF fileAir Circuit Breaker HiAN 630 ~ 1600AF ... Easy maintenance and inspection mechanism ... Type HiAN 08 HiAN 12 HiAN 16 HiAN 20 HiAN 25 HiAN

Outline Dimension

Panel Cut-out

Vertical Bus-bar Type (Only for Draw-out Type) | HiAN 06~32

270

4-R5

284

33.5

12-Ø

4

334

CONTROL CIRCUIT TERMINALS

FIXING BLOCKS

X

40.5

320

100100 100

5.5

2-Ø

12

V W

FH

J

GI

K

115

115

115

Y

383.

2

(FOR MARINE)

7559 69

18.9

Z

aa

b

a

286.

5

mmm

mmm

d

h

i

g

f

c’

j-Ø12.5 j-Ø

12.5

j-Ø12.5

15515

15

5 5e

100

for HiAN20for HiAN06~HiAN16 for HiAN25~HiAN32

32 | HiAN & HiAS Type

Air Circuit BreakerHiAN Type

Draw-out Type

Page 33: Air Circuit Breaker - HUỲNH LAI · PDF fileAir Circuit Breaker HiAN 630 ~ 1600AF ... Easy maintenance and inspection mechanism ... Type HiAN 08 HiAN 12 HiAN 16 HiAN 20 HiAN 25 HiAN

3 Pole

4 Pole

HiAN 20

HiAN 25

HiAN 32

Dimension(mm)

TypeF G H I J K V W X a b c、 d e f g h i j m n r

105

105

150

150

150

105

105

150

150

150

160

160

205

205

205

160

160

205

205

205

167.3

167.3

212.3

212.3

212.3

167.3

167.3

212.3

212.3

212.3

204

204

249

249

249

204

204

249

249

249

216

216

261

261

261

90

90

120

120

120

60

60

80

100

100

160.75

157.25

157.25

153.75

149.75

8

15

15

22

30

130.75

127.25

117.25

103.75

99.75

60

60

80

100

100

108

115

115

122

130

8

15

15

22

30

30

30

40

20

20

12

12

18

18

18

30

30

50

60

60

92.2

92.2

102.2

108.3

108.3

35.5

35.5

35.5

35

40

Y Z

216

216

261

261

261

277.8

277.8

367.8

367.8

367.8

HiAN 20

HiAN 25

HiAN 32

Dimension(mm)

TypeF G H I J K V W X a b c、 d e f g h i j m n r

105

105

150

150

150

195

195

270

270

270

160

160

205

205

205

250

250

325

325

325

167.3

167.3

212.3

212.3

212.3

257.3

257.3

332.3

332.3

332.3

204

204

249

249

249

294

294

369

369

369

216

216

261

261

261

90

90

120

120

120

60

60

80

100

100

160.75

157.25

157.25

153.75

149.75

8

15

15

22

30

130.75

127.25

117.25

103.75

99.75

60

60

80

100

100

108

115

115

122

130

8

15

15

22

30

30

30

40

20

20

16

16

24

24

24

30

30

50

60

60

92.2

92.2

102.2

108.3

108.3

35.5

35.5

35.5

35

40

Y Z

306

306

381

381

381

367.8

367.8

487.8

487.8

487.8

HiAN 06~

HiAN 10

HiAN 12~

HiAN 16

HiAN 06~

HiAN 10

HiAN 12~

HiAN 16

n

r

293.6

490

64

312.

2

216

EARTH TERMINAL MOUNT’G

70.5

4-Ø14 HOLEs

30

15

29.9

25050

358

420

ISOLATED

TEST

CONNECTED

HiAN Air Circuit Breaker | 33

HiAN Type

P : Front PNL Center LineC

Page 34: Air Circuit Breaker - HUỲNH LAI · PDF fileAir Circuit Breaker HiAN 630 ~ 1600AF ... Easy maintenance and inspection mechanism ... Type HiAN 08 HiAN 12 HiAN 16 HiAN 20 HiAN 25 HiAN

Outline Dimension

Horizontal Bus-bar Type | HiAN 40 (3P, 4P)

Panel Cut-out

※❶ is neutral pole of 4pole breaker.❷ Mounting angle steel is not supplied.

Front View 3P

Rear View 3PSide View

34 | HiAN & HiAS Type

Air Circuit BreakerHiAN Type

N

Page 35: Air Circuit Breaker - HUỲNH LAI · PDF fileAir Circuit Breaker HiAN 630 ~ 1600AF ... Easy maintenance and inspection mechanism ... Type HiAN 08 HiAN 12 HiAN 16 HiAN 20 HiAN 25 HiAN

P : Front PNL Center LineC

Front View 4P

Rear View 4P

HiAN Air Circuit Breaker | 35

HiAN Type

Page 36: Air Circuit Breaker - HUỲNH LAI · PDF fileAir Circuit Breaker HiAN 630 ~ 1600AF ... Easy maintenance and inspection mechanism ... Type HiAN 08 HiAN 12 HiAN 16 HiAN 20 HiAN 25 HiAN

Outline Dimension

Vertical Bus-bar Type (Only for Draw-out Type) | HiAN 40 (3P, 4P)

Panel Cut-out

Front View

Rear ViewSide View

36 | HiAN & HiAS Type

Air Circuit BreakerHiAN Type

※❶ is neutral pole of 4pole breaker.❷ Mounting angle steel is not supplied.

N

Page 37: Air Circuit Breaker - HUỲNH LAI · PDF fileAir Circuit Breaker HiAN 630 ~ 1600AF ... Easy maintenance and inspection mechanism ... Type HiAN 08 HiAN 12 HiAN 16 HiAN 20 HiAN 25 HiAN

Front View

Rear View

HiAN Air Circuit Breaker | 37

HiAN Type

P : Front PNL Center LineC

Page 38: Air Circuit Breaker - HUỲNH LAI · PDF fileAir Circuit Breaker HiAN 630 ~ 1600AF ... Easy maintenance and inspection mechanism ... Type HiAN 08 HiAN 12 HiAN 16 HiAN 20 HiAN 25 HiAN

Outline Dimension

Horizontal Bus-bar Type | HiAN 50~63 (3P, 4P) (N 50%, Standard)

Panel Cut-out

Front View 3P

Rear View 3PSide View

38 | HiAN & HiAS Type

Air Circuit BreakerHiAN Type

※❶ is neutral pole of 4pole breaker.(N phase is 50% size of the other phase)❷ Mounting angle steel is not supplied.

N

Page 39: Air Circuit Breaker - HUỲNH LAI · PDF fileAir Circuit Breaker HiAN 630 ~ 1600AF ... Easy maintenance and inspection mechanism ... Type HiAN 08 HiAN 12 HiAN 16 HiAN 20 HiAN 25 HiAN

Front View 4P

Rear View 4P

HiAN Air Circuit Breaker | 39

HiAN Type

P : Front PNL Center LineC

Page 40: Air Circuit Breaker - HUỲNH LAI · PDF fileAir Circuit Breaker HiAN 630 ~ 1600AF ... Easy maintenance and inspection mechanism ... Type HiAN 08 HiAN 12 HiAN 16 HiAN 20 HiAN 25 HiAN

Outline Dimension

Vertical Bus-bar Type | HiAN 50~63 (3P, 4P) (N 50%, Standard)

Panel Cut-out

Front View

Rear ViewSide View

40 | HiAN & HiAS Type

Air Circuit BreakerHiAN Type

※❶ is neutral pole of 4pole breaker.(N phase is 50% size of the other phase)❷ Mounting angle steel is not supplied.

N

Page 41: Air Circuit Breaker - HUỲNH LAI · PDF fileAir Circuit Breaker HiAN 630 ~ 1600AF ... Easy maintenance and inspection mechanism ... Type HiAN 08 HiAN 12 HiAN 16 HiAN 20 HiAN 25 HiAN

Side View

Rear View

HiAN Air Circuit Breaker | 41

HiAN Type

P : Front PNL Center LineC

Page 42: Air Circuit Breaker - HUỲNH LAI · PDF fileAir Circuit Breaker HiAN 630 ~ 1600AF ... Easy maintenance and inspection mechanism ... Type HiAN 08 HiAN 12 HiAN 16 HiAN 20 HiAN 25 HiAN

Outline Dimension

Horizontal & Vertical Bus-bar Type | HiAN 50~63 (4P) (N 100%, Option)

Panel Cut-out

ISOLATED POSITION

TEST POSITION

CONNECTED POSITION

MAX. CONNECT LENGTH

(NOT SUPPLIED)

Front View

Rear ViewSide View

42 | HiAN & HiAS Type

Air Circuit BreakerHiAN Type

※❶ is neutral pole of 4pole breaker.(N phase is 100% size of the other phase)❷ Mounting angle steel is not supplied.

N

Page 43: Air Circuit Breaker - HUỲNH LAI · PDF fileAir Circuit Breaker HiAN 630 ~ 1600AF ... Easy maintenance and inspection mechanism ... Type HiAN 08 HiAN 12 HiAN 16 HiAN 20 HiAN 25 HiAN

ISOLATED POSITION

TEST POSITION

CONNECTED POSITION

(NOT SUPPLIED)

MAX. CONNECT LENGTH

Side View

Rear View

HiAN Air Circuit Breaker | 43

HiAN Type

P : Front PNL Center LineC

Page 44: Air Circuit Breaker - HUỲNH LAI · PDF fileAir Circuit Breaker HiAN 630 ~ 1600AF ... Easy maintenance and inspection mechanism ... Type HiAN 08 HiAN 12 HiAN 16 HiAN 20 HiAN 25 HiAN

Circuit Diagram

Over-Current Protective Device

Main CircuitCT: Current Transformer for APR

19 20

22 24 AP

25 26 AL AS AI

27

MHT

28 AG

Control Power Terminal (CP/I)

Under Voltage Trip (UVT)

11 12 Control Power Terminal

T1 T2 Remote Trip Terminal

Motor Charging/Closing Circuits

1 2 Charging Power Terminal

Condenser Trip

Auxiliary Switch

31~46 Auxiliary Contact

Position Switch

3 4 Closing Power Terminal

15 16 Spring Charge Switch Terminal

Indication Terminal

Indication Terminal

Indication Terminal

Magnetic Hold Trigger

M Charging motor

Shunt Trip (SHT)

7 8 Control Power Terminal

U V Control Power Terminal

P N Remote Trip Terminal

TEST position61-62 ON61-63 OFF64-65 ON64-66 OFF

CONNECTED position71-72 ON71-73 OFF74-75 ON74-76 OFF

INSERTED position84-85 ON84-86 OFF

ISOLATED position81-82 ON81-83 OFF

SHT Shunt trip coil

LRC Latch release coil

UVT Under voltage trip coil

*1 : Attach at rated voltage DC 125 V *2 : Option(MCR)

R1 Resistance

Draw-out Type

44 | HiAN & HiAS Type

Air Circuit BreakerHiAN Type

Page 45: Air Circuit Breaker - HUỲNH LAI · PDF fileAir Circuit Breaker HiAN 630 ~ 1600AF ... Easy maintenance and inspection mechanism ... Type HiAN 08 HiAN 12 HiAN 16 HiAN 20 HiAN 25 HiAN

Control Circuit Lay-out APR-1S-AS Circuit

15

16

(Sho

rt ’b

’ con

tact

) opt

ion

30 28 26 24 22 20 14 12 10 2 4 8 16 32 34 36 38 42 44 46 48 504029 27 25 23 19 13 11 9 1 3 7 15 31 33 35 37 39 43 45 47 4941

Draw-out Type

Fixed Type

Manufacturer wiring part User wiring part Disconnecting device

HiAN Air Circuit Breaker | 45

HiAN Type

Page 46: Air Circuit Breaker - HUỲNH LAI · PDF fileAir Circuit Breaker HiAN 630 ~ 1600AF ... Easy maintenance and inspection mechanism ... Type HiAN 08 HiAN 12 HiAN 16 HiAN 20 HiAN 25 HiAN

APR Wiring Diagram

3 Pole 4 Pole

APR - 1L - ALAPR -1S - AL

APR - 1L - AS

APR - 1L - AM

APR - 1L - GL

46 | HiAN & HiAS Type

Air Circuit BreakerHiAN Type

Page 47: Air Circuit Breaker - HUỲNH LAI · PDF fileAir Circuit Breaker HiAN 630 ~ 1600AF ... Easy maintenance and inspection mechanism ... Type HiAN 08 HiAN 12 HiAN 16 HiAN 20 HiAN 25 HiAN

3 Pole 4 Pole

APR - 1L - GSAPR -2L - GS

APR - 1L - GM

APR - 1D - GM

APR - 1S - ASAPR - 2S - AS

HiAN Air Circuit Breaker | 47

HiAN Type

Page 48: Air Circuit Breaker - HUỲNH LAI · PDF fileAir Circuit Breaker HiAN 630 ~ 1600AF ... Easy maintenance and inspection mechanism ... Type HiAN 08 HiAN 12 HiAN 16 HiAN 20 HiAN 25 HiAN

Ordering Information

HiAN type ACBs have an extensive range of available accessories, enabling the circuit breaker to be custom-built to suit everyapplication. When ordering HiAN ACBs, please give us a complete order No. nomenclature as shown in following tables.

Order No. nomenclature

The 6th Order No. Suffix (Other accessories)

The 5th Order No. Suffix (Rating of CT)

The 4th Order No. Suffix (Kind of trip release)

The 3th Order No. Suffix (Over-current release)

The 2th Order No. Suffix (Charging mechanism)

The 1th Order No. Suffix (Breaker poles and mounting method)

The Basic Order No. (Breaker type)

NO.

Frame

IAN06 IAN08 IAN10 IAN12 IAN16 IAN20 IAN25 IAN32 IAN40 IAN50 IAN63

630 A 800 A 1000 A 1250 A 1600 A 2000 A 2500 A 3200 A 4000 A 5000 A 6300 A

PolesMounting

3 Poles

4 Poles

Fixed Type Draw-out Type Remark

3F

4F

3D

4D

NO.

H0

M1

M2

Description Description

Manual Charge

Motor Charge/AC110 V

Motor Charge/AC220 V

Motor Charge/DC110 V

Motor Charge/DC220 V

Motor Charge/DC24 V

NO.

General Protection Generator Protection

00

20

21

22

23

24

25

26

27

Function APR Type NO. Function APR Type

Without APR

AL-AS-AI-IU

AL-AS-AI-AP-CP/I/AC, DC

AL-AS-AI-AP-IU/CP/I, AC, DC

AL-AS-AI-AG, IU

AL-AS-AI-AP-AG-CP/ I/AC, DC

AL-AS-AI-AP-AG-IU/AC, DC

AL-AS-AI-AP-AG-IU/AC, DC

AL-AS-AI-AP-AG-IU/CP/I, AC, DC

-

APR-1L-AL

APR-1L-AS

APR-1L-AM

APR-1L-GL

APR-1L-GS

APR-2L-GS

APR-1D-GM

APR-1L-GM

The basic order NO. (Breaker frame)

The 1st order NO. (Poles and mounting method)

The 2nd order NO. (Charging mechanism description)

The 3rd order NO. (ACB protection relay)

M5

M6

M7

NO. DescriptionMotor Charge/DC48 V

Motor Charge/DC125 V

M8

M9

NO.

00

28

29

30

Without APR

AL-AS-AI-IU

AL-AS-AI-AP-IU/AC, DC

AL-AS-AI-AP-IU/AC, DC

-

APR-1S-AL

APR-1S-AS

APR-2S-AS

48 | HiAN & HiAS Type

Air Circuit BreakerHiAN Type

Page 49: Air Circuit Breaker - HUỲNH LAI · PDF fileAir Circuit Breaker HiAN 630 ~ 1600AF ... Easy maintenance and inspection mechanism ... Type HiAN 08 HiAN 12 HiAN 16 HiAN 20 HiAN 25 HiAN

NO.

X5

X6

W1

W2

W3

W4

W5

W6

W7

C1

C2

Description NO. Description Description Description

UVT(Delay)/AC430~470 V

UVT(Delay)/AC480~500 V

UVT(INST)/AC100 V

UVT(INST)/AC220 V

UVT(INST)/AC380 V

UVT(INST)/AC440 V

UVT(INST)/DC100 V

UVT(INST)/DC200 V

S1+T1

S2+T2

S3+T3

T4

T5

U1

U2

U3

U4

U5

U6

D1

D2

D3

NO. NO.

D4

I1

I2

I3

I4

I5

I6

X1

X2

X3

X4

V

T

H

J

K

320 A

630 A

800 A

1000 A

1250 A

IAN12~IAN16

IAN06~IAN16

IAN08~IAN16

IAN10~IAN16

IAN12~IAN16

The 4th order NO. (Kind of trip release)

The 5th order NO. (Rated primary current of CT)

S1

S2

S3

S4

S5

S6

S7

S8

T1

T2

T3

SHUNT/AC100~150 V

SHUNT/AC180~250 V

SHUNT/AC380~420 V

SHUNT/AC421~480 V

SHUNT/DC90~125 V

SHUNT/DC150~230 V

SHUNT/DC24 V

SHUNT/DC48 V

UVT(Delay)/AC100~120 V

UVT(Delay)/AC200~240 V

UVT(Delay)/AC360~400 V

L

M

N

P

Q

S

X

Zero

1600 A

2000 A

2500 A

3200 A

4000 A

5000 A

6300 A

None (Over current release ordering NO. “00”)

IAN16

IAN20~IAN32

IAN25~IAN32

IAN32

IAN40~IAN63

IAN50~IAN63

IAN63

NO. Description Type NO. NO.Description DescriptionType Type

The 6th order NO. (Other accessories)

NO.

B

D

E

F

G

H

J

K

L

M

N

Q

R

S

T

U

V

W

X

Z

1

2

3

4

5

6

7

8

Acc’y Name NO. NO.Acc’y Name Acc’y Name

Key Lock (Lock In Open)

Cycle Counter

Safety Shutter

Fixing Block

Door Flange

Vertical Type Mount’g Bus-bar

Test Jumper

Short b Contact

Lifting Hook

Button Cover & Key

Neutral CT

Position Switch (Conn: 1C, Test: 1C)

Position Switch (Conn: 2C)

Position Switch (Test: 2C)

Position Switch(Inserted: 1C, Isolated: 1C)

Position Switch(Inserted: 1C)

Position Switch(Isolated: 1C)

Wrong Insert’n Prevent’n Device

Arc Shield

APR Checker (IANS-HOC5)

Mechanical Interlock (Hori. 2ST)

Mechanical Interlock (Hori. 3ST)

Mechanical Interlock (Vert. 2ST)

Mechanical Interlock (Vert. 3ST)

100% N phase (HiAN 50, 63)

Spring Charge Switch

ATS(Automatic Transfer Switch)

MCR (Making Current Release)

When ordering more than one kind of accessory, please list order NO. according to the order of alphabet and Arabia numbers.

S4+T4

S1+U1

S2+U2

S3+U3

S4+U4

S5+U5

S6+U6

S5+T3

S1+T3

S7+T4

S7+T2

S6+T2

S6+T3

S1+T2

S1+T4

S2+T4

S5+T1

S5+T2

S5+T4

S5+T5

CTD/AC110 V

CTD/AC220 V

Specification Order Number

Setting values of over-current release

Other Accessories:Key lock in open position, safety shutter

Rated Primary Current of CT: 1250 A / 0.2 A

Kind of Trip: Shunt Trip / DC 100 V

Over-Current Release: for generalFeeder circuit, AL-AS-AI-IU

3 Pole, Draw-out Type

Motor-Charging / DC 100 V

Amperes Frame: 1250 ARated Breaking Capacity: AC500 V / 70 kA

Example

K

Base current (lo) 1250 APick-up Current [l1] 1250 A Time-delay [l1] 15 s

IAN12

IAN12 3 D

IAN12 3 D M 5

IAN12 3 D M 5 2 0

IAN12 3 D M 5 2 0 S 5

IAN12 3 D M 5 2 0 S 5

IAN12

AL

Pick-up Current [l2] 7500 A Time-delay [l2] 240 sAS

Pick-up Current [l3] 12500 AAI

3 D M 5 2 0 S 5 K EB

HiAN Air Circuit Breaker | 49

HiAN Type

Page 50: Air Circuit Breaker - HUỲNH LAI · PDF fileAir Circuit Breaker HiAN 630 ~ 1600AF ... Easy maintenance and inspection mechanism ... Type HiAN 08 HiAN 12 HiAN 16 HiAN 20 HiAN 25 HiAN

Ordering Information

HiAN ACB spare part list

No NoType TypeDescription Description

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

51

52

53

54

55

56

57

58

59

60

61

62

63

64

65

66

67

68

69

70

71

72

73

74

75

76

77

78

79

80

IANS-20

IANS-21

IANS-22

IANS-23

IANS-24

IANS-25

IANS-26

IANS-27

IANS-28

IANS-29

IANS-30

IANS-116 (F)

IANS-216 (F)

IANS-316 (F)

IANS-416 (F)

IANS-132 (F)

IANS-232 (F)

IANS-332 (F)

IANS-432 (F)

IANS-ANTI110

IANS-ANTI 220

IANS-A/RLY24

IANS-AB163

IANS-AB164

IANS-AB323

IANS-AB324

IANS-AB503

IANS-AB504

IANS-AS

IANS-ATS

IANS-BL

IANS-CA163S

IANS-CA164S

IANS-CA323S

IANS-CA324S

IANS-CA403S

IANS-CA404S

IANS-CA503S

IANS-CA504S

IANS-CJ

IANS-CK

IANS-SB

IANS-CT032E

IANS-CT063E

IANS-CT080E

IANS-CT110E

IANS-CT113E

IANS-CT116E

IANS-CT120E

IANS-CT225E

IANS-CT332E

IANS-CT440E

IANS-CT550E

IANS-CT660E

IANS-DI16P

IANS-DI32P

IANS-DI63P

IANS-DP

IANS-DP63

IANS-FB

IANS-FB63

IANS-HANDLE

IANS-HOC5

IANS-IC06E

IANS-IC08E

IANS-IC10E

IANS-IC12E

IANS-IC16E

IANS-IC20E

IANS-IC25E

IANS-IC32E

IANS-IC40E

IANS-IC50E

IANS-IC63E

IANS-KL/B

IANS-L1

IANS-L2

IANS-L5

IANS-L6

IANS-L7

ACB Protection Relay (APR-1L-AL)

ACB Protection Relay (APR-1L-AS)

ACB Protection Relay (APR-1L-AM)

ACB Protection Relay (APR-1L-GL)

ACB Protection Relay (APR-1L-GS)

ACB Protection Relay (APR-2L-GS)

ACB Protection Relay (APR-1D-GM)

ACB Protection Relay (APR-1L-GM)

ACB Protection Relay (APR-1S-AL)

ACB Protection Relay (APR-1S-AS)

ACB Protection Relay (APR-2S-AS)

Mech. Interlock (for HiAN 06~16, Horizontal 2st)

Mech. Interlock (for HiAN 06~16, Horizontal 3st)

Mech. Interlock (for HiAN 06~16, Vertical 2st)

Mech. Interlock (for HiAN 06~16, Vertical 3st)

Mech. Interlock (for HiAN 20~32, Horizontal 2st)

Mech. Interlock (for HiAN 20~32, Horizontal 3st)

Mech. Interlock (for HiAN 20~32, Vertical 2st)

Mech. Interlock (for HiAN 20~32, Vertical 3st)

Anti-pumping Relay (110 V)

Anti-pumping Relay (220 V)

Anti-pumping Relay (DC 24 V)

Arc Shield (HiAN 06~16, 3P)

Arc Shield (HiAN 06~16, 4P)

Arc Shield (HiAN 20~32, 3P)

Arc Shield (HiAN 20~32, 4P)

Arc Shield (HiAN 50~63, 3P)

Arc Shield (HiAN 50~63, 4P)

Aux. Switch

ATS Controller

Button Lock Device

Safety Shutter (HiAN 06~16, 3P)

Safety Shutter (HiAN 06~16, 4P)

Safety Shutter (HiAN 20~32, 3P)

Safety Shutter (HiAN 20~32, 4P)

Safety Shutter (HiAN 40, 3P)

Safety Shutter (HiAN 40, 4P)

Safety Shutter (HiAN 50~63, 3P)

Safety Shutter (HiAN 50~63, 4P)

Control Jack

Cycle Counter

Short Circuit b Contact

CT (320/0.2 A)

CT (630/0.2 A)

CT (800/0.2 A)

CT (1000/0.2 A)

CT (1250/0.2 A)

CT (1600/0.2 A)

CT (2000/0.2 A)

CT (2500/0.2 A)

CT (3200/0.2 A)

CT (4000/0.2 A)

CT (5000/0.2 A)

CT (6300/0.2 A)

DI-unit (HiAN 06~16)

DI-unit (HiAN 20~32)

DI-unit (HiAN 40~63), 1 Pole

Door Flange (630~3200 A)

Door Flange (4000~6300 A)

Fixing Block (630~3200 A)

Fixing Block (4000~6300 A)

Handle

APR Checker

Isolating Contact (630 A)

Isolating Contact (800 A)

Isolating Contact (1000 A)

Isolating Contact (1250 A)

Isolating Contact (1600 A)

Isolating Contact (2000 A)

Isolating Contact (2500 A)

Isolating Contact (3200 A)

Isolating Contact (4000 A)

Isolating Contact (5000 A)

Isolating Contact (6300 A)

Key Lock Unit (Lock in Open)

LRC Unit (AC 110 V)

LRC Unit (AC 220 V)

LRC Unit (DC 110 V)

LRC Unit (DC 220 V)

LRC Unit (DC 24 V)

50 | HiAN & HiAS Type

Air Circuit BreakerHiAN Type

Page 51: Air Circuit Breaker - HUỲNH LAI · PDF fileAir Circuit Breaker HiAN 630 ~ 1600AF ... Easy maintenance and inspection mechanism ... Type HiAN 08 HiAN 12 HiAN 16 HiAN 20 HiAN 25 HiAN

No NoType TypeDescription Description

81

82

83

84

85

86

87

88

89

90

91

92

93

94

95

96

97

98

99

100

101

102

103

104

105

106

107

108

109

110

111

112

113

114

115

116

117

118

119

120

121

122

123

124

125

126

127

128

129

130

131

132

133

134

135

136

137

138

139

140

141

142

143

144

IANS-L8

IANS-L6

IANS-LL

IANS-M1

IANS-M2

IANS-M5

IANS-M6

IANS-M7

IANS-M8

IANS-M9

IANS-M6

IANS-MHT

IANS-NCT032E

IANS-NCT063E

IANS-NCT080E

IANS-NCT110E

IANS-NCT113E

IANS-NCT116E

IANS-NCT120E

IANS-NCT225E

IANS-NCT332E

IANS-NCT440E

IANS-NCT550E

IANS-NCT660E

IANS-PS

IANS-S1

IANS-S2

IANS-S3

IANS-S4

IANS-S5

IANS-S6

IANS-S7

IANS-S8

IANS-S6

IANS-T1

IANS-T2

IANS-T3

IANS-T4

IANS-T5

IANS-TU6

IANS-TJ

IANS-U1

IANS-U2

IANS-UVT/Coil

IANS-UVT/Coil 6

IANS-WI

DAT06-3D

DAT06-4D

DAT08-3D

DAT08-4D

DAT10-3D

DAT10-4D

DAT12-3D

DAT12-4D

DAT16-3D

DAT16-4D

DAT20-3D

DAT20-4D

DAT25-3D

DAT25-4D

DAT32-3D

DAT32-4D

HAFS-T7

HAFS-T9

LRC Unit (DC 48 V)

LRC Unit (4000~6300 A, ex: AC 110 V→IANS-L16)

Lifting Lugs

Charging Motor Unit (AC 110 V)

Charging Motor Unit (AC 220 V)

Charging Motor Unit (DC 110 V)

Charging Motor Unit (DC 220 V)

Charging Motor Unit (DC 24 V)

Charging Motor Unit (DC 48 V)

Charging Motor Unit (DC 220 V)

Charging Motor Unit (4000~6300 A, ex: AC 110 V→IANS-M16)

MHT Unit

Neutral CT (320/0.2 A)

Neutral CT (630/0.2 A)

Neutral CT (800/0.2 A)

Neutral CT (1000/0.2 A)

Neutral CT (1250/0.2 A)

Neutral CT (1600/0.2 A)

Neutral CT (2000/0.2 A)

Neutral CT (2500/0.2 A)

Neutral CT (3200/0.2 A)

CT (4000/0.2 A)

CT (5000/0.2 A)

CT (6300/0.2 A)

Position Switch

Shunt Trip Unit (AC 110 V)

Shunt Trip Unit (AC 220 V)

Shunt Trip Unit (AC 380 V)

Shunt Trip Unit (AC 450 V)

Shunt Trip Unit (DC 110 V)

Shunt Trip Unit (DC 220 V)

Shunt Trip Unit (DC 24 V)

Shunt Trip Unit (DC 48 V)

Shunt Trip Unit (4000~6300 A, ex: AC 110 V→IANS-S16)

Under Voltage Trip Unit (AC 110 V)

Under Voltage Trip Unit (AC 220 V)

Under Voltage Trip Unit (AC 380 V)

Under Voltage Trip Unit (AC 450 V)

Under Voltage Trip Unit (AC 480 V)

Under-voltage Trip Unit (4000~6300 A, ex: AC 110 V→IANS-T1U6)

Test Jumper

Under Voltage Trip Unit (DC 110 V)

Under Voltage Trip Unit (DC 220 V)

Under Voltage Trip Coil (630~3200 A)

Under Voltage Trip Coil (4000~6300 A)

Wrong Insertion Prevention Device

Draw-out frame Unit (HiAN 06, 3P)

Draw-out frame Unit (HiAN 06, 4P)

Draw-out frame Unit (HiAN 08, 3P)

Draw-out frame Unit (HiAN 08, 4P)

Draw-out frame Unit (HiAN 10, 3P)

Draw-out frame Unit (HiAN 10, 4P)

Draw-out frame Unit (HiAN 12, 3P)

Draw-out frame Unit (HiAN 12, 4P)

Draw-out frame Unit (HiAN 16, 3P)

Draw-out frame Unit (HiAN 16, 4P)

Draw-out frame Unit (HiAN 20, 3P)

Draw-out frame Unit (HiAN 20, 4P)

Draw-out frame Unit (HiAN 25, 3P)

Draw-out frame Unit (HiAN 25, 4P)

Draw-out frame Unit (HiAN 32, 3P)

Draw-out frame Unit (HiAN 32, 4P)

Condenser Trip Device (AC 110V)

Condenser Trip Device (AC 220V)

HiAN Air Circuit Breaker | 51

HiAN Type

Page 52: Air Circuit Breaker - HUỲNH LAI · PDF fileAir Circuit Breaker HiAN 630 ~ 1600AF ... Easy maintenance and inspection mechanism ... Type HiAN 08 HiAN 12 HiAN 16 HiAN 20 HiAN 25 HiAN

Ordering Information

HiAN ACB spare parts for marine applications

No Order No. Specifications201612

Type

08 25 32 40 50 63

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

IANS-SP01

IANS-SP02

IANS-SP03

IANS-SP04

IANS-SP05

IANS-SP06

IANS-SP07

IANS-SP08

IANS-SP09

IANS-SP10

IANS-SP11

IANS-SP12

IANS-SP13

IANS-SP14

IANS-SP15

IANS-SP16

IANS-SP17

IANS-SP18

IANS-SP19

IANS-SP20

IANS-SP21

IANS-SP22

IANS-SP23

IANS-SP24

IANS-SP25

IANS-SP26

IANS-SP27

IANS-SP28

IANS-SP29

IANS-SP30

IANS-SP31

IANS-SP32

IANS-SP33

IANS-SP34

IANS-SP35

IANS-SP36

IANS-SP37

IANS-SP38

IANS-SP39

IANS-SP40

IANS-SP41

IANS-SP42

With Motor, APR, UVT Trip

With Motor, APR, UVT Trip

With Motor, APR, UVT Trip

With Motor, APR, UVT Trip

With Motor, APR, UVT Trip

With Motor, APR, UVT Trip

With Motor, APR, UVT Trip

With Motor, APR, UVT Trip

With Motor, APR, UVT Trip

With Motor, APR, UVT Trip

With Motor, APR, UVT Trip

With Motor, APR, UVT Trip

With Motor, APR, UVT Trip

With Motor, APR, UVT Trip

With Motor, APR, UVT Trip

With Motor, APR, UVT Trip

With Motor, APR, UVT Trip

With Motor, APR, UVT Trip

With Motor, APR, SHT Trip

With Motor, APR, SHT Trip

With Motor, APR, SHT Trip

With Motor, APR, SHT Trip

With Motor, APR, SHT Trip

With Motor, APR, SHT Trip

With Motor, APR, SHT Trip

With Motor, APR, SHT Trip

With Motor, APR, SHT Trip

With Motor, APR, SHT Trip

With Motor, APR, SHT Trip

With Motor, APR, SHT Trip

With Motor, APR, SHT Trip

With Motor, APR, SHT Trip

With Motor, APR, SHT Trip

With Motor, APR, SHT Trip

With Motor, APR, SHT Trip

With Motor, APR, SHT Trip

With Motor, APR, UVT Trip

With Motor, APR, UVT Trip

With Motor, APR, UVT Trip

With Motor, APR, UVT Trip

With Motor, APR, UVT Trip

With Motor, APR, UVT Trip

52 | HiAN & HiAS Type

Air Circuit BreakerHiAN Type

Page 53: Air Circuit Breaker - HUỲNH LAI · PDF fileAir Circuit Breaker HiAN 630 ~ 1600AF ... Easy maintenance and inspection mechanism ... Type HiAN 08 HiAN 12 HiAN 16 HiAN 20 HiAN 25 HiAN

ACB Operation Environment

The standard environment for ACBs is as follows:

Ambient Temperature

-5 to +40

The average temperature for 24hours must not exceed 35

Relative Humidity

45% to 85%

Attitude

Below 2000m (6,600 feet)

Atmosphere

Excessive water vapor, oil vapor, smoke, dust or corrosive gases must not exist.

Sudden change in temperature, condensation, or icing must not occur.

Transportation Conditions

Never enter the area under the air circuit breaker when it is lifted or suspended using a lifter

or chain block.

The air circuit breaker may suddenly drop.

Installation Conditions

When installing the HiAN series air circuit breaker, refer to the installation instructions in the

catalogue and instruction manual.

IP Protection

Standard : IP20

A door flange can be used as a decoration panel that covers the cutout on the switchboard

panel, and provides IP20 protection.

With rubber shield : IP31

For IP31 protection please specify the door flange with a gasket.

Storage

Store the breaker in a dry indoor location to prevent condensation due to a sudden change in

temperature, which is quite harmful to the breaker insulation.

Store the breaker in a clean place free of corrosive gases, dirt and dust.

This catalog is subject to be up-dated without notice.

This catalog shall be applied to only HiAN type Air Circuit Breaker.

Please contact the representative of Hyundai Heavy Industries for further information.

Safety Notice

HiAN Air Circuit Breaker | 53

HiAN Type

Page 54: Air Circuit Breaker - HUỲNH LAI · PDF fileAir Circuit Breaker HiAN 630 ~ 1600AF ... Easy maintenance and inspection mechanism ... Type HiAN 08 HiAN 12 HiAN 16 HiAN 20 HiAN 25 HiAN

Air Circuit Breaker

54 | HiAN & HiAS Type

SafetyConvenience

SmallLight Weight

Economical

Page 55: Air Circuit Breaker - HUỲNH LAI · PDF fileAir Circuit Breaker HiAN 630 ~ 1600AF ... Easy maintenance and inspection mechanism ... Type HiAN 08 HiAN 12 HiAN 16 HiAN 20 HiAN 25 HiAN

[ Basic Standard ]

IEC 60947-2 International Electrotechnical Commission

EN 60947-2 European Standard

AS 3972-2 Australian Standard

NEMA PUB NO. SG3 National Electrical Manufactures Association

VDE 0660 Verband Deutscher Elektrotechniker

[ Authorization ]

KER/KOREA Korea Electrotechnology Research Institute

Economical Alterations for HiAS Type ACBIn spite of HiAS Type ACB’s excellant characteristics,general users want to have simple optioned, butmaintaining main funtioned ACB.

These caused from the fact that HiAS Type ACB isdesigned and manufactured to cover all kinds of optionaland special requirements.

For the fulfillment of these kinds of customer’srequirements, we prepared economical conversion withthe following alterations.

HiAS Air Circuit Breaker | 55

HiAS Type

Page 56: Air Circuit Breaker - HUỲNH LAI · PDF fileAir Circuit Breaker HiAN 630 ~ 1600AF ... Easy maintenance and inspection mechanism ... Type HiAN 08 HiAN 12 HiAN 16 HiAN 20 HiAN 25 HiAN

Feature

56 | HiAN & HiAS Type

Air Circuit BreakerHiAS Type

Front View Designed for the HiAS ACB

➊ Front cover

➋ Charging handle

➌ Position lock device

➍ Close button

➎ Trip button

➏ Charged / Discharged

indicator

➐ Close and open indicator

➑ Cycle counter option

➒ Control circuit

➓ Protection Relay

Name plate

Key lock device option

Fixing blocks option

Page 57: Air Circuit Breaker - HUỲNH LAI · PDF fileAir Circuit Breaker HiAN 630 ~ 1600AF ... Easy maintenance and inspection mechanism ... Type HiAN 08 HiAN 12 HiAN 16 HiAN 20 HiAN 25 HiAN

Rating

Ratings for Industrial Plant Applications

Type HiAS 32HiAS 25HiAS 20HiAS 16HiAS 12HiAS 10HiAS 08HiAS 06

HiAN 32HiAN 25HiAN 20HiAN 16HiAN 12HiAN 10HiAN 08630 800 1000 1250 1600 2000 2500 3200

630 800 1000 1250 1600 2000 2500 3200

3, 4 Poles

320 320 320 320 320 2000 2000 2000

630 630 630 630 630 2500 2500

800 800 800 800 3200

1000 1000 1000

1250 1250

1600

AC 1000 V

AC 690 V

42 42 42 42 42 50 50 50

50 50 50 50 50 65 65 65

50 50 50 50 50 65 65 65

42 42 42 42 42 50 50 50

50 50 50 50 50 65 65 65

88.2 88.2 88.2 88.2 88.2 105 105 105

110 110 110 110 110 143 143 143

110 110 110 110 110 143 143 143

88.2 88.2 88.2 88.2 88.2 105 105 105

110 110 110 110 110 143 143 143

8

42 42 42 42 42 50 50 50

42 42 42 42 42 50 50 50

B

0.03

10

0.04

43 43 43 49 49 60 63 65

65 65 65 72 72 87 92 96

51 51 51 58 58 69 76 83

76 76 76 85 85 100 110 120

490

320 410

461.2

※ Value is open air at 40

IEC

VDE

BS

AS

IEC

VDE

BS

AS

ClosingOperatingTime

Weight(kg)

1 sec

with Inst.

Icu=100 % lcs

with Inst.

Icu=100 % lcs

without Inst.

(MCR)

without Inst.

(MCR)

Rated Current (A)

Neutral Phase Current (A)

Poles

Rated Primary Current of OCR [ICT] (A)

Rated Insulation Voltage (Ui) (V)

Rated Operation Voltage (Ue) (V)

Rated Breaking Capacity (kA sym) [lcu]

AC 690 V

AC 500 V

AC 415 V below

AC 600 V

AC 500 V below

Rated Making Capacity (kA peak) [lcm]

AC 690 V

AC 500 V

AC 415 V below

AC 600 V

AC 500 V below

Rated Impulse Withstand Voltage. (Uimp) [kV]

Rated Short-time Withstand

Current [lcw] (rms)

Rated Latching Current (kA)

Utilisation Category

Total Breaking Time (sec)

Charging Time (sec) max.

Closing Time (sec) max.

3 Poles, Fixed Type

3 Poles, Draw-out Type

4 Poles, Fixed Type

4 Poles, Draw-out Type

Dimension (mm) H

(3 Poles, Draw-out Type) W

D

HiAS Air Circuit Breaker | 57

HiAS Type

Page 58: Air Circuit Breaker - HUỲNH LAI · PDF fileAir Circuit Breaker HiAN 630 ~ 1600AF ... Easy maintenance and inspection mechanism ... Type HiAN 08 HiAN 12 HiAN 16 HiAN 20 HiAN 25 HiAN

A wide choice of specifications to suit your particular application

“HiAS ACB” classified into eight categories.

We are sure that our custom-built specification of “HiAS ACB” will contribute to your system design.

Selection of Specification

58 | HiAN & HiAS Type

Air Circuit BreakerHiAS Type

Page 59: Air Circuit Breaker - HUỲNH LAI · PDF fileAir Circuit Breaker HiAN 630 ~ 1600AF ... Easy maintenance and inspection mechanism ... Type HiAN 08 HiAN 12 HiAN 16 HiAN 20 HiAN 25 HiAN

Type of Mounting

Draw-out TypeThis type of ACB consists of a breaker body and a draw-out cradle. The breaker body can be moved within or removed

from the draw-out cradle that is fixed in the switchboard. There are four breaker body positions: CONNECTED, TEST,

ISOLATED, and Removed. The switchboard panel door can be kept closed the CONNECTED, TEST, and ISOLATED positions

(“shut-in three positions”)

TEST positionThe main circuit is isolated and the controlcircuits are connected. This positionpermits operation tests without the needfor opening the switchboard panel door.

ISOLATED positionBoth the main and control circuits aredisconnected. The switchboard panel door does notneed to be opened.

CONNECTED positionBoth the main and control circuits areconnected for normal service.

Fixed TypeThis type of ACB has no draw-out cradle and is designed to be directly mounted in the switchboard.

Control Circuit TerminalsControl circuit terminals are front located to allow easy wiring/access.

Connection MethodsMain circuit terminals

Two types of main circuit terminal arrangements are available: vertical terminals, horizontal terminals.

Different types of terminal arrangements can be specified for the line and load sides. Unless otherwise specified by

the user, horizontal terminals are given to all types.

Horizontal terminals

ex) HiAS 12, 16

Vertical terminals

ex) HiAS 12, 16

HiAS Air Circuit Breaker | 59

HiAS Type

Page 60: Air Circuit Breaker - HUỲNH LAI · PDF fileAir Circuit Breaker HiAN 630 ~ 1600AF ... Easy maintenance and inspection mechanism ... Type HiAN 08 HiAN 12 HiAN 16 HiAN 20 HiAN 25 HiAN

Outline Dimension

P : Front PNL Center LineC

Horizontal Bus-bar Type | HiAS 06~32

Panel Cut-out

Panel Cut-out

Draw-out Type

Fixed Type

60 | HiAN & HiAS Type

Air Circuit BreakerHiAS Type

Page 61: Air Circuit Breaker - HUỲNH LAI · PDF fileAir Circuit Breaker HiAN 630 ~ 1600AF ... Easy maintenance and inspection mechanism ... Type HiAN 08 HiAN 12 HiAN 16 HiAN 20 HiAN 25 HiAN

45

55

55

80

80

80

HiAS 06~

HiAS 10

HiAS 12

HiAS 16

HiAS 20

HiAS 25

HiAS 32

Dimension(mm)

Type A

Draw-out Fixed Draw-out Fixed Draw-out Fixed

B CD E F G H I J K L M N O T V W X Y Z

60

60

60

80

80

80

30

30

30

50

60

60

30

30

30

50

50

50

15

15

15

15

20

20

15

15

15

15

15

15

12.5

12.5

12.5

12.5

12.5

12.5

90

90

90

120

120

120

105

105

105

150

150

150

105

105

105

150

150

150

160

160

160

205

205

205

167.3

167.3

167.3

212.3

212.3

212.3

167.3

167.3

167.3

209.3

209.3

209.3

154.3

154.3

154.3

199.3

199.3

199.3

154.3

154.3

154.3

199.3

199.3

199.3

168.5

168.5

168.5

213.5

213.5

213.5

168.5

168.5

168.5

213.5

213.5

213.5

8

8

15

15

22

30

204

204

204

249

249

249

204

204

204

249

249

249

216

216

216

261

261

261

216

216

216

261

261

261

277.8

277.8

277.8

367.8

367.8

367.8

3 Pole

45

55

55

80

80

80

Dimension(mm)

Type A

Draw-out Fixed Draw-out Fixed Draw-out Fixed

B CD E F G H I J K L M N O T V W X Y Z

60

60

60

80

80

80

30

30

30

50

60

60

30

30

30

50

50

50

15

15

15

15

20

20

15

15

15

15

15

15

12.5

12.5

12.5

12.5

12.5

12.5

90

90

90

120

120

120

105

105

105

150

150

150

195

195

195

270

270

270

160

160

160

205

205

205

250

250

250

325

325

325

167.3

167.3

167.3

212.3

212.3

212.3

257.3

257.3

257.3

332.3

332.3

332.3

154.3

154.3

154.3

199.3

199.3

199.3

168.5

168.5

168.5

213.5

213.5

213.5

258.5

258.5

258.5

333.5

333.5

333.5

204

204

204

249

249

249

294

294

294

369

369

369

216

216

216

261

261

261

306

306

306

381

381

381

367.8

367.8

367.8

487.8

487.8

487.8

4 Pole

HiAS 06~

HiAS 10

HiAS 12

HiAS 16

HiAS 20

HiAS 25

HiAS 32

160

160

160

205

205

205

244.3

244.3

244.3

319.3

319.3

319.3

8

8

15

15

22

30

HiAS Air Circuit Breaker | 61

HiAS Type

Page 62: Air Circuit Breaker - HUỲNH LAI · PDF fileAir Circuit Breaker HiAN 630 ~ 1600AF ... Easy maintenance and inspection mechanism ... Type HiAN 08 HiAN 12 HiAN 16 HiAN 20 HiAN 25 HiAN

Outline Dimension

P : Front PNL Center LineC

Vertical Bus-bar Type | HiAN 06~32

Panel Cut-out

Draw-out Type

Fixed Type

62 | HiAN & HiAS Type

Air Circuit BreakerHiAS Type

Page 63: Air Circuit Breaker - HUỲNH LAI · PDF fileAir Circuit Breaker HiAN 630 ~ 1600AF ... Easy maintenance and inspection mechanism ... Type HiAN 08 HiAN 12 HiAN 16 HiAN 20 HiAN 25 HiAN

105

105

150

150

150

HiAS 06~

HiAS 10

HiAS 12~

HiAS 16

HiAS 20

HiAS 25

HiAS 32

Dimension(mm)

TypeF G H I J K V W X Y Z a b c’ d e f g h i j m n r

105

105

150

150

150

160

160

205

205

205

160

160

205

205

205

167.3

167.3

212.3

212.3

212.3

167.3

167.3

212.3

212.3

212.3

204

204

249

249

249

204

204

249

249

249

216

216

261

261

261

216

216

261

261

261

277.8

277.8

367.8

367.8

367.8

90

90

120

120

120

45

55

80

80

80

160.75

157.25

157.25

153.75

149.75

8

15

15

22

30

130.75

127.25

117.35

103.75

99.75

60

60

80

100

100

108

115

115

122

130

8

15

15

22

30

45

35

40

40

40

12

12

18

18

18

30

30

50

60

60

92.5

92.5

102.2

108.3

108.3

35.5

35.5

35.5

35

40

3 Pole

105

105

150

150

150

HiAS 06~

HiAS 10

HiAS 12~

HiAS 16

HiAS 20

HiAS 25

HiAS 32

Dimension(mm)

TypeF G H I J K V W X Y Z a b c’ d e f g h i j m n r

195

195

270

270

270

160

160

205

205

205

250

250

325

325

325

167.3

167.3

212.3

212.3

212.3

257.3

257.3

332.3

332.3

332.3

204

204

249

249

249

294

294

369

369

369

216

216

261

261

261

306

306

381

381

381

277.8

277.8

367.8

367.8

367.8

90

90

120

120

120

45

55

80

80

80

160.75

157.25

157.25

153.75

149.75

8

15

15

22

30

130.75

127.25

117.25

103.75

99.75

60

60

80

100

100

108

115

115

122

130

8

15

15

22

30

45

35

40

40

40

16

16

24

24

24

30

30

50

60

60

92.2

92.2

102.2

108.3

108.3

4 Pole

35.5

35.5

35.5

35

40

HiAS Air Circuit Breaker | 63

HiAS Type

Page 64: Air Circuit Breaker - HUỲNH LAI · PDF fileAir Circuit Breaker HiAN 630 ~ 1600AF ... Easy maintenance and inspection mechanism ... Type HiAN 08 HiAN 12 HiAN 16 HiAN 20 HiAN 25 HiAN

Circuit Diagram

Over-current Protective Device

Main CircuitCT: Current Transformer for APR

19 20

22 23 AL AS AI AG

Control Power Terminal (CP/I) Type(APR-1L-AM/GM Type)

17 APR Indication Terminal

Under Voltage Trip (UVT)

U1 U2 Control Power Terminal

T1 T2 Remote Trip Terminal

Motor Charging/Closing Circuits

1 2 Charging Power Terminal

Auxiliary Switch

31~42 Auxiliary Switch Terminal

Spring Charge Switch

15~16 Spring Chage Switch

3 4 Closing Power Terminal

Indication Terminal

M Charging Motor

Shunt Trip (SHT)

7 8 Control Power Terminal

AUX. SW. Auxiliary Switch

SHT Shunt Trip Terminal

LRC Latch Release Coil (Close)

UVT Under Voltage Trip

Condenser Trip

U V Condenser Trip Power Terminal

P N Condenser Remote Trip Terminal

64 | HiAN & HiAS Type

Air Circuit BreakerHiAS Type

Page 65: Air Circuit Breaker - HUỲNH LAI · PDF fileAir Circuit Breaker HiAN 630 ~ 1600AF ... Easy maintenance and inspection mechanism ... Type HiAN 08 HiAN 12 HiAN 16 HiAN 20 HiAN 25 HiAN

Control Circuit Lay-out IU Type APR Circuit APR-1L-AM, GM Circuit

*1 : Attach at rated voltage DC 125 V Manufacturer wiring part User wiring part Disconnecting device

HiAS Air Circuit Breaker | 65

HiAS Type

< Control Circuit >

< Aux. Contact >

Page 66: Air Circuit Breaker - HUỲNH LAI · PDF fileAir Circuit Breaker HiAN 630 ~ 1600AF ... Easy maintenance and inspection mechanism ... Type HiAN 08 HiAN 12 HiAN 16 HiAN 20 HiAN 25 HiAN

Ordering Information

HiAN type ACBs have an extensive range of available accessories, enabling the circuit breaker to be custom-built to suit everyapplication. When ordering HiAN ACBs, please give us a complete order No. nomenclature as shown in following tables.

Order No. nomenclature

The 6th Order No. Suffix (Other accessories)

The 5th Order No. Suffix (Rating of CT)

The 4th Order No. Suffix (Kind of trip release)

The 3th Order No. Suffix (Over-current release)

The 2th Order No. Suffix (Charging mechanism)

The 1th Order No. Suffix (Breaker poles and mounting method)

The Basic Order No. (Breaker type)

NO.

Frame

IAS06 IAS08 IAS10 IAS12 IAS16 IAS20 IAS25 IAS32

630 A 800 A 1000 A 1250 A 1600 A 2000 A 2500 A 3200 A

PolesMounting

3 Poles

4 Poles

Fixed Type Draw-out Type Remark

3F

4F

3D

4D

NO.

H0

M1

M2

Description Description

Manual Charge

Motor Charge/AC110 V

Motor Charge/AC220 V

Motor Charge/DC110 V

Motor Charge/DC220 V

Motor Charge/DC24 V

NO.

General Protection

00

20

22

23

27

Function APR Type

Without APR

AL-AS-AI-IU

AL-AS-AI-AP-IU/CP/I, AC, DC

AL-AS-AI-AG-IU

AL-AS-AI-AP-AG-IU/CP/I, AC, DC

-

APR-1L-AL

APR-1L-AM

APR-1L-GL

APR-1L-GM

The basic order NO. (Breaker frame)

The 1st order NO. (Poles and mounting method)

The 2nd order NO. (Charging mechanism description)

The 3rd order NO. (ACB protection relay)

M5

M6

M7

NO. DescriptionMotor Charge/DC48 V

Motor Charge/DC125 V

M8

M9

NO.

NO.

General Protection

00

28

Function APR Type

Without APR

AL-AS-AI-IU

-

APR-1S-AL

66 | HiAN & HiAS Type

Air Circuit BreakerHiAS Type

Page 67: Air Circuit Breaker - HUỲNH LAI · PDF fileAir Circuit Breaker HiAN 630 ~ 1600AF ... Easy maintenance and inspection mechanism ... Type HiAN 08 HiAN 12 HiAN 16 HiAN 20 HiAN 25 HiAN

NO.

X5

X6

W1

W2

W3

W4

W5

W6

W7

C1

C2

Description NO. Description Description Description

UVT(Delay)/AC430~470 V

UVT(Delay)/AC480~500 V

UVT(INST)/AC100 V

UVT(INST)/AC220 V

UVT(INST)/AC380 V

UVT(INST)/AC440 V

UVT(INST)/DC100 V

UVT(INST)/DC200 V

S1+T1

S2+T2

S3+T3

T4

T5

U1

U2

U3

U4

U5

U6

D1

D2

D3

NO. NO.

D4

I1

I2

I3

I4

I5

I6

X1

X2

X3

X4

V

T

H

J

320 A

630 A

800 A

1000 A

IAN06~IAN16

IAN06~IAN16

IAN08~IAN16

IAN10~IAN16

The 4th order NO. (Kind of trip release)

The 5th order NO. (Rated primary current of CT)

S1

S2

S3

S4

S5

S6

S7

S8

T1

T2

T3

SHUNT/AC100~150 V

SHUNT/AC180~250 V

SHUNT/AC380~420 V

SHUNT/AC421~480 V

SHUNT/DC90~125 V

SHUNT/DC150~230 V

SHUNT/DC24 V

SHUNT/DC48 V

UVT(Delay)/AC100~120 V

UVT(Delay)/AC200~240 V

UVT(Delay)/AC360~400 V

K

L

M

N

P

Zero

1250 A

1600 A

2000 A

2500 A

3200 A

None (Over current release ordering NO. “00”)

IAN12~IAN16

IAN16

IAN20~IAN32

IAN25~IAN32

IAN32

NO. Description Type NO. NO.Description DescriptionType Type

The 6th order NO. (Other accessories)

NO.

B

D

E

F

G

H

L

M

N

Q

R

S

W

X

Z

8

Acc’y Name NO. NO.Acc’y Name Acc’y Name

Key Lock (Lock In Open)

Cycle Counter

Safety Shutter

Fixing Block

Door Flange

Vertical Type Mount’g Bus-bar

Lifting & Hook

Button Cover & Key

Neutral CT

Position Switch (Conn: 1C, Test: 1C)

Position Switch (Conn: 2C)

Position Switch (Test: 2C)

Wrong Insert’n Prevent’n Device

Arc Shield

APR Checker (IANS-HOC5)

MCR (Making Current Release)

When ordering more than one kind of accessory, please list order NO. according to the order of alphabet and Arabia numbers.

S4+T4

S1+U1

S2+U2

S3+U3

S4+U4

S5+U5

S6+U6

S5+T3

S1+T3

S7+T4

S7+T2

S6+T2

S6+T3

S1+T2

S1+T4

S2+T4

S5+T1

S5+T2

S5+T4

S5+T5

CTD/AC110 V

CTD/AC220 V

Specification Order Number

Setting values of over-current release

Other Accessories:Key lock in open position, safety shutter

Rated Primary Current of CT: 1250 A / 0.2 A

Kind of Trip: Shunt Trip / DC 100 V

Over-Current Release: for generalFeeder circuit, AL-AS-AI-IU

3 Pole, Draw-out Type

Motor-Charging / DC 100 V

Amperes Frame: 1250 ARated Breaking Capacity: AC500 V / 70 kA

Example

K

Base current (lo) 1250 APick-up Current [l1] 1250 A Time-delay [l1] 15 s

IAS12

IAS12 3 D

IAS12 3 D M 5

IAS12 3 D M 5 2 0

IAS12 3 D M 5 2 0 S 5

IAS12 3 D M 5 2 0 S 5

IAS12

AL

Pick-up Current [l2] 7500 A Time-delay [l2] 240 sAS

Pick-up Current [l3] 12500 AAI

3 D M 5 2 0 S 5 K EB

HiAS Air Circuit Breaker | 67

HiAS Type

Page 68: Air Circuit Breaker - HUỲNH LAI · PDF fileAir Circuit Breaker HiAN 630 ~ 1600AF ... Easy maintenance and inspection mechanism ... Type HiAN 08 HiAN 12 HiAN 16 HiAN 20 HiAN 25 HiAN

HH

IS-W

C-LE

-B42-01, 2007.3 D

esigned by Design K

orea

www.hyundai-elec.com

Head Office 1 Jeonha-dong, Dong-gu, Ulsan, Korea Tel. 82-52-202-8101~8 Fax. 82-52-202-8100

Seoul 140-2, Gye-dong, Jongno-gu, Seoul, Korea(Sales & Marketing) Tel. 82-2-746-7510, 7589 Fax. 82-2-746-7648

Orlando 3452 Lake Lynda Drive, Suite 170, Orlando, Florida 32817, U.S.A. Tel. 1-407-249-7350 Fax.1-407-275-4940

London 2nd Floor, The Triangle, 5-17 Hammersmith Grove London, W6 0LG, UKTel. 44-20-8741-0501 Fax. 44-20-8741-5620

Tokyo 8th Fl., Yurakucho Denki Bldg.1-7-1, Yuraku-cho, Chiyoda-gu, Tokyo 100-0006, JapanTel. 81-3-3212-2076, 3215-7159 Fax. 81-3-3211-2093

Cairo Apartment No. 503, 5th Fl., Bldg. No. 7 Block 2, 9th Division, El-nasr Road, New Maadi, Cairo, EgyptTel. 20-2-520-0148~9 Fax. 20-2-754-7528

Sofia 1271, Sofia 41, Rojen Blvd. BulgariaTel. 359-2-803-3200 Fax. 359-2-803-3203

Yangzhong Lianzhong Avenue, Xinba Scientific and Technologic Zone, Yangzhong City, Jiangsu 212212, ChinaTel. 86-511-842-0666, 0500 Fax. 86-511-842-0668, 0231

※Recyled paper used for environmental protection.