48
Instruction Manual Models 7EF and 7HF Controllers 1262-IN-011-0-02 December 1997 DG

Barber Colman 7EF

Embed Size (px)

Citation preview

Page 1: Barber Colman 7EF

Instruction Manual

Models 7EF and 7HFControllers

1262-IN-011-0-02December 1997

DG

Page 2: Barber Colman 7EF

2

1/8 DIN, Four Digit DisplayTemperature Controller

MODEL: 0 7 - 9 3 1 1 - 3 0 0 - 0 - 0 0Field No. 1 2 3 4 5 6 7 8 9 10 11 12 13 1415

Fields 1 through 4. BASE07EF - Vertical Mount Controller07HF - Horizontal Mount Controller

Fields 5 through 8. INPUT/OUTPUT9311 - TC types J, K, L, N, R and S;

Pt 100, 3 wire RTD;0 to 20 mAdc and 4 to 20 mAdc;0 to 60 mVdc and 12 to 60 mVdc;0 to 5 Vdc and 1 to 5 Vdc;0 to 10 Vdc and 2 to 10 Vdc.

Note: All inputs are factory calibrated andselectable by keys. Factory set at type J.Output 1: SPST relay (NO/NC jumper

selectable) or SSROutput 2: SPST relayOutput 3:SPST relay alarm 2/hbd (heater

breakdown) if specified

Field 9. OPTIONS1 - None2 - Hbd alarm, plus output 4 (alarm 3)3 - RS-485, plus output 4 (alarm 3)4 - RS-485, plus hbd alarm, plus output 4

(alarm 3)Note: Hbd current transformer must be orderedseparately.

Field 10. POWER SUPPLY3 - 100 to 240 Vac

Fields 11 through 15. RESERVED

Page 3: Barber Colman 7EF

3

Congratulations

. . . on your purchase of one of the easiest toconfigure controllers on the market. After a fourstep configuration procedure, your process willbe up and running.

Guide to simple setup

Only four steps are required to setup yourcontroller:1. Wire the instrument2. Configure the instrument3. Check the operating mode parameters4. Check the AutoTune (Smart AT) process

Un p ac k t he In st ru m e nt

W iring

C o nf ig u ra tio n

O p erating Pa ra m et ers

Au to tu ning

S V

Page 4: Barber Colman 7EF

4

CAUTION:USE WIRE SUITABLEFOR 75°C MINIMUM.

NOTES

• For supply connections use No 16 AWG orlarger wires rated for at least 75 °C.

• Use copper conductors only.• Class 2 wiring must be separated a

minimum of 1/4 inch from any Class 1conductors.

Contents

Guide to simple setup ..................................3Mounting Requirements ............................... 5Wiring Guidelines.......................................... 7Configuration .............................................. 14

Preliminary Hardware Settings ..... 14Configuration Key Functions ........ 15Configuration Procedure .............. 15Advanced Configuration Procedure20Default Configuration Parameters 22

Operating Mode..........................................24Display Function .......................... 24Indicators ..................................... 24Operating Key Functions ............. 25Output 1 Failure Detection ........... 26Manual Function........................... 26Setpoint Access ........................... 26Serial Link ..................................... 27Lamp Test ..................................... 27Operating Parameters .................. 28Error Messages ............................ 30Default Operating Parameters ...... 32

Specifications ............................................. 33Calibration .................................................. 38

General Guidelines ....................... 38Calibration Parameters ................ 38Procedure ..................................... 39

Maintenance ...............................................45

Page 5: Barber Colman 7EF

5

Mounting Requirements

Select a mounting location with the followingcharacteristics:1) Minimum vibrations.2) An ambient temperature range between 0

and 50 °C (32 and 122°F).3) Easy access to the rear of the instrument.4) No corrosive gases (sulfuric gas, ammo-

nia, etc.).5) No water or other fluid (i.e. condensation).6) Relative humidity of 20 to 80% non-

condensing.

The instrument can be mounted on a panel upto 15 mm (0.591 in) thick with a cutout of 45 x92 mm (1.772 x 3.622 in). For outline refer toDimensions and Panel Cutout.

Panel surface texture must be better than 248microinches

The instrument is shipped with a rubber panelgasket (50 to 60 Sh). To assure the IP65 andNEMA 4X protection, insert the panel gasket be-tween the instrument and the panel as shownbelow.

Install the instrument as follows:

1) Insert the instrument case in the gasket.2) Insert the instrument in the panel cutout.3) Pushing the instrument against the panel,

insert the mounting bracket.4) Torque the mounting bracket screws

between 0.3 and 0.4 Nm (2.2 and 2.7 lbft).5) Make sure the instrument will not move

within the cutout to insure NEMA 4X/IP65protection.

B ra c k e t

P a nel

G a sk et

Page 6: Barber Colman 7EF

6

Dimensions and Panel Cutout

11 6 m m 4 .5 67 in

60 m m 2.36 2 in

12 5 m m 4.92 1 in

4 5 m m , - 0, +0.6 m m 1 .77 2 in, - 0, +0.0 24 in

9 2 m m , -0 , +0 .8 m m 3 .62 2 in , -0 , +0 .03 1 in

4 8 m m 1 .8 90 in

96 m m 3.78 0 in

1 0 m m (0.39 4 in )

6 0 m m 2 .3 6 2 in

1 25 m m 4 .9 21 in

4 5 m m , -0, +0 .6 m m 1 .7 72 in , -0, +0 .02 4 in

9 2 m m , - 0, +0.8 m m 3 .62 2 in, - 0, +0.0 31 in

48 m m 1 .8 90 in

9 6 m m 3 .7 8 0 in

Mo d el 7EF

M od e l 7H F

Page 7: Barber Colman 7EF

7

Wiring Guidelines

Note: When a relay output is used to drive aninductive load, connect an external snubber net-work (RC) across the terminals:

CR

in accordance with the following table:

Load C R P Resistor andCurrent (µF) (W) (W) Capacitor Voltage<40 mA 0.047 100 1/2 260 Vac<150 mA 0.1 22 2 260 Vac<0.5 Amp 0.33 47 2 260 Vac< 1 Amp 0.47 47 2 260 Vac

7EF Terminal Board

7EH Terminal Board

1 0 0 / 2 40 Va c PW R L IN E

12

13

15

14S SR

OU T 1

IN - C T

SP/ SP 2

16

17

18

19

21

22 11

10

9

8

7

6

5

4

3

TC

1

20

C O UT 3 & 4

N O OU T 4

N O OU T 3

N O

N O

L IN EA R IN P UT S

RTD

OU T 2

OU T 1

R S 48 5

C

C

A /A ’

B /B ’

C /C ’

100/240Vac PW

R LINE

121315 14S

SR

OU

T 1

IN - C

T

SP/SP2

161718

1921

2211 10 9 8 7 6 5 4 3

TC

1

20

C O

UT 3 & 4

NO

OU

T 4

NO

OU

T 3

NO

NO

LINEA

R

INP

UTS

RT D

OU

T2

OU

T1

RS

485

CC

A/A

B/B

C/C

Page 8: Barber Colman 7EF

8

Measuring Inputs

Any external components (like zener diodes,etc.) connected between the sensor and inputterminals may cause measurement errors (ex-cessive or unbalanced line resistance or pos-sible leakage currents).

T/C input

S hie ld

S hie ld

1

3

1

3

+

-

+

-

Note:1) Do not run input wires with power cables.2) For TC wiring use proper compensating

cable, preferably shielded (see Thermo-couple Compensating Cable ColorCodes).

3) Shielded cable should be grounded at oneend only.

Linear Input

1

3

m A , m V o r V

Sh ie ld

-

+

1

3

m A , m V o r V

Sh ie ld

-

G

+

Note:1) Do not run input wires with power cables.2) High line resistance can cause measure-

ment errors.3) When shielded cable is used, ground it at

one end only to avoid ground loopcurrents.

4) The input impedance is equal to:Less than 5 Ω for 20 mA input;Greater than 1 MΩ for 60 mV input;Greater than 200 kΩ for 5 V input;Greater than 400 kΩ for 10 V input.

Page 9: Barber Colman 7EF

9

Thermocouple Compensating Cable Color CodesBritish American German French

Type Material Leg BS1843 ANSI MC 96.1 DIN 43710 NFE 18-001T Copper + White Blue Red Yellow

Constantan - Blue Red Brown BlueBlue Blue Brown Blue

J/L Iron + Yellow White Red YellowConstantan - Blue Red Blue Black

Black Black Blue BlackK Nickel Chromium + Brown Yellow Red Yellow

Nickel Aluminum - Blue Red Green PurpleRed Yellow Green Yellow

R Platinum + White Black Red WhitePlatinum 13% Rh - Blue Red White Green

Green Green White GreenS Platinum + White Black Red White

Platinum 10% Rh - Blue Red White GreenGreen Green White Green

E Chromel + Brown Violet Red YellowConstantan - Blue Red Black Violet

Brown Violet Black VioletB Platinum 30% Rh/ + Grey Red

Platinum 6% Rh - Red GreyGrey Grey

N Nicrosil + Orange Orange Orange OrangeNisil - Red Red Red Red

Orange Orange Orange Orange

RTD Input

4 3

R T D

1 4 3

R T D

1

Note: Do not run RTD wires with power cables.Shielded cable should be grounded at one endonly. Use the correct size copper wires. Theresistance of the three wires must be the same.

Page 10: Barber Colman 7EF

10

Current Transformer Input

This input will measure and display the currentrunning in the load, driven by OUT 1, during theon and off period of the OUT 1 cycle time. OUT1 failure detection is also available.

5

6 C u rren t Tr ans fo rm er

L oa d

Safety Note:• Do not run current transformer input

wiring with AC power cables.Note:• Input impedance is equal to 10Ω.• Maximum input current is equal to 50 mA

(50/60 Hz).• The minimum time to perform this

measurement 400 msec.

Logic Input

7

8

L o g ic In pu t

Safety Note:• Do not run logic input wiring with AC

power cables.• Use external dry contact capable of

switching 0.5 mA, 5 Vdc.• The instrument requires at least 100 msec

to recognize a change in contact status• Logic input is not isolated by the measur-

ing input.

This input selects between SP and SP2 as theoperating setpoint. Input open = SP; inputclosed = SP2.

Page 11: Barber Colman 7EF

11

Inductive Loads

High voltage transients can occur when switch-ing inductive loads. Through the internal con-tacts these transients may introduce distur-bances which can affect instrument perfor-mance. For outputs 1 and 2, the internal pro-tection (varistor) assures protection up to 0.5Amps of inductive component.

The same problem can occur when a switch isused in series with the internal contacts asshown:

L O A D

CR

P O W E R L IN E

In this case, it is good electrical practice to in-stall and additional RC network across theexternnal contacts as shown. The value of ca-pacitor (C) and resistor (R) are shown in the fol-lowing table.Load C R P OperatingCurrent (µF) (Ω) (W) Voltage<40 mA 0.047 100 1/2 260 Vac<150 mA 0.1 22 2 260 Vac<0.5 Amp 0.33 47 2 260 Vac< 1 Amp 0.47 47 2 260 Vac

Relay output wiring must be as far away as pos-sible from input wiring and communicationscables.

Relay Outputs

1 6

1 7

1 8

N O - O ut 3

N O - O ut 4

C - O ut 3 /4

1 9

2 0 C

N O

2 1

2 2

C

N OO u t 1

O u t 2

O u t 4

O u t 3

Outputs 1 and 2 protected by varistor against induc-tive load with inductive component up to 0.5 A.Out 1: Contact rating of 3 Amps/250 Vac resistive

load.Out 2, 3, and 4: Contact rating of 2 Amps/250 Vac

resistive load.Number of operations: 1 x 105 at specified rating.

Notes:1) To avoid electric shock, connect the

power line at the end of the wiringprocedure.

2) For power connections, use number 16AWG or larger wires rated for at least75°C.

3) Use copper conductors only.4) Don't run input wires with power cables.5) Relay output and SSR drive outputs are

both available. When a relay output isdesired, it is necessary to enable the SSRoutput and vice-versa. See "PreliminaryHardware Settings."

Page 12: Barber Colman 7EF

12

Voltage Outputs for SSR Drive

This is a time proportioning output.

Logic voltage for SSR drive.Logic level 0: Vout less than 0.5 Vdc.Logic level 1: 14 Vdc +20% @ 20 mA.

24 Vdc +20% @ 1 mA.Maximum current = 20 mA.

1 4

- -

+

+

O U T 1

1 5

S olid S tate R e la y

Note: This output is not isolated. A double orreinforced isolation between the instrument out-put and the power supply must be made by anexternal solid state relay.

Relay output and SSR drive outputs are bothavailable. When a relay output is desired, it isnecessary to enable the SSR output and vice-versa. See "Preliminary Hardware Settings."

Serial Interface

The RS-485 interface can connect up to 30 in-struments with the remote master unit. Maxi-mum cable length: 1.5 km (9/10 mile) at 9600baud.

Note: According to EIA specifications for RS-485.a) The "A" terminal of the generator shall be

negative with respect to the "B" terminalfor a binary 1 (MARK or OFF) state.

b) The "A" terminal of the generator shall bepositive with respect to the "B" terminalfor a binary 0 (SPACE or ON) state.

1 1

1 0

9

A /A ’ A ’ /A

B /B ’ B’/B

C o m m o n

M A S T E R

Connect the instrument (maximum of 30) to themaster unit by interface communication typeRS-485.

1 1

1 0

9

A /A ’ A ’ /A

B /B ’ B’/B

C o m m o n

1 1

1 0

9

M A S T E R

Page 13: Barber Colman 7EF

13

Power Line Wiring

1 3

1 2

Pow e r S up ply 10 0 to 240 Va c rm s (50/60 Hz )

or 24 Va c/Vd c

N

NR (S, T )

R (S, T )Note:1) Before connecting the power line,

check that the voltage is correct(see Model Number).

2) To avoid electric shock, connect powerline at the end of the wiring procedure.

3) For supply connections use 16 AWG orlarger wires rated for at least 75 °C.

4) Use copper conductors only.5) Do not run input wires with power cables.6) For 24 Vdc, polarity does not matter.7) The power supply input is not fuse

protected. Please provide it externally:Supply Fuse Type Current Voltage24 Vac/Vdc T 500 mA 250 V100/240 Vac T 63 mA 250 VWhen fuse fails, return instrument tosupplier to verify power supply circuit.

8) Safety requirements for permanentlyconnected equipment: Include a switchor circuit-breaker in the installation. Placeit in close proximity to the equipment andwithin easy reach of the operator. Mark itas the disconnecting device for theequipment. Note: A single switch orcircuit-breaker can drive more than oneinstrument.

9) When a neutral line is present, connect itto terminal 13.

Page 14: Barber Colman 7EF

14

Open Input CircuitThis instrument is able to identify an open cir-cuit for TC and RTD inputs. The open circuitcondition for RTD input is shown by an“overrange” indication. For TC input, either anoverrange indication (standard) or an underrangeindication can be selected from the followingtable:

Overrange (std) CH2 = close SH2 = openUnderrange CH2 = open SH2 = close

Caution: Solder carefully to avoid damage toPCB or other components.

Preliminary Hardware Settings

1) Remove the instrument from its case.2) Set J1 according to the following table:

Configuration

INPUT J1

TYPE 1-2 3-4 5-6 7-8 9-10

TC-RTD open close open open open

60 mV open close open open open

5 V close open close open open

10 V open open close open open

20 mA open open open close close

Note: Store unused jumper on pins 7-9.

V1

SH2CH2

Both pads are locted on thesolder side of the CPU card

Page 15: Barber Colman 7EF

15

Selection of Output 1 TypeJ303 is used to set OUT 1 as an SSR output (1-2) or relay output (2-3). When relay output isselected, J302 is used to select the contact ac-tion as shown below N.O.=1-2; N.C. = 2-3:

Configuration Procedure

1) Remove the instrument from its case.2) Open switch V1 (see Figure 1, Preliminary

Hardware Settings).3) Re-insert the instrument in its case.4) Switch on power to the instrument.

The display will show COnF. (If CAL isdisplayed, press the s key to return tothe configuration procedure.)

5) Press the FUNC key.

SEr1 = Serial interface protocolOFF = No serial interface.Ero = Poll/select using proprietary protocol.nbUS = Modbus.jbUS = Jbus.

SEr2 = Serial link device addressNot available when SEr1 = OFF.From 1 to 95 for proprietary protocol.From 1 to 255 for all other protocols.Note: The RS-485 serial interface allows 30 de-vices maximum with a master unit.

SEr3 = Baud rate for serial linkNot available when SEr1 = OFFFrom 600 to 19200 baud.Note: 19200 baud is displayed as 19.2.

Configuration Key Functions

FUNC = The new setting of the selectedparameter is stored and the displayadvances to the next parameter.

MAN = Scrolls back through the parameterswithout storing the new setting.

s = Increases the setting of the selectedparameter.

t = Decreases the setting of the selectedparameter.

Page 16: Barber Colman 7EF

16

P1 = Input type and standard range0 = TC type L 0 to +400.0 °C1 = TC type L 0 to +900 °C2 = TC type J -100.0 to +400.0 °C3 = TC type J -100 to +1000 °C4 = TC type K -100.0 to +400.0 °C5 = TC type K -100 to +1370 °C6 = TC type N -100 to +1400 °C7 = TC type R 0 to +1760 °C8 = TC type S 0 to +1760 °C9 = RTD type Pt 100 -199.9 to +400.0 °C10 = RTD type Pt 100 -200 to +800 °C11 = mV Linear 0 to 60 mV12 = mV Linear 12 to 60 mV13 = mA Linear 0 to 20 mA14 = mA Linear 4 to 20 mA15 = V Linear 0 to 5 V16 = V Linear 1 to 5 V17 = V Linear 0 to 10 V18 = V Linear 2 to 10 V19 = TC type L 0 to +1650 °F20 = TC type J -150 to +1830 °F21 = TC type K -150 to +2500 °F22 = TC type N -150 to +2550 °F23 = TC type R 0 to +3200 °F24 = TC type S 0 to +3200 °F

25 = RTD type Pt 100 -199.9 to +400.0 °F26 = RTD type Pt 100 -330 to +1470 °F27 = TC type T -199.9 to 400.0°C28 = TC type T -330 to 750°F

Note: Setting P1 = 0, 2, 4, 9, 25 or 27 automati-cally sets P40 = FLtr. For all other ranges, in-strument will set P40 = nOFL.

P2 = Decimal point positionThis parameter is available only when a linearinput is selected (P1 = 11, 12, 13, 14, 15, 16, 17or 18).

– – – – . = No decimal.– – – . – = One decimal place.– – . – – = Two decimal places.– . – – – = Three decimal places.

P3 = Initial scale valueCan be programmed from -1999 to 4000 for lin-ear inputs, and within the input range for TCand RTD. When this parameter is modified, rLwill also change.

P4 = Full scale valueProgrammable from -1999 to 4000 for linear in-puts, and within the input range for TC and RTD.When this parameter is modified, rH will alsochange.

The initial and full scale values determine theinput span used by the PID algorithm, autotuning(Smart AT), and the alarm functions.

SEr4 = Byte format for serial linkNot available when SEr1 = OFF7E = 7 bits + even parity (proprietary

protocol only)7O = 7 bits + odd parity (proprietary

protocol only)8E = 8 bits + even parity8O = 8 bits + odd parity8 = 8 bits without parity

Page 17: Barber Colman 7EF

17

Note: Minimum input span (S = P4 - P3) shouldbe set as follows:For linear inputs, S > 100 units.For TC input with °C readout, S > 300 °C.For TC input with °F readout, S > 550 °F.For RTD input with °C readout, S > 100 °C.For RTD input with °F readout, S > 200 °F.

P5 = Output 1 typeChanging this parameter (P5) will also changethe cycle time (Cy1). Hardware change is alsorequired – see "Preliminary Hardware Settings."rEL = Relay (the cycle time will be forced to

15 seconds).SSr = SSR (the cycle time will be forced to

4 seconds).

P6 = Output 1 actionThis parameter is skipped if P7 = 4.rEV = Reverse acting (Heating).dir = Direct acting (Cooling).

Inpu

tO

utp

ut

D irect A ct ion

t

t

t

t

Inpu

tO

utp

ut

R eve rse A c tio n

P7 = Output 2 function.0 = Output not used.1= Used as Alarm 1 output and Alarm 1

is programmed as a process alarm.2 = Used as Alarm 1 output and Alarm 1

is programmed as a band alarm.3 = Used as Alarm 1 output and Alarm 1

is programmed as a deviation alarm.4 = Used as second control output

(Cooling output).Note: Setting P7 to 4 forces P6 to “rEV.”

P8 = Cooling mediaAvailable only when P7 = 4AIr = AirOIL = OilH2O = WaterChanging P8 forces the cycle time and relativecooling gain to the default settings of the se-lected cooling media.When:P8 = AIr, Cy2 = 10 seconds and rC = 1.00P8 = OIL, Cy2 = 4 seconds and rC = 0.80P8 = H2O, Cy2 = 2 seconds and rC = 0.40

P9 = Alarm 1 operating modeAvailable only when P7 = 1, 2 or 3.H.A.= High alarm (or outside of the band)

with automatic reset.L.A.= Low alarm (or inside the band) with

automatic reset.H.L.= High alarm (or outside of the band)

with manual reset.L.L.= Low alarm (or inside the band) with

manual reset.

Page 18: Barber Colman 7EF

18

P10 = Current measurement for OFD alarm(See also "Display Function" and "Out1 Failure Detection.")

OFF = Current measurement is disabled.n.O. = The current measurement will be

made during the ON period (loaddriven from a N.O. relay contact or alogic status 1 for an SSR).

n.C.= The current measurement will bemade during the OFF period (loaddriven from a N.C. relay contact or alogic status 0 for an SSR).

P11 = Current transformer rangeNot available when P10 = OFF. It can be pro-grammed from 10 to 100 Amps.

P12 = Output 3 function0 = Alarm 2 not used.1 = Used as Alarm 2 output and Alarm 2

is programmed as a process alarm.2 = Used as Alarm 2 output and Alarm 2

is programmed as a band alarm.3 = Used as Alarm 2 output and Alarm 2

is programmed as a deviation alarm.Note: output 3 relay operates as a logic OR be-tween Alarm 2 and the out 1 failure detectionfunction.

P13 = Alarm 2 operating mode and"Out 1 Failure Detection" reset.

Available only when P12 not 0, orP10 = n.O or n.CH.A. = High alarm (or outside of the band)

with automatic reset.L.A. = Low alarm (or inside the band) with

automatic reset.H.L. = High alarm (or outside of the band)

with manual reset.L.L. = Low alarm (or inside the band) with

manual reset.Note: Out 1 failure detection function assumesonly the selected reset type (manual or auto-matic).

P14 = Output 4 function0 = Output not used.1 = Used as Alarm 3 output and Alarm 3

is programmed as a process alarm.2 = Used as Alarm 3 output and Alarm 3

is programmed as a band alarm.3 = Used as Alarm 3 output and Alarm 3

is programmed as a deviation alarm.

P15 = Alarm 3 operating modeAvailable only when P14 not 0.H.A. = High alarm (or outside of the band)

with automatic reset.L.A. = Low alarm (or inside the band) with

automatic reset.H.L. = High alarm (or outside of the band)

with manual reset.L.L. = Low alarm (or inside the band) with

manual reset.

Page 19: Barber Colman 7EF

19

P16 = Alarm 3 programmabilityAvailable when P14 not• 0.OPrt = Alarm 3 setpoint and hysteresis can

be set with keys in the operatingmode.

COnF= Alarm 3 setpoint and hysteresis canbe set with keys in the configurationmode.

P17 = Alarm 3 setpointAvailable only when P14 not 0 andP16 = “COnF.”Range: For process alarm: span limits.

For band alarm: 0 to 500 units.For deviation alarm: -500 to 500units.

P18 = Alarm 3 hysteresisAvailable only when P14 not 0 andP16 = “COnF.”Range: From 0.1 to 10.0% of the span

selected with P3 and P4 parameters.

P19 = Soft start setpointSetpoint setting (in engineering units), to initiatethe “soft start” function (output power limiting)at start-up. Not used when tOL = InF.Range: Within the readout span.

P20 = Safety lock0 = No parameter protection. The

instrument is always in unlockcondition and all parameters can bemodified.

1 = The instrument is in lock condition.No parameter, except setpoint andalarm manual reset, can be modified.See P31 for Smart AT.

2 to 4999 = This combination number issecret value to be used in run time toput device in lock/unlock condition.See nnn parameter. For SP, SP2 andmanual reset of alarms, the lock/unlock condition has no affect. SeeP31 for Smart AT.

5000 to 9999 = This combination number issecret value to be used in run time toput device in lock/unlock condition.See nnn parameter. For SP, SP2 andmanual reset of AL1, AL2, AL3, HBD,and SCA, the lock/unlock conditionhas no affect. See P31 for Smart AT.

When safety lock is selected, the secret valuecannot be displayed again and the display willshow 0, 1, SFt.A when P20 = 2 to 4999; or SFT.bwhen P20 = 5000 to 9999.

The configuration procedure is now complete.The instrument should show “ –.–.–.–.“ on bothdisplays. Press the FUNC key; the instrumentwill return to the beginning of the configurationprocedure. To continue with controller setupgo to the operating mode found in the next sec-tion.

To access the advanced configuration param-eters proceed as follows:

1) Using the s or t keys, set code to 233.2) Press the FUNC key.

Page 20: Barber Colman 7EF

20

Advanced Configuration Procedure

P21 = Alarm 1 actionNot available when P7 = 0 or 4.dir = Direct (relay energized in alarm

condition).rEV = Reverse (relay de-energized in alarm

condition).

P22 = Alarm 1 standbyNot available when P7 = 0 or 4.OFF = Standby disabled.ON = Standby enabled.Note: If the alarm is a band or deviation alarm,the alarm is masked after a setpoint change orat start-up until the process variable reaches thealarm setpoint plus or minus hysteresis. If thealarm is a process alarm, the condition ismasked at start-up until the process variablereaches the alarm setpoint plus or minus hys-teresis.

P23 = Alarm 2 and Out 1 failure detectionaction

Not available when P12 =0 or P10 = “OFF.”dir = Direct (relay energized in alarm

condition).rEV = Reverse (relay de-energized in alarm

condition).

P24 = Alarm 2 standbyNot available when P12 = 0.OFF = Standby disabled.ON = Standby enabled.

P25 = Alarm 3 actionNot available when P14 = 0.dir = Direct (relay energized in alarm

condition).rEV = Reverse (relay de-energized in alarm

condition).

P26 = Alarm 3 standbyNot available when P14 = 0.OFF = Standby disabled.On = Standby enabled.

P27 = OFFSET applied to measured valueUsed to apply a constant OFFSET throughoutthe entire range (not used for linear inputs). Forreadout ranges with a decimal place, P27 canbe set with keys from -19.9 to 19.9. For rangeswithout a decimal place, P27 can be set withkeys from -199 to 199.

P28 - Not available

P29 = Protected display parametersThis parameter is skipped when P20 = 0.OFF = Protected parameters cannot be

displayed.On = Protected parameters can be

displayed.

Real curveReadout

Adjustedcurve

Input

P27

Page 21: Barber Colman 7EF

21

P36 = Minimum value of the integral timecalculated by autotuning

Not available when P31 = 0. Can be pro-grammed from one second (00.01) to two min-utes (02.00).

P37 = Status at instrument start-upThis parameter is skipped when P30 = OFF.0 = Instrument starts in the AUTO mode.1 = The instrument starts in the same

mode it was in prior to shutdown. Ifmanual, power output will be set to 0.

P38 Not available

P39 = Timeout selectionDuration of the timeout used by the instrumentduring the operating mode.tn.10 = 10 seconds.tn.30 = 30 seconds.

P40 = Digital filter on the measured valuenoFL.= No filterFLtr = Filter enabled:

A first order digital filter with a timeconstant equal to:4 seconds for TC and RTD inputs.2 seconds for linear inputs.

P41 = Conditions for output safety value0 = No safety value.1 = Safety value for overrange or

underrange condition.2 = Safety value for overrange condition.3 = Safety value for underrange condition.

P30 = MANUAL functionOFF= Manual function is disabled.On = Manual function can be enabled/

disabled by MAN key.

P31 = Autotuning (Smart AT)0= Autotuning disabled.1 = Autotuning not protected by safety lock.2 = Autotuning protected by safety lock.

P32 = Relative cooling gain calculated byautotuning

Available only if P7 = 4, and P31 not 0.OFF = Autotuning algorithm does not

calculate rC.On = Autotuning algorithm calculates rC.

P33 = Maximum value of the proportionalband calculated by autotuning

Not available if P31 = 0.Can be programmed from P34 or P35 to 100.0%.

P34 = Minimum value of the proportionalband calculated by autotuning whenthe instrument has two controloutputs

This parameter is available only when P7 = 4 andP31 •not 0. Can be set with keys from 1.5% toP33 setting.

P35 = Minimum value of Pb calculated byautotuning when instrument has onecontrol output

Not available when P7 = 4 or P31 = 0. Can beset with keys from 1.0% to P33 setting.

Page 22: Barber Colman 7EF

22

P42 = Output safety valueThis parameter is skipped when P41 = 0.Can be set:

from 0 to 100% when P7 is not 4.from -100 to 100% when P7 = 4.

P43 = Extension of the anti-reset wind upRange from -30 to 30% of the proportional band.A positive value increases the high limit of the anti-reset wind up (over the setpoint); a negative valuedecreases the low limit of the anti-reset-wind up(under the setpoint).

P44 = Control action typePid = Instrument operates with Pid algorithm.Pi = Instrument operates with Pi algorithm.

P45 = Setpoint indicationFn.SP = During operating mode, when

instrument performs a ramp, it willshow the final setpoint value.

OP.SP = During operating mode, wheninstrument performs a ramp, it willshow the operating setpoint.

P46 = Operating setpoint alignment atinstrument start-up

0 = At start-up, operating setpoint will bealigned to SP or SP2, according to thestatus of the logic input.

1 = At start-up, operating setpoint will bealigned to the measured value, and itwill reach the selected setpoint with aprogrammable ramp. (See Grd1 andGrd2 operating parameters).

Note: If the instrument detects an out of range,or an error condition on the measured value, itwill operate as described for P46 = 0.

This completes the advanced configuration pro-cedure. The display should show “COnF.”

Default Configuration Parameters

The configuration parameters can be loadedwith predetermined default values. These arethe settings loaded into the instrument prior toshipment from the factory. To load the defaultvalues proceed as follows:

a) Open switch V1 (see Figure 1, in Prelimi-nary Hardware Settings).

b) The upper (or left) display will show:

c) Press the t key; the lower (or right)display will show the firmware version.

d) Still holding the t key and press the skey; the display will show:

Page 23: Barber Colman 7EF

23

P5 rEL rELP6 rEV rEVP7 1 1P8 AIr AIrP9 H.A. H.A.P10 OFF OFFP11 10 10P12 0 0P13 H .A H.A.P14 0 0P15 H.A. H.A.P16 OPrt. OPrt.P17 0 0P18 0.1 0.1P19 0 0P20 0 0P21 rEV rEVP22 OFF OFFP23 rEV rEVP24 OFF OFFP25 rEV rEVP26 OFF OFFP27 0 0P28 not availableP29 ON ONP30 ON ONP31 2 2P32 OFF OFFP33 30 30P34 1.5 1.5P35 1.0 1.0P36 00.50 00.50P37 0 0P38 not availableP39 tn 10 tn 30P40 nO.FL nO.FLP41 0 0P42 0 0P43 10 10P44 Pid PidP45 Fn.SP Fn.SPP46 0 0

e) Press the s key to select table 1(European) or table 2 (American) defaultparameters; the display will show:

f) Press the FUNC key; the display willshow:

This indicates that the loading procedure hasbeen initiated. After about 3 seconds the pro-cedure is complete and the instrument revertsto the “COnF” display. The following is a list ofthe default configuration parameters loaded dur-ing the procedure:

PARA. TABLE 1 TABLE 2EuropeanUSA

SEr 1 Ero EroSEr 2 1 1SEr 3 19200 19200SEr 4 7E 7EP1 3 20P2 – – – – . – – – – .P3 0 0P4 400 1000

Page 24: Barber Colman 7EF

24

Operating Mode

1) Remove the instrument from its case.2) Close switch V1 (see Figure 1, "Prelimi-

nary Hardware Settings").3) Re-insert the instrument in its case.4) Switch on power to the instrument.

Display FunctionIn the normal display mode, the upper (or left)display shows the measured value while thelower (or right) display shows the programmedsetpoint.

Note: When the rate of change (Grd1, Grd2) isused, the displayed setpoint may be differentfrom the operating setpoint.

It is possible to change the information on thelower (or right) display as follows:• Press and hold the FUNC key for more

than three seconds but less than tenseconds. The lower (or right) display willshow “A.” followed by the OUT 1 current(measured by the current sensingtransformer) when the load is in ON .

• Press the FUNC key again. The lower (orright) display will show "b" followed by theleakage current running in the load drivenby OUT 1 when the load is in OFFcondition. (See also "OUT 1 FailureDetection.")

• Press the FUNC key again. The lower (orright) display will show “H.” followed bythe OUT 1 power (from 0 to 100%).

• Press the FUNC key again. The lower (orright) display will show “C.” followed bythe OUT 2 power (from 0 to 100%).

• Press the FUNC key again. The displaywill return to the normal display mode.

Note: OUT 1 current and the OUT 2 power ap-pear only if the respective function is config-ured.

If no keys are pressed within the timeout period(see P39), the display will automatically returnto the normal display mode.

In order to keep the desired information con-tinuously on the lower display, press the s ort key to stop the timeout. To return to the nor-mal display mode, press the FUNC key again.

Indicators°C Lit when the process variable is

shown in degrees Celsius.°F Lit when the process variable is

shown in degrees Fahrenheit.AT Flashes during first part of autotuning

(Smart AT). Lit steadily when secondpart of autotuning is active.

OUT1 Lit when OUT 1 is ON.OUT2 Lit when OUT 2 is ON or Alarm 1 is in

alarm state.OUT3 Lit when Alarm 2 is in alarm state.

Flashes (slow rate) when "Out 1Failure Detection" is in alarm state.Flashes (faster rate) when "Out 1Failure Detection" and Alarm 2 are inthe alarm state.

Page 25: Barber Colman 7EF

25

OUT4 Lit when Alarm 3 is in alarm state.RMT Lit when the instrument is in REMOTE

(functions and parameters arecontrolled via serial link).

SP2 Lit when Setpoint 2 is used.Flashes when serial link setpoint isused.

MAN Lit when the instrument is inMANUAL mode.

Operating Key FunctionsFUNC = In the normal display mode:

• Press for less than three secondsto start the parameter modificationprocedure.

• Press for three to ten seconds tochange lower (or right) indication.See "Display Function."

• Press for ten seconds to enablethe lamp test. See "Lamp Test."

FUNC = During parameter modification:New setting of the selected param-eter is stored and the next parameteris displayed (in increasing order).

MAN = In the normal display mode:Press for more than one second toenable or disable the manualfunction.

MAN = During parameter modification:Scrolls back through the parameterswithout storing the new setting.

s = During parameter modification:Increases the setting of the selectedparameter.

s = During manual mode:Increases the output value.

t = During parameter modification:Decreases the setting of the selectedparameter.

t = During manual mode:Decreases the output value.

s +MAN =During parameter modification:Jumps to the maximum program-mable value.

t + MAN = During parameter modification:Jumps to the minimum program-mable value.

Note: A 10 or 30 second timeout (P39) can beselected for parameter modification. If no keysare pressed during this time period, the instru-ment goes automatically to the normal displaymode and the last parameter is not changed.

Enable/Disable the Control OutputWith the instrument in the normal display mode,press and hold for five seconds the s key andthe FUNC key to disable the control outputs.The device will then function as an indicator. Allcontrol outputs will be OFF and the word OFFwill appear in the lower (or right) display. Alarmswill be in a non-alarm condition. The alarm out-put conditions depend on the alarm action type(see P21-P23-P25). Press and hold for five sec-onds the s key and the FUNC key a secondtime to restore the control status. If the alarmstandby function has been configured, alarmswill respond as though it were a power-up con-dition. If a shut down occurs when the controlis disabled, control output will be disabled againat instrument power-up.

Page 26: Barber Colman 7EF

26

Output 1 Failure DetectionFor the load driven by OUT 1, the instrumentwill measure and display:

• current running in the load when theload is energized

• leakage current flowing through the loadwhen the load is de-energized

If P10 parameter has been correctly set, the in-strument generates an alarm when:

• current running through the load is lowerthan the "Hbd" parameter value. (Itshows a partial or total breakdown of theload, the breakdown of the actuator, or apower down due to a protection or fuseintervention).

• leakage current is higher than the "SCA"parameter value. (It shows a shortcircuit of the actuator).

The "Display Function" paragraph describeshow to show the two current values. A faultcondition is shown by OUT 3 LED flashing, andby OUT 3 relay status.

If the on or off period is more than 400 ms, therelative measurement couldn't be performed andthe instrument will show flashing the last mea-sured value.

Manual FunctionThe manual mode can be accessed (if P30 =On) by pressing the MAN key for one second.The command is accepted and executed only ifthe display is in the normal display mode. Whenin the manual mode, the MAN LED is lit and the

lower display shows the power output values.The value of OUT 1 is shown in the two mostsignificant digits field while the value of OUT 2(if present) is shown in the two least significantdigits field. The decimal point between the twovalues will be flashing to indicate the instrumentis in manual mode.

Note: “ “ is used for OUT1 = 100 “ “ is used for OUT2 = 100

Power output can be modified by using the sand t keys. Hold for two seconds the MAN keyagain to return the device to the AUTO mode.

The transfer from AUTO to MANUAL and backis bumpless (this function is not provided if in-tegral action is excluded). If the transfer fromauto to manual occurs during the first part ofthe autotuning (Smart AT) algorithm (tune), whenit return to AUTO mode, instrument will be forcedautomatically to the second part of theautotuning algorithm (ADAPTIVE).

At power-up, the instrument will be in the AUTOmode or in the mode it was in prior to powershutdown (depending on P37).

Note: When start-up occurs in the manual mode,the power output (OUT1 - OUT2) is set to 0.

Setpoint AccessWhen the instrument is in AUTO mode and inthe normal display mode, SP and SP2 can bedirectly accessed.

Page 27: Barber Colman 7EF

27

Press the s or t key (and hold for two sec-onds); the setpoint will start to change. The newsetpoint becomes operative since no key hasbeen pressed at the end of two second timeout.

SP/SP2 SelectionThe operating setpoint (SP or SP2) can beswitched only by an external contact (terminals7 and 8). By setting P45, it is possible to dis-play the final or operating setpoint during rampexecution.

Serial LinkThis instrument can be connected to a host com-puter by a serial link. The host computer canput the instrument in either LOCAL (functionsand parameters are controlled by the keys) orREMOTE (functions and parameters are con-trolled by serial link). REMOTE is signified bythe LED labeled RMT.

To download instrument configuration throughthe serial link proceed as follows;1) Serial parameters SEr1 through SEr4 must

be properly configured from the keys.2) The instrument must be in the operating

mode.

During downloading of the configuration, the in-strument goes into open loop control with alloutputs in OFF state. At the end of the configu-ration procedure, the instrument performs an au-tomatic reset and returns to closed loop con-trol.

Autotuning (Smart AT)Autotuning is used to automatically optimize thecontrol action. To enable autotuning, press theFUNC key until “Snrt” appears. Press the s ort key to set the display to “On” and then pressthe FUNC key. The AT LED will turn on or beginflashing according to the selected algorithm.When autotuning is enabled, the control param-eters (Pb, ti, td, rC) can be displayed but notmodified.

To disable autotuning, press the FUNC key until“Snrt” appears. Press the s or t key to set thedisplay to “OFF” and press the FUNC key again.The AT LED will turn off. Once autotuning isturned off, the instrument maintains the calcu-lated control parameters, but allows the param-eters to be modified.

Note: Autotuning is disabled when Pb = 0 (ON/OFF control). Autotune enable/disable can beprotected by a password (see P31).

Lamp TestWhen it is desired to verify the display efficiency,push FUNC button for more than 10 seconds.The instrument will turn on with a 50% duty cycleall LEDs. Lamp test does not time out – to re-turn to normal display mode, push FUNC but-ton again. During lamp test, the instrument con-tinues to control the process, but keyboard func-tions are not available, except FUNC.

Page 28: Barber Colman 7EF

28

Operating ParametersWith instrument in the normal operating mode,press the FUNC key. The lower display will showthe code while the upper display will show thesetting or the status (ON or OFF) of the selectedparameter.

Press the s or t key to change the setting.Press the FUNC key again and the instrumentstores the new setting and goes to the next pa-rameter.

Some of the following parameters may not ap-pear, depending on the configuration.

Param. DescriptionSP Setpoint (in engineering units).

Range from rL to rH. Operativewhen the logic input is open.

Snrt Autotune status.On or OFF indicates the status ofautotuning (enabled or disabledrespectively).Set to On to enable autotuning.Set to OFF to disable autotuning.

n.rSt Manual reset of the alarms.Set to ON to reset the alarms. Thisparameter is skipped if none of thealarms have manual reset function.

SP2 Setpoint 2 (in engineering units).Range from rL to rH. Operative whenlogic input is closed.

nnn Software key, password for param-eter protection. This parameter isskipped if P20 = 0 or 1On =The instrument is LOCKEDOFF = The instrument is UNLOCKEDTo switch from LOCKED to UN-LOCKED, enter the P20 parametersetting. To switch from UNLOCKED toLOCKED, enter any number otherthan the P20 parameter setting.

AL1 Alarm 1 setpoint Available only ifP7=1, 2 or 3. Ranges:•span limits for process alarm•0 to 500 units for band alarm•-500 to 500 units for deviation alarm

HSA1 Alarm 1 hysteresis. Available only ifP7 = 1, 2, or 3. Range from 0.1% to10.0% of input span, or 1 LSD. If thehysteresis band is larger than thealarm band, the instrument will use ahysteresis value equal to theprogrammed band minus 1 digit.

AL2 Alarm 2 setpoint. Available only ifP12 = 1, 2, or 3. Ranges:•span limits for process alarm•0 to 500 units for band alarm•-500 to 500 units for deviation alarm

HSA2 Alarm 2 hysteresis. Available only ifP12 = 1, 2, or 3. Range from 0.1% to10.0% of input span, or 1 LSD. If thehysteresis band is larger than thealarm band, the instrument will use ahysteresis value equal to theprogrammed band minus 1 digit.

Page 29: Barber Colman 7EF

29

AL3 Alarm 3 setpoint. Available only ifP14 = 1, 2 or 3 and P16 = OPrt.Ranges:•span limits for process alarm•0 to 500 units for band alarm•-500 to 500 units for deviation alarm

HSA3 Alarm 3 hysteresis. Available only ifP14 = 1, 2 or 3 and P16 = OPrt.Range from 0.1% to 10.0% of inputspan, or 1 LSD. If the hysteresisband is larger than the alarm band,the instrument will use a hysteresisvalue equal to the programmed bandminus 1 digit.

Pb Proportional band . Range:• 1.0% to 100.0% of input span

when P7 not 4• 1.5% to 100.0% of input span

when P7 = 4When Pb parameter is set to 0, thecontrol actions becomes on-off.Note: when the instrument is workingwith autotuning algorithm, Pb valuewill be limited by P33 and P35 whenP7 • 4; and P33 and P34 when P7 = 4.

HyS Hysteresis for on-off control action.Available only when Pb = 0. Rangefrom 0.1% to 10.0% of input span.

ti Integral time. Skipped if Pb = 0.Range from 00.01 to 20.00 mm.ss.Above this value the display blanksand integral action is excluded.When the instrument is working withthe autotune algorithm, minimal valueof integral time is limited by P36.

td Derivative time. Skipped if Pb = 0 orP44 = Pi. Range from 00.00 to 10.00mm.ss. When instrument is workingwith autotune algorithm, the td valuewill be equal to a quarter of ti value.

IP Integral preload. Skipped if Pb = 0.For one control output, program-mable from 0 to 100% of the outputspan; for two control outputs,programmable from -100% to 100%(100% cooling to 100% heating).

Cy1 Output 1 cycle time. Range from 1 to200 seconds.

Cy2 Output 2 cycle time. Available only ifP7 = 4. Range from 1 to 200seconds.

rC Relative Cooling gain. Skipped ifPb = 0 or P7 not 4. Range from 0.20to 1.00. When the instrument isworking with the autotune algorithmand P32 is set to ON, the rC value islimited in accordance with theselected type of cooling media:0.85 to 1.00 when P8 = Air0.80 to 0.90 when P8 = OIL0.30 to 0.60 when P8 = H2O

OLAP Deadband/Overlap between H/Coutputs. Skipped if Pb = 0 or P7 not4. Range from -20 to 50% ofproportional band. A negative OLAPvalue shows a deadband; a positivevalue shows an overlap.

rL Setpoint low limit. Range fromminimum range value (P3) to rH.When P3 is modified, rL will berealigned to it.

Page 30: Barber Colman 7EF

30

Error MessagesOverrange, Underrange, and Sensor Break

This instrument is capable of detecting processvariable faults (OVERRANGE, UNDERRANGE orSENSOR BREAK). When the process variableexceeds the span limits established by configu-ration parameter P1, an OVERRANGE conditionwill appear as:

An UNDERRANGE condition will appear as:

If P41 is not zero and an out of range conditionis detected, the instrument operates in accor-dance with P41 and P42.

rH Setpoint high limit. Range from rL tofull scale value (P4). When P4 ismodified, rH will be realigned to it.

Grd1 Ramp applied to an increasingsetpoint change. Range from 1 to100 digits per minute. Above thisvalue the display shows InF, meaningthat the transfer will be done as astep change.

Grd2 Ramp applied to an decreasingsetpoint change. Range from 1 to100 digits per minute. Above thisvalue the display shows "InF,"meaning that the transfer will be doneas a step change.

OLH Output high limit. Range from 0.0 to100.0% when instrument is config-ured with one control output; from-100.0 to 100.0% when device isconfigured with two control outputs.

tOL Duration of the output power limiter(soft start). Range from 1 to 540minutes. Above this value the displayshows "InF" meaning that the limitingaction is always on. Note: the tOLcan be modified but the new valuewill become operative only at the nextinstrument start-up.

Hbd Out 1 breakdown alarm setpoint.Skipped if P10 = off. Range from 0to full scale value (see P11). Func-tion: see "Out 1 Failure Detection."Note: setpoint resolution will be equalto 0.1 A for range up to 20 A, and 1 Afor range up to 100 A. Hysteresis ofthis alarm is fixed to 1% of fsv.

SCA Setpoint value for OUT 1 short circuitalarm. Skipped if P10 = off. Rangefrom 0 to full scale value (see P11).Function: see "Out 1 Failure Detec-tion." Note: setpoint resolution willbe equal to 0.1 A for range up to 20A, and 1 A for range up to 100 A.Hysteresis of this alarm is fixed at 1%of fsv.

rnP Control output maximum rage of rise.Programmable from 1% to 25% ofthe output per second. Above25%/s, the display will show "InF"meaning that no ramp is imposed.

Page 31: Barber Colman 7EF

31

Power UpOn power-up, the instrument performs a self-diagnostic test. When an error is detected, thelower (or right) display shows an “Err” indica-tion while the upper (or left) display shows thecode of the detected error.

Error ListSEr Serial interface parameter error100 EEPROM write error.200 Attempt to write to protected

memory.201 - 2xx Configuration parameter error. The

two LSDs show the number of thewrong parameter. For example, 209indicates an error in parameter P9.

301 RTD input calibration error.305 TC/mV input calibration error.307 RJ input calibration error.310 CT input calibration error.311 20 mA input calibration error.312 5 V input calibration error.313 10 V input calibration error.400 Control parameter error.500 Auto-zero error.502 RJ error.510 Error during calibration procedure

Dealing with error messagesWhen a configuration parameter error is de-tected, repeat the configuration procedure ofthat specific parameter. If an error 400 is de-tected, simultaneously press the s and t keyto load the default parameters and then repeatthe control parameter setup. For all other er-rors, contact your supplier.

Output action on over/underrangeIf P41= 0, the following conditions may occur if:• The instrument is set for one output only

and an OVERRANGE is detected, OUT 1turns OFF (if reverse acting) or ON (ifdirect acting).

• The instrument is set for heating/coolingand an OVERRANGE is detected, OUT 1turns OFF and OUT 3 turns ON.

• The instrument is set for one output onlyand an UNDERRANGE is detected, OUT 1turns ON (if reverse acting) or OFF (ifdirect acting).

• The instrument is set for heating/coolingand an UNDERRANGE is detected, thenOUT 1 turns ON and OUT 3 turns OFF.

The sensor break can be signalled as:• For TC/mV input: OVERRANGE or

UNDERRANGE (selected by solderjumper)

• For RTD input: OVERRANGE• For mA/V input:UNDERRANGE

Note: On the mA/V input, a sensor break canbe detected only when the range selected hasa zero elevation (4-20 mA, 1-5 V, or 2-10 V).

On the RTD input a special test is provided tosignal an OVERRANGE when input resistanceis less than 15 Ohms (short circuit sensor de-tection).

Page 32: Barber Colman 7EF

32

Default Operating Parameters

The control parameters can be loaded with pre-determined default values. These are the set-tings loaded into the instrument prior to ship-ment from the factory. To load the default val-ues proceed as follows:

a) Close switch V1 (see Figure 1 in Configu-ration section of this manual).

b) Autotuning (Smart AT) must be disabled.c) The upper (or left) display will show the

process variable and the lower (or right)display will show the setpoint.

d) Hold down the t key and press the skey; the display will show:

7EF 7HF

e) Press either the t or s key; the displaywill show:

f) Press the FUNC key; the display will show:

This indicates that the loading procedure hasbeen initiated. After about three seconds theloading procedure is complete and the instru-

ment reverts to the normal display mode. Thefollowing is a list of the default operating pa-rameters loaded during the procedure:

SP = Initial scale valueSnrt = Disabledn.SRt = OFFSP2 = Initial scale valuennn = OFFA1, A2, A3 = Initial scale value (process

alarms). 0 (deviation or bandalarms)

HSA1, HSA2, HSA3 = 0.1%Pb = 4.0%HyS = 0.5%ti = 4.00 (4 minutes)td = 1.00 (1 minute)IP = 30%Cy1 = 15 seconds (relay output)

4 seconds (SSR output)Cy2 = 10 seconds for P8 = AIr

4 seconds for P8 = OIL2 seconds for P8 = H2O

rC = 1.00 for P8 = AIr0.80 for P8 = OIL0.40 for P8 = H2O

OLAP = 0rL = Initial scale valuerH = Full scale valueGrd 1 = Infinite (step transfer)Grd 2 = Infinite (step transfer)OLH = 100%tOL = InfiniteHbd = 50% of the full scaleSCA = 100% of the full scale valuernP = 25%/s

Page 33: Barber Colman 7EF

33

Specifications

General

Case: PC-ABS black color. Self-extinguish-ing degree V-0 according to UL 94.

Front Protection: Designed and tested forIP65 and NEMA 4X for indoor locations(when panel gasket is installed). Testsperformed in accordance with CEI 70-1 andNEMA 250 - 1991 std.

Installation: Panel mounting by means ofbrackets.

Rear Terminal Block: 21 screw terminals, withconnection diagrams and safety rear cover.(Screw M3 for cables from AWG 22 to AWG14).

Dimensions: 48 x 96 mm (1.890 x 3.780 in.)according to DIN 43700; 116 mm (4.567 in.)deep.

Weight: 450 grams (1 pound).Power Supply: 100 to 240 Vac, 50/60 Hz (-15

to 10% of the nominal value); 24 Vac/Vdc±10% of nominal value

Power Consumption: 8 VA max.Insulation Resistance: Greater than 100 MΩ

according to IEC 1010-1.Dielectric Strength: 1500 Vrms according to

IEC 1010-1.Display Updating Time: 500 ms.Sampling Time: 250 ms for linear inputs; 500

ms for TC and RTD inputs.Resolution: 30000 counts.Accuracy: ±0.2% f.s.v., ±1 digit @ 25°C

ambient temperature.

Common Mode Rejection: 120 dB @ 50/60Hz.

Normal Mode Rejection: 60 dB @ 50/60 Hz.Electrostatic Compatibility and Safety

Requirements: This instrument is markedCE. Therefore, it is conforms to councildirectives 89/336/EEC (reference harmo-nized standard EN 50081-2 and EN 50082-2) and to council directives 73/23/EEC and93/68/EEC (reference harmonized standardEN 61010-1).

Installation Category: IITemperature Drift (Reference Junction

Excluded):< 200 ppm/°C of span for mV and TCranges 1, 3, 5, 6, 19, 20, 21, 22< 300 ppm/°C of span for mA/V< 400 ppm/°C of span for RTD ranges 10,

26, and TC ranges 0, 2, 4, 27, and 28< 500 ppm/°C of span for RTD range 9 and

TC ranges 7, 8, 23, 24< 800 ppm/°C of span for RTD range 25.

Operating Temperature: 0 to 50 °C.Storage Temperature: -20 to 70 °C.Humidity:20 to 85% rh non-condensing.Protection:

a) WATCH DOG for automatic restart.b) DIP switches for configuration and

calibration parameters.

Page 34: Barber Colman 7EF

34

Inputs

ThermocoupleTypes: J, K, L, R, S, N and T are keyboard

programmable.Engineering Units: °C and °F keyboard

programmable.External Resistance: 100Ω max., maximum

error 0.1% of span.Burnout: Shown as an overrange condition

(standard). It is possible to obtain anunderrange indication by cut and short.

Reference Junction: Automatic compensationfrom 0 to 50 °C.

Reference Junction Accuracy: 0.1 °C/°C.Input Impedance: Greater than 1 MΩ.Calibration: According to IEC 584-1 and DIN

43710-1977.Standard Ranges

Type Range °C Range °FL 0 0 to 400.0 –L 1 0 to 900 19 0 to 1650J 2 -100.0 to 400.0 –J 3 -100 to 1000 20-150 to 1830K 4 -100.0 to 400.0 –K 5 -100 to 1370 21-150 to 2500N 6 -100 to 1400 22-150 to 2550R 7 0 to 1760 23 0 to 3200S 8 0 to 1760 24 0 to 3200T 27 -199.9 to 400.0 28 -330 to 750

RTD (Resistance Temperature Detector)Type: Pt 100 Ω 3 wire connection.Input Circuit: Current injection.°C/°F Selection: Front keys or serial link.Line Resistance: Automatic compensation up

to 20 Ω/wire with no measurable error.Calibration: According to 43760.Burnout: Up scale. A special test is provided

to signal overrange when input resistance isless than 15 Ω.

Standard Ranges:9 -199.9 to 400.0 °C10 -200 to 800 °C25 -199.9 to 400.0 °F26 -330 to 1470 °F

Linear InputsReadout: Keyboard programmable between

-1900 and 4000Decimal Point: Programmable in any positionBurnout: Instrument shows burnout as

• underrange for 4 to 20 mA, 1 to 5 V,and 2 to 10 V

• underrange or overrange (selectableby solder jumper) for 0 to 60 mV and12 to 60 mV.

• No indication available for 0 to 20 mA,0 t 5 V and 0 to 10 V input types

Accuracy: 0.2% + 1 digit @ 25°C.

Page 35: Barber Colman 7EF

35

Impedance: Type11 0 to 60 mV >1 MΩ12 12 to 60 mV >1 MΩ13 0 to 20 mA <5 Ω14 4 to 20 mA <5 ý15 0 to 5 V >200 kΩ16 1 to 5 V >200 kΩ17 0 to 10 V >400 kΩ18 2 to 10 V >400 kΩ

Current Transformer Inputfor OUT 1 Failure DetectionFunction: Detects and signals a possible

failure of the line driven by OUT 1 (See "Out1 Failure Detection").

Input Range: 50 mAac.Scaling:Programmable from 10 Amps to 100

Amps (with 1 Amp step).Resolution:

• For full scale up to 20 Amps: 0.1 Amp.• For full scale from 21 Amps to 100Amps: 1 Amp.

Minimum Duration of On or Off Period to Per-form Measurement: 400 ms.

Logic InputInstrument is equipped with one input from con-tact (voltage free) for setpoint selection.Contact Open = Main setpointContact Closed = Auxiliary setpointNote: use an dry external contact capable ofssitching 0.5 mA, 5 Vdc. The instrument needs100 ms to recognize a contact status variation.Logic inputs are not isolated by the measuringinput.

Setpoints

This instrument can use two setpoints: SP andSP2. Setpoint selection is possible by logic in-puts.Setpoint Transfer: Transfer from one setpoint

to another, or between two different setpointvalues, may be realized by a step transfer orby a ramp with two different programmablerates of change (ramp up and ramp down).

Slope Value: 1 to 100 eng. unit/min or step.Setpoint Limiter: RLO and RHI parameters,

programmable.

Control Action

Algorithm: PID + Autotune.Type: One (heating or cooling) or two (heating

and cooling) control outputs.Proportional Band: Programmable:

• from 1.0 to 100.0% of the input span fora process with one control output.

• from 1.5 to 100.0% of the input span fora process with two control outputs.

Setting the Pb equal to 0 changes thecontrol action to on-off

Hysteresis (for on-off control action): Pro-grammable from 0.1 to 10.0% of the inputspan.

Integral Time: Programmable from 1 secondto 20 minutes (or excluded by 0 value).

Derivative Time: Programmable from 1second to 10 minutes (or excluded by 0value).

Page 36: Barber Colman 7EF

36

Outputs

Type: Time proportioning.Control Output Updating Time:

• 250 ms when linear input is used• 500 ms when TC or RTD input is used

Control Output Resolution: 1% of spanControl Action: Direct/reverse programmableOutput Level Indication (for control outputs):

Output 1 value and output 2 value displayedseparately.

Output Level Limiter (for control outputs):• One control medium: 0.0 to 100.0%• Two control mediums: -100.0 to 100.0%.This function may be operative at instrumentstart-up for programmable time (to avoidthermal shock and/or preheating the plant).

Relay OutputsOutput 1: SPST contact with rated current 3 A

@ 250 Vac on resistive load (NO contact).Output 2: SPST contact with rated current 2 A

@ 250 Vac on resistive load.Output 3: SPST contact with rated current 2 A

@ 250 Vac on resistive load.Output 4: SPST contact with rated current 2 A

@ 250 Vac on resistive load.Note: Side C of Out 3 and Out 4 are common.Logic Voltage for SSR Driver (0utput 1 only)

Logic Level 0: Vout <0.5 VdcLogic Level 1: 14 Vdc ±20% @ 20 mA

24 Vdc ±20% @ 1 mAMaximum current = 20 mA

Note: Out 1 can be selected by jumper asrelay output or SSR driver output.

Output Status Indicator: Four indicators (Out1, 2, 3, 4) are lit when the respective outputis in the on condition.

Integral Pre-load: Programmable:• for 1 control output, from 0 to 100% of

the output range.• for 2 control outputs, from -100.0 to

100.0% of the heating/cooling outputrange.

Autotuning: Keyboard enable/disable.Auto/Manual: Keyboard selectable.Auto/Manual Transfer: BumplessAuto/Manual Indicator: (MAN) off in auto

mode; lit in manual mode.

Page 37: Barber Colman 7EF

37

Alarms

This instrument is equipped with three indepen-dent outputs programmable as:

• Heating + Alarm 1 + Alarm 2• Heating + Cooling + Alarm 2• Heating + Alarm 1 + Out 1 failure

detection (or Alarm 2 + Out 1 failuredetection in OR condition)

• Heating + Cooling + Out 1 failuredetection (or Alarm 2 + Out 1 failuredetection in OR condition).

An optional output is available as Alarm 3 .Action: Direct or reverse acting.Alarm Functions: Each alarm can be

configured as process alarm, band alarm ordeviation alarm.

Alarm Reset: Automatic or manual resetprogrammable on each alarm.

Stand-by (mask): Each alarm can beconfigured with or without stand-byfunction. Alarm masking deletes falseindication at start-up and after a setpointchange.

Process AlarmOperating Mode: High or low programmable.Setpoint: Programmable in engineering units

within the input span.Hysteresis: Programmable from 0.1 to 10.0%

of the input span (P4 - P3).

Band AlarmOperating Mode: Inside or outside band

programmable.Setpoint: Programmable from 0 to 500 units.Hysteresis: Programmable from 0.1 to 10.0%

of the input span.

Deviation AlarmOperating Mode: High or low programmable.Setpoint: Programmable from -500 to 500

units.Hysteresis: Programmable from 0.1% to

10.0% of the input span.

Serial Communications Interface

Type: RS-485.Protocol Type: MODBUS, JBUS, or propri-

etary polling/selecting.Baud: Programmable from 600 to 19200.Byte Format: 7 or 8 bit programmable.Parity: Even, odd or none programmable.Stop Bit: One.Address: 1 to 95 for proprietary protocol.

1 to 255 for all other protocols.Output Voltage Levels: According to EIA

standards.

Page 38: Barber Colman 7EF

38

h) Use calibrators with the following:AccuracyCurrent Input: ±0.025% output

±0.0025% range±0.01 microvolt

Voltage Input: ±0.005% output±0.001% range±5 microvolt

TC Input: ±0.005% output±0.001% range±5 microvolt

RTD Input: ±0.02%±0.0025 Ω/decade

CJ Compensation: better than 0.1°CResolutionCurrent Input: 0.5 microampVoltage Input: 100 microvoltTC Input: 1 microvoltRTD Input: 10 milliohmCJ Compensation: better than 0.1°C

Calibration Parameters

Following is a complete list of calibrationsymbols:Code ParametertL TC/mV Input Minimum ValuetH TC/mV Input Maximum Valuet. TC/mV Input CheckrJ Reference Junction CompensationrJ. Reference Junction Compensation

CheckPL RTD Input Minimum Value (0 Ω)PH RTD Input Maximum Value (300 Ω)P. RTD Input Check

Calibration

Calibration parameters are logically divided intogroups of two parameters each – initial scalevalue and final scale value. A calibration checkis provided after entering the values of eachgroup. A calibration check can be initiated with-out making an entry: press the FUNC key toadvance to the desired calibration check. Theupper or left display will show the parametercode (t. - rJ. - P. - nA. - 5U. - 10U. - Ct.) and thelower or right display will show "ON" or "OFF".

Before beginning calibration, be sure internalswitch V2 is open (see Configuration Procedure,Figure 1).

General Guidelines

a) The instrument should be mounted in itscase in order to keep the internaltemperature constant.

b) Ambient temperature should be stable.Avoid drift due to air conditioning or othermechanical devices.

c) Relative humidity should not exceed 70%.d) Minimum warm up time should be at least

20 minutes.e) Operate as much as possible in a noise

free environment.f) During calibration, connect one input at a

time to the rear terminal block.g) Before input calibration, the specific

preliminary hardware settings as de-scribed in the Configuration section mustbe made.

Page 39: Barber Colman 7EF

39

nAL Current Input Minimum Value (0 mA)nAH Current Input Maximum Value (20 mA)nA. Current Input Check5UL 5 Volt Input Minimum Value (0 V)5UH 5 Volt Input Value (5 V)5U. 5 Volt Input Check10UL 10 Volt Input Minimum Value (0 V)10UH 10 Volt Input Maximum Value (10 V)10U. 10 Volt Input Checkct.L Current Transformer Input Minimum

Value (0 mAac)ct.H Current Transformer Input Maximum

Value (50 mAac)ct. Current Transformer Input Check

Procedure

Switch on the instrument; the lower or left dis-play will show “COnF”. Press the s key andthe display will show “CAL”. Press the “FUNC”key to start the calibration process. Repeat-edly press the FUNC key until the desired cali-bration (parameter) code appears.

Use the s and t keys to select between ONand OFF. To go to the next parameter withoutmodifying the calibration, press the FUNC keywhen the display shows “OFF” .

To start parameter calibration, press the FUNCkey when the display shows “ON”.

Note: Press the AT key to display the previousparameter without storing the new calibration.

Entering Calibration Values

tL TC/mV input minimum range valuea) Perform the preliminary hardware settings

described in the Configuration section ofthis manual, and connect the calibratorand instrument as shown below.

1

3

+

-

b) The display shows “OFF” and “tL”.c) Set calibrator to 0.000 mV.d) Press the s key; the display changes to

“ON”.e) After a few seconds, start calibration by

pressing the FUNC key. The decimalpoint of the least significant digit will lightto indicate the instrument is performingthe calibration. When calibration iscomplete, the instrument will proceed tothe next parameter.

tH TC/mV input maximum range valuea) Set the calibrator to 60.000 mV.b) Press the s key; the displays will show

“ON” and “tH”.c) After a few seconds, start calibration by

pressing the FUNC key. The decimal pointof the least significant digit will light toindicate the instrument is performing thecalibration. When this calibration iscomplete, the instrument will proceed to thenext parameter.

Page 40: Barber Colman 7EF

40

t. TC/mV input checkThe display will show “t.” followed by a num-ber showing the measured value in counts. Thecalibration is correct if the indication is “t. 30000” ±10 counts.

a) Check the minimum range value bysetting the calibrator to 0.000 mV - thereadout must be equal to "t. 0 0000" ±10counts.

b) Check linearity at half scale by setting30.000 mV on the calibrator. The readoutmust be "t. 1 5000" ±10 counts.

c) Press the FUNC key, "OFF" and "rJ" willappear on the displays.

rJ Reference junction compensationNote: Make sure tL and tH are correctlycalibrated before attempting rJ calibra-tion.

a) Measure the temperature close toterminals 1 and 3 using an appropriateinstrument, as shown:

1

3

M ea su ring D ev ice

+

-

b) Wait a few minutes to allow temperaturestabilization of the entire system (compen-sation cable, sensor, calibrator andinstrument).

c) Use the s and t keys to make thereadout value equal to the temperaturemeasured by the measuring device intenths of °C.

d) After a few seconds, start calibration bypressing the FUNC key. The decimalpoint of the least significant digit will lightto indicate the instrument is performingthe calibration. When this calibration iscomplete, the instrument will proceed tothe next parameter.

rJ. Reference junction compensation checkThe display will show “rJ.” and the temperaturein tenths of °C, measured by the compensator.Check that the display readout is equal to thevalue read by the measuring device. Press theFUNC key, the instrument will proceed to thenext parameter.

PL RTD input minimum range valuea) Perform the preliminary hardware settings

described in the Configuration section,and connect the calibrator and instrumentas shown below.

4

3

1

Page 41: Barber Colman 7EF

41

b) Set 0.000 Ω on the resistor box.c) Press the s key; the displays show “ON”

and “PL”.d) After a few seconds, start calibration by

pressing the FUNC key. The decimalpoint of the least significant digit will lightto indicate the instrument is performingthe calibration. When this calibration iscomplete, the instrument will proceed tothe next parameter.

PH RTD input maximum range valuea) Set resistor box to 375.000 Ω.b) Press the s key; the displays will show

“ON” and “PH”.c) After a few seconds, start calibration by

pressing the FUNC key. The decimalpoint of the least significant digit will lightto indicate the instrument is performingthe calibration. When this calibration iscomplete, the instrument will proceed tothe next parameter.

P. RTD input checkThe display shows “P.” followed by a numbershowing the measured value in counts:

Check the calibration (not linear) by setting theresistance box to:a) 0.00 Ω; the readout should be “P. 0 0000”

±10 counts.

b) 125.00 Ω; the readout should be“P.1 0190” ±10 counts.

c) 250.00 Ω; readout should be “P. 2 0189”±10 counts.

d) 375.00 Ω; readout should be “P. 3 0000”±10 counts.

e) Press the FUNC key and proceed to nextparameter.

nAL Current minimum range valuea) Perform the preliminary hardware settings

described in the Configuration section,and connect the calibrator and instrumentas shown below.

1

3

+

-

b) Set 0.000 mA on the calibrator (even if theminimum range value is 4 mA).

c) Press the s key, the display will show"nAL" and "ON".

d) After a few seconds, start calibration bypressing the FUNC key. The decimalpoint of the least significant digit will lightto indicate the instrument is performingthe calibration. When this calibration iscomplete, the instrument will proceed tothe next parameter.

Page 42: Barber Colman 7EF

42

nAH Current maximum range valuea) Set 20.000 mA on the calibrator.b) Press the s key, the display will show

"nAH" and "ON".c) After a few seconds, start calibration by

pressing the FUNC key. The decimalpoint of the least significant digit will lightto indicate the instrument is performingthe calibration. When this calibration iscomplete, the instrument will proceed tothe next parameter.

nA. Current input checkThe display will show "nA." followed by a num-ber showing the measured value in counts. Thecalibration is correct if the indication is "A. 30000" ±10 counts.

a) Check the minimum range calibration bysetting the calibrator to 0.000 mA; thereadout should be “nA. 0 0000” ±10counts.

b) Check the linearity at half scale by settingthe calibrator to 10.000 mA; the readoutshould be “nA. 1 5000” ±10 counts.

c) Press the FUNC key to proceed to thenext parameter.

5UL 5 volt input-minimum range valuea) Perform the preliminary hardware settings

described in the Configuration section,and connect the calibrator and instrumentas shown below.

1

3

+

-

b) Set 0.000 V on the calibrator (even if theminimum range value is 1 V).

c) Press the s key, the display will show"5UL" and "ON".

d) After a few seconds, start calibration bypressing the FUNC key. The decimalpoint of the least significant digit will lightto indicate the instrument is performingthe calibration. When this calibration iscomplete, the instrument will proceed tothe next parameter.

5UH 5 volt input-maximum range valuea) Set 5.000 V on the calibrator.b) Press the s key, the display will show

"5UH" and "ON".c) After a few seconds, start calibration by

pressing the FUNC key. The decimalpoint of the least significant digit will lightto indicate the instrument is performingthe calibration. When this calibration iscomplete, the instrument will proceed tothe next parameter.

Page 43: Barber Colman 7EF

43

5U. 5 volt input checkThe display will show "5U." followed by a num-ber showing the measured value in counts. Thecalibration is correct if the indication is "5U. 30000" ±10 counts.

a) Check the minimum range calibration bysetting the calibrator to 0.000 V; thereadout should be “5U. 0 0000” ±10counts.

b) Check the linearity at half scale by settingthe calibrator to 2.500 V; the readoutshould be “5U. 1 5000” ±10 counts.

c) Press the FUNC key to proceed to thenext parameter.

10UL 10 volt input-minimum range valuea) Perform the preliminary hardware settings

described in the Configuration section,and connect the calibrator and instrumentas shown below.

1

3

+

-

b) Set 0.000 V on the calibrator (even if theminimum range value is 2 V).

c) Press the s key, the display will show"10UL" and "ON".

d) After a few seconds, start calibration bypressing the FUNC key. The decimalpoint of the least significant digit will lightto indicate the instrument is performingthe calibration. When this calibration iscomplete, the instrument will proceed tothe next parameter.

10UH 10 volt input-maximum range valuea) Set 10.000 V on the calibrator.b) Press the s key, the display will show

"10UH" and "ON".c) After a few seconds, start calibration by

pressing the FUNC key. The decimalpoint of the least significant digit will lightto indicate the instrument is performingthe calibration. When this calibration iscomplete, the instrument will proceed tothe next parameter.

10U. 10 volt input checkThe display will show "10U." followed by a num-ber showing the measured value in counts. Thecalibration is correct if the indication is "10U. 30000" ±10 counts.

a) Check the minimum range calibration bysetting the calibrator to 0.000 V; thereadout should be “10U.0 0000” ±10counts.

Page 44: Barber Colman 7EF

44

b) Check the linearity at half scale by settingthe calibrator to 5.000 V; the readoutshould be “10U.1 5000” ±10 counts.

c) Press the FUNC key to proceed to thenext parameter.

CtL Current transformer input-minimum rangevaluea) Connect the calibrator and instrument as

shown below.

5

6

b) Set 0.000 mA ac on the calibrator.c) Press the s key, the display will show

"CtL" and "ON".d) After a few seconds, start calibration by

pressing the FUNC key. The decimalpoint of the least significant digit will lightto indicate the instrument is performingthe calibration. When this calibration iscomplete, the instrument will proceed tothe next parameter.

CtH Current transformer input-maximum rangevaluea) Set 50.000 mA ac on the calibrator.b) Press the s key, the display will show

"CtH" and "ON".

c) After a few seconds, start calibration bypressing the FUNC key. The decimalpoint of the least significant digit will lightto indicate the instrument is performingthe calibration. When this calibration iscomplete, the instrument will proceed tothe next parameter

Ct. Current transformer input checkThe display will show "Ct." followed by a num-ber showing the measured value in counts. Thecalibration is correct if the indication is "Ct.1000" ±10 counts.

a) Check the minimum range calibration bysetting the calibrator to 0.000 mA ac; thereadout should be “Ct. 0000” ±10 counts.

b) Check the linearity at half scale by settingthe calibrator to 25.000 mA ac; thereadout should be “Ct. 500” ±10 counts.

d) Press the FUNC key to proceed to thenext parameter.

This completes the calibration procedure. Toenter the configuration procedure press the skey, the display will show “CnF”. If configura-tion and calibration are complete, switch the in-strument off and close switch V1.

Page 45: Barber Colman 7EF

45

Maintenance

1. Remove power from the power supplyterminals and from relay output terminals.

2. Remove the instrument from case.3. Using a vacuum cleaner or a compressed

air jet (max. 3kg/cm2) remove dust anddirt which may be present on the louversand on the internal circuits, being carefulto not damage the electronic components.

4. Clean external plastic or rubber parts onlywith a cloth moistened with ethyl alcohol(pure or denatured) [C2H5OH]; or isopropylalcohol (pure or denatured) [(CH3)2CHOH];or water [H2O]

5. Verify that there are no loose terminals.6. Before re-inserting the instrument in its

case, be sure it is perfectly dry.7. Re-insert the instrument and turn it ON.

Page 46: Barber Colman 7EF

46

Page 47: Barber Colman 7EF

47

Page 48: Barber Colman 7EF

48

Barber-Colman CompanyIndustrial Instruments Division1354 Clifford AvenueP.O. Box 2940Loves Park, IL U.S.A. 61132-2940

Telephone +1 800 232 4343Facsimile +1 815 637 5341http://www.barber-colman.com

A Siebe Group CompanyCopyright © 1997 Barber-Colman Company.