1489-A, AC Circuit Breakers
1489-D, DC Circuit Breakers
Bulletin 1489 UL489 Circuit BreakersTech Data
1489-A Standard AC Circuit Breaker1489-D DC Circuit Breaker
Bulletin 1489 UL 489 Circuit Breaker Specifications
Bulletin 1489-A Industrial Circuit Breaker for AC Applications
Specifications
Bulletin 1489-A Number of Poles 1, 2, and 3
Standards UL 489CSA C22.2 No. 5EN/IEC 60947-2
Certifications UL Listed Circuit Breaker (File Number E197878)CSA Certified, VDE Certified, CE Marked
HACR Rating (USA/Canada) Yes SWD Rating (USA/Canada) Yes (0.5...20 A) Calibration Temperature UL/CSA: 40 °C EN/IEC: 30 °C Rated Interrupting Capacity EN/IEC - Icu: 15 000 A
UL/CSA (See Below) Trip Curve Rated Current
(In)Interrupt Rating (UL/CSA)
C Curve 0.5...13 A 10,000 A 15...25 A 14,000 A 30...40 A 10,000 A
D Curve 0.5...10 A 10,000 A 13...20 A 14,000 A 25...40 A 10,000 A
Rated Tripping Current UL/CSA: 0.5...32 A, 480Y/277V AC0.5...40 A, 240V AC0.5…40 A 48V DC 1-pole0.5…40 A 96V DC 2-poleEN/IEC: 0.5...40 A, 415V AC 48V DC
Degree of Protection Finger-safe from front:-IP20 per IEC 529 from front-IP00 at wire terminals
Dielectric Strength 1960V AC Shock 25 G Half sine wave for 11 ms (3 axes) Vibration Frequency range: 10…200 Hz
Max. Amplitude (p-p) = 0.030 in.Max. Acceleration = 5 G2 hours each of 3 axes
Normal Operating Environment -25…+55 °C (-13...+131 °F) (non-condensing) Trip Curves C curve (Inductive) 5...10 IN
D curve (Highly Inductive) 10...20 IN
Shipment and Short-Term Storage Limits -40...+85 °C (-40...+185 °F) Wire Size 1 wire: #18...6 AWG
2 wires: #18...10 AWG Terminal Torque #18...12 AWG: 21 lb•in.
#10...8 AWG: 25 lb•in.#6 AWG: 36 lb•in.#2 PoziDriv
Recommended Wire Strip Length 0.5 in. (12 mm)
1
Bulletin 1489 UL 489 Circuit Breaker Specifications
Figure 1: Bulletin 1489-A Time Current Charateristic, UL
0.0005
Trip
ping
tim
e t [
sec]
7200
3600
1200
600
300
120
60
30
10
5
2
1
0.5
0.2
0.1
0.05
0.02
0.005
0.01
0.002
0.001
03 04 0551 022 3 4 5 6 7 8 9 011
acc. to IEC 60898-1
Instantaneous tripping
5454
3
12
1
2
t
nt
4
6
3
I = 1.0 I (T = 40 °C)
I = 1.35 I : t < 1 h (T = 25 °C)
2.0 I : t = 12 - 120 s (T = 25 °C)
10 I n : t < 0.1 s
20 I n : t < 0.1 s
conventional non-tripping current
conventional tripping current
type C: 5 I n : t > 0.1 s
type D: 10 I n : t > 0.1 s
Tripping characteristic acc. to UL 489
3
DC
n
n
n
Ambient Temperature 40 °C
2
Bulletin 1489 UL 489 Circuit Breaker Specifications
Figure 2: Bulletin 1489-A Power Loss at In
Figure 3: Bulletin 1489-A Internal Resistance (Room Temperature)
1p 2p 3p
In /A P* [W] P* [W] P* [W]
0.5 1.6 3.2 4.71 1.1 2.2 3.4
1.5 1.3 2.6 3.92 1.4 2.8 4.33 1.2 2.4 3.64 1.4 2.9 4.35 1.9 3.7 5.66 1.2 2.3 3.57 1.4 2.8 4.38 1.4 2.8 4.2
10 1.8 #3.6 5.313 2.4 4.7 7.115 1.9 3.8 5.616 2.1 4.3 6.420 2.9 5.8 8.725 3.1 6.2 9.330 3.0 6.0 9.032 3.4 6.8 10.235 3.7 7.4 11.040 4.0 8.1 12.1
*50Hz
C Characteristic
1p 2p 3p
In /A P* [W] P* [W] P* [W]
0.5 1.6 3.2 4.81 0.8 1.5 2.3
1.5 1.0 2.1 3.12 1.0 2.1 3.13 1.2 2.4 3.64 1.4 2.9 4.35 1.5 2.9 4.46 1.2 2.3 3.57 1.4 2.8 4.38 1.2 2.4 3.7
10 1.5 3.0 4.513 2.0 4.1 6.115 1.5 3.1 4.616 1.7 3.5 5.220 1.8 3.7 5.525 2.6 5.1 7.730 2.7 5.4 8.132 3.1 6.2 9.335 3.8 7.6 11.340 3.9 7.8 11.6
*50Hz
D Characteristic
In /A Z [mΏ]* R [mΏ]*
0.5 6400 63001 770 755
1.5 460 4502 250 2453 132 1304 86 855 57 566 31 307 28 278 18 17.6
10 13.5 13.213 10.5 10.315 5.9 5.816 5.9 5.820 4.0 3.925 3.4 3.330 2.5 2.532 2.5 2.535 2.5 2.540 2.0 2.0
*50Hz
D Characteristic
In /A Z [mΏ]* R [mΏ]*
0.5 6400 63001 1100 1080
1.5 560 5502 340 3303 132 1304 86 855 70 696 31 307 28 278 20 19.6
10 15.8 15.513 12.3 12.115 7.1 7.016 7.1 7.020 6.0 5.925 4.1 4.030 2.8 2.732 2.8 2.735 2.5 2.540 2.1 2.1
*50Hz
C Characteristic
3
Bulletin 1489 UL 489 Circuit Breaker Specifications
Figure 4: Bulletin 1489-A Influence of Ambient Temperature (T) on Load-Carrying Capacity
Bulletin 1489 Ambient Temperature DeratingCalibration Temperature 40º C (UL)Application below 0º C is for non-condensingatmosphere
Dev
ice
Mar
ked
Cur
rent
Rat
ing
[A]
@ 4
0 °C
Ambient Temperature (°C)
-25 -20 -10 0 10 20 30 35 40 45 50 55
0.5 0.6 0.6 0.6 0.6 0.6 0.5 0.5 0.5 0.50 0.5 0.5 0.5
1.0 1.3 1.2 1.2 1.2 1.1 1.1 1.0 1.0 1.0 1.0 1.0 0.9
1.5 1.9 1.9 1.8 1.7 1.7 1.6 1.6 1.5 1.5 1.5 1.4 1.4
2.0 2.5 2.5 2.4 2.3 2.2 2.2 2.1 2.0 2.0 2.0 1.9 1.9
3.0 3.8 3.7 3.6 3.5 3.4 3.2 3.1 3.1 3.0 2.9 2.9 2.8
4.0 5.0 5.0 4.8 4.6 4.5 4.3 4.2 4.1 4.0 3.9 3.8 3.8
5.0 6.3 6.2 6.0 5.8 5.6 5.4 5.2 5.1 5.0 4.9 4.8 4.7
6.0 7.5 7.4 7.2 7.0 6.7 6.5 6.2 6.1 6.0 5.9 5.8 5.6
7.0 8.8 8.7 8.4 8.1 7.8 7.6 7.3 7.1 7.0 6.9 6.7 6.6
8.0 10.0 9.9 9.6 9.3 9.0 8.6 8.3 8.2 8.0 7.8 7.7 7.5
10.0 12.6 12.4 12.0 11.6 11.2 10.8 10.4 10.2 10 9.8 9.6 9.4
13.0 16.3 16.1 15.6 15.1 14.6 14.0 13.5 13.3 13 12.7 12.5 12.2
15.0 18.8 18.6 18.0 17.4 16.8 16.2 15.6 15.3 15 14.7 14.4 14.1
16.0 20.1 19.8 19.2 18.6 17.9 17.3 16.6 16.3 16 15.7 15.4 15.0
20.0 25.1 24.8 24.0 23.2 22.4 21.6 20.8 20.4 20 19.6 19.2 18.8
25.0 31.4 31.0 30.0 29.0 28.0 27.0 26.0 25.5 25 24.5 24.0 23.5
30.0 37.7 37.2 36.0 34.8 33.6 32.4 31.2 30.6 30 29.4 28.8 28.2
32.0 40.2 39.7 38.4 37.1 35.8 34.6 33.3 32.6 32 31.4 30.7 30.1
40.0 43.9 43.4 42.0 40.6 39.2 37.8 36.4 35.7 35 34.3 33.6 32.9
Care should be taken for application below 0 °C. These devcies are notcertified to operate correctly in the presence of ice.
All other specifications for standard Bulletin 1489-A products remainunchanged.The ambient temperature derating applies to applications of the device as anIEC Miniature Circuit Breaker (MCB), following 60 947-2 and as Circuit Breaker to UL489/CSA 22.2 No 5.. Ambient temperature refers to the free air temperature in contact with the1489 device
4
Bulletin 1489 UL 489 Circuit Breaker Specifications
Figure 5: Bulletin 1489-A Maximum Let Through Energy
Type C (0.5-32 A) 277V
Prospective short-circuit current [A]
5000
6000
7000
8000
9000
1000
0
1500
0
1000
1500
2000
3000
400050
0
300
400
70000
50000
30000
15000
900
9000
7000
5000
3000
1500
700
500
Let-T
hrou
gh E
nerg
y I
² t² [
A se
c]80000
60000
40000
20000
10000
8000
6000
4000
2000
1000
800
600
C13C10
C2
C1,5
C8
C5
C0.5
C3C4
C6, C7
C15, C16
C30, C32
C20
C25
C1
5
Bulletin 1489 UL 489 Circuit Breaker Specifications
Figure 6: Bulletin 1489-A Maximum Let Through Energy
Type C (35-40 A) 240V
Prospective short-circuit current [A]
5000
6000
7000
8000
9000
1000
0
1000
1500
2000
3000
400050
0
300
400
70000
50000
30000
15000
900
9000
7000
5000
3000
1500
700
500
80000
60000
40000
20000
10000
8000
6000
4000
2000
1000
800
600
C35C40
2Le
t-Thr
ough
Ene
rgy
I t [A
sec
]2
6
Bulletin 1489 UL 489 Circuit Breaker Specifications
Figure 7: Bulletin 1489-A Maximum Let Through Energy
Type D (0.5-32 A) 277V
Prospective short-circuit current [A]
5000
6000
7000
8000
9000
1000
0
1500
0
1000
1500
2000
3000
400050
0
300
400
70000
50000
30000
15000
900
9000
7000
5000
3000
1500
700
500
80000
60000
40000
20000
10000
8000
6000
4000
2000
1000
800
600
Let-T
hrou
gh E
nerg
y I
² t² [
A se
c]
D15,D16
D30,D32
D13
D10D8
D2
D1.5
D6,D7
D5
D3
D4
D20D25
D0.5
D1
7
Bulletin 1489 UL 489 Circuit Breaker Specifications
Figure 8: Bulletin 1489-A Maximum Let Through Energy
Type D (35-40 A) 240V
Prospective short-circuit current [A]
5000
6000
7000
8000
9000
1000
0
1000
1500
2000
3000
400050
0
300
400
70000
50000
30000
15000
900
9000
7000
5000
3000
1500
700
500
80000
60000
40000
20000
10000
8000
6000
4000
2000
1000
800
600
D35
D40
2Le
t-Thr
ough
Ene
rgy
I t [A
sec
]2
8
Bulletin 1489 UL 489 Circuit Breaker Specifications
Figure 9: Bulletin 1489-A Maximum Let Through Current
Type C (0.5-32 A) 277V
Let-T
hrou
gh C
urre
nt I
LT
[A]
peak
10000
9000
1000
0
1500
0
9000
8000
7000
8000
7000
6000
5000
4500
4000
3500
3000
2500
2000
1500
1000
500
6000
5000
4000
3000
2000
1500
100050
0
C15, C
16C30, C
32
C20C25
C13
C0.5
C6, C7
C5
C1
C1.5C2
C3 C4
C10 C8
Prospective Short-Circuit Current [A]
9
Bulletin 1489 UL 489 Circuit Breaker Specifications
Figure 10: Bulletin 1489-A Maximum Let Through Current
Type C (35-40 A) 240V
LTLe
t-Thr
ough
Cur
rent
I
[A]
peak
Prospective Short-Circuit Current [A]
10000
9000
1000
090
0080
0070
00
8000
7000
6000
5000
4500
4000
3500
3000
2500
2000
1500
1000
500
6000
5000
4000
3000
2000
1500
100050
0C40
C35
10
Bulletin 1489 UL 489 Circuit Breaker Specifications
Figure 11: Bulletin 1489-A Maximum Let Through Current
Type D (0.5-32 A) 277V
Let-T
hrou
gh C
urre
nt I
LT
[A]
peak
Prospective Short-Circuit Current [A]
10000
9000
1000
0
1500
0
9000
8000
7000
8000
7000
6000
5000
4500
4000
3500
3000
2500
2000
1500
1000
500
6000
5000
4000
3000
2000
1500
100050
0
D8
D13D15, D
16D30, D
32
D20
D25D10
D6, D7
D5
D3
D2
D4
D1
D1.5
D0.5
11
Bulletin 1489 UL 489 Circuit Breaker Specifications
Figure 12: Bulletin 1489-A Maximum Let Through Current
Type D (35-40 A) 240V
LTLe
t-Thr
ough
Cur
rent
I
[A]
peak
Prospective Short-Circuit Current [A]
10000
9000
1000
090
0080
0070
00
8000
7000
6000
5000
4500
4000
3500
3000
2500
2000
1500
1000
500
6000
5000
4000
3000
2000
1500
100050
0
D40
D35
12
Bulletin 1489 UL 489 Circuit Breaker Specifications
Bulletin 1489-D Industrial Circuit Breaker for DC Applications
Specifications
Bulletin 1489-D Number of Poles 1, 2, and 3
Standards UL 489CSA C22.2 No. 5EN/IEC 60947-2
Certifications UL Listed Circuit Breaker (File Number E197878)CSA Certified, CE Marked
HACR Rating (USA/Canada) N/ASWD Rating (USA/Canada) N/A Calibration Temperature UL/CSA: 40 °C EN/IEC: 30 °C Rated Interrupting Capacity EN/IEC - Icu: 10 000 A
UL/CSA (See Below) Trip Curve Rated Current
(In)Interrupt Rating (UL/CSA)
C Curve 2...40 A 10,000 A Rated Tripping Current UL/CSA: 2...40 A,
-125V DC 1-pole-250V DC 2-pole
EN/IEC: 2...40 A, -250V DC 1-pole-500V DC 2-pole
Degree of Protection Finger-safe from front:-IP20 per IEC 529 from front-IP00 at wire terminals
Dielectric Strength 1960V AC Shock 25 G Half sine wave for 11 ms (3 axes) Vibration Frequency range: 10…200 Hz
Max. Amplitude (p-p) = 0.030 in.Max. Acceleration = 5 G2 hours each of 3 axes
Normal Operating Environment -25…+55 °C (-13...+131 °F) (non-condensing) Trip Curve C curve (Inductive) 7...15 INShipment and Short-Term Storage Limits -40...+85 °C (-40...+185 °F) Wire Size 1 wire: #18...6 AWG
2 wires: #18...10 AWG Terminal Torque #18...12 AWG: 21 lb•in.
#10...8 AWG: 25 lb•in.#6 AWG: 36 lb•in.#2 PoziDriv
Recommended Wire Strip Length 0.5 in.
13
Bulletin 1489 UL 489 Circuit Breaker Specifications
Figure 13: Bulletin 1489-D Circuit Diagram
1 pole 2 poles
14
Bulletin 1489 UL 489 Circuit Breaker Specifications
Figure 14: Bulletin 1489-D Time Current Charateristic, UL
0.0005
Trip
ping
tim
e t [
sec]
nI / I
7200
3600
1200
600
300
120
60
30
10
5
2
1
0.5
0.2
0.1
0.05
0.02
0.005
0.01
0.002
0.001
03 04 0551 022 3 4 5 6 7 8 9 011
C
1
2
t
nt
4
3
I = 1.0 In
I = 1.35 In : t < 1 h
2.0 In : t = 12 - 120 s
conventional non-tripping current
conventional tripping current
7 In : t > 0.1 s
Tripping Characteristic acc. to UL 489
15 In : t < 0.1 s
54
3
2
3
1
5
15
Bulletin 1489 UL 489 Circuit Breaker Specifications
Bulletin 1489-D Time Current Charateristic, IEC/EN
0.0005
Trip
ping
tim
e t [
sec]
nI / I
7200
3600
1200
600
300
120
60
30
10
5
2
1
0.5
0.2
0.1
0.05
0.02
0.005
0.01
0.002
0.001
03 04 0551 022 3 4 5 6 7 8 9 011
C
1
2
t
nt
4
3
I = 1.05 In : t > 1 h
I = 1.30 In : t < 1 h
conventional non-tripping current
conventional tripping current
7 In : t > 0.1 s
Tripping Characteristic acc. to IEC/EN 60947
15 In : t < 0.1 s
43
21
16
Bulletin 1489 UL 489 Circuit Breaker Specifications
Figure 15: Bulletin 1489-D Power Loss at In
Figure 16: Bulletin 1489-D Internal Resistance (Room Temperature)
1p 2p
In [A] P [W] P [W]
2 1.4 2.8
3 1.2 2.4
4 1.4 2.8
5 1.4 2.8
6 1.2 2.4
7 1.7 3.4
8 1.4 2.8
10 1.8 3.6
13 2.3 4.6
15 1.9 3.8
16 2.1 4.3
20 2.9 5.8
25 3.0 6.0
30 3.0 6.0
32 3.4 6.8
35 3.7 7.4
40 4.0 8.1
Type CC Characteristic
R [m ]In [A] [A]
2 341
3 128
4 84
5 56
6 31
7 28
8 21
10 16
13 12
15 7.0
16 7.0
20 5.9
25 4.2
30 2.7
32 2.7
35 2.5
40 2.1
/A
C Characteristic
17
Bulletin 1489 UL 489 Circuit Breaker Specifications
Figure 17: Bulletin 1489-D Influence of Ambient Temperature (T) on Load-Carrying CapacityBulletin 1489 Ambient Temperature DeratingCalibration Temperature 40º C (UL)Application below 0º C is for non-condensingatmosphere
Dev
ice
Mar
ked
Cur
rent
Rat
ing
[A]
@ 4
0 °C
Ambient Temperature (°C)
-25 -20 -10 0 10 20 30 35 40 45 50 55
0.5 0.6 0.6 0.6 0.6 0.6 0.5 0.5 0.5 0.50 0.5 0.5 0.5
1.0 1.3 1.2 1.2 1.2 1.1 1.1 1.0 1.0 1.0 1.0 1.0 0.9
1.5 1.9 1.9 1.8 1.7 1.7 1.6 1.6 1.5 1.5 1.5 1.4 1.4
2.0 2.5 2.5 2.4 2.3 2.2 2.2 2.1 2.0 2.0 2.0 1.9 1.9
3.0 3.8 3.7 3.6 3.5 3.4 3.2 3.1 3.1 3.0 2.9 2.9 2.8
4.0 5.0 5.0 4.8 4.6 4.5 4.3 4.2 4.1 4.0 3.9 3.8 3.8
5.0 6.3 6.2 6.0 5.8 5.6 5.4 5.2 5.1 5.0 4.9 4.8 4.7
6.0 7.5 7.4 7.2 7.0 6.7 6.5 6.2 6.1 6.0 5.9 5.8 5.6
7.0 8.8 8.7 8.4 8.1 7.8 7.6 7.3 7.1 7.0 6.9 6.7 6.6
8.0 10.0 9.9 9.6 9.3 9.0 8.6 8.3 8.2 8.0 7.8 7.7 7.5
10.0 12.6 12.4 12.0 11.6 11.2 10.8 10.4 10.2 10 9.8 9.6 9.4
13.0 16.3 16.1 15.6 15.1 14.6 14.0 13.5 13.3 13 12.7 12.5 12.2
15.0 18.8 18.6 18.0 17.4 16.8 16.2 15.6 15.3 15 14.7 14.4 14.1
16.0 20.1 19.8 19.2 18.6 17.9 17.3 16.6 16.3 16 15.7 15.4 15.0
20.0 25.1 24.8 24.0 23.2 22.4 21.6 20.8 20.4 20 19.6 19.2 18.8
25.0 31.4 31.0 30.0 29.0 28.0 27.0 26.0 25.5 25 24.5 24.0 23.5
30.0 37.7 37.2 36.0 34.8 33.6 32.4 31.2 30.6 30 29.4 28.8 28.2
32.0 40.2 39.7 38.4 37.1 35.8 34.6 33.3 32.6 32 31.4 30.7 30.1
40.0 43.9 43.4 42.0 40.6 39.2 37.8 36.4 35.7 35 34.3 33.6 32.9
Care should be taken for application below 0 °C. These devcies are notcertified to operate correctly in the presence of ice.
All other specifications for standard Bulletin 1489-A products remainunchanged.The ambient temperature derating applies to applications of the device as anIEC Miniature Circuit Breaker (MCB), following 60 947-2 and as Circuit Breaker to UL489/CSA 22.2 No 5.. Ambient temperature refers to the free air temperature in contact with the1489 device
18
Bulletin 1489 UL 489 Circuit Breaker Specifications
Figure 18: Bulletin 1489-D Maximum Let Through Energy
C35, C
40
C30, C
32
C25
C15, C
16, C
20
C10, C
13
C4, C5,
C6C7, C8
Prospective Short Circuit Current I [A]
5000
6000
7000
8000
9000
1000
0
1000
1500
2000
3000
400050
0
300
400
70000
50000
30000
15000
900
9000
7000
5000
3000
1500
700
500
80000
60000
40000
20000
10000
8000
6000
4000
2000
1000
800
600
acc. to IEC/EN 60947-2
Type C
C2, C3
19
Bulletin 1489 UL 489 Circuit Breaker Specifications
Figure 19: Bulletin 1489-D Maximum Let Through Current
acc. to IEC/EN 60947-2
Let-T
hrou
gh C
urre
nt I
LT
[
A] p
eak
Prospective Short-Circuit Current I [A]
10000
9000
1000
090
0080
0070
00
8000
7000
6000
5000
4500
4000
3500
3000
2500
2000
1500
1000
500
6000
5000
4000
3000
2000
1500
100050
0
C35, C40
C15, C16, C20
C6C7, C8C10, C13
C30, C32
C25
Type C
C2, C3
C4, C5
20
Publication 1489-TD001E-EN-P June 2011 Copyright ©2011 Rockwell Automation, Inc. All Rights Reserved. Printed in USA.Supersedes Publication 1489-TD001D-EN-P December 2010
Rockwell Automation and Allen-Bradley are trademarks of Rockwell Automation, Inc.