Cable Faults

Embed Size (px)

Citation preview

CABLE FAULTS

CABLE FAULTSCable fault refers to something that occurs and current cant flow smoothly. It is due to an open circuit or short circuit causing the current flow to be of a high value.Most faults are caused by dampness in the paper insulation of the cable due to porous or otherwise damaged lead sheath.The causes of damage to the lead sheath are: crystallization of the lead through vibration; chemical action on the lead when buried in the earth and insufficiently protected; mechanical damage.1CABLE FAULTSIn summary, what makes insulation go bad include:mechanical damage VibrationExcessive heat or coldDirtOilcorrosive vaporsMoisture or humidity.These enemies of insulation are at work as time goes on combined with the electrical stresses that exist.As pin holes or cracks develop, moisture and foreign matter penetrate the surfaces of the insulation, providing a low resistance path for leakage current.2CABLE FAULTSOnce started, the different enemies tend to aid each other, permitting excessive current through the insulation.Sometimes the drop in insulation resistance is sudden, as when equipment is flooded. Usually, however, it drops gradually, giving plenty of warning, if checked periodically. Such checks permit planned reconditioning before service failure. If there are no checks, a motor with poor insulation, for example, will becomedangerous to touch when voltage is applied, subject to burn out. What was good insulation has become a partial conductor.3CABLE FAULTSEquipment to determine cable fault is ohmmeter. Beside that, a few test can be done to determine cable faults such as:1. Continuity Test2. Insulation Resistance TestTYPES OF CABLE FAULTSThe faults which are most likely to occur in the cables are:Ground or Earth Faults (Break-down of cable insulation) When the insulation of the cable gets damaged, the current starts flowing from core to earth or to cable sheath.Short Circuit Faults When the insulation between two cables or between two cores of a multicore cable gets damaged, the current starts flowing from one cable to another cable or from one core to another core of a multi-core cable directly (without passing through load)TYPES OF CABLE FAULTSOpen Circuit Faults When the conductor of a cable is broken or joint is pulled out and there is no current in the cable.PROCEDURE TO FIND CABLE FAULT1. Testing (Analysis of fault)a. Continuity Test open circuit faultsb. Insulation Test short circuit faults

2. Locating cable fault from terminal cables.To find length of faults from testing station.

3. Confirmation fault point.To find actual location faults.

4. Repair the faultCABLE FAULTS TESTContinuity TestContinuity test is the checking for open circuit of cable faults. Usually, this test uses a bell and battery or multimeter. This test is divided into two types:1. Short alignment2. Long alignment

CABLE FAULTS TESTShort alignment

Short alignment for Continuity TestUses a bell and battery. This test is used for conduit types. For testing CC1 cables, a connection is made between C and C1 through a bell and battery. If a bell rings, the cable is in continues condition, and the cable is marked with C1 If the bell is not ringing, the cable is not in continues condition. For A and B cables, the same method is used to test the cable condition. CABLE FAULTS TESTLong AlignmentLong alignment for Continuity Test

The method is suitable to use for long cable.For cable A, B and C, choose a pair of cable, for example cable A and B will be connected with tester while the end of the same cable with short circuited. If the test shows an open circuit, the end of the cable will be changed with another pair and the circuit tested again.If a low reading is detected, the cables are label with A1 or B1. Then, connect one of the cables with another cable eg cable A and B, and test with the same method.

Insulation Resistance Test

Insulation Resistance Test

Megger Insulation testerCable under testInsulation Resistance between conductors and earthInsulation resistance between conductorsInsulation Resistance TestSometimes it is helpful to ground all conductors that are not part of the test. Why? ( Assignment)

Insulation Resistance TestPurpose of IR is to prove the quality of the insulating materials used in the installationInsulation should be such that there is no possibility of earth leakage currents between conductors conductors and the general mass of earth. The test voltage is d.c not less than twice the normal voltage of the supply (r.m.s value)For test on medium-voltage circuits the test voltage need not exceed 500V d.c.The minimum accepted value of IR is one Megohm.

Insulation Resistance TestIR value of an installation will not always remain the same.A good deal depends on the amount of moisture and dirt present at the time of testing.Deterioration of the insulation is usually due to:agingunsuitable operation conditions

Machine TestingElectrical Testing is an important factor in preventive maintenance.A breakdown however small:Cost moneyReplacement of equipmentLoss of productionLabour in rectifying the situationFires often accompany breakdownsRisk of electric shocks to personnelMost Electrical failures are attributed to Faulty electrical installation

Machine TestingPeriodic testing of machine has yielded valuable information for assessing trends in the condition of insulationResult of gradual deterioration of the insulation materials possibly initiated by mechanical damage which is further accelerated by the ingress of moisture and dirt into an imperfect dielectric.

Machine TestingNo.Condition Action1Fair to high values, well maintainedNo action2Fair to high values, with a downward tendencyLocate and correct the fault3Low values but well maintainedCondition is probably satisfactory4Low values, unsafeClean, dry out or otherwise raise the values before placing the equipment in service5Fair on high values previously well maintained but showing sudden dropTest should be made at frequent intervals until the cause of the low value is located and corrected; or until values have become steady at lower level but safe for operation. If the value so low that the equipment is unsafe, remove it from service and thoroughly overhaul.General observations on how Periodic Insulation Test can be interpreted together with the recommended Remedial Action Machine TestingWhen an apparatus is under test, the current flowing through has three components:Conductive leakage current (IL )Capacitive charging leakage current (IC )Polarization absorption leakage current (IA )

Machine TestingConductive leakage current (IL )Conductive current is a small (micro-amp) amount of current that normally flows through insulation, between conductors or from a conductor to ground.This current increases as insulation deteriorates and becomes predominant after the absorption current (Figure 1 below) vanishes.Because it is fairly steady and time independent, this is the most important current for measuring insulation resistance.

Machine TestingCapacitive charging leakage current (IC )When two or more conductors are run together in a raceway, they act as a capacitor. Due to this capacitive effect, a leakage current flows through conductor insulation. This current lasts only for a few seconds as the dc voltage is applied and drops out after the insulation has been charged to its full test voltage.

Machine TestingIn low-capacitance equipment, the capacitive current is higher than conductive leakage current, but usually disappears by the time we start recording the data. Because of this, it is important to let the reading settle out before recording it.On the other hand, when testing high capacitance equipment the capacitive charging leakage current can last for a very long time before settling out.

Machine TestingPolarization absorption leakage current (IA )Absorption current is caused by the polarization of molecules within dielectric material.In low-capacitance equipment, the current is high for the first few seconds and decreases slowly to nearly zero. When dealing with high capacitance equipment or wet and contaminated insulation, there will be no decrease in the absorption current for a long time.Machine Testing

Machine Testing The total current representing the three component currents will decrease with time and will reach a steady value only if the absorption current component also becomes steadyBecause the capacitive charging current falls to a low value in a comparatively short time, the effect often can be attributed to absorption current components.It is the effect of this component which will give an assessment of the state of the dielectric.In order to make use of this phenomenon, Resistance Test are carried out.Machine Testing Types of insulation resistance tests.Proof test (Assignment)Short time/spot reading test (Assignment)Time resistance test.Step voltage test.Machine TestingTime resistance test.This test method is based on taking successive readings at fixed time intervals, and then plotting the readings. This is an especially effective method when moisture and other contaminants might be present. As noted earlier, absorption current starts out high and gradually decreases over time as voltage is applied. In a machine with healthy insulation, this trend will continue for several minutes and show an increasing level of resistance. (See Fig below). On the other hand, if the insulation is poor, the level of resistance will flatten out after an initial burst.(See Fig below). Machine Testing

The best way to quantify the results of a time resistance test is through a dielectric absorption ratio. The dielectric absorption ratio consists of two time resistance readings. A commonly used set of intervals is a 60-second reading divided by a 30-second reading.Another frequently used set is a 10-minute reading divided by a 1-minute reading. This resulting value is referred to as the polarization index. The information summarized in the Table above providing general guidelines for interpreting dielectric absorption ratios.

Machine TestingStep voltage test. A step voltage test involves testing the insulation at two or more voltages and comparing the results.Good insulation will show a relatively consistent resistance reading regardless of the voltage applied.On the other hand, when the resistance level drops as the voltage level increases, it's usually an indication that the insulation is aging, contaminated, or brittle. This occurs because small imperfections like pinholes and cracks reveal themselves under increased electrical stress. When performing a step voltage test, it's important that you start with the lowest test voltage and then move to a higher voltage level. Test duration is typically 60 seconds. Direct Current Armature FaultsLOCALIZATION OF CABLE FAULT TESTSimple and basic methods to localize cable fault: Murray loop test, Varley loop testPulse Echo test These methods used basic equipment that are easily obtained.These tests are performed for the location of either an earth fault or short circuit fault in underground cable.Murray Loop test and Varley Loop Test employ the principle of Wheatstone bridge.

LOCALIZATION OF CABLE FAULT TESTAll the localisation tests normally involves some calculations of some kind and slide-rule accuracy is sufficient for tests on short length cables.Where cables are long, log tables or hand calculations are best for a really accurate pin-pointing of the fault position. Most common fault in a cable is a fault to earth, affecting either one or more cores.Open circuit faults and short circuit faults are much less common.The first step in the fault location procedure is to determine the characteristic of the fault,Murray Loop Test

Murray Loop Test Circuit.The circuit diagram to locate fault by Murray loop test method is shown in the figure above ( earth fault ).P and Q are two ratio arms consisting of resistors, G is a galvanometer, E is a battery and S1 is a battery key.Murray Loop Test Murray loop for location of ground fault.A known good conductor is joined to the faulty conductor at a convenient point beyond the fault but at a known distance from the test connection. One terminal of the test battery is grounded. The resulting Wheatstone bridge is then balanced by adjusting RB until a null is obtained. Ratio RA/RB is then known. For a circuit having a uniform ratio of resistance with length, circuit resistance is directly proportional to circuit length

Murray Loop Test Fig. Murray loop for location of ground fault.

2L-XX