78
i CRITICAL NOTE(S): WHAT NEXT? 1 N IF NO - CONTINUE to Q A 1 N B ANSWER ALL - Does this location: 1 Overall response is: Y B.1 Process wood? N 0 B.2 Manufacture wood products? n 0 B.3 N 0 B.4 Create wood chips, particles, or dusts? N 0 B.5 Make wood flour? N 0 B.6 Do industrial woodworking? N 0 B.7 Make furniture? N 0 B.8 Make plywood? N 0 B.9 Make composite board? N 0 B.10 A lumber mill? Y 1 B.11 N 0 1 Y Check the MY STAT C ANSWER ALL - Does ANY condition apply at your location? 1 Overall response is: Y ↓ START HERE - CAN YOU USE THIS CHECKLIST? ↓ You MUST assess your operation before using this checklist. IF ONLY Non-Combustible particulate Solids are at this location, or specific CANNOT be used for COMBUSTIBLE WOOD DUST at the location or specific area. Answer the questions below to determine you Question Number DETERMINATION, REQUIREMENT, OBSERVATION, MEASUREMENT STATUS Y for YES, N for NO Does this location have ONLY Non-Combustible particulate Solids? Wood Dust IS COMBUSTIBLE. If you generate Wood Dust, and you MUST answer Question A as "NO". You must also answer Question B. NFPA 91→ ANSWER ALL the questions below first to determine IF your location can use this Combustible Dust Checklist. The overall answer will appear for you in the STATUS column. Doing anything with wood qualifies as a "process". DON'T enter this value - It appears automatically based on question responses. IF NO - STOP HERE - You don this checklis NFPA 664→ Use wood or cellulosic fiber as a substitute for or additive to wood fiber? Do production woodworking and carpentry that is incidental to the operation that would not otherwise fall under NFPA 664? ANSWER ALL the questions below to determine IF your location can use this Combustible Dust Checklist. The overall answer will appear for you in the STATUS column. Doing anything with wood qualifies as a "process". DON'T enter this value - It appears automatically based on question responses. NFPA 664→

CD Inspection Checklist - Occupational Safety and Health … · XLS file · Web view2012-11-05 · INSPECTION CHECKLIST COMBUSTIBLE DUST INSPECTION CHECKLIST Y ... This checklist

  • Upload
    doanbao

  • View
    316

  • Download
    5

Embed Size (px)

Citation preview

Page 1: CD Inspection Checklist - Occupational Safety and Health … · XLS file · Web view2012-11-05 · INSPECTION CHECKLIST COMBUSTIBLE DUST INSPECTION CHECKLIST Y ... This checklist

i

CRITICAL NOTE(S): WHAT NEXT?

1

N IF NO - CONTINUE to Question BA

1

NB

ANSWER ALL - Does this location: 1 Overall response is: Y

B.1 Process wood? N 0B.2 Manufacture wood products? n 0B.3 Use wood or cellulosic fiber as a substitute for or additive to wood fiber? N 0B.4 Create wood chips, particles, or dusts? N 0B.5 Make wood flour? N 0B.6 Do industrial woodworking? N 0B.7 Make furniture? N 0B.8 Make plywood? N 0B.9 Make composite board? N 0

B.10 A lumber mill? Y 1

B.11 N 01

Y Check the MY STATUS box belowC

ANSWER ALL - Does ANY condition apply at your location? 1 Overall response is: Y

↓ START HERE - CAN YOU USE THIS CHECKLIST? ↓

You MUST assess your operation before using this checklist. IF ONLY Non-Combustible particulate Solids are at this location, or specific area, this checklist CANNOT be used for COMBUSTIBLE WOOD DUST at the location or specific area. Answer the questions below to determine your status.

Question Number

DETERMINATION, REQUIREMENT, OBSERVATION, MEASUREMENT

STATUS Y for YES, N

for NO

Does this location have ONLY Non-Combustible particulate Solids?

Wood Dust IS COMBUSTIBLE. If you generate Wood Dust, and you

MUST answer Question A as "NO". You must also answer

Question B. ↓NFPA 91→

ANSWER ALL the questions below first to determine IF your location can use this Combustible Dust Checklist. The overall answer will appear for you in the STATUS column.

Doing anything with wood qualifies as a "process". DON'T

enter this value - It appears automatically based on question

responses. →

IF NO - STOP HERE - You don’t qualify for this checklist

NFPA 664→

Do production woodworking and carpentry that is incidental to the operation that would not otherwise fall under NFPA 664?

ANSWER ALL the questions below to determine IF your location can use this Combustible Dust Checklist. The overall answer will appear for you in the STATUS column.

Doing anything with wood qualifies as a "process". DON'T

enter this value - It appears automatically based on question

responses. →NFPA 664→

A34
INSTRUCTIONS FOR DOCUMENT USERS: 1-READ and REVIEW the content of this section. 2-RESPOND to Questions A & B to see if you can use this checklist.
Page 2: CD Inspection Checklist - Occupational Safety and Health … · XLS file · Web view2012-11-05 · INSPECTION CHECKLIST COMBUSTIBLE DUST INSPECTION CHECKLIST Y ... This checklist

C.1 Y 1 You are Subject to NFPA 664-Proceed to Question C.2

C.2 N 0

i 0

X←OR→

0

i START HERE - This is The BEGINNING of the Initial Self-Assessment CHECKLIST

RESULTS SECTION - 1Initial: 50% 10

NFPA 77 - RECOMMENDED PRACTICE ON STATIC ELECTRICITYNFPA 79 - ELECTRICAL STANDARD FOR INDUSTRIAL MACHINERY

F1.1 F1.1 F1.3 F1.4 F1.5 F1.6 F1.7 F1.8 F1.9 F1.1010 500%

100% 100% 100% 100% 100% 100% 100% 100% 100% 100%1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 1.10

50%Follow-Up: 100% 10 100% 0% 0% 0% 100% 100% 100% 100% 0% 0%

FOCUS on STATIC ELECTRICITY and MACHINERY FIX WHAT? When? Who?100%

10 1000%

i 1 ANY UNGROUNDED, CONDUCTIVE objects?

N 100% NO FIX NEEDED

When? Who?

N 100%

This location conducts woodworking operations that occupy areas which equal or exceed 5000 square feet (Ft2) which is equivalent to 465 square meters (M2). (Length X Width = 5,000 ft2 OR 465 M2)

This location operates production equipment requiring a total dust collection air flow rate of 1500 cubic feet per minute (Ft3/Min) which is equal to 2549 cubic meters per hour (M3/Hr).

IF you have no dust collection equipment OR have reduced design flow, you may STILL be subject to NFPA 664 & OSHA requirements

MY STATUS

MY LOCATION IS NOT COVERED BY NFPA 664 (Regarding Wood Dust). IT MAY BE COVERED BY THE COMBUSTIBLE DUST

COMPLIANCE DIRECTIVE AS SOME OTHER TYPE OF DUST. I CANNOT USE THIS

CHECKLIST FOR WOOD DUST. I will need to Check NFPA 91 and 654 for applicable

requirements.

MY LOCATION IS COVERED BY NFPA 664 AND THE COMBUSTIBLE DUST

COMPLIANCE DIRECTIVE. I CAN USE THIS CHECKLIST. I will complete the sections below to identify my percent readiness for minimizing Combustible Wood Dust.

←MY STATUS

CAUTION! The following NFPA Codes are extensive and cannot be adequately summarized within this checklist. As an alternative, common electrical problems that can generate or become ignition sources will be summarized. Their code compliant solution MUST be retrieved and MUST meet the applicable code requirements in the applicable NFPA code.

FOLLOW-UP SCORES

Question Number

A80
INSTRUCTIONS FOR DOCUMENT USERS: 1-This section shows the RESULTS of your coverage by this checklist. 2-IF you can use it, BEGIN at Section 1 and continue until you either EXIT OUT, or until the End of Checklist indicator.
A89
INSTRUCTIONS FOR DOCUMENT USERS: 1-BEGIN HERE. Please note that several of the questions might seem to be duplicates, but they are under different NFPA codes or OSHA Standards. 2-Complete all questions asked. You only have to be concerned with the INITIAL results. 3-Later on, Follow-Up Scores will be completed and the total of 2 results will be compared.
A106
INSTRUCTIONS FOR DOCUMENT USERS: 1-Respond to each question by entering a capital Y for "YES", or N for "NO" 2-IF the item is deficient, it needs to be FIXED. This is the SAME a preventive or corrective action. Put an entry under "FIX WHAT"? That describes what needs to be corrected. Example: replace wiring having worn thru insulation. 3- Under the "WHEN"? column, list the date the FIX WHAT will be done. 4-Under the "WHO"? column, list who will do it. Example: Larry the Maintenance guy. 5-Also notice that the "Follow-Up Scores" in the gray box have blackout areas below it. These are the follow-up responses for later use. leave them hidden for now.
Page 3: CD Inspection Checklist - Occupational Safety and Health … · XLS file · Web view2012-11-05 · INSPECTION CHECKLIST COMBUSTIBLE DUST INSPECTION CHECKLIST Y ... This checklist

1.1 Where? N 100% NO FIX NEEDED N 100%

1 ANY evidence of STATIC Electricity (e-) accumulation?

Y 0%

When? Who?

N 100%1.2 Where?

1 ANY suspended (wood) dust in air?

Y 0%

When? Who?

N 100%1.3 Where?

1 ALL conductive bag house parts always grounded?

N 0%

When? Who?

Y 100%1.4 Where?

1

Y 100% NO FIX NEEDED

When? Who?

Y 100%1.5

1 Is the design and e- power supply correct for all machinery?

Y 100% NO FIX NEEDED

When? Who?

Y 100%1.6 Where?

i1 Are ground terminals & enclosed local disconnects present for machinery?

Y 100% NO FIX NEEDED

When? Who?

Y 100%1.7 List ONLY if missing:

1

Y 100% NO FIX NEEDED

When? Who?

Y 100%1.8 List ONLY if missing:

1 Are over current protection devices in place?

N 0%

When? Who?

Y 100%1.9 List ONLY if missing:

1 Is ALL equipment electrically grounded?

N 0%

When? Who?

Y 100%

NFPA 77→

Find static e sources & Minimize

NFPA 77→

Control accomulation and

apply Housekeeping

NFPA 77→

Check and fix ground on conductive

baghousesNFPA 77→

NON-NFPA - Has a qualified electrician been consulted for ways to reduce or prevent static e-discharge(s)?

NFPA 77→

NFPA 79→

NFPA 79→

Are LIVE electrical parts at or above 50 Volts guarded against contact (including by insulation)?

NFPA 79→

Install overcurrent devices as needed

NFPA 79→

Test & Ground all electrical

equipment as needed

C110
Per NFPA, Static e- accumulates on or about the following: 1-Moving belts over pulleys. 2-"Flyaway Hair" on persons near moving processed materials. 3-DRY AIR conditions - naturally, or at Dryers, Kilns, etc. 4-Flowing liquids or bulk solids. 5-Plastic sheeting or wraps. 6-Ductwork containing rigid or plastic components. 7-Materials made of rubber, plastic, metal.
A129
INSTRUCTIONS FOR DOCUMENT USERS: 1-Each NFPA Code relating to the questions is identified. This one is highlighted in yellow because a different code applies.
Page 4: CD Inspection Checklist - Occupational Safety and Health … · XLS file · Web view2012-11-05 · INSPECTION CHECKLIST COMBUSTIBLE DUST INSPECTION CHECKLIST Y ... This checklist

1.10 List ONLY if missing: N 0% Y 100%

RESULTS SECTION - 2Initial: 63% 8

NFPA 70 - NATIONAL ELECTRIC CODENFPA 70E - STANDARD FOR ELECTRICAL SAFETY IN THE WORKPLACE

F2.1 F2.2 F2.3 F2.4 F2.5 F2.6 F2.7 F2.8 F2.98 500%

0% 0% 0% 0% 0% 100% 100% 100% 0%2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.8 2.9

63%Follow-Up: 38% 8 0% 100% 100% 100% 0% 0% 0% 200% 0%

FOCUS on GENERAL ELECTRICAL HAZARDS - Conduit, Electrical Panels, etc. FIX WHAT? When? Who?38%

8 300%

1 ANY energized damaged electrical conduits?

y 0% Repair or Replace

When? Who?

Y 0%2.1 List ONLY if missing:

1 ANY exposed breakers within a breaker panel?

N 100% NO FIX NEEDED

When? Who?

Y 0%2.2 List ONLY if missing:

1 ANY SUBSTANDARD electrical repairs?

N 100% NO FIX NEEDED

When? Who?

Y 0%2.3 List ONLY if missing:

1 ANY exposed wiring that could short, or cause a spark?

N 100% NO FIX NEEDED

When? Who?

Y 0%2.4 List ONLY if missing:

1

Y 0%

When? Who?

Y 0%

Test & Ground all electrical

equipment as needed

NFPA 79→

CAUTION! NFPA 70 & 70E Codes are extensive and cannot be adequately summarized within this checklist. Equivalently, look for common electrical problems that are ignition sources. Code compliant solution MUST be retrieved and meet the applicable NFPA requirements.

NFPA 499 - RECOMMENDED PRACTICE FOR THE CLASSIFICATION OF COMBUSTIBLE DUSTS AND OF HAZARDOUS (CLASSIFIED) LOCATIONS FOR ELECTRICAL INSTALLATIONS IN CHEMICAL PROCESS AREAS

Follow-Up Scores↓

Question Number

NFPA 70→

NFPA 70→

NFPA 70→

NFPA 70→ANY electrical conditions that can cause material ignition? (consult electrician)

Repair and Upgrade to Code

D150
WHY is this number 8, and not 9? There are 9 questions, BUT only 1 set of responses from EITHER 2.8 or 2.9 is counted. This means that the number of subsections is effectively 8, NOT 9.
Page 5: CD Inspection Checklist - Occupational Safety and Health … · XLS file · Web view2012-11-05 · INSPECTION CHECKLIST COMBUSTIBLE DUST INSPECTION CHECKLIST Y ... This checklist

2.5 List ONLY if missing: Y 0% Y 0%

1

Y 0%

When? Who?

N 100%2.6 List ONLY if effectiveness voided:

1

N 0%

When? Who?

Y 100%2.7

1

Y 200%

When? Who?

N 100%i 2.8

ANSWER ALL - Do ANY of the following exist? 1 Overall response is: 200% When? Who? 1 100%

1

N 0% 499 Does Not Apply N 0%2.8.1

1Can or is the dust released into the atmosphere or accumulated on surfaces? Y 100% N 0%

2.8.2

1Are there sources of ignition, such as electrical systems or equipment? Y 100% N 0%

2.8.3

1

Y 0% N 100%2.8.4

1

N 0% 499 Does Not Apply N 0%2.9

i DETERMINATION - EXIT CHECKLIST OR FIRE TRIANGLE CONDITIONS?

Repair and Upgrade to Code

NFPA 70→

At hazardous locations (in hazardous Atmospheres) are there ARE equipment breaks that void effectiveness? (IF NO hazardous locations, answer NO) SEE OSHA 1910.307 Repair-Upgrade-

Check against Code

NFPA 70E→

Is HOT WORK controlled by a permit system? (Both NFPA & OSHA 1910.252 apply) Implement written program-Formulate procedures-Acquire equipment & Train

employeesNFPA 70E→

Answer the Questions below FIRST to DETERMINE your location's status under NFPA 499. It ONLY APPLIES IF the area under review is ALSO A CHEMICAL PROCESS AREA. Is your location subject to NFPA 499?

Don't ENTER this

value→

499 Applies-REFER to NFPA for Specific

Requirements

NFPA 499→

is there a DUST that is produced, processed, handled, or likely to be at this area that's under review?

499 May Apply if area is also a Chemical Process

Area

499 May Apply if area is also a Chemical Process

Area

Is this area ALSO A CHEMICAL PROCESS AREA? (IF YES, Consult NFPA 499 for code specifics. Also answer Question 2.9. (NOTE: Chemical Process Areas are not common, and go significantly beyond the scope of this checklist)

499 Applies-CHECK Specific Requirements

IF NFPA 499 APPLIES, is this location meeting ALL REQUIRMENTS?

NFPA 499→

C192
What defines a "CHEMICAL PROCESS AREA"? Under NFPA 499, a "Chemical Process Area" is an area that: 1-
A193
INSTRUCTIONS FOR DOCUMENT USERS: 1-This is a type of question that DEPENDS on the existence of conditions, processes, or equipment. 2-Go to the ANSWER ALL section below and respond to those questions. The letters are in BLUE to show they're to be done first. The OVERALL RESPONSE will automatically be calculated for you. 3-In a question of this type, DO NOT attempt to enter the overall response which is indicated in red. This value is filled in for you. If this is done, you'll either have to repair the formula (difficult if you're not familiar with excel) or start over.
A216
INSTRUCTIONS FOR DOCUMENT USERS: 1-The checklist questions are listed in a specific order. At this point in the checklist, you either have an opportunity to EXIT OUT because you don't have enough of the conditions present, or you have conditions that are at least enough for a FIRE HAZARD. 2-If you are able to exit out - CONGRATULATIONS! You don't have the conditions and / or you're 100% prepared! 3-If you have FIRE TRIANGLE conditions, proceed. You'll need to finish out this checklist to see what other conditions can develop.
Page 6: CD Inspection Checklist - Occupational Safety and Health … · XLS file · Web view2012-11-05 · INSPECTION CHECKLIST COMBUSTIBLE DUST INSPECTION CHECKLIST Y ... This checklist

DETERMINATION - EXIT CHECKLIST OR FIRE TRIANGLE CONDITIONS?

56% X69% X

RESULTS SECTION - 3Initial: 21% 11

NFPA 68 - EXPLOSION PROTECTIONS BY DEFLAGRATION VENTING

NFPA 69 - STANDARD ON EXPLOSION PREVENTION SYSTEMS

NFPA 664 - STANDARD FOR THE PREVENTION OF FIRES AND EXPLOSIONS IN WOOD PROCESSING AND WOODWORKING FACILITIES

Follow-Up: 50% 11i F3.1 F3.2 F3.3 F3.4 F3.5 F3.6 F3.7 F3.8 F3.9 F3.10 F3.11

11% 63% 60% 60% 20% 29% 70% 80% 100% 54%3.1 3.2 3.3 3.4 3.5 3.6 3.7 3.8 3.9 3.10 3.11

33% 13% 80% 60% 0% 6% 9% 0% 33% 0%1

33%

When? Who?

11%3.1

ANSWER ALL - Do ANY of the following exist? 9 Overall response is: 300% When? Who? 9 100%

IF sufficient conditions DO NOT EXIST, FIRE, DEFLAGRATION, or EXPLOSION CANNOT result. However, Oxygen, Heat, and Fuel results in a FIRE HAZARD.

Cumulative "Percent Prepared" & Hazard Condition Indicated

by "X" is:

FOLLOW-UP Cumulative "Percent Prepared" & Hazard Condition Indicated

by "X" is:

NFPA 654 - STANDARDS FOR THE PREVENTION OF FIRE AND DUST EXPLOSIONS FROM THE MANUFACTURING, PROCESSING, AND HANDLING OF COMBUSTIBLE PARTICULATE SOLIDS

Follow-Up Scores↓

The following questions apply to NFPA 68, 69, and 664. Answer the questions below FIRST to determine if NFPA 68 specifics apply, then continue through the questions.

IF you produce WOOD DUST, AND you have a bag house or ANY OTHER type of enclosure,

You MUST answer YES.

←Percentage for this Question

NFPA 68→

A245
INSTRUCTIONS FOR DOCUMENT USERS: 1-DON'T delete or change ANY of the black shaded checklist areas. They contain the formulas that drive the checklist!
C249
What defines a "CHEMICAL PROCESS AREA"? Under NFPA 499, a "Chemical Process Area" is an area that: 1-
Page 7: CD Inspection Checklist - Occupational Safety and Health … · XLS file · Web view2012-11-05 · INSPECTION CHECKLIST COMBUSTIBLE DUST INSPECTION CHECKLIST Y ... This checklist

ANSWER ALL - Do ANY of the following exist? 9 Overall response is: 300% When? Who? 9 100%

1

N 100% N 100%3.1.1

1

N 100% Y 0%3.1.2

1

N 100% Y 0%3.1.3

1Were engineering controls IN PLACE during the event? N 0% Y 0%

3.1.4

1Did the engineering controls activate during the event? N 0% N 0%

3.1.5

1

N 0% N 0%3.1.6

1

N 0% N 0%3.1.7

1Were enclosures evaluated for needed engineering controls per NFPA 68? n 0% N 0%

3.1.8

1

N 0% N 0%3.1.9

1

13%

When? Who?

63%3.2

ANSWER ALL - Do ANY of the following exist? 8 100% When? Who? 8 500%

Are there any ENCLOSURES where combustible wood dust is present? (If NO, NFPA 68 does not apply. Skip to NFPA 69, AT QUESTION #5)

NFPA 68 Does not apply. OTHER NPFA Codes may

apply

Are there ANY IGNITION SOURCES that can possibly reach the inside of a process enclosure?

NFPA 68 Does not apply. OTHER NPFA Codes may

apply

Prior to today, was there a deflagration or explosion event involving combustible wood dust?

VERIFY requirements met

Implement controls specified under NFPA 664 and other codes

Determine reason for non-activation and

correct it

Are the engineering controls on a periodic maintenance and testing schedule?

Implement periodic maintenance and testing

schedule & doucmentation

IF Engineering Controls ARE NOT CURRENTLY IN PLACE, was NFPA 68 reviewed in detail by representatives of your company? (If already in place, answer Y for YES)

Review NFPA 68 in detail as required.

Evaluate enclosures per NFPA

IF Engineering Controls ARE NOT CURRENTLY IN PLACE, has an installation date for them been scheduled?

Determine an installation date after review with AHJ and

others

ANSWER the questions below to determine your location's status. NFPA 69 ONLY APPLIES IF you have listed conditions.

Don't Enter this value - it automatically appears

based on question responses →

←Percentage for this Question

NFPA 69→

C284
What defines a "CHEMICAL PROCESS AREA"? Under NFPA 499, a "Chemical Process Area" is an area that: 1-
Page 8: CD Inspection Checklist - Occupational Safety and Health … · XLS file · Web view2012-11-05 · INSPECTION CHECKLIST COMBUSTIBLE DUST INSPECTION CHECKLIST Y ... This checklist

1

Y 0% NFPA 69 Applies Y 100%3.2.1

1

N 0% N 0%3.2.2

1

Are there ENGINEERING CONTROLS present? N 0% N 0%3.2.3

1

Were the controls acceptance tested? N 0% Y 100%3.2.4

1

N 0% Y 100%3.2.5

1

N 0% Y 100%3.2.6

1

Y 100% Maintain as required N 0%3.2.7

1

Does the system allow for automatic shutdown? N 0% Y 100%3.2.8

1

80%

When? Who?

60%3.3

Does a DEFLAGRATION hazard exist? (IF you produce WOOD DUST, and it can become airborne, you MUST answer YES. IF YES, continue. IF NO, STOP HERE! NFPA 69 DOES NOT APPLY. Skip to Question 3.3)

Has the design basis of the deflagration scenario been identified and documented?

MUST identify & document design basis of deflagration scenario

ALL controls MUST be either or both-specify

Controls MUST be acceptance tested

Are the controls on a periodic inspection & maintenance schedule (Additional requirement under NFPA 664)

Controls MUST be periodically inspected

and maintained

Is location aware of required housekeeping under NFPA 654 or 664? (detailed elsewhere in this checklist)

Housekeeping under NFPA 654 OR 664 MUST

be applied

Has the engineering control system been checked against NFPA requirements for Operation, Maintenance, and Safety requirements?

Automatic system shutdown MUST be

required

Do the ENGINEERING CONTROLS use ANY of the following detection system(s) or methods?

Don't Enter this value - it automatically appears

based on question responses →

←Percentage for this Question

Page 9: CD Inspection Checklist - Occupational Safety and Health … · XLS file · Web view2012-11-05 · INSPECTION CHECKLIST COMBUSTIBLE DUST INSPECTION CHECKLIST Y ... This checklist

3.3 80% 60%

ANSWER ALL - Do ANY of the following exist? 5 Overall response is: 400% When? Who? 5 300%

1

Y 100% Y 100%3.3.1

1Is there a DEFLAGRATION PASSIVE ISOLATION SYSTEM in place? Y 100% Y 100%

3.3.2

1Is there a DEFLAGRATION PRESSURE CONTAINMENT SYSTEM in place? Y 100% Y 100%

3.3.3

1Is there a DEFLAGRATION PRESSURE CONTAINMENT SYSTEM in place? Y 100% N 0%

3.3.4

1

N 0% N 0%3.3.5

1 NFPA 664 Chapter 4 - General Requirements

60%

When? Who?

60%3.4

ANSWER ALL - Do ANY of the following exist? 10 Overall response is: 600% When? Who? 10 600%

1

N 0% Y 100%3.4.1

1

Y 100% Requirement Met Y 100%3.4.2

1

n 0% Y 100%3.4.3

1

Y 100% Requirement Met Y 100%

Do the ENGINEERING CONTROLS use ANY of the following detection system(s) or methods?

Don't Enter this value - it automatically appears

based on question responses →

←Percentage for this Question

NFPA 69→

Are DEFLAGRATION SUPPRESSION AND EXPLOSION VENTING components also used?

Component indicated as present-verify its

appropriate

Component indicated as present-verify its

appropriate

Component indicated as present-verify its

appropriate

Component indicated as present-verify its

appropriate

Does the CONTROL SYSTEM use Oxidant Reduction Concentration to prevent combustion? (see comment notes)

Check NFPA 69 to verify if component is needed

Don't Enter this value - it automatically appears

based on question responses →

←Percentage for this Question

These questions assess the design of the fire and deflagration safety provisions at the location. Consult NFPA 664 for definitions and specific details.NFPA 664→

PROCESS ANALYSIS - is the design, physical and chemical properties, and documented results, maintained for the life of the process & and on location?

Implement PROCESS ANALYSIS

MANAGEMENT of CHANGE (MOC) - Are there written procedures to manage the change of process materials, technology, equipment, procedures, and facilities?

Does (MOC) Include - Technical basis of Changes, Safety & Health Implications, Temporary-Permanent, Procedure Modifications, Employee Training, Authorization requirements for proposed change?

UPGRADE to meet all requirements

DESIGNER & INSTALLER QUALIFICATIONS - Are systems designed and installed under the supervision of a knowledgeable, Qualified Engineer?

Page 10: CD Inspection Checklist - Occupational Safety and Health … · XLS file · Web view2012-11-05 · INSPECTION CHECKLIST COMBUSTIBLE DUST INSPECTION CHECKLIST Y ... This checklist

3.4.4 Y 100% Requirement Met Y 100%

1

Y 100% Requirement Met Y 100%3.4.5

1

Y 100% Requirement Met Y 100%3.4.6

1

N 0% N 0%3.4.7

1

Y 100% Requirement Met N 0%3.4.8

1

N 0% N 0%3.4.9

1

Y 100% Requirement Met N 0%3.4.10

1

N 0% N 10%

i 0% 20%

0% 10%

1 NFPA 664 Chapter 5 - Performance-Based Design Option

0%

When? Who?

10%3.5

DESIGNER & INSTALLER QUALIFICATIONS - Are systems designed and installed under the supervision of a knowledgeable, Qualified Engineer?

LIFE SAFETY - Is the design, construction, & equipment maintained to prevent building occupants from Fire / Deflagration / Explosion?

LIFE SAFETY - Is the structure located, designed, constructed, & maintained to prevent propagation of Fire / Deflagration?

LIFE SAFETY - Is structure designed, constructed, & equipped to maintain Structural Integrity in spite of the effects of Fire / Deflagration?

UPGRADE to meet all LIFE SAFETY

requirements-SEE NFPA 101

MITIGATION of FIRE SPREAD & EXPLOSIONS - are there sufficient safeguards to prevent failure of adjacent building compartments?

COMPLIANCE OPTIONS - PERFORMANCE BASED - Is the design documented with calculations, references and sources, per NFPA 101 (Life Safety Code) and NFPA 664 (Chapter 5)?

ACQUIRE missing items and create

documentation

COMPLIANCE OPTIONS - PRESCRIPTIVE BASED - does the design meet the requirements of NFPA 664 - Chapters 6 through 11?

REVIEWER(S) - EITHER Performance based system

questions at 3.5 OR Prescriptive based system questions at 3.6 APPLIES - CHOOSE one then ONLY

ANSWER the questions in that section!

What→ type of

system does this location

have?

This location has a Performance Based System - I want questions

in 3.5 to apply.

IF NO-This location MUST be a Prescriptive System-ONLY ANSWER the

Questions at 3.6 & skip 3.5

←total value cell

DO NOT manually enter value - it ↗ will automatically appear OR remain the

same based on your responses

Don't Enter this value - it automatically appears

based on question responses →

←Percentage for this QuestionThese questions assess the Performance Based Design Option at

the location. Consult NFPA 664 for definitions and specific details.NFPA 664→

Page 11: CD Inspection Checklist - Occupational Safety and Health … · XLS file · Web view2012-11-05 · INSPECTION CHECKLIST COMBUSTIBLE DUST INSPECTION CHECKLIST Y ... This checklist

ANSWER ALL - Do ANY of the following exist? 10 0% When? Who? 10 100%

1

N 0% Y 100%3.5.1

1

N 0% N 0%3.5.2

1

N 0% N 0%3.5.3

1

N 0% N 0%3.5.4

1

N 0% N 0%3.5.5

1

N 0% N 0%3.5.6

1

N 0% N 0%3.5.7

1

N 0% N 0%3.5.8

1

N 0% N 0%3.5.9

1

N 0% N 0%3.5.10

1 NFPA 664 Chapter 6 - Building Construction

0%

When? Who?

10%3.6

APPROVED QUALIFICATIONS & INDEPENDENT REVIEW - Was design prepared by a person acceptable to the Authority Having Jurisdiction (AHJ)?

VERIFY acceptability with Authority Having

Jurisdiction-AHJ

INDEPENDENT REVIEW - IF REQUIRED by the AHJ, was the design REVIEWED by an independent 3rd Party? (If NOT REQUIRED, answer Y for YES)

VERIFY requirement with Authority Having Jurisdiction-AHJ

DATA SOURCES - Have data sources for design aspects been identified?VERIFY Data Sources &

Design Aspects with Authority Having Jurisdiction-AHJ

DESIGN FEATURES MAINTAINED - Are they maintained for operation as originally designed, or modified with AHJ approval?

Maintain design features or obtain AHJ approval

for change

PREVENTION of IGNITION - Has the NFPA criteria been met? Prevent ignition per NFPA criteria

PREVENTION of FIRE EXTENSION - Has the NFPA criteria been met?Implement controls to

prevent fire from spreading

EFFECTS of DEFLAGRATION - Has the NFPA criteria been met?Implement controls to

prevent effects of deflagration-SEE NFPA

664

DESIGN FIRE SCENARIOS - Has the NFPA criteria been met? Perform Design Fire Scenarios per NFPA 664

DEFLAGRATION SCENARIOS - Has the NFPA criteria been met? Perform Deflagration Scenarios per NFPA 664

EVALUATION of PROPOSED DESIGN - Did the AHJ approve all items identified by NFPA 5.4?

Obtain AHJ Evaluation of proposed design NFPA

664- at 5.4

Don't Enter this value - it automatically appears

based on question responses →

←Percentage for this Question

These questions assess the Prescriptive Based Design Option for Building Construction at the location. Consult NFPA 664 for definitions and specific details.

Page 12: CD Inspection Checklist - Occupational Safety and Health … · XLS file · Web view2012-11-05 · INSPECTION CHECKLIST COMBUSTIBLE DUST INSPECTION CHECKLIST Y ... This checklist

0% 10%

ANSWER ALL - Do ANY of the following exist? 10 Overall response is: 0% When? Who? 10 100%

1

N 0% Y 100%3.6.1

1

N 0% N 0%3.6.2

1

N 0% N 0%3.6.3

1

N 0% N 0%3.6.4

1

N 0% N 0%3.6.5

1

N 0% N 0%3.6.6

1

N 0% N 0%3.6.7

1

N 0% N 0%3.6.8

1

N 0% N 0%3.6.9

1

N 0% N 0%3.6.10

These questions assess the Prescriptive Based Design Option for Building Construction at the location. Consult NFPA 664 for definitions and specific details.

Don't Enter this value - it automatically appears

based on question responses →

←Percentage for this Question

NFPA 664→

COMPARTMENTATION - are there passive fire protection features in place to prevent the spread of FIRE / DEFLAGRATIONS?

Possible location UPGRADE may be

needed - Consult AHJ

COMPARTMENTATION - are there Fire Walls, Fire Partitions, & Fire Barrier Walls?

Possible location UPGRADE may be

needed - Consult AHJ

PROTECTION of OPENINGS & PENETRATIONS - are listed systems or approved materials used that conform to NFPA 221?

Possible location UPGRADE may be

needed - Consult AHJ

OCCUPANT LIFE SAFETY SYSTEMS MEANS OF EGRESS - does the design, construction, installation, & maintenance of Life Safety Systems meet NFPA 101 - Life Safety Code?

Possible location UPGRADE may be

needed - Consult AHJ

SPECIAL REQUIREMENTS - SURFACES & LEDGES IN DUST AREAS - are interior areas designed to minimize dust accumulation?

MINIMIZE dust at these locations

SPECIAL REQUIREMENTS - DAMAGE LIMITING CRITERIA - are enclosed areas designed to prevent breach, provide explosion resistance, and include venting to a safe outside location?

Possible location UPGRADE may be

needed - Consult AHJ

SPECIAL REQUIREMENTS - DRAFT CURTAINS - where required, are they made of noncombustible materials?

Possible location UPGRADE may be

needed - Consult AHJ

SPECIAL REQUIREMENTS - DRAFT CURTAINS - are they made of a minimum of 26 gauge steel, and NOT made of Aluminum?

Possible location UPGRADE may be

needed - Consult AHJ

SPECIAL REQUIREMENTS - DRAFT CURTAINS - do they fit tightly against the roof deck, and extend downward a minimum of 10 Percent of the total height?

Possible location UPGRADE may be

needed - Consult AHJ

SPECIAL REQUIREMENTS - BEAMS, PURLINS & OTHER STRUCTURAL MEMBERS - Does this location have these structures that extend downward equal to or greater than 10 Percent of floor to ceiling height (IF YES - they are a substitute for DRAFT CURTAINS)

Possible location UPGRADE may be

needed - Consult AHJ

Page 13: CD Inspection Checklist - Occupational Safety and Health … · XLS file · Web view2012-11-05 · INSPECTION CHECKLIST COMBUSTIBLE DUST INSPECTION CHECKLIST Y ... This checklist

1 NFPA 664 Chapter 7 - Prevention of Ignition & Control of Ignition Sources

6%

When? Who?

29%3.7

ANSWER ALL - Do ANY of the following exist? 17 Overall response is: 100% When? Who? 17 500%

1

N 0% N 0%3.7.1

1

N 0% Y 100%3.7.2

1

N 0% N 0%3.7.3

1

N 0% N 0%3.7.4

1

N 0% N 0%3.7.5

1

N 0% N 0%3.7.6

1

N 0% N 0%3.7.7

1

N 0% N 0%3.7.8

1

N 0% N 0%3.7.9

Don't Enter this value - it automatically appears

based on question responses →

←Percentage for this Question

`These questions assess the Prevention of Ignition and Control of Ignition Sources at the location. Consult NFPA 664 for definitions and specific details.NFPA 664→

HOT WORK - Is Hot Work controlled according to NFPA 51B? (Also consult 29 CFR 1910.276 - Welding, Cutting, Burning)

HOT WORK must be controlled

ELECTRICAL SYSTEMS - Do electrical systems meet NFPA 70? (Also see OSHA 29 CFR 1910.303 and the following)

ELECTRICAL SYSTEMS must meet code

requirements-SEE NFPA 70

HOT SURFACES - Are exterior surfaces of heated process equipment in contact with wood prevented from a MAXIMUM allowable temperature of 500 degrees (500 *F) [260 *C]?

Wood exposed to HOT SURFACES exceeding the

auto-ignition temperature of wood at 399 degrees may ignite

BEARINGS - Are they monitored for adequate lubrication and excessive wear?

Inadequate lubrication & wear leads to frictional

heating and auto-ignition of wood dust

POWERED INDUSTRIAL TRUCKS - IF they operate in areas with a deflagration hazard, are they the correct classification? (See NFPA 505)

Powered Industrial Trucks are sources of

ignition-CHECK Classification

LIGHTING - Are they designed, installed, & maintained so they aren't an ignition hazard during normal operation OR catastrophic failure?

Evaluate & Upgrade lighting to low

temperature & enclosed devices

FUEL FIRED EQUIPMENT - Are they designed, installed, & maintained so they aren't an ignition hazard? (See NFPA 31-Oil Burning, NFPA 54-Fuel Gas, NFPA 85-Boilers Combustion)?

CHECK fuel fired equipment against NFPA

31 requirements

STATIC ELECTRICITY - Does equipment contain design features that include - Conductivity, bonding & grounding, grounded metal combs, other effective means approved by the AHJ?

Consult electrician for Static Electricity minimizations

MACHINES & PROCESSING EQUIPMENT - Are they operated per manufacturer's specifications, at a condition of sharpness to minimize heat, and abrasives used within design life?

Look for equipment generation of sparks and

ignition

Page 14: CD Inspection Checklist - Occupational Safety and Health … · XLS file · Web view2012-11-05 · INSPECTION CHECKLIST COMBUSTIBLE DUST INSPECTION CHECKLIST Y ... This checklist

1

N 0% Y 100%3.7.10

1

Y 100% Y 100%3.7.11

1

N 0% N 0%3.7.12

1

N 0% N 0%3.7.13

1

N 0% Y 100%3.7.14

1

N 0% Y 100%3.7.15

1

N 0% N 0%3.7.16

1

N 0% N 0%3.7.17

1 NFPA 664 Chapter 8 - Processes, Operations, & Special Systems

9%

When? Who?

70%3.8

1ANSWER ALL - Do ANY of the following exist?

T-percent T-Count Q-Count Q-Sect%20%

FTpercent FTCount FQCount FQSect%60%

120% 13 10 200% 911% 13 10 600%

FOREIGN MATERIAL - Is wood stock inspected for nails and other objects prior to processing?

Inspect for and minimize foreign material that can

generate sparks and cause ignition

FOREIGN MATERIAL - Is fugitive (A.K.A "tramp") metal prevented from entering wood and dust process equipment? (These are materials capable of creating a spark that could ignite materials)

Determine materials sources and minimize

FRICTION - Is all equipment designed, installed, and operated to maintain alignment and lubrication to avoid frictional heat ignition?

CHECK equipment to minimize frictional

heating

FANS - Is combustible residue on fans, fan shrouds, and drive mechanisms prevented to avoid frictional heat ignition of the deposits?

Schedule and maintain cleaning of these parts

SPONTANEOUS IGNITION & CHEMICAL ACTION - Has the storage of wood particulates been evaluated to determine any spontaneous ignition hazards due to chemical reaction(s)?

Evaluate hazards and minimize

PROPELLANT ACTUATED TOOLS - Is their use PROHIBITED, UNLESS - dust producing machinery is shut down AND, Equipment / Floors / Walls are cleaned, AND dust accumulations are removed?

DON'T use propellant actuated tools unless

conditions are met

SMOKING - Is smoking restricted to designated areas having devices for smoking material disposal that is free of combustible / flammable hazards or storage?

Restrict smoking as specified

PORTABLE ELECTRIC EQUIPMENT & APPLIANCES - Is their use LISTED for the areas where they're used? (Example - Space heaters approved for use in dusty areas)

Equipment MUST be either UL or FM listed and only sed where

allowed

Don't Enter this value - it automatically appears

based on question responses →

←Percentage for this SECTIONThese questions apply to SYSTEMS, such as pneumatic, dust control, mechanical conveyors,

and all other equipment types used to convey, re-size, dry, or otherwise process wood, wood particles, & cellulosic material.

NFPA 664→

Page 15: CD Inspection Checklist - Occupational Safety and Health … · XLS file · Web view2012-11-05 · INSPECTION CHECKLIST COMBUSTIBLE DUST INSPECTION CHECKLIST Y ... This checklist

1

N 0% Y 100%3.8.1

1

N 0% N 0%3.8.2

1

Y 100% N 0%3.8.3

1

N 0% N 0%3.8.4

1

Y 100% Y 100%3.8.5

1

Y 0% Y 0%3.8.6

1

Y 0% N 100%3.8.7

1

N 0% Y 100%3.8.8

1

N 0% Y 100%3.8.9

1

N 0% Y 100%3.8.10

10% 100%

3.8.11

WHAT TYPE of CONTROL SYSTEM for 3.8.11?Count SubCount SubSect%

0%SubCount SubSect%

100%1 0% 1 100%

1

N 0% Y 100%

PARTICULATE CONVEYING & DUST COLLECTION SYSTEMS - Was a HAZARD ANALYSIS done to determine if the materials was GREEN, DRY NON-DEFLAGRABLE, or DEFLAGRABLE?

A Hazard Analysis must be conducted

FIRE & DEFLAGRATION HAZARD - Is ONLY GREEN MATERIAL collected or conveyed in A SPECIFIC area? (IF YES, Fire & Deflagration hazards are deemed non-exist in that area)

IF green & dry material present - NFPA 664 controls required

FIRE & DEFLAGRATION HAZARD - Is DRY WOOD PARTICULATE collected or conveyed in A SPECIFIC area? (IF YES, A Fire hazard is deemed to exist in that area)

NFPA 664 controls required

FIRE & DEFLAGRATION HAZARD - Is OR Could DRY WOOD PARTICULATE be suspended in air? (IF YES, A Deflagration hazard is deemed to exist in that area)

NFPA 664 controls NOT required

PNEUMATIC CONVEYING & DUST COLLECTION SYSTEMS - Are all such systems designed per NFPA 654?

VERIFY-Non professionally

engineered systems WILL NOT qualify

PNEUMATIC CONVEYING & DUST COLLECTION SYSTEMS - Are ANY OTHER spark producing systems tied into the woodworking particle conveying system?

NFPA 664 PROHIBITS THIS CONDITION.

Separate systems As Soon As Possible

PNEUMATIC CONVEYING & DUST COLLECTION SYSTEMS - Were ANY system modifications made (capture points, etc) WITHOUT system rebalancing?

System may need rebalancing to assure

capture velocity

PNEUMATIC CONVEYING & DUST COLLECTION SYSTEMS - Is (Are) Dust collection systems operated whenever wood stock is being processed?

MUST operate system when wood stock

processed

DUCT SYSTEMS - GENERAL REQUIREMENTS - Are Duct systems METALLIC, and NOT made of plastic(s)?

MAXIMIZE METAL - MINIMIZE PLASTIC - See comment for specifics

DUCT SYSTEMS - GENERAL REQUIREMENTS - Are Duct systems protected from corrosion AND bonded and grounded?

Provide corrosion protection and-or bond

& ground

DUCTS WITH A FIRE HAZARD - Answer the questions below FIRST - Are ducts conveying DRY MATERIAL where equipment generates sparks protected by one of the following?

Don't Enter value it automatically appears

based on question responses →

←Percentage for this Question

System A: 1-Material Entry Point > 2-Listed Spark Detection & Extinguishing System > 3-Collection Equipment

Provide corrosion protection and-or bond

& ground

C542
1 - The analysis needs to address each entry point in the system where downstream particles are present. Moisture content and particle size will affect the particle's "deflagrability". 2 - This is a highly technical question that requires calculating a "MINIMUM EXPLOSIBLE CONCENTRATION" (MEC) for all deflagrable material. You will need to consult NFPA 664 and an engineer for this analysis.
C551
The NFPA states that 75% of the MINIMUM EXPLOSIBLE CONCENTRATION (MEC) in air triggers the presumption. Because AIR SAMPLING under the OSHA Combustible Dust Compliance Directive is NOT SPECIFIED OR REQUIRED to assess this level, you MUST assume that dust in air can be "deflagrable".
C554
1 - NFPA 654 contains the design requirements. It's full title is "Standard for the Prevention of Fire and Dust Explosions from the Manufacturing, Processing, and Handling of Combustible Dust Solids. In some cases, NFPA 664 may qualify the design requirements, but that will be identified.
C557
1 - NFPA 654 contains the design requirements. It's full title is "Standard for the Prevention of Fire and Dust Explosions from the Manufacturing, Processing, and Handling of Combustible Dust Solids. In some cases, NFPA 664 may qualify the design requirements, but that will be identified.
C560
1 - AFTER a duct system has been balanced, additional pick-up points, duct modifications, etc can REDUCE SYSTEM PERFORMANCE. 2 - You must ensure system performs as originally designed. Consult a ventilation engineer to verify system performance.
C566
1 - NFPA specifically REQUIRES ductwork to be made of metal because they are conductive. PLASTICS are non-conductive, and as a result, will accumulate static electric charges which is an ignition source. 2 - NFPA specifically lists PVC as a nonconductive, non-permitted material for duct construction. 3 - The one EXCEPTION to this is that "flexible ducting shall be permitted for final machine connection in a length not exceeding the minimum required for machine operation". (NFPA). 4 - Lengths of flexible plastic ducting that are "excessive", or a replacement for metallic ducting is a subjective judgment call. The best practice is to minimize plastic duct length. 5 - Duct repairs with plastic instead of metal is NOT ALLOWED.
C577
1 - To make the inspection of system presence easy, the ORDER of component occurrence is structured into the statement. The (Material Entry Point) precedes the LISTED spark detection & extinguishing system because it matters. The listed system MUST be DOWNSTREAM from the material entry point. 2 - A "LISTED" system means one that has been tested and approved by an organization that actually tests and issues approvals, such as Underwriter's Laboratories (UL) or Factory Mutual (FM). Note that REGULATORY AGENCIES ARE NOT APPROVAL ORGANIZATIONS! There is no such thing as an "OSHA APPROVED" system. 3 This means that self-designed, self-built, and self-installed systems that have not been tested by an approval issuing entity are NOT LISTED, and ARE NOT ACCEPTABLE!
Page 16: CD Inspection Checklist - Occupational Safety and Health … · XLS file · Web view2012-11-05 · INSPECTION CHECKLIST COMBUSTIBLE DUST INSPECTION CHECKLIST Y ... This checklist

3.8.11.1 N 0% Y 100%

1

N 0% N 0%3.8.11.2

1

N 0% N 0%3.8.11.3

10% 100%

3.8.12

WHAT TYPE of CONTROL SYSTEM for 3.8.12?Count SubCount SubSect%

0%SubCount SubSect%

100%1 0% 1 100%

1

N 0% Y 100%3.8.12.1

1

N 0% N 0%3.8.12.2

1

N 0% N 0%3.8.12.3

1

N 0% N 0%3.8.12.4

1

N 0% N 0%3.8.12.5

1

N 0% N 0%3.8.12.6

1

N 0% Y 100%3.8.13

System A: 1-Material Entry Point > 2-Listed Spark Detection & Extinguishing System > 3-Collection Equipment

Provide corrosion protection and-or bond

& ground

System B: 1-LiSTED spark Detection & Extinguishing System > 2-Actuating a High Speed Abort Gate > 3-Diversion to Atmosphere before entry to collection or storage equipment

Provide corrosion protection and-or bond

& ground

System C: 1-Conveying to location with minimal personnel and personnel risk > 2-Acceptable Risk Analysis to the Authority Having Jurisdiction.

Provide corrosion protection and-or bond

& ground

DUCTS WITH A DEFLAGRATION HAZARD - Answer the questions below FIRST -Are ducts having a deflagration hazard designed, constructed, and installed by at least ONE of the following?

Don't Enter value it automatically appears

based on question responses →

←Percentage for this Question

Control System A: 1-Ducts and all metal hatches constructed of metal; 2-Able to withstand maximum deflagration pressures.

Provide corrosion protection and

ELECTRICALLY bond & ground

Control System B: 1-Metal Ducts protected by a LISTED EXPLOSION SUPPRESSION SYSTEM that is able to withstand maximum deflagration pressures.

Provide corrosion protection and-or bond

& ground

Control System C: 1-Metal Ducts located INDOORS; 2-Equipped with DEFLAGRATION RELIEF PIPES less than 20 feet length; 3-Extending to safe areas outside of building; 4-Able to withstand maximum deflagration pressures.

Provide corrosion protection and-or bond

& ground

Control System D: 1-Metal Ducts located INDOORS; 2-equipped with deflagration relief vents EXHAUSTING THROUGH LISTED FLAME QUENCHING DEVICES; 3-Able to withstand maximum deflagration pressures.

Provide corrosion protection and-or bond

& ground

Control System E: 1-Metal Ducts located OUTDOORS; 2-equipped with deflagration relief vents; 2-Able to withstand maximum deflagration pressures.

Provide corrosion protection and-or bond

& ground

Control System F: 1-Metal Ducts located OUTDOORS; 2-Having weaker construction permitted IF subject to a RISK ANALYSIS acceptable to the AHJ.

Provide corrosion protection and-or bond

& ground

HOODS & ENCLOSURES - Do hoods & enclosures capture wood dusts and particulates? (The air flow rate must be sufficient to capture & carry it into the ductwork)

Check system performance against design specifications-

check for leaks or material plugs

C580
1 - To make the inspection of system presence easy, the ORDER of component occurrence is structured into the statement. The (Material Entry Point) precedes the LISTED spark detection & extinguishing system because it matters. The listed system MUST be DOWNSTREAM from the material entry point. 2 - A "LISTED" system means one that has been tested and approved by an organization that actually tests and issues approvals, such as Underwriter's Laboratories (UL) or Factory Mutual (FM). Note that REGULATORY AGENCIES ARE NOT APPROVAL ORGANIZATIONS! There is no such thing as an "OSHA APPROVED" system. 3 This means that self-designed, self-built, and self-installed systems that have not been tested by an approval issuing entity are NOT LISTED, and ARE NOT ACCEPTABLE!
C583
1 - This item is an ADMINISTRATIVE CONTROL, not an engineering control. There may be a case where a minimal hazard exists. In that case, the system is "subject to" an acceptable risk analysis by the AUTHORITY HAVING JURISDICTION (AHJ). If, in their determination, the risk of fire or deflagration is minimal, there may be no conditions requiring engineered system controls.
C592
1 - These system features must be professionally designed. Ultimately, the AHJ must accept their design, which means that there must be an engineer involved. Material thicknesses and design are complex calculations.
C595
1 - The AHJ will determine what is acceptable. An engineer will need to be involved. Calculations are complex. 2 - A "LISTED" system means one that has been tested and approved by an organization that actually tests and issues approvals, such as Underwriter's Laboratories (UL) or Factory Mutual (FM). Note that REGULATORY AGENCIES ARE NOT APPROVAL ORGANIZATIONS! There is no such thing as an "OSHA APPROVED" system. 3 This means that self-designed, built, and installed systems that are NOT LISTED, ARE NOT ACCEPTABLE!
C598
1 - The AHJ will determine what is acceptable. An engineer will need to be involved. Calculations are complex. 2 - A "LISTED" system means one that has been tested and approved by an organization that actually tests and issues approvals, such as Underwriter's Laboratories (UL) or Factory Mutual (FM). Note that REGULATORY AGENCIES ARE NOT APPROVAL ORGANIZATIONS! There is no such thing as an "OSHA APPROVED" system. 3 This means that self-designed, built, and installed systems that are NOT LISTED, ARE NOT ACCEPTABLE!
C601
1 - The AHJ will determine what is acceptable. An engineer will need to be involved. Calculations are complex. 2 - A "LISTED" system means one that has been tested and approved by an organization that actually tests and issues approvals, such as Underwriter's Laboratories (UL) or Factory Mutual (FM). Note that REGULATORY AGENCIES ARE NOT APPROVAL ORGANIZATIONS! There is no such thing as an "OSHA APPROVED" system. 3 This means that self-designed, built, and installed systems that are NOT LISTED, ARE NOT ACCEPTABLE!
C605
1 - The AHJ will determine what is acceptable. An engineer will need to be involved. Calculations are complex. 2 - A "LISTED" system means one that has been tested and approved by an organization that actually tests and issues approvals, such as Underwriter's Laboratories (UL) or Factory Mutual (FM). Note that REGULATORY AGENCIES ARE NOT APPROVAL ORGANIZATIONS! There is no such thing as an "OSHA APPROVED" system. 3 This means that self-designed, built, and installed systems that are NOT LISTED, ARE NOT ACCEPTABLE!
C608
1 - The AHJ will determine what is acceptable. An engineer will need to be involved. Calculations are complex.
Page 17: CD Inspection Checklist - Occupational Safety and Health … · XLS file · Web view2012-11-05 · INSPECTION CHECKLIST COMBUSTIBLE DUST INSPECTION CHECKLIST Y ... This checklist

3.8.13 N 0% Y 100%

1

N 0% Y 100%3.8.14

1

0% 100%3.8.15

NFPA ALLOWABLE DUST COLLECTOR LOCATIONS:Count SubCount SubSect%

0%SubCount SubSect%

100%1 0% 1 100%

1

OUTSIDE OF BUILDINGS N 0% Y 100%3.8.15.1

1

INDOORS - ONLY IF NO fire hazard or deflagration is deemed to exist. N 0% N 0%3.8.15.2

1

N 0% N 0%3.8.15.3

1

N 0% N 0%3.8.15.4

1

N 0% N 0%3.8.15.5

10% 50%

3.8.16

HOODS & ENCLOSURES - Do hoods & enclosures capture wood dusts and particulates? (The air flow rate must be sufficient to capture & carry it into the ductwork)

Check system performance against design specifications-

check for leaks or material plugs

HOODS & ENCLOSURES - Are hoods & enclosures made of NON-COMBUSTIBLE MATERIALS? (IF NO, they MUST be protected by sprinklers described by NFPA 13)

NFPA 13-Standard for the Installation of Sprinkler Systems-

applies

DUST COLLECTORS - GENERAL REQUIREMENTS - CAUTION! NFPA 664 Specifies permitted dust collector placement based on SPECIFIC requirements. Pick the system placement at your location and consult NFPA for detail. A SUMMARY of conditions appears below.

Don't Enter value it automatically

appears based on question responses

←Percentage for this Question

Check system performance against design specifications-

check for leaks or material plugs

Check system performance against design specifications-

check for leaks or material plugs

INDOORS - Because ONLY A FIRE HAZARD exists AND it is PROTECTED by the design requirements of NFPA 664

Provide corrosion protection and-or bond

& ground

INDOORS - Because A DEFLAGRATION HAZARD exists BUT it is PROTECTED by deflagration relief vents or pipes per the design requirements of NFPA 664

Provide corrosion protection and-or bond

& ground

INDOORS - Because it is an ENCLOSURELESS device that MEETS the following: 1- Used ONLY for wood processing machinery; 2-NOT used on Sanders or abrasive planers; 3-Each collector has maximum air flow rate of 5000 cfm; 4-Fan motor is totally enclosed and fan cooled; 5-Daily or greater removal of collected dust; 6-Collector located 20 ft or more from persons or other collectors.

Provide corrosion protection and-or bond

& ground

DUST COLLECTORS WITH FIRE or DEFLAGRATION HAZARDS - CAUTION! NFPA 664 requires specific construction methods. Consult NFPA for requirements.

Don't Enter value it automatically appears

based on question responses →

←Percentage for this Question

C628
1 -
Page 18: CD Inspection Checklist - Occupational Safety and Health … · XLS file · Web view2012-11-05 · INSPECTION CHECKLIST COMBUSTIBLE DUST INSPECTION CHECKLIST Y ... This checklist

3.8.16 0% 50%

ANSWER ALL - Do ANY of the following exist?Count SubCount SubSect%

0%SubCount SubSect%

When? Who? 50%2 0% 2 100%

1

N 0% Y 100%3.8.16.1

1

N 0% N 0%3.8.16.2

1

0% 100%3.8.17

ANSWER The Question that applies to your system:Count SubCount SubSect%

0%SubCount SubSect%

When? Who? 100%1 0% 1 100%

1

N 0% Y 100%3.8.17.1

1

N 0% N 0%3.8.17.2

1

0% 71%3.8.18

Count SubCount SubSect%0%

SubCount SubSect%When? Who? 71%

7 0% 7 500%1

N 0% Y 100%3.8.18.1

1Fugitive dust emissions minimized? N 0% Y 100%

3.8.18.2

DUST COLLECTORS WITH FIRE or DEFLAGRATION HAZARDS - CAUTION! NFPA 664 requires specific construction methods. Consult NFPA for requirements.

Don't Enter value it automatically appears

based on question responses →

←Percentage for this Question

Do Dust collectors WITH FIRE HAZARDS meet the design requirements in NFPA?

Review NFPA 664 and corrrect

Do Dust collectors WITH DEFLAGRATION HAZARDS meet the design requirements in NFPA?

Review NFPA 664 and corrrect

RECYCLED EXHAUST AIR - CAUTION! NFPA 664 prohibits recycling air UNLESS certain equipment is installed based on the air flow rate of the system. Choose the air flow rate at your location and consult NFPA for detail.

Don't Enter value it automatically appears

based on question responses →

←Percentage for this Question

Do RECYCLED AIR SYSTEMS less than or equal to 5000 cubic feet per minute (CFM) meet the design requirements in NFPA 664?

Review NFPA 664 and corrrect

Do RECYCLED AIR SYSTEMS greater than 5000 cubic feet per minute (CFM) meet the design requirements in NFPA 664?

Review NFPA 664 and corrrect

MECHANICAL CONVEYING SYSTEMS - GENERAL REQUIREMENTS - CAUTION! NFPA 664 has specific requirements for mechanical conveying system design.

Don't Enter value it automatically

appears based on question responses

←Percentage for this Question

What design features does your system have? Answer all that apply:

Designed, Installed, & Operated to maintain alignment and minimize excessive heat build-up?

Review NFPA 664 - Minimize heat build-up

Review NFPA 664 and Minimize fugitive dust

emissions

Page 19: CD Inspection Checklist - Occupational Safety and Health … · XLS file · Web view2012-11-05 · INSPECTION CHECKLIST COMBUSTIBLE DUST INSPECTION CHECKLIST Y ... This checklist

1Dust tight ball or roller bearings used wherever practical? N 0% N 0%

3.8.18.3

1

N 0% N 0%3.8.18.4

1Shaft seals provided where rotating shafts penetrate equipment walls? N 0% Y 100%

3.8.18.5

1Access hatches & covers tightly fitted & fastened for dust tight operation? N 0% Y 100%

3.8.18.6

1

N 0% Y 100%3.8.18.7

1

0% 30%3.8.19

ANSWER ALL - Do ANY of the following exist?Count SubCount SubSect%

0%SubCount SubSect%

When? Who? 30%10 0% 10 300%

1

N 0% N 0%3.8.19.1

1Physically separated from a manufacturing area? N 0% N 0%

3.8.19.2

1Discharged to a safe location? N 0% N 0%

3.8.19.3

1

Uses a WELDED piping system? N 0% Y 100%3.8.19.4

1Are piping systems INSULATED if routed through production areas? N 0% N 0%

Review NFPA 664 and UPGRADE bearings

where possible

Bearings and bushings located outside of equipment UNLESS there's no other alternative?

Review NFPA 664 and correct where needed

Review NFPA 664 and correct where needed

Review NFPA 664 and UPGRADE as required

Do Mechanical Conveying Systems with a FIRE or DEFLAGRATION Hazard meet NFPA 664 sprinkler & isolation requirements?

Review NFPA 664 and UPGRADE as required

THERMAL OIL HEATING SYSTEMS - CAUTION! NFPA 664 has specific requirements for thermal oil heating systems. Inspect your location's equipment based on the specific requirements below. Consult NFPA for detail.

Don't Enter value it automatically

appears based on question responses

←Percentage for this Question

Designed, Operated, & Maintained to minimize thermal oil spills, fires, & explosions?

Review NFPA 664 requirements and

corrrect

Review NFPA 664 requirements and

corrrect

Review NFPA 664 requirements and

corrrect

NON-WELDED piping systems are NOT

acceptable-Review NFPA 664 and corrrect

Review NFPA 664 and corrrect

Page 20: CD Inspection Checklist - Occupational Safety and Health … · XLS file · Web view2012-11-05 · INSPECTION CHECKLIST COMBUSTIBLE DUST INSPECTION CHECKLIST Y ... This checklist

3.8.19.5Are piping systems INSULATED if routed through production areas? N 0% N 0%

1Do expansion or storage tanks meet design requirements? N 0% N 0%

3.8.19.6

1Are there SAFETY CONTROLS & INTERLOCKS? N 0% N 0%

3.8.19.7

1Has FUEL BURNER CONTROLS & INTERLOCKS? N 0% N 0%

3.8.19.8

1

N 0% Y 100%3.8.19.9

1

N 0% Y 100%3.8.19.10

1

0% 0%3.8.20

ANSWER ALL - Have the following been completed?Count SubCount SubSect%

0%SubCount SubSect%

When? Who? 0%3 0% 3 0%

1Was the HAZARD ANALYSIS based on particle size? N 0% N 0%

3.8.20.1

1

N 0% N 0%3.8.20.2

1

N 0% N 0%3.8.20.3

Review NFPA 664 and corrrect

Review NFPA 664 requirements and

corrrect

Review NFPA 664 and corrrect

Review NFPA 664 and corrrect

Have OPERATIONAL CONSIDERATIONS been completed? (Procedures, operator training, etc)

Review NFPA 664 requirements-Create

procedures and conduct operator training

Is FIRE PROTECTION provided, IF REQUIRED, for areas where a hot oil spill could accumulate? (SEE NFPA 664 8.3.2.10)

Review NFPA 664 requirements and

corrrect

PARTICULATE SIZE REDUCTION EQUIPMENT - CAUTION! NFPA 664 has specific requirements for particulate size reduction equipment. These requirements apply to operations that include specific types of products or production equipment. Consult NFPA for detail.

Don't Enter value it automatically

appears based on question responses

←Percentage for this Question

Review NFPA 664-Hazard Analysis MUST

be based on particle size

Is foreign material (AKA, Tramp metal), removed by self-cleaning magnets, air separators, or BOTH?

Review NFPA 664 and corrrect

Does equipment meet NFPA requirements for FIRE or DEFLAGRATION hazards? (SEE NFPA 664 beginning at 8.4.2.3)

Review NFPA 664 requirements

Page 21: CD Inspection Checklist - Occupational Safety and Health … · XLS file · Web view2012-11-05 · INSPECTION CHECKLIST COMBUSTIBLE DUST INSPECTION CHECKLIST Y ... This checklist

1

N 100% N 100%

i Average F-Average Q-Total F-Total100% 100%

0% 0% 3 3 0% 0% 0%

0% 0%0% 0% 0%

1

0% 0%3.8.21

ANSWER ALL - Do ANY of the following exist?Count SubCount SubSect%

0%SubCount SubSect%

When? Who? 0%4 0% 4 0%

1Is dust controlled within enclosures? N 0% N 0%

3.8.21.1

1

N 0% N 0%3.8.21.2

1

N 0% N 0%3.8.21.3

1Designed, Installed, & Operated for dust tight operation? N 0% N 0%

3.8.21.4

1

0% 0%3.8.22

ANSWER ALL - Do ANY of the following exist?Count SubCount SubSect%

0%SubCount SubSect%

When? Who? 0%6 0% 6 0%

1

N 0% N 0%

REVIEWER(S) - SPECIAL REQUIREMENTS APPLY TO PANEL MANUFACTURERS - CHOOSE Either A or B and

follow the instructions

Provide→ a response to

this question

Does the reviewed location MAKE Panel Products like

PLYWOOD or MDF?

IF NO - SPECIAL REQUIREMENTS DON'T APPLY to you. You've been FULLY CREDITED. SKIP

Questions 3.8.21 & 3.8.22 & 3.8.23

←total value cell

F3.8.21â F3.8.22â F3.8.23â

DO NOT manually enter value - it ↗ will automatically appear OR remain the

same based on your responses

3.8.21â 3.8.22â 3.8.23â

PANEL PRODUCT MANUFACTURING EQUIPMENT - CAUTION! NFPA 664 has specific requirements for panel product manufacturing equipment. Consult NFPA for detail.

Don't Enter value it automatically

appears based on question responses

←Percentage for this Question

Review NFPA 664 - Provide enclosures to

control dust

Designed, Installed, & Operated to maintain alignment and minimize excessive heat build-up?

Review NFPA 664 and corrrect

Foreign material is removed by self-cleaning magnets, air separators, or BOTH?

Review NFPA 664 and corrrect

Review NFPA 664 and corrrect

DRYER SYSTEMS - CAUTION! NFPA 664 has specific requirements for dryer systems. Consult NFPA 664 for detail.

Don't Enter value it automatically

appears based on question responses

←Percentage for this Question

IF PRESENT, does my location meet requirements for VENEER and/or FIBERBOARD DRYERS?

Review NFPA 664 and corrrect

Page 22: CD Inspection Checklist - Occupational Safety and Health … · XLS file · Web view2012-11-05 · INSPECTION CHECKLIST COMBUSTIBLE DUST INSPECTION CHECKLIST Y ... This checklist

3.8.22.1 N 0% N 0%

1IF PRESENT, does my location meet requirements for ROTARY DRYERS? N 0% N 0%

3.8.22.2

1IF PRESENT, does my location meet requirements for CONVEYOR DRYERS? N 0% N 0%

3.8.22.3

1IF PRESENT, does my location meet requirements for FLASH TUBE DRYERS? N 0% N 0%

3.8.22.4

1IF PRESENT, does my location meet requirements for KILN DRYERS? N 0% N 0%

3.8.22.5

1

N 0% N 0%3.8.22.6

1

N 0% N 0%3.8.23

1

0% 0%3.8.24

ANSWER ALL - Do ANY of the following exist?Q-Count SubCount SubSect%

0%SubCount SubSect%

When? Who? 0%6 0% 6 0%

1

N 0% N 0%3.8.24.1

1

N 0% N 0%3.8.24.2

1

N 0% N 0%

IF PRESENT, does my location meet requirements for VENEER and/or FIBERBOARD DRYERS?

Review NFPA 664 and corrrect

Review NFPA 664 and corrrect

Review NFPA 664 and corrrect

Review NFPA 664 and corrrect

Review NFPA 664 and corrrect

IF PRESENT, does my location meet requirements for FINISH ROOM DRYERS?

Review NFPA 664 and corrrect

POLLUTION CONTROL EQUIPMENT - Does pollution control equipment meet NFPA 664 requirements? (SEE NFPA 8.9 for detail).

Schedule installation date and verify

requirements with Authority Having Jurisdiction-AHJ

FIRE CONTROL SYSTEMS - CAUTION! NFPA 664 has specific requirements for fire control that vary by system type and location. Assess the presence of systems and check local requirements.

Don't Enter value it automatically

appears based on question responses

←Percentage for this Question

IF REQUIRED, are fire control systems in place for DRY LUMBER storage? (If not required, ANSWER YES)

CHECK requirements and VERIFY if needed

IF REQUIRED, are fire control systems in place for FLAMMABLE LIQUID storage? (If not required, ANSWER YES)

CHECK requirements and VERIFY if needed

IF REQUIRED, are fire control systems in place for SILOS and/or STORAGE BINS? (If not required, ANSWER YES)

CHECK requirements and VERIFY if needed

Page 23: CD Inspection Checklist - Occupational Safety and Health … · XLS file · Web view2012-11-05 · INSPECTION CHECKLIST COMBUSTIBLE DUST INSPECTION CHECKLIST Y ... This checklist

3.8.24.3 N 0% N 0%

1

N 0% N 0%3.8.24.4

1

N 0% N 0%3.8.24.5

1

N 0% N 0%3.8.24.6

1 NFPA 664 Chapter 9 - Fire Protection Systems

0%

When? Who?

80%3.9

5 0% When? Who? 5 400%

1

N 0% Y 100%3.9.1

1

N 0% N 0%3.9.2

1

N 0% Y 100%3.9.3

1

N 0% Y 100%3.9.4

1

N 0% Y 100%3.9.5

1 NFPA 664 Chapter 10 - Human Element

33%

When? Who?

100%

IF REQUIRED, are fire control systems in place for SILOS and/or STORAGE BINS? (If not required, ANSWER YES)

CHECK requirements and VERIFY if needed

IF REQUIRED, are fire control systems in place for Indoor DRY, FINE PARTICULATE storage? (If not required, ANSWER YES)

CHECK requirements and VERIFY if needed

IF REQUIRED, are fire control systems in place for HOT PRESSES - Continuous or MULTI-OPENING Batch-Type? (If not required, ANSWER YES)

CHECK requirements and VERIFY if needed

IF REQUIRED, are fire control systems in place for WOOD SCRAP PROCESSING & DISPOSAL? (If not required, ANSWER YES)

CHECK requirements and VERIFY if needed

Don't Enter value it automatically

appears based on question responses

←Percentage for this QuestionThese questions apply to FIRE PROTECTION SYSTEMS.

Requirements may vary and may not apply in every location.NFPA 664→

ANSWER ALL - Are the following items, IF REQUIRED, present and properly designed?

Automatic sprinklers? (SEE NFPA 13 or 15) Item NOT REQUIRED or Exempt, or Not in Place

Detection and Extinguishing systems? (SEE NFPA 11, 12, 15, 17, 25, 69, 72, 750, 2001)

Item NOT REQUIRED or Exempt, or Not in Place

Inside Hose Stations? (SEE NFPA 14) Item NOT REQUIRED or Exempt, or Not in Place

Water Supply? (SEE NFPA 20, 22, 24) Item NOT REQUIRED or Exempt, or Not in Place

Portable Fire Extinguishers? (SEE NFPA 10) Item NOT REQUIRED or Exempt, or Not in Place

Don't Enter value it automatically

appears based on question responses

←Percentage for this Question

Page 24: CD Inspection Checklist - Occupational Safety and Health … · XLS file · Web view2012-11-05 · INSPECTION CHECKLIST COMBUSTIBLE DUST INSPECTION CHECKLIST Y ... This checklist

3.10 33% 100%

ANSWER ALL - Do ANY of the following exist? 12 400% When? Who? 12 1200%

1

Y 100% Maintain as needed Y 100%3.10.1

1

Y 100% Maintain as needed Y 100%3.10.2

1

N 0% Y 100%3.10.3

1

Is GENERAL & JOB SPECIFIC Employee Training being done? N 0% Y 100%3.10.4

1

N 0% Y 100%3.10.5

1

Is PORTABLE APPLIANCE use regulated by a written policy? N 0% Y 100%3.10.6

1

N 0% Y 100%3.10.7

1

Is there a procedure for Fire & Explosion System Impairments? N 0% Y 100%3.10.8

Don't Enter value it automatically

appears based on question responses

←Percentage for this QuestionThese questions apply to the HUMAN ELEMENT under the NFPA

664 definition.NFPA 664→

Is there an INSPECTION, TESTING, & MAINTENANCE program for Fire & Explosion protection systems?

Does the INSPECTION, TESTING, & MAINTENANCE program also cover Dust Collection systems?

Are RECORDS for INSPECTION, TESTING, & MAINTENANCE kept for their useful life?

Ensure records are kept for their useful life

Conduct general & job-specific employee

training

Are CONTRACTORS properly trained, qualified, and their documentation retained on-site?

Ensure contractors are properly trained,

qualified, and their documentation is retained on-site

Establish written policy & regulate portable

appliance use

Is EVERY INCIDENT that results in a FIRE or EXPLOSION INVESTIGATED & RECORDED?

Investigate and record every incident involving

fire or explosion

Establish a procedure for fire & explosion system

impairment

Page 25: CD Inspection Checklist - Occupational Safety and Health … · XLS file · Web view2012-11-05 · INSPECTION CHECKLIST COMBUSTIBLE DUST INSPECTION CHECKLIST Y ... This checklist

3.10.8Is there a procedure for Fire & Explosion System Impairments? N 0% Y 100%

1

Is the procedure being used? N 0% Y 100%3.10.9

1

Y 100% Maintain as needed Y 100%3.10.10

1

Y 100% Maintain as needed Y 100%3.10.11

1

N 0% Y 100%3.10.12

1 NFPA 664 Chapter 11 - Housekeeping

0%

When? Who?

54%3.11

CHECK and VERIFY the following conditions: 13 0% When? Who? 13 700%

1

N 0% Y 100%3.11.1

1

N 0% N 0%3.11.2

1

N 0% N 0%3.11.3

1

N 0% N 0%3.11.4

Establish a procedure for fire & explosion system

impairment

Determine why and implement procedures

SMOKING - Is smoking restricted to designated areas having devices for smoking material disposal that is free of combustible / flammable hazards or storage?

HOT WORK - Is Hot Work controlled according to NFPA 51B? (Also consult 29 CFR 1910.276 - Welding, Cutting, Burning)

EMERGENCY PLANNING & RESPONSE - Does it meet the requirements of NFPA 600? (Also consult 29 CFR 1910.38 - Emergency Action Plan)

Meet requirements for Emergency Planning &

Response

Don't Enter value it automatically

appears based on question responses

←Percentage for this QuestionThese questions apply to HOUSEKEEPING requirements under the

NFPA 664 definition.NFPA 664→

Is the Housekeeping & Inspection program is DEVELOPED, MAINTAINED, & DOCUMENTED?

Develop, maintain & document Housekeeping

& Inspection program

Are large quantities of waste or debris that impede energized or moving equipment removed immediately?

Immediately remove waste accumulation that

impedes equipment operation

Is combustible waste placed in metal covered receptacles until removed for daily disposal?

Place combustible waste in metal covered

receptacles for daily disposal

Is non-reusable combustible waste placed in metal covered receptacles until removed for daily disposal?

Place non-reusable combustible waste in

metal covered receptacles for daily

disposal

Page 26: CD Inspection Checklist - Occupational Safety and Health … · XLS file · Web view2012-11-05 · INSPECTION CHECKLIST COMBUSTIBLE DUST INSPECTION CHECKLIST Y ... This checklist

3.11.4 N 0% N 0%

1

N 0% Y 100%3.11.5

1

N 0% Y 100%3.11.6

1If an area can't be reached for housekeeping purposes, is it sealed? N 0% Y 100%

3.11.7

1

N 0% Y 100%3.11.8

1Are Combustible or Flammable liquid spills cleaned up without delay? N 0% N 0%

3.11.9

1

N 0% Y 100%3.11.10

1

N 0% N 0%3.11.11

1

N 0% Y 100%3.11.12

1

N 0% N 0%3.11.12

1

0% 50%3.11.13

Is non-reusable combustible waste placed in metal covered receptacles until removed for daily disposal?

Place non-reusable combustible waste in

metal covered receptacles for daily

disposal

Is collected Fugitive (Tramp) metal SEPARATED so it can't re-enter the process?

Collect & separate fugitive metal to prevent

system re-entry

Is Production Equipment maintained and operated to minimize debris & dust escape?

Collect & separate fugitive metal to prevent

system re-entry

Seal unreachable areas to prevent dust

accumulation & ignition

If an area can't be reached TO ASSESS OPERATING TEMPERATURE, is a remote detection method considered?

Consider an assessment method - surfaces

exceeding 399*F are an ignition hazard

Cleanup combustable & flammable liquid spills as

soon as possible

Are volatile oil & resin residues removed from areas such as Ovens, Dryers, Fume Extraction, or Ventilation systems?

Cleanup Volatile oil & resin residues - they are

combustable or flammable

Are volatile oil & resin residues that are removed STORED near sources of ignition or areas such as Ovens, Dryers, Fume Extraction, or Ventilation systems?

RELOCATE STORAGE-Manage and Dispose of

volatile oil & resin residues per regulations

Are OILY soaked cloths or waste material stored in approved metal receptacles with self closing lids?

Provide approved metal receptacles having self-

closing lids

Are FLAMMABLE LIQUIDS, IF PRESENT, stored per the requirements of NFPA 30? (Flammable & Combustible Liquids Code)

Review NFPA 30 for specific requirements and UPGRADE storage

methods as needed

CLEAN-UP METHODS - CAUTION! NFPA 664 has specific requirements for clean-up methods. Several procedures are allowed if other procedures are followed

Don't Enter value it automatically

appears based on question responses

←Percentage for this Question

Page 27: CD Inspection Checklist - Occupational Safety and Health … · XLS file · Web view2012-11-05 · INSPECTION CHECKLIST COMBUSTIBLE DUST INSPECTION CHECKLIST Y ... This checklist

ANSWER ALL - Are the following conditions met? 4 0% When? Who? 4 200%

1

N 0% Y 100%3.11.13.1

1

N 0% N 0%3.11.13.2

1ONLY LOW Gauge air pressure of 15 Pounds Per Square Inch (PSI) is used. N 0% N 0%

3.11.13.3

1

N 0% Y 100%3.11.13.4

i RESULTS SECTION - 4Initial: 0% 1

This item is based on the OSHA Compliance Directive.

4.1 F4.1Follow-Up: 0% 1 0% 0%

DETERMINATION, REQUIREMENT, OBSERVATION, MEASUREMENT FIX WHAT? When? Who?

1Is DUST ACCUMULATION equal to or greater than 1/32 of an inch? Y 0%

When? Who?

N 100%4.1Where?

Floor & Equipment areas are vacuumed with a the correct equipment? (Equipment MUST be approved for CLASS II, Division 1, Group G Per NFPA 70, Article 502)(National Electrical Code)

Review NFPA 664 and corrrect

Electrical and other Ignition Sources are either 1-SHUT DOWN or REMOVED from the area, OR, 2-Classified for use in dusty areas.

Review NFPA 664 and corrrect

Review NFPA 664 and corrrect

There are NO open flames, sparks from spark producing equipment, or hot surfaces that can ignite a dust cloud or layer.

Review NFPA 664 and corrrect

Follow-Up Scores↓Question

NumberSTATUS Y for YES, N

for NO

Control dust accumulation to less

than 1/32 inch

OSHA CPL→

A992
INSTRUCTIONS FOR DOCUMENT USERS: 1-The OSHA assessment items BEGIN in this section. Questions directly reflect the Compliance Directive used for combustible dust.
Page 28: CD Inspection Checklist - Occupational Safety and Health … · XLS file · Web view2012-11-05 · INSPECTION CHECKLIST COMBUSTIBLE DUST INSPECTION CHECKLIST Y ... This checklist

RESULTS SECTION - 5Initial: 0% 1

This item is based on the OSHA Compliance Directive.

5.1 F5.1Follow-Up: 0% 1 0% 0%

DETERMINATION, REQUIREMENT, OBSERVATION, MEASUREMENT FIX WHAT? When? Who?

1

Is there VISIBLE DUST ACCUMULATION at the following areas? 0% PERCENTAGE

When? Who?

40%5.1

ANSWER ALL - Do ANY of the following exist? 5 Overall response is: 0% When? Who? 5 200%

1Slopes Y 0% Y 100%

5.1.1

1Overhead beams Y 0% Y 100%

5.1.2

1Joists Y 0% N 0%

5.1.3

1Ducts Y 0% N 0%

5.1.4

1Equipment tops Y 0% N 0%

5.1.4

Follow-Up Scores↓Question

NumberSTATUS Y for YES, N

for NO

Don't Enter value it automatically

appears based on question responses

→OSHA CPL→

Control accumulation on

Slopes

Control accumulation on Overhead Beams

Control accumulation on

Joists

Control accumulation on

Ducts

Control accumulation on Equipment Tops

Page 29: CD Inspection Checklist - Occupational Safety and Health … · XLS file · Web view2012-11-05 · INSPECTION CHECKLIST COMBUSTIBLE DUST INSPECTION CHECKLIST Y ... This checklist

5.1.4 Equipment tops Y 0% N 0%

RESULTS SECTION - 6Initial: 0% 1

This item is based on the OSHA Compliance Directive.

6.1 F6.1Follow-Up: 100% 1 0% 100%

DETERMINATION, REQUIREMENT, OBSERVATION, MEASUREMENT FIX WHAT? When? Who?

1

Y 0%

When? Who?

N 100%6.1Where?

RESULTS SECTION - 7Completed: 0% 1

This item is based on the OSHA Compliance Directive.

7.1 F7.1Follow-Up: 100% 1 0% 100%

DETERMINATION, REQUIREMENT, OBSERVATION, MEASUREMENT FIX WHAT? When? Who?

Control accumulation on Equipment Tops

Follow-Up Scores↓Question

NumberSTATUS Y for YES, N

for NO

Are DUST ACCUMULATIONS on all surfaces GREATER THAN 5% of surface area?

Calculate area square footage and control to less than

5%OSHA CPL→

Follow-Up Scores↓Question

NumberSTATUS Y for YES, N

for NO

Page 30: CD Inspection Checklist - Occupational Safety and Health … · XLS file · Web view2012-11-05 · INSPECTION CHECKLIST COMBUSTIBLE DUST INSPECTION CHECKLIST Y ... This checklist

DETERMINATION, REQUIREMENT, OBSERVATION, MEASUREMENT FIX WHAT? When? Who?

1

N 0%

When? Who?

N 100%7.1

RESULTS SECTION - 8Initial: 13% 1

This item is based on the OSHA Compliance Directive.

8.1 F8.1Follow-Up: 88% 1 13% 88%

DETERMINATION, REQUIREMENT, OBSERVATION, MEASUREMENT FIX WHAT? When? Who?

1

13% PERCENTAGE

When? Who?

88%8.1

ANSWER ALL - Are ANY of the following devices present? 8 Overall response is: 100% When? Who? 8 700%

1

Space heaters (electrical, gas, etc)? N 0% Controlled Y 100%8.1.1

1

Heat Guns, Soldering irons, other electrical heat producing items? N 0% Controlled Y 100%8.1.2

Question Number

STATUS Y for YES, N

for NO

Follow-Up Scores↓

Are DUST ACCUMULATIONS CONTROLLED under the Housekeeping standard (FED 29 CFR 1910.22)

Consult OSHA standard and minimize dust accumulation

OSHA CPL→

Follow-Up Scores↓Question

NumberSTATUS Y for YES, N

for NO

DETERMINE if IGNITION SOURCES are present anywhere in the inspection area. Complete the questions below:

Don't Enter value it automatically

appears based on question responses

→OSHA CPL→

Page 31: CD Inspection Checklist - Occupational Safety and Health … · XLS file · Web view2012-11-05 · INSPECTION CHECKLIST COMBUSTIBLE DUST INSPECTION CHECKLIST Y ... This checklist

1

HOT WORK - Welding, Burning, Cutting in area? Y 100% Y 100%8.1.3

1

Camp stoves or gas lanterns or other flame sources? N 0% Controlled N 0%8.1.4

1

Hot Plates or other appliances? N 0% Controlled Y 100%8.1.5

1

N 0% Controlled Y 100%8.1.6

1

N 0% Controlled Y 100%8.1.7

1

N 0% Controlled Y 100%8.1.8

i DETERMINATION - FIRE TRIANGLE OR DEFLAGRATION CONDITIONS?

6% X

Remove or prohibit HOT WORK in area when

deflagration or explosion conditions exist

Halogen or Metal Halide lamps near the auto-ignition temperature of wood (At approximately 399 *F) as verified by DIRECT MEASUREMENT or Thermographic Imagery?

Metal surfaces such as bearings, drive motors, etc. near the auto-ignition temperature of wood (approx 399 *F) as verified by DIRECT MEASUREMENT or Thermographic Imagery?

OTHER Heat or Ignition causing SOURCES? (IF YES, LIST)

DEFLAGRATION results from Oxygen, Heat, Fuel (wood dust) with DISPERSION IN AIR without confinement that results in a subsonic explosion (A slow expanding pressure wave).

Cumulative "Percent Prepared" & Hazard Condition Indicated

by "X" is:

A1150
INSTRUCTIONS FOR DOCUMENT USERS: 1-The checklist questions are listed in a specific order. At this point in the checklist, you either have a FIRE TRIANGLE hazard, or possibly a DEFLAGRATION HAZARD. 2-If you have a DEFLAGRATION HAZARD, several ADDITIONAL NFPA codes apply. Proceed with the rest of the checklist questions.
Page 32: CD Inspection Checklist - Occupational Safety and Health … · XLS file · Web view2012-11-05 · INSPECTION CHECKLIST COMBUSTIBLE DUST INSPECTION CHECKLIST Y ... This checklist

6% X56% X

RESULTS SECTION - 9Initial: 0% 2

This item is based on the OSHA Compliance Directive.

9.1 9.2 F9.1 F9.1Follow-Up: 50% 2 0% 0% 100% 0%

DETERMINATION, REQUIREMENT, OBSERVATION, MEASUREMENT FIX WHAT? When? Who?

1

Y 0%

When? Who?

N 100%9.1Where?

1

0% PERCENTAGE

When? Who?

0%9.2

8 Overall response is: 0% When? Who? 8 0%

1

Uncontrolled DUST BLOW DOWN operations on process equipment? Y 0% Y 0%9.2.1

Cumulative "Percent Prepared" & Hazard Condition Indicated

by "X" is:

FOLLOW-UP Cumulative "Percent Prepared" & Hazard Condition Indicated

by "X" is:

Follow-Up Scores↓Question

NumberSTATUS Y for YES, N

for NO

Could wood dust become dispersed in air due to vibration, other disturbances, OR a primary explosion?

Control by minimizing

accumulationOSHA CPL→

Determine if ANY of the following processes are occurring WHEN dust could become dispersed in air due to vibration, other disturbances, OR a primary explosion. ANSWER ALL conditions:

Don't Enter value it automatically

appears based on question responses

→OSHA CPL→

ANSWER ALL - Are ANY of the following processes performed WHILE MACHINERY IS OPERATING?

Control by procedure that shuts down

equipment-removes IGNITION SOURCES and

requires immediate clean-up

Page 33: CD Inspection Checklist - Occupational Safety and Health … · XLS file · Web view2012-11-05 · INSPECTION CHECKLIST COMBUSTIBLE DUST INSPECTION CHECKLIST Y ... This checklist

9.2.1Uncontrolled DUST BLOW DOWN operations on process equipment? Y 0% Y 0%

1

Y 0% Y 0%9.2.2

1

Uncontrolled FLOOR SWEEPING? Y 0% Y 0%9.2.3

1

Y 0% y 0%9.2.4

1

Has the Dust collection system failed OR been turned off? Y 0% y 0%9.2.5

1

Y 0% y 0%9.2.6

1

Y 0% y 0%9.2.7

1

Y 0% y 0%9.2.8

Control by procedure that shuts down

equipment-removes IGNITION SOURCES and

requires immediate clean-up

Uncontrolled AIR LANCING (at greater than 15 Pounds per Square Inch [psi]) of equipment or areas?

Control by procedure that removes IGNITION SOURCES and requires

immediate clean-up

Control by procedure that removes IGNITION SOURCES and requires

immediate clean-up

Vibrating, moving, or milling equipment CAUSING DUST TO BE AIRBORNE?

Control by procedure that removes IGNITION SOURCES and requires

immediate clean-up

Shut down system-Inspect-Repair unit-Start-up and check

operation.

Is Excessive dust accumulation subjected to wind or other environmental conditions?

Control by procedure that isolates and-or

minimizes dust accumulation and

controls all IGNITION SOURCES

Are Mechanical conveying systems in use, and CAUSING DUST TO BE AIRBORNE?

Control by procedure that removes IGNITION SOURCES and requires

immediate clean-up

OTHER Conditions or equipment that CAUSE DUST TO BE AIRBORNE? (IF YES, LIST) Control by procedure

that removes IGNITION SOURCES and requires

immediate clean-up

Page 34: CD Inspection Checklist - Occupational Safety and Health … · XLS file · Web view2012-11-05 · INSPECTION CHECKLIST COMBUSTIBLE DUST INSPECTION CHECKLIST Y ... This checklist

9.2.8 Y 0% y 0%

RESULTS SECTION - 10Initial: 0% 1

This item is based on the OSHA Compliance Directive.

10.1 F10.1Follow-Up: 100% 1 0% 100%

FIX WHAT? When? Who?

1

Y 0%

When? Who?

N 100%10.1

RESULTS SECTION - 11Initial: 14% 2

This item is based on the OSHA Compliance Directive.

11.1 11.2 F11.2 F11.1Follow-Up: 93% 2 29% 0% 100% 86%

DETERMINATION, REQUIREMENT, OBSERVATION, MEASUREMENT FIX WHAT? When? Who?

OTHER Conditions or equipment that CAUSE DUST TO BE AIRBORNE? (IF YES, LIST) Control by procedure

that removes IGNITION SOURCES and requires

immediate clean-up

Follow-Up Scores↓Question

NumberDETERMINATION, REQUIREMENT, OBSERVATION,

MEASUREMENTJUSTIFY PARTICLE

SIZE DETERMINATIONS

STATUS Y for YES, N

for NO

Is the material explosible under the OSHA Lab test? (You MUST assume the answer is YES, UNLESS the particle size is too large OR the OSHA lab result is known. Randomly generated particles will include less than 420 micron size)

Control by applying Housekeeping methods

and engineering controls

OSHA CPL→

Follow-Up Scores↓Question

NumberSTATUS Y for YES, N

for NO

Page 35: CD Inspection Checklist - Occupational Safety and Health … · XLS file · Web view2012-11-05 · INSPECTION CHECKLIST COMBUSTIBLE DUST INSPECTION CHECKLIST Y ... This checklist

DETERMINATION, REQUIREMENT, OBSERVATION, MEASUREMENT FIX WHAT? When? Who?

1

29% PERCENTAGE

When? Who?

86%11.1

7 Overall response is: 200% FIX WHAT? When? Who? 7 600%

1

Silos, Bunkers, Cyclones? N 100% Y 100%11.1.1

1

Covered screw conveyors? N 100% Y 100%11.1.2

1

Air Ducts and associated piping? Y 0% Y 100%11.1.3

1

Dust Bins? Y 0% Y 100%11.1.4

1

Bag houses, either in-doors or outside areas? Y 0% Y 100%11.1.5

1

Intermediate stage collection vessels? Y 0% N 0%

Question Number

STATUS Y for YES, N

for NO

Follow-Up Scores↓

ANSWER the questions BELOW to determine if your location has wood dust suspended in air, AND under confinement.

Don't Enter value it automatically

appears based on question responses

→OSHA CPL→

ANSWER ALL - Does this location have any of the following process equipment that has wood dust in air AND under confinement, AND unprotected?

NFPA Engineering Controls NOT Needed

OR already in place

NFPA Engineering Controls NOT Needed

OR already in place

Review & Select NFPA engineering control

options and VERIFY with Authority Having Jurisdiction - AHJ

Review & Select NFPA engineering control

options and VERIFY with Authority Having Jurisdiction - AHJ

Review & Select NFPA engineering control

options and VERIFY with Authority Having Jurisdiction - AHJ

Review & Select NFPA engineering control

options and VERIFY with Authority Having Jurisdiction - AHJ

Page 36: CD Inspection Checklist - Occupational Safety and Health … · XLS file · Web view2012-11-05 · INSPECTION CHECKLIST COMBUSTIBLE DUST INSPECTION CHECKLIST Y ... This checklist

11.1.6Intermediate stage collection vessels? Y 0% N 0%

1 OTHER - List:

Y 0% Y 100%11.1.7

1

N 0%

When? Who?

Y 100%11.2List areas where NOT working:

i DETERMINATION - DEFLAGRATION OR EXPLOSION CONDITIONS?

5% X81% X

Review & Select NFPA engineering control

options and VERIFY with Authority Having Jurisdiction - AHJ

Review & Select NFPA engineering control

options and VERIFY with Authority Having Jurisdiction - AHJ

Are there WORKING ENGINEERING CONTROLS that are currently protecting ALL of these systems from prevention or mitigation of Deflagrations And/or Explosions?

NFPA Engineering Controls NOT Needed

OR already in place

OSHA CPL→

EXPLOSION is a DEFLAGRATION resulting from Oxygen, Heat, Fuel (wood dust) with dispersion in air WHICH IS UNDER CONFINEMENT, that results in a Supersonic Explosion (a rapidly expanding pressure wave).

Cumulative "Percent Prepared" & Hazard Condition Indicated

by "X" is:

FOLLOW-UP Cumulative "Percent Prepared" & Hazard Condition Indicated

by "X" is:

STOP HERE! This is The END of the Initial Self-Assessment CHECKLIST - Schedule a FOLLOW-UP Assessment in 2 months to assess Performance after Corrective Action has been applied

A1319
INSTRUCTIONS FOR DOCUMENT USERS: 1-The checklist questions are listed in a specific order. At this point in the checklist, you either have a DEFLAGRATION HAZARD and / or an EXPLOSION HAZARD. 2-If you have EITHER HAZARD, the use of NFPA Codes will help you engineer out the hazards. At this point, formulate a plan of preventive or corrective action. This checklist specified requirements or references to help you make the changes and upgrades you need to control and minimize deflagrations and explosions. After that has been done, re-assess your location using this same checklist and the follow-up scores will be calculated. You'll be able to exit out NEXT TIME after you applied the FIXES identified by this checklist.
Page 37: CD Inspection Checklist - Occupational Safety and Health … · XLS file · Web view2012-11-05 · INSPECTION CHECKLIST COMBUSTIBLE DUST INSPECTION CHECKLIST Y ... This checklist

15% 65% 51%

2 MONTH FOLLOW-UP - DETERMINATION of CHECKLIST EFECTIVENESS, COMBUSTIBLE WOOD DUST INFORMATION, & CORRECTIVE ACTION

1 WAS TRAINING & ASSESSMENT EFFECTIVE?- Provide SUMMARY EXPLANATION of PERFORMANCE Increase or Decrease

2 Provide DETAILED ANALYSIS for ANY QUESTION not resulting in PERFORMANCE Increase Duplicate rows as needed.

INITIAL Self-Assessment CHECKLIST RESULT (in

Cumulative %)→

2 MONTH FOLLOW-UP Self-Assessment

CHECKLIST RESULT (in Cumulative %)→

Percent PERFORMANCE

INCREASE (or DECREASE)→

This Checklist is a Self-Assessment, Self-Scoring tool to determine percent compliance on Combustible Wood Dust Issues. As a measure of percent effectiveness, a SECOND LOOK at identical issues AFTER the first look should result in the following: #1-Corrected Conditions, AND, #2-An

increased Self assessment score relative to the baseline. Comparative percentages is the best method to QUANTIFY RESULTS after information on combustible wood dust has been presented, reviewed, and opportunities for corrective action have had a chance to be implemented.

Question Number

Question Number

E1340
This PERCENTAGE is a measure of how prepared your location is for the prevention of FIRE, DEFLAGRATION, and EXPLOSION relating to COMBUSTIBLE DUST. The MAXIMUM value obtainable is 100%. IF your score allowed you to EXIT OUT of this checklist, you don't even have a FIRE exposure.
J1340
This PERCENTAGE is a measure of how prepared your location is for the prevention of FIRE, DEFLAGRATION, and EXPLOSION relating to COMBUSTIBLE DUST, AFTER you have conducted an INITIAL Self-Assessment Checklist. The MAXIMUM value obtainable is 100%. UNCOVER black columns for re-determination of score.
O1340
This PERCENTAGE is a measure of Performance INCREASE OR DECREASE between the INITIAL and 2 MONTH FOLLOW-UP Self-Assessment Checklist. The percentage SHOULD INCREASE as additional preventive measures are applied and safeguards are installed. UNCOVER it for the 2nd assessment.
Page 38: CD Inspection Checklist - Occupational Safety and Health … · XLS file · Web view2012-11-05 · INSPECTION CHECKLIST COMBUSTIBLE DUST INSPECTION CHECKLIST Y ... This checklist

Question Number

Question Number

Question Number

Question Number

Question Number

Question Number

Question Number

Question Number

Page 39: CD Inspection Checklist - Occupational Safety and Health … · XLS file · Web view2012-11-05 · INSPECTION CHECKLIST COMBUSTIBLE DUST INSPECTION CHECKLIST Y ... This checklist

Question Number