CO2 cooling for FPCCD Vertex Detector Yasuhiro Sugimoto KEK 2012/4/24 @KILC2012 1

CO2 cooling for FPCCD Vertex Detector

Embed Size (px)

DESCRIPTION

CO2 cooling for FPCCD Vertex Detector. Yasuhiro Sugimoto KEK 2012/4/24 @KILC2012. FPCCD prototype. FPCCD vertex detector. Fine Pixel CCD Pixel size ~ 5 m m Fully depleted epitaxial layer Multi-port readout Read out between trains (No power pulsing) FPCCD vertex detector - PowerPoint PPT Presentation

Citation preview

Page 1: CO2 cooling for FPCCD Vertex Detector

1

CO2 cooling for FPCCD Vertex Detector

Yasuhiro Sugimoto

KEK

2012/4/24 @KILC2012

Page 2: CO2 cooling for FPCCD Vertex Detector

2

FPCCD vertex detector

• Fine Pixel CCD– Pixel size ~ 5mm– Fully depleted epitaxial layer– Multi-port readout– Read out between trains (No

power pulsing)

• FPCCD vertex detector– Double-sided ladder– Sensors and front-end ASICs

inside a cryostat– Power consumption > 50W inside

the cryostat

FPCCD prototype

Page 3: CO2 cooling for FPCCD Vertex Detector

3

Operation temperature

• Optimization for radiation tolerance– Charge transfer

inefficiency (CTI) due to radiation damage is a function of temperature

– A simple simulation of CTI based on Shockley-Read-Hall theory shows around -40℃ is optimal

~1x1011 e/cm2

Page 4: CO2 cooling for FPCCD Vertex Detector

4

Cooling options

• Cold nitrogen gas– Flow rate of ~1 L/s is necessary to extract 50W

power with DT=40K– Thick cooling tube would be necessary

• Two-phase CO2– Flow rate of ~0.15 g/s is necessary to extract

50W power with DT~0K (latent heat)– Thin tube is OK

• Less material budget• Less space between forward Si disks and beam pipe

Page 5: CO2 cooling for FPCCD Vertex Detector

5

Advantages of CO2 cooling

• Large latent heat ~300 J/g (x3 of PFC)• High pressure ~1 MPa @-40℃

– Less evaporated gas volume– Less temperature drop due to pressure drop

• Much less Global Warming Potential

CO2 C2F6 C3F8

Latent heat @-40C 321 J/g ~100 J/g ~110 J/g

Critical point 31.1℃ 19.7℃ 71.9℃

Pressure @-40C 1 MPa ~0.5 MPa ~0.1 MPa

GWP 1 9200 7000

Page 6: CO2 cooling for FPCCD Vertex Detector

6

CO2 cooling for FPCCD VTX• Cooling tube is attached to VTX end-

plate and heat produced by CCD output amp and ASIC is removed by conduction through CFRP ladder (simulation study for thermal design is necessary)

• Return line of CO2 will be used to cool the electronics outside the cryostat (~200W/side)

• Inner support tube should be air-tight and filled with dry air/nitrogen in order to prevent condensation on the CO2 tube

Page 7: CO2 cooling for FPCCD Vertex Detector

7

CO2 blow system

• CO2 collaboration in Japan– ILC VTX, ILC TPC, Belle-II VTX, and KEK cryogenic group– We constructed “blow system” and temperature was successfully

controlled between -40℃ and +15℃

Page 8: CO2 cooling for FPCCD Vertex Detector

8

CO2 cooling test mockup

• Acril pipe filled with dry air, which mimics ILD inner support tube

• Purpose– Demonstrate that a bare cooling tube can be used in the dry

air: No condensation, small heat penetration– Measure pressure drop (temperature drop) through a thin

tube

P

1 .6m

3 0cm A cri l p ipe

D ry A ir o u t

D ry A ir in

C O 2 in

C O 2 o u t

2m m tu be C ab le sP

90cm

Pt temperature sensors

Thermo-camera

Dew point sensor

Page 9: CO2 cooling for FPCCD Vertex Detector

9

CO2 cooling test mockup

Data logger

Acril pipeDry air generator

Cooling system

Page 10: CO2 cooling for FPCCD Vertex Detector

10

Test results (1)

• Dew point of <-45℃ can be easily achieved within 5 hours with the dry air flow rate of 5 L/min

• No condensation was observed on the 2 mm tube with -40℃ 2-phase CO2

Page 11: CO2 cooling for FPCCD Vertex Detector

11

Test results (2)

• Heat penetration– Heat penetration was obtained from the

difference of flow rates when “dry-out” occurs at different points

– Dry out can be observed as a sudden rise of temperature

– Flow rate difference of 0.03g/s caused dry-out point difference of 50cm

heat penetration ~ 20 W/m

Page 12: CO2 cooling for FPCCD Vertex Detector

12

Future plan (1)

• Cooling test of dummy ladder/end-plate

0 .3

R

Cooling tube

Carbon foamAl (0.1mm)

Capton (0.05mm)

Al

Al (0.1mm)

Capton (0.05mm)

R

1722.5

131

135

V1G1G2V2

R1-R20R21- R40

6

R1-R40 :1608または1005

Page 13: CO2 cooling for FPCCD Vertex Detector

13

Future plan (2)

• Blow system Circulating system– We will conduct R&D on a 2-phase CO2 cooling system which

circulates CO2 using a compressor– One compressor may be used for different sub-detectors (different

temperature)

Chiller Condenser

Reservoir

Compressor BufferCO2Back-pressure

valve

Heat exchanger

Needle valve

Detector

Heater

Other sub-det.

Other sub-det.

Page 14: CO2 cooling for FPCCD Vertex Detector

14

Summary

• Two-phase CO2 cooling is a very attractive option for the cooling system of FPCCD vertex detector

• It has been demonstrated that 2mm cooling tube can be used in dry-air atmosphere without condensation and with reasonably small heat penetration of 20 W/m @-40℃

• We will conduct R&D on the circulating CO2 cooling system using a compressor