Upload
a-v-dmitriev
View
212
Download
0
Embed Size (px)
Citation preview
A vortex chamber with an atomizing device is proposed for cooling of return water from industrial plants,
and the effect of design and production parameters are theoretically investigated.
Thermal and nuclear power plants in which cooling towers are widely used in return-water supply circuits make up
the basic part of generating capacities for the power industry of the Russian Federation. As practice indicates, a large portion
of the cooling towers in use were constructed 20–40 years ago, and all these installations are now technically and physically
obsolete. Packed units do not provide the efficiency required for cooling of the water, and the entrainment separators have a
high percentage of carry off of drop moisture. Moreover, ecological problems with operation of the towers, such as carry-off
of drop moisture, discharge of harmful substances (CO2, NOx, SO2), vapor flame, and noise, and also with the proximity of
manufacturing entities to residential development transportation arteries, have begun to appear as the productivity of the
structures and their number on industrial sites continue to grow [1].
Use of vortex chambers with an atomizing device [2] represents a possible solution to the problem of return-water
cooling. In these devices, air, on passing through a tangential vane swirler, acquires a rotational motion. While rotating, the
air flow is displaced toward the center of the vessel, and is removed through a branch pipe. The return water enters the ves-
sel through a branch pipe situated in the lower part of the vessel. Falling onto the atomizing device, the water is repulsed in
different directions, and a three-dimensional spray cone is formed. Moreover, the flow of air breaks the water down into drops
that are taken up into joint rotational motion. This pattern of interaction between the air and water drops results in the for-
mation of a finely disperse rotating trickling layer, increasing the area of contact between the phases, and the intensity of heat
and mass exchange.
To assess the effectiveness of cooling of water by an air flow in a vortex chamber, we theoretically investigated the
effect of design and production parameters. An annular element of a volume with a width dr was conditionally isolated in
the effective zone of the vessel (Fig. 1).
For the isolated element, the heat balance with respect to air with allowance for its longitudinal displacement can be
represented as
(1)G C T Q Q S C DdT
drG C T dT S C D
dT
dr
d T
drdrm G G G G G
Gm G G G G G G
G G+ + + = +( ) + +⎡
⎣⎢⎢
⎤
⎦⎥⎥1 2 1
2
2ρ ρ ,
Chemical and Petroleum Engineering, Vol. 47, Nos. 7–8, November, 2011 (Russian Original Nos. 7–8, July–August, 2011)
COOLING OF RETURN WATER FROM INDUSTRIAL
PLANTS IN VORTEX CHAMBERS
A. V. Dmitriev,1 O. S. Makusheva,2
and N. A. Nikolaev2
Translated from Khimicheskoe i Neftegazovoe Mashinostroenie, No. 7, pp. 19–22, July, 2011.
0009-2355/11/0708-0462 ©2011 Springer Science+Business Media, Inc.462
1 Scientific Center for Power-Industry Problems, Kazan Scientific Center, Russian Academy of Sciences, Russia.2 Kazan State Technological University, Russia.
where DG is the coefficient of molecular diffusion for the air in m2/sec, CG = Ch + Csx is the specific mass heat capacity of
the moist air (at a constant pressure) in kJ/(kg·K) [3], Ch = 1.006 kJ/(kg·K) is the specific mass heat capacity of the dry air
in the temperature interval from –40 to + 60°C at a constant pressure, Cs = 1.8068 kJ/(kg·K) is the specific mass heat capac-
ity of the water vapor, and S = 2πr(h1 + (Ra – r) tanα) and S1 = 2π(rh + (h – r tanα)dr) are the cross-sectional areas of the
effective zone of the vessel at the inlet (outlet), respectively, in the isolated volume in m2.
For the isolated element, the amount of heat that goes over from the water into the air due to heat conduction can be
defined as
Q1 = αG (TL – TG)dF, (2)
and due to evaporation:
Q2 = ISdLm, (3)
where Is = CLTL + r is the enthalpy of the vapor at the temperature of the water in J/kg/K, and r = 2493 kJ/kg is the specific
heat of vapor formation.
The mass flow rate of evaporating water in the isolated element:
dLm = βG(xe – x)dF, (4)
where xe = 0.622ps/(pm – ps) is the equilibrium moisture content in kg/kg, pm is the total pressure of the moist air in kPa, and
ps = 479 + (11.52 + 1.62TG)2 is the partial pressure of the saturated vapor in kPa.
The surface of the drops in the isolated volume in m2:
dF = πa2dN, (5)
where a is the drop diameter in m.
The number of drops in the isolated volume:
(6)
In [4], the fraction of water that exists in drop form within the effective zone of the vortex chamber is determined
from the formula
(7)EL
G
R
rAynm
mbx
a= ⋅⎛
⎝⎜
⎞
⎠⎟
⎛
⎝⎜
⎞
⎠⎟
−−
5 13 1030 34
0 9
0
1 22
. Re ,.
..
dNE dV
a
yn L=6
3π.
463
Fig. 1. Design dimensions of vortex chamber.
where Rebx = WbxRaρG /μG is the Reynolds number for the air at the inlet to the vortex chamber, μG is the coefficient of
dynamic viscosity of the air in Pa·sec, Wbx = Gv / (2πRah1) is the air velocity at the inlet to the vortex chamber in m/sec,
A = πRa2/(nbh1) is the coefficient of twist of the flow, n is the number of vanes, b is the distance between vanes in m, and h1
is the height of the vanes in m.
The volume of water in the isolated element (for the average distribution of water throughout the effective zone of
the vortex chamber):
(8)
The isolated volume of the effective zone of the vortex chamber:
(9)
Using formulas (6), (8), and (9), formula (5) takes on the form
(10)
The holding capacity of the vortex chamber is determined from a formula derived on the basis of the processing of
experimental data acquired in [5]:
(11)
The volume of the effective zone of the vortex chamber in m3:
(12)
After transformations, Eq. (1) assumes the form
(13)
where PeG = WbxRa /DG is the Peclet number for air.
For the isolated element, the heat balance with respect to the water with allowance for its longitudinal displacement
can be represented as
(14)
where DL is the coefficient of molecular diffusion for water in m2/sec.
= + + − + +⎡
⎣⎢⎢
⎤
⎦⎥⎥
Q Q L C T dT S C DdT
dr
d T
drdrm L L L L L L
L L1 2 1
2
2( ) ρ ,
L C T S C DdT
drm L L L L LL+ =ρ
= − + −( )α βρG G L S Gyn L
G G bx aT T I x x
E V
C aV W R( ) ( )e
,6
1 1 12
21
1 1Pe PeG
G
a a G
Gd T
dr
h
r h R r r h R r
dT
dr+
+ −( ) +⎛
⎝⎜⎜ −
+ −( )⎛
⎝⎜⎜
⎞
⎠⎟⎟
⎞
⎠⎟⎟ =
( ) tan
tan
tanαα
α
V h R r R r R ra a a= − + + −( )πα
33 2 31
202 3
03
02( ) ( ) tan .
V AL
GAL
m
m= ⋅ +( ) ⎛
⎝⎜
⎞
⎠⎟ + +( )⎡
⎣⎢⎢
⎤
⎦⎥⎥
−5 31 10 0 974 7 834 0 3085. ln ( . ln . ln .) ( ) .
dFrE V
aVr R h dr
yn La= − −( )12
1
πα( tan .)
dV r r R h dra= − −( )2 1π α( tan .)
dVV
VdVL
L= .
464
After transformations, Eq. (14) takes on the form
(15)
where PeL = UbxRa /DL is the Peclet number for water, and Ubx is the velocity of the water at the inlet to the vortex chamber
in m/sec.
The material balance for the isolated element can be represented as
(16)
After transformations, Eq. (16) assumes the form
(17)
Let us introduce the dimensionless parameter ξ = r /Ra, where r is the current radius of the vortex chamber in m, and
Ra is the radius of the vortex chamber in m. Ultimately, the system of three equations (13), (15), and (17) for the cooling of
water in the vortex chamber is written as
(18)
System of equations (18) is solved with the following boundary conditions: TL(ξ0) = TL0, TG(1) = TG0, xe(ξ0) = xe,
x(1) = x0, dTL /dξ(ξ0) = 0, and dTG /dξ(1) = 0.
The calculations were performed for a vortex chamber with a radius Ra = 0.26 m, a branch pipe with a radius
r0 = 0.05 m for the discharge of the gas–liquid mixture, and a vane swirler with a height h1 = 30 mm in which the water is
air-cooled. The cooling efficiency of the water was assessed by the parameter ET = 1 – TL /TL0, and the fraction of the water
that has been evaporated by the parameter EL = (1 – Lm /Lm0)·100%.
The calculations indicated that cooling efficiency in the vortex chamber decreases with decreasing air flow, since the
motive force of heat-transfer tends to zero, and cooling of the water is slowed. It should be pointed out that a significant reduc-
dx
d
x x R E V
G aVh RG a yn L
maξ
β ξπξ α=
−+ −( )( )
( ) tan .e 121
2
1
= − + −( )α βρG L G S G
a yn L
L L bxT T I x x
R E V
C a U V( ) ( )e ;
6
11 1 2
1
2
2
1
1Pe
Pe
PeL
LL
m
m
G
L
bx
bxa
L a
Ld T
d
hL
G
W
UR
h R
dT
dξ
ρρ
ξ α
ξ ξ α ξ+
−⎛
⎝⎜
⎞
⎠⎟ + −
+ −( ) =( ) tan
( ) tan
= − + −( )α βρG G L S G
a yn L
G G bxT T I x x
R E V
C a W V( ) ( )e ;
6
1 1 1 2
1
2
21
1Pe
Pe
PeG
G G a
G a
Gd T
d
h R
h R
dT
dξ
ξ αξ ξ α ξ
++ + −
+ −( ) =( ) ( ) tan
( ) tan
dx
drx x
rE V
G aVr R hG
yn L
ma= − − −( )β
πα( ) ( tan .e )
121
G x dL G x dxm m m+ = +( ).
= − + −( )α βρG L G S Gyn L
L L bx aT T I x x
E V
C aV U R( ) ( )e
,6
1 1 12
21
1
1Pe PeL
L
a L
m
m
G
L
bx
bx a
Ld T
dr r h R r
L
G
W
U
h
r h R r
dT
dr+ −
+ −⎛
⎝⎜
⎞
⎠⎟
⎛
⎝⎜ −
+ −( )⎞
⎠⎟⎟ =
tan
( ) tan ( ) tan
αα
ρρ α
465
466
Fig. 2. Dependence of cooling efficiency of water (a) and fraction of water evaporated (b) on ratio of mass
flow rates of phases and initial air temperature: Wbx = 10 m/sec; tL0 = 50°C; tG0, °C: 1) 40; 2) 20; 3) 10.
Fig. 3. Dependence of cooling efficiency of water (a) and fraction of water evaporated (b) on ratio of mass
flow rates of phases and initial water temperature: Wbx = 10 m/sec; tG0 = 20°C; tL0, °C: 1) 50; 2) 40; 3) 30.
Fig. 4. Dependence of cooling efficiency of water (a) and fraction of water evaporated (b) on ratio of mass flow
rates of phases and air velocity at inlet to chamber: tG0 = 20°C; tL0 = 40°C; Wbx, m/sec: 1) 7; 2) 10; 3) 15.
tion in efficiency is observed when the ratio of the mass flow rates of the phases is more than 0.2 (Figs. 2a, 3a). When the
air temperature changes at the inlet to the vessel, the fraction of evaporation is changed by less than 0.1%, since the time of
contact is essentially independent of this parameter. The fraction of water that has evaporated decreases with increasing ini-
tial air temperature owing to reduction in the motive force of mass transfer as the equilibrium moisture content increases
(see Fig. 2b), and, conversely, the higher the water temperature at the inlet to the vortex chamber, the more vigorous the evap-
oration (see Fig. 3b).
A change in air velocity at the inlet to the vortex chamber has virtually no effect on the cooling efficiency of the
water, since during the short relaxation time of the drops, the coefficient of heat transfer, which depends on the relative
velocity of the drops, remains essentially constant (Fig. 4a). It should be pointed out that a reduction in the fraction of water
evaporated takes place with increasing air velocity at the inlet to the vortex chamber, because the water drops exist in the
effective zone of the vessel for a shorter time when the volume of the chamber is the same (see Fig. 4b).
Thus, return water enters the vessel in the form of drops, uniformly coating the effective zone; this excludes the pos-
sibility that air will pass through without contact with the water, and makes it possible to increase the cooling efficiency of
the return water from industrial plants. A high carrying capacity with respect to air, and also a comparatively low hydraulic
resistance are basic advancements in vortex chambers, and carry-off of droplet moisture is eliminated, rendering the ecolog-
ical situation of industrial regions and regions adjacent to them appreciably improved. When vortex chambers are utilized,
moreover, the electric motor of the fan does not come under the influence of moist flows, as occurs in ventilated evaporative
cooling towers.
The study was conducted with financial support from the Ministry of Education and Science of the Russian Feder-
ation within the framework of implementation of the Federal Targeted Program on Scientific and Teaching Staff for an Inno-
vative Russia in 2009–2013 (State Contracts 02.740.11.0062, 02.740.11.0685, 02.740.11.0753, and P560) and a grant from
the president of the Russian Federation.
REFERENCES
1. V. S. Ponomarenko and Yu. I. Arefiev, Cooling Towers of Industrial and Power-Generating Establishments: Reference
Manual [in Russian], Energoatomizdat, Moscow (1998).
2. O. S. Makusheva, A. V. Dmitriev, and N. A. Nikolaev, Russian Federation Patent No. 89000, MPK V 05 V 1/26,
“Atomizing device,” applicant and patent holder is the Kazan Scientific Center, Russian Academy of Sciences,
No. 2009129889/22, appl. Aug. 3, 2009, publ. Nov. 27, 2009, Byull., No. 33.
3. V. I. Polushkin, O. N. Rusak, and S. I. Burtsev, Heating, Ventilation, and Conditioning of Air [in Russian], Professiya,
St. Petersburg (2002).
4. S. A. Laptev, “Behavior of a gas-liquid flow in vortex chambers,” Sib. Fiz. Tekhn. Zh., No. 5, 131–134 (1992).
5. S. A. Laptev, A. A. Ovchinnikov, and N. A. Nikolaev, “Dynamics of a gas-liquid flow in vortex chambers,” Khim.
Prom., No. 9, 52–55 (1994).
467