- 1 - NECOM ® TRANSFORMERS CTN - indoor current instrument transformers Product presentation MEDIUM VOLTAGE Highest voltage for equipment [kV] 7,2 ÷ 24 Power frequency test voltage - 1 min. [kV] 10 ÷ 50 Lightning impulse test voltage - 1,2 / 50 µs [kV] 40 ÷ 125 Rated primary current – Ip [A] 10 ÷ 1000 Rated short-time thermal current - 1 sec. - Ith [kA] 1 ÷ 100 Rated secondary current - Is [A] 1 or 5 Rated output (burden) [VA] 5 ÷ 30 Accuracy class of measuring windings [%] 0,2S ÷ 1 Instrument security factor - FS - 5 or 10 Accuracy class of protection windings - 5P or 10P Accuracy limit factor - ALF - 5 ÷ 20 Designed and manufactured according to IEC 60044 - 1 & IEC 61869 - 2 Product overview CTNx.xx.xxx current instrument transformers are casted in epoxy resin under vacuum and designed for indoor use. They are used for measuring and protection in medium voltage equipments, with insulation level of 7,2; 12 or 24 kV. The transformers are designed with the possibility to be reconnectible on the primary side. The number of secondary windings can be 1, 2 or 3, depending on: accuracy class, rated output and the rated short-time thermal current. One terminal of each secondary winding used must be earthed during the transformer operation, using a M5 screw on the transformer base plate. Not used secondary windings have to be short-circuited. Connections to the secondary terminals will be made into a terminal box, provided with a sealable transparent cover and with cable glands. The transformers are support-type and can operate in any position. The transformers mounting is achieved by the fixing base plate, using four M10 or M12 screws. Connection to the earth will be made with a M8 screw fixed on the transformer base plate. CTNx.xx.xxx instrument transformers will be delivered with all required screws to connect it in the circuit. Technical data Rated current in primary windings can have the value: 10, 15, 20, 25, 30, 50, 75, 100, 150, 200, 250, 300, 400, 500, 600, 800, 1000 A. On request we can provide another value for primary currents. Primary reconnectable transformers can be made up to 2 x 300 A. Rated current in secondary windings can be 1 A or 5 A, or another values on request. Accuracy class of measuring windings can be: 0,2S; 0,2; 0,5S; 0,5 or 1 for a value between 25 … 100% from the rated output and for rated primary current between (1) 5 ... 120%. Instrument security factor: FS5 or FS10. Accuracy class of protection windings can be: 5P or 10P at rated output. Accuracy limit factor (ALF) can be: 5; 10; 15; 20 or with another values on request. It’s not recommended to connect in the transformer secondary other burdens than those from the specified range. Rated frequency: 50 or 60 Hz. Operating altitude: max. 1000 m. Operating ambient temperature: - 25 … + 40ºC. Storage temperature: - 40 … + 40ºC. Force limits for screws tightening: M 5 = 2,8 … 3,5 Nm M 8 = 16 … 20 Nm M12 = 40 … 50 Nm

CTN - indoor current instrument transformersCTN - indoor current instrument transformers Product presentation MEDIUM VOLTAGE Highest voltage for equipment [kV] 7,2 ÷ 24 Power frequency

  • Upload
    others

  • View
    5

  • Download
    0

Embed Size (px)

Citation preview

Page 1: CTN - indoor current instrument transformersCTN - indoor current instrument transformers Product presentation MEDIUM VOLTAGE Highest voltage for equipment [kV] 7,2 ÷ 24 Power frequency

- 1 -

NECOM

®

TRANSFORMERS

CTN - indoor current instrument transformers

Product presentation

MEDIUM VOLTAGE

Highest voltage for equipment [kV] 7,2 ÷ 24

Power frequency test voltage - 1 min. [kV] 10 ÷ 50

Lightning impulse test voltage - 1,2 / 50 µs [kV] 40 ÷ 125

Rated primary current – Ip [A] 10 ÷ 1000

Rated short-time thermal current - 1 sec. - Ith [kA] 1 ÷ 100

Rated secondary current - Is [A] 1 or 5

Rated output (burden) [VA] 5 ÷ 30

Accuracy class of measuring windings [%] 0,2S ÷ 1

Instrument security factor - FS - 5 or 10

Accuracy class of protection windings - 5P or 10P

Accuracy limit factor - ALF - 5 ÷ 20

Designed and manufactured according to IEC 60044 - 1 & IEC 61869 - 2

Product overview

CTNx.xx.xxx current instrument transformers are casted in

epoxy resin under vacuum and designed for indoor use.

They are used for measuring and protection in medium

voltage equipments, with insulation level of 7,2; 12 or 24

kV.

The transformers are designed with the possibility to be

reconnectible on the primary side.

The number of secondary windings can be 1, 2 or 3,

depending on: accuracy class, rated output and the rated

short-time thermal current.

One terminal of each secondary winding used must be

earthed during the transformer operation, using a M5 screw

on the transformer base plate.

Not used secondary windings have to be short-circuited.

Connections to the secondary terminals will be made into a

terminal box, provided with a sealable transparent cover

and with cable glands.

The transformers are support-type and can operate in any

position.

The transformers mounting is achieved by the fixing base

plate, using four M10 or M12 screws.

Connection to the earth will be made with a M8 screw fixed

on the transformer base plate.

CTNx.xx.xxx instrument transformers will be delivered with

all required screws to connect it in the circuit.

Technical data

Rated current in primary windings can have the value:

10, 15, 20, 25, 30, 50, 75, 100, 150, 200, 250, 300, 400,

500, 600, 800, 1000 A. On request we can provide another

value for primary currents.

Primary reconnectable transformers can be made up to

2 x 300 A.

Rated current in secondary windings can be 1 A or 5 A, or

another values on request.

Accuracy class of measuring windings can be:

0,2S; 0,2; 0,5S; 0,5 or 1 for a value between 25 … 100%

from the rated output and for rated primary current between

(1) 5 ... 120%.

Instrument security factor: FS5 or FS10.

Accuracy class of protection windings can be: 5P or

10P at rated output.

Accuracy limit factor (ALF) can be: 5; 10; 15; 20 or with

another values on request.

It’s not recommended to connect in the transformer

secondary other burdens than those from the specified

range.

Rated frequency: 50 or 60 Hz.

Operating altitude: max. 1000 m.

Operating ambient temperature: - 25 … + 40ºC.

Storage temperature: - 40 … + 40ºC.

Force limits for screws tightening:

M 5 = 2,8 … 3,5 Nm

M 8 = 16 … 20 Nm

M12 = 40 … 50 Nm

Page 2: CTN - indoor current instrument transformersCTN - indoor current instrument transformers Product presentation MEDIUM VOLTAGE Highest voltage for equipment [kV] 7,2 ÷ 24 Power frequency

- 2 -

NECOM

®

TRANSFORMERS

Terminal markings of current instrument transformers

Code designation

Type

CTN

Ith/Idyn

[kA]

Ratio

[A]

Burden

[VA] Accuracy FS/ALF

1.A1.350 6,3/16 10/5 10 0,5(5P) FS5(10)

1.A1.350 6,3/16 10//5/5 10/10 0,5/5P FS5/10

1.A1.350 12,5/31,5 10/5 10 0,5(5P) FS5(10)

1.A1.350 12,5/31,5 10//5/5 10/10 0,5/5P FS5/10

1.A1.350 6,3/16 15/5 10 0,5(5P) FS5(10)

1.A1.350 6,3/16 15//5/5 10/10 0,5/5P FS5/10

1.A1.350 12,5/31,5 15/5 10 0,5(5P) FS5(10)

1.A1.450 12,5/31,5 15//5/5 10/10 0,5/5P FS5/10

1.A1.350 16/40 15/5 10 0,5(5P) FS5(10)

1.A1.450 16/40 15//5/5 10/10 0,5/5P FS5/10

1.A1.350 6,3/16 20/5 15 0,5(5P) FS5(10)

1.A1.350 6,3/16 20//5/5 15/15 0,5/5P FS5/10

1.A1.350 12,5/31,5 20/5 15 0,5(5P) FS5(10)

1.A1.350 12,5/31,5 20//5/5 15/15 0,5/5P FS5/10

1.A1.350 16/40 20/5 15 0,5(5P) FS5(10)

1.A1.450 16/40 20//5/5 15/15 0,5/5P FS5/10

1.A1.350 6,3/16 25/5 15 0,5(5P) FS5(10)

1.A1.350 6,3/16 25//5/5 15/15 0,5/5P FS5/10

1.A1.350 12,5/31,5 25/5 15 0,5(5P) FS5(10)

1.A1.350 12,5/31,5 25//5/5 15/15 0,5/5P FS5/10

1.A1.350 16/40 25/5 15 0,5(5P) FS5(10)

1.A1.350 16/40 25//5/5 15/15 0,5/5P FS5/10

P1 P2

S1 S2

P1 P2

S1 S2 S3

1S1 1S2 2S1 2S2

P1 P2 P1 P2

1S1 1S2 2S1 2S2 3S1 3S2

P1 P2

1S1 1S2 1S3 2S1 2S2 2S3

P1 C1 C2 P2

1S1 1S2 2S1 2S2

(5) (6)

(1) (2)

(4)

(3)

CTN x xx xxx

Base plate type (dimension)

Primary terminal type (A1, A2, A3, A4, A5, B1, B2 and C1)

The number of primary windings (1 or 2)

NECOM Current instrument Transformer

Page 3: CTN - indoor current instrument transformersCTN - indoor current instrument transformers Product presentation MEDIUM VOLTAGE Highest voltage for equipment [kV] 7,2 ÷ 24 Power frequency

- 3 -

NECOM

®

TRANSFORMERS

Type

CTN

Ith/Idyn

[kA]

Ratio

[A]

Burden

[VA] Accuracy FS/ALF

1.A1.350 25/63 25/5 15 0,5(5P) FS5(10)

1.A1.450 25/63 25//5/5 15/15 0,5/5P FS5/10

1.A1.350 6,3/16 30/5 15 0,5(5P) FS5(10)

1.A1.350 6,3/16 30//5/5 15/15 0,5/5P FS5/10

1.A1.350 12,5/31,5 30/5 15 0,5(5P) FS5(10)

1.A1.350 12,5/31,5 30//5/5 15/15 0,5/5P FS5/10

1.A1.350 16/40 30/5 15 0,5(5P) FS5(10)

1.A1.350 16/40 30//5/5 15/15 0,5/5P FS5/10

1.A1.350 25/63 30/5 15 0,5(5P) FS5(10)

1.A1.350 25/63 30//5/5 15/15 0,5/5P FS5/10

1.A1.350 6,3/16 50/5 15 0,5(5P) FS5(10)

1.A1.350 6,3/16 50//5/5 15/15 0,5/5P FS5/10

1.A1.350 12,5/31,5 50/5 15 0,5(5P) FS5(10)

1.A1.350 12,5/31,5 50//5/5 15/15 0,5/5P FS5/10

1.A1.350 16/40 50/5 15 0,5(5P) FS5(10)

1.A1.350 16/40 50//5/5 15/15 0,5/5P FS5/10

1.A1.350 25/63 50/5 15 0,5(5P) FS5(10)

1.A1.350 25/63 50//5/5 15/15 0,5/5P FS5/10

1.A1.350 31,5/80 50/5 15 0,5(5P) FS5(10)

1.A1.350 31,5/80 50//5/5 15/15 0,5/5P FS5/10

1.A1.350 12,5/31,5 75/5 15 0,5(5P) FS5(10)

1.A1.350 12,5/31,5 75//5/5 15/15 0,5/5P FS5/10

1.A1.350 16/40 75/5 15 0,5(5P) FS5(10)

1.A1.350 16/40 75//5/5 15/15 0,5/5P FS5/10

1.A1.350 25/63 75/5 15 0,5(5P) FS5(10)

1.A1.350 25/63 75//5/5 15/15 0,5/5P FS5/10

1.A1.350 31,5/80 75/5 15 0,5(5P) FS5(10)

1.A1.350 31,5/80 75//5/5 15/15 0,5/5P FS5/10

1.A1.350 16/40 100/5 15 0,5(5P) FS5(10)

1.A1.350 16/40 100//5/5 15/15 0,5/5P FS5/10

1.A1.350 25/63 100/5 15 0,5(5P) FS5(10)

1.A1.350 25/63 100//5/5 15/15 0,5/5P FS5/10

1.A1.350 31,5/80 100/5 15 0,5(5P) FS5(10)

1.A1.350 31,5/80 100//5/5 15/15 0,5/5P FS5/10

1.A1.350 16/40 150/5 15 0,5(5P) FS5(10)

1.A1.350 16/40 150//5/5 15/15 0,5/5P FS5/10

1.A1.350 25/63 150/5 15 0,5(5P) FS5(10)

1.A1.350 25/63 150//5/5 15/15 0,5/5P FS5/10

1.A1.350 31,5/80 150/5 15 0,5(5P) FS5(10)

1.A1.350 31,5/80 150//5/5 15/15 0,5/5P FS5/10

1.A1.350 16/40 200/5 15 0,5(5P) FS5(10)

1.A1.350 16/40 200//5/5 15/15 0,5/5P FS5/10

1.A1.350 25/63 200/5 15 0,5(5P) FS5(10)

1.A1.350 25/63 200//5/5 15/15 0,5/5P FS5/10

1.A1.350 31,5/80 200/5 15 0,5(5P) FS5(10)

1.A1.350 31,5/80 200//5/5 15/15 0,5/5P FS5/10

1.A1.350 40/100 200/5 15 0,5(5P) FS5(10)

Page 4: CTN - indoor current instrument transformersCTN - indoor current instrument transformers Product presentation MEDIUM VOLTAGE Highest voltage for equipment [kV] 7,2 ÷ 24 Power frequency

- 4 -

NECOM

®

TRANSFORMERS

Type

CTN

Ith/Idyn

[kA]

Ratio

[A]

Burden

[VA] Accuracy FS/ALF

1.A1.350 40/100 200//5/5 15/15 0,5/5P FS5/10

1.A1.350 25/63 250/5 15 0,5(5P) FS5(10)

1.A1.350 25/63 250//5/5 15/15 0,5/5P FS5/10

1.A1.350 31,5/80 250/5 15 0,5(5P) FS5(10)

1.A1.350 31,5/80 250//5/5 15/15 0,5/5P FS5/10

1.A1.350 40/100 250/5 15 0,5(5P) FS5(10)

1.A1.350 40/100 250//5/5 15/15 0,5/5P FS5/10

1.A1.350 31,5/80 300/5 15 0,5(5P) FS5(10)

1.A1.350 31,5/80 300//5/5 15/15 0,5/5P FS5/10

1.A1.350 40/100 300/5 15 0,5(5P) FS5(10)

1.A1.350 40/100 300//5/5 15/15 0,5/5P FS5/10

1.A1.350 50/125 300/5 15 0,5(5P) FS5(10)

1.A1.350 50/125 300//5/5 15/15 0,5/5P FS5/10

1.A2.350 40/100 400/5 15 0,5(5P) FS5(10)

1.A2.350 40/100 400//5/5 15/15 0,5/5P FS5/10

1.A2.350 50/125 400/5 15 0,5(5P) FS5(10)

1.A2.350 50/125 400//5/5 15/15 0,5/5P FS5/10

1.A2.350 40/100 500/5 15 0,5(5P) FS5(10)

1.A2.350 40/100 500//5/5 15/15 0,5/5P FS5/10

1.A2.350 50/125 500/5 15 0,5(5P) FS5(10)

1.A2.350 50/125 500//5/5 15/15 0,5/5P FS5/10

1.A2.350 40/100 600/5 15 0,5(5P) FS5(10)

1.A2.350 40/100 600//5/5 15/15 0,5/5P FS5/10

1.A2.350 50/125 600/5 15 0,5(5P) FS5(10)

1.A2.350 50/125 600//5/5 15/15 0,5/5P FS5/10

1.A3.350 40/100 800/5 15 0,5(5P) FS5(10)

1.A3.350 40/100 800//5/5 15/15 0,5/5P FS5/10

1.A3.350 50/125 800/5 15 0,5(5P) FS5(10)

1.A3.350 50/125 800//5/5 15/15 0,5/5P FS5/10

1.A3.350 50/125 1000/5 15 0,5(5P) FS5(10)

1.A3.350 50/125 1000//5/5 15/15 0,5/5P FS5/10

1.A3.350 63/160 1000/5 15 0,5(5P) FS5(10)

1.A3.350 63/160 1000//5/5 15/15 0,5/5P FS5/10

Notes:

1. The transformers (CTN1) 100 // 5 / 5A with Ith/Idyn = 16 / 40 kA can be ordered reconnectable on the primary side

(CTN2). In this case, the transformer 2 x 100 // 5 / 5A with Ith/Idyn = 16 / 40 kA will became 200 // 5 / 5A with Ith/Idyn =

32 / 80 kA.

2. For another values of rated output (burden), transformer ratio, Ith / Idyn, accuracy class (0,2S; 0,2; 0,5S; 1), FS, ALF, the

price and overall dimensions will be communicated on request.

Page 5: CTN - indoor current instrument transformersCTN - indoor current instrument transformers Product presentation MEDIUM VOLTAGE Highest voltage for equipment [kV] 7,2 ÷ 24 Power frequency

- 5 -

NECOM

®

TRANSFORMERS

Page 6: CTN - indoor current instrument transformersCTN - indoor current instrument transformers Product presentation MEDIUM VOLTAGE Highest voltage for equipment [kV] 7,2 ÷ 24 Power frequency

- 6 -

NECOM

®

TRANSFORMERS

Page 7: CTN - indoor current instrument transformersCTN - indoor current instrument transformers Product presentation MEDIUM VOLTAGE Highest voltage for equipment [kV] 7,2 ÷ 24 Power frequency

- 7 -

NECOM

®

TRANSFORMERS

VTN1 - indoor voltage instrument transformers (single pole)

Product presentation

MEDIUM VOLTAGE

Highest voltage for equipment [kV] 7,2 ÷ 24

Power frequency test voltage - 1 min. [kV] 10 ÷ 50

Lightning impulse test voltage - 1,2 / 50 µs [kV] 40 ÷ 125

Rated primary voltage [kV] max. 20/√3

Rated secondary voltage of measuring windings [V] 100/√3; 110/√3

Rated secondary voltage of protection windings [V] 100/3; 110/3

Overvoltage factor - 1,9*Un / 8 hrs.

Accuracy class of measuring windings [%] 0,2; 0,5; 1

Accuracy class of protection windings [Hz] 3P or 6P

Rated frequency - 50 ÷ 60

Designed and manufactured according to IEC 60044-2 & IEC 61869 - 3

Product Overview

VTN1.xxx.xx.xx.xx voltage instrument transformers are

casted in epoxy resin under vacuum and designed for

indoor use. They are used for measuring and protection in

medium voltage equipments, with insulation level of 7,2;

12 or 24 kV.

The number of secondary windings can be 1 or 2,

depending on rated output (burden) and accuracy class.

The "N" terminal of the primary winding and “n” and “dn”

terminals of the secondary windings must be earthed.

Connections to the secondary terminals will be made into

a terminal box, provided with a sealable transparent cover

and with cable glands.

The transformers are support-type and can operate in any

position.

The transformers mounting is achieved by the fixing base

plate, using four M10 or M12 screws.

Connection to the earth will be made with a M8 screw

fixed on the transformer base plate.

VTN1.xxx.xx.xx.xx instrument transformers will be

delivered with all required screws to connect it in the

circuit.

Technical data

Rated voltage in primary winding can have the value 6/√3,

10/√3 or 20/√3 kV. On request we can provide another

values for primary voltage.

Rated voltage in secondary windings can be 100/√3,

110/√3 V for measuring and 100:3, 110:3 V for protection,

or another values on request.

Rated output (burden) for both secondary windings

(summed) can be max. 170 VA or 200 VA.

Accuracy class of measuring windings can be: 0,2; 0,5;

or 1 for a value between 25 … 100% from the rated output

and for rated primary voltage between 80...120%.

Accuracy class of protection windings can be: 3P or 6P

at rated output.

Operating altitude: max. 1000 m.

Operating ambient temperature: - 25 … + 40ºC.

Storage temperature: - 40 … + 40ºC.

Force limits for screws tightening:

M 5 = 2,8 … 3,5 Nm

M 8 = 16 … 20 Nm

M10 = 20 … 25 Nm

Page 8: CTN - indoor current instrument transformersCTN - indoor current instrument transformers Product presentation MEDIUM VOLTAGE Highest voltage for equipment [kV] 7,2 ÷ 24 Power frequency

- 8 -

NECOM

®

TRANSFORMERS

Terminal markings of voltage instrument transformers

Code designation

Type

VTN1

U primary

[kV]

U secondary

[V] Accuracy

Burden

[VA]

Max. weight

[kg]

30 / 30

50 / 50 SBK.150.78.50.50 6 / √3 100 / √3 100 / 3

0,5 / 3P

50 / 120

36

30 / 30

50 / 50 SBK.150.78.50.50 10 / √3 100 / √3 100 / 3

0,5 / 3P

50 / 120

38

30 / 30

50 / 50 SBK.150.78.50.50 20 / √3 100 / √3 100 / 3

0,5 / 3P

50 / 120

38

Notes:

1. Voltage instrument transformers type VTN1.SBK.150.78.50.50 can be made with 1 or 2 secondary windings, for the

following rated output (burdens):

- max. 10 VA for accuracy cl. 0,2 and max. 10 VA for accuracy cl. 3P (or max. 30 VA for accuracy cl. 6P);

- max. 50 VA for accuracy cl. 0,5 and max. 120 VA for accuracy cl. 3P;

- max. 70 VA for accuracy cl. 0,5 and max. 70 VA for accuracy cl. 0,5.

2. For max. 75 VA accuracy cl. 0,5 and max. 125 VA accuracy cl. 6P, the transformers will be manufactured on

VTN1.SBK.152.85.50.50 structure.

3. For another values of rated output (burden), transformer ratio, accuracy class (0,2; 1), the price and overall dimensions

will be comunicated on request.

A N

a n

(1)

A N A N

1a 1n 2a 2n

(2) (3)

a n da dn

Single pole ( + “S” extension for fuse – VTN1S )

NECOM Voltage instrument Transformer

VTN SBK xxx xx xx 1

Internal Code

xx

Page 9: CTN - indoor current instrument transformersCTN - indoor current instrument transformers Product presentation MEDIUM VOLTAGE Highest voltage for equipment [kV] 7,2 ÷ 24 Power frequency

- 9 -

NECOM

®

TRANSFORMERS

Page 10: CTN - indoor current instrument transformersCTN - indoor current instrument transformers Product presentation MEDIUM VOLTAGE Highest voltage for equipment [kV] 7,2 ÷ 24 Power frequency

- 10 -

NECOM

®

TRANSFORMERS

Page 11: CTN - indoor current instrument transformersCTN - indoor current instrument transformers Product presentation MEDIUM VOLTAGE Highest voltage for equipment [kV] 7,2 ÷ 24 Power frequency

- 11 -

NECOM

®

TRANSFORMERS

VTN2 - Indoor voltage instrument transformers (double pole)

Product presentation

MEDIUM VOLTAGE

Highest voltage for equipment [kV] 7,2 ÷ 24

Power frequency test voltage - 1 min. [kV] 10 ÷ 50

Lightning impulse test voltage - 1,2 / 50 µs [kV] 40 ÷ 125

Rated primary voltage [kV] max. 20

Rated secondary voltage of measuring windings [V] 100; 110

Rated secondary voltage of protection windings [V] 100; 110

Overvoltage factor - 1,2*Un / cont.

Accuracy class of measuring windings [cl.] 0,2; 0,5; 1

Accuracy class of protection windings [cl.] 3P or 6P

Rated frequency [Hz] 50 ÷ 60

Designed and manufactured according to IEC 60044-2 & IEC 61869 - 3

Product Overview

VTN2.xxx.xx.xx.xx voltage instrument transformers are

casted in epoxy resin under vacuum and designed for

indoor use. They are used for measuring and protection in

medium voltage equipments, with insulation level of 7,2;

12 or 24 kV.

The number of secondary windings can be 1, 2 or 3,

depending on rated output (burden) and accuracy class.

Primary windings are isolated from the earth.

Connections to the secondary terminals will be made into

a terminal box, provided with a sealable transparent cover

and with cable glands.

The transformers are support-type and can operate in any

position.

The transformers mounting is achieved by the fixing base

plate, using four M10 or M12 screws.

Connection to the earth will be made with a M8 screw

fixed on the transformer base plate.

VTN2.xxx.xx.xx.xx instrument transformers will be

delivered with all required screws to connect it in the

circuit.

Technical data

Rated voltage in primary winding can have the value 6, 10

or 20 kV. On request we can provide another values for

primary voltage.

Rated voltage in secondary windings can be 100; 110 V for

measuring and 100, 110 V for protection, or another values

on request.

Rated output (burden) for both secondary windings

(summed) can be max. 100 VA.

Accuracy class of measuring windings can be: 0,2; 0,5;

or 1 for a value between 25 … 100% from the rated output

and for rated primary voltage between 80 ...120%.

Accuracy class of protection windings can be: 3P or 6P

at rated output.

Operating altitude: max. 1000 m.

Operating ambient temperature: - 25 … + 40ºC.

Storage temperature: - 40 … + 40ºC.

Force limits for screws tightening:

M 5 = 2,8 … 3,5 Nm

M 8 = 16 … 20 Nm

M10 = 20 … 25 Nm

Page 12: CTN - indoor current instrument transformersCTN - indoor current instrument transformers Product presentation MEDIUM VOLTAGE Highest voltage for equipment [kV] 7,2 ÷ 24 Power frequency

- 12 -

NECOM

®

TRANSFORMERS

Terminal markings of voltage instrument transformers

Code designation

Type

VTN2

U primary

[kV]

U secondary

[V] Accuracy

Burden

[VA]

Max. weight

[kg]

15 / 15

30 / 30 SBK.152.85.50.50 6 100 100

0,5 / 3P

50 / 50

40

15 / 15

30 / 30 SBK.152.85.50.50 10 100 100

0,5 / 3P

50 / 50

40

15 / 15

30 / 30 SBK.152.85.50.50 20 100 100

0,5 / 3P

50 / 50

40

Notes:

4. Voltage instrument transformers type VTN2.SBK.152.85.50.50 can be made with 1, 2 or 3 secondary windings, for the

following rated output (burdens):

- max. 10 VA for accuracy cl. 0,2 and max. 50 VA for accuracy cl. 3P;

- max. 50 VA for accuracy cl. 0,5 and max. 50 VA for accuracy cl. 3P.

5. For another values of rated output (burden), transformer ratio, accuracy class (0,2; 1), the price and overall dimensions

will be comunicated on request.

For any other information, please contact us!

A B

a b

(1)

A B A B

1a 1b 2a 2b

(2) (3)

a b da dn

Double pole ( + “S” extension for fuse – VTN2S )

NECOM Voltage instrument Transformer

VTN SBK xxx xx xx 2

Internal Code

xx

Page 13: CTN - indoor current instrument transformersCTN - indoor current instrument transformers Product presentation MEDIUM VOLTAGE Highest voltage for equipment [kV] 7,2 ÷ 24 Power frequency

- 13 -

NECOM

®

TRANSFORMERS

Page 14: CTN - indoor current instrument transformersCTN - indoor current instrument transformers Product presentation MEDIUM VOLTAGE Highest voltage for equipment [kV] 7,2 ÷ 24 Power frequency

- 14 -

NECOM

®

TRANSFORMERS

Instrument transformers laboratory

Our metrological laboratory has the facilities and expertise to perform routine tests and check the results for voltage and current instrument transformers in accordance with the actual applicable standards, as following: Current instrument transformers for medium and low voltage, indoor and outdoor type ( according to: IEC 60044 - 1 & IEC 61869 – 2 ). - primary current up to 4000 A, secondary current 5 or 1 A, accuracy class: 0,2S; 0,2; 0,5S; 0,5 for one or more measurement intervals. Voltage instrument transformers for medium and low voltage, indoor and outdoor type (according to IEC 60044-2 & IEC 61869 – 3 ). - primary voltage up to 24 kV, secondary voltage: 100√3; 110√3; 100; 110 V, accuracy class: 0,2; 0,5 or 1 % for one or more measurement intervals. Each instrument transformer is subjected to all routine tests including partial discharge test, according to applicable standards and customer specifications on request. NECOM instrument transformers are type tested by approved laboratories for design validation and fault withstand capabilities. All these tests allow us to ensure the high quality of transformers. The laboratory is accredited by Romanian Bureau of Legal Metrology. All equipments and standards used, has beeen calibrated by accredited laboratories ( PTB, METAS, INM, EPRO ), thereby traceability of measurment results is ensured. The testing of instrument transformers service is also available to external companies.

Page 15: CTN - indoor current instrument transformersCTN - indoor current instrument transformers Product presentation MEDIUM VOLTAGE Highest voltage for equipment [kV] 7,2 ÷ 24 Power frequency

- 15 -

NECOM

®

TRANSFORMERS

TSN 2 - indoor auxiliary power transformers

Product presentation

MEDIUM VOLTAGE

Highest voltage for equipment [kV] 7,2 ÷ 24

Power frequency test voltage - 1 min. [kV] 10 ÷ 50

Lightning impulse test voltage - 1,2 / 50 µs [kV] 40 ÷ 125

Rated primary voltage [kV] max. 20

Rated secondary voltage [V] 100; 220; 230

Short-circuit voltage - Uk [%] max. 10

Rated frequency [Hz] 50 ÷ 60

Insulation class - B

Degree of protection - IP 00

Cooling type - AN

Designed and manufactured according to IEC 60076 - 11

Product overview

TSN2.xxx.xx.xx.xx transformers for auxiliary services are

casted in epoxy resin under vacuum and designed for

indoor use, to make the transition from medium voltage to

low voltage, as auxiliary power supply for many

consumers.

They are provided with only one secondary winding.

The primary winding is isolated from the earth.

At request, these type of transformers can be made in

monopolar version. In this case, B terminal of primary

winding becomes N and must be earthed.

Connections to the secondary terminals will be made with

two M10 screws.

The transformers are support-type and can operate in any

position, except TSN2.SBK.184.90.90.R type that must be

placed only vertically.

The transformers mounting is achieved by the fixing base

plate, using four M10 or M12 screws.

Connection to the earth will be made with a M8 screw

fixed on the transformer base plate.

Technical data

Rated voltage in primary winding can have the value 6, 10

or 20 kV. If is asking for monopolar version, the rated

primary voltage have the value: 6/√3, 10/√3 or 20/√3 kV.

On request we can provide another values for primary

voltage.

Rated voltage in secondary windings can be: 100 V, 220 V,

230 V or another values on request.

It is mandatory to use protective devices, both on the

primary and on the secondary syde of the transformer.

Operating altitude: max. 1000 m.

Operating ambient temperature: - 25 … + 40ºC.

Storage temperature: - 40 … + 40ºC.

Force limits for screws tightening:

- M 8 = 16 … 20 Nm

- M10 = 20 … 25 Nm

Terminal markings

TSN 2

A B a b

Primary

Secondary

Page 16: CTN - indoor current instrument transformersCTN - indoor current instrument transformers Product presentation MEDIUM VOLTAGE Highest voltage for equipment [kV] 7,2 ÷ 24 Power frequency

- 16 -

NECOM

®

TRANSFORMERS

Code designation

Type

TSN2

Primary voltage

[kV]

Secondary voltage

[V]

Power

[VA]

Max. weight

[kg]

6 100 / 220 / 230 1000

10 100 / 220 / 230 800 SBK.150.78.50.50

20 100 / 220 / 230 600

36

6 100 / 220 / 230 1500

10 100 / 220 / 230 1200 SBK.152.85.50.50

20 100 / 220 / 230 1000

40

6 100 / 220 / 230 2000

10 100 / 220 / 230 2000 SBK.172.88.55.55

20 100 / 220 / 230 1500

58

6 100 / 220 / 230 4000

10 100 / 220 / 230 4000

20 100 / 220 / 230 4000 SBK.184.90.90-R

20 100 / 220 / 230 2500

80

Notes:

1. On request we can made the transformer in single pole version (TSN1). 2. For another values of the rated power or rated primary voltage, the prices will be communicated on request.

Double pole ( “1” assigned for single pole type )

NECOM Auxiliary power transformer

TSN SBK xxx xx xx 2

Internal code

xx

Page 17: CTN - indoor current instrument transformersCTN - indoor current instrument transformers Product presentation MEDIUM VOLTAGE Highest voltage for equipment [kV] 7,2 ÷ 24 Power frequency

- 17 -

NECOM

®

TRANSFORMERS

Page 18: CTN - indoor current instrument transformersCTN - indoor current instrument transformers Product presentation MEDIUM VOLTAGE Highest voltage for equipment [kV] 7,2 ÷ 24 Power frequency

- 18 -

NECOM

®

TRANSFORMERS

Page 19: CTN - indoor current instrument transformersCTN - indoor current instrument transformers Product presentation MEDIUM VOLTAGE Highest voltage for equipment [kV] 7,2 ÷ 24 Power frequency

- 19 -

NECOM

®

TRANSFORMERS

Page 20: CTN - indoor current instrument transformersCTN - indoor current instrument transformers Product presentation MEDIUM VOLTAGE Highest voltage for equipment [kV] 7,2 ÷ 24 Power frequency

- 20 -

NECOM

®

TRANSFORMERS