4
Data Sheet VDIKD102 © Danfoss | FHH | 2015.10 | 1 FHM-CN1 Pre-assembled Mixing Shunt Application The Danfoss FHM-CN1 pre-assembled mixing shunt is used for regulation of flow and supply temperature in hydronic floor heating systems. The compact, flexible design allows mounting the mixing shunt directly to the manifold on right side, with the primary connection from the side or below by bends (088U0821) which can be ordered separately. A self-acting proportional regulator (type FTC + RA-C control valve) is used to regulate the sup- ply temperature. The regulator ensures that the desired supply temperature to the underfloor heating system always remains constant. The FHM-CN1 mixing shunt can be mounted directly to the Danfoss manifold system without the use of special equipment. By using Danfoss floor heating controls all expec- tations of a professional floor heating system are fullfilled. Ordering Product Pump type Temperature setting range Type Code no. FHM-CN1 pre-assembled mixing shunt Grundfos UPSO 15-60 35 - 70° C FHM-CN1 088U0681 Accessories Product Type Code no. Bend ¾”, 1x FHM-CB 088U0821 Safety thermostat FH-ST55 088U0301

Data Sheet FHM-CN1 Pre-assembled Mixing Shuntheating.danfoss.com/PCMPDF/FHM-CN1_VDIKD102.pdf · FHM-CN1 Pre-assembled Mixing Shunt Application The Danfoss FHM-CN1 pre-assembled mixing

  • Upload
    buidung

  • View
    229

  • Download
    2

Embed Size (px)

Citation preview

Page 1: Data Sheet FHM-CN1 Pre-assembled Mixing Shuntheating.danfoss.com/PCMPDF/FHM-CN1_VDIKD102.pdf · FHM-CN1 Pre-assembled Mixing Shunt Application The Danfoss FHM-CN1 pre-assembled mixing

Data Sheet

VDIKD102 © Danfoss | FHH | 2015.10 | 1

FHM-CN1Pre-assembled Mixing Shunt

Application

The Danfoss FHM-CN1 pre-assembled mixing shunt is used for regulation of flow and supply temperature in hydronic floor heating systems. The compact, flexible design allows mounting the mixing shunt directly to the manifold on right side, with the primary connection from the side or below by bends (088U0821) which can be ordered separately.

A self-acting proportional regulator (type FTC + RA-C control valve) is used to regulate the sup-ply temperature. The regulator ensures that the

desired supply temperature to the underfloor heating system always remains constant.

The FHM-CN1 mixing shunt can be mounted directly to the Danfoss manifold system without the use of special equipment.

By using Danfoss floor heating controls all expec-tations of a professional floor heating system are fullfilled.

OrderingProduct Pump type Temperature

setting range Type Code no.

FHM-CN1 pre-assembled mixing shunt Grundfos UPSO 15-60 35 - 70° C FHM-CN1 088U0681

Accessories Product Type Code no.

Bend ¾”, 1x FHM-CB 088U0821

Safety thermostat FH-ST55 088U0301

Page 2: Data Sheet FHM-CN1 Pre-assembled Mixing Shuntheating.danfoss.com/PCMPDF/FHM-CN1_VDIKD102.pdf · FHM-CN1 Pre-assembled Mixing Shunt Application The Danfoss FHM-CN1 pre-assembled mixing

Data Sheet FHM-CN1 Pre-assembled Mixing Shunt

2 | © Danfoss | FHH | 2015.010 VDIKD102

Technical specifications Primary connection ¾” internal thread

Max. differential pressure 0.6 bar

Max. working pressure PN10

Max. flow temperature (primary side) 90 °C

Materials Body, unions and other metal parts Brass

O-rings EPDM

Capacity Heat capacity[kW]

Tsupply /Treturnat primary side

[°C]

Tsupply /Treturnat secondary side

[°C]

∆P at RA-C DN20* [kPa]

24 70/40 50/40 12.6

28 80/40 50/40 9.6

* based on kv (Xp = 4K) with FTC

FH-ST55Safety Thermostat

230V / 16ATS 55°C

Electrical connection

Code no. 088U0301

Shut-off temperature 55° C

Switch difference 4 K

Classification IP 40 (mounted)

The FH-ST safety thermostat is fixed on the sup-ply pipe and protects floor and system against too high temperatures, especially important for wooden floors. The FH-ST thermostat switches off the power supply of the floor heating base unit, when the temperature reaches 55° C.By switching off the power supply of the floor heating base unit, the actuators (NC) will close

automatically and the floor heating system is protected.The FH-ST55 can also be connected to a pump or a zone valve.

Note! The electrical installation must be carried out by an authorized installer only (230 V DC).

Page 3: Data Sheet FHM-CN1 Pre-assembled Mixing Shuntheating.danfoss.com/PCMPDF/FHM-CN1_VDIKD102.pdf · FHM-CN1 Pre-assembled Mixing Shunt Application The Danfoss FHM-CN1 pre-assembled mixing

Data Sheet FHM-CN1 Pre-assembled Mixing Shunt

© Danfoss Danfoss | FHH | 201510 | 3VDIKD102

System

Pump curve H [m]

Q [m2/h]

7

6

5

4

3

2

1

00.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0

Page 4: Data Sheet FHM-CN1 Pre-assembled Mixing Shuntheating.danfoss.com/PCMPDF/FHM-CN1_VDIKD102.pdf · FHM-CN1 Pre-assembled Mixing Shunt Application The Danfoss FHM-CN1 pre-assembled mixing

4 | © Danfoss | Danfoss | FHH | 2015.10 VDIKD102

Danfoss A/SFloor Heating Hydronics • Ulvehavevej 61 • DK-7100 Vejle • Denmark • Phone: +45 7488 8500 • Fax: +45 7488 [email protected] • www.floorheating.danfoss.comDanfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed.All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.

Dimensions

306

50

23121223

7825

G1 ISO228/1

G¾ISO228/1

G¾ISO228/1

213

G1 ISO228/1

FHM-CN1

G1 ISO228/1

G¾ ISO228/1

G¾ ISO228/1

G1 ISO228/1

306

50

23

121223119

25

213

78

FHM-CN1 with bend