Jon “Matt” Rouse Department of Civil Engineering Iowa State University November 4, 2013 [email protected] Design of Overhead Power Transmission Structures

Design of Overhead Power Transmission Structures · PDF fileDesign of Overhead Power Transmission Structures. ... ASCE MOP 74 moving toward reliability based ... Design of Overhead

Embed Size (px)

Citation preview

Page 1: Design of Overhead Power Transmission Structures · PDF fileDesign of Overhead Power Transmission Structures. ... ASCE MOP 74 moving toward reliability based ... Design of Overhead

Jon “Matt” RouseDepartment of Civil Engineering

Iowa State UniversityNovember 4, 2013

[email protected]

Design of Overhead Power Transmission Structures

Page 2: Design of Overhead Power Transmission Structures · PDF fileDesign of Overhead Power Transmission Structures. ... ASCE MOP 74 moving toward reliability based ... Design of Overhead

Current State of the Infrastructure

2013 ASCE Energy Infrastructure Grade: D+ $94 billion investment gap in electric T & D infrastructure by 2020

3300 new miles of new transmission lines/year needed in the next decade (N. American Electric Reliability Corp.)

$880 billion national investment in transmission + distribution required to meet DOE renewable energy and carbon emission goals by 2030 (Brattle Group)

“Terrorist attacks on multiple-line transmission corridors could cause cascading blackouts.” (Natl. Research Council of the Natl. Academies)

Page 3: Design of Overhead Power Transmission Structures · PDF fileDesign of Overhead Power Transmission Structures. ... ASCE MOP 74 moving toward reliability based ... Design of Overhead

Current T&D Structure Types

Transmission-Scale Structures (ASCE MOP 74)

Tubular Steel Monopoles (ASCE 48-11, 2012) Lattice Towers (ASCE 10-97, 2000) Prestressed Concrete Poles (ASCE MOP 123, 2012) Wood or Steel H-Frames Engineered Timber

Distribution-Scale Structures

Wood poles (ASCE MOP 111, 2006) Engineered Timber

However…

Page 4: Design of Overhead Power Transmission Structures · PDF fileDesign of Overhead Power Transmission Structures. ... ASCE MOP 74 moving toward reliability based ... Design of Overhead

Design Loads on Transmission Structures

Transverse design loads Well calibrated and specified Typically govern size of a structure

Longitudinal loads on intact systems Differential ice/wind/temperature loads Unequal wire tension

Secondary longitudinal loads and failure containment Result of an initial component failure Caused by extreme natural events or manmade attack Difficult to quantify Can trigger a cascade event (progressive collapse)

Page 5: Design of Overhead Power Transmission Structures · PDF fileDesign of Overhead Power Transmission Structures. ... ASCE MOP 74 moving toward reliability based ... Design of Overhead

Historical Perspective

Early on (circa 1910) emphasis on longitudinal flexibility with no longitudinal strength requirements cascading collapses

1921 NESC recommended dead-ends at least every 10 spans 1941 NESC this recommendation was removed 1977 NESC : “structures having a longitudinal strength

capability be provided at reasonable intervals along the line”

This recommendation remains in the NESC today ASCE MOP 74 moving toward reliability based design

Page 6: Design of Overhead Power Transmission Structures · PDF fileDesign of Overhead Power Transmission Structures. ... ASCE MOP 74 moving toward reliability based ... Design of Overhead

Preventing Longitudinal Cascades

The problem: severely unbalanced wire tension Possible Causes Extreme ice and/or wind events, landslides, ground movements,

flooding, lightning, vehicle/aircraft accidents Vandalism or sabotage

Prevention All tangent structures have significant longitudinal strength Intermittent dead-ends or stop structures Release mechanisms A new alternative

Page 7: Design of Overhead Power Transmission Structures · PDF fileDesign of Overhead Power Transmission Structures. ... ASCE MOP 74 moving toward reliability based ... Design of Overhead

A Different Approach to Cascade Prevention

Substitute ductility for longitudinal strength

This approach is used for seismic design of buildings and bridges

Ductility is not flexibility

(Stringing difficulties arise with highly flexible structures)

Structures must continue to sustain significant longitudinal forces even while undergoing large longitudinal deflections

Page 8: Design of Overhead Power Transmission Structures · PDF fileDesign of Overhead Power Transmission Structures. ... ASCE MOP 74 moving toward reliability based ... Design of Overhead

Equivalent Maximum Design Load on Intact System

Which Behavior is Preferable?

Page 9: Design of Overhead Power Transmission Structures · PDF fileDesign of Overhead Power Transmission Structures. ... ASCE MOP 74 moving toward reliability based ... Design of Overhead

40 k40 k

800 ft.-k

30 k40 k

10 k

800 ft.-k

20 k30 k

10 k

800 ft.-k

10 k20 k

10 k 10 k

800 ft.-k

10 k

100

ft.

80 f

t.650 ft. 650 ft. 650 ft. 650 ft.

645 ft. 645ft. 645 ft. 645 ft. 20 ft.

All

wir

es

seve

red

Page 10: Design of Overhead Power Transmission Structures · PDF fileDesign of Overhead Power Transmission Structures. ... ASCE MOP 74 moving toward reliability based ... Design of Overhead

But what kind of pole can do this?

Must be at least as strong as a typical structure in the transverse direction

Must be designed for both ductility and strength in the longitudinal direction

Must be cost competitive Ideally would be quickly reparable

Components of a prototype segmented pole Hinge near base to allow large longitudinal deflections Structural fuses to resist rotation and protect the rest of the structure Elastic post-tensioning to maintain resistance at large deflections

Page 11: Design of Overhead Power Transmission Structures · PDF fileDesign of Overhead Power Transmission Structures. ... ASCE MOP 74 moving toward reliability based ... Design of Overhead

Yielded Fuse Plate

Reduced-Scale Push-Over Tests

Load

Buckled Fuse Plate

Pin

Dead Weights

Pin

Longitudinal Axis & Load Direction

Transverse Axis

Structural Fuse Plate

Page 12: Design of Overhead Power Transmission Structures · PDF fileDesign of Overhead Power Transmission Structures. ... ASCE MOP 74 moving toward reliability based ... Design of Overhead

Push-Over Test Results

-15

-10

-5

0

5

10

15

20

25

30

-10 0 10 20 30 40 50 60 70 80 90 100 110 120 130

Lat

eral

Loa

d (

kN)

Top Displacement (cm)

Set 1

Set 2

Buckling of Structural Fuse on Compression Side

Slippage of Bolted Fuse Connections

Fracture of Structural Fuse on Tension Side

22% Drift while Sustaining 75% of Peak Resistance

Page 13: Design of Overhead Power Transmission Structures · PDF fileDesign of Overhead Power Transmission Structures. ... ASCE MOP 74 moving toward reliability based ... Design of Overhead

50 feet

Structural Fuse Plate

50 feet

0.28"

20.00"

30.00"40.00"

10.00"

0.28" 38.96"

Slip Joint

Post-tensioning Tendons

Transverse (y) Axis

Parallel (x) Axis

Base Cross SectionsPrototype Typical Monopole

Page 14: Design of Overhead Power Transmission Structures · PDF fileDesign of Overhead Power Transmission Structures. ... ASCE MOP 74 moving toward reliability based ... Design of Overhead

Relative Advantages of the Prototype

Less steel per tangent structure 7.5% reduction for comparison example

Elimination of dead-end structures Assuming dead-ends every 5 miles and each dead-end costs 4x a tangent

pole 6.5% cost reduction for comparison example

Simplified erection Pole with slip joints assembled on ground and tilted up into place Post-tensioning used to seat slip joints from ground level No crane required Less right of way for mobilization of large cranes? Particularly advantageous for rough or environmentally sensitive terrain

Page 15: Design of Overhead Power Transmission Structures · PDF fileDesign of Overhead Power Transmission Structures. ... ASCE MOP 74 moving toward reliability based ... Design of Overhead

Relative Advantages of the Prototype (cont.)

Lifecycle/maintenance costs No additional maintenance envisioned Easily inspected from ground level Post-tensioning reduces tensile stresses in base plate and base plate-

shaft weld to alleviate fatigue

Wide range of applicability Large transmission-scale structures Small distribution-scale poles

Enhanced Security Attack on a single structure or wires will not lead to a cascade Cascades prevented at the point of origin not merely contained in

magnitude Reduces risk and enhances reliability

Page 16: Design of Overhead Power Transmission Structures · PDF fileDesign of Overhead Power Transmission Structures. ... ASCE MOP 74 moving toward reliability based ... Design of Overhead

Moving Forward

Future Research Testing of full-scale transmission structures Testing of multiple structures under worst-case scenario loading Development of construction details Formal design procedures and guidelines

Summary More Resilient, Reliable, and Sustainable Lower Cost Longer Service Life