50
EIO0000000547.00 www.schneider-electric.com EIO0000000547 11/2009 RTU Configuration Software a SoCollaborative software User Manual 11/2009

EIO0000000547 11/2009 RTU Configuration Software

  • Upload
    others

  • View
    7

  • Download
    0

Embed Size (px)

Citation preview

Page 1: EIO0000000547 11/2009 RTU Configuration Software

EIO0000000547 11/2009

EIO

0000

0005

47.0

0

www.schneider-electric.com

RTU Configuration Softwarea SoCollaborative softwareUser Manual

11/2009

Page 2: EIO0000000547 11/2009 RTU Configuration Software

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein. This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications. It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof. Neither Schneider Electric nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein. If you have any suggestions for improvements or amendments or have found errors in this publication, please notify us.

No part of this document may be reproduced in any form or by any means, electronic or mechanical, including photocopying, without express written permission of Schneider Electric.

All pertinent state, regional, and local safety regulations must be observed when installing and using this product. For reasons of safety and to help ensure compliance with documented system data, only the manufacturer should perform repairs to components.

When devices are used for applications with technical safety requirements, the relevant instructions must be followed.

Failure to use Schneider Electric software or approved software with our hardware products may result in injury, harm, or improper operating results.

Failure to observe this information can result in injury or equipment damage.

© 2009 Schneider Electric. All rights reserved.

2 EIO0000000547 11/2009

Page 3: EIO0000000547 11/2009 RTU Configuration Software

Table of Contents

Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5About the Book . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Chapter 1 Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9General Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10Hardware Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Software Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

Chapter 2 RTU Library . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15RTU Library . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

Chapter 3 RTU Configuration Software . . . . . . . . . . . . . . . . . . . . . . 17Variable Name Creation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18Information Object Address. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19User Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20Station Configuration Browser. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22Common Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23Device Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24Single Points Properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25Double Points Properties. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26Measured Values Properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27Integrated Totals Properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28Single Commands Properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29Double Commands Properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30Set Points Properties. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31Import of Data to Unity Pro . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32Edit Variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

Appendices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35Appendix A RTU Application Example . . . . . . . . . . . . . . . . . . . . . . . . 37

Configuration with the Embedded Web Server . . . . . . . . . . . . . . . . . . . . . 38RTU Configuration Software Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40Resulting Variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45

Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49

EIO0000000547 11/2009 3

Page 4: EIO0000000547 11/2009 RTU Configuration Software

4 EIO0000000547 11/2009

Page 5: EIO0000000547 11/2009 RTU Configuration Software

§

Safety Information

Important Information

NOTICE

Read these instructions carefully, and look at the equipment to become familiar with the device before trying to install, operate, or maintain it. The following special messages may appear throughout this documentation or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.

EIO0000000547 11/2009 5

Page 6: EIO0000000547 11/2009 RTU Configuration Software

PLEASE NOTE

Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.

A qualified person is one who has skills and knowledge related to the construction and operation of electrical equipment and the installation, and has received safety training to recognize and avoid the hazards involved.

6 EIO0000000547 11/2009

Page 7: EIO0000000547 11/2009 RTU Configuration Software

About the Book

At a Glance

Document Scope

This manual describes the RTU Configuration Software, which helps you to parameterize variables that are used in a telecontrol module.

Validity Note

This documentation is valid for RTU Configuration Software V1.0.

Related Documents

You can download these technical publications and other technical information from our website at www.schneider-electric.com.

User Comments

We welcome your comments about this document. You can reach us by e-mail at [email protected].

Title of Documentation Reference Number

W315, W320E Remote Interface Units User Manual NT00135-EN-04

Unity Pro Reference Manual 35006144 (Eng), 35006146 (Ger)

Unity Pro Operating Modes Manual 33003101 (Eng), 33003103 (Ger)

EIO0000000547 11/2009 7

Page 8: EIO0000000547 11/2009 RTU Configuration Software

8 EIO0000000547 11/2009

Page 9: EIO0000000547 11/2009 RTU Configuration Software

EIO0000000547 11/2009

1

Introduction

EIO0000000547 11/2009

Introduction

Overview

This chapter provides general information on the RTU Configuration Software.

What's in this Chapter?

This chapter contains the following topics:

Topic Page

General Information 10

Hardware Requirements 13

Software Requirements 14

Installation 14

9

Page 10: EIO0000000547 11/2009 RTU Configuration Software

Introduction

General Information

Overview

The RTU Configuration Software helps you to parameterize variables that are used in telecontrol modules.

The tool simplifies the configuration of variables significantly, because you configure the variables per variable type instead of parameterizing every single variable.

NOTE: This tool is not an alternative to the embedded web server of telecontrol modules, because it only covers the variable part and not the complete configuration of telecontrol modules.

W@DE Modules

The W@DE TSXETW3xx product range is a PLC-based remote control solution incorporating:

operation in local or remote modedata archivingdirect user alarm notification.

Each remote control interface communicates with a control station using Modbus, IEC or DNP3 open protocols over a communication medium (Radio, PSTN, GSM, RS232, Ethernet, USB).

10 EIO0000000547 11/2009

Page 11: EIO0000000547 11/2009 RTU Configuration Software

Introduction

Data Flow

The following graphic shows the data flow between a telecontrol module, a PLC, the RTU Configuration Software and Unity Pro.

EIO0000000547 11/2009 11

Page 12: EIO0000000547 11/2009 RTU Configuration Software

Introduction

Backup of Module Configuration

NOTE: It is recommended to save the telecontrol module configuration (created with the embedded web server of the module) before importing the variable type configuration (created with the RTU Configuration Software).

Build/Import

During installation of the RTU Configuration Software an additional library (RTU library), providing the DFBs and DDT needed by the tool, is installed in Unity Pro.

Stages for build/import

For detailed information on how to build and import a configuration please refer to User Interface (see page 20).

Save, Edit

For detailed information on how to save and edit a configuration please refer to User Interface (see page 20).

Stage Description

1 Build of the configuration data out of the common settings and the different variable types in the RTU Configuration Software.

2 Export of the generated data out of the RTU Configuration Software for:Unity Pro (Variable list and Sections)telecontrol module (variable configuration)

3 Import of the generated data to Unity Pro and to the telecontrol module.

12 EIO0000000547 11/2009

Page 13: EIO0000000547 11/2009 RTU Configuration Software

Introduction

Hardware Requirements

PC

Telecontrol Modules

The following W@DE modules can be used with the tool:TSXETW315xxTSXETW320xxxxTSXETW325xxxx

PLCs

The following PLC platforms can be used with the tool:PremiumQuantumModicon M340

Component Description

System with Microsoft Windows Vista

System Pentium Processor 2.4 GHz or higherrecommended: 3.0 GHz

RAM Memory 1 GB minimumrecommended: 2 GB

Hard Disk minimum available free space: 100 MB

System with Microsoft Windows XP

System Pentium Processor 1.2 GHz or higherrecommended: 3.0 GHz

RAM Memory 512 MB minimumrecommended: 1 GB

Hard Disk minimum available free space: 100 MB

Component Description

Drive CD-ROM drive, to install the softwarerecommended: CD-ROM writer

Component Description

Display VGA (800-600) minimumrecommended: SVGA (1024-768 or more) with high color 24 bits

EIO0000000547 11/2009 13

Page 14: EIO0000000547 11/2009 RTU Configuration Software

Introduction

Software Requirements

General Software

The following software has to be installed on your PC:Microsoft Windows XP Professional or Microsoft Windows VistaMicrosoft .NET Framework V3.5Microsoft Internet Explorer 5.5 or laterUnity Pro 4.0 or later

After installing the software mentioned above you can start to install the RTU Configuration Software 1.0.

Installation

Overview

To install, repair or remove the tool you have to start the setup.exe.

After starting the setup.exe follow the installation routine.

NOTE: Please refer to the Software Requirements (see page 14) before starting the installation.

Result

The result of the installation process is the following:The RTU Configuration Software is available.A icon to start the tool is available in the Unity Pro toolbar.The additional RTU library, providing the DFBs and DDTs needed by the tool, is available in Unity Pro.

14 EIO0000000547 11/2009

Page 15: EIO0000000547 11/2009 RTU Configuration Software

EIO0000000547 11/2009

2

RTU Library

EIO0000000547 11/2009

RTU Library

RTU Library

Overview

During installation of the RTU Configuration Software an additional library (RTU library), providing the DFBs and DDT needed by the tool, is installed in Unity Pro.

These DFBs/DDT must be available before you can import the variable list and sections generated by the RTU Configuration Software.

DFBs

The RTU Configuration Software needs the following DFBs:

DFB Name Description

IEC_DTI calculation of the number cycles per seconds

IEC_RTU_COMMAND Word to Bit

IEC_RTU_TimeSync time synchronization after PLC restart (second, minute, hour, day, month, year, weekday)

IEC_SCAL_ME scaling of data values

15

Page 16: EIO0000000547 11/2009 RTU Configuration Software

RTU Library

DDT

The RTU Configuration Software needs the DateAndTime DDT.

The DateAndTime DDT has the following structure:

Element Data Type

hour INT

minute INT

second INT

day INT

month INT

year INT

monday BOOL

tuesday BOOL

wednesday BOOL

thursday BOOL

friday BOOL

saturday BOOL

sunday BOOL

weekday BOOL

weekend BOOL

summertime BOOL

IV BOOL

16 EIO0000000547 11/2009

Page 17: EIO0000000547 11/2009 RTU Configuration Software

EIO0000000547 11/2009

3

RTU Configuration Software

EIO0000000547 11/2009

RTU Configuration Software

Overview

This chapter provides information on the RTU Configuration Software.

What's in this Chapter?

This chapter contains the following topics:

Topic Page

Variable Name Creation 18

Information Object Address 19

User Interface 20

Station Configuration Browser 22

Common Settings 23

Device Configuration 24

Single Points Properties 25

Double Points Properties 26

Measured Values Properties 27

Integrated Totals Properties 28

Single Commands Properties 29

Double Commands Properties 30

Set Points Properties 31

Import of Data to Unity Pro 32

Edit Variables 33

17

Page 18: EIO0000000547 11/2009 RTU Configuration Software

RTU Configuration Software

Variable Name Creation

Overview

The variable names are automatically generated from different data entered in the interface of the RTU Configuration Software.

For detailed information on the different data please refer to the Device configuration section and the respective variable types (e.g Single points) sections.

Name Creation

The following data is used to generate the variable names:

The concatenated data are separated from each other with an underline.

Example: Station01_SP0001_102_100

Data Defined in Description/Comment

Station prefix Device configuration properties window

optionalThis prefix is only used to generate the variable names, if the Prefix is used check box is activated.Example: Station01

Prefix properties window of the respective variable type (e.g. Single points properties window)

IEC variable type specific prefixThis prefix is merged with a 4-digits incremental number.Example: SP0001

Objects address properties window of the respective variable type (e.g. Single points properties window)

starting object address of the related IEC variable typeExample: 102

Objects start address

Device configuration properties window

station addressThe specific %MW Object address of a variable is calculated from the inserted Objects start address. Example: 100

WARNINGUNINTENDED EQUIPMENT OPERATION

Test and verify the complete configuration and the final application.

Ensure that no mistakes were made during configuration.

Failure to follow these instructions can result in death, serious injury, or equipment damage.

18 EIO0000000547 11/2009

Page 19: EIO0000000547 11/2009 RTU Configuration Software

RTU Configuration Software

Information Object Address

Overview

According to the IEC-60870/101 and 104, the information object address (IOA) is used to identify the configured data points in the telecontrol module.

Together with the hardware address (the link address for a Modbus Serial Line connection or the IP address for a Modbus TCP/IP connection) and the sector address (common address) the data points can be accessed from outside of the device.

EIO0000000547 11/2009 19

Page 20: EIO0000000547 11/2009 RTU Configuration Software

RTU Configuration Software

User Interface

Overview

The user interface consists of several windows, a menu bar and a toolbar.

Legend

Number Description

1 Menu bar(File → New, Open, Save, Save As, Exit)(Build → Configuration, Prepare Unity Pro Part...)(Extras → Cleanup Log-Window)

2 Toolbar (New, Open, Save)

3 Station Configuration Browser (see page 22)

4 Properties windowThe displayed properties depend on the variable type selected in the Station Configuration Browser at the left.For the different variable type properties please refer to the subsequent sections.

5 Information window (provides information on the status of operations)You can clear the information window using Extras → Cleanup Log-Window.

20 EIO0000000547 11/2009

Page 21: EIO0000000547 11/2009 RTU Configuration Software

RTU Configuration Software

Saving the Configuration

To open, save or exit the configuration, use the menu bar or the toolbar.

You can save the configuration to any folder you like to.

The configuration is saved as a *.config file.

Building the Configuration

To build the configuration use Build → Configuration.

When building the configuration, a sub-folder is created in the folder you saved your configuration to, named as your configuration file.

Example: MyConfiguration.config will result in a sub-folder MyConfiguration.

This sub-folder (e.g. MyConfiguration) contains:a file Variables.TXT (telecontrol module variable list)another sub-folder for each station you defined in your configuration (named as the respective station) with

a variable list, the structures and the sections for Unity Pro

Editing the Configuration/Variables

To edit the configuration or the variables, use the Configuration or the Variables tab.

Now you can modify your configuration or variables and add comments in a list format.

Importing the Data

The generated data for the telecontrol modules you have to import manually.

For Unity Pro the import is done automatically using Build → Prepare Unity Pro part.... Please refer to Import of Data to Unity Pro (see page 32).

EIO0000000547 11/2009 21

Page 22: EIO0000000547 11/2009 RTU Configuration Software

RTU Configuration Software

Station Configuration Browser

Overview

The Station Configuration Browser provides toadd, delete or rename a stationselect the group of properties you want to edit (for example Common settings, Monitoring → Single points, Controlling → Single commands)

Adding, Deleting or Renaming the Station

Right-click a station and select the respective item from the context menu (Add, Delete, Rename).

22 EIO0000000547 11/2009

Page 23: EIO0000000547 11/2009 RTU Configuration Software

RTU Configuration Software

Selecting a Group of Properties

To select a group of properties you want to edit, click on of the following items/sub-items:

Device configuration (see page 24)Monitoring (data, read from the station)

Single points (see page 25)Double points (see page 26)Measured values (see page 27)Integrated totals (see page 28)

Controlling (data, written to the station)Single commands (see page 29)Double commands (see page 30)Set points (see page 31)

Common Settings

Overview

Select Common settings in the Station Configuration Browser to open the Common settings properties window.

In this window you can define up to 5 Cycles (range: 0..100000 ms).

The defined Cycles are available in the Query cycle drop down list of the different variable types (e.g. in the Single points properties window).

EIO0000000547 11/2009 23

Page 24: EIO0000000547 11/2009 RTU Configuration Software

RTU Configuration Software

Device Configuration

Overview

Select Device configuration in the Station Configuration Browser to open the Device configuration properties window.

In this window you can define the general settings for each station configuration.

For information on how variable names are generated please refer to Variable Name Creation (see page 18).

Data/Properties

You can define the following data/properties in the Device configuration properties window:

Data Property Description

Description This station manages ... for example

description of the station

Version 0.0.001 ... for example

version of the station configuration

PLC drop-down list PLC, the module communicates withM340PremiumQuantum

Station prefix Station01 for example

prefix for the stationThis prefix will be used to generate the variable names, if the Prefix is used check box is activated.

Prefix is used check box If this check box is activated the Station prefix generate the variable names.

Modbus slave address

32 for example Modbus Serial Line slave address

Network address [x.y.z.n]

192.168.19.2 for example

Modbus TCP/IP address of the station

Objects start address

1000 for example start address of the ASDU data (%MW)

Quality bits start address

100 for example start address of the quality data (%MW)

Structure name RTU for example name of the variable structure in Unity Pro

24 EIO0000000547 11/2009

Page 25: EIO0000000547 11/2009 RTU Configuration Software

RTU Configuration Software

Single Points Properties

Overview

Select Single Points in the Station Configuration Browser to open the properties window of the Single Point variable type.

For information on how variable names are generated please refer to Variable Name Creation (see page 18).

Data/Properties

You can define the following data/properties for the Single Point variable type:

NOTE: For all used variable types the Number of objects and the Objects address have to be defined.

Data Property Description

Prefix SP for example IEC variable type specific prefixFor variable name generation this prefix is merged with a 4-digits incremental number.Example: SP0001

Structure name SinglePoints for example

name of the subelement of the variable structure in Unity Pro

Number objects 10 for example number of variables of this typeNOTE: If this variable type is not used set the number to 0.

Objects address 100 for example address of the first variable of this typeThe Object address is used to access the variables from a control station via a RTU connection (according to IEC-60870/101 and /104; DNP3).

Datatype BOOL for example Unity Pro datatype

Query cycle 1000ms for example

choice of cycle defined in the Common settings

EIO0000000547 11/2009 25

Page 26: EIO0000000547 11/2009 RTU Configuration Software

RTU Configuration Software

Double Points Properties

Overview

Select Double points in the Station Configuration Browser to open the properties window of the Double point variable type.

For information on how variable names are generated please refer to Variable Name Creation (see page 18).

Data/Properties

You can define the following data/properties for the Double point variable type:

NOTE: For all used variable types the Number of objects and the Objects address have to be defined.

Data Property Description

Prefix DP for example IEC variable type specific prefixFor variable name generation this prefix is merged with a 4-digits incremental number.Example: DP0001

Structure name DoublePoints for example

name of the subelement of the variable structure in Unity Pro

Number objects 10 for example number of variables of this typeNOTE: If this variable type is not used set the number to 0.

Objects address 200 for example address of the first variable of this typeThe Object address is used to access the variables from a control station via a RTU connection (according to IEC-60870/101 and /104; DNP3).

Datatype DBOOL for example Unity Pro datatype

Query cycle 1000ms for example

choice of cycle defined in the Common settings

26 EIO0000000547 11/2009

Page 27: EIO0000000547 11/2009 RTU Configuration Software

RTU Configuration Software

Measured Values Properties

Overview

Select Measured Values in the Station Configuration Browser to open the properties window of the Measured Value variable type.

For information on how variable names are generated please refer to Variable Name Creation (see page 18).

Data/Properties

You can define the following data/properties for the Measured Value variable type:

NOTE: For all used variable types the Number of objects and the Objects address have to be defined.

Data Property Description

Prefix ME for example IEC variable type specific prefixFor variable name generation this prefix is merged with a 4-digits incremental number.Example: ME0001

Structure name MeasuredValues for example

name of the subelement of the variable structure in Unity Pro

Number objects 10 for example number of variables of this typeNOTE: If this variable type is not used set the number to 0.

Objects address 300 for example address of the first variable of this typeThe Object address is used to access the variables from a control station via a RTU connection (according to IEC-60870/101 and /104; DNP3).

Datatype INT for example Unity Pro datatype

Query cycle 1000ms for example choice of cycle defined in the Common settings

Variation method TIMEINTEGRALPERCENTFIXED

variation of a variable to avoid multiple events with lowest values / value changes

Variation value 100 for example value for the configured Variation method (Example for the variation method TIMEINTEGRAL: integrated value until the data point variable gets transmitted.

Variation reference

32767 for example reference value to which the measured value will be normalized

EIO0000000547 11/2009 27

Page 28: EIO0000000547 11/2009 RTU Configuration Software

RTU Configuration Software

Integrated Totals Properties

Overview

Select Integrated totals in the Station Configuration Browser to open the properties window of the Integrated total variable type.

For information on how variable names are generated please refer to Variable Name Creation (see page 18).

Data/Properties

You can define the following data/properties for the Integrated total variable type:

NOTE: For all used variable types the Number of objects and the Objects address have to be defined.

Data Property Description

Prefix IT for example IEC variable type specific prefixFor variable name generation this prefix is merged with a 4-digits incremental number.Example: IT0001

Structure name IntegratedTotals for example

name of the subelement of the variable structure in Unity Pro

Number objects 10 for example number of variables of this typeNOTE: If this variable type is not used set the number to 0.

Objects address 400 for example address of the first variable of this typeThe Object address is used to access the variables from a control station via a RTU connection (according to IEC-60870/101 and /104; DNP3).

Datatype INT for example Unity Pro datatype

Query cycle 1000ms for example

choice of cycle defined in the Common settings

Periodic event is used

check box If this check box is activated the integrated total values are saved periodically. See Periodic event.

Periodic event 15 min for example

time span between 2 savings of the integrated total valuesYou can select the Periodic event data from a list (10 sec up to 1 day).This property is used only, if the Periodic event is used check box is activated.

Reset value 1000000 for example

Overflow value that must be exceeded, for the integrated total value to be reset.

28 EIO0000000547 11/2009

Page 29: EIO0000000547 11/2009 RTU Configuration Software

RTU Configuration Software

Single Commands Properties

Overview

Select Single commands in the Station Configuration Browser to open the properties window of the Single command variable type.

For information on how variable names are generated please refer to Variable Name Creation (see page 18).

Data/Properties

You can define the following data/properties for the Single command variable type:

NOTE: For all used variable types the Number of objects and the Objects address have to be defined.

Data Property Description

Prefix SC for example IEC variable type specific prefixFor variable name generation this prefix is merged with a 4-digits incremental number.Example: SC0001

Structure name SingleCommands for example

name of the subelement of the variable structure in Unity Pro

Number objects 10 for example number of variables of this typeNOTE: If this variable type is not used set the number to 0.

Objects address 500 for example address of the first variable of this typeThe Object address is used to access the variables from a control station via a RTU connection (according to IEC-60870/101 and /104; DNP3).

Datatype BOOL for example Unity Pro datatype

EIO0000000547 11/2009 29

Page 30: EIO0000000547 11/2009 RTU Configuration Software

RTU Configuration Software

Double Commands Properties

Overview

Select Double commands in the Station Configuration Browser to open the properties window of the Double command variable type.

For information on how variable names are generated please refer to Variable Name Creation (see page 18).

Data/Properties

You can define the following data/properties for the Double command variable type:

NOTE: For all used variable types the Number of objects and the Objects address have to be defined.

Data Property Description

Prefix DC for example IEC variable type specific prefixFor variable name generation this prefix is merged with a 4-digits incremental number.Example: DC0001

Structure name DoubleCommands for example

name of the subelement of the variable structure in Unity Pro

Number objects 10 for example number of variables of this typeNOTE: If this variable type is not used set the number to 0.

Objects address 600 for example address of the first variable of this typeThe Object address is used to access the variables from a control station via a RTU connection (according to IEC-60870/101 and /104; DNP3).

Datatype DBOOL for example Unity Pro datatype

30 EIO0000000547 11/2009

Page 31: EIO0000000547 11/2009 RTU Configuration Software

RTU Configuration Software

Set Points Properties

Overview

Select Set points in the Station Configuration Browser to open the properties window of the Set point variable type.

For information on how variable names are generated please refer to Variable Name Creation (see page 18).

Data/Properties

You can define the following data/properties for the Set points variable type:

NOTE: For all used variable types the Number of objects and the Objects address have to be defined.

Data Property Description

Prefix SE for example IEC variable type specific prefixFor variable name generation this prefix is merged with a 4-digits incremental number.Example: SP0001

Structure name SetPoints for example

name of the subelement of the variable structure in Unity Pro

Number objects 10 for example number of variables of this typeNOTE: If this variable type is not used set the number to 0.

Objects address 700 for example address of the first variable of this typeThe Object address is used to access the variables from a control station via a RTU connection (according to IEC-60870/101 and /104; DNP3).

Datatype INT for example Unity Pro datatype

EIO0000000547 11/2009 31

Page 32: EIO0000000547 11/2009 RTU Configuration Software

RTU Configuration Software

Import of Data to Unity Pro

Overview

After building the configuration (Build → Configuration), you can import the application specific part automatically to Unity Pro by selecting Build → Prepare Unity Pro part....

Procedure

NOTE: Using Open: Unity application... or Import: Unity application... you have to verify that the %MW addresses generated with the RTU Configuration Software are not used for other variables in the Unity application you are opening or importing.

Batch Processing

NOTE: Using the so called Batch processing you can create 1 new Unity Pro application for every station in 1 step.

Step Action

1 Select the Station you want to import.

2 Either open an existing Unity Pro application using Open: Unity application...or create a new one using Create: Unity application...or import an existing XEF file using Import: Unity application...

3 Import the generated sections and variables of the selected station by clicking the Generate button.

32 EIO0000000547 11/2009

Page 33: EIO0000000547 11/2009 RTU Configuration Software

RTU Configuration Software

Edit Variables

Overview

For each variable you can insert an additional comment in the variable list using the Variables tab.

Also a measurement unit can be defined for the Measured values.

An optional text can be defined for all BOOL and DBOOL variables to indicate the value of the variable.

This text can be displayed in an HMI for the values 1 or rather 0 of the variable.

XML File

After the generation, an Excel XML file is available for each station in the corresponding folder, which documents the whole variable configuration.

The name of this file is build accordingly to the following scheme:

<Station Prefix>_VariablesExcel.xml

EIO0000000547 11/2009 33

Page 34: EIO0000000547 11/2009 RTU Configuration Software

RTU Configuration Software

34 EIO0000000547 11/2009

Page 35: EIO0000000547 11/2009 RTU Configuration Software

EIO0000000547 11/2009

Appendices

EIO0000000547 11/2009 35

Page 36: EIO0000000547 11/2009 RTU Configuration Software

36 EIO0000000547 11/2009

Page 37: EIO0000000547 11/2009 RTU Configuration Software

EIO0000000547 11/2009

A

RTU Application Example

EIO0000000547 11/2009

RTU Application Example

Overview

This chapter provides information on the configuration of a W@DE module using the RTU Configuration Software.

What's in this Chapter?

This chapter contains the following topics:

Topic Page

Configuration with the Embedded Web Server 38

RTU Configuration Software Settings 40

Resulting Variables 45

37

Page 38: EIO0000000547 11/2009 RTU Configuration Software

RTU Application Example

Configuration with the Embedded Web Server

Overview

The configuration of the RTU transmission protocol has to be done once using the embedded web server of the W@DE modules.

This can be done before or after using the RTU Configuration Software.

Communication Configuration

In the Modbus master Communication Configuration dialog you have to configure the general parameters for the Modbus communication (e.g. reply timeout, transmission speed, parity, etc.).

The topics are automatically configured and linked to the variables by the import of the configuration file from the RTU Configuration Software.

38 EIO0000000547 11/2009

Page 39: EIO0000000547 11/2009 RTU Configuration Software

RTU Application Example

Protocol Parameters

In the Protocol Parameters IEC 60870-5-101 dialog you have toconfigure the settings for transmission with time-tag (with/without and 3-Byte/7-Byte time-tag)adjust the transmission priority of the classes

In the example the measurement values are transmitted as normalized values.

Therefore you have to configure the parameter of the measured value as shown below.

EIO0000000547 11/2009 39

Page 40: EIO0000000547 11/2009 RTU Configuration Software

RTU Application Example

RTU Configuration Software Settings

Overview

For the RTU application example please define the data/properties listed below.

For information on how variable names are generated please refer to Variable Name Creation (see page 18).

Device Configuration

Data Property Description/Comment

Description This is an example station. -

Version 0.0.001 version of the station configuration

PLC Select M340 from the drop-down list.

PLC, the module communicates with

Station prefix Tele1 This prefix will be used to generate the variable names.

Prefix is used activate the check box -

Modbus slave address

32 Modbus Serial Line slave address

Network address [x.y.z.n]

- Modbus TCP/IP address of the station (not used for this example)

Objects start address

1000 start address of the ASDU data (%MW)

Quality bits start address

100 start address of the quality data (%MW)

Structure name RTU name of the variable structure in Unity Pro

40 EIO0000000547 11/2009

Page 41: EIO0000000547 11/2009 RTU Configuration Software

RTU Application Example

Single Points

The above properties correspond to 25 single points starting from the object address 100.

The variable names start with Tele1_SP0000_100_1000.

2 WORDs are required to transmit these 25 single points.

Single Commands

The above properties correspond to 15 single commands starting from the object address 500.

The variable names start with Tele1_SC0000_500_1002.

Only 1 WORD (%MW1002) is required to transmit these 15 single commands.

Data Property Description

Prefix SP For variable name generation this prefix is merged with a 4-digits incremental number.

Structure name SinglePoints name of the subelement of the variable structure in Unity Pro

Number objects 25 number of variables of this type

Objects address 100 address of the first variable of this type

Datatype BOOL Unity Pro datatype

Query cycle 1000ms choice of cycle defined in the Common settings

Data Property Description

Prefix SC For variable name generation this prefix is merged with a 4-digits incremental number.

Structure name SingleCommands name of the subelement of the variable structure in Unity Pro

Number objects 15 number of variables of this type

Objects address 500 address of the first variable of this type

Datatype BOOL Unity Pro datatype

EIO0000000547 11/2009 41

Page 42: EIO0000000547 11/2009 RTU Configuration Software

RTU Application Example

Double Points

The above properties correspond to 10 double points starting from the object address 200.

The variable names start with Tele1_DP0000_200_1003.

2 WORDs are required to transmit these 10 double points.

Double Commands

The above properties correspond to 5 double commands starting from the object address 600.

The variable names start with Tele1_DC0000_600_1005.

Only 1 WORD is required to transmit these 5 double commands.

Data Property Description

Prefix DP For variable name generation this prefix is merged with a 4-digits incremental number.

Structure name DoublePoints name of the subelement of the variable structure in Unity Pro

Number objects 10 number of variables of this type

Objects address 200 address of the first variable of this type

Datatype DBOOL Unity Pro datatype

Query cycle 5000ms choice of cycle defined in the Common settings

Data Property Description

Prefix DC For variable name generation this prefix is merged with a 4-digits incremental number.

Structure name DoubleCommands name of the subelement of the variable structure in Unity Pro

Number objects 5 number of variables of this type

Objects address 600 address of the first variable of this type

Datatype DBOOL Unity Pro datatype

42 EIO0000000547 11/2009

Page 43: EIO0000000547 11/2009 RTU Configuration Software

RTU Application Example

Measured Values

The above properties correspond to 20 measured values starting from the object address 300.

Variation value was set to 100 and Variation reference was set to 32767.

The variable names start with Tele1_ME0000_300_1006.

20 WORDs are required to transmit these 20 measured values.

Set Points

Set Number objects to 0. So all other settings for Set points will be ignored.

Data Property Description

Prefix ME For variable name generation this prefix is merged with a 4-digits incremental number.

Structure name MeasuredValues name of the subelement of the variable structure in Unity Pro

Number objects 20 number of variables of this type

Objects address 300 address of the first variable of this type

Datatype INT Unity Pro datatype

Query cycle 1000ms choice of cycle defined in the Common settings

Variation method select TIMEINTEGRAL from the drop-down list

variation of a variable to avoid multiple events with lowest values / value changes

Variation value 100 value for the configured Variation method(TIMEINTEGRAL: integrated value until the data point variable gets transmitted.

Variation reference 32767 reference value to which the measured value will be normalized

EIO0000000547 11/2009 43

Page 44: EIO0000000547 11/2009 RTU Configuration Software

RTU Application Example

Integrated Totals

The above properties correspond to 3 integrated totals starting from the object address 400.

Reset value was set to 1000000 and Periodic event was set to 5 min.

The variable names start with Tele1_IT0000_400_1026.

6 WORDs are required to transmit these 3 integrated totals.

Data Property Description

Prefix IT For variable name generation this prefix is merged with a 4-digits incremental number.

Structure name IntegratedTotals

name of the subelement of the variable structure in Unity Pro

Number objects 3 number of variables of this type

Objects address 400 address of the first variable of this type

Datatype INT Unity Pro datatype

Query cycle 1000ms choice of cycle defined in the Common settings

Periodic event is used

activate this check box

If this check box is activated the integrated total values are saved periodically. See Periodic event.

Periodic event 5 min time span between 2 savings of the integrated total valuesThis property is used only, if the Periodic event is used check box is activated.

Reset value 1000000 Overflow value that must be exceeded, for the integrated total value to be reset.

44 EIO0000000547 11/2009

Page 45: EIO0000000547 11/2009 RTU Configuration Software

RTU Application Example

Resulting Variables

The complete configuration includes 32 WORDs in the area of %MW1000 to %MW1031.

Variable Type Name Object Address %MW Address

Single point1 Tele1_SP0000_100_1000 100 1000.0

Single point2 Tele1_SP0001_101_1000 101 1000.1

Single point3 Tele1_SP0002_102_1000 102 1000.2

Single point4 Tele1_SP0003_103_1000 103 1000.3

Single point5 Tele1_SP0004_104_1000 104 1000.4

Single point6 Tele1_SP0005_105_1000 105 1000.5

Single point7 Tele1_SP0006_106_1000 106 1000.6

Single point8 Tele1_SP0007_107_1000 107 1000.7

Single point9 Tele1_SP0008_108_1000 108 1000.8

Single point10 Tele1_SP0009_109_1000 109 1000.9

Single point11 Tele1_SP0010_110_1000 110 1000.10

Single point12 Tele1_SP0011_111_1000 111 1000.11

Single point13 Tele1_SP0012_112_1000 112 1000.12

Single point14 Tele1_SP0013_113_1000 113 1000.13

Single point15 Tele1_SP0014_114_1000 114 1000.14

Single point16 Tele1_SP0015_115_1000 115 1000.15

Single point17 Tele1_SP0016_116_1001 116 1001.0

Single point18 Tele1_SP0017_117_1001 117 1001.1

Single point19 Tele1_SP0018_118_1001 118 1001.2

Single point20 Tele1_SP0019_119_1001 119 1001.3

Single point21 Tele1_SP0020_120_1001 120 1001.4

Single point22 Tele1_SP0021_121_1001 121 1001.5

Single point23 Tele1_SP0022_122_1001 122 1001.6

Single point24 Tele1_SP0023_123_1001 123 1001.7

Single point25 Tele1_SP0024_124_1001 124 1001.8

Single command1 Tele1_SC0000_500_1002 500 1002.0

Single command2 Tele1_SC0001_501_1002 501 1002.1

Single command3 Tele1_SC0002_502_1002 502 1002.2

Single command4 Tele1_SC0003_503_1002 503 1002.3

EIO0000000547 11/2009 45

Page 46: EIO0000000547 11/2009 RTU Configuration Software

RTU Application Example

Single command5 Tele1_SC0004_504_1002 504 1002.4

Single command6 Tele1_SC0005_505_1002 505 1002.5

Single command7 Tele1_SC0006_506_1002 506 1002.6

Single command8 Tele1_SC0007_507_1002 507 1002.7

Single command9 Tele1_SC0008_508_1002 508 1002.8

Single command10 Tele1_SC0009_509_1002 509 1002.9

Single command11 Tele1_SC0010_510_1002 510 1002.10

Single command12 Tele1_SC0011_511_1002 511 1002.11

Single command13 Tele1_SC0012_512_1002 512 1002.12

Single command14 Tele1_SC0013_513_1002 513 1002.13

Single command15 Tele1_SC0014_514_1002 514 1002.14

Double point1 Tele1_DP0000_200_1003 200 1003.0

Double point2 Tele1_DP0001_201_1003 201 1003.2

Double point3 Tele1_DP0002_202_1003 202 1003.4

Double point4 Tele1_DP0003_203_1003 203 1003.6

Double point5 Tele1_DP0004_204_1003 204 1003.8

Double point6 Tele1_DP0005_205_1003 205 1003.10

Double point7 Tele1_DP0006_206_1003 206 1003.12

Double point8 Tele1_DP0007_207_1003 207 1003.14

Double point9 Tele1_DP0008_208_1004 208 1004.0

Double point10 Tele1_DP0009_209_1004 209 1004.2

Double command1 Tele1_DC0000_600_1005 600 1005.0

Double command2 Tele1_DC0001_601_1005 601 1005.2

Double command3 Tele1_DC0002_602_1005 602 1005.4

Double command4 Tele1_DC0003_603_1005 603 1005.6

Double command5 Tele1_DC0004_604_1005 604 1005.8

Measured value1 Tele1_ME0000_300_1006 300 1006

Measured value2 Tele1_ME0001_301_1007 301 1007

Measured value3 Tele1_ME0002_302_1008 302 1008

Measured value4 Tele1_ME0003_303_1009 303 1009

Measured value5 Tele1_ME0004_304_1010 304 1010

Measured value6 Tele1_ME0005_305_1011 305 1011

Measured value7 Tele1_ME0006_306_1012 306 1012

Measured value8 Tele1_ME0007_307_1013 307 1013

Variable Type Name Object Address %MW Address

46 EIO0000000547 11/2009

Page 47: EIO0000000547 11/2009 RTU Configuration Software

RTU Application Example

Measured value9 Tele1_ME0008_308_1014 308 1014

Measured value10 Tele1_ME0009_309_1015 309 1015

Measured value11 Tele1_ME0010_310_1016 310 1016

Measured value12 Tele1_ME0011_311_1017 311 1017

Measured value13 Tele1_ME0012_312_1018 312 1018

Measured value14 Tele1_ME0013_313_1019 313 1019

Measured value15 Tele1_ME0014_314_1020 314 1020

Measured value16 Tele1_ME0015_315_1021 315 1021

Measured value17 Tele1_ME0016_316_1022 316 1022

Measured value18 Tele1_ME0017_317_1023 317 1023

Measured value19 Tele1_ME0018_318_1024 318 1024

Measured value20 Tele1_ME0019_319_1025 319 1025

Integrated total1 Tele1_IT0000_400_1026 400 1026

Integrated total2 Tele1_IT0002_401_1028 401 1028

Integrated total3 Tele1_IT0003_402_1030 402 1030

Variable Type Name Object Address %MW Address

EIO0000000547 11/2009 47

Page 48: EIO0000000547 11/2009 RTU Configuration Software

RTU Application Example

48 EIO0000000547 11/2009

Page 49: EIO0000000547 11/2009 RTU Configuration Software

Index

EIO0000000547 11/2009

CBA

Index

Bbrowser

station configuration, 22

Ccommon settings, 23configuration

device, 24configuration with the embedded web server, 38

Ddevice configuration, 24DFBs, DDT, 15double commands

properties, 30double points

properties, 26

Eedit variables, 33embedded web server

configuration, 38example

configuration tool settings, 40resulting variables, 45

EIO0000000547 11/2009

Ggeneral information, 10

Hhardware requirements, 13

Iimport of data to Unity Pro, 32information object address, 19installation, 14integrated totals

properties, 28

Llibrary

RTU, 15

Mmeasured values

properties, 27

Nname creation

variables, 18

49

Page 50: EIO0000000547 11/2009 RTU Configuration Software

Index

Oobject address, 19

Pproperties

double commands, 30double points, 26integrated totals, 28measured values, 27set points, 31single commands, 29single points, 25

Rrequirements

hardware, 13software, 14

resulting variables (example), 45RTU library, 15

Sset points

properties, 31settings

common, 23settings (example)

configuration tool, 40single commands

properties, 29single points

properties, 25software requirements, 14station configuration browser, 22

UUnity Pro

import of data, 32user interface, 20

50

Vvariable name creation, 18variables

edit, 33

EIO0000000547 11/2009