14
TITLE: PROJECT: BY REVISIONS SHEET JOB SCALE DATE CHECKED DRAWN STAMP H C S ENGINEERING, INC. CONSULTING ELECTRICAL ENGINEERS 4512 FEATHER RIVER DRIVE, SUITE F STOCKTON, CA 95219 (209) 478 - 8270 email address richard@hcs - eng.com H H H H T T T I I I M M M S S S S C C C C D D D D R R R R A A A A H H H C C C I I I R R R R No. E14303 No. E14303 No. E14303 No. E14303 Exp. 6 Exp. 6 Exp. 6 Exp. 6- - -30 30 30 30- - -21 21 21 21 E E E L L L L E E E E C C C C T T T T R R R R I I I I C C C C A A A A L L L R R R R E E E E G G G G I I I I S S S S T T T T E E E R R R E E E D D D P P P P R R R R O O O O F F F F E E E E S S S S S S S S I I I I O O O O N N N N A A A A L L L E E E N N N G G G G I I I I N N N N E E E E E E E E R R R R E E E E O O O O F F F F C C C C A A A A L L L L I I I I F F F F O O O O R R R N N N I I I A A A S S S S T T T A A A T T T 8/12/2019 8:23:11 AM C:\Users\RichardSmith\HCS ENGINEERING\Projects - Documents\Add to 2018\PORT WAREHOUSE 5\Port Chargers Rev 3.rvt A0 2017.xxx Checker Author WORLD CHARGERS PORT OF STOCKTON WAREHOUSE 5 Enter address here COVER SHEET Project #: 2017.xxx Drafter: Author Engineer: Designer MTD MOUNTED MTL METAL NIC NOT IN CONTRACT NO NUMBER NTS NOT TO SCALE O.P. OVERFLOW PIPE OA OVERALL OC ON CENTER OD OUTSIDE DIAMETER OPG OPENING OPP OPPOSITE PERM PERIMETER PG PAINT GRADE PLAM PLASTIC LAMINATE PLAS PLASTER PR PAIR PT PAINT R RISER RAD RADIUS RCP REFLECTED CEILING PLAN RD ROOF DRAIN REF REFRIGERATOR REINF REINFORCED REQD REQUIRED RESIL RESILIENT RO ROUGH OPENING RTU ROOF TOP UNIT (MECH) SAFB SOUND ATTENUATION FIBER BATT SC SCUPPER SCD SEE CIVIL DRAWINGS SCHED SCHEDULE SEAL SEALANT SECT SECTION SED SEE ELECTRICAL DRAWINGS SF SQUARE FOOT SFPD SEE FIRE PROTECTION DRAWINGS SHT SHEET SIM SIMILAR SLD SEE LANDSCAPE DRAWINGS SMD SEE MECHANICAL DRAWINGS SPD SEE PLUMBING DRAWINGS SPEC SPECIFICATION SQ SQUARE SS STAINLESS STEEL SSD SEE STRUCTURAL DRAWINGS STD STANDARD STL STEEL STOR STORAGE SUSP SUPSPENDED SYM SYMMMETRICAL T TREAD THK THICK THR THRESHOLD TO TOP OF TYP TYPICAL UC UNDERCUT UNFIN UNFINISHED UNO ULNESS NOTED OTHERWISE UON UNLESS OTHERWISE NOTED VCT VINYL COMPOSITION TILE VIF VERIFY IN FIELD VTR VENT TERMINATION PIPE VWC VINYL WALL COVERING W/ WITH W/O WITHOUT WC WATERCLOSET WIN WINDOW WP WATERPROOF WSCT WAINSCOT WT WEIGHT ACOUS ACOUSTICAL ACT ACOUSTICAL CEILING TILE AD AREA DRAIN ADJ ADJUSTABLE AFF ABOVE FINISH FLOOR ALT ALTERNATE ARCH ARCHITECT B.O. BOTTOM OF BD BOARD BET BETWEEN BLKG BLOCKING BM BEAM BOT BOTTOM BRKT BRACKET BUR BUILT UP ROOF C.G. CORNER GUARD CAB CABINET CALK CAULKING CER CERAMIC CJ CONTROL JOINT CLOS CLOSET CLR CLEAR CO CASED OPENING COL COLUMN CONT CONTINUOUS CPT CARPET CT CERAMIC TILE CTR CENTER DIA DIAMETER DIM DIMENSION DN DOWN DR DOOR DS DOWN SPOUT DWG DRAWING (E) EXISTING EA EACH ELEV ELEVATION EMER EMERGENCY ENCL ENCLOSURE EOS EDGE OF SLAB EQ EQUAL EW EACH WAY F.O. FACE OF FA FIRE ALARM FAP FIRE ANNUNCIATOR PANEL FD FLOOR DRAIN FE FIRE EXTINGUISHER FEC FIRE EXTINGUISHER CABINET FH FIRE HYDRANT FIN FINISH FRP FIBER-REINFORCED PLASTIC FT FOOT OR FEET FUR FURRING G.S.M. GALVANIZED SHEET METAL GAL GALLON GALV GALVANIZED GB GRAB BAR GC GENERAL CONTRACTOR GL GLASS GND GROUND GWB GYPSUM BOARD H.W.H. HOT WATER HEATER HDWD HARDWOOD HM HOLLOW METAL HT HEIGHT ID INSIDE DIAMETER INSUL INSULATION INT INTERIOR JST JOIST JT JOINT LAM LAMINATE LAV LAVATORY LDG LANDING LT LIGHT MEMB MEMBRANE MFR MANUFACTURER MIN MINIMUM MISC MISCELLANEOUS MO MASONRY OPENING REFERENCE DESCRIPTION INTERPRETATION DESCRIPTION SCOPE NEW METAL BUILDING TO HOUSE EV CHARGERS LOCATION WAREHOUSE 5 and THE WEST COMPLEX ZONING APN SPECIAL USE PERMIT GENERAL INFORMATION 1ST FLOOR AREA 1900 2ND FLOOR AREA N/A TOTAL BUILDING AREA 1900 ACTUAL BUILDING HEIGHT 20'-0" ACTUAL NUMBER OF STORIES 1 STORIES OCCUPANCY CBC 303.1 GROUP - CBC 305 GROUP - CBC 508.3 AUTOMATIC FIRE SPRINKLERS CBC TABLE 601 CONSTRUCTION TYPE CBC TABLE 503 ALLOWABLE BUIDING HEIGHT CBC TABLE 503 ALLOWABLE NUMBER OF STORIES CBC TABLE 503 ALLOWABLE BUIDING AREA CBC 506.1 AREA INCREASE Aa = (At + [At X If] + [At X Is]) Aa = (_____ + [If NOT USED] + [_____ X 2]) Aa = (_____ + 0 + _____) TITLE 19 CCR, PUBLIC SAFETY, STATE FIRE MARSHAL REGULATIONS TITLE 24 CCR, PART 1 - 2016 BUILDING STANDARDS ADMINISTRATIVE CODE TITLE 24 CCR, PART 2 - 2016 CALIFORNIA BUILDING CODE, VOL. 1 & 2 (CBC) (2015 IBC, AS AMENDED BY CA) TITLE 24 CCR, PART 3 - 2016 CALIFORNIA ELECTRICAL CODE (CEC) (2014 NEC, AS AMENDED BY CA) TITLE 24 CCR, PART 4 - 2016 CALIFORNIA MECHANICAL CODE (CMC) (2012 IAPMO UMC, AS AMENDED BY CA) TITLE 24 CCR, PART 5 - 2016 CALIFORNIA PLUMBING CODE (CPC) (2011 IAPMO UPC, AS AMENDED BY CA) TITLE 24 CCR, PART 6 - 2016 CALIFORNIA ENERGY CODE TITLE 24 CCR, PART 9 - 2016 CALIFORNIA FIRE CODE (CFC) (2012 IFC, AS AMENDED BY CA) TITLE 24 CCR, PART 11 - 2016 CALIFORNIA GREEN BUILDING STANDARDS CODE TITLE 24 CCR, PART 12 - 2016 CALIFORNIA REFERENCED STANDARDS (PARTIAL LIST - SEE CBC CH. 35 AND CFC CH. 80) 2016 NFPA 13, INSTALLATION OF SPRINKLER SYSTEMS (CA AMENDED) 2013 NFPA 14, INSTALLATION OF STANDPIPE AND HOSE SYSTEMS 2016 NFPA 20, INSTALLATION OF STATIONARY PUMPS FOR FIRE PROTECTION 2013 NFPA 22, WATER TANKS FOR PRIVATE FIRE PROTECTION 2016 NFPA 24, INSTALLATION OF PRIVATE FIRE SERVICE MAINS 2016 NFPA 72, NATIONAL FIRE ALARM CODE (CA AMENDED); SEE UL STD. 1971 FOR "VISUAL DEVICES" 2016 NFPA 80, FIRE DOOR AND OTHER OPENING PROTECTIVES 2015 NFPA 2001, CLEAN AGENT FIRE EXTINGUISHING SYSTEMS 2005 UL 300, CLASS I HOOD FIRE SUPPRESSION SYSTEMS 2003 UL, 464, AUDIBLE SIGNAL APPLIANCES 1999 UL 521, HEAT DETECTORS FOR FIRE PROTECTIVE SIGNALING SYSTEMS Electric Fork Lift Battery Chargers WAREHOUSE 5 and West Complex Chargers PORT OF STOCKTON ADDRESS: PHONE: CONTACT: EMAIL: PORT OF STOCKTON OWNER: ADDRESS: PHONE: CONTACT: EMAIL: HCS ENGINEERING 4512 FEATHER RIVER DR #F STOCKTON, CA 95219 209.478.8270 RICHARD SMITH RICHARD@HCS - ENG.COM ELECTRICAL ENGINEER: GENERAL NOTES CONTACTS PROJECT DATA SHEET INDEX APPLICABLE CODES SYMBOLS LEGEND ABBREVIATIONS 1. ON-SITE VERIFICATION OF ALL DIMENSIONS AND DETAILS SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR AND EACH SUBCONTRACTOR FOR HIS INDIVIDUAL WORK. THE OWNER OR ARCHITECT SHALL BE NOTIFIED IF ANY DISCREPANCIES ARE FOUND PRIOR TO COMMENCING ANY WORK. THE RESPONSIBILITY FOR WORK COMPLETED WITHOUT PROPER NOTIFICATION SHALL BE BORNE BY THE INDIVIDUAL CONTRACTOR INVOLVED. 2. THE CONTRACT DOCUMENTS INDICATE THE EXTENT AND APPROXIMATE LOCATION OF ELEMENTS OF THE BUILDING AND SITE. ALL CONDITIONS, LOCATIONS, DEVICES AND ELEMENTS SHALL BE VERIFIED BY THE CONTRACTOR PRIOR TO COMMENCING THE WORK. 3. ALL WORK PERFORMED IN CONNECTION WITH THESE CONTRACT DOCUMENTS SHALL COMPLY WITH THE AMERICANS WITH DISABILITIES ACT (ADA), ALL APPLICABLE STATE AND LOCAL CODES, ORDINANCES, AND ZONING REGULATIONS IN EFFECT AT THE TIME OF CONSTRUCTION. THIS PROJECT SHALL COMPLY WITH TITLE 24, 2016 CBC, CMC, CPC, CFC, CEC BASED ON THE 2016 CALIFORNIA ENERGY STANDARDS. 4. IT SHALL BE UNDERSTOOD THAT THE INTENT OF THESE CONSTRUCTION DOCUMENTS IS TO CONSTRUCT THE FACILITY IN ACCORDANCE WITH THE APPLICABLE CODES AND ORDINANCES. SHOULD ANY CONDITION BE UNCOVERED OR DEVELOP DURING THE EXECUTION OF THESE DOCUMENTS, WHICH IS NOT DEFINED HEREIN, THE CONTRACTOR SHALL CEASE WORK AND NOTIFY THE ARCHITECT AT ONCE. 5. THE TYPICAL DETAILS SHOWN IN THESE PLANS SHALL APPLY IN ALL SIMILAR CASES UNLESS SPECIFICALLY NOTED OTHERWISE. WHERE NO DETAIL IS SHOWN, CONSTRUCTION SHALL BE AS INDICATED FOR OTHER SIMILAR WORK AND, OR APPLICABLE INDUSTRY PRACTICE. 6. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL COORDINATION OF INSTALLATION, INSPECTION, AND FINAL APPROVAL OF ALL UTILITIES. 7. VERIFY ALL DIMENSIONS, EXISTING CONDITIONS, AND METHODS OF CONSTRUCTION PRIOR TO START OF ANY WORK. NOTIFY THE ARCHITECT OF ANY DISCREPANCIES. 8. IT IS NOT THE INTENT OF THESE CONTRACT DOCUMENTS TO SEPARATE THE WORK INTO SUBTRADE DIVISIONS. IT SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR TO DIVIDE THE WORK AND ORGANIZE ALL WORK AS REQUIRED TO COMPLETE THE WORK AS INTENDED BY THESE DOCUMENTS. 9. SITE DEVELOPMENT AND GRADING SHALL PROVIDE ACCESS TO PRIMARY ENTRANCES AND NORMAL PATHS OF TRAVEL, AND SHALL INCORPORATE PEDESTRIAN RAMPS, CURB RAMPS, ETC. ALL RAMPS SHALL HAVE A MAXIMUM SLOPE OF 1:12, OR AS NOTED ON THESE CONSTRUCTION DOCUMENTS. ANY PATH OF TRAVEL SHALL BE CONSIDERED A RAMP IF IT'S SLOPE IS GREATER THAN 1 FT. RISE IN 20 FT. RUN (5%) 10. EACH PARKING FACILITY WHERE PARKING IS PROVIDED FOR THE PUBLIC, GUESTS OR EMPLOYEES SHALL PROVIDE ACCESSIBLE PARKING AND LOADING STALLS DESIGNATED SPECIFICALLY FOR HANDICAPPED PERSONS. 11. THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING THE LOCATION OF ALL EXISTING UNDERGROUND UTILITIES PRIOR TO THE COMMENCEMENT OF WORK. HE SHALL BE RESPONSIBLE FOR THE LOCATION AND PRESERVATION OF ALL SUCH FACILITIES IN THE AREA OF CONSTRUCTION, AND SHALL NOTIFY UTILITY COMPANIES 48 HOURS IN ADVANCE OF ANY CONSTRUCTION (UNDERGROUND SERVICE ALERT 1-800-227-2600) 12. EACH PARKING SPACE RESERVED FOR PERSONS WITH PHYSICAL DISABILITIES SHALL BE IDENTIFIED BY A REFLECTORIZED SIGN PERMANENTLY POSTED IMMEDIATELY ADJACENT TO AND VISIBLE FROM EACH STALL OR SPACE, CONSISTING OF A PROFILE VIEW OF A WHEELCHAIR OCCUPANT IN WHITE ON A BLUE BACKGROUND. THE SIGN SHALL NOT BE SMALLER THAN 70 SQ. IN. IN AREA AND, WHEN POSTED IN A PATH OF TRAVEL, SHALL BE A MINIMUM HEIGHT OF 80 INCHES FROM THE BOTTOM OF THE SIGN TO THE PARKING SPACE FINISH GRADE, UON. IN ADDITION, A SIGN, AS SPECIFIED IN TITLE 24 ACCESSIBILITY STANDARDS, SHALL BE POSTED IN A CONSPICUOUS PLACE, AT EACH ENTRANCE TO OFF-STREET PARKING FACILITIES, OR IMMEDIATELY ADJACENT TO AND VISIBLE FROM EACH STALL OR SPACE. SAID SIGNS SHALL BE NOT LESS THAN 17 INCHES X 22 INCHES IN SIZE WITH LETTERING NOT LESS THAN 1 INCH HIGH. 13. PROVIDE A CLEAR AND LEVEL LANDING ON EACH SIDE OF AN EXIT DOOR. THE LANDING SHALL BE 48 INCHES IN LENGTH WHERE THE DOOR SWINGS AWAY FROM THE LANDING, AND 60 INCHES IN LENGTH IN THE DIRECTION OF DOOR SWING AS MEASURED AT RIGHT ANGLES TO THE PLANE OF THE DOOR IN THE CLOSED POSITION. 14. GENERAL DEMOLITION: WHENEVER EXISTING FACILITIES OR MATERIALS ARE REMOVED, DAMAGED, BROKEN, OR CUT IN THE INSTALLATION OF WORK COVERED BY THE DRAWINGS AND SPECIFICATIONS, SAID FACILITIES AND MATERIALS SHALL BE REPLACED AT THE CONTRACTOR'S EXPENSE. SAID FACILITIES OR MATERIALS SHALL BE EQUAL TO OR BETTER THAN THE ORIGINAL FACILITIES OR MATERIALS. THE FINISH PRODUCT SHALL BE SUBJECT TO THE APPROVAL OF THE COUNTY AND ITS AGENTS. 15. NO WORK SHALL COMMENCE AT THE PROJECT SITE BEFORE A BUILDING PERMIT IS FULLY EXECUTED AND AVAILABLE FOR POSTING AT THE JOB SITE. 16. CONSTRUCTION LIMITS: CONTRACTOR AND SUB-CONTRACTORS, WORKERS AND OTHER PERSONNEL RELATED TO THIS SCOPE OF WORK, SHALL BE CONFINED WITH THE AREAS DESIGNATED AS CONSTRUCTION LIMITS AS INDICATED BY THESE DRAWINGS AND RELATED AREAS. AREAS BEYOND THIS SCOPE OF WORK SHALL BE OFF LIMITS, AND THEIR USE SHALL BE PROHIBITED WITHOUT PRIOR AUTHORIZATION OF SAN JOAQUIN COUNTY. THE GENERAL CONTRACTOR SHALL VERIFY THESE LIMITS AND BE RESPONSIBLE TO INFORM THE APPROPRIATE PERSONNEL AND ENFORCE THESE LIMITS. 17. PROVIDE CONTINUOUS 16GA. X REQUIRED WIDTH (6" MIN.) FLAT BACKING STRAP AT WALLS WITH WALL MOUNTED EQUIPMENT, CASEWORK, AND/OR ACCESSORIES - TYPICAL UNLESS OTHERWISE NOTED. 18. THE CONTRACTOR SHALL CAREFULLY STUDY AND COMPARE THE CONTRACT DOCUMENTS AND THE EXISTING FIELD CONDITIONS, AND SHALL AT ONCE REPORT TO THE ARCHITECT ANY ERROR, INCONSISTENCY, OR OMISSION HE MAY DISCOVER. THE CONTRACTOR SHALL PERFORM NO PORTION OF THE WORK AT ANY TIME WITHOUT APPROVED CONTRACT DOCUMENTS OR WHERE REQUIRED, APPROVED SHOP DRAWINGS, PRODUCT LITERATURE, DATA, SAMPLES OR INSTALLATION INSTRUCTIONS. 19. THE CONTRACTOR SHALL OBTAIN AN ENCROACHMENT PERMIT, WHERE APPLICABLE, FOR ANY WORK DONE WITHIN THE RIGHT-OF-WAY OR EASEMENTS FROM THE AUTHORITY HAVING JURISDICTION. THE CONTRACTOR SHALL NOTIFY THE OWNER 48 HOURS IN ADVANCE OF COMMENCEMENT OF THE WORK OR AS REQUIRED BY SAID PERMITS. 20 THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CUTTING, FITTING, OR PATCHING THAT MAY BE REQUIRED TO COMPLETE THE INTENT OF THESE CONSTRUCTION DOCUMENTS, TO MAKE IT'S SEVERAL PARTS FIT TOGETHER PROPERLY. THE CONTRACTOR SHALL PATCH ARCHITECTURAL FINISHES AS NECESSARY TO ACCOMPLISH WORK DEFINED IN STRUCTURAL, MECHANICAL, PLUMBING, ELECTRICAL, AND ARCHITECTURAL DRAWINGS. EXISTING FIELD CONDITIONS SHALL BE VERIFIED BY THE CONTRACTOR AND ACCEPTED AS CONDITIONS OF THIS SCOPE OF WORK. 21. THE ELECTRICAL CONTRACTOR SHALL COORDINATE WITH PG&E AND/OR SERVICE PROVIDER FOR ANY NEW SERVICE INSTALLATIONS. THE CONTRACTOR SHALL COORDINATE THE SHUT DOWN OF THE FACILITIES WITH THE OWNER FOR AS MINIMAL DURATION AS POSSIBLE. INTERCEPT THE EXISTING SERVICE CONDUIT, EXTEND IT TO NEW TRANSFORMERS AND PAD (TO BE INSTALLED BY CONTRACTOR) AND EXTEND SECONDARY CONDUITS TO THE NEW SWITCHBOARD. COORDINATE WITH THE OWNER TO VERIFY LOCATION, PROVIDE TRAFFIC BARRIER POSTS PER PG&E REQUIREMENTS. 22. CONTRACTOR SHALL FLUSH ALL WATER, SEWER, AND DRAIN LINES PRIOR TO HOOK UP. 23. DIMENSIONS SHALL BE MEASURED TO FACE OF FRAMING, U.O.N. DO NOT SCALE DRAWINGS. 24. PROVIDE 2% SLOPE AWAY FROM THE BUILDING FOR 10'-0" AT FRONT AND SIDES. 25. NO DRAINAGE ACROSS OR ONTO ADJACENT PROPERTY. PROVIDE 2% SLOPE AWAY FROM THE BUILDING FOR 10'-0" AT FRONT AND SIDES. 26. DO NOT SCALE THE DRAWINGS. 27. SUBSTITUTIONS OR CHANGES AFFECTING THE APPROVED DRAWINGS, SPECIFICATIONS OR DSA REGULATED ITEMS SHALL BE MADE BY ADDENDA OR SUBMITTED AS; DSA 140 APPLICATION FOR APPROVAL OF CONSTRUCTION CHANGE DOCUMENT - CCD CATEGORY A/B, AS PER SECTION 4-338, PART 1 TITLE 24, CCR, AND INTERPRETATION OF REGULATION (IR) A-6. DEFERRED APPROVALS METAL BUILDING WITH FOUNDATION TO BE PROVIDED BY CONTACTOR WITH STAMPED SHOP DRAWINGS ADDRESS: PHONE: CONTACT: EMAIL: DILLON AND MUPHY 847 CLUFF AVE LODI, CA 95240 209.334.6613 JOE MURPHY [email protected] CIVIL ENGINEER: A0 COVER SHEET A1 WAREHOUSE 5 ARCHITECTURAL SITE PLAN A2 WAREHOUSE 5 ELEVATION A3 WAREHOUSE 5 FOUNDATION A4 WEST COMPLEX CANOPY E1 ELECTRICAL INFORMATION E2 WAREHOUSE 5 ELECTRICAL PLAN E3 WAREHOUSE 5 ELECTRICAL DETAILS E4 WEST COMPLEX ARRANGEMENT E5 WEST COMPLEX ELECTRICAL PLAN E6 WEST COMPLEX ELECTRICAL DETAILS S0 CANOPY STRUCTURAL NOTES S1.0 CANOPY FRAMING PLAN / SECTION S1.1 CANOPY DETAILS OWNER PROVIDED MATERIALS THE PORT OF STOCKTON WILL PROVIDE THE CONTRACTOR WITH A. EV CHARGERS

Electric Fork Lift Battery Chargers - Port of Stockton€¦ · 2016 nfpa 20, installation of stationary pumps for fire protection 2013 nfpa 22, water tanks for private fire protection

  • Upload
    others

  • View
    5

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Electric Fork Lift Battery Chargers - Port of Stockton€¦ · 2016 nfpa 20, installation of stationary pumps for fire protection 2013 nfpa 22, water tanks for private fire protection

TIT

LE

:P

RO

JE

CT

:

BYREVISIONS

SHEET

JOB

SCALE

DATE

CHECKED

DRAWN

STAMP

H C

S

EN

GIN

EE

RIN

G, IN

C.

CO

NS

UL

TIN

G E

LE

CT

RIC

AL

EN

GIN

EE

RS

451

2 F

EA

TH

ER

RIV

ER

DR

IVE

, S

UIT

E F

ST

OC

KT

ON

, C

A 9

521

9 (

20

9)

478

-82

70

em

ail

ad

dres

s r

ich

ard

@h

cs-e

ng

.co

m

HHHHTTTTIIII

MMMMSSSSCCCCDDDDRRRRAAAAHHHH

CCCCIIIIRRRR

No. E14303No. E14303No. E14303No. E14303Exp. 6Exp. 6Exp. 6Exp. 6----30303030----21212121

EEEE

LLLLEEEECCCCTTTTRRRR IIII CCCCAAAALLLL

RR RREEEEGGGGIIIISSSSTTTTEEEERRRR

EEEEDDDDPPPPRRRROOOOFFFFEEEESSSSSSSSIIIIOOOONNNNAAAALLLL

EEEENNNNGGGGIIIINNNNEEEEEEEERR RR

EEEEOOOOFFFF CCCCAAAALLLL IIIIFFFF

OOOORRRRNNNN

IIIIAAAA

SSSSTTTTAAAATTTT

8/12/2019 8:23:11 AM

C:\Users\RichardSmith\HCS ENGINEERING\Projects - Documents\Add to 2018\PORT WAREHOUSE 5\Port Chargers Rev 3.rvt

A0

2017.xxx

Checker

Author

WO

RLD

CH

AR

GE

RS

PO

RT

OF

ST

OC

KT

ON

WA

RE

HO

US

E 5

Ente

r addre

ss h

ere

CO

VE

R S

HE

ET

Pro

ject

#:

2017.x

xx D

raft

er:

Au

tho

r E

ng

ineer:

Desig

ner

MTD MOUNTED

MTL METAL

NIC NOT IN CONTRACT

NO NUMBER

NTS NOT TO SCALE

O.P. OVERFLOW PIPE

OA OVERALL

OC ON CENTER

OD OUTSIDE DIAMETER

OPG OPENING

OPP OPPOSITE

PERM PERIMETER

PG PAINT GRADE

PLAM PLASTIC LAMINATE

PLAS PLASTER

PR PAIR

PT PAINT

R RISER

RAD RADIUS

RCP REFLECTED CEILING PLAN

RD ROOF DRAIN

REF REFRIGERATOR

REINF REINFORCED

REQD REQUIRED

RESIL RESILIENT

RO ROUGH OPENING

RTU ROOF TOP UNIT (MECH)

SAFB SOUND ATTENUATION FIBERBATT

SC SCUPPER

SCD SEE CIVIL DRAWINGS

SCHED SCHEDULE

SEAL SEALANT

SECT SECTION

SED SEE ELECTRICAL DRAWINGS

SF SQUARE FOOT

SFPD SEE FIRE PROTECTIONDRAWINGS

SHT SHEET

SIM SIMILAR

SLD SEE LANDSCAPE DRAWINGS

SMD SEE MECHANICAL DRAWINGS

SPD SEE PLUMBING DRAWINGS

SPEC SPECIFICATION

SQ SQUARE

SS STAINLESS STEEL

SSD SEE STRUCTURAL DRAWINGS

STD STANDARD

STL STEEL

STOR STORAGE

SUSP SUPSPENDED

SYM SYMMMETRICAL

T TREAD

THK THICK

THR THRESHOLD

TO TOP OF

TYP TYPICAL

UC UNDERCUT

UNFIN UNFINISHED

UNO ULNESS NOTED OTHERWISE

UON UNLESS OTHERWISE NOTED

VCT VINYL COMPOSITION TILE

VIF VERIFY IN FIELD

VTR VENT TERMINATION PIPE

VWC VINYL WALL COVERING

W/ WITH

W/O WITHOUT

WC WATERCLOSET

WIN WINDOW

WP WATERPROOF

WSCT WAINSCOT

WT WEIGHT

ACOUS ACOUSTICAL

ACT ACOUSTICAL CEILING TILE

AD AREA DRAIN

ADJ ADJUSTABLE

AFF ABOVE FINISH FLOOR

ALT ALTERNATE

ARCH ARCHITECT

B.O. BOTTOM OF

BD BOARD

BET BETWEEN

BLKG BLOCKING

BM BEAM

BOT BOTTOM

BRKT BRACKET

BUR BUILT UP ROOF

C.G. CORNER GUARD

CAB CABINET

CALK CAULKING

CER CERAMIC

CJ CONTROL JOINT

CLOS CLOSET

CLR CLEAR

CO CASED OPENING

COL COLUMN

CONT CONTINUOUS

CPT CARPET

CT CERAMIC TILE

CTR CENTER

DIA DIAMETER

DIM DIMENSION

DN DOWN

DR DOOR

DS DOWN SPOUT

DWG DRAWING

(E) EXISTING

EA EACH

ELEV ELEVATION

EMER EMERGENCY

ENCL ENCLOSURE

EOS EDGE OF SLAB

EQ EQUAL

EW EACH WAY

F.O. FACE OF

FA FIRE ALARM

FAP FIRE ANNUNCIATOR PANEL

FD FLOOR DRAIN

FE FIRE EXTINGUISHER

FEC FIRE EXTINGUISHER CABINET

FH FIRE HYDRANT

FIN FINISH

FRP FIBER-REINFORCED PLASTIC

FT FOOT OR FEET

FUR FURRING

G.S.M. GALVANIZED SHEET METAL

GAL GALLON

GALV GALVANIZED

GB GRAB BAR

GC GENERAL CONTRACTOR

GL GLASS

GND GROUND

GWB GYPSUM BOARD

H.W.H. HOT WATER HEATER

HDWD HARDWOOD

HM HOLLOW METAL

HT HEIGHT

ID INSIDE DIAMETER

INSUL INSULATION

INT INTERIOR

JST JOIST

JT JOINT

LAM LAMINATE

LAV LAVATORY

LDG LANDING

LT LIGHT

MEMB MEMBRANE

MFR MANUFACTURER

MIN MINIMUM

MISC MISCELLANEOUS

MO MASONRY OPENING

REFERENCE DESCRIPTION INTERPRETATION

DESCRIPTION

SCOPE NEW METAL BUILDING TOHOUSE

EV CHARGERS

LOCATION WAREHOUSE 5 and THE WESTCOMPLEX

ZONING

APN

SPECIAL USEPERMIT

GENERAL INFORMATION

1ST FLOOR AREA 1900

2ND FLOOR AREA N/A

TOTAL BUILDING AREA 1900

ACTUAL BUILDING HEIGHT 20'-0"

ACTUAL NUMBER OF STORIES 1 STORIES

OCCUPANCY

CBC 303.1 GROUP -

CBC 305 GROUP -

CBC 508.3 AUTOMATIC FIRE SPRINKLERS

CBC TABLE 601 CONSTRUCTION TYPE

CBC TABLE 503 ALLOWABLE BUIDING HEIGHT

CBC TABLE 503 ALLOWABLE NUMBER OFSTORIES

CBC TABLE 503 ALLOWABLE BUIDING AREA

CBC 506.1 AREA INCREASE

Aa = (At + [At X If] + [At X Is])

Aa = (_____ + [If NOT USED] +[_____ X 2])

Aa = (_____ + 0 + _____)

TITLE 19 CCR, PUBLIC SAFETY, STATE FIRE MARSHAL REGULATIONS

TITLE 24 CCR, PART 1 - 2016 BUILDING STANDARDS ADMINISTRATIVE CODE

TITLE 24 CCR, PART 2 - 2016 CALIFORNIA BUILDING CODE, VOL. 1 & 2 (CBC) (2015 IBC, ASAMENDED BY CA)

TITLE 24 CCR, PART 3 - 2016 CALIFORNIA ELECTRICAL CODE (CEC) (2014 NEC, ASAMENDED BY CA)

TITLE 24 CCR, PART 4 - 2016 CALIFORNIA MECHANICAL CODE (CMC) (2012 IAPMO UMC,AS AMENDED BY CA)

TITLE 24 CCR, PART 5 - 2016 CALIFORNIA PLUMBING CODE (CPC) (2011 IAPMO UPC, ASAMENDED BY CA)

TITLE 24 CCR, PART 6 - 2016 CALIFORNIA ENERGY CODE

TITLE 24 CCR, PART 9 - 2016 CALIFORNIA FIRE CODE (CFC) (2012 IFC, AS AMENDED BYCA)

TITLE 24 CCR, PART 11 - 2016 CALIFORNIA GREEN BUILDING STANDARDS CODE

TITLE 24 CCR, PART 12 - 2016 CALIFORNIA REFERENCED STANDARDS (PARTIAL LIST -SEE CBC CH. 35 AND CFC CH. 80)

2016 NFPA 13, INSTALLATION OF SPRINKLER SYSTEMS (CA AMENDED)

2013 NFPA 14, INSTALLATION OF STANDPIPE AND HOSE SYSTEMS

2016 NFPA 20, INSTALLATION OF STATIONARY PUMPS FOR FIRE PROTECTION

2013 NFPA 22, WATER TANKS FOR PRIVATE FIRE PROTECTION

2016 NFPA 24, INSTALLATION OF PRIVATE FIRE SERVICE MAINS

2016 NFPA 72, NATIONAL FIRE ALARM CODE (CA AMENDED); SEE UL STD. 1971 FOR"VISUAL DEVICES"

2016 NFPA 80, FIRE DOOR AND OTHER OPENING PROTECTIVES

2015 NFPA 2001, CLEAN AGENT FIRE EXTINGUISHING SYSTEMS

2005 UL 300, CLASS I HOOD FIRE SUPPRESSION SYSTEMS

2003 UL, 464, AUDIBLE SIGNAL APPLIANCES

1999 UL 521, HEAT DETECTORS FOR FIRE PROTECTIVE SIGNALING SYSTEMS

Electric Fork Lift Battery Chargers WAREHOUSE 5

andWest Complex Chargers

PORT OF STOCKTON

ADDRESS:

PHONE:

CONTACT:

EMAIL:

PORT OF STOCKTON

OWNER:

ADDRESS:

PHONE:

CONTACT:

EMAIL:

HCS ENGINEERING

4512 FEATHER RIVER DR #F

STOCKTON, CA 95219

209.478.8270

RICHARD SMITH

[email protected]

ELECTRICAL ENGINEER:

GENERAL NOTES

CONTACTS PROJECT DATA SHEET INDEX

APPLICABLE CODES

SYMBOLS LEGEND

ABBREVIATIONS

1. ON-SITE VERIFICATION OF ALL DIMENSIONS AND DETAILS SHALL BE THERESPONSIBILITY OF THE GENERAL CONTRACTOR AND EACH SUBCONTRACTORFOR HIS INDIVIDUAL WORK. THE OWNER OR ARCHITECT SHALL BE NOTIFIED IF ANYDISCREPANCIES ARE FOUND PRIOR TO COMMENCING ANY WORK. THERESPONSIBILITY FOR WORK COMPLETED WITHOUT PROPER NOTIFICATION SHALLBE BORNE BY THE INDIVIDUAL CONTRACTOR INVOLVED.

2. THE CONTRACT DOCUMENTS INDICATE THE EXTENT AND APPROXIMATE LOCATIONOF ELEMENTS OF THE BUILDING AND SITE. ALL CONDITIONS, LOCATIONS, DEVICESAND ELEMENTS SHALL BE VERIFIED BY THE CONTRACTOR PRIOR TO COMMENCINGTHE WORK.

3. ALL WORK PERFORMED IN CONNECTION WITH THESE CONTRACT DOCUMENTSSHALL COMPLY WITH THE AMERICANS WITH DISABILITIES ACT (ADA), ALLAPPLICABLE STATE AND LOCAL CODES, ORDINANCES, AND ZONING REGULATIONSIN EFFECT AT THE TIME OF CONSTRUCTION. THIS PROJECT SHALL COMPLY WITHTITLE 24, 2016 CBC, CMC, CPC, CFC, CEC BASED ON THE 2016 CALIFORNIA ENERGYSTANDARDS.

4. IT SHALL BE UNDERSTOOD THAT THE INTENT OF THESE CONSTRUCTIONDOCUMENTS IS TO CONSTRUCT THE FACILITY IN ACCORDANCE WITH THEAPPLICABLE CODES AND ORDINANCES. SHOULD ANY CONDITION BE UNCOVEREDOR DEVELOP DURING THE EXECUTION OF THESE DOCUMENTS, WHICH IS NOTDEFINED HEREIN, THE CONTRACTOR SHALL CEASE WORK AND NOTIFY THEARCHITECT AT ONCE.

5. THE TYPICAL DETAILS SHOWN IN THESE PLANS SHALL APPLY IN ALL SIMILARCASES UNLESS SPECIFICALLY NOTED OTHERWISE. WHERE NO DETAIL IS SHOWN,CONSTRUCTION SHALL BE AS INDICATED FOR OTHER SIMILAR WORK AND, ORAPPLICABLE INDUSTRY PRACTICE.

6. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL COORDINATION OFINSTALLATION, INSPECTION, AND FINAL APPROVAL OF ALL UTILITIES.

7. VERIFY ALL DIMENSIONS, EXISTING CONDITIONS, AND METHODS OFCONSTRUCTION PRIOR TO START OF ANY WORK. NOTIFY THE ARCHITECT OF ANYDISCREPANCIES.

8. IT IS NOT THE INTENT OF THESE CONTRACT DOCUMENTS TO SEPARATE THEWORK INTO SUBTRADE DIVISIONS. IT SHALL BE THE RESPONSIBILITY OF THEGENERAL CONTRACTOR TO DIVIDE THE WORK AND ORGANIZE ALL WORK ASREQUIRED TO COMPLETE THE WORK AS INTENDED BY THESE DOCUMENTS.

9. SITE DEVELOPMENT AND GRADING SHALL PROVIDE ACCESS TO PRIMARYENTRANCES AND NORMAL PATHS OF TRAVEL, AND SHALL INCORPORATEPEDESTRIAN RAMPS, CURB RAMPS, ETC. ALL RAMPS SHALL HAVE A MAXIMUMSLOPE OF 1:12, OR AS NOTED ON THESE CONSTRUCTION DOCUMENTS. ANY PATHOF TRAVEL SHALL BE CONSIDERED A RAMP IF IT'S SLOPE IS GREATER THAN 1 FT.RISE IN 20 FT. RUN (5%)

10. EACH PARKING FACILITY WHERE PARKING IS PROVIDED FOR THE PUBLIC, GUESTSOR EMPLOYEES SHALL PROVIDE ACCESSIBLE PARKING AND LOADING STALLSDESIGNATED SPECIFICALLY FOR HANDICAPPED PERSONS.

11. THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING THE LOCATION OF ALLEXISTING UNDERGROUND UTILITIES PRIOR TO THE COMMENCEMENT OF WORK.

HE SHALL BE RESPONSIBLE FOR THE LOCATION AND PRESERVATION OF ALL SUCH FACILITIES IN THE AREA OF CONSTRUCTION, AND SHALL NOTIFY UTILITY

COMPANIES 48 HOURS IN ADVANCE OF ANY CONSTRUCTION (UNDERGROUNDSERVICE ALERT 1-800-227-2600)

12. EACH PARKING SPACE RESERVED FOR PERSONS WITH PHYSICAL DISABILITIESSHALL BE IDENTIFIED BY A REFLECTORIZED SIGN PERMANENTLY POSTEDIMMEDIATELY ADJACENT TO AND VISIBLE FROM EACH STALL OR SPACE,CONSISTING OF A PROFILE VIEW OF A WHEELCHAIR OCCUPANT IN WHITE ON ABLUE BACKGROUND. THE SIGN SHALL NOT BE SMALLER THAN 70 SQ. IN. IN AREAAND, WHEN POSTED IN A PATH OF TRAVEL, SHALL BE A MINIMUM HEIGHT OF 80INCHES FROM THE BOTTOM OF THE SIGN TO THE PARKING SPACE FINISH GRADE,UON. IN ADDITION, A SIGN, AS SPECIFIED IN TITLE 24 ACCESSIBILITY STANDARDS,SHALL BE POSTED IN A CONSPICUOUS PLACE, AT EACH ENTRANCE TOOFF-STREET PARKING FACILITIES, OR IMMEDIATELY ADJACENT TO AND VISIBLEFROM EACH STALL OR SPACE. SAID SIGNS SHALL BE NOT LESS THAN 17 INCHES X22 INCHES IN SIZE WITH LETTERING NOT LESS THAN 1 INCH HIGH.

13. PROVIDE A CLEAR AND LEVEL LANDING ON EACH SIDE OF AN EXIT DOOR. THELANDING SHALL BE 48 INCHES IN LENGTH WHERE THE DOOR SWINGS AWAY FROMTHE LANDING, AND 60 INCHES IN LENGTH IN THE DIRECTION OF DOOR SWING ASMEASURED AT RIGHT ANGLES TO THE PLANE OF THE DOOR IN THE CLOSEDPOSITION.

14. GENERAL DEMOLITION: WHENEVER EXISTING FACILITIES OR MATERIALS AREREMOVED, DAMAGED, BROKEN, OR CUT IN THE INSTALLATION OF WORK COVEREDBY THE DRAWINGS AND SPECIFICATIONS, SAID FACILITIES AND MATERIALS SHALLBE REPLACED AT THE CONTRACTOR'S EXPENSE. SAID FACILITIES OR MATERIALSSHALL BE EQUAL TO OR BETTER THAN THE ORIGINAL FACILITIES OR MATERIALS.THE FINISH PRODUCT SHALL BE SUBJECT TO THE APPROVAL OF THE COUNTY ANDITS AGENTS.

15. NO WORK SHALL COMMENCE AT THE PROJECT SITE BEFORE A BUILDING PERMITIS FULLY EXECUTED AND AVAILABLE FOR POSTING AT THE JOB SITE.

16. CONSTRUCTION LIMITS: CONTRACTOR AND SUB-CONTRACTORS, WORKERS ANDOTHER PERSONNEL RELATED TO THIS SCOPE OF WORK, SHALL BE CONFINEDWITH THE AREAS DESIGNATED AS CONSTRUCTION LIMITS AS INDICATED BY THESEDRAWINGS AND RELATED AREAS. AREAS BEYOND THIS SCOPE OF WORK SHALLBE OFF LIMITS, AND THEIR USE SHALL BE PROHIBITED WITHOUT PRIORAUTHORIZATION OF SAN JOAQUIN COUNTY. THE GENERAL CONTRACTOR SHALLVERIFY THESE LIMITS AND BE RESPONSIBLE TO INFORM THE APPROPRIATEPERSONNEL AND ENFORCE THESE LIMITS.

17. PROVIDE CONTINUOUS 16GA. X REQUIRED WIDTH (6" MIN.) FLAT BACKING STRAPAT WALLS WITH WALL MOUNTED EQUIPMENT, CASEWORK, AND/OR ACCESSORIES -TYPICAL UNLESS OTHERWISE NOTED.

18. THE CONTRACTOR SHALL CAREFULLY STUDY AND COMPARE THE CONTRACTDOCUMENTS AND THE EXISTING FIELD CONDITIONS, AND SHALL AT ONCE REPORTTO THE ARCHITECT ANY ERROR, INCONSISTENCY, OR OMISSION HE MAYDISCOVER. THE CONTRACTOR SHALL PERFORM NO PORTION OF THE WORK ATANY TIME WITHOUT APPROVED CONTRACT DOCUMENTS OR WHERE REQUIRED,APPROVED SHOP DRAWINGS, PRODUCT LITERATURE, DATA, SAMPLES ORINSTALLATION INSTRUCTIONS.

19. THE CONTRACTOR SHALL OBTAIN AN ENCROACHMENT PERMIT, WHEREAPPLICABLE, FOR ANY WORK DONE WITHIN THE RIGHT-OF-WAY OR EASEMENTSFROM THE AUTHORITY HAVING JURISDICTION. THE CONTRACTOR SHALL NOTIFYTHE OWNER 48 HOURS IN ADVANCE OF COMMENCEMENT OF THE WORK OR ASREQUIRED BY SAID PERMITS.

20 THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CUTTING, FITTING, ORPATCHING THAT MAY BE REQUIRED TO COMPLETE THE INTENT OF THESECONSTRUCTION DOCUMENTS, TO MAKE IT'S SEVERAL PARTS FIT TOGETHERPROPERLY. THE CONTRACTOR SHALL PATCH ARCHITECTURAL FINISHES ASNECESSARY TO ACCOMPLISH WORK DEFINED IN STRUCTURAL, MECHANICAL,PLUMBING, ELECTRICAL, AND ARCHITECTURAL DRAWINGS. EXISTING FIELDCONDITIONS SHALL BE VERIFIED BY THE CONTRACTOR AND ACCEPTED ASCONDITIONS OF THIS SCOPE OF WORK.

21. THE ELECTRICAL CONTRACTOR SHALL COORDINATE WITH PG&E AND/OR SERVICEPROVIDER FOR ANY NEW SERVICE INSTALLATIONS. THE CONTRACTOR SHALLCOORDINATE THE SHUT DOWN OF THE FACILITIES WITH THE OWNER FOR ASMINIMAL DURATION AS POSSIBLE. INTERCEPT THE EXISTING SERVICE CONDUIT,EXTEND IT TO NEW TRANSFORMERS AND PAD (TO BE INSTALLED BYCONTRACTOR) AND EXTEND SECONDARY CONDUITS TO THE NEW SWITCHBOARD.COORDINATE WITH THE OWNER TO VERIFY LOCATION, PROVIDE TRAFFIC BARRIERPOSTS PER PG&E REQUIREMENTS.

22. CONTRACTOR SHALL FLUSH ALL WATER, SEWER, AND DRAIN LINES PRIOR TOHOOK UP.

23. DIMENSIONS SHALL BE MEASURED TO FACE OF FRAMING, U.O.N. DO NOT SCALEDRAWINGS.

24. PROVIDE 2% SLOPE AWAY FROM THE BUILDING FOR 10'-0" AT FRONT AND SIDES.

25. NO DRAINAGE ACROSS OR ONTO ADJACENT PROPERTY. PROVIDE 2% SLOPE AWAYFROM THE BUILDING FOR 10'-0" AT FRONT AND SIDES.

26. DO NOT SCALE THE DRAWINGS.

27. SUBSTITUTIONS OR CHANGES AFFECTING THE APPROVED DRAWINGS,SPECIFICATIONS OR DSA REGULATED ITEMS SHALL BE MADE BY ADDENDA ORSUBMITTED AS; DSA 140 APPLICATION FOR APPROVAL OF CONSTRUCTIONCHANGE DOCUMENT - CCD CATEGORY A/B, AS PER SECTION 4-338, PART 1 TITLE24, CCR, AND INTERPRETATION OF REGULATION (IR) A-6.

DEFERRED APPROVALSMETAL BUILDING WITH FOUNDATION TO BE PROVIDED BY CONTACTOR WITH STAMPED SHOP DRAWINGS

ADDRESS:

PHONE:

CONTACT:

EMAIL:

DILLON AND MUPHY

847 CLUFF AVE

LODI, CA 95240

209.334.6613

JOE MURPHY

[email protected]

CIVIL ENGINEER:

A0 COVER SHEET

A1 WAREHOUSE 5 ARCHITECTURAL SITEPLAN

A2 WAREHOUSE 5 ELEVATION

A3 WAREHOUSE 5 FOUNDATION

A4 WEST COMPLEX CANOPY

E1 ELECTRICAL INFORMATION

E2 WAREHOUSE 5 ELECTRICAL PLAN

E3 WAREHOUSE 5 ELECTRICAL DETAILS

E4 WEST COMPLEX ARRANGEMENT

E5 WEST COMPLEX ELECTRICAL PLAN

E6 WEST COMPLEX ELECTRICALDETAILS

S0 CANOPY STRUCTURAL NOTES

S1.0 CANOPY FRAMING PLAN / SECTION

S1.1 CANOPY DETAILS

OWNER PROVIDED MATERIALSTHE PORT OF STOCKTON WILL PROVIDE THE CONTRACTOR WITH

A. EV CHARGERS

Page 2: Electric Fork Lift Battery Chargers - Port of Stockton€¦ · 2016 nfpa 20, installation of stationary pumps for fire protection 2013 nfpa 22, water tanks for private fire protection

13' - 0" 13' - 0"74' - 0"

25

' -

8"

38

' -

0"

WAREHOUSE 5

---

-

SEE ENLARGED PLANS

74' - 0"

26

' -

0"

15' - 9"

EQ EQ

2' - 6"3' - 0"

7' - 0"

3' -

6"

8' -

7"

A2

4

A2 2 A23

3' - 10"

PROVIDE 12x12 COIL ALUMINUM ROLL UP DOORTYPICAL

3'x6" EXTERIORSECURITY DOORTYPICAL

DUAL WORLD CHARGERSON RAISED CONCRETEFOUNDATION

ELECTRIC FORKLIFTS

1858 SF

Room

1

TIT

LE

:P

RO

JE

CT

:

BYREVISIONS

SHEET

JOB

SCALE

DATE

CHECKED

DRAWN

STAMP

H C

S

EN

GIN

EE

RIN

G, IN

C.

CO

NS

UL

TIN

G E

LE

CT

RIC

AL

EN

GIN

EE

RS

451

2 F

EA

TH

ER

RIV

ER

DR

IVE

, S

UIT

E F

ST

OC

KT

ON

, C

A 9

521

9 (

20

9)

478

-82

70

em

ail

ad

dres

s r

ich

ard

@h

cs-e

ng

.co

m

HHHHTTTTIIII

MMMMSSSSCCCCDDDDRRRRAAAAHHHH

CCCCIIIIRRRR

No. E14303No. E14303No. E14303No. E14303Exp. 6Exp. 6Exp. 6Exp. 6----30303030----21212121

EEEE

LLLLEEEECCCCTTTTRRRR IIII CCCCAAAALLLL

RR RREEEEGGGGIIIISSSSTTTTEEEERRRR

EEEEDDDDPPPPRRRROOOOFFFFEEEESSSSSSSSIIIIOOOONNNNAAAALLLL

EEEENNNNGGGGIIIINNNNEEEEEEEERR RR

EEEEOOOOFFFF CCCCAAAALLLL IIIIFFFF

OOOORRRRNNNN

IIIIAAAA

SSSSTTTTAAAATTTT

As indicated

8/12/2019 8:23:13 AM

C:\Users\RichardSmith\HCS ENGINEERING\Projects - Documents\Add to 2018\PORT WAREHOUSE 5\Port Chargers Rev 3.rvt

A1

2017.xxx

Checker

Author

WO

RLD

CH

AR

GE

RS

PO

RT

OF

ST

OC

KT

ON

WA

RE

HO

US

E 5

Ente

r addre

ss h

ere

WA

RE

HO

US

E 5

AR

CH

ITE

CT

UR

AL

SIT

EP

LA

NP

roje

ct

#:

2017.x

xx D

raft

er:

Au

tho

r E

ng

ineer:

Desig

ner

SCALE: 1/16" = 1'-0"

WAREHOUSE 5 ARCHITECURAL SITE PLAN1

SCALE: 1/4" = 1'-0"

WAREHOUSE 5 Architectural Floor Plan2

METAL BUILDING DESIGN:

THE CONTRACTOR SHALL PROVIDE A COMPLETE DESIGNPACKAGE FOR THE METAL BUILDING INCLUDING FOUNDAITONDESIGN AND STRUCTURAL CALCULATIONS.

THE CONTRACTOR SHALL PROVIDE A COMPLETE PACKAGESTAMPED AND SIGNED BY A REGISTERED STATE OF CALIFORNIAPROFESSIONAL ENIGINEER

TITLE 24 COMPLIANCE.PROVIDE A COMPLETE TITLE 24 DOCUMENTATION PACKAGE INCLUDING ALL REQUIRED INSULATION AND VENTILATIONFOR THE BUILDING (TO BE INCLUDED IN THE CONTRACTOR'S PRICE AS PART OF THE SHOP DRAWING PACKAGE.

Page 3: Electric Fork Lift Battery Chargers - Port of Stockton€¦ · 2016 nfpa 20, installation of stationary pumps for fire protection 2013 nfpa 22, water tanks for private fire protection

16' - 9" 2' - 10" 6' - 5"

26' - 0"

16

' -

0"

GUTTER

DOWNSPOUT, SPILL TO GRADE

6' - 5" 2' - 10"

26' - 0"

RAIN GUTTER

DOWNSPOUT, SPILL TO GRADE

16

' -

0"

10' - 8" 12' - 0" 4' - 0" 4' - 0" 4' - 0"

74' - 0"

12' TALL ALUMINUM ROLL UP DOOR 12' TALL ALUMINUM ROLL UP DOOR 12' TALL ALUMINUM ROLL UP DOOR 12' TALL ALUMINUM ROLL UP DOOR

RAIN GUTTER

RAIN WATERLEADER

SPILL TO GRADE

TIT

LE

:P

RO

JE

CT

:

BYREVISIONS

SHEET

JOB

SCALE

DATE

CHECKED

DRAWN

STAMP

H C

S

EN

GIN

EE

RIN

G, IN

C.

CO

NS

UL

TIN

G E

LE

CT

RIC

AL

EN

GIN

EE

RS

451

2 F

EA

TH

ER

RIV

ER

DR

IVE

, S

UIT

E F

ST

OC

KT

ON

, C

A 9

521

9 (

20

9)

478

-82

70

em

ail

ad

dres

s r

ich

ard

@h

cs-e

ng

.co

m

HHHHTTTTIIII

MMMMSSSSCCCCDDDDRRRRAAAAHHHH

CCCCIIIIRRRR

No. E14303No. E14303No. E14303No. E14303Exp. 6Exp. 6Exp. 6Exp. 6----30303030----21212121

EEEE

LLLLEEEECCCCTTTTRRRR IIII CCCCAAAALLLL

RR RREEEEGGGGIIIISSSSTTTTEEEERRRR

EEEEDDDDPPPPRRRROOOOFFFFEEEESSSSSSSSIIIIOOOONNNNAAAALLLL

EEEENNNNGGGGIIIINNNNEEEEEEEERR RR

EEEEOOOOFFFF CCCCAAAALLLL IIIIFFFF

OOOORRRRNNNN

IIIIAAAA

SSSSTTTTAAAATTTT

1/4" = 1'-0"

8/12/2019 8:23:14 AM

C:\Users\RichardSmith\HCS ENGINEERING\Projects - Documents\Add to 2018\PORT WAREHOUSE 5\Port Chargers Rev 3.rvt

A2

2017.xxx

Checker

BA

WO

RLD

CH

AR

GE

RS

PO

RT

OF

ST

OC

KT

ON

WA

RE

HO

US

E 5

Ente

r addre

ss h

ere

WA

RE

HO

US

E 5

EL

EV

AT

ION

Pro

ject

#:

2017.x

xx D

raft

er:

BA

En

gin

eer:

RC

S

SCALE: 1/4" = 1'-0"

NORTH ELEVATION2SCALE: 1/4" = 1'-0"

SOUTH ELEVATION3

SCALE: 1/4" = 1'-0"

WEST ELEVATION4

Page 4: Electric Fork Lift Battery Chargers - Port of Stockton€¦ · 2016 nfpa 20, installation of stationary pumps for fire protection 2013 nfpa 22, water tanks for private fire protection

PROVIDE 6" RAISED FOUNDATION FOR CHARGERS

PROVIDE 6" CONCRETE FLOOR OVERREINFORCED WEB. PROVIDE SHOPDRAWINGS STAMPED BY CALIFORNIACIVIL / STRUCUTRAL ENGINEER

PROVIDE SHOP DRAWINGS WITH PERIMETER WALLAND FOOTING CALCULATIONS STAMPED BY CALIFORNIACIVIL / STRUCTURAL ENGINEER

WAREHOUSE 5

37

' -

6"

86' - 0"

CUT AND REMOVE ASPHAULTPROVIDE NEW FOUNDATION (UNDER SHOP DRAWINGS)PROVIEW NEW ASPHAULTTAPPERED FROM NEW FINISHEDFLOOR TO EXISTINGGRADE, SLOPING AWAY FROM BUILDING

TIT

LE

:P

RO

JE

CT

:

BYREVISIONS

SHEET

JOB

SCALE

DATE

CHECKED

DRAWN

STAMP

H C

S

EN

GIN

EE

RIN

G, IN

C.

CO

NS

UL

TIN

G E

LE

CT

RIC

AL

EN

GIN

EE

RS

451

2 F

EA

TH

ER

RIV

ER

DR

IVE

, S

UIT

E F

ST

OC

KT

ON

, C

A 9

521

9 (

20

9)

478

-82

70

em

ail

ad

dres

s r

ich

ard

@h

cs-e

ng

.co

m

HHHHTTTTIIII

MMMMSSSSCCCCDDDDRRRRAAAAHHHH

CCCCIIIIRRRR

No. E14303No. E14303No. E14303No. E14303Exp. 6Exp. 6Exp. 6Exp. 6----30303030----21212121

EEEE

LLLLEEEECCCCTTTTRRRR IIII CCCCAAAALLLL

RR RREEEEGGGGIIIISSSSTTTTEEEERRRR

EEEEDDDDPPPPRRRROOOOFFFFEEEESSSSSSSSIIIIOOOONNNNAAAALLLL

EEEENNNNGGGGIIIINNNNEEEEEEEERR RR

EEEEOOOOFFFF CCCCAAAALLLL IIIIFFFF

OOOORRRRNNNN

IIIIAAAA

SSSSTTTTAAAATTTT

As indicated

8/12/2019 8:23:14 AM

C:\Users\RichardSmith\HCS ENGINEERING\Projects - Documents\Add to 2018\PORT WAREHOUSE 5\Port Chargers Rev 3.rvt

A3

2017.xxx

Checker

Author

WO

RLD

CH

AR

GE

RS

PO

RT

OF

ST

OC

KT

ON

WA

RE

HO

US

E 5

Ente

r addre

ss h

ere

WA

RE

HO

US

E 5

FO

UN

DA

TIO

N

Pro

ject

#:

2017.x

xx D

raft

er:

Au

tho

r E

ng

ineer:

Desig

ner

SCALE: 1/4" = 1'-0"

WAREHOUSE 5 FOUNDATION PLAN1

SCALE: 1/16" = 1'-0"

APHAULT CUT AND PATCH2

Page 5: Electric Fork Lift Battery Chargers - Port of Stockton€¦ · 2016 nfpa 20, installation of stationary pumps for fire protection 2013 nfpa 22, water tanks for private fire protection

9" CONCRETE STEPFOR CHARGERS

COLUMN FOR ROOFSTRUCTURE, SEESTRUCTURAL PLANS

PORT SECURITY FENCE TO BE REROUTEDTHROUGH THE CENTER OF THE CHARGERBAY BY THE CONTRACTOR.

NEW ASPHAULT PAVING

179' - 3"

81

' -

6"

TIT

LE

:P

RO

JE

CT

:

BYREVISIONS

SHEET

JOB

SCALE

DATE

CHECKED

DRAWN

STAMP

H C

S

EN

GIN

EE

RIN

G, IN

C.

CO

NS

UL

TIN

G E

LE

CT

RIC

AL

EN

GIN

EE

RS

451

2 F

EA

TH

ER

RIV

ER

DR

IVE

, S

UIT

E F

ST

OC

KT

ON

, C

A 9

521

9 (

20

9)

478

-82

70

em

ail

ad

dres

s r

ich

ard

@h

cs-e

ng

.co

m

HHHHTTTTIIII

MMMMSSSSCCCCDDDDRRRRAAAAHHHH

CCCCIIIIRRRR

No. E14303No. E14303No. E14303No. E14303Exp. 6Exp. 6Exp. 6Exp. 6----30303030----21212121

EEEE

LLLLEEEECCCCTTTTRRRR IIII CCCCAAAALLLL

RR RREEEEGGGGIIIISSSSTTTTEEEERRRR

EEEEDDDDPPPPRRRROOOOFFFFEEEESSSSSSSSIIIIOOOONNNNAAAALLLL

EEEENNNNGGGGIIIINNNNEEEEEEEERR RR

EEEEOOOOFFFF CCCCAAAALLLL IIIIFFFF

OOOORRRRNNNN

IIIIAAAA

SSSSTTTTAAAATTTT

1/8" = 1'-0"

8/12/2019 8:23:15 AM

C:\Users\RichardSmith\HCS ENGINEERING\Projects - Documents\Add to 2018\PORT WAREHOUSE 5\Port Chargers Rev 3.rvt

A4

2017.xxx

Checker

Author

WO

RLD

CH

AR

GE

RS

PO

RT

OF

ST

OC

KT

ON

WA

RE

HO

US

E 5

Ente

r addre

ss h

ere

WE

ST

CO

MP

LE

XC

AN

OP

Y

Pro

ject

#:

2017.x

xx D

raft

er:

Au

tho

r E

ng

ineer:

Desig

ner

SCALE: 1/8" = 1'-0"

WEST COMPLEX - CANOPY1

Page 6: Electric Fork Lift Battery Chargers - Port of Stockton€¦ · 2016 nfpa 20, installation of stationary pumps for fire protection 2013 nfpa 22, water tanks for private fire protection

ELECTRICAL SPECIFICATIONS

GENERAL NOTES:

1. ELECTRICAL INSTALLATION SHALL COMPLY WITH TITLE 24, CALIFORNIA CODE OF REGULATIONS, INCLUDING THE FOLLOWING: TITLE 24, CCR, PART 2, 2016 CBC TITLE 24, CCR, PART 3, 2016 CEC TITLE 24, CCR, PART 4, 2016 CMC TITLE 24, CCR, PART 9, 2016 CFC ALL APPLICABLE LOCAL CODES. 2. ELECTRICAL CONTRACTOR SHALL PROCURE AND PAY FOR ALL LICENSES, ETC. REQUIRED TO CARRY ON AND COMPLETE THE WORK. PERMIT BY OWNER. 3. PROVIDE ALL LABOR, MATERIALS, TOOLS, PLANT EQUIPMENT, TRANSPORTATION AND PERFORM ALL OPERATIONS NECESSARY FOR ANY REASONABLE INCIDENTAL TO PROPER EXECUTION AND COMPLETION OF ALL "ELECTRICAL WORK" WHETHER SPECIFICALLY MENTIONED OR NOT; ALL AS INDICATED, SPECIFIED HEREIN, AND/OR IMPLIED THEREBY TO CARRY OUT THE APPARENT INTENT THEREOF. 4. ALL ELECTRICAL MATERIALS SHALL BE NEW AND LISTED WITH THE UNDERWRITERS' LABORATORIES, INC., SHALL MEET THEIR REQUIREMENTS AND SHALL BEAR THEIR LABEL WHEREVER STANDARDS HAVE BEEN ESTABLISHED AND LABEL SERVICE IS REGULARLY FURNISHED BY THAT AGENCY. 5. ELECTRICAL DRAWINGS ARE ESSENTIALLY DIAGRAMMATIC AND ALTHOUGH THE SIZE AND LOCATIONS OF EQUIPMENT ARE SHOWN TO SCALE WHEREVER POSSIBLE, CONTRACTOR SHALL MAKE USE OF ALL DATA IN ALL CONTRACT DOCUMENTS AND VERIFY THIS INFORMATION AT THE SITE. CONTRACTOR SHALL BE RESPONSIBLE FOR LAYING OUT AND INSTALLING HIS WORK TO AVOID INTERFERENCE WITH OTHER TRADES. 6. CONDUCTORS SHALL BE COPPER CONDUCTORS TYPE THWN UNLESS OTHERWISE NOTED OR REQUIRED BY CODE. 7. ALL LUMINAIRES AND BALLASTS SHALL BE CERTIFIED BY THE MANUFACTURER TO THE CALIFORNIA ENERGY COMMISSION. 8. FLASH AND COUNTER FLASH ALL ITEMS PASSING THROUGH THE ROOF. ANY ROOF PENETRATIONS WILL BE APPROVED BY THE OWNER. ROOFING MFG. HAS SPECS. AS TO NOT VOID 20 YEAR WARRANTY. 9. WORK SHOWN ON THE DRAWINGS TO BE INSTALLED UNDERGROUND SHALL BE INSTALLED AT LEAST 24" BELOW GRADE. BACKFILL IN 6" THICK, PROPERLY MOISTENED LAYERS, SOLIDLY PACKED AND IRON TAMPED TO A DENSITY NOT LESS THAN THAT OF ADJACENT, UNDISTURBED EARTH. RESTORE SURFACES, ROADWAYS, WALKS, CURBS, WALLS, EXISTING UNDERGROUND INSTALLATIONS TO ORIGINAL CONDITION IN AN ACCEPTABLE MANNER. 10. THE OWNER RESERVES THE RIGHT TO RELOCATE ALL LIGHTING, OUTLETS AND SWITCHES BEFORE THEY ARE ROUGHED IN AT NO EXTRA COST. 11. ALL EXIT SIGNS TO BE UNSWITCHED. NAMEPLATES & IDENTIFICATION: INSTALL ENGRAVED NAMEPLATES FOR EACH PANELBOARD, CABINET, DISCONNECT, ETC. NAMEPLATES SHALL BE SECURELY FASTENED TO THE EQUIPMENT WITH #4 PHILLIPS ROUND HEAD CADMIUM PLATED SELF-TAPPING SCREWS, BRASS BOLT, OR WITH A PLASTIC RESIN ADHESIVE GLUE, GOODYEAR "PLIEBOND" OR EQUAL.

HVAC UNIT DISCONNECTS: 1. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH MECHANICAL CONTRACTOR FOR EXACT LOCATIONS OF ALL HVAC UNITS, DISCONNECTS AND DEVICES IN FIELD. VERIFY AND CONFIRM THE ACTUAL MOUNTING LOCATION ON THE HVAC UNIT FOR THE DISCONNECT. 2. THE RATING OF THE DISCONNECT SHALL BE SUCH AS TO ENABLE THE LARGEST FUSE SIZE ON THE UNIT NAMEPLATE TO BE INSTALLED IN THE DISCONNECT. PROVIDE FUSES OF THIS RATING. 3. FURNISH AND INSTALL ALL LINE VOLTAGE AND LOW VOLTAGE CONDUITS AND LINE VOLTAGE WIRING (LOW VOLTAGE WIRING BY OTHERS) TO HVAC EQUIPMENT AND ASSOCIATED CONTROLS AND DEVICES AS SHOWN ON THE ELECTRICAL AND MECHANICAL PLANS, UNLESS OTHERWISE NOTED.

WIRING METHODS: 1. ALL WIRING SHALL BE INSTALLED IN STEEL CONDUITS, CONCEALED IN WALL AND CEILING U.O.N. 2. MINIMUM CONDUIT SIZE SHALL BE 1/2". MINIMUM ACCEPTABLE CONDUITS ARE A. GALVANIZED RIGID STEEL. B. GALVANIZED STEEL EMT. C. LIQUID TIGHT STEEL FLEX - FOR FINAL CONNECTION TO OUTDOOR EQUIPMENT. D. FLEXIBLE STEEL CONDUIT - FOR INDOOR FINAL CONNECTIONS TO MECHANICAL EQUIPMENT (NOT TO EXCEED 36"). E. PVC CONDUIT SCHEDULE 40, UNDERGROUND. 3. NMC CABLING SYSTEMS ARE NOT ALLOWED IN THIS BUILDING. 4. MC CABLING SYSTEMS ARE NOT ALLOWED IN THIS BUILDING. WIRING DEVICES: UNITS SHALL BE EQUAL TO THE DEVICES SET FORTH HEREIN, IN STANDARD COLORS (BROWN, WHITE, GREY, BEIGE OR IVORY) AS SELECTED BY THE ARCHITECT:

A. WIRING DEVICES LEVITON # HUBBELL # P & S # SINGLE POLE SWITCH 1221 1221 20AC1 THREE WAY SWITCH 1223 1223 20AC3 DUPLEX CONV. OUT. 15A 5262 5262 5262 DUPLEX GFI CONV. OUT. GF5262

DEVICE PLATES:

1. ALL DEVICE PLATES FOR INDOOR USE SHALL BE SMOOTH NYLON OR APPROVED EQUAL UNLESS OTHERWISE NOTED. ALL DEVICE PLATES FOR OUTDOOR USE SHALL BE RAISED METAL.

2. DEVICE COVERS FOR SURFACE MOUNTED BOXES SHALL BE 1/2" RAISED STEEL PLATES. WEATHERPROOF COVERS TO BE SNAP TYPE COVERS.

3. DEVICE PLATES FOR TELEPHONE AND COMPUTER OUTLETS TO BE PROVIDED BY OWNER'S VENDOR. ALL TELEPHONE AND COMPUTER SYSTEM WIRING BY OWNER'S VENDOR.

SUPPORTS: 1. FURNISH ALL NECESSARY FOUNDATIONS, SUPPORTS, BACKING, ETC., FOR ALL ELECTRICAL ENCLOSURES, CONDUITS AND EQUIPMENT. 2. ATTACH ALL BOXES, CABINETS, ETC. TO WOOD WITH WOOD OR LAG SCREWS, TO METAL WITH MACHINE SCREWS OR BOLTS AND TO CONCRETE WITH EXPANSION ANCHORS AND MACHINE SCREWS OR BOLTS.

GROUNDING: 1. GROUND AND BOND ALL EQUIPMENT AS REQUIRED BY GOVERNING CODES AND SPECIFICALLY INCLUDING SWITCHBOARD, PANELBOARDS, MOTOR CASES, ETC.

PANELBOARDS:

UNITS SHALL BE FLUSH OR SURFACE MOUNTED AS INDICATED ON THE PANEL SCHEDULE, WITH THE NUMBER AND SIZE OF BREAKERS INDICATED ON THE PANEL SCHEDULE. SINGLE POLE, TWO POLE AND THREE POLE BREAKERS SHALL BE BOLT-ON TYPE. THE PANEL DOORS SHALL HAVE FLUSH TYPE LOCKS, ALL LOCKS SHALL BE KEYED ALIKE AND HAVE TYPEWRITTEN DIRECTORIES INDICATING FIXTURES, EQUIPMENT, OR OUTLETS SERVICED BY EACH BREAKER. ALL BUSSING SHALL BE COPPER.

WORKING CLEARANCES FOR PANELS & SWITCHBOARDS 1. COORDINATE WITH OTHER TRADES TO ENSURE CODE REQUIRED WORKING CLEARANCES, ACCESS, ETC. FOR PANELS AND SWITCHBOARDS PER C.E.C. SECTIONS 110-16 AND 384-4.

TESTING:

1. THE ENTIRE ELECTRICAL INSTALLATION SHALL BE FREE FROM SHORT CIRCUITS AND IMPROPER GROUNDS. TEST ALL WIRING AND CONNECTIONS FOR CONTINUITY AND GROUNDS BEFORE ANY FIXTURES OR EQUIPMENT ARE CONNECTED AND WHETHER SUCH TESTS INDICATE FAULTY INSULATION OR OTHER DEFECTS, THEY SHALL BE LOCATED, REPAIRED AND RETESTED AT THE CONTRACTOR'S EXPENSE.

2. DEMONSTRATE TO THE OWNER AND THE ARCHITECT, THAT THE ENTIRE INSTALLATION IS COMPLETE, IN PROPER OPERATING CONDITION AND THAT THE CONTRACT HAS BEEN PROPERLY AND FULLY EXECUTED. PROVIDE ALL INSTRUMENTS TO MAKE SUCH TESTS.

LIGHT SWITCH, +48" TO TOP OF BOX• D = DIMMER• 3 = SWAY• P = PILOT SWITCH• os = LINE VOLTAGE OCCUPANCY SENSOR• T = TIMMER• VS = VACANCY SENSOR

WALL MOUNT OCCUPANCY SENSOR (LINE VOLTAGE)

EMERGENCY LIGHTING

EXIT SIGN WITH 90 MIN BATTERY BACKUP

WALL MOUNT EMERGENCY LIGHT WITH 90 MIN BATTERY BACK

EXTERIOR LANDING EMERGENCY LIGHT. CONNECTTO INTERIOR EXIT SIGN FOR POWER.

FIXTURES WITH INTEGRAL EMERGENCY BALLAST

LIGHTING FIXTURES

LINEAR FIXTURE• SQUARE = RECESSED• CIRCLE =SURFACE

DOWNLIGHT, SQUARE = RECESSED

WALL MOUNT

CEILING EXHAUST FAN

POLE MOUNT AREA LIGHT

ELECTRICAL LEGEND

MOUNTING HEIGHTS

CONVIENCE OUTLETS, PHONE & DATA OUTLETS, +15" TO BOTTOMOF BOX

SYSTEMS FURNITURECONNECTIONS +15" TOBOTTOM OF BOXES

LIGHT SWITCHES

FIRE ALARM MANUAL PULL STATION SHALL NOTREQUIRE "TIGHT GRASPING,PINCHING OR TWISTING OF THE WRIST"

12" TYPICAL

THERMOSTATOR WALL PHONE

FINISHED FLOOR

48" TO TOPOF BOX

FINISHED CEILING

AUDIBLE FIRE ALARM APPLIANCENOT LESS THEN 90" AFF OR ATLEAST 6" BELOW CEILING

VISUAL APPLIANCE TO BE NOT LESS THAN 80" AFF MIN,AND NOT MORE THAN 96" AFF TO BOTTOM

TITLE 24 LIGHTING CONTROLS

LIGHT SWITCH

COMPONENTS OF DIMMING ROOM CONTROLLER• US = LOW VOLTAGE OCCUPANCY SENSOR (CAT 5 OR AS REQUIRED)• DRC = DIMMING ROOM CONTROLLER• PE = LOW VOLTAGE DIMMING PHOTOCELL (CAT 5 OR AS REQUIRED)• D = LOW VOLTAGE DIMMER (CAT 5 OR AS REQUIRED)• R = PLUG LOAD CONTROLLER• ADR = AUTOMATIC DEMAND RESPOSNE (FOR BUILDINGS OVER 10,000 SF)

BASIC LIGHTING CONTROLS

NOTES:

1. FOR SUBMITTAL INCLUDE FACTORY CONTROL DRAWINGS.

2. CONDUCT A CONTROLS PRE-CONSTRUCTION MEETING WITH CONTROLSSTARTUP TEAM. PROVIDE AGENDA AND ATTENDEES AS A SUBMITTAL. INCLUDEDEVICE I.D. TAGS, PROGRAMMING, CABLE ROUTING, PROGRAM AND TIMESCHEDULES AND DATE OF PROGRAMMING AND TESTING.

3. CONTRACTOR TO HAVE SYSTEM FACTORY SUPPORT FOR START UP,PROGRAMMING AND COMMISSIONING. VERIFY OPERATIONAL HOURS WITH OWNERPRIOR TO COMMISSIONING.

DRAFTING NOTATIONS

KEY NOTE, SEE SCHEDULE

EQUIPMENT TAG, SEE SCHEDULE

REFERENCE TO A DETAIL VIEW "A" ON SHEET E-2

NEW ELECTRICAL

EXISTING ELECTRICAL OR DEMOLISHED WHERE NOTED

EXISTING DEVICE, TO REMAIN IN OPERATION

REMOVE DEVICE, KEEP REMAINDER OF CIRCUIT IN OPERATION

REMOVE, RELOCATE AND RECONNECT DEVICE ON EXISTING CIRCUIT, EXTEND CIRCUIT

ELECTRICAL LEGEND

N##

N##

A

E-2

FIXTURE NOTATIONS:A,(b),C-12 FIXTURE TYPE "A", SWITCH "b", CIRCUIT C-12

ONE LINE DIAGRAM

BUS / SWITCHBOARD

PANEL

GROUND

METER

CURRENT TRANSFORMER

POTENTIAL TRANSFORMER

DRY TYPE TRANSFORMER

MOTOR

RELAY CR# = CONTROL RELAY TDR = TIME DELAY RELAY M = MOTOR STARTER CONTACTOR RELAY ETM = ELAPSE TIME METER

CONTACT (OPEN)

CONTACT (CLOSED)

VARIABLE FREQ. DRIVE

MOTOR OVERLOAD HEATER

INDICATOR LIGHT (R) RED, (W) WHITE

ANTENNA

CIRCUIT BREAKER 50 AMP RATED, 3 POLE

GFI = GROUND FAULT INTERRUPTER AFCI = ARC FAULT CIRCUIT INTERRUPTER

DISCONNECT, RATED TO POWER SOURCEVOLTAGE AND AMPERAGE RATING FOR FUSEOR AS NOTED

FUSE, SIZE = 60 AMPS

AUTOMATIC TRANSFER SWITCH

ENGINE DRIVEN GENERATOR RATING AS NOTED AGAINST THE UNIT.

DRAW OUT DEVICE

ANSI RELAY

50/3

60

(e) (E)

(r) (R)

(RR)

M

CR1

50/3G

VFD

R

52

1X

1Y

1Z

1A TSP#16 ADDRESSIBLE INPUT CIRCUIT2#14 HARD WIRED NON-ADDRESSIBLE CIRCUITS2#12 VISUAL CIRCUIT2#14/SHIELDED AUDIBLE CIRCUIT

FIRE ALARM CONTROL PANEL (FACP)

SMOKE DETECTOR

HEAT DETECTOR

HEAT DETECTOR IN ATTIC (194DEGREE)

STROBE

COMBINATION SPEAKER/STROBE

EXTERIOR HORN

PULL STATION

A

HD

HD

SD

FIRE ALARM

FIRE ALARM ABBREVIATIONS:

CD = CANDELLADSD = DUCT SMOKE DETECTOREOL = END OF LINE RESISTORNAC = NOTIFICATION POWER SUPPLYPIV = POST INDICATOR VALVETS = TAMPER SWITCHWF = WATER FLOW SWITCHWP = WEATHERPROOF

MARKINGS:a### = CIRCUIT "a" DEVICE ###15CD = 15 CANDELLA VISUAL DEVICE1/2W = 1/2 WATT AUDIBLE DEVICE

TELEPHONE BACKBOARD, PROVIDE #8 GND TO SERVICE GROUND

COMMUNICATIONS OUTLET, PHONE & DATA

PHONE ONLY OUTLET, PREWIRED WITH CAT 5e CABLE

DATA ONLY OUTLET JACK, PREWIRED WITH CAT 6 CABLE

ELECTRICAL POWER

COMMUNICATIONS

ALL LINE VOLTAGE WIRING IN CONDUIT, SEE GENERAL NOTES TICKS = # OF #12 WIRE, SHORT = HOT, LONG = NEUTRAL, DOT = GROUND, UNLESS NOTED OTHERWISE

120V OUTLET, +18" TO BOTTOM OF BOX• S = SIGN• F = FLOOR• GFI = GROUND FAULT INTERUPTER

COUNTER OUTLET

QUADRUPLEX OUTLET

HALF SWITCHED OUTLETS

OUTLETS ON EMERGENCY SYSTEMS

DUCT SMOKE DETECTOR

JUCTION BOX

MOTOR / DISCONNECT

PANELBOARD TRANSFORMER / SWITCHBOARD AS NOTED

SD

XX

TIT

LE

:P

RO

JE

CT

:

BYREVISIONS

SHEET

JOB

SCALE

DATE

CHECKED

DRAWN

STAMP

H C

S

EN

GIN

EE

RIN

G, IN

C.

CO

NS

UL

TIN

G E

LE

CT

RIC

AL

EN

GIN

EE

RS

451

2 F

EA

TH

ER

RIV

ER

DR

IVE

, S

UIT

E F

ST

OC

KT

ON

, C

A 9

521

9 (

20

9)

478

-82

70

em

ail

ad

dres

s r

ich

ard

@h

cs-e

ng

.co

m

HHHHTTTTIIII

MMMMSSSSCCCCDDDDRRRRAAAAHHHH

CCCCIIIIRRRR

No. E14303No. E14303No. E14303No. E14303Exp. 6Exp. 6Exp. 6Exp. 6----30303030----21212121

EEEE

LLLLEEEECCCCTTTTRRRR IIII CCCCAAAALLLL

RR RREEEEGGGGIIIISSSSTTTTEEEERRRR

EEEEDDDDPPPPRRRROOOOFFFFEEEESSSSSSSSIIIIOOOONNNNAAAALLLL

EEEENNNNGGGGIIIINNNNEEEEEEEERR RR

EEEEOOOOFFFF CCCCAAAALLLL IIIIFFFF

OOOORRRRNNNN

IIIIAAAA

SSSSTTTTAAAATTTT

As indicated

8/12/2019 8:23:16 AM

C:\Users\RichardSmith\HCS ENGINEERING\Projects - Documents\Add to 2018\PORT WAREHOUSE 5\Port Chargers Rev 3.rvt

E1

2017.xxx

Checker

Author

WO

RLD

CH

AR

GE

RS

PO

RT

OF

ST

OC

KT

ON

WA

RE

HO

US

E 5

Ente

r addre

ss h

ere

EL

EC

TR

ICA

LIN

FO

RM

AT

ION

Pro

ject

#:

2017.x

xx D

raft

er:

Au

tho

r E

ng

ineer:

Desig

ner

Page 7: Electric Fork Lift Battery Chargers - Port of Stockton€¦ · 2016 nfpa 20, installation of stationary pumps for fire protection 2013 nfpa 22, water tanks for private fire protection

WAREHOUSE 5

(e)800A 480V SWITCHBOARD

PANEL HEV

PANEL HEV

HEV-1,3,5HEV-7,9,11 HEV-13,15,17 HEV-19,21,23

HEV-25,27,29

1"C-3#4+1#8 GNDTYPICAL

B

A A A A A A A A A A

B

BB

B

A A A A A

HEV-2

HEV-4

MANUAL TRANSFERSWITCH

15 KVA TRANSFORMERWALL MOUNT

PANEL P

P-1P-3

ALL ELECTRICAL OUTLETSON THIS PROJECT WILL BE WP, GFIWITH HEAVY DUTY IN USE COVERSMOUNTED AT +48" AFF.PROVIDE 1/2HP WALL MOUNT FAN WITH

MANUAL MOTOR DISCONNECTAND LINE VOLTAGE THERMOSTATON WALL AT HIGH LEVEL

P-5

THE CONTRACTOR SHALL INSTALL AND CONNECT PORT PROVIDED CHARGERS T

ITLE

:P

RO

JE

CT

:

BYREVISIONS

SHEET

JOB

SCALE

DATE

CHECKED

DRAWN

STAMP

H C

S

EN

GIN

EE

RIN

G, IN

C.

CO

NS

UL

TIN

G E

LE

CT

RIC

AL

EN

GIN

EE

RS

451

2 F

EA

TH

ER

RIV

ER

DR

IVE

, S

UIT

E F

ST

OC

KT

ON

, C

A 9

521

9 (

20

9)

478

-82

70

em

ail

ad

dres

s r

ich

ard

@h

cs-e

ng

.co

m

HHHHTTTTIIII

MMMMSSSSCCCCDDDDRRRRAAAAHHHH

CCCCIIIIRRRR

No. E14303No. E14303No. E14303No. E14303Exp. 6Exp. 6Exp. 6Exp. 6----30303030----21212121

EEEE

LLLLEEEECCCCTTTTRRRR IIII CCCCAAAALLLL

RR RREEEEGGGGIIIISSSSTTTTEEEERRRR

EEEEDDDDPPPPRRRROOOOFFFFEEEESSSSSSSSIIIIOOOONNNNAAAALLLL

EEEENNNNGGGGIIIINNNNEEEEEEEERR RR

EEEEOOOOFFFF CCCCAAAALLLL IIIIFFFF

OOOORRRRNNNN

IIIIAAAA

SSSSTTTTAAAATTTT

As indicated

8/12/2019 8:23:18 AM

C:\Users\RichardSmith\HCS ENGINEERING\Projects - Documents\Add to 2018\PORT WAREHOUSE 5\Port Chargers Rev 3.rvt

E2

2017.xxx

Checker

Author

WO

RLD

CH

AR

GE

RS

PO

RT

OF

ST

OC

KT

ON

WA

RE

HO

US

E 5

Ente

r addre

ss h

ere

WA

RE

HO

US

E 5

EL

EC

TR

ICA

L P

LA

N

Pro

ject

#:

2017.x

xx D

raft

er:

Au

tho

r E

ng

ineer:

Desig

ner

SCALE: 1/16" = 1'-0"

WAREHOUSE 5 ELECTRICAL SITE PLAN1

SCALE: 1/4" = 1'-0"

WAREHOUSE 5 ELECTRICAL PLAN2

FIXTURE SCHEDULE

Type Mark Lamp Description Manufacturer Model Apparent Load

A LED 4' INDUSTRIAL FIXTURE, CHAIN HUNG WITH MOTIONSENSOR

LITHONIA WL4 40LMOTIONSENSOR

35 VA

B LED WALL AREA LIGHT, PHOTOCELL CONTROL EATON XTORA 3A PC 30 VA

Page 8: Electric Fork Lift Battery Chargers - Port of Stockton€¦ · 2016 nfpa 20, installation of stationary pumps for fire protection 2013 nfpa 22, water tanks for private fire protection

MAIN SERVICE SWITCHBOARD "MSB". NEMA 3R.

DANGERARC FLASH AND SHOCK HAZARD

FOLLOW ALL REQUIREMENTS IN NFPA 70E FOR SAFE WORK PRACTICES AND FOR PERSONAL PROTECTIVE EQUIPMENT

ARC FLASH LABELLING REQUIREMENT:PROVIDE THE FOLLOWING LABEL AS A MINIMUMFOR COMPLIANCE WITH NFPA AND NEC ON THIS PROJECT:

(2)5"CO PG&E SECONDARYINSTALLED 36" BELOW GRADEIN TRUCK TRAFFIC AREAS TOPG&E TRANSFORMER

GROUND TO 3/4”x10’ GND ROD WITH3/0 AND 20’ OF #4UFER GROUND

400A - 480/277V, 3PH, 4W BUS

400

3M

PANEL"HV"

4”C-4#500MCM+1/0 GND

400A, 480V, 3 PHASE NEMA 3RMANUAL TRANSFER SWITCH

4”C-4#500MCM+1/0 GND

TEMPORARY GENERATOR LUG CABINET

GROUND TO 3/4”x10’ GND ROD WITH3/0 AND 20’ OF #4UFER GROUND

PANEL"P"

15KVA TRANSFORMER480:120/208V, 3PH,4WGROUND TO BUILDING STEEL, WATER AND GAS PIPE WITH #4

1"C-4#8+1#8 GND

1"C-3#10+1#10 GND

PROVIDED AND INSTALLEDBY PG&E

PROVIDED AND INSTALLEDUNDER THIS PROJECT

TIT

LE

:P

RO

JE

CT

:

BYREVISIONS

SHEET

JOB

SCALE

DATE

CHECKED

DRAWN

STAMP

H C

S

EN

GIN

EE

RIN

G, IN

C.

CO

NS

UL

TIN

G E

LE

CT

RIC

AL

EN

GIN

EE

RS

451

2 F

EA

TH

ER

RIV

ER

DR

IVE

, S

UIT

E F

ST

OC

KT

ON

, C

A 9

521

9 (

20

9)

478

-82

70

em

ail

ad

dres

s r

ich

ard

@h

cs-e

ng

.co

m

HHHHTTTTIIII

MMMMSSSSCCCCDDDDRRRRAAAAHHHH

CCCCIIIIRRRR

No. E14303No. E14303No. E14303No. E14303Exp. 6Exp. 6Exp. 6Exp. 6----30303030----21212121

EEEE

LLLLEEEECCCCTTTTRRRR IIII CCCCAAAALLLL

RR RREEEEGGGGIIIISSSSTTTTEEEERRRR

EEEEDDDDPPPPRRRROOOOFFFFEEEESSSSSSSSIIIIOOOONNNNAAAALLLL

EEEENNNNGGGGIIIINNNNEEEEEEEERR RR

EEEEOOOOFFFF CCCCAAAALLLL IIIIFFFF

OOOORRRRNNNN

IIIIAAAA

SSSSTTTTAAAATTTT

12" = 1'-0"

8/12/2019 8:23:19 AM

C:\Users\RichardSmith\HCS ENGINEERING\Projects - Documents\Add to 2018\PORT WAREHOUSE 5\Port Chargers Rev 3.rvt

E3

2017.xxx

Checker

Author

WO

RLD

CH

AR

GE

RS

PO

RT

OF

ST

OC

KT

ON

WA

RE

HO

US

E 5

Ente

r addre

ss h

ere

WA

RE

HO

US

E 5

EL

EC

TR

ICA

L D

ET

AIL

S

Pro

ject

#:

2017.x

xx D

raft

er:

Au

tho

r E

ng

ineer:

Desig

ner

Legend:

Total Amps: 219 A 217 A 217 A

Total Load: 60525 VA 60143 VA 60000 VA

HEV-29 -- -- -- 12000 VA HEV-30HEV-27 -- -- -- 12000 VA HEV-28HEV-25 CHARGER 60 A 3 12000... HEV-26HEV-23 -- -- -- 12000 VA HEV-24HEV-21 -- -- -- 12000 VA HEV-22HEV-19 CHARGER 60 A 3 12000... HEV-20HEV-17 -- -- -- 12000 VA HEV-18HEV-15 -- -- -- 12000 VA HEV-16HEV-13 CHARGER 60 A 3 12000... HEV-14HEV-11 -- -- -- 12000 VA HEV-12HEV-9 -- -- -- 12000 VA 0 VA -- -- -- HEV-10HEV-7 CHARGER 60 A 3 12000... 0 VA -- -- -- HEV-8HEV-5 -- -- -- 12000 VA 0 VA 3 30 A 15 kVA, PANEL P HEV-6HEV-3 -- -- -- 12000 VA 150 VA 1 20 A EXTERIOR LIGHTING HEV-4HEV-1 CHARGER 60 A 3 12000... 525 VA 1 20 A Lighting HEV-2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: Type 1 MCB Rating: 400 A

Mounting: Surface Wires: 4 Mains Rating: 400 A

Supply From: Phases: 3 Mains Type: MCB

Location: Room 1 Volts: 480/277 Wye A.I.C. Rating: 22,000

PANEL HEV

SCALE: NTSONE LINE DIAGRAM1

Legend:

Total Amps: 3 A 3 A 7 A

Total Load: 360 VA 360 VA 864 VA

P-11 0 VA 1 20 A Spare P-12P-9 0 VA 1 20 A Spare P-10P-7 0 VA 1 20 A Spare P-8P-5 FAN 20 A 1 864 VA 0 VA 1 20 A Spare P-6P-3 Receptacle 20 A 1 360 VA 0 VA 1 20 A Spare P-4P-1 Receptacle 20 A 1 360 VA 0 VA 1 20 A Spare P-2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: Type 1 MCB Rating: 50 A

Mounting: SURFACE Wires: 4 Mains Rating: 50 A

Supply From: Phases: 3 Mains Type: MCB

Location: Volts: 120/208 Wye A.I.C. Rating: 18,0000

PANEL P

Page 9: Electric Fork Lift Battery Chargers - Port of Stockton€¦ · 2016 nfpa 20, installation of stationary pumps for fire protection 2013 nfpa 22, water tanks for private fire protection

9" CONCRETE STEPFOR CHARGERS

COLUMN FOR ROOFSTRUCTURE, SEESTRUCTURAL PLANS

PROVIDE LUMINAIRE LIGHTINGVPF 84 SERIES WET LABEL WASHDOWN INDUSTRIALFIXTURE

FUTURE CAMERA, PROVIDE1"C TO SIGNAL CABINET

CAMERACONNECT TO SECURITYCABINET

480V SERVICE

DRY TRANSFORMER

208V DIST

WIREWAY

480V DIST UTILITY TRANSFORMER.ELECTRICAL CONTRACTOR TOPROVIDE TRANSFORMERPAD AND BARRIER POSTS PER PG&E STADNARDS

PORT SECURITY FENCE TO BE REROUTEDTHROUGH THE CENTER OF THE CHARGERBAY BY THE CONTRACTOR.

W-H-11

PROVIDE 36x36x18 NEMA 3R CAN ATHIGH LEVEL. CONNECT ALL CAMERACONDUITS TO THIS LOCATION

TIT

LE

:P

RO

JE

CT

:

BYREVISIONS

SHEET

JOB

SCALE

DATE

CHECKED

DRAWN

STAMP

H C

S

EN

GIN

EE

RIN

G, IN

C.

CO

NS

UL

TIN

G E

LE

CT

RIC

AL

EN

GIN

EE

RS

451

2 F

EA

TH

ER

RIV

ER

DR

IVE

, S

UIT

E F

ST

OC

KT

ON

, C

A 9

521

9 (

20

9)

478

-82

70

em

ail

ad

dres

s r

ich

ard

@h

cs-e

ng

.co

m

HHHHTTTTIIII

MMMMSSSSCCCCDDDDRRRRAAAAHHHH

CCCCIIIIRRRR

No. E14303No. E14303No. E14303No. E14303Exp. 6Exp. 6Exp. 6Exp. 6----30303030----21212121

EEEE

LLLLEEEECCCCTTTTRRRR IIII CCCCAAAALLLL

RR RREEEEGGGGIIIISSSSTTTTEEEERRRR

EEEEDDDDPPPPRRRROOOOFFFFEEEESSSSSSSSIIIIOOOONNNNAAAALLLL

EEEENNNNGGGGIIIINNNNEEEEEEEERR RR

EEEEOOOOFFFF CCCCAAAALLLL IIIIFFFF

OOOORRRRNNNN

IIIIAAAA

SSSSTTTTAAAATTTT

1/8" = 1'-0"

8/12/2019 8:23:20 AM

C:\Users\RichardSmith\HCS ENGINEERING\Projects - Documents\Add to 2018\PORT WAREHOUSE 5\Port Chargers Rev 3.rvt

E4

2017.xxx

Checker

Author

WO

RLD

CH

AR

GE

RS

PO

RT

OF

ST

OC

KT

ON

WA

RE

HO

US

E 5

Ente

r addre

ss h

ere

WE

ST

CO

MP

LE

XA

RR

AN

GE

ME

NT

Pro

ject

#:

2017.x

xx D

raft

er:

Au

tho

r E

ng

ineer:

Desig

ner

SCALE: 1/8" = 1'-0"

WEST COMPLEX - GENERAL ARRANGEMENT1

Page 10: Electric Fork Lift Battery Chargers - Port of Stockton€¦ · 2016 nfpa 20, installation of stationary pumps for fire protection 2013 nfpa 22, water tanks for private fire protection

9" CONCRETE STEPFOR CHARGERS

SECURITY FENCE

480V SERVICE

DRY TRANSFORMER

208V DIST

WIREWAY

480V DIST

EV TRACKMOBILE

UTILITY TRANSFORMER(PAD BY CONTRACTOR)

SIX CPE250 FAST CHARGERS 4 STANDARD CHARGERS 1 DUAL OUTLET WORLD CHARGER

6 STANDARD CHARGERS 6 FUTURE CHARGERS, WITH 2"CO TO SWITCHBOARD

W-H-1

W-H-2

W-H-3 W-H-4

W-H-5

W-H-6 WL-1 WL-2 WL-3 WL-4

WL-5

WL-6

WL-7WL-8

WL-9

WL-10

W-H-9

TIT

LE

:P

RO

JE

CT

:

BYREVISIONS

SHEET

JOB

SCALE

DATE

CHECKED

DRAWN

STAMP

H C

S

EN

GIN

EE

RIN

G, IN

C.

CO

NS

UL

TIN

G E

LE

CT

RIC

AL

EN

GIN

EE

RS

451

2 F

EA

TH

ER

RIV

ER

DR

IVE

, S

UIT

E F

ST

OC

KT

ON

, C

A 9

521

9 (

20

9)

478

-82

70

em

ail

ad

dres

s r

ich

ard

@h

cs-e

ng

.co

m

HHHHTTTTIIII

MMMMSSSSCCCCDDDDRRRRAAAAHHHH

CCCCIIIIRRRR

No. E14303No. E14303No. E14303No. E14303Exp. 6Exp. 6Exp. 6Exp. 6----30303030----21212121

EEEE

LLLLEEEECCCCTTTTRRRR IIII CCCCAAAALLLL

RR RREEEEGGGGIIIISSSSTTTTEEEERRRR

EEEEDDDDPPPPRRRROOOOFFFFEEEESSSSSSSSIIIIOOOONNNNAAAALLLL

EEEENNNNGGGGIIIINNNNEEEEEEEERR RR

EEEEOOOOFFFF CCCCAAAALLLL IIIIFFFF

OOOORRRRNNNN

IIIIAAAA

SSSSTTTTAAAATTTT

1/8" = 1'-0"

8/12/2019 8:23:22 AM

C:\Users\RichardSmith\HCS ENGINEERING\Projects - Documents\Add to 2018\PORT WAREHOUSE 5\Port Chargers Rev 3.rvt

E5

2017.xxx

Checker

Author

WO

RLD

CH

AR

GE

RS

PO

RT

OF

ST

OC

KT

ON

WA

RE

HO

US

E 5

Ente

r addre

ss h

ere

WE

ST

CO

MP

LE

XE

LE

CT

RIC

AL

PL

AN

Pro

ject

#:

2017.x

xx D

raft

er:

Au

tho

r E

ng

ineer:

Desig

ner

SCALE: 1/8" = 1'-0"

WEST COMPLEX - ELECTRICAL PLAN1

THE PORT WILL BE PROVIDING CHARGERS FOR THE CONTRCATORTO INSTALL:

FAST CHARGERS - CHARGE POINT CPE250 OR EQUAL REQUIRES 80 AMP BREAKER AT 480 VOLT, 3 PHASE PROVIDE 2"C- 3#4+1#8 GND USE VENDOR TEMPLATE FOR LAYOUT

STANDARD CHARGER REQUIRES 40 AMP 208 VOLT 3 PHASE PROVIDE 2"C-3#8+1#10 GND USE SAME TEMPLATE AS FAST CHARGER TO ALLOW FOR FUTURE UPGRADE.

WORLD CHARGER - REQUIRES 40A BREAKER AT 480 VOLT, 3 PHASE PROVIDE (1) 2"C-3#8+1#10 GND FOR THE PAD CLOSETS TO THE TRACKMOBILE AND A SPARE 2" CONDUIT AT THE SECOND FORKLIFT LOCATION FOR FUTURE UGPRADES. INSTALL WITH SAME TEMPLATE AT FAST CHARGER.

FOR DEVELOPED SPACES, PROVIDE 2" CONDUIT FROM THE FAST CHARGER TEMPLATE TO THE ELECTRICAL SERVICE.

TRACKMOBILE - PROVIDE APPLETON 100A 480V OUTLET REQUIRES 100A BREAKER, 480 VOLT, 3 PHASE PROVIDE 2"C-3#2+1#8 GND

Page 11: Electric Fork Lift Battery Chargers - Port of Stockton€¦ · 2016 nfpa 20, installation of stationary pumps for fire protection 2013 nfpa 22, water tanks for private fire protection

MAIN SERVICE SWITCHBOARD "W15". NEMA 3R.

DANGERARC FLASH AND SHOCK HAZARD

FOLLOW ALL REQUIREMENTS IN NFPA 70E FOR SAFE WORK PRACTICES AND FOR PERSONAL PROTECTIVE EQUIPMENT

ARC FLASH LABELLING REQUIREMENT:PROVIDE THE FOLLOWING LABEL AS A MINIMUMFOR COMPLIANCE WITH NFPA AND NEC ON THIS PROJECT:

(8)5"CO

200

3

GROUND TO 3/4”x10’ GND ROD WITH3/0 AND 20’ OF #4UFER GROUND

2000A - 480/277V, 3PH, 4W BUS

2000

3M

MAIN DISTRIBUTION PANEL “W-L” : NEMA 3R

400A - 120/208V, 3PH, 4W BUS

400

3

2"C-4#3/0+1#4 GND

SEEGROUNDDETAIL

2"C-3#2+1#8GND

80

3

FASTCHARGER

2"C-3#2+1#8GND

80

3

FASTCHARGER

150KVA TRANSFORMER480:120/208V, 3PH,4WGROUND TO BUILDING STEEL, WATER AND GAS PIPE WITH #4

2"C-2#4+1#8GND

40

2

CHARGER

2"C-2#4+1#8GND

40

2

CHARGER

GFI

4”C-4#600MCM+1#250MCM GND

10 TOTAL

6 INSTALLED NOW

1-1/2"C-3#2+1#8GND

100

3

TRACKMOBILE

2"CO STUBTO FRAME FOR FUTURESOLAR

XX

3

3/4"CO STUBFOR LIGHTINGTO FRAME

20

2

80

3

FASTCHARGER

80

3

FASTCHARGER

18 FUTURE

40

3

WORLDCHARGER

M

MAIN

UGPS

7' -

7"

3' - 0"

14' - 0"

3'-6" NEMA 3R

NOTES: MAIN SERVICE SWITCHBOARD

1. ALL DIMENSIONS ARE NOMINAL.2. THE COMPLETE SWITCHBOARD SHALL HAVE A SYMMETRICAL SHORT CIRCUIT RATING EQUAL TO OR GREATER THAN THAT AVAILABLE FROM THE UTILITY COMPANY.3. MINIMUM INTEGRAL A.I.C. RATING OF SWITCHBOARD AND FEEDER CIRCUIT BREAKERS TO BE 42,000 AMPS.4. BOLT SECTIONS OF THE SWITCHBOARD TOGETHER WITH 1/2" BOLT AND NUTS AT 4 PLACES PER SECTION.5. BOLT EACH SECTION OF SWITCHBOARD TO FLOOR WITH (4) 1/2"x3" ANCHOR BOLTS.

6" HOUSE KEEPING SLAB3" AROUND FRONT ANDBOTH SIDES

3' - 0" 3' - 0"

W-H W-L

wireway

3' - 0" 2' - 0"

(24)CHAGER STUBS

150KVATRANSFORMER

TIT

LE

:P

RO

JE

CT

:

BYREVISIONS

SHEET

JOB

SCALE

DATE

CHECKED

DRAWN

STAMP

H C

S

EN

GIN

EE

RIN

G, IN

C.

CO

NS

UL

TIN

G E

LE

CT

RIC

AL

EN

GIN

EE

RS

451

2 F

EA

TH

ER

RIV

ER

DR

IVE

, S

UIT

E F

ST

OC

KT

ON

, C

A 9

521

9 (

20

9)

478

-82

70

em

ail

ad

dres

s r

ich

ard

@h

cs-e

ng

.co

m

HHHHTTTTIIII

MMMMSSSSCCCCDDDDRRRRAAAAHHHH

CCCCIIIIRRRR

No. E14303No. E14303No. E14303No. E14303Exp. 6Exp. 6Exp. 6Exp. 6----30303030----21212121

EEEE

LLLLEEEECCCCTTTTRRRR IIII CCCCAAAALLLL

RR RREEEEGGGGIIIISSSSTTTTEEEERRRR

EEEEDDDDPPPPRRRROOOOFFFFEEEESSSSSSSSIIIIOOOONNNNAAAALLLL

EEEENNNNGGGGIIIINNNNEEEEEEEERR RR

EEEEOOOOFFFF CCCCAAAALLLL IIIIFFFF

OOOORRRRNNNN

IIIIAAAA

SSSSTTTTAAAATTTT

As indicated

8/12/2019 8:23:22 AM

C:\Users\RichardSmith\HCS ENGINEERING\Projects - Documents\Add to 2018\PORT WAREHOUSE 5\Port Chargers Rev 3.rvt

E6

2017.xxx

Checker

Author

WO

RLD

CH

AR

GE

RS

PO

RT

OF

ST

OC

KT

ON

WA

RE

HO

US

E 5

Ente

r addre

ss h

ere

WE

ST

CO

MP

LE

XE

LE

CT

RIC

AL

DE

TA

ILS

Pro

ject

#:

2017.x

xx D

raft

er:

Au

tho

r E

ng

ineer:

Desig

ner

SCALE: NTSCHARGERS ONE LINE WEST1

Legend:

Total Amps: 647 A

Total Conn.... 538260 VA

W-H-30

W-H-29

W-H-28

W-H-27

W-H-26

W-H-25

W-H-24

W-H-23

W-H-22

W-H-21

W-H-20

W-H-19

W-H-18

W-H-17

W-H-16

W-H-15

W-H-14

W-H-13

W-H-12

W-H-11 Lighting 20 A 1 1260 VA

W-H-10

W-H-9 TRACKMOBILE 100 A 3 96000 VA

W-H-8

W-H-7 TRANS TW 200 A 3 66000 VA

W-H-6 CPE250 80 A 3 62500 VA

W-H-5 CPE250 80 A 3 62500 VA

W-H-4 CPE250 80 A 3 62500 VA

W-H-3 CPE250 80 A 3 62500 VA

W-H-2 CPE250 80 A 3 62500 VA

W-H-1 CPE250 80 A 3 62500 VA

CKT Circuit Description Trip RatingNumber of

Poles Load Remarks

Notes:

Enclosure: NEMA 3R MCB Rating: 2500 A

Mounting: FREE STANDING Wires: 4 Mains Rating: 2500 A

Supply From: Phases: 3 Mains Type: MCB

Location: Volts: 480/277 Wye A.I.C. Rating: 42,000

SERVICE W-H

Legend:

Total Amps: 183 A

Total Conn.... 66000 VA

WL-20

WL-19

WL-18

WL-17

WL-16

WL-15

WL-14

WL-13

WL-12

WL-11

WL-10 STANDARD CHARGER 40 A 2 6600 VA

WL-9 STANDARD CHARGER 40 A 2 6600 VA

WL-8 STANDARD CHARGER 40 A 2 6600 VA

WL-7 STANDARD CHARGER 40 A 2 6600 VA

WL-6 STANDARD CHARGER 40 A 2 6600 VA

WL-5 STANDARD CHARGER 40 A 2 6600 VA

WL-4 STANDARD CHARGER 40 A 2 6600 VA

WL-3 STANDARD CHARGER 40 A 2 6600 VA

WL-2 STANDARD CHARGER 40 A 2 6600 VA

WL-1 STANDARD CHARGER 40 A 2 6600 VA

CKT Circuit Description Trip RatingNumber of

Poles Load Remarks

Notes:

Enclosure: NEMA 3R MCB Rating: 400 A

Mounting: FREE STANDING Wires: 4 Mains Rating: 400 A

Supply From: TRANS TW Phases: 3 Mains Type: MCB

Location: Volts: 120/208 Wye A.I.C. Rating: 22,000

SERVICE WL

SCALE: NTS

WEST SERVICE ELEVATION2

Page 12: Electric Fork Lift Battery Chargers - Port of Stockton€¦ · 2016 nfpa 20, installation of stationary pumps for fire protection 2013 nfpa 22, water tanks for private fire protection
Page 13: Electric Fork Lift Battery Chargers - Port of Stockton€¦ · 2016 nfpa 20, installation of stationary pumps for fire protection 2013 nfpa 22, water tanks for private fire protection
Page 14: Electric Fork Lift Battery Chargers - Port of Stockton€¦ · 2016 nfpa 20, installation of stationary pumps for fire protection 2013 nfpa 22, water tanks for private fire protection