FAIRA TRANSPARENCY REPORTS
9126 1st Pl NE, #1, Lake Stevens, WA 98258
May 5th, 2017 Thank you for your interest in this Faira Certified home. We have coordinated the efforts of certified and licensed inspection and title professionals to create the Faira Transparency Reports for this home. The Faira Transparency Reports are a detailed portfolio of information that is prepared on behalf of buyers in preparation for making an informed offer on the property.
You may view more detailed information for this home and can make an offer at
http://www.faira.com/listings/11081 All of the information in the Faira Transparency Reports was gathered and compiled without any bias or influence from the seller(s). In fact, these reports are materially identical had you as the buyer(s) ordered the same professionals to perform the evaluations on the same date. Nevertheless, Faira takes no obligation of the reports being complete or accurate. The buyers are recommended to conduct their own due-diligence to their satisfaction. Please contact us if you have any questions or would like more information. We’re happy you’ve chosen a Faira Certified home and look forward to the opportunity of working with you! The Faira Team
RW West ConsultantsProperty Inspection Report
Cover Page
RW West Consultants 9126 1st Pl NE, Lake Stevens, WA
9126 1st Pl NE, #1, Lake Stevens, WA 98258Inspection prepared for: Faira
Real Estate Agent: Christopher Ellis - Faira
Date of Inspection: 5/4/2017 Time: 1:30 PM Age of Home: 1979 Size: 738 Weather: Sunny 72 degrees
Order ID: 1906Front door faces North for orientation purposes only.
Inspector: Dee Robert InmanWA St. Home Inspector License #1459, FAA UAS License #3976466
Email: [email protected]
RW West Consultants 9126 1st Pl NE, Lake Stevens, WA
Page 2 of 30
Inspection Details We appreciate the opportunity to conduct this inspection for you! Please carefully read your entireInspection Report. Call us after you have reviewed your report, so we can go over any questionsyou may have. Remember, when the inspection is completed and the report is delivered, we are stillavailable to you for any questions you may have, throughout the entire closing process.Properties being inspected do not "Pass" or "Fail.” - The following report is based on an inspectionof the visible portion of the structure; inspection may be limited by vegetation and possessions. Depending upon the age of the property, some items like GFCI outlets may not be installed; thisreport will focus on safety and function, not current code. This report identifies specific non-code,non-cosmetic concerns that the inspector feels may need further investigation or repair. For your safety and liability purposes, we recommend that licensed contractors evaluate and repairany critical concerns and defects. Note that this report is a snapshot in time. We recommendthat you or your representative carry out a final walk-through inspection immediately beforeclosing to check the condition of the property, using this report as a guide. Red Notes Denote serious, safety or items that require further investigationBlue notes denote minor or maintenance itemGreen note denote locations and shutoff valves
1. AttendanceIn Attendance: Seller present
2. Home TypeHome Type: Condominium/Townhouse
3. OccupancyOccupancy:• Occupied - Furnished: Heavy volume of personal and household items observed.• The utilities were on at the time of inspection.
RW West Consultants 9126 1st Pl NE, Lake Stevens, WA
Page 3 of 30
Exterior Areas 1. Siding ConditionSiding appeared in fair condition overall. • Cement fiber board siding shake • Plywood T111 sidingObservations:• Paint flaking at the siding, recommend loose paint is removed, barewood areas primed andrepainted.
North Elevation East Elevation
South Elevation West Elevation2. GuttersGutters and downspouts appeared in good condition overall.
RW West Consultants 9126 1st Pl NE, Lake Stevens, WA
Page 4 of 30
3. Driveway and Walkway ConditionConcrete sidewalks appeared in good condition overall. • Asphalt driveways appeared in goodcondition overall.
RW West Consultants 9126 1st Pl NE, Lake Stevens, WA
Page 5 of 30
4. SoffitSoffits and eaves appeared in fair condition overall.Observations:• Paint flaking at soffit areas, recommend repainting.
5. Door/WindowExterior doors appeared in operable condition, at time of inspection. • Threshold and jambsappeared in good condition overall. • Window frames and sills appeared in good condition overall.
RW West Consultants 9126 1st Pl NE, Lake Stevens, WA
Page 6 of 30
6. GradingGrading appeared in good condition overall.
East yard South yard7. Cable FeedsMaterials: Primary Service is Underground Service Lateral
RW West Consultants 9126 1st Pl NE, Lake Stevens, WA
Page 7 of 30
8. Exterior Faucet ConditionExterior faucets were in operable condition overall.Observations:• Hose bib at west side of house leaks from packing nut.• Sometimes tightening packing nut will remedy this condition.
9. Pressure65 psi
65 psi10. Gate ConditionMaterials: Chain linkObservations:• Fences are NOT INCLUDED as part of a home inspection.
RW West Consultants 9126 1st Pl NE, Lake Stevens, WA
Page 8 of 30
Roof 1. Roof ConditionArchitectural Composition shingle. • Roof surface is appeared in good condition overall. •Inspected from drone .Type Average life span 30 years for this type surface with proper maintenance and care.
2. FlashingFlashing appeared in good condition overall.
RW West Consultants 9126 1st Pl NE, Lake Stevens, WA
Page 9 of 30
Attic 1 1. AtticGround floor unit, no access available.
RW West Consultants 9126 1st Pl NE, Lake Stevens, WA
Page 10 of 30
General Interior Note 1. General NotesMaterials: Windows in the home are Double panel insulated glass windows. Any deficiencies arenoted in each room section for accessible windows • Doors in the home are considered operationalunless otherwise noted in each room sectionObservations:• Home contains popcorn ceilings. This material could contain asbestos, testing is not within thescope of this inspection
RW West Consultants 9126 1st Pl NE, Lake Stevens, WA
Page 11 of 30
Entryway 1. ConditionsCeiling and walls are in good condition overall. Light fixture operates. Entry door operates andlocks overall. • Tile floor is in good condition.
RW West Consultants 9126 1st Pl NE, Lake Stevens, WA
Page 12 of 30
Living Room 1. LocationLocation South
2. Living RoomWalls and ceilings appear in good condition overall. Flooring is carpet. Heat register present.Accessible outlets operate.
3. Window-Wall AC or Heat
Baseboard heat is operational4. Window DeficienciesObservations:• Cracked or broken window glass was observed. Injury could occur. Recommend repair orreplacement of the damaged glass.
RW West Consultants 9126 1st Pl NE, Lake Stevens, WA
Page 13 of 30
RW West Consultants 9126 1st Pl NE, Lake Stevens, WA
Page 14 of 30
Dining Room 1. LocationLocation Southeast
2. Dining RoomWalls and ceilings appear in good condition overall. Flooring is carpet. Heat register present.Accessible outlets operate. • Light fixture operates.
3. Window-Wall AC or Heat
Baseboard heat is operational
RW West Consultants 9126 1st Pl NE, Lake Stevens, WA
Page 15 of 30
Kitchen 1. Kitchen RoomWalls and ceilings appear in good condition overall. Flooring is wood. Heat register present.Accessible outlets operate. Light fixture operates. Sink and faucets are in operable conditionoverall. Cabinet doors and drawers are in operable condition overall.
2. Counter ConditionFormica counter is in good condition overall.
3. CabinetCabinet doors and drawers are in operable condition overall.
4. DisposalDisposal operates overall.
5. DishwasherDishwasher was in operable condition.
6. Stove/OvenStove/oven were in operable condition overall.
RW West Consultants 9126 1st Pl NE, Lake Stevens, WA
Page 16 of 30
7. RefrigeratorRefrigerator was in operable condition.
Refrigerator temperature Freezer temperature8. SinksSink was in operable condition overall.
9. ElectricalOutlets are GFCI protected at the counters.
10. Vent ConditionVent fan appears to exhaust to the exterior.
11. HeatingElectric baseboard heater operates. In nearby dining room.
RW West Consultants 9126 1st Pl NE, Lake Stevens, WA
Page 17 of 30
Laundry 1. ConditionCeiling and walls are in good condition overall. Accessible outlets operate. • Light fixture operates. •Washer and dryer were in operable condition at the time of inspection.Observations:• Washer and Dryer connections were not visible. Inspection of connections was not conducted.
2. Exhaust FansNo vent fan.
RW West Consultants 9126 1st Pl NE, Lake Stevens, WA
Page 18 of 30
Master Bedroom 1. LocationLocation Southwest
2. BedroomWalls and ceilings appear in good condition overall. Flooring is carpet in good condition. Heatregister present. Accessible outlets operate. • Light fixture operates.
3. HeatingElectric baseboard heater operates.
RW West Consultants 9126 1st Pl NE, Lake Stevens, WA
Page 19 of 30
Hall Bathroom1 1. RoomCeiling and walls are in good condition overall. Accessible outlets operate. Light fixture operates.
2. ElectricalGFI outlets within 6 feet of water sources.
3. CountersFormica counter tops are in good condition overall.
4. CabinetsCabinet doors and drawers are in operable condition overall.
5. Exhaust FansVent fan operates overall.
6. FloorsLinoleum Flooring is in good condition overall.
7. TubTub and shower were in good condition overall.
8. SinksSink was in operable condition overall.
9. ToiletToilet was in operable condition overall.
RW West Consultants 9126 1st Pl NE, Lake Stevens, WA
Page 20 of 30
Bedroom 1 1. LocationLocation Northwest
2. Bedroom RoomWalls and ceilings appear in good condition overall. Flooring is carpet. Heat register present.Accessible outlets operate. • Light fixture operates.
3. HeatingElectric baseboard heater operates.
Baseboard heater is operational
RW West Consultants 9126 1st Pl NE, Lake Stevens, WA
Page 21 of 30
Plumbing/Water Heater1 1. PlumbingWater lines were copper.
2. Water Heater ConditionHeater Type: Electric water heater. • 50 gallonsLocation: The heater is located in the hall closet.Observations:• Inspection covers at water heater are missing. Recommend replacement to avoid electrical shock
Water temp at kitchen sink 116 degrees
RW West Consultants 9126 1st Pl NE, Lake Stevens, WA
Page 22 of 30
3. AgeObservations:• Water heater in excess of 12 years and has exceeded useful life span, recommend monitoring orreplacement.• Approximately 23 years of age, average life span is 10 to 12 years.
4. ConditionObservations:• Seismic straps are not in place/ improperly installed. Normally there should be seismic strapsinstalled at the upper and lower one thirds of the tank.• Expansion tank is not in place. This is a hazardous condition on closed water systems.Recommend conditions are investigated further and corrected as required by licensed plumbingcontractor.• Drip pan does not have outlet drain to exterior, recommend outlet drain be installed or leak alarmsensor
5. TPRV ConditionTemperature Pressure Relief Valve (TPR Valve) present.Observations:• Temperature and pressure relief valve routes at an upward angle. This condition can cause waterto set in the outlet drain resulting in corrosion to the temperature and pressure relief valve andcause it not to engage when needed. This is an extremely hazardous condition, stronglyrecommend conditions are corrected by licensed HVAC contractor.
RW West Consultants 9126 1st Pl NE, Lake Stevens, WA
Page 23 of 30
Upward angle
RW West Consultants 9126 1st Pl NE, Lake Stevens, WA
Page 24 of 30
Electrical 1 1. LocationMaterials: Located in the Bedroom
2. Electrical150 AMP service, 2/0 Aluminum service entrance wires.
RW West Consultants 9126 1st Pl NE, Lake Stevens, WA
Page 25 of 30
3. GroundingElectrical service is grounded and bonded.
4. Wiring TypeBreaker system present. Wiring sizes conform to breaker sizes overall. Smaller branch circuit wiringis copper.Observations:• White neutral wires connected to circuit breakers should be black or red taped to designate theyare hot, recommend further investigation and correction by licensed electrical contractor.
RW West Consultants 9126 1st Pl NE, Lake Stevens, WA
Page 26 of 30
Foundation/Crawlspaces 1. FoundationContinuous concrete foundation visible portion appeared in good condition overall. No access fromthis unit available
RW West Consultants 9126 1st Pl NE, Lake Stevens, WA
Page 27 of 30
Shutoffs 1. Shutoff LocationsObservations:• Water heater water line shutoff is located above the water heater.• Could not locate main water shutoff within the unit, recommend consulting with owner.
||2||Water heater water line shutoff is located above the water heater.
RW West Consultants 9126 1st Pl NE, Lake Stevens, WA
Page 28 of 30
Equipment 1. Appliances/EquipmentObservations:• Stove• Oven• Refrigerator• Dishwasher• Water Heater
||2||Refrigerator ||2||Stove
||2||Dishwasher ||2||Disposal
RW West Consultants 9126 1st Pl NE, Lake Stevens, WA
Page 29 of 30
||2||Water Heater
RW West Consultants 9126 1st Pl NE, Lake Stevens, WA
Page 30 of 30
Report SummaryReport Summary
The summary below consists of potentially significant findings. These findings can be a safetyhazard, a deficiency requiring a major expense to correct or items I would like to draw extra attentionto. The summary is not a complete listing of all the findings in the report, and reflects the opinion ofthe inspector. Please review all pages of the report as the summary alone does not explain all of theissues. All repairs should be done by a licensed & bonded tradesman or qualified professional. Irecommend obtaining a copy of all receipts, warranties and permits for the work done.General Interior NotePage 10 Item: 1 General Notes • Home contains popcorn ceilings. This material could contain
asbestos, testing is not within the scope of this inspectionLiving RoomPage 12 Item: 4 Window
Deficiencies• Cracked or broken window glass was observed. Injury couldoccur. Recommend repair or replacement of the damagedglass.
Plumbing/Water Heater1Page 21 Item: 2 Water Heater
Condition• Inspection covers at water heater are missing. Recommendreplacement to avoid electrical shock
Page 22 Item: 3 Age • Water heater in excess of 12 years and has exceeded usefullife span, recommend monitoring or replacement.• Approximately 23 years of age, average life span is 10 to 12years.
Page 22 Item: 4 Condition • Seismic straps are not in place/ improperly installed.Normally there should be seismic straps installed at the upperand lower one thirds of the tank.• Expansion tank is not in place. This is a hazardous conditionon closed water systems. Recommend conditions areinvestigated further and corrected as required by licensedplumbing contractor.• Drip pan does not have outlet drain to exterior, recommendoutlet drain be installed or leak alarm sensor
Page 22 Item: 5 TPRV Condition • Temperature and pressure relief valve routes at an upwardangle. This condition can cause water to set in the outlet drainresulting in corrosion to the temperature and pressure reliefvalve and cause it not to engage when needed. This is anextremely hazardous condition, strongly recommendconditions are corrected by licensed HVAC contractor.
ShutoffsPage 27 Item: 1 Shutoff Locations • Could not locate main water shutoff within the unit,
recommend consulting with owner.