    FUNCTION DESIGN SPECIFICATIONS

    SSE SCADA UPGRADING

    PENGABUAN STATION

    2 SEP 28, 2012 FOR REVIEW NM HT HH

    3 NOV 13, 2012 FOR REVIEW NM HT HH

    REV DATE ISSUE TYPE PREPD

    BYREVD BY APPD

    BY

    CLIENT

    APPD

    PT. Integra Automasi

  • 7/27/2019 fds pengabuan medco

    2/9

    SSE SCADA UPGRADING

    TITLE DOCUMENT NUMBER REV DATE PAGE

    Functional Design Specification MEP-SCUP-ENG-02.7 3 13-11-12 2 of 9

    Pengabuan Station Function Design Specification 2 OF 9

    REVISION CONTROL SHEET

    Latest

    RevDATE ISSUED

    PRED

    BY

    REVD

    BYAPPD BY

    CLIENT

    APPDCOMMENTS

    0 FEB 19, 2012 AT HT HH

    1 SEP 4, 2012 NM HT HH

    2 SEP 28, 2012 NM HT HH

    3 NOV 13, 2012 NM HT HH

  • 7/27/2019 fds pengabuan medco

    3/9

    SSE SCADA UPGRADING

    TITLE DOCUMENT NUMBER REV DATE PAGE

    Functional Design Specification MEP-SCUP-ENG-02.7 3 13-11-12 3 of 9

    Pengabuan Station Function Design Specification 3 OF 9

    TABLE OF CONTENT

    1 SYSTEM ARCHITECTURE 41.1 SCADA System Architecture 41.2 Pengabuan Station Existing System Architecture 41.3 Pengabuan Station Proposed System Architecture 51.4 Bandwidth Requirement 62 SCADA/HMI DESIGN 72.1 Overview Pengabuan Station 72.2 Alarms 72.3 Trending 83 BILL OF MATERIALS 9

  • 7/27/2019 fds pengabuan medco

    4/9

    SSE SCADA UPGRADING

    TITLE DOCUMENT NUMBER REV DATE PAGE

    Functional Design Specification MEP-SCUP-ENG-02.7 3 13-11-12 4 of 9

    Pengabuan Station Function Design Specification 4 OF 9

    1 SYSTEM ARCHITECTURE

    The Operator Station shall be based on standard off-the-shelf workstation hardware running on a

    Windows based operating system. Vijeo Citect is using full 32 bit (65 million) colors. For

    integration with existing Historian we use Matrikon OPC Server client for ODBC. This OPC server

    is using for logging data to SQL Server.

    1.1 SCADA System Architecture

    SCADA System centralizes in Soka Office. All parameter in all stations can be monitor in Central

    Monitoring room SCADA at Soka Office.

    1.2 Pengabuan Station Existing System Architecture

    An Existing HMI runtime is Experion HS. and set of redundant PLC system using Honeywell PLC

    MasterLogic 200.

  • 7/27/2019 fds pengabuan medco

    5/9

    SSE SCADA UPGRADING

    TITLE DOCUMENT NUMBER REV DATE PAGE

    Functional Design Specification MEP-SCUP-ENG-02.7 3 13-11-12 5 of 9

    Pengabuan Station Function Design Specification 5 OF 9

    1.3 Pengabuan Station Proposed System Architecture

  • 7/27/2019 fds pengabuan medco

    6/9

    SSE SCADA UPGRADING

    TITLE DOCUMENT NUMBER REV DATE PAGE

    Functional Design Specification MEP-SCUP-ENG-02.7 3 13-11-12 6 of 9

    Pengabuan Station Function Design Specification 6 OF 9

    1.4 Bandwidth Requirement

    Bandwidth requirement for SCADA is less than 32 Kbps. Please find this example below. This

    example is for bandwidth calculation.

    Status Register

    The 128 Status Register will be retrieve every 250 ms and using Modbus Function code 2

    This results is 23 bytes every 250 ms = 92 bytes per second or 736 bits per second = 0.7 kbps

    Input Register

    The 64 Input Register will be retrieve every 250 ms and using Modbus Function code 4

    This results is 141 bytes every 250 ms = 564 bytes per second or 4512 bits per second = 4.5 kbps

    Request

    8 bytes

    Response

    15 bytes

    Request

    8 bytes

    Response

    133 bytes

  • 7/27/2019 fds pengabuan medco

    7/9

    SSE SCADA UPGRADING

    TITLE DOCUMENT NUMBER REV DATE PAGE

    Functional Design Specification MEP-SCUP-ENG-02.7 3 13-11-12 7 of 9

    Pengabuan Station Function Design Specification 7 OF 9

    2 SCADA/HMI DESIGN

    2.1 Overview Pengabuan Station

    2.2 Alarms

  • 7/27/2019 fds pengabuan medco

    8/9

    SSE SCADA UPGRADING

    TITLE DOCUMENT NUMBER REV DATE PAGE

    Functional Design Specification MEP-SCUP-ENG-02.7 3 13-11-12 8 of 9

    Pengabuan Station Function Design Specification 8 OF 9

    2.3 Trending

  • 7/27/2019 fds pengabuan medco

    9/9

    SSE SCADA UPGRADING

    TITLE DOCUMENT NUMBER REV DATE PAGE

    Functional Design Specification MEP-SCUP-ENG-02.7 3 13-11-12 9 of 9

    Pengabuan Station Function Design Specification 9 OF 9

    3 BILL OF MATERIALS

    ITEM NO. DESCRIPTION Manufacture Model Qty Unit

    Hardware & Software

    Pengabuan Station

    1 SCADA

    1.1 Hardware

    Wall Mounted Panel Fortuna 12 U 1 Ea

    Cable and Accessories 1 Lot

    2Engineering and Services

    Pengabuan Station

    1 Lot

    Engineering