FIREFIGHTING

FIREFIGHTING - idrobios.com · Standard UNI EN 12845 concerns "Fixed firefighting systems - Automatic sprinkler systems - Design, installation and maintenance”. This standard harmonises

Embed Size (px)

Citation preview

FIREFIGHTING

Firefighting units constructed in compliance with UNI EN 12845 and UNI 10779 standards _02

Electric pump + jockey pump _06

2 Electric pumps + jockey pump _08

Combustion engine pump + jockey pump _10

Electric pump + combustion engine pump + jockey pump _12

Electric pump + submersible jockey pump _14

2 Electric pumps + submersible jockey pump _16

Compact firefighting system for hotels _18

Technical shelter in compliance with UNI 11292 _19

CE declaration of conformity _20

CONTENTS

1

Standard UNI EN 12845 concerns "Fixed firefighting

systems - Automatic sprinkler systems - Design,

installation and maintenance”.

This standard harmonises the execution of sprinkler

based firefighting systems on a European level,

establishing the method of construction of the fire pump

systems that can be installed in Europe, serving sprinkler

and/or hydrant firefighting networks.

IDROBIOS operates in the design, production and

worldwide distribution of products for the management

of water, constantly developing new products in

compliance with customer demands.

All the systems manufactured are individually tested in

compliance with the requirements of UNI EN 12845.

IDROBIOS fire pumps are composed of one

or more main pumps driven by an electric

motor or internal combustion engine and

equipped with a jockey pump that keeps the

system constantly pressurised without starting

the main pumps.

Designed to operate automatically in the

presence of water withdrawal demands

from any service of the firefighting system,

including:

Sprinkler systems

Hose reel systems

Hydrant systems (UNI 45 / UNI 70)

Firefighting units constructed in compliance with UNI EN 12845 and UNI 10779 standards

2

FIREFIGHTING

Operation

The pumps start in response to a pressure drop in the firefighting circuit.

The jockey pump is started first; if the jockey pump is unable to restore system pressure, the feed pump is started.

The feed pump is started by two pressure switches via an electrical control panel; the feed pump must run continuously

until it is stopped with a manual command to UNI EN 12845 par. 10.7.5.2; or, taking account of UNI10779 related

to hydrant circuits, the pump can be stopped automatically by means of a timer installed in the control panel, with

minimum time setting of 20 minutes.

The two pump start pressure switches must be calibrated to comply with the following pressure values:

Units with one electric pump - max pump pressure (x 0.8 bar)

Units with two electric pumps - pump 1 max pressure (x 0.8 bar)

- pump 2 max pressure (x 0.6 bar )

Example: max pressure 10 bar - pump 1 starts at 8 bar - - pump 2 starts at 6 bar -

Starting of the main pump(s) is signalled by an acoustic/visual indicator; the indicator trips also in the event of a phase loss

or power loss.

The low flow rate jockey pump is an electric centrifugal pump, generally a self-priming type of low power, designed to maintain

the system pressure and compensate for minor leakage from the firefighting circuit, thereby avoiding unnecessary starts of the

main pump(s).

The jockey pump is started automatically by a dedicated control panel and associated pressure switch set to a pressure value

that is slightly higher than the main pump pressure switch.

The jockey pump stops when system pressure is restored.

3

IDROBIOS offers firefighting units fully assembled on a single skid, or divided into separate modules to facilitate

transport and management of the installation spaces on the work site. The standard composition of firefighting units

preassembled on a single skid includes:

Standardised main pumps to EN733.

Pressure switches (two for each electric pump/combustion engine pump).

Glycerine-filled pressure gauges.

Water circulation connection for pump protection.

Check valve on main pump outlet for connection of a priming tank, if required (for suction lif t installation).

Double-flanged outlet manifold in painted steel.

Batteries for starting the diesel engine pump, if present.

Fuel tank constructed in compliance with EN 12845, complete with standard flexible connections,

with combustion engine pump.

Electrical panel in metal enclosure in compliance with EN 12845 for control of the main electric pump.

Electrical panel in metal enclosure in compliance with EN 12845 for control of the main combustion

engine pump.

Electrical panel for jockey pump control.

Steel skid complete with deck for electric pumps, combustion engine pump (if present), for electrical control

panels and for batteries (if present).

Membrane expansion vessels, capacity 20l.

The electrical panels installed on firefighting units comply with the following specifications, required by EN 12845:

For surface pumps

direct starting for power ratings up to 10 HP

star-delta starting for power ratings ≥ 12.5 HP

For submersible pumps:

direct starting for power ratings up to 10 HP

stator resistance starter for power ratings ≥ 12.5 HP

Firefighting units constructed in compliance with UNI EN 12845 and UNI 10779 standards

4

Wafer type butterfly

shut-of f valve.

Eccentric flanged

reductions to install on the suction

connections of the main pumps.

Direct reading flow meter

For accurate reading of the flow rate shown on

the flow meter, interpose two sections of pipe

having a length that is 5 times the diameter (DNA)

of the pipe upstream and downstream of the flow

meter.

Antivibration flexible compensators

If the system includes a combustion

engine pump it will include a flexible

compensator to dampen vibrations.

Clapet check valve

installed on the pumps outlet line.

Local alarm panel for

remotable visual - acoustic

alarms.

FIREFIGHTING

Water/water cooling circuit with heat exchanger, available

on request. The system draws the necessary volume of water to

cool the engine directly from the main pump; take account of

this flow rate and exclude it from the calculation for firefighting

duties (to select the fire pump correctly add the design flow

rate to the flow required by the heat exchanger).

The configuration of the cooling system with water/water heat

exchanger includes a by-pass circuit complete with shut-off

valves, pressure reducers, pressure gauge, and "Y" filters.

100 l priming tank (for LH risk class) and 500 l for OH, HHP

and HHS.

5

Single-stage centrifugal main pumps with standardised bare shaft of the back pull-out type, constructed in compliance

with EN 733 (ex DIN 24255).

Connection with asynchronous three-phase electric motor made by means of a flexible spacer coupling.

The firefighting unit is complete with a main electric pump mounted on a skid made of painted steel profiles, wired to

the electrical control panel installed on the skid vertical frame.

The supply of the IDROBIOS firefighting unit includes the following components on the suction line: shut-of f valve and

eccentric reduction mounted on the suction side of the main electric pump.

Flow rates up to 420 m3/h and maximum pressure head of 97 m w.g.

Maximum speed of 2900 rpm.

For higher flow rates and pressure heads consult our engineering department.

Electric pump + jockey pump

6

(01) Main electric pump(02) Electric jockey pump(03) Outlet manifold(04) Flow meter kit(05) Pressure tank (06) Pressure gauge(07) Inspectable check valve(08) Priming kit - for suction lift installation(09) Pressure switches (no.2 for each of the main electric pumps)

(10) Eccentric reduction with vacuum meter

(11) Spacer coupling for pump/motor connection (12) Electrical control panels(13) Skid/motor coupling with anti-vibration joint(14) Standardised pump with bare shaft to EN 733(15) Three-phase asynchronous motor(16) Glycerine filled pressure gauge with isolator cock(17) Wafer type shut-off valve(18) Ball valve to isolate flow meter circuit(19) Flow meter circuit with return to storage(20) Electric jockey pump pressure switch(21) Frame/Skid(22) Omega profile for cable routing

Key:

DNA1 (Suction)

(2)

(8) (8)

(10)

(16)

(15)

(11)

(13)(21)

(14)

(8)

(6)

(12)

(5) (5)(5)

(4) (4)

(20)

(22)(17)

(18)(19)

(9)

(19)

(7) (7)

(3)DNM

(1)

DNA2

Main components

FIREFIGHTING

7

Single-stage centrifugal main pumps with standardised bare shaft of the back pull-out type, constructed in compliance

with EN 733 (ex DIN 24255).

Connection with asynchronous three-phase electric motor made by means of a flexible spacer coupling.

The firefighting unit is complete with two main electric pumps mounted on a skid made of painted steel profiles, wired

to the electrical control panels installed on the skid vertical frame.

The supply of the IDROBIOS firefighting unit includes the following components on the suction line: shut-of f valve and

eccentric reduction mounted on the suction side of the main electric pumps.

Flow rates up to 420 m3/h and maximum pressure head of 97 m w.g. (data referred to single pump)

For higher flow rates and pressure heads consult our engineering department.

2 Electric pumps + jockey pump

8

(01) Main electric pump(02) Electric jockey pump(03) Outlet manifold(04) Flow meter kit(05) Pressure tank(06) Pressure gauge(07) Inspectable check valve(08) Priming kit - for suction lift installation(09) Pressure switches (no.2 for each of the main electric pumps)

(10) Eccentric reduction with vacuum meter

(11) Spacer coupling for pump/motor connection (12) Electrical control panels(13) Skid/motor coupling with anti-vibration joint(14) Standardised pump with bare shaft to EN 733(15) Three-phase asynchronous motor(16) Glycerine filled pressure gauge with isolator cock(17) Wafer type shut-off valve(18) Ball valve to isolate flow meter circuit(19) Flow meter circuit with return to storage(20) Electric jockey pump pressure switch(21) Frame/Skid(22) Omega profile for cable routing

Key:

Main components

(Suction) DNA1=DNA2

(Suction) DNA1=DNA2

(Suction) DNA3

(2)

(8) (8) (8)

(10)

(16)

(15)

(11)

(13)(21)

(14)

(8)

(6)

(12)

(5) (5)(5) (5)

(4) (4)

(20)

(22)(17)

(18)(19)(9)

(19)

(7) (7) (7)

(3)DNM

(1) (1)

FIREFIGHTING

9

Single-stage centrifugal main pumps with standardised bare shaft of the back pull-out type, constructed in compliance

with EN 733 (ex DIN 24255).

Connection with internal combustion engine (diesel) made by means of a flexible spacer coupling.

The firefighting unit is complete with a combustion engine pump mounted on a skid made of painted steel profiles,

wired to the electrical control panel installed on the skid vertical frame.

The supply of the IDROBIOS firefighting unit includes the following components on the suction line: shut-of f valve,

eccentric reduction, and rubber anti-vibration joint, mounted on the suction side of the main combustion engine pump.

Flow rates up to 420 m3/h and maximum pressure head of 97 m w.g.

Maximum speed of 2900 rpm

For higher flow rates and pressure heads consult our engineering department.

Combustion engine pump + jockey pump

10

(01) Combustion engine pump(02) Electric jockey pump(2’) Fuel tank(03) Outlet manifold(04) Flow meter kit(05) Pressure tank(06) Pressure gauge(07) Inspectable check valve(08) Priming kit - for suction lift installation(09) Pressure switches (no.2 per combustion engine pump)

(10) Eccentric reduction with vacuum meter

(11) Spacer coupling for pump/motor connection(12) Electrical control panels (1 for combustion engine pump. 1 for jockey pump)(13) Skid/motor coupling with anti-vibration joint(14) Standardised pump with bare shaft to EN 733(15) Internal combustion engine.(16) Glycerine filled pressure gauge with isolator cock(17) Wafer type shut-off valve(18) Ball valve to isolate flow meter circuit(19) Flow meter circuit with return to storage(20) Electric jockey pump pressure switch(21) Frame/Skid(22) Rubber anti-vibration joint

Key:

Main components

DNA DNA2

(2) (8)

(10)

(16)

(15)

(11)

(13)

(21)

(14)

(8)

(6)(12)

(5)(5)

(4)

(20)

(24)(22 )

(17)

(18)(19)(9)

(19)

(7) (7)

(3)

(23) (23)

(4)

(2’)

(1)

FIREFIGHTING

11

Single-stage centrifugal main pumps with standardised bare shaft of the back pull-out type, constructed in compliance

with EN 733 (ex DIN 24255).

Connection with electric motor and internal combustion engine made by means of a flexible spacer coupling.

The firefighting unit is complete with a main electric pump, a combustion engine pump and an electric jockey pump,

mounted on a skid made of painted steel profiles, wired to the associated electrical control panels installed on the

skid vertical frame.

The supply of the IDROBIOS firefighting unit includes the following components on the suction line: shut-of f valve,

eccentric reduction, and rubber anti-vibration joint (for combustion engine pump), mounted on the suction side of the

main pumps.

Flow rates up to 420 m3/h and maximum pressure head of 97 m w.g.

Maximum speed of 2900 rpm.

For higher flow rates and pressure heads consult our engineering department.

Electric pump + combustion engine pump + jockey pump

12

(01) Main electric pump(01’) Combustion engine pump(02) Electric jockey pump(03) Outlet manifold(04) Flow meter kit(05) Pressure tank(06) Pressure gauge(07) Inspectable check valve(08) Priming kit - for suction lift installation(09) Pressure switches (no.2 for each of the main electric pumps)

(10) Eccentric reduction with vacuum meter(11) Spacer coupling for pump/engine connection

(12) Electrical control panels (13) Skid/motor coupling with anti-vibration joint(14) Standardised pump with bare shaft to EN 733(15) Three-phase asynchronous motor(15') Internal combustion engine(16) Glycerine filled pressure gauge with isolator cock(17) Wafer type shut-off valve(18) Ball valve to isolate flow meter circuit(19) Flow meter circuit with return to storage(20) Electric jockey pump pressure switch(21) Frame/Skid(22) Omega profile for unit connection cables(23)Rubber anti-vibration joint (combustion engine pump suction)(24) Batteries(25) Fuel tank

Key:

Main components

DNA1

DNA2DNA3

(2)(8)

(10)

(16)

(15’)

(11)

(13)(21)

(14)

(8)

(8)(8)

(6)

(12)

(12)

(5)(5) (5)

(4)

(20)

(24)

(22 ) (17)

(18)(9)

(19)

(15)

(7) (7)(7)

(7)

(3)

(23) (23)

(23)

(25)

(4)

(1) (1’)

FIREFIGHTING

13

Submersible type main pump with asynchronous three-phase electric motor. The firefighting unit is complete with a main

electric pump and a submersible electric jockey pump, supplied disconnected from the hydraulic control assembly.

Together with the electrical control panels, this latter is mounted on a skid made of painted steel profiles.

Supply of the IDROBIOS firefighting unit includes the components listed below complete with a main electric pump

and jockey pump (supplied separately - installation to be carried out by the customer).

Flow rates of up to 90 m3/h and maximum pressure head of 136 m w.g.

Maximum speed of 2900 rpm.

For higher flow rates and pressure heads consult our engineering department.

Electric pump + submersible jockey pump

14

Main components

DNA1

DNM

DNA2

(2)(2)

(10) (10)

5xDNA 5xDNA

Return to storage tank

Submersible electric pump

Main electric pump control panel

Jockey pump control panel

External jacket

DNA

(8)

(6)

(6)

(5) (5)

(9)(9)

(7)

(3) (3) (3)

(4)

(1)

DNA1 Main electric pump connectionDNA2 Electric jockey pump connection(01) Outlet manifold(02) Wafer valve for connection of flow meter kit(03) Pressure tank

(04) Pressure gauge(05) Inspectable check valve(06) Pressure switches(07) Electrical control panels (1 for main pump + 1 for jockey pump)

(08) Wafer type shut-off valve(09) Pressure relief valve(10) Frame/Skid

Key:

FIREFIGHTING

15

Submersible type main pumps with asynchronous three-phase electric motor. The firefighting unit is complete with

two main electric pumps and a submersible electric jockey pump, supplied disconnected from the hydraulic control

assembly.

Together with the electrical control panels, this latter is mounted on a skid made of painted steel profiles.

The IDROBIOS firefighting unit supply includes the following components complete with main and jockey

electric pumps (supplied separately - installation to be performed by the customer).

Flow rates of up to 90 m3/h and maximum pressure head of 136 m w.g.

Maximum speed of 2900 rpm.

For higher flow rates and pressure heads consult our engineering department.

2 Electric pumps + submersible jockey pump

16

Main components

DNA1

DNM

DNA2

DNA3

(2) (2)

2000

(2)

(10) (10)

5xDNA 5xDNA

Return to storage tank

Submersible electric pump

Submersible electric pump

Main electric pump 1 control panel

Main electric pump 2 control panel

Jockey pump control panel

External jacketExternal jacket

DNA

(8)(8)

(8)

(6)

(6)(6)

(5) (5)(5)

(9)(9)

(7)

(3) (3)

(4)

(1)

DNA1 Main electric pump connectionDNA2 Electric jockey pump connection(01) Outlet manifold(02) Wafer valve for connection of flow meter kit(03) Pressure tank

(04) Pressure gauge(05) Inspectable check valve(06) Pressure switches(07) Electrical control panels (08) Wafer type shut-off valve(09) Pressure relief valve(10) Frame/Skid

Key:

FIREFIGHTING

17

The system is designed for hotels with up to 100 beds. The fire-protection water distribution activities for this type of building are governed by art. 11.3.1 of Italian ministerial decree 9 April 1994 and by Italian ministerial decree 6 October 2003. The former decree requires that: Hotels with a number of beds from 25 up to 100 must be equipped with DN 20 hose reels. The hose reels can be connected to the normal water mains on the condition it is able to feed the two hose reels in the most hydraulically unfavourable position in addition to the normal services, assuring for each of the foregoing hose reels a flow rate of at least 35 l/min at a minimum pressure of 1.5 bar, when both hoses are open. The water supply must assure water output for at least 60 min. If the water mains is unable to meet the foregoing condition the system shown alongside can be installed, comprising a water storage tank having total capacity of 2000 litres, two submersible electric pumps, one of which a jockey pump, control panels, alarm panel, and hydraulic assembly.

Firefighting units with vertical axis pumps

Submersible main vertical axis pump

0.00

Submersible electric jockey pump

Suction rose

Pump Head

Distribution baseDistribution base

Head

Outlet manifold

Internal combustion

engineFlow meter

Electric Motor

Electric, diesel and/or mixed type. Constructed in accordance with UNI EN 12845. Flow rates up to 1200 m3/h, Pressure head of up to 310 m w.g.

Compact firefighting system for hotels Construction to UNI EN 12845 composed of 1 main electric pump + 1 electric jockey pump (both submersible type).

Flow meter

Door Lock

OverloadLock

ELECTRIC JOCKEY PUMP CONTROL PANEL

MAIN ELECTRIC PUMP CONTROL PANEL

Run Run

M - 0 - A M - 0 - A

Overload Trip

Overload Trip

PowerOn

Mute

PowerOn

PowerOn

ALARMVisual Acoustic

Door Lock

18

UNI 11292 specifies the construction

and functional requirements for technical

shelters to accommodate firefighting

pressurisation units.

The indications in the standard complete

the prescriptions of the legislation

applicable to the subject and specifically

EN 12845 (fixed firefighting systems

— Sprinkler systems), UNI 10779

(Hydrant circuits — design, installation

and operation) and UNI 10803

(Prefabricated stairs legislation). The

latter is applicable only to underground

systems.

IDROBIOS offers prefabricated

firefighting technical shelters with R60

structural resistance to fire; optionally

also with integral or modular water

storage, in both underground and above

ground versions.

Configuration of the standard system

includes the installed firefighting unit,

lighting, heating, a fire extinguisher and

all the parts required by the reference

standards to ensure conformity with the

certifications issued by the company.

Technical shelter in compliance with UNI 11292

FIREFIGHTING

19

All firefighting units described in the following catalogue are complete with a

DECLARATION OF CONFORMITY

Drafted in compliance with the requirements of the machinery directive 2009/127/EEC (ex 2006/42/EC)

Each machine is supplied complete with the relevant technical documentation, namely:

Operating and maintenance manual

Name and address of the manufacturer

Model

Serial number

Year of construction

CE declaration of conformity

DICHIARAZIONE DI CONFORMITA’

La Idrobios srl

D I C H I A R A

CHE IL GRUPPO DI PRESSURIZZAZIONE ANTINCENDIO

Marca: IDROBIOSModello: ______________ Descrizione: Es. gruppo antincendio costituito da una elettropompa principale, una

motopompa diesel ed una elettropompa pilota. Matricola: ______________ Anno costruzione: ______________

È stato realizzato in conformità alle direttive:

• Direttiva macchine (2009/127/CEE) (Ex 98/37/CE – Ex 2006/42/EC)

• Bassa tensione (2006/95/CE) (Ex 73/23/CEE – Ex 93/68/CEE)

• Compatibilità elettromagnetica (2004/108/CE) (Ex 89/336/CEE – Ex 92/31/CEE – Ex 93/68/CEE)

nel rispetto delle vigenti:

• UNI EN 12845 “Impianti fissi di estinzione incendi - Sistemi automatici”

• UNI 10779 “Impianti di estinzione incendi - Reti di Idranti”

• UNI EN ISO 9906 “Prove di prestazioni idrauliche pompe”

Dichiara inoltre che sono state applicate le seguenti Norme Armonizzate:

• UNI EN ISO 12100-1 (Ex 292/1) • UNI EN ISO 12100-2 (Ex 292/2) • CEI EN 60204-1 “Sicurezza del macchinario, equipaggiamento elettrico delle macchine. Regole generali” • CEI 17/13-1 Quadri BT.

Le informazioni tecniche sono presso: Idrobios srl Via Sant’Anna 612/B 41122 Modena

Lì, __________________ Firma

(Lusvarghi Paolo)

DICHIARAZIONE DI CONFORMITA’

La Idrobios srl

D I C H I A R A

CHE IL GRUPPO DI PRESSURIZZAZIONE ANTINCENDIO

Marca: IDROBIOSModello: ______________ Descrizione: Es. gruppo antincendio costituito da una elettropompa principale, una

motopompa diesel ed una elettropompa pilota. Matricola: ______________ Anno costruzione: ______________

È stato realizzato in conformità alle direttive:

• Direttiva macchine (2009/127/CEE) (Ex 98/37/CE – Ex 2006/42/EC)

• Bassa tensione (2006/95/CE) (Ex 73/23/CEE – Ex 93/68/CEE)

• Compatibilità elettromagnetica (2004/108/CE) (Ex 89/336/CEE – Ex 92/31/CEE – Ex 93/68/CEE)

nel rispetto delle vigenti:

• UNI EN 12845 “Impianti fissi di estinzione incendi - Sistemi automatici”

• UNI 10779 “Impianti di estinzione incendi - Reti di Idranti”

• UNI EN ISO 9906 “Prove di prestazioni idrauliche pompe”

Dichiara inoltre che sono state applicate le seguenti Norme Armonizzate:

• UNI EN ISO 12100-1 (Ex 292/1) • UNI EN ISO 12100-2 (Ex 292/2) • CEI EN 60204-1 “Sicurezza del macchinario, equipaggiamento elettrico delle macchine. Regole generali” • CEI 17/13-1 Quadri BT.

Le informazioni tecniche sono presso: Idrobios srl Via Sant’Anna 612/B 41122 Modena

Lì, __________________ Firma

(Lusvarghi Paolo)

DICHIARAZIONE DI CONFORMITA’

La Idrobios srl

D I C H I A R A

CHE IL GRUPPO DI PRESSURIZZAZIONE ANTINCENDIO

Marca: IDROBIOSModello: ______________ Descrizione: Es. gruppo antincendio costituito da una elettropompa principale, una

motopompa diesel ed una elettropompa pilota. Matricola: ______________ Anno costruzione: ______________

È stato realizzato in conformità alle direttive:

• Direttiva macchine (2009/127/CEE) (Ex 98/37/CE – Ex 2006/42/EC)

• Bassa tensione (2006/95/CE) (Ex 73/23/CEE – Ex 93/68/CEE)

• Compatibilità elettromagnetica (2004/108/CE) (Ex 89/336/CEE – Ex 92/31/CEE – Ex 93/68/CEE)

nel rispetto delle vigenti:

• UNI EN 12845 “Impianti fissi di estinzione incendi - Sistemi automatici”

• UNI 10779 “Impianti di estinzione incendi - Reti di Idranti”

• UNI EN ISO 9906 “Prove di prestazioni idrauliche pompe”

Dichiara inoltre che sono state applicate le seguenti Norme Armonizzate:

• UNI EN ISO 12100-1 (Ex 292/1) • UNI EN ISO 12100-2 (Ex 292/2) • CEI EN 60204-1 “Sicurezza del macchinario, equipaggiamento elettrico delle macchine. Regole generali” • CEI 17/13-1 Quadri BT.

Le informazioni tecniche sono presso: Idrobios srl Via Sant’Anna 612/B 41122 Modena

Lì, __________________ Firma

(Lusvarghi Paolo)

20

Strada Sant’Anna, 612/B41122 Modena - Italytel. +39 059 451 117fax +39 059 451 210 VAT number and Tax Code [email protected] - www.idrobios.com