91
Rental Guide

Fps xylem rental guide

Embed Size (px)

DESCRIPTION

Xylem pumps available to rent from Filpumps Ltd.

Citation preview

Rental Guide

3

Contents

4 General Guide to Pump Selection

5 Guide to Performance Data

6 Pumping Definitions

7 - 14 2000/BS Series - Drainers

15 - 20 2600 Range

21 2000/BS Series/2600 - Electrical Information

22 - 26 3000/C Series - Sewage

27 - 33 3000/N Series - Sewage

34 - 35 Chopper Pumps

36 - 44 Great and Grey – Sewage

45 ATEX Approved Explosion Proof Submersible

46 Telemetry

47 Electrical Equipment

48 - 49 Soft Start Control Panels - Specification

50 3000 Series - Electrical Information

51 - 55 Godwin CD series

56 - 62 Godwin HL series

63 - 65 Godwin NC series

66 - 68 Godwin Heidra series

69 - 70 Solid Handling - Robot Range

71 - 73 Water Treatment

74 - 77 Mixers

78 - 79 Aeration - Radial Aerators

80 Radial Aerators - Oxygen Transfer Rate

81 Aeration - Flyjet and Hydroejectors

82 Pump Flotation Modules

83 - 84 Hoses and Fittings

85 Friction Loss in Pipe Fittings Chart

86 - 87 Weight Reference Guide

88 - 89 Conversion Factors

90 Flange Sizes

91 - 93 TotalCare

94 - 95 Birkenburn Reservoir Case Study

96 - 97 Mont Cuet Landfill Site Case Study

99 Contact Details

4

General Guide to Pump Selection

Check:-The Electrical Supply available – What Voltage, Single or 3 Phase and the MaximumAmperage. If the Power Supply is inadequate, please ask for details of Generators orconsider using a Flygt Prime Assisted Diesel Pump.

Total Head Requirement – The most important calculation to get right! It is the sumof the Total Static Head (the vertical distance from the Suction Strainer to the point ofDischarge) plus any Friction Loss allowances. When sizing a pump, the critical thingto determine is the Total Generated Head (TGH) requirement.

Calculation:-Static Suction (strainer to the pump) + Static Delivery (from pump to the point ofDischarge) + Friction Loss (resistance incurred by liquid when flowing through hoses)= Total Generated Head.

Dirty Water or Solids Handling?

Use Drainer Submersibles (BS Series) and General Purpose Diesels for Dirty Waterpumping and where particles are relatively small e.g. sand and gravel.

Use Sewage Submersibles (C/N Series) and Solids Handling Diesels for Sewagepumping and where particles are larger e.g. stones and debris.

The Information contained within this document is for guidance only and is accurate to the best ofour knowledge at time of going to print.

Guide to Performance Data

The following curves are QH charts showing the performance of the hydraulic unit atconstant shaft speeds. Q is represented as litres per second, and total head, H, is in metres.

The data represented in this section is for your guidance only. Detailed informationcan be obtained from your local Xylem Sales Engineer.

Head (m)

Flow (l/s)

Head (m)

Flow (l/s)

80

60

Impeller No. of Outlet dia. mm Through Motor rpm AvailableCode vanes CP vers let, mm rating kW versions

252 1 80 Ø52 4.4 2850 CP/CS254 1 80 Ø46 4.4 2850 CP/CS

C, D, H and N Pumps

The power consumption is shown onthe chart. The power consumptionvalues for two selected performanceduty points are shown by plottedstraight lines from the lower to theupper chart. The lower chart andcorresponding table provideperformance data for different impellersused in a high head 3102 pump.Additional charts for LT, MT and SHmodels are shown for each respectivepump type.

BS and D Pumps

The curve is the specified performanceof the impeller selected. The valuesshown are for a BS 2125 pump. Impellercharacteristics are coded as follows:LT=Low head. MT=Medium head.HT=High head. SH=Super High Head.

5

6

Pumping Definitions

Pumping is the addition of energy to a fluid, which is used mainly for the purpose of moving the fluid from one point to another.

Centrifugal Pumps

One which transfers energy to the liquid by means of an impeller; i.e. “a rotatingdevice equipped with suitable vanes”. (The liquid is therefore delivered in acontinuous and uninterrupted flow).

Positive Displacement Pumps

One which transfers energy to a liquid by means of a reciprocating piston, or similardevice, giving an intermittent or “pulsed flow”.

Ejector or Jet Pumps

By mixing a high speed drive medium with a low velocity pumped medium, an energy exchange is achieved converting velocity energy into pressure, giving a continuous flow.

Q= Capacity or VolumeH= Total HeadTotal Head= Static Head + Friction loss head.

Static Head

The head against which the pump must work when the liquid is stationary.

Friction loss head

The head generated by friction of moving liquid, against the walls of the discharge pipes.

P= Pump total pressure in metres.

Net Positive Suction Head (npsh)

Energy from an outside source i.e. static head or atmosphere pressure required to ensure liquid enters the pump volute.

Cavitation

Cavitation occurs when there is insufficient n.p.s.h. i.e., too low a suction pressureinduces cavitation. This causes erosion to the metal surfaces due to the vapourbubble collapsing, allowing the liquid to rush into the subsequent spaces at highvelocity, thus creating a water hammer effect.

7

2000 / BS Series - Bibo Drainers

Introduction

Flygt Type BS - Pumps are suitable for a very broad field of application. They areused for dewatering on construction sites for houses, streets and roads, tunnels androck caverns, harbours and dams, for drainage and ballast pumping in shipyards, fordrainage in the event of flooding in mines and industrial plants, for cooling, cleanwater and raw water supply, water spraying, etc.

The Type BS - Pump is of transportable design and requires no installation. All youneed to do is to lower it into water and start it. There is a type BS pump suitable forall applications - be it for high capacities, high heads, confined spaces or explosive environments.

The Type BS - Impeller is an open or semi-open channel impeller, made of abrasionresistant high chromium steel and designed specifically for handling mediacontaining highly abrasive materials, such as clay, sand and drilling fines etc.

8

2000 / BS Series Bibo Pumps

Can be installed in a variety of applications

The Type BS - Pump can stand directlyon the sump floor

The compact design enables Type BS -Pumps to be used in confined spaces -a 200mm diameter pipe is sufficient forthe slimmest pump

The head generated can be increasedby connecting two or more Type BS -Pumps in series

or can be suspended from a ropeor chain

9

A

B

A

B

A B StrainerOpening

Pump type mm mm mm

BS2052 530 200 5x18BS2066 520 385/405/288 7x21BS2102MT 505 390/430 7x40HT 505 375/390/335 7x40BS2125MT 710 485/515/535 6x50HT 710 465/390 6x50BS2151LT 745 640/655 10x42MT 745 640/655 10x42HT 745 570/590 10x42BS2201Cast IronMT 1200 620 15x45HT 1050 430 10x10AluminiumMT 1253 500 15x45HT 1050 430 10x10BS2250MT 1144 885/912 15x45HT 1144 830 15x45BS2400MT 1250 780 10x10HT 1250 680 10x10BS2610 570 230 7 x 16BS2620 620 275 7 x 16BS2640MT 760 375 8 x 18HT 760 342 8 x 18BS2660MTHT 832 430 9 x 18BS2670MT 955 500 10 x 20HT 955 480 10 x 20

Dimensions

10

BS 2052

A

B

Head (m)

Flow (l/s)

BS 2066

A

B

Head (m)

Flow (l/s)

Motor 2.2 kW, 2800rpmMax. power input 2.8 kWWeight 30kg

Dimensions: A=520mmB=362/375mmHose Size: 75mm

Motor 1 kW, 2700 rpmMax. power input 1.4 kWWeight 18kg

Dimensions: A=530mmB=200mm Hose Size: 50mm

BS 2052 and BS 2066

11

BS 2102 and BS 2125

BS 2102 MT & HT

A

B

Head (m)

Flow (l/s)

A

B

Head (m)

Flow (l/s)

BS 2125 MT & HT

Motor 3.7 kW/ 5.2 kW, 2850 rpmMax. power input 4.5 kW/6.3kWWeight 50kg

Motor MT 8.0 kW, 2800 rpmMax. power input 9.5 kWWeight MT 83kg HT 92kg

Dimensions:A=710mmB=MT 485/515/535mm HT 465mmHose Size: HT 75mm MT 150mm

Dimensions: A=505mm B=MT=395/430mm HT=375/390mm HoseSize: HT 75mm MT 100mm

12

BS 2151 and BS 2201 MT

BS 2151 MT & HT

A

B

Head (m)

Flow (l/s)

BS 2201 MT

A

B

Head (m)

Flow (l/s)Motor 37 kW, 2920 rpmMax.Power input 41 kW Weight MT Aluminium - 280 kg, Cast Iron - 445kg

Dimensions:A=1253mmB=500mmHose Size: 200mm

Dimensions: A=745mmB=MT 640/655mm MT=570/590mmHose Size: HT 100mm LT 150mm

Motor 20 kW, 2900 rpmMax. power input 23 kWWeight 165kg

13

BS 2201 HT and BS 2250

BS 2250 MT & HT

A

B

Head (m)

Flow (l/s)

BS 2201 HT

A

B

Head (m)

Flow (l/s)Motor 37 kW, 2920 rpmMax. power input 41 kWWeight HT Aluminium 240 kg Cast Iron 350kg

Dimensions:A=1050mmB=430mmHose Size: 100mm

Motor 54 kW, 1470 rpmMax. power input 58 kWWeight 540kg

Dimensions:A=1100mmB=950mm Hose Size: HT 150mm MT 200mm MT 250mm

14

BS 2400

BS 2400 MT & HT

A

B

Motor 90 kW, 2970 rpmMax. power input 97 kWOver temperature protection instator windingsWeight MT 900kg HT 985 kg

Dimensions:A=MT 1250mm HT 1251mm B=MT 778mm HT 680mmHose size: HT=100mm MT=150mm

Head (m)

Flow (l/s)

2600/Range Introduction

Introduction

Clearing your worksite of unwanted water is critical to productivity. Flooding meanstime delays, cost overruns and unsafe working conditions. To get to the bottom of any dewatering job, rely on Flygt 2600 pumps.

Undertaking tough dewatering jobs is what the Flygt 2600 series does best. Itensures that you can get on with the work at hand safely and reliably. All this, thanksto extreme portability, automatic operation, easy maintenance, lasting performance.

The Flygt 2600 series is built to last. Radically engineered from the ground up, theserobust dewatering pumps feature innovative hydraulics, durable materials and a practical, ergonomic design. The result is unmatched wear resistance, consistentperformance over time.

Flygt 2600 pumps cover low, medium, high and super-high pressures to handle mostany application for worksites of every size.

15

16

BS 2610 MT 110V Single Phase

0 1 2 3 4 5 6 7 8 10 0

2

4

6

8

10

12

14

Flow (l/s)

Head (m)

243

0

2

4

6

8

10

12

14

16

1820

234

0 2 4 6 8 10 12 14Flow (l/s)

Head (m)

Rated Power 0.85 kW, Weight 21kg

Rated Power 1.2 kW, Weight 21kg

BS 2610 MT 400V 3 Phase

2600 Range

Dimensions: Max. Height=570mmMax. Width=230mm Discharge Ø=2" Strainer Hole: 7x16mm

Dimensions: Max. Height=570mmMax. Width=230mm Discharge Ø=2" Strainer Hole: 7x16mm

17

BS 2620 MT

0

4

8

12

16

20

24

226

0 2 4 6 8 10 12 14 15 Flow (l/s)

Head (m)

0

5

10

15

20

25

30

226

0 5 10 15 20 25 30 35 40 Flow (l/s)

Head (m)

Rated Power 5.6 kW, Weight 51kg

BS 2640 MT

Dimensions: Max. Height=760mmMax. Width=375mm Discharge Ø=4" Strainer Hole: 8x18mm

2600 Range

Dimensions: Max. Height=620mmMax. Width=275mm Discharge Ø=3" Strainer Hole: 7x16mm

Rated Power 2.2 kW, Weight 32kg

18

BS 2640 HT

0

5

10

15

20

25

30

35

40

45

50

257

0 4 8 12 16 20 24 Flow (l/s)

Head (m)

0

5

10

15

20

25

30

35

40

226

0 10 20 30 40 50 60 Flow (l/s)

Head (m)

Rated Power 5.6 kW, Weight 51kg

Rated Power 10 kW, Weight 78kg

BS 2660 MT

2600 Range

Dimensions: Max. Height=832mmMax. Width=430mm Discharge Ø=6" Strainer Hole: 9x18mm

Dimensions: Max. Height=760mmMax. Width=342mm Discharge Ø=3" Strainer Hole: 8x18mm

BS 2660 HT

0

10

20

30

40

50

60

70

251

0 5 10 15 20 25 30 35 Flow (l/s)

Head (m)

0

5

10

15

20

25

30

35

40

45

226

0 20 40 60 80 100 Flow (l/s)

Head (m)

Rated Power 10 kW, Weight 78kg

Dimensions: Max. Height=832mmMax. Width=430mm Discharge Ø=4" Strainer Hole: 9x18mm

Rated Power 18 kW, Weight 141kg

BS 2670 MT

Dimensions: Max. Height=955mmMax. Width=500mm Discharge Ø=6" Strainer Hole: 10x12mm

2600 Range

19

20

BS 2670 HT

0

10

20

30

40

50

60

70

251

0 5 10 15 20 25 30 35 40 45 50Flow (l/s)

Head (m)

Rated Power 18 kW, Weight 141kg

Dimensions: Max. Height=955mmMax. Width=480mm Discharge Ø=4" Strainer Hole: 10x12mm

2600 Range

21

2000/BS Series/2600 - Electrical Information

When two pumps are driven by the same generator, the rating required is 1.5 timesthat indicated for a single pump

Some form of time lag should be connected to prevent both pumps from starting simultaneously, unless the generator has been selected for pumps to start simultaneously.

The Information contained within this document is for guidance only and is accurate to the best of ourknowledge at time of going to print.

BS2052 1.0 110 1 14.0 46 CAP 5

BS2052 1.0 230 1 3.8 17 CAP 5

BS2052 1.0 400 3 2.2 9.9 DOL 7.5

BS2066 2.2 400 3 4.5 26 DOL 20

BS2071 3.0 400 3 6.6 43 DOL 30

BS2075 3.7 400 3 7.1 36 DOL 25

BS2075 5.5 400 3 11.0 50 DOL 35

BS2084 7.5 400 3 13.0 78 DOL 55

BS2102 5.2 400 3 10.0 71 DOL 50

BS2125 8.0 400 3 15.0 125 DOL 90

BS2151 20.0 400 3 35.0 281 ATX 100

BS2201 37.0 400 3 65.0 430 ATX 150

BS2250 54.0 400 3 104.0 590 ATX 450

BS2400 90.0 400 3 148.0 1245 ATX 425

BS2610 0.9 110 1 11.0 38 CAP 5

BS2610 1.2 400 3 2.7 12 DOL 10

BS2620 2.2 400 3 4.7 27 DOL 20

BS2640 5.6 400 3 11.0 48 DOL 35

BS2660 10.0 400 3 19.0 107 DOL 75

BS2670 18.0 400 3 32.0 213 DOL 150

PumpModel

Kw(ShaftPower) PhaseVoltage

FLCAmps

StartingMethod

MinimumGeneratorin Kva toStart/Run

DOLStartingCurrentAMPS

22

Introduction

This series of pumps covers an extensive performance range and can be used in a variety of applications: from pumping sewage in treatment plants and municipalapplications to irrigation, industrial effluent, process water and raw water handling to applications in aquaculture and agriculture.

An extensive range of hydraulic sections, i.e. impellers and volutes, are available to handle the different types of media.

Built-in cooling system on all pumps rated above 9kW. Vanes are at the top of thepump impeller circulate cooling water through a narrow slot around the stator housing.

3000 / C Series - Sewage

Channel Impeller

C - Pumps are equipped with a shrouded, single or multi-vane impeller that runs in a volute. The shape and size of the impeller is designed to minimise clogging,which makes this pump ideal for wastewater applications.

Nevaclog®

The Nevaclog® impeller is designed specially for smaller C - Pumps. Nevaclog® hasexcellent flow passing properties, because all the parts that might cause cloggingwhen water is flowing at low speed through the impeller channel have beeneliminated. This, coupled with the volute’s design is what enables wastewater to flow freely.

3000 / C Series - Sewage

23

ø D

C

C

A

B

A

B

C - Pumps

CS3085 MT 480 603 350 75

CS3085 HT 450 512 320 75

CS3085 LT 1 638 660 380 100

CS3085 LT 2 638 655 400 100

CS3102 LT/150 720 718 400 150

CS3102 LT/100 640 718 400 100

MT 640 703 383 100

HT 640 698 340 100

CS3127 LT 870 776 439 200

MT/150 780 761 430 150

MT/100 700 761 406 100

HT (curve 480-485) 700 722 407 100

HT (curve 250-259) 700 714 380 80

HS 550 741 403 100

CS3152 LT 1150 1327 576 250

CS3152 MT 900 1228 530 200

CS3152 HT/100 773 1190 530 100

CS3152 HT/150 845 1190 530 150

HS3152 845 1190 490 150

CS3201 LT 1417 1598 1000 250

CS3201 MT 1150 1442 576 200

CS3201 HT 1050 1453 576 150

HS3201 1050 1453 576 150

CS3300 LT 1675 1920 1000 250

CS3300 MT 1624 1915 1000 200

CS3300 HT/200 1494 1827 1000 200

CS3300 HT/150 1443 1827 1000 150

FS3085 605 535 317 100

FS3102 660 619 315 100

FS3127 750 693 415 100

FS3152 LT 735 1055 465 100

FS3152 HT 710 1035 440 100

NS3301 1438 1680 1000 250

Pump type A B C øD

C 3085 MT and C 3102 MT/HT

Impeller No. of Outlet dia. mm Through Motor rpm AvailableCode vanes CP vers let, mm rating kW versions

430 1 100 Ø76 3.1 1400 CP/CS/MT252 1 80 Ø52 4.4 2850 CP/CS/MT

Flow (l/s)

Head (m)

00 10 20 30 40

2

4

6

8

10

12

14

16

Flow (l/s)

Head (m)

00 10 20 3025155 35

5

10

15

20

25

30

Flow (l/s)

Head (m)

00 5 10 15 20 25 30 35

2

4

6

8

10

12

C 3085 MT

C 3102 MT/HT

Discharge size: 75mm/100mm Weight: 116kgHeight: 718mm Maximum width: 640mmMotor rating: 3.1kW

Flow (l/s)

Head (m)

00 4 8 12 16 18

5

10

15

20

25

30

Discharge size: 75mm Weight: 71kg Height: 655mm Maximum width: 638mmMotor rating: 2.0kW

24

Impeller No. of Outlet dia. mm Through Motor rpm AvailableCode vanes CP vers let, mm rating kW versions

432 1 100 Ø76 2.0 1400 CP/CS252 1 80 Ø40 2.4 2840 CP/CS

C 3127 and C 3152

Flow (l/s)

Head (m)

00 10 20 30 40 50 60

5

10

15

20

25

30

35

40

Flow (l/s)

Head (m)

00 20 40 60 80

4

8

12

16

20

24

C 3127

Discharge size: 100/150mm Weight: 175kgHeight: 761mm Maximum width: 780mmMotor rating: 5.9/7.4kW

Flow (l/s)

Head (m)

00 50 100 150 200 250 300

2

6

4

8

10

Impeller No. of Outlet dia. mm Through Motor rpm AvailableCode vanes CP vers let, mm rating kW versions

616 2 250 102x102 8.8 950 CP/CT/CS430 1 250 100x115 13.5 1450 CP/CT/CS452 HT 1 150 76x76 13.5 1450 CP/CT/CS265 SH 1 100 40x40 150 2920 CP/CT/CS

Discharge size: 150/200mm Weight: 426kgHeight: 1228mm Maximum width: 900mmMotor rating: 13.5kW

Flow (l/s)

Head (m)

00 20 40 60 80 100 120

5

10

15

20

25

30

35

C 3152

25

Impeller No. of Outlet dia. mm Through Motor rpm AvailableCode vanes CP vers let, mm rating kW versions

430 1 100/150 100x110 5.9 1450 CP/CS250 HT 1 80 Ø58 7.4 2900 CP/CS

26

C 3201 and C 3300

C 3201

Impeller No. of Outlet dia. mm Through Motor rpm AvailableCode vanes CP vers let, mm rating kW versions

630 1 200 144x120 22 965 CP/CT/CS456 1 150 Ø100 30 1250 CP/CT/CS

Flow (l/s)

Head (m)

00 40 80 120 160 200 240

5

10

15

20

25

30

35

Flow (l/s)

Head (m)

00 20 40 60 80 100 120 140

51015202530

50

4045

35

Discharge size: 200/250mm Weight: 1218kgHeight: 1915mm Maximum width: 1624mmMotor rating: 54/44kW

Discharge size: 200/250mm Weight: 588kgHeight: 1442mm Maximum width: 1150mmMotor rating: 30/22kW

Impeller No. of Outlet dia. mm Through Motor rpm AvailableCode vanes CP vers let, mm rating kW versions

632 1 250 Ø190 44 970 CP/CT/CS452 1 150 90x96 54 1450 CP/CT/CS620 3 300 Ø102 44 975 CP/CT/CS

MT & HT

Flow (l/s)

Head (m)

00 100 200 300 400 500 600

5

10

15

20

25

30

35

Flow (l/s)

Head (m)

00 20 40 60 80 100 120 140 160

10

20

30

40

50

60

70

C 3300

N Pump Technology

Sustained high efficiency for wastewater handlingWith its unique semi-open, self-cleaning impeller, the N-pump series can handlefluids with high concentrations of fibrous material, whilst still maintaining a high levelof pumping efficiency over long duty periods. The special relief groove in the volutereduces the risk of clogging by creating a self-cleaning flow path through the pump.

27

3000/N Series - Sewage

N Series Pumps

N series pumps are available, contact your local Flygt Rental Centre for curve details:N 3085, N 3102, N 3127, N 3153, N 3171, N 3202, N 3301

Adaptive N-impellers

The Adaptive N-hydraulics further improves the self-cleaning characteristics of N-technology with unmatched clog-free performance. This is achieved through theunique axial movement of the Adaptive N-impeller.

The Adaptive N-impeller is designed to move axially upwards when needed,allowing the most bulky of rags and toughest of debris to pass through smoothly.After the debris has passed, the hydraulic pressure returns the impeller to its originalposition.

The axial movement of this hydraulic reduces stress on the shaft, seals, and bearings,thereby extending their lifespan. Ultimately clog-free performancerequires almost none, or at the very most, simple maintenance and servicing. All inall, the Adaptive N-hydraulics is your assurance of highly economical and reliablepumps that give you peace of mind.

28

N 3085 MT and N 3102 MT

Flow (l/s)

Head (m)

N 3085 MT

Discharge size: 75mmHeight: 655mmMotor rating: 2.0kWWeight: 71kgMaximum width: 450mm

Impeller No. of Outlet dia. mm Motor rpm AvailableCode vanes NP vers rating kW versions

460 2 80 2.0 1400 NP/NS/NT

Flow (l/s)

Head (m)

N 3102 MT and SH

Discharge size: 80mm/100mmHeight: 705mmMotor rating: 3.1/4.2kWWeight: 116kgMaximum width: 610mm

Impeller No. of Outlet dia. mm Motor rpm AvailableCode vanes NP vers rating kW versions

461 MT 2 100 3.1 1440 NP/NS255 SH 2 80 4.2 2890 NP/NS

29

N 3127 and N 3153 MT

Flow (l/s)

Head (m)

N 3127 MT and HT

Impeller No. of Outlet dia. mm Motor rpm AvailableCode vanes NP vers rating kW versions

437 MT 2 100/150 5.9 1450 NP/NS/NT487 HT 2 100 5.9 1450 NP/NS/NT

Discharge size: 100/150mmHeight: 765mmMotor rating: 5.9kWWeight: 170kgMaximum width: 725mm

N 3153 MT

Flow (l/s)

Head (m)

Impeller No. of Outlet dia. mm Motor rpm AvailableCode vanes NP vers rating kW versions

431 2 150 13.5 1455 NP/NT/NS433 2 150 13.5 1455 NP/NT/NS

Discharge size: 150mmHeight: 1068mmMotor rating: 13.5kWWeight: 252kgMaximum width: 834mm

N 3153 HT/SH and N 3171 LT/MT/HT

30

Flow (l/s)

Head (m)

N 3153 HT/SH

Discharge size: 80/100mmHeight: 1052mmMotor rating: 13.5/15.0kWWeight: 242kgMaximum width: 763mm

Impeller No. of Outlet dia. mm Motor rpm AvailableCode vanes NP vers rating kW versions

611 LT 2 250 15.0 965 NP/NS/NT431 MT 2 150 22.0 1460 NP/NS/NT452 HT 2 100 22.0 1460 NP/NS/NT

Flow (l/s)

Head (m)

Discharge size: 100/250mmHeight: 1299mmMotor rating: 15/22kWWeight: 460kgMaximum width: 1151mm

Impeller No. of Outlet dia. mm Motor rpm AvailableCode vanes NP vers rating kW versions

451 HT 2 100 13.5 1455 NP/NT/NS272 SH 2 80/100 15.0 2910 NP/NT/NS

N 3171 LT MT and HT

N 3171 SH and N 3202 LT/MT/HT

31

Flow (l/s)

Head (m)

0 10 20 30 40 500

10

20274

30

40

50

60

70

80

Flow (l/s)

Head (m)

Discharge size: 150/300mmHeight: 1571mmMotor rating: 22/45kWWeight: 900kgMaximum width: 1439mm

N 3171 SH

N 3202 LT MT and HT

Discharge size: 100mmHeight: 1179mmMotor rating: 22kWWeight: 366kgMaximum width: 884mm

Impeller No. of Outlet dia. mm Motor rpm AvailableCode vanes NP vers rating kW versions

274 LT 2 108 22.0 2925 NP/NS/NT

Impeller No. of Outlet dia. mm Motor rpm AvailableCode vanes NP vers rating kW versions

617 LT 2 250 22.0 970 NP/NS/NT433 MT 2 200 30.0 1475 NP/NS/NT454 HT 2 150 45.0 45.0 NP/NS/NT

32

N 3301 LT/MT 55kW

Flow (l/s)

Head (m)

0 50 100 150 200 250 300 350 400Flow (l/s)

Head (m)Discharge size: 250mm

Height NS: 1705mm

Motor rating: 55kW

Weight: 1110kg

Maximum width NS: 1439mm

Impeller No. of Outlet dia. mm Motor rpm AvailableCode vanes NS vers rating kW versions

620 LT 2 250 55 985 NP/NT/NS/NZ630 MT 2 250 55 985 NP/NT/NS/NZ632 MT 2 250 55 985 NP/NT/NS/NZ

N 3301 LT and MT 55kW

33

N3301 HT 55kW/70kW

Impeller No. of Outlet dia. mm Motor rpm AvailableCode vanes NS vers rating kW versions

454 2 150 70 1475 NP/NT/NS/NZ454 HT 2 150 55 1400 NP/NT/NS/NZ456 HT 2 150 55 1400 NP/NT/NS/NZ458 HT 2 150 55 1400 NP/NT/NS/NZA Selection of impellers are available on request; also Variable Frequency Drive Starters

N 3301 HT 55 kW

Flow (l/s)

Head (m)

N 3301 454 HT Impeller 70 kW VFD Curves

Discharge size: 150mm

Height NS: 1641mm

Motor rating: 55/70kW

Weight: 920kg

Maximum width NS: 1242mm

0 20 40 60 80 100 120 140 160

80

70

60

50

40

30

20

10

0

Flow (l/s)

Head (m)

Chopper Pumps

34

Introduction

Chopper pumps with N Impeller Technology

Flygt Chopper pumps have the unique patented N Impeller along with a Hard Ironchopper ring which drastically reduces the risk of clogging. Rugged, wear resistant andself cleaning, it cuts through solids without clogging or sacrificing pump efficiency.

The Flygt Chopper pump range brings to an end troublesome and costly cloggingwith its heavy-duty and highly dependable chopping abilities. By adding the chopperfunction to the well proven Flygt N-pump, outstanding performance in heavy dutyapplications has been achieved. This new pump design has undergone extensivetesting in the field. The results from these tests show considerably fewer runningproblems and considerably lower energy consumption.

Typical applications: • Agriculture • Aquaculture • Food processing • Pulp and paper • Harsh wastewater facilities.

Impeller No. of Outlet dia. mm Motor rpm AvailableCode vanes NP vers rating kW versions

428 MT 2 100/150 4.7 1455 NP/NS/NT/NZ

N 3127 Chopper MT and HT

Discharge size: 100/15mmHeight NS: 765mmMotor rating: 4.7kWWeight: 170kgMaximum width NS: 725mm

Flow - [l/s]70605040302010

00

2

4

6

8

10

12

14

25

Chopper Pumps

35

Flow (l/s)

Head (m)

Impeller No. of Outlet dia. mm Motor rpm AvailableCode vanes NP vers rating kW versions

431 MT 2 150 13.5 1455 NP/NS/NT451 HT 2 100 13.5 1455 NP/NS/NT

Discharge size: 100/150mmHeight NS: 1068mmMotor rating: 13.5kWWeight: 252kgMaximum width NS: 763mm

Impeller No. of Outlet dia. mm Motor rpm AvailableCode vanes NP vers rating kW versions

431 MT 2 150 22.0 1460 NP/NS/NT451 HT 2 100 22.0 1460 NP/NS/NT

Discharge size: 100/150mmHeight NS: 1225mmMotor rating: 22.0kWWeight: 362kgMaximum width NS: 884mm

451

431

Flow (l/s)

Head (m)

N 3153 Chopper MT and HT

N 3171 Chopper MT and HT

36

Great and Grey - Sewage

After revolutionizing the market for small and midrange wastewater pumps, the FlygtN Pumps are now available in the larger units.

Introduction

• Incorporating the N Pump technology the potential for blockage issubstantially reduced

• Due to sustained efficiency, energy costs can be cut by up to 50%• Heads of up to 90mts achieved• Flows in excess of 700l/s

• General by-pass over-pumping• Pump replacement• Application proving• Storm water handling• Industrial effluent handling• Irrigation

Pumps from 90 to 250kW available to rent in NP/NS/NT and NZ build (see Page 37).Ex units available on request.

Applications

37

N and C Installation Method

Flygt centrifugal pumps are designed to pumpwastewater containing solids and fibres insuspension. The pump can also be used forpumping raw water.

Liquid temperature: max 40ºC (105ºF) Liquid density: max 1100 kg/m3

The pH of thepumped liquid: 6 - 11Depth of immersion: max 20 m (65 ft)

For pumping in an explosive or flammableenvironment the pump can be ATEX certified.

The Flygt pump is fully submersible, compactand easy to install. It is available in four versions,depending of the type of installation:

C/NP: This system with guide bars and dischargeconnection permits automatic connection of thepump to the discharge line. The pump can belifted up for inspection without anyone having toenter the sump. The pump works completely orpartially submerged under water.

C/NS: A transportable pump designed foroperating completely or partially submerged inthe pump liquid. It is equipped with base standand hose connection.

C/NT: The pump is installed vertically dry on abase stand and connected directly to the inletand outlet lines. The submersible design of thepump prevents damage in the event of flooding.

C/NZ: The pump is installed Horizontally dry on abase stand and connected directly to the inletand outlet lines. The submersible design of thepump prevents damage in the event of flooding.

For other applications, contact your local FlygtRental Centre for information.

P

S

T

Z

38

N3315 105kW

N3315 105kW 451HT 440mm

0

20

0 20 40 60 80 100 120 140 160

40

60

80

100

50Hz

45Hz40Hz

35Hz

POWER LIMIT

451HT

Flow (l/s)

Head (m)

Impeller No. of Outlet dia. mm Motor rpm AvailableCode vanes NS vers rating kW versions

451HT 3 150 105 1480 NP/NS/NT/NZ

Rated Power: 105kW

Weight: 1220kg

Dimensions: Max. Height=1992mmMax. Width=1450mm

39

N3231 85kW / 105kW

00

10

20

30

40

50

60

50 100 150 200 250 300 350

50Hz

45Hz40Hz

35Hz

POWER LIMIT

Flow (l/s)

Head (m)

N3231 85kW 480/360mm

Rated Power: 85kW

Weight: 1380kg

Dimensions: Max. Height=2060mmMax. Width=1570mm

Impeller No. of Outlet dia. mm Motor rpm AvailableCode vanes NS vers rating kW versions

480-360 3 200 85 1475 NP/NS/NT/NZ

N3231 105kW 480/400mm

0 50 100 150 200 250 300

POWER LIMIT

50Hz

45Hz

40Hz

35Hz

0

10

20

30

40

50

60

70

Flow (l/s)

Head (m)

Impeller No. of Outlet dia. mm Motor rpm AvailableCode vanes NS vers rating kW versions

480-400 3 200 105 1480 NP/NS/NT/NZ

Rated Power: 105kW

Weight: 1590kg

Dimensions: Max. Height=2060mmMax. Width=1570mm

N3231 125kW / 170kW

40

0 50 100 150 200 250 300 350 4000

10

20

30

40

50

60

50Hz45Hz40Hz

35Hz

Flow (l/s)

Head (m)

0 50 100 150 200 250 300 350

50Hz

45Hz

40Hz

35Hz

0

20

40

60

80

100

Flow (l/s)

Head (m)

POWER LIMIT

Impeller No. of Outlet dia. mm Motor rpm AvailableCode vanes NS vers rating kW versions

470-490 3 200 170 1480 NP/NT/NS/NZA Selection of impellers are available on request; also Variable Frequency Drive Starters

Impeller No. of Outlet dia. mm Motor rpm AvailableCode vanes NS vers rating kW versions

470-370 3 200 125 1450 NP/NT/NS/NZ

N 3231 170 kW 470/490mm

N 3231 125 kW 470/370mm

Discharge size: 200mm

Height NS: 2185mm

Motor rating: 125kW

Weight: 1760kg

Maximum width NS: 1390mm

Rated Power 170kW

Weight 1760kg

Dimensions: Max. Height=2305mmMax. Width=1570mm

41

N3231 170kW / 215kW

0 50 100 150 200 250 300 350 4000

10

20

30

40

50

60

70

80

90

100

POWER LIMIT

50Hz

45Hz

40Hz

35Hz

Flow (l/s)

Head (m)N3231 170kW 480/490mm

00

50 100 150 200 250 300 350 400

POWER LIMIT

35Hz

40Hz

45Hz

50Hz

102030405060708090

100110

Flow (l/s)

Head (m)

N3231 215kW 480/490mm

Rated Power 170kW

Weight 1760kg

Dimensions: Max. Height=2305mmMax. Width=1570mm

Impeller No. of Outlet dia. mm Motor rpm AvailableCode vanes NS vers rating kW versions

480-490 3 200 170 1480 NP/NS/NT/NZ

Rated Power 215kW

Weight 1910kg

Dimensions: Max. Height=2305mmMax. Width=1570mm

Impeller No. of Outlet dia. mm Motor rpm AvailableCode vanes NS vers rating kW versions

480-490 3 200 215 1485 NP/NS/NT/NZ

N3312 100kW / 180kW

42

Impeller No. of Outlet dia. mm Motor rpm AvailableCode vanes NS vers rating kW versions

670-450 3 300 100 985 NP/NT/NS/NZ670-545 3 300 180 990 NP/NT/NS/NZA Selection of impellers are available on request; also Variable Frequency Drive Starters

0 100 200 300 400 500 600 7000

5

10

15

20

25

30

35

50Hz45Hz

40Hz35Hz

40

Flow (l/s)

Head (m)

N 3312 180 kW 670/545mm

Rated Power: 100kW

Weight: 1975kg

Dimensions: Max. Height=2240mmMax. Width=1650mm

Rated Power: 180kW

Weight: 2275kg

Dimensions: Max. Height=2975mmMax. Width=1875mm

N 3312 100 kW 670/450mm

0 100 200 300 400 500 600 7000

10

20

30

40

50

60

50Hz45Hz

40Hz35Hz

Flow (l/s)

Head (m)

43

N3312 / N3356

N3312 250kW 670/585mm

0 100 200 300 400 500 600 7000

10

20

30

40

50

60

70

50Hz45Hz

40Hz35Hz

Flow (l/s)

Head (m)

Rated Power: 250kW

Weight: 3125kg

Dimensions: Max. Height=2975mmMax. Width=1875mm

Impeller No. of Outlet dia. mm Motor rpm AvailableCode vanes NS vers rating kW versions

670-585 3 300 250 990 NP/NS/NT/NZ

0 100 200 300 400 500 600 700

VFD Curves

0

5

10

15

20

25

30

35

40

50Hz45Hz

40Hz35Hz

Flow (l/s)

Head (m)

N3356 90 kW 670/470

Impeller No. of Outlet dia. mm Motor rpm AvailableCode vanes NS vers rating kW versions

670-470 3 350 90 985 NP/NT/NS/NZ

Discharge size: 350mm

Height NS: 2400mm

Motor rating: 90kW

Weight: 2200kg

Max. Width=1875 mm

44

N3356 / N3400

0 100 200 300 400 500 600 7000

5

10

15

20

25

30

35

40

50Hz45Hz

35Hz40Hz

Flow (l/s)

Head (m)N3356 100kW 670/475mm

Impeller No. of Outlet dia. mm Motor rpm AvailableCode vanes NS vers rating kW versions

670-475 3 350 100 985 NP/NT/NZ

Rated Power: 100kW

Weight: 1750kg

Dimensions: Max. Height=2275mmMax. Width=1900mm

N3400 250kW 670/575mm

Rated Power: 250kW Weight: 3750kgDimensions: Max. Height=3428mmMax. Width=1900mm

Impeller No. of Outlet dia. mm Motor rpm AvailableCode vanes NS vers rating kW versions

670-575 3 400 250 990 NP/NT/NZ

00

10

20

30

40

50

60

100 200 300 400 500 600 700 800 900 1000

POWER LIMIT

50Hz45Hz

40Hz35Hz

Flow (l/s)

Head (m)

45

Many of the Flygt range of pumps can be provided certified for use in Zone 1 andZone 2 hazardous areas.

Pumps are certified: EEx d IIB T4 or EEx d IIB T3

According to the pump model:

ATEX category II 2G

The pumps are constructed and approved in accordance with:

BS EN 50018, BS EN 50019, BS EN 13463-1, BS EN 60079-1, BS EN 60079-7

As appropriate according to the pump model.

For availability of ‘Ex’ units and any other technical assistance contact your nearestFlygt Rental Centre.

Explosion Pumps Available:

• Copies of the relevant ‘Ex’ certification can be made available on request. • The pumps are maintained in accordance with BS EN 60079 Part 19. • Before any Flygt ‘Ex’ pump is made available for Rental all parts, flame pathsetc; are checked and recorded using regularly calibrated instruments andprocedures in accordance with BS EN 60079-19

B Pumps C & N Pumps Mixers(ring forconfirmation)

2201 3085 46202400 3102 4630

3127 46403153 46503171 4660320233013231331233563400

ATEX Approved Explosion Proof Submersible Pumps

46

Telemetry

Mobile Telemetry & Alarms

Our Rental team is able to call upon the expertise of the Monitoring and ControlDivision of Xylem Water Solutions UK Ltd, and has many ways of monitoring theoverpumping installation, ranging from a simple “pay as you go” GSM alarm unitcapable of sending text messages to nominated numbers, to the D716x DynamicLogic Telemetry Outstation.

Flygt D716x Telemetry Alarm Unit

The Flygt D716x is a remote telemetry outstation/alarm unit utilising the mobiletelephone network or fixed PSTN telephone line.

This adaptable unit can monitor and be programmed to deliver an SMS textmessage to a number of mobile phones. The text message content is fullyprogrammable and can uniquely identify the problem or fault. The system iscompatible with all the major Telephone networks on 'Contract' or 'Pay As You Go'.

On larger installations for municipal Water Companies, The D716x is capable ofconnecting directly to an existing Telemetry Master Station.

The D716x Telemetry unit can be powered by different sources depending upon siteconditions. It can use alkaline batteries that power the unit for up to 7 years,depending on usage and temperature conditions, or is available in a dc-poweredconfiguration with an internal battery backup of up to 1 year.

47

Electrical Equipment

We specialise in electrical submersible pumps, therefore, it is logical that we are theexperts when it comes to the starter and controls that are required for a temporary pumping installation. From a simple single phase starter to a complexmulti pump 3 phase control panel, Rental Engineers are available to give advice onall aspects of electromotive power.

Our Rental team carry a comprehensive range of starters, isolators, controlequipment, alarm and monitoring devices. Also, sufficient cable to suit day to dayusage is stocked both at Nottingham and at all Rental Depot locations. For the largerand more complex installations we are able to select and supply the appropriateextension cables and junction boxes to connect the pump to the control panel. We can also supply ATEX Certified “Ex” junction boxes and cables glands for use in hazardous areas. If level regulators (floats) are used as the level control we cansupply the required I/S protection relays.

Variable Frequency Drives and Soft Start Units

Variable Frequency Drives are available to drive pump units from 10.0kW to200.0kW. The drives provide economical and intelligent pump control and can be configured for running wastewater pumps. With the intelligent VFD you canexpect all the advantages of speed regulation, plus top pumping efficiency.The 10.0kW to 55.0kW drives are IP54 rated and are suitable for use outdoors anddo not need an additional weather protective enclosure. The 200kW drives are available for indoor use or housed in a lockable mobile MotorControl Centre, complete with heating, ventilation, a distribution board is fitted alongwith internal lighting. 200.0kW is not the ceiling for the supply of VFD control panels,our Rental division have supplied a 400.0kW in its own Mobile MCC.

Also available is a range of Soft Start units for the smaller pumps that require simplebut efficient motor control.

48

Specification:• IP54 Zintex Panel• Rain canopy• Load break door interlocked isolator• Soft starter• Special wide ranging overload unit to protect different size pumps

• Earth leakage protection.• Hand/auto switch.• Door mounted alphanumeric keypad showing run & trip conditions and also containing – stop/reset-start buttons, Hand or auto LED’s, running LED and flashing tripped LED.

• Door mounted emergency stop (also to terminals)• Thermal Switch or Klixon trip circuit• Analogue output related to motor current• Inter-panel interlock system• Lifting hook• Motor & control connections wired to terminals• 12vdc control for floats• 24vdc , 100ma for optional alarm. • 24vdc , 500ma for optional ultrasonic unit• 24vac power supply customer use

The Heart of the Panel• Designed and manufacturedespecially for Rental from Xylem

• Unique wide ranging overload• Simple kilowatt selection willset up the overload protection

• Built in earth leakage• Thermal Switch or Klixon

Digital Display• Kilowatt selected• Running amps• Hand, auto, running and tripped led• Start and stop pushbutton• Last eight fault history

Soft Start Unit - 1.0 - 15kW

49

Specification :• IP54 free standing panel • Load break door interlocked isolator• Rain canopy• Torq-master 2000 soft starter• Motor output hard wired to 3 x 70mm stud terminals• Main contactor• By-pass contactor• Door mounted keypad (hand control)• 24v ac control system• Float switch control (hard wired)• Emergency stop circuit• Hand/auto selector switch• Remote connection via terminals (auto control)• Standard ‘t’ bar locking system• Lifting bar with hook• Earth leakage protection• Motor Thermal Switch or Klixon hard wired toterminals• Extra relay for telemetry – wired to terminals• Terminals for panel interlocking system• 24vdc , 100ma for optional alarm• 24vdc , 500ma for optional ultrasonic unit

The Heart of the Panel • Soft start unit • Pin locked menu• Adjustable pump range by amps• Adjustable too many starts protection• Float less control• Thermal Switch or Klixon connections• Electronic overload• Under load trip• Electronic shear pin

Information• Motor current• Ambient temperature• RMS Volts• Run hours• Service time indication (for the motor)• Motor status• Printable 1000 event data log

Soft Start Unit - 15 - 90kW

3000 Series - Electrical Information

3085 1.3 400 3 3.1 19 DOL 153085 2.0 400 3 4.5 19 DOL 153085 2.4 400 3 4.7 28 DOL 203102 3.1 400 3 6.9 33 DOL 253102 4.2 400 3 8.3 72 DOL 503127 4.7 400 3 9.6 56 DOL 403127 5.9 400 3 12.0 77 DOL 553127 7.4 400 3 14.0 114 DOL 803152 - 4 Pole 13.5 400 3 27.0 162 ASD 403152 - 2 Pole 15.0 400 3 28.0 229 ASD 553153 7.5 400 3 16.0 91 ASD 253153 9.0 400 3 19.0 107 ASD 253153 11.0 400 3 24.0 132 ASD 353153 - 4 Pole 13.5 400 3 28.0 150 ASD 353153 - 2 Pole 15.0 400 3 27.0 213 ASD 503170 15.0 400 3 31.0 210 ASD 503171 22.0 400 3 41.0 248 ASD 603201 30.0 400 3 56.0 365 ASD 853202 37.0 400 3 66.0 460 ASD 1103202 45.0 400 3 82.0 605 ASD 1503300 44.0 400 3 82.0 515 ATX 1503300 54.0 400 3 100.0 535 ATX 1503301-6 Pole LT 55.0 400 3 113.0 660 ATX 2253301-4 Pole MT 55.0 400 3 103.0 435 ATX 1503301 70.0 400 3 132.0 565 ATX 1953315 HT 105.0 400 3 199.0 1105 VFD 2103231 - 4 Pole 85.0 400 3 159.0 710 VFD 1703231 - 4 Pole 105.0 400 3 200.0 955 VFD 2103231 - 4 Pole 125.0 400 3 234.0 1525 VFD 2453231 - 4 Pole 170.0 400 3 300.0 2020 VFD 3153231 - 4 Pole 215.0 400 3 395.0 2945 VFD 4153312 - 6 Pole 100.0 400 3 202.0 1150 VFD 2103312 - 6 Pole 180.0 400 3 360.0 2215 VFD 3753312 - 6 Pole 250.0 400 3 465.0 2645 VFD 4853356 - 6 Pole 90.0 400 3 185.0 1160 VFD 1953356 - 6 pole 100.0 400 3 202.0 1150 VFD 2103400 - 6 Pole 250.0 400 3 465.0 2645 VFD 485

PumpModel

Kw(ShaftPower) Voltage Phase

FLCAmps

DOLStartingCurrentAMPS

StartingMethod

MinimumGeneratorin Kva toStart/Run

Solid Handling Products

When two pumps are driven from the same generator, the rating required is 1.5times that indicated for a single pump.

Some form of time lag should be connected to prevent both pumps from startingsimultaneously, unless the generator has been selected for multiple pumps to startsimultaneously.

The Information contained within this document is for guidance only and is accurate to the best of ourknowledge at time of going to print.

50

GodwinIn 2010 Xylem acquired Godwin Pumps, bringing with them over 100 years of experience in the design, manufacture, and supply of diesel pumps. GodwinPumps is renowned for quality, reliability, and long life.

Today, the product range is used throughout the world, in construction, industry, oilrefineries, chemical plants, mines, specialist offshore pumping, irrigation and waterdistribution.

Our Rental division now has access to Godwin’s range of automatic self-primingpumps adding an additional and wider range of Diesel driven Dri - Prime® pumps.The new Godwin pumps can be skid or trailer mounted for use in mobileapplications which can provide exceptional energy efficiency and a significantlyreduced clogging capability.

Godwin CD seriesThe Godwin CD range is ideal for high volume, medium head pumping and is capable of handling large solids.

Godwin HL seriesThe Godwin HL range is ideal for medium volume, high head pumping and is alsocapable of handling large solids-handling.

Godwin CD, HL, Heidra and NC series pumps are now available to rent from Xylem.

All models are available trailer mounted for safe on site transportation or with a skidbase. Cast Iron pump end construction, and sound attenuated enclosures.

3000 rpm

2600 rpm

2200 rpm

1800 rpm

1400 rpm

Minimum capacitylimitation

Maximum capacitylimitation

Hea

d (m

etre

s)

Flow

m³/hr

l/s

00

5

10

15

20

25

30

35

40

45

10 20 30 40 50 60 70 80 90 1000 2.5 5.5 8.5 12 14 17 19.5 22.5 25 28

CD80D Dri-Prime®Hush-Pac

The CD80M can handle solids up to 40mm in diameter. Allows for dry runningfor prolonged periods whileautomatically priming and repriming.This makes it an extremely effectivepump, suitable for both slurry, cleanwater applications as well as smalldewatering and bypass applications.

Godwin CD series

Overalldimensions

Length1621mm

Width853mm

Height1333mm

EngineOption

Kubota Z482

Suction connection 80 mm

Delivery connection 80 mm

Max capacity 65 m³/hr

Max Head 15 metres

Max Solids 40 mm

Max Suction Lift 8.5M

Wet Weight 725kgs

Impeller diameter 166 mm

Max working pressure 4.0 bar

Max operating speed 2000 rpm

Engine Kubota Z482

CD80M Kubota Z482

52

Godwin CD series

2200 rpm

2000 rpm

1800 rpm

1600 rpm

1400 rpm

1200 rpm

Minimum capacitylimitation

Maximum capacitylimitation

m³/hr

l/s

00

5

10

15

20

25

30

35

40

20 40 60 80 100 120 140 160 180 200 220 2400 5.5 12 17 22.5 28 33 39 44.5 50 55.5 66.562

Hea

d (m

etre

s)

Flow

CD100M Dri-Prime® Hush-Pac

Able to perform in the toughest conditions,the CD100M can handle solids up to 45 mmin diameter. Allows for dry running forprolonged periods while automaticallypriming and repriming. This makes it anextremely effective pump, suitable for bothslurry, clean water, sewer bypass and generaldewatering and many other applications.

Overalldimensions

Length1940mm

Width1050mm

Height1500mm

Suction connection 100 mm

Delivery connection 100 mm

Max capacity 200 m³/hr

Max Head 29 metres

Max Solids 45 mm

Max Suction Lift 8.5M

Wet Weight 1168kgs

Impeller diameter 220 mm

Max working pressure 3.8 bar

Max operating speed 2000 rpm

Engine Perkins 403D-15

CD100M Perkins 403D-15

EngineOption

Perkins 403D-15

53

Godwin CD series

m³/hr

l/s

00

5

10

15

20

25

30

35

40

50

45

50 100 150 200 250 300 350 400 450 550500

0 14 28 41.5 55.5 69 83.5 97 111 125 139 153

Hea

d (m

etre

s)

Flow

2200 rpm

2000 rpm

1800 rpm

1600 rpm

1400 rpm

1200 rpm

Minimum capacitylimitation

Maximum capacitylimitation

CD150M Dri-Prime®Hush-Pac

Able to perform in the toughestconditions, the CD150M can handlesolids up to 75 mm in diameter. Allowsfor dry running for prolonged periodswhile automatically priming andrepriming. This makes it an extremelyeffective pump, suitable for both slurryand clean water applications. Thepowerful CD150M has proven itself apump of choice for contractors, localauthorities, industrial andenvironmental companies.

Overalldimensions

Length2190mm

Width1050mm

Height1500mm

Suction connection 150 mm

Delivery connection 150 mm

Max capacity 329 m³/hr

Max Head 19 metres

Max Solids 75 mm

Max Suction Lift 8.5M

Wet Weight 1403kgs

Impeller diameter 260 mm

Max working pressure 4.8 bar

Max operating speed 1500 rpm

Engine Perkins 404D-22

CD150M Perkins 404D-22

EngineOptions

Perkins 404D-22

Perkins 1104D-44TA

54

Godwin CD series

CD300M Dri-Prime®Hush-Pac

The CD300M can handle solids up to95 mm in diameter. This makes it anextremely effective pump, suitable forboth slurry and clean waterapplications. The powerful CD300Mhas proven itself a pump of choice formines, quarries and many other highcapacity applications.

Suction connection 300 mm

Delivery connection 300mm

Max capacity 1380m³/hr

Max Head 54 metres

Max Solids 95 mm

Max Suction Lift 8.5M

Wet Weight 6620kgs

Impeller diameter 362 mm

Max working pressure 6.0 bar

Max operating speed 1800 rpm

Engine Caterpillar C9

CD300M Caterpillar C9

1800 rpm

1700 rpm

1600 rpm

1500 rpm

1400 rpm

1300 rpm

Minimum capacitylimitation

Maximum capacitylimitation

m³/hr

l/s

00

10

20

30

40

50

60

70

100 300200 400 500 600 700 1000900800 1100 1200 1300 14000 28 83.555.5 111 139 166.5 194 278250222 305.5 333 361 388

Hea

d (m

etre

s)

Flow

Overalldimensions

Length4850mm

Width2065mm

Height2545mm

EngineOptions

Perkins 1106D-E66TA

Caterpillar C9

55

Godwin HL series

HL80M Dri-Prime®Hush-Pac

The HL80M can handle solids up to 25mm in diameter. This makes it anextremely effective pump, suitable forboth slurry and clean waterapplications. The powerful HL80M hasproven itself a pump of choice forsewage handling, dewatering, localauthority usage and many otherapplications.

Suction connection 100 mm

Delivery connection 80 mm

Max capacity 80 m³/hr

Max Head 58 metres

Max Solids 25 mm

Max Suction Lift 8.5M

Wet Weight 1450kgs

Impeller diameter 315 mm

Max working pressure 10 bar

Max operating speed 2000 rpm

Engine Perkins 404D-22T

HL80M Perkins 404D-22T

m³/hr

l/s

00

8

16

24

32

40

48

56

64

72

80

96

88

112

104

10 20 30 40 50 60 70 80 90 1101000 2.5 5.5 8.5 12 14 17 19.5 22.5 25 30.528

Hea

d (m

etre

s)

Flow

2400 rpm

2200 rpm

2000 rpm

1800 rpm

1600 rpm

1400 rpm

Minimum capacitylimitation

Maximum capacitylimitation

EngineOptions

Perkins 404D-22T

Perkins 1104D-44T

Overalldimensions

Length2190mm

Width1050mm

Height1500mm

56

Godwin HL series

HL80M Dri-Prime®Hush-Pac

The HL80M can handle solids up to 25mm in diameter. This makes it anextremely effective pump, suitable forboth slurry and clean waterapplications. The powerful HL80M hasproven itself a pump of choice forsewage handling, dewatering, localauthority usage and many otherapplications.

Suction connection 100 mm

Delivery connection 80 mm

Max capacity 101 m³/hr

Max Head 68 metres

Max Solids 25 mm

Max Suction Lift 8.5M

Wet Weight 2200kgs

Impeller diameter 325 mm

Max working pressure 10 bar

Max operating speed 2100 rpm

Engine Perkins 1104D-44T

HL80M Perkins 1104D-44T

m³/hr

l/s

00

8

16

24

32

40

48

56

64

72

80

96

88

112

104

10 20 30 40 50 60 70 80 90 1101000 2.5 5.5 8.5 12 14 17 19.5 22.5 25 30.528

Hea

d (m

etre

s)

Flow

2400 rpm

2200 rpm

2000 rpm

1800 rpm

1600 rpm

1400 rpm

Minimum capacitylimitation

Maximum capacitylimitation

EngineOptions

Perkins 404D-22T

Perkins 1104D-44T

Overalldimensions

Length2890mm

Width1300mm

Height1800mm

57

m³/hr

l/s

00

8

16

24

32

40

48

56

64

72

80

96

88

112

104

10 20 30 40 50 60 70 80 90 1101000 2.5 5.5 8.5 12 14 17 19.5 22.5 25 30.528

Hea

d (m

etre

s)

Flow

2400 rpm

2200 rpm

2000 rpm

1800 rpm

1600 rpm

1400 rpm

Minimum capacitylimitation

Maximum capacitylimitation

HL125M Dri-Prime®Hush-Pac

The HL125M can handle solids upto 35 mm in diameter. This makes itan extremely effective pump,suitable for both slurry and cleanwater applications. The powerfulHL125M has proven itself a pump ofchoice for sewer bypass, generaldewatering and many otherapplications.

Suction connection 150 mm

Delivery connection 100 mm

Max capacity 275 m³/hr

Max Head 115 metres

Max Solids 35 mm

Max Suction Lift 8.5M

Wet Weight 3200kgs

Impeller diameter 370 mm

Max working pressure 6.0 bar

Max operating speed 2200 rpm

Engine Perkins 1106D-E66TA

HL125M Perkins 1106D-E66TA (129)

2400 rpm

2200 rpm

2000 rpm

1800 rpm

1600 rpm

1400 rpm

Minimum capacitylimitation

Maximum capacitylimitation

m³/hr

l/s

00

20

40

60

80

100

120

140

25 50 75 100 125 150 175 200 225 325275 3002500 7 14 21 28 35 41.5 48.5 55.5 62.5 9076 8369

Hea

d (m

etre

s)

Flow

Overalldimensions

Length3350mm

Width1300mm

Height1887mm

Godwin HL series

EngineOptions

Perkins 1104D-E44TA

Perkins 1106D-E66TA

58

m³/hr

l/s

00

20

40

60

80

100

120

160

140

50 100 150 200 250 4003503000 14 28 41.5 55.5 69 1119783

Hea

d (m

etre

s)

Flow

2400 rpm

2200 rpm

2000 rpm

1800 rpm

1600 rpm

1400 rpm

Minimum capacitylimitation

Maximum capacitylimitation

HL150M Dri-Prime®Hush-Pac

The HL150M can handle solidsup to 35 mm in diameter. Thismakes it an extremely effectivepump, suitable for both slurryand clean water applications. Thepowerful HL150M has provenitself a pump of choice forcontractors, local authorities,industrial and environmentalcompanies.

Overalldimensions

Length3350mm

Width1300mm

Height1887mm

Suction connection 150 mm

Delivery connection 150 mm

Max capacity 350 m³/hr

Max Head 125 metres

Max Solids 35 mm

Max Suction Lift 8.5M

Wet Weight 3400kgs

Impeller diameter 385 mm

Max working pressure 14.8 bar

Max operating speed 2200 rpm

Engine Perkins 1106D-E66TA

HL150M Perkins 1106D-E66TA (168)

Godwin HL series

EngineOptions

Perkins 1104D-E44TA

Perkins 1106D-E66TA

59

Godwin HL series

m³/hr

l/s

00

8

16

24

32

40

48

56

64

72

80

96

88

112

104

10 20 30 40 50 60 70 80 90 1101000 2.5 5.5 8.5 12 14 17 19.5 22.5 25 30.528

Hea

d (m

etre

s)

Flow

2400 rpm

2200 rpm

2000 rpm

1800 rpm

1600 rpm

1400 rpm

Minimum capacitylimitation

Maximum capacitylimitation

HL160M Dri-Prime® The HL160M can handle solids up to35 mm in diameter. This makes it anextremely effective pump, suitablefor both slurry and clean waterapplications. The powerful HL160Mhas proven itself a pump of choicefor mines, quarries and many otherhigh capacity applications.

Suction connection 200 mm

Delivery connection 150 mm

Max capacity 486 m³/hr

Max Head 187 metres

Max Solids 35 mm

Max Suction Lift 8.5M

Wet Weight 5944kgs

Impeller diameter 508 mm

Max working pressure 19 bar

Max operating speed 2000 rpm

Engine Volvo TAD951VE

HL160M Volvo TAD951VE

2000 rpm

1800 rpm

1600 rpm

1400 rpm

1200 rpm

Minimum capacitylimitation

m³/hr

l/s

00

20

40

60

80

140

120

100

160

180

200

50 100 150 200 250 300 350 5004504000 14 28 41.5 55.5 69 83.5 97 139125111

Hea

d (m

etre

s)

Flow

Maximum capacitylimitation

Overalldimensions

Length3700mm

Width1700mm

Height2200mm

EngineOptions

Volvo TAD951VE

Caterpillar C15

60

Godwin HL series

2000 rpm

1800 rpm

1600 rpm

1400 rpm

1200 rpm

Minimum capacitylimitation

Maximum capacitylimitation

m³/hr00

20

40

60

80

140

120

100

160

180

200

50 100 150 200 250 300 350 500450400

Hea

d (m

etre

s)

Flow

l/s0 14 28 41.5 55.5 69 83.5 97 139125111

HL160M Dri-Prime®Hush-Pac

The HL160M can handle solids upto 35 mm in diameter. This makesit an extremely effective pump,suitable for both slurry and cleanwater applications. The powerfulHL160M has proven itself a pumpof choice for mines, quarries andmany other high capacityapplications.

Overalldimensions

Length4580mm

Width2065mm

Height2545mm

Suction connection 200 mm

Delivery connection 150 mm

Max capacity 486 m³/hr

Max Head 187 metres

Max Solids 35 mm

Max Suction Lift 8.5M

Wet Weight 7000kgs

Impeller diameter 508 mm

Max working pressure 19 bar

Max operating speed 2000 rpm

Engine Volvo TAD951VE

HL160M Volvo TAD951VE

EngineOptions

Volvo TAD951VE

Caterpillar C15

61

Godwin HL series

m³/hr

l/s

00

8

16

24

32

40

48

56

64

72

80

96

88

112

104

10 20 30 40 50 60 70 80 90 1101000 2.5 5.5 8.5 12 14 17 19.5 22.5 25 30.528

Hea

d (m

etre

s)

Flow

2400 rpm

2200 rpm

2000 rpm

1800 rpm

1600 rpm

1400 rpm

Minimum capacitylimitation

Maximum capacitylimitation

HL250M Dri-Prime®Hush-Pac

The HL250M can handle solidsup to 65 mm in diameter. Thismakes it an extremely effectivepump, suitable for both slurryand clean water applications.The powerful HL250M hasproven itself a pump of choicefor mines, quarries and manyother high capacity applications.

Suction connection 300 mm

Delivery connection 250 mm

Max capacity 1224 m³/hr

Max Head 119 metres

Max Solids 65 mm

Max Suction Lift 8.5M

Wet Weight 9200kgs

Impeller diameter 440 mm

Max working pressure 13 bar

Max operating speed 2000 rpm

Engine Caterpillar C15

HL250M Caterpillar C15

m³/hr

l/s

00

1020

30

4050

6070

80

90

100

110

140

130

120

100 200 300 400 500 600 700 800 900 130012001000 11000 28 55.5 83.5 111 139 166.5 194 222 250 361333278 305.5

Hea

d (m

etre

s)

Flow

2000 rpm

1800 rpm

1600 rpm

1400 rpm

1200 rpm

Minimum capacitylimitation

Maximum capacitylimitation

Overalldimensions

Length5500mm

Width2700mm

Height2500mm

EngineOptions

Volvo TAD1215VE

Caterpillar C15

62

Godwin NC series

Godwin NC series

With two of the world’smarket leading pumpbrands, Flygt and Godwin,now under the Xylemumbrella, we havecombined the world’s mostreliable portable pumpswith the world’s mostefficient self-cleaninghydraulics to bring you themost efficient and reliableGodwin pumps ever.

The new range of GodwinNC pumps are not onlyreliable, they comeequipped with the non-clogging, performance of the proven Flygt N-technology.

This breakthrough combination gives you a best-in-class portable pump that deliverssustained hydraulic efficiency to handle tough wastewater pumping applications.

Self-cleaning Flygt N-technology saves costs

The high efficiency of Flygt N-technology is sustained over time due to its self-cleaning ability, keeping energy/fuel costs to a minimum.

Without a doubt, no matter what the challenge, you will always have the peace ofmind knowing that our Godwin NC Series Dri-Prime® pumps are on the job.

Godwin pumps, now with sustained high efficiency N hydraulics

• Self-cleaning reliability

• Hydraulic efficiency

• Non-stop optimum performance

• Long term energy/fuel savings

• Optimized operating speed for low energy/fuel consumption

• Low downtime

• Extended service intervals

• Minimum maintenance

• Service friendly

63

Godwin NC series

2200 rpm

2000 rpm

1800 rpm

1600 rpm

1400 rpm

1200 rpm

Minimum capacitylimitation

m³/hr

l/s

00

10

20

30

40

50

25 50 75 100 125 150 175 250200 2250 7 14 21 28 35 41.5 48.5 6955.5 62.5

Hea

d (m

etre

s)

Flow

NC100 Dri-Prime®

Features the unique patented N-technology with its innovative self-cleaningimpeller. Able to perform in the toughestconditions, the NC100 can handle solids upto 35 mm in diameter. This makes it anextremely effective pump, suitable for bothsewage and clean water applications. Thepowerful NC100 has proven itself a pumpof choice when pumping stringy materialand general dewatering applications.

Overalldimensions

Length2190mm

Width1050mm

Height1500mm

Suction connection 100 mm

Delivery connection 100 mm

Max capacity 188 m³/hr

Max Head 27 metres

Solids Handling 35 mm

Max Suction Lift 8.5M

Wet Weight 1345kgs

Impeller diameter 256 mm

Max working pressure 5.0 bar

Max operating speed 1800 rpm

Engine Perkins 403D-15

NC100 Perkins 403D-15

EngineOptions

Perkins 403D-15

Perkins 404D-22

64

Godwin NC series

0

10

20

30

40

50

60

70

Hea

d (m

etre

s)

m³/hr

l/s

0 50 100 150 250 300 350 42540020025 75 125 225 275 325 375175

0 14 28 41.5 69 83.5 97 111 11855.57 21 35 62.5 76.5 90 10448.5Flow

2200 rpm

2000 rpm

1800 rpm

1600 rpm

1400 rpm

1200 rpm

Minimum capacitylimitation

NC150 Dri-Prime®

Features the unique patented N-technologywith its innovative self-cleaning impeller.Able to perform in the toughest conditions,the NC150 can handle solids up to 42 mmin diameter. This makes it an extremelyeffective pump, suitable for both sewageand clean water applications. The powerfulNC150 has proven itself a pump of choicewhen pumping stringy material and generaldewatering applications.

Overalldimensions

Length2190mm

Width1050mm

Height1500mm

Suction connection 150 mm

Delivery connection 150 mm

Max capacity 241 m³/hr

Max Head 26 metres

Solids Handling 42 mm

Max Suction Lift 8.5M

Wet Weight 1410kgs

Impeller diameter 265 mm

Max working pressure 6.0 bar

Max operating speed 1600 rpm

Engine Perkins 404D-22

NC150 Perkins 404D-22

EngineOptions

Perkins 404D-22

Perkins 1104D-44T

65

Godwin Heidra series

Heidra Hydraulic Submersible Hush-Pac

When the suction lift is greater 8.5 m, Heidra pumps take over where Dri-Primepumps leave off. Heidra hydraulic submersibles are basically Dri-Prime pumps thathave been engineered to work submerged in the liquid they pump. Tough andreliable, Heidra pumps are designed for general pumping of light slurries andmunicipal sludges

Liquid bath mechanical seal = dry-running and reduced maintenance costs

Seals in pumps that often run dry can overheat and fail. Godwin mechanical shaftseals run in a liquid bath, which dissipates heat through the pump casing and allowsthe pump to run dry. This provides more reliable operation, frees operators fromclosely monitoring the pumps, while reducing maintenance costs.

Durable pump-end = long lifetime

Cast iron, the standard build, offers excellent durability.

Open impeller = versatility and fewer stoppages

With their open impeller design, Godwin Heidra pumps handle solids of up to125mm in diameter, reducing the risk of stoppages. The open impeller also meansyou can use Godwin pumps in a wide range of applications from water andwastewater, to drilling muds and industrial fluids.

66

Godwin Heidra NC series

Maximum capacity limitation

Minimum capacity limitation

0

5

10

15

20

25

30

35

40

Hea

d (m

etre

s)

Flow

l/s

m3/hr0 25 50 75 100 125 150 175 200 225

0 7 14 21 28 35 41.5 48.5 55.5 62.5

2000 rpm (1540 rpm)

1800 rpm (1386 rpm)

1600 rpm (1232 rpm)

1400 rpm (1078 rpm)

Delivery 100 mm Bauer

Inlet 100 mm c/w Strainer

Max capacity 200 m³/hr

Max Head 35 metres

Solids Handling 35 mm

Suction Lift No Limit

Wet Weight 1500kgs

Pump Weight 135kgs

Impeller diameter 256 mm

Max working pressure 4.0 bar

Max operating speed 2200 rpm

Engine Duetz F4M2011

HNC100 Duetz F4M2011

Heidra HNC100 - Duetz Power Pack

An extremely powerful yetcompact pump. Able toperform in the toughestconditions, the Heidra100NC can handle solids upto 35 mm in diameter. Thepowerful Heidra 100NC hasproven itself a pump ofchoice when pumping stringymaterial and generaldewatering applications.

67

Overall dimensions

Length 2200mm

Width 1050mm

Height 1845mm

Godwin Heidra NC series

2000 rpm (1540 rpm)

1800 rpm (1386 rpm)

1600 rpm (1232 rpm)

1400 rpm (1078 rpm)

Minimum capacity limitationMaximum capacity limitation0

5

10

15

20

25

30

35

Flow

Hea

d (m

etre

s)

l/s

m³/hr0 25 50 75 100 125 150 175 200 225 250 275

0 7 14 21 28 35 41.5 48.5 55.5 65.5 69 76

Delivery 150 mm Bauer

Inlet 150 mm c/w Strainer

Max capacity 225 m³/hr

Max Head 29 metres

Solids Handling 42 mm

Suction Lift No Limit

Wet Weight 1500kgs

Pump Weight 155kgs

Impeller diameter 280 mm

Max working pressure 5.7 bar

Max operating speed 2000 rpm

Engine Duetz F4M2011

HNC150 Duetz F4M2011

Heidra HNC150 - Duetz Power Pack

An extremely powerful yetcompact pump with flowcapabilities to 385 m³/hr anddischarge heads to 56 metres.Able to perform in the toughestconditions, the Heidra 150NCcan handle solids up to 42 mmin diameter. The powerfulHeidra 150NC has proven itselfa pump of choice whenpumping stringy material andgeneral dewatering applications.

68

Overall dimensions

Length 2200mm

Width 1050mm

Height 1845mm

Solids Handling - Robot Range

m³/hr

l/s

00

5

10

15

20

25

30

36 72 108 144 180 216 252

0 10 20 30 40 50 60 70

Head (m)

Flow

Flygt 100VX Robot

Heavy duty pump, for pumping rawsewage and slurries. The Vortex Flowdesign allows solids of up to 80mm topass through. Ideal for sewer by-passwork and where large solids are insuspension.

Connection Size 100mm

Max Capacity 180 m3/h

Max Head 19 Metres

Suction Lift 9 Metres

Max Solids 80mm

Air Handling 50 m3/h

Operating Speed 1500 rpm

Wet Weight 1484 Kg

Fuel Tank 150 Lts

Engine Duetz F2M2011

100VX

Fuel consumption 7.2 litres per hour at full speed

69

Solids Handling - Robot Range

Flygt 150VX Robot

Silenced, Heavy Duty pump, for pumpingRaw Sewage and Slurries. The VortexFlow design allows solids of up to100mm to pass through. Ideal for Sewerby-pass work and where large solids arein suspension.

Connection Size 150mm

Max Capacity 240 m3/h

Max Head 32 Metres

Suction Lift 8 Metres

Max Solids 100mm

Air Handling 50 m3/h

Operating Speed 1750 rpm

Wet Weight 1990 Kg

Fuel Tank 142 Lts

Engine Duetz F4M2011

150VX

0

4

8

12

16

20

24

28

32

36

40Head (m)

m³/hr

l/s

0 40 80 120 160 200 240 280 320 400360

0 11 22 33 44.5 55.5 66.5 78 89 111100Flow

Fuel consumption 7.2 litres per hour at full speed

70

71

Water Treatment

We can now rent water treatment products from our Sanitaire & Wedeco brands. Ourhigh-tech treatment systems can provide the most cost-effective solutions for ourcustomers without putting an undue burden on the environment.

Wedeco UV technology can be used to disinfect drinking water, wastewater andindustrial process water. UV treatment is chemical-free and an environmentallyfriendly alternative to chlorine disinfection. Our Wedeco systems use rays of UV lightto kill dangerous micro-organisms, including bacteria, viruses and yeasts, preventingthem from multiplying.

Sanitaire diffuser systems offer higher oxygen transfer efficiency, resulting in lowerairflow rates, lower back pressure and reduced cost over long term usage. They aregenerally employed for biological aeration, pre-discharge aeration and sludgeholding odour control.

Sanitaire Silver Series II

Sanitaire Silver Series II - Diffuser Grid

For a combination of high aeration efficiency andlow operating costs, there’s the Sanitaire SilverSeries II membrane diffuser – the most widelyused fine bubble diffused aeration systemavailable today.

The Sanitaire Silver Series II is well establishedand time proven in the market. This product is widely utilised in the municipal water industryfor standard and low-pressure aeration applications; and our LP (low pressure)membrane is an excellent solution for applications where the back pressure allowedon the blower is already defined, such as a refurbishment.

Xylem can now offer a complete fine bubble aeration system (4m x 2m) with ourmarket leading Sanitaire Silver Series II fine bubble membrane diffusers and a600m3/hr blower unit.

Description kW Voltage

Lift Out S/S Aeration Grid 4m x 2m c/w72 x 9" Sanitaire Membrane Diffuser Heads 30 400/3/50600m3/h Blower Unit 3m x 2m x2m

72

Wedeco Spektron

Wedeco Spektron

The Wedeco Spektron shines newlight on the environmentallyfriendly process of using UVdisinfection for drinking water.Featuring highly efficient UV lamptechnology and advanced flowdistribution, the Spektron series suitsmodern drinking water treatment plants and covers a wide array of applications from domesticwater supply and industrial uses to large municipal waterplants with a capacity of more than one thousand m3/h per unit.

Xylem now has Wedeco Spektron 400 and 600 UV reactors available to rent togetherwith their own control panel for ease of use and inspection. The Spektron range can be used in a number of applications where water treatmentis needed.

Description kW Voltage

Spektron 400300mm Dia x 2.5m S/S UV Reactor c/w

2.9 400/3/508 x 330w UV Lamps & Control Panel

Spektron 600350mm Dia x 2.9m S/S UV Reactor c/w

4.3 400/3/5012 x 330w UV Lamps & Control Panel

73

74

Mixers

Flygt Submersible Mixers consist of a drive unit and propeller, integrated into a compact unit. The mixer is mounted on a guide bar, to enable it to be raised andlowered, to operate at different depths. It can also be angled upwards or downwardand can be swivelled to the sides. Its mixing action can therefore be directed to anypoint in a lagoon or tank.

This flexibility aided by the large blade propeller, running at relatively low speeds,sets in motion large volumes of sludge and water. The Flygt submersible mixer is at least three times as efficient as a conventional mixer. This is due to the highefficiency hydraulic design and the fact that the motor and propeller are integratedinto a lightweight, compact unit. No energy is lost in complicated gearing, supportbearings and heavy shafts. Also, the mixer can be run intermittently, thus providingfurther energy savings.

Compact design

The machines are either direct-driven or include a reduction gearbox between themotor and the propeller. However, all models are well integrated into a compactunit. So no energy is lost in long heavy shafts and support bearings.

Circular tanks

One mixer is normally sufficient for tank volumes up to 2,000m3. Depending on thecharacteristics of the liquid and the desired degree of agitation, more than onemixer may be necessary for larger tank volumes.

Rectangular tanks

If the length, width and depth dimensions of the tank differ considerably, severalmixers may be necessary to ensure good results. Rectangular tanks are often locatedunderground. Since Flygt Mixers are installed from the top, installation in underground tanks is easy.

For specific duties on the range of Flygt Submersible Mixers please contact yourlocal service centre.

75

Homogeneous liquid manure in a couple of hours.

Flygt Submersible Mixers have an important role to play in agriculture, forhomogenising liquid manure. Even if the manure is old, with a thick dry crust and allthe solids have settled at the bottom of the tank, it will be possible by mixing for thewhole tank contents to become homogeneous. This is due to the fact that the mixercan operate at different depths, can be orientated in any direction and will quicklyset in motion large volumes of the manure.

Wide field of applications in industry

Flygt Submersible Mixers are used for keeping liquids of different viscosities in suspension, for mixing dry solids into liquids, for thickening after sedimenting anddecanting, and for transporting liquids,

Good environment in fish farming

Whether in netting enclosures in open water or in dammed bays, Flygt submersiblemixers will maintain ideal fish farming conditions at a modest cost. The mixer willsupply a briskly-flowing current of fresh water with good oxygen contents and an abundance of natural food. At the same time, fish droppings will be removed. Therisk of rotting and formation of decay gases is eliminated. By establishing circulationbetween the bottom and the surface , the mixer also evens out the watertemperature, which favours the growth of the fish.

Improving the efficiency in sewage treatment plants

Flygt Submersible Mixers have been widely adopted in sewage treatment plantsthroughout the world. Particularly in thickening, sludge and storm water ponds, in buffer tanks and in the mixing of chemicals and lime into the water, the efficiencyand low operating costs of the mixers can be utilised to the greatest possible extent.

Flow creation

For low head, high capacity laminar flows the large propeller mixer can be used in lake reservoirs, fish farms as well as process mixing.

Mixers in Practice

Mixers

As shown:

4620 1.5 kW mixer fitted on a portable, free standing steelwork - available to rent.

76

øA

GF

HE

øD

ø B

HG

øA MAX

Type

AB

CD

EF

GH

IWeights

(max)

Max

Max

mm

mm

mm

mm

mm

mm

mm

kg (lbs)

Ø mm

Ø mm

4410

2500

--

--

-1110

1010

100

230(507)

4430

2500

--

--

-1110

1010

100

263 (580)

4630

390

636

405

559

469

117

574

457

5061(134)

4640

390

636

405

559

509

117

614

497

5064 (141)

4650

650

1027

675

931

721

195

878

700

100

177 (390)

4660

650

1027

675

931

831

195

988

810

100

218 (481)

4670

880

1372

908

1256

835

264

992

816

100

363 (800)

4680

880

1372

908

1256

985

264

1192

966

100/150

482 (1063)

Available Mixers

77

Aeration - Radial Aerators

Fields of application

The efficient mixing characteristics and the simple design of our Ejectors andAerators make them suitable for aerating biological ponds, fishfarm ponds, lakes and waterways.

The function of the ejectors

The principle on which the Ejector operates is simple and well-known. A drive jetfrom a Flygt Submersible pump is led into the Ejector. The drive jet flows through a nozzle into the ejector housing, which has a delivery pipe for the medium, e.g. air,which is to be pumped (the secondary flow). A drop in pressure occurs when thedrive jet passes through the mixing tube. This partial vacuum automatically entrainsthe pump medium with the drive jet and the contents of the primary and secondaryflows are mixed intensively with each other.

The function of the Radial Aerator

Aeration by means of high efficiency mixing.

Air dispersion by the same method as the Ejector is distributed radially within a tank,basin or lagoon, via the series of diffusers mounted around a central turbineimpeller. As with the Ejectors, being totally submerged significant advantages ariseover other forms of aeration.

Low noise levels.

No sprays or liquid dispersion in the atmosphere.

Installation

Installation of these aeration products is straightforward either by bolting to the tankfloor or they even will be suspended by their own weight in certain circumstances.

Applications

Subject to the tank configuration the ejector oraerator can be selected to: Replace existingaeration equipment during breakdown ormaintenance periods. Upgrade existingtreatment capacity without major investment.Increase oxygen levels. Reduce ammonia levels.

78

Dimensions and Weight - Radial Aerators

A

B

C

Type Power Current Dimensions (mm) Weighta b c Kg*

308 2.4 4.5 610 660 50 75310 4.4 8.5 700 660 50 105312 5.9 11.0 800 950 80 180315 13.5 25.0 1130 995 100 295320 22 42.0 1320 1150 150 500

* Weight includes 10m of cable

79

Radial Aerators - Oxygen Transfer Rate

80

81

Flyjet and Hydroejector

Utilising the principles of an Ejector; the Flyjet and Hydroejector can be used to resuspend solids which have settled in storage tanks.

They can be used in storm water retention tanks at sewage works;for example. 4” and 6” jet pipes are available.

82

Pump Flotation Modules

The conceptOur range of pump flotation modules has been developed to provide a light-weight and cost-effective alternative to the traditional steel pontoon. Theflotation modules are prefabricated from light-weight, foam-filled, GRP (Glass fibreReinforced Polymer) and are available in four sizes.

General applicationsPump Flotation Modules can be supplied to suit Flygt 2000 Series / BS dewateringpumps, C/N-series wastewater pumps and slurry pumps.• Applications include:

• Mine dewatering• Tailing dams• Underground dams• Sewage treatment

• Quarries• Aeration ponds• Construction site dewatering• Flooding control

InstallationThe pump and integral module can be simply installed by use of a central liftingattachment. Once in the water, the module can be towed by boat, if required, andsecured in position by anchor or guy ropes. The float module remains visible abovethe water surface for easy recovery.

By having the pump floating close to the surface, it increases service life throughreduced maintenance since it is no longer working within high solids environment.

• Compact and lightweight• Stainless steel metal parts• Easily mounted to pumpson site

• Lifting points for easy installation• Easy to transport as an integral unit• Foam filled to prevent sinking

PFM550

PFM550

PFM 550 Part Number2201 691 69 003140 *3152/3153 *3170/3171 *5100 (<52kW) *5150 (<52kW) *

* On request

1400 x 1400 x 540mm 20 kg

Design features:

83

To complement our comprehensive range of pumps, extensive stocks of pipeworkand hoses are held. Our Rental engineers can supply all your needs from 2” hoseincreasing in size to steel pipes in excess of 450mm.

Also BSP pipe and cast iron fittings to suit most applications including valve, taper,hose spigot, flexible couplings and hose clamps, specialised hoses for high pressureapplications are also stocked.

Hoses and Fittings

Hoses and Fittings

A tough hose developed for the construction industry, with a tube of smoothsynthetic rubber, covered with weather resistant synthetic rubber, reinforced withcords of synthetic textile and an embedded helix of high-tensile steel wire. It is flexible and heavy, yet easy enough to manoeuvre. It seals well onto the pipe fittings, withstands high pressure and is also tough. It is ideal for suctions and for discharge where the bend must not collapse.

SpecificationBore Outside Working Weight perdia. dia. Pressure 6m incl. cpgs mm in. mm bars kg

50 2 58 5 675 3 87 5.5 10100 4 115 4.5 25150 6 167 3 40

PVC is a high grade hose, flexible, lightweight, with exceptional resistance toabrasion and weathering. The smooth bore offers minimum resistance to flow. The strengthened PVC helix is embedded in the hose wall for extra strength.

PVC Suction andDischarge Hose

SpecificationBore Outside Working Weight perdia. dia. Pressure 6m incl. cpgs mm in. mm in. bars psi kg

50 2 65 2.5 6 90 875 3 90 3.5 4 60 14100 4 115 4.5 3 50 18150 6 170 6.75 3 50 43Polythene Delivery Hose

A pump relies on a secure link between the source and the discharge point. Poorhoses will leak, collapse and cause unwanted problems. So, at Xylem we only sellthose hoses we use ourselves – “Cheap hose is expensive hose in the long run”.

This is a proven semi-rigid delivery hose, which is well known throughout theindustry. It is damage resistant, but also lightweight and simple to handle. Friction loss is kept to a minimum in this smooth bore hose.

84

SpecificationBore Outside Working Weight perdia. dia. Pressure 6m incl. cpgs mm mm bars kg

51 63 8 1276 89 8 26102 116 8 35150 169 5 60

Wire-armouredSuction Hose

85

Friction Loss in Pipe Fittings Chart

The table refers to new pipes and moderate corrosion could increase resistance by30%. To calculate resistance of Bends and Fittings, an ‘equivalent length’ for eachaccessory needs to be added to the actual length of pipe. The equivalent length infeet can be estimated by multiplying the factors in the adjacent table by the pipediameter in inches.

Example :- A 6” Gate Valve is equivalent to 12 ft of extra pipe

Mitre elbow or tee 5Round elbow 3Slowbend 2Square edged entrance 3Gate valve fully open 2Globe valve fully open 10Non-return valve (flap type) 3Foot-valve and strainer (clean) 5

Losses in m/100 or ft./100ft

I.G.P.M.2” 3” 4” 6” 8” 10” 12” m3/h

50 10 1.4 0.3 1075 20 3 0.7 15100 35 5 1 0.1 20150 12 2.5 0.35 30200 18 4.5 0.6 50300 40 10 1.2 0.4 75400 18 2.2 0.7 100500 28 3.5 1.1 0.35 125600 38 4.5 1.5 0.5 150700 6.5 2 0.7 175800 8 2.7 0.8 200900 10 3.4 1 0.4 2251000 13 4 1.4 0.5 2501200 18 6 2 0.8 3001400 26 8 3 1 3501600 32 11 4 1.5 4001800 36 14 4.5 2 4502000 38 17 5 2.5 5002500 25 9 4 6503000 38 12 5 7504000 21 8 10005000 32 13 1250

m3/h x 4 = g.p.m. approx

Friction Loss In Smooth Bore Pipe

86

Weight Reference Guide - Pumps

The weights above DO NOT include Cable, Chains or HosesThe weights contained within this guide are an estimate only and the actual weight of the item to be

lifted must be separately assessed and verified

2052 18Kgs2066 30Kgs2102 50Kgs2125 Aluminium 89Kgs2125 Cast Iron 180Kgs2151 165Kgs2201MT Aluminium 280Kgs2201MT Cast Iron 445Kgs2201HT Aluminium 240Kgs2201HT Cast Iron 350Kgs2250 540Kgs2400 985Kgs2610 MT 21Kgs2620 MT 32Kgs2640 MT & HT 51Kgs2660 MT & HT 78Kgs2670 MT & HT 141Kgs3085MT 71Kgs3102MT 116Kgs3102SH 114Kgs3127MT 170Kgs3127HT 155Kgs3152LT 426Kgs3152MT 321Kgs3152HT 280Kgs3153 LT 379Kgs3153MT 252Kgs3153HT 232Kgs3153SH 242Kgs3171LT 460Kgs3171MT 362Kgs3171HT 321Kgs3201MT 588Kgs3201HT 540Kgs3202LT 900Kgs3202MT 610Kgs3202HT 580Kgs3300LT 1'175Kgs3300MT 1'188Kgs3300HT 988Kgs3301LT 1'110Kgs3301MT 1'030Kgs3301HT 920Kgs3315HT 1220Kgs

SubmersiblePump Type

BS/NS/CS Weight Inc Base Stand Large Submersible Pump Range

3231 85Kw 1'380Kgs - Pump Only3231 105Kw 1'590Kgs - Pump Only3231 125Kw 1'530Kgs - Pump Only3231 170Kw 1'760Kgs - Pump Only3231 215Kw 1'910Kgs - Pump Only3312 100Kw 1'975Kgs - Pump Only3312 180Kw 2'275Kgs - Pump Only3312 250Kw 3'125Kgs - Pump Only3356 100Kw 1'750Kgs - Pump Only3400 75Kw 2'700Kgs - Pump Only3400 250Kw 3'750Kgs - Pump Only

Original Flygt Diesel RangeFlygt Swell 100 - Full Fuel Tank 1'510KgsFlygt Swell 150 - Full Fuel Tank 1'790KgsFlygt ROBOT 100VX - Full Fuel Tank 1'484KgsFlygt ROBOT 150VX - Full Fuel Tank 1'990KgsFlygt 150WP - Full Fuel Tank 1'820KgsFlygt Swell 200 - Full Fuel Tank 1'750Kgs

Godwin Diesel Range - Skidbase HushpacCD80D - Kubota Z482 Engine - Wet Weight 725KgsCD100M - Perkins 403D-15 Engine - Wet Weight 1'168KgsCD150M - Perkins 404D-22 Engine - Wet Weight 1'403KgsCD300M - Caterpillar C9 Engine - Wet Weight 6'620KgsHL80M - Perkins 1104D-44T Engine - Wet Weight 2'200KgsHL125M - Perkins 1106D-E66TA Engine - Wet Weight3'200KgsHL150M - Perkins 1106D-E66TA Engine - Wet Weight3'400KgsHL160M - Volvo TAD 951VE Engine - Wet Weight 7'000KgsHL250M - Caterpillar C15 Engine - Wet Weight 9'200KgsNC100 - Perkins 403D-15 Engine - Wet Weight 1'390KgsNC150 - Perkins 404D-22 Engine - Wet Weight 1'410KgsHeidra 150 Duetz F4M2011 Power Pack - Wet Weight1'500KgsHNC100 Pump Only 135KgsHNC150 Pump Only 155Kgs

Mixers4620 18Kgs4630 60Kgs4640 63Kgs4650 174Kgs4660 209Kgs4670 345Kgs

Panels15Kw Soft Start 30Kgs90Kw Soft Start 130Kgs

Pump Type Weight

The Information contained within this document is for guidance only and is accurate to the best of ourknowledge at time of going to print.

87

Weight Reference Guide - AccessoriesSize

2" - 50mm

3" - 80mm

4" - 100mm

6" - 150mm

8" - 200mm

10" - 250mm

12" - 300mm

Cast Iron Pipe & Fittings

Kg

Kg

Kg

Kg

Kg

Kg

Kg

Gate Valve Metal Wedge

1723

3565

104

170

228

NRV Cast Iron Flap Type

1216

2137

69132

187

D/F Bend Short

1113

2234

5577

D/F Bend Long

1621

3452

74101

Duck Foot Bend

1519

3350

82116

Equal Tee

1721

3654

87115

Radial Tee

2634

5583

121

164

“Y” Piece

1720

3654

89127

Taper

810

1522

3346

VJFA

45

711

1520

Cast Iron Pipe Cement lined kg/M

1620

3040

5266

NP 16 Flange

56

810

1519

Hoses

Wire Armoured Hose C/W Bauers

6M12

2635

60PVC Suction & Discharge Hose C/W Bauers6M

610

2540

Polythene Semi Rgid Hose C/W Bauers6M

814

1843

Wire Armoured Hose C/W Bauers

3M50

95Wire Armoured Hose C/W Flanges

3M95

125

Steel “Bauer” Type Pipe & Fittings

2" - 50mm

3" - 76mm

41/4" - 108mm61/4" - 159mm75/8" - 194mm

Galvanised pipe

1M3

58

1520

Galvanised pipe

2M3

712

2030

Galvanised pipe

3M7

1116

3240

Bauer Ball Connector

0.2

0.3

11.5

2Bauer Level Closure Ring

0.5

11.5

46

Bauer Socket

0.1

0.3

0.6

1.2

2.5

Bauer 90 Deg Bend C/W Closure Ring

12.5

5.5

1113

Bauer Equal Tee C/W 2 Closure Rings

1.5

48

15Bauer Flanged with ball & Closure Ring

35

814

22Bauer Flanged with Socket

34

57

15

The weights contained within this guide are an estimate only and the actual weight of the item to be

lifted must be separately assessed and verified

Inches x 25.4 = mm x 0.0394 = Inches

Feet x 03048 = m x 3.281 = Feet

Yards x 0.9144 = m x 1.0936 = Yards

Miles x 1.609 = km x 0.6214 = Miles

Ft2 x 0.0929 = m2 x 10.764 = Ft2

Miles2 x 2.59 = km2 x 0.3861 = Miles2

In3 x 16387 = mm3 x 0.000061 = In3

Ft3 x 0.02832 = m3 x 35.31 = Ft3

Gals (Imp) x 4.546 = L x 0.22 = Gals (Imp)

Gals (Imp) x 0.004546 = m3 x 220 = Gals (Imp)

Gals (US) x 3.785 = L x 0.2642 = Gals (US)

LBS x 0.4536 = kg x 2.2046 = LBS

Tons x 1016 = kg x 0.000984 = Tons

Gal/Min (Imp) x 0.2727 = m3/h x 3.6667 = Gal/Min (Imp)

Gal/Min (Imp) x 0.0757 = L/Sec x 13.21 = Gal/Min (Imp)

L/Sec x 3.6 = m3/h x 0.277 = L/Sec

Gal/Min (Imp) x 1.2 = USGPM x 0.833 = Gal/Min (Imp)

PSI x 0.06895 = Bar x 14.504 = PSI

PSI x 0.703 S.G = M Liquid x 1.422xS.G = PSI

Ft Liquid x 0.02989xS.G = Bar x 33.456 SG = Ft Liquid

STD. ATM x 1.01225 = Bar x 0.9879 = STD. ATM

HP x 0.7457 = kW x 1.341 = HP

Conversion Factors

88

Conversion Factors

Flow Conversions

M3/min GPHUS GPM GPM

dm3/min dm3/hr L/HR

Kg/hr

Kg/sec

264 1.2 60

604.4 3.66

219.6792

60

CFM

M3/Sec

2.12

1000

1000

3.6 L/Sec

Tonne Hr

100xSG

3.6SG

0.06

1.0SG

=L/min L/min1.0 60

M3/hr

1000 100016.67

x

Head/Pressure Conversions

PSI

KN/m2

MegaPascal MPA

Kg/

14.22

14.5

1.02

10

100

k Pa

Ft

1

9.8xSG

10.211SG

33.5SG

bar

3.28

9.8xSG

M

x ÷

1.42xSG

6.9

Atmos-phere

33.9

10.34

PSI

2.31SG

÷

13.2

= dm 3/5

89

Flange Sizes

Normal Table Dia. P.C.D Bolt No. of Flange Thickness Bore Flange Dia. Bolts Grey Cast Iron

1” D&E 4.50” 3.25” .50” 4 .50”1.25” D&E 4.75” 3.44” .50” 4 .625”1.5” D 6.00” 4.50” .625” 4 .688”2” E 6.00” 4.50” .625” 4 .75050mm NP16 165mm 125mm M16 4 20mm2.5” D 6.50” 5.00” .625” 4 .688”

E 6.50” 5.00” .625” 4 .750”3” D&E 7.25” 5.75” .625” 4 .750”80mm NP10 200 (7.87) 160 (6.30) M16 8 21 (.83)

NP16 200 (7.87) 160 (6.30) M16 8 21 (.83)4” D 8.50” 7.00” .625” 4 .750”

E 8.50” 7.00” .625” 8 8.75”

100mm NP10 220 (8.66) 180 (7.09) M16 8 22 (.87)NP16 220 (8.66) 180 (7.09) M16 8 22 (.87)

5” D 10.00” 8.25” .625” 8 .813”E 10.00” 8.25” .625” 8 .875”

6” D 11.00” 9.25” .625” 8 .813”E 11.00” 9.25” .750” 8 8.75”

150mm NP10 285 (11.22) 240 (9.49) M20 8 23 (.91)N16 285 (11.22) 240 (9.49) M20 8 23 (.91)

7” D 12.00” 10.25” .625” 8 .875”E 12.00” 10.25” .750” 8 1.00”

8” D 13.25” 11.50” .675” 8 .875”E 13.25” 11.50” .750” 8 1.00”

200mm NP10 340 (12.38) 295(11.61) M20 8 245 (.96)NP16 340 (12.38) 295(11.61) M20 12 245 (.96)

9” D 14.50” 12.75” .625” 8 .875”E 14.50” 12.75” .750” 12 1.00”

10” D 16.00” 14.00” .750” 8 1.00”E 16.00” 14.00” .750” 12 1.00”

250mm NP10 400 (15.75) 350(13.78) M20 12 26 (1.02)NP16 400 (15.75) 355 (13.98) M25 12 26 (1.02)

12” D 18.00” 16.00” .750” 12 1.00”E 18.00” 1.00” .875” 12 1.125”

300mm NP10 455 (17.91) 400 (15.75) M20 12 27.5 (1.08)NP16 455 (17.91) 410 (16.14) M25 12 27.5 (1.08)

90

NP10 and NP16 are for cold water pressure of 10 bar and 16 bar and are the currentBritish Standard. They are unnecessarily heavy for most contractors’ pumps.

98

Notes

Thainstone Business ParkInverurieAberdeenshireAB51 5GT

Tel 01467 623010Fax 01467 623011Email [email protected]

www.filpumps.co.uk