GS01C31T01-01EN (EJA-E Series HART 5 and HART 7 Communication)

Embed Size (px)

Citation preview

  • 8/12/2019 GS01C31T01-01EN (EJA-E Series HART 5 and HART 7 Communication)

    1/4

    GeneralSpecications

    EJA-E SeriesHART 5/HART 7 Communication

    Yokogawa E lectric Corporation2-9-32 Nakacho, Musashino-shi, Tokyo, 180-8750 JapanPhone: 81-422-52-5690 Fax.: 81-422-52-2018

    GS 01C31T01-01EN

    GS 01C31T01-01ENCopyright June 20121st Edition June 2012

    DPharp EJA-E Series can perform remote settingand monitoring of measuring ranges, dampingtime constant, etc. through a HART protocolrevision5(HART 5) and revision7(HART 7) compliantconguration tool.

    FEATURES Remote Ranging and Monitoring Functions

    Ranges can be remotely set and monitored throughHART communication.

    On-line Communication

    Output signal and communication signal do notinterfere making on-line communication possible.

    Enhanced Burst Mode and Event Notication(HART 7)

    Advanced burst mode includes the variety oftransmission setting by specifying burst variables,update period, and message triger mode, and eventnotication function gives you alert signal basedon the status change in preset values and self-diagnosis.

    Long Tag Supporting Up to 32 Characters(HART 7)

    Long tag secures a better asset management withabundant digits in its software.

    Self-DiagnosticPressure input outside of range limit, excessiveambient temperature, incorrect span setting etc. canbe diagnosed through HART communication.

    HART protocol revision selectableSelectable from HART 5 and HART 7.

    STANDARD SPECIFICATIONSFor items other than those described below, refer toeach General Specication sheet.

    HART Protocol RevisionHART protocol revision can be selected from 5 or 7when ordering.The protocol revision can be changed by userconguration.

    Write Protection Switch:Hardware/software write protection switch

    Conditions of Communication Line:Supply Voltage;

    General Use & Explosion proof Type16.6 to 42 V DC

    Intrinsically safe TypeRefer to each General Specicationsheet.

    Load resistance;See gure 1.

    R=

    250

    600

    10.5 16.6 42

    Power supply voltage E (V DC)

    Communication

    applicable

    range

    F01E.ai

    25.2

    E10.5

    0.0244External

    load

    resistance

    R ()

    Figure 1. Relationship Between Power SupplyVoltage and External Load Resistance

    http://localhost/var/www/apps/conversion/tmp/submenu.htmhttp://localhost/var/www/apps/conversion/index.htmhttp://localhost/var/www/apps/conversion/index.htmhttp://localhost/var/www/apps/conversion/tmp/submenu.htm
  • 8/12/2019 GS01C31T01-01EN (EJA-E Series HART 5 and HART 7 Communication)

    2/4

    2

    All Rights Reserved. Copyright 2012, Yokogawa Electric Corporation

    GS 01C31T01-01EN

    FUNCTIONAL SPECIFICATIONS

    Functional specications for remote setting and monitoring

    ITEM DISPLAY SETTING SUMMARY Factory setting

    Tag Number (Software Tag) Up to 8 alphanumeric characters As specied in order

    Long Tag (Software Tag) Up to 32 alphanumeric characters (HART 7) As specied in order

    Output Mode LINEAR/SQUARE ROOT outputLINEAR unless otherwise

    specied in order

    Display Function LINEAR/SQUARE ROOT displayLINEAR unless otherwise

    specied in order

    Display Mode Input pressure, % of range, User set scale, Inputstatic pressure, or % of static pressure range.

    PRES %

    Damping Adjustment Software damping in 0.00 to 100.00 second 2 s

    Lowest Limit of CalibrationRange

    Pressure equal to 4 mA value. As specied in order

    Highest Limit of CalibrationRange

    Pressure equal to 20 mA value. As specied in order

    Instantaneous Value of Input(Differential Pressure orPressure)

    _ Display actual Differential Pressure or actual

    Pressure._

    Instantaneous Value of Output(Current)

    _ Display actual % of calibrated span or 4-20 mA

    output value._

    Unit of Calibration Range In H2O, in Hg, ftH2O, mmH2O, mmHg, psi, bar,mbar, g/cm2, kg/cm2, Pa, hPa, kPa, MPa,Torr,or atm

    As specied in order

    Constant Current Output 4 to 20 mA DC_

    Self-diagnostic Pressure input outside of range limits, Excessiveambient temperature, or Incorrect rangesetting.

    _

    Advanced Test Output Simulate device variable for xed PV output withltering functions such as damping and low cutmode. (HART 7)

    _

    Burst Mode

    Continuous transmission of following information(Max. three burst messages for HART 7) PV % range/current

    process vars/current process vars/% range/current self diagnosis (HART 7)

    _

    Event Notication Signal transmission triggered by detecting thesetting change or the self-diagnostics as anevent to alarm (HART 7)

    _

    Squawk Identifying the transmitter by displaying theparticular pattern on LCD (HART 7)

    _

    Multidrop Communication _

    Up to 15 (HART 5)/63 (HART 7) transmitters canbe connected. An analog signal output availablefor one device in a loop for HART 7.

    _

    June 20, 2012-00

    http://localhost/var/www/apps/conversion/tmp/submenu.htmhttp://localhost/var/www/apps/conversion/index.htmhttp://localhost/var/www/apps/conversion/index.htmhttp://localhost/var/www/apps/conversion/tmp/submenu.htm
  • 8/12/2019 GS01C31T01-01EN (EJA-E Series HART 5 and HART 7 Communication)

    3/4

    3

    All Rights Reserved. Copyright 2012, Yokogawa Electric Corporation GS 01C31T01-01EN June 20, 2012-00

    MODEL AND SUFFIX CODES

    EJA E-J - /

    Output signal . . . 4 to 20 mA DC with digital communication (HART 5/HART 7 protocol*)

    *: HART 5 or HART 7 selectable. Specify HART 5 or HART 7 when ordering.

    Selection guide for HART 5 and HART 7Select HART 5 or HART 7 according to Table 1.

    Table 1. Selection guide for HART 5 and HART 7

    Specied item when orderingHART protocol revision

    HART protocolrevision

    Selection guide

    NoteRequirement for HART 7functionality

    Specify 5 HART 5Select when HART 7 functionalityis not required.

    Indicate the most typical selection for HARTcommunication. In case of selecting HART 7without conforming to Table 2, communicationwill not be available. Select this when HART 7functionality is not required.

    Specify 7 HART 7

    Select when HART 7 functionalityis required.In this case, be sure to conrmthat HART conguration toolsupports HART 7 by Table 2.

    HART protocol revision and communicationProtocol revision supported by HART conguration tool must be the same or higher than that of the EJA-Etransmitters.HART 7 communication is supported by FieldMate R2.02 or later.

    Table 2. HART protocol revision and communication

    Protocol revision supportedby HART conguration tool

    HART 5 HART 7

    Protocol revision of EJX

    HART 5Communication

    AvailableCommunication

    Available

    HART 7Communication

    Not AvailableCommunication

    Available

    http://localhost/var/www/apps/conversion/tmp/submenu.htmhttp://localhost/var/www/apps/conversion/index.htmhttp://localhost/var/www/apps/conversion/index.htmhttp://localhost/var/www/apps/conversion/tmp/submenu.htm
  • 8/12/2019 GS01C31T01-01EN (EJA-E Series HART 5 and HART 7 Communication)

    4/4

    4

    Subject to change without notice.All Rights Reserved. Copyright 2012, Yokogawa Electric Corporation GS 01C31T01-01EN

    Specify the following when ordering.1. Model, sufx codes, and optional codes2. Calibration range and units: 1) Calibration range can be specied with range

    value specication up to 5 digits (excluding anydecimal point) for low or high range limits within the

    range of -32000 to 32000. 2) Specify only one unit from the above table, Unit ofCalibration Range.

    3. Select linear or square root for output mode anddisplay mode.

    Note: If not specied, the instrument is shipped set forlinear mode

    4. Display scale and units (for transmitters equippedwith the integral indicator only)

    Specify either 0 to 100 % or Range and Unit forengineering units scale:

    Scale range can be specied with range limitspecications up to 5 digits (excluding any decimalpoint) for low or high range limits within the rangeof -32000 to 32000. Unit display consists of 6-digit,therefore, if the specied scaling unit excluding / islonger than 6-characters, the rst 6 characters will bedisplayed on the unit display.

    5. Tag Number (if required) Specify tag number (up to 16 letters) to be engraved

    on the tag plate. The specied letters are written onTag (the rst 8 letters) and Long tag(16 letters)*2inthe amplier memory.

    6. Software tag Specify this software tag when tag number which is

    different from the tag number specied in the Tag

    Number is required. The tag number specied*1inSOFTWARE TAG will be entered on Tag (the rst8 letters) and Long tag (32 letters)*2in the ampliermemory.

    7. HART protocol revision Specify the HART protocol revision 5 or 7.

    *1: Up to 32 characters are specied*2: Applicable only for HART 7

    HART; Trademark of the HART CommunicationFoundation.

    June 20, 2012-00