  • DISAJIKAN DALAM PEMBINAAN PENGELOLAAN HANDAK MIGAS

    OLEH

    ST. SUHARTO SAHERO

  • HANDAK HARUS DISIMPAN DI DALAM GUDANG YANG SESUAI DAN, MEMENUHI :

    PERATURAN PERUNDANG-UNDANG YANG BERLAKU

    KAIDAH KESELAMATAN

    KAIDAH KEAMANAN

    STANDAR DAN KAIDAH KETEKNIKAN YANG BAIK

  • UU No. 22 Th. 2001

    MIJN POLITIE REGLEMENT stbl.1930 No 341

    PERATURAN PEMERINTAH No. 17 TAHUN 1974

    ORDONANSI BAHAN PELEDAK LN. 1931 No. 168

    PPS -12 Th. 1972, TENTANG KETENTUAN PELAKSANAAN UMUM ATAS OPERASI PERMINYAKAN DI DAERAH LEPAS PANTAI MENGENAI PENYIMPANAN BAHAN PELEDAK PADA INSTALASI PEMBORAN

    JUKLAK KAPOLRI No. Pol : Juklak/29/VII/1991 tanggal 23 Juli 1991, TENTANG PENGAWASAN, PENGENDALIAN DAN PENGAMANAN BAHAN PELEDAK NON ORGANIK ABRI.

  • TENTANG MINYAK DAN GAS BUMI, PASAL 40,

    BU atau BUT MENJAMIN KESELAMATAN DAN KESEHATAN

    KERJA SERTA PENGELOLAAN LINGKUNGAN HIDUP

    PEMBINAAN DAN PENGAWASAN OLEH MENTERI ESDM

  • TENTANG KESELAMATAN DAN KESEHATAN KERJA TAMBANG

    TAMBANG TERMASUK PERTAMBANGAN MINYAK DAN GAS BUMI

    BAHAN PELEDAK DIATUR DALAM PASAL 102 sd 122

    (KEPMEN PE NO. 555.K/26/MPE/1995)

  • KONSTRUKSI GUDANG

    ACUAN YANG DIPERGUNAKAN, ANTARA LAIN:

    - MIJN POLITIE REGLEMENT No. 341 TAHUN 1930(KEPMEN PE NO. 555.K/26/MPE/1995, KESELAMATAN DAN KESEHATAN KERJA PERTAMBANGAN UMUM)

    - KK-03-DJM (PEDOMAN PELAKSANAAN PENANGANAN BAHAN PELADAK YANG AMAN DI INDONESIA, DPE DITJEN MIGAS)

    - SNI 19-3996-1995 (PEDOMAN K3 PENYIMPANAN DAN PENANGANAN BAHAN PELEDAK)

    - NFPA 495 (EXPLOSIVE MATERIALS CODE, NATIONAL FIRE PROTECTION ASSOCIATION, INC.)

    - STANDAR-STANDAR LAIN YANG BERLAKU SECARA INTERNASIONAL

    - IME CONSTRUCTION GUIDE FOR EXPLOSIVES MAGAZINES

  • DIBEDAKAN BERDASARKAN LOKASI

    DI ATAS TANAH

    DI BAWAH TANAH

    TEMPAT PENIMBUN PEMBANTU DI BAWAH TANAH

    DISETUJUI OLEH KEPALA INSPEKSI TAMBANG

    gudang handak MPR 1930/341

  • TEMPAT PENIMBUNAN DI ATAS TANAH UNTUK JUMLAH > 50 KG

    DINDING TIDAK MUDAH TERBAKAR

    ATAP SERINGAN MUNGKIN

    MEMILIKI DUA RUANGAN (PENIMBUNAN DAN PENGELUARAN) DENGAN SATU JALAN MASUK

    DILINDUNGI TANGKAL KILAT

    DILENGKAPI VENTILASI

    BILA DILENGKAPI TANGGUL, JARAK AMAN DAPAT DIKURANGI SEPARONYA DAN DAPAT DIPERKECIL LAGI MENJADI SEPEREMPAT

    DENGAN PERTIMBANGAN KEPALA INSPEKSI TAMBANG.

    gudang handak MPR 1930/341

  • (PEDOMAN PELAKSANAAN PENANGANAN BAHAN PELEDAK YANG AMAN DI INDONESIA, (DITJEN MIGAS - 1994)

    KETENTUAN UMUM

    TAHAN PELURU

    TAHAN CUACA

    TAHAN API

    TAHAN PENCURI

  • GUDANG HANDAK (KK-03-DJM)

    GUDANG PERMANEN

    GUDANG SEMENTARA

    GUDANG SEMENTARA BERBENTUK KONTAINER

  • GUDANG PERMANEN

    BANGUNAN TERDIRI DARI 2 KAMAR, UNTUK PEMASUKAN / PENGELUARAN DAN PENYIMPANAN.

    GUDANG TERLETAK PADA TEMPAT KERING DAN DENGAN SISTEM DRAINASIYG BAIK.

    PONDASI PASANGAN BATU KALI

    RANGKA BANGUNAN BETON BERTULANG / PROFIL BAJA

    RANGKA ATAP PROFIL BAJA, BAGIAN DALAM ATAP DILENGKAPI PALANG PENGAMAN UNTUK MENCEGAH MASUKNYA ORANG.

    DINDING PASANGAN BATU BATA PADAT TEBAL NOMINAL 20 CM

    GUDANG HANDAK (KK-03-DJM)

  • GUDANG HANDAK (KK-03-DJM)

    ATAP BAHAN ASBES / SENG

    LANTAI BETON COR,

    SATU BUAH DAUN PINTU DENGAN RANGKA PROFIL BAJA, DILAPIS PLAT BAJA TEBAL MIN. 3 MM DAN MEMBUKA KELUAR. PINTU DILENGKAPI 3 (TIGA) BUAH GEMBOK.

    VENTILASI HARUS DIPASANG PADA DINDING BAGIAN BAWAH DAN SISI ATAS DEKAT ATAP ATAU DI BAGIAN ATAP.

    TINGGI LUBANG VENTILASI 25 CM SUHU DALAM GUDANG HARUS DIJAGA TIDAK LEBIH DARI 35 C

    PENANGKAL PETIR HARUS DITEMPATKAN SECARA TERPISAH DARI KONSTRUKSI GUDANG HANDAK PADA JARAK MINIMUM 1,80 M. RESISTENSI PEMBUMIAN < 5 KECUALI BILA DIRANCANG UNTUK MENAMPUNG JUMLAH KECIL (< 25 KG) TIDAK PERLU PENANGKAL PETIR.

  • GUDANG HANDAK (KK-03-DJM)

    TANGGUL TANAH BERBENTUK TRAPESIUM HARUS DIBUAT DISEKELILING GUDANG,

    TINGGI MIN. 2,0 M DAN LEBAR BAGIAN ATAS 1,0 M. JALAN MASUK TIDAK BOLEH BERHADAPAN LANGSUNG DENGAN PINTU GUDANG.

    SEKELILING BANGUNAN GUDANG DIPAGAR SETINGGI MIN. 2,50 M DAN DIATASNYA DIBERI KAWAT BERDURI.

    POS DAN MENARA JAGA HARUS TERLETAK DI BAGIAN LUAR DAERAH YANG DIPAGAR.

    GENERATOR DIESEL UNTUK PENERANGAN DI TEMPATKAN > 15 M DARI GUDANG

  • GUDANG HANDAK (KK-03-DJM)K

    GUDANG SEMENTARA

    SAMA DENGAN GUDANG PERMANEN KECUALI DINDING DAPAT DIBUAT DARI PLAT TEBAL 1 MM DENGAN BAGIAN DALAM DILAPIS DENGAN PAPAN KAYU TEBAL 3-5 MM.

    GUDANG SEMENTARA BERBENTUK KONTAINER

    DINDING TERBUAT DARI PELAT BESI TEBAL MINIMUM 3 MM DENGAN BAGIAN DALAM DILAPIS PAPAN KAYU TEBAL 3-5 MM.

  • (EXPLOSIVE MATERIALS CODE)

    BANGUNAN ATAU STRUKTUR YANG DIIZINKAN SEBAGAI GUDANG BAHAN PELEDAK, SELAIN BANGUNAN YANG DIPERGUNAKAN OLEH PABRIK BAHAN PELEDAK

  • MEMPERTIMBANGKAN ASPEK KESELAMATAN DAN KEAMANAN.

    HANDAK YANG DIKLASIFIKASIKAN SEBAGAI HIGH EXPLOSIVES HARUS DISIMPAN DALAM GUDANG TIPE 1, 2 ATAU 3

    TIPE 1, GUDANG PERMANENTIPE 2, GUDANG PORTABLE DAN MOBILE INDOOR/OUTDOORTIPE 3, GUDANG UNTUK PENYIMPANAN TERJAGA

    GUDANG YANG BERISI EXPLOSIVE MATERIAL HARUS DIBUKA DAN DIINSPEKSI SETIAP 3 HARI SEKALI

    PINTU GUDANG HARUS SELALU TERKUNCI.

    KETENTUAN KESELAMATAN PENGOPERASIAN GUDANG HARUS DITEMPEL DIBAGIAN LUAR GUDANG

    GUDANG NFPA 495

  • LAMPU PENERANGAN, LAMPU SOROT ATAU LENTERA KESELAMATAN ELEKTRIK DAPAT DIPERGUNAKAN DALAM GUDANG HARUS MEMENUHI KETENTUAN NFPA 70.

    DRAINASI SEKITAR GUDANG HARUS CUKUP BAIK.

    TIDAK BOLEH ADA FERROUS METAL YANG TEREKSPOSE DI DALAM GUDANG

    LANTAI DARI BAHAN YANG TIDAK MENIMBULKAN PERCIKAN API

    KETENTUAN UMUM GUDANG NFPA 495

  • TYPE 1 KONSTRUKSI HARUS PERMANEN SEPERTI HALNYA BANGUNAN GEDUNG ATAU IGLOO, YANG TAHAN TERHADAP PELURU, API, PENCURIAN, PERUBAHAN MUSIM DAN BERVENTILASI.

    TIPE 2 STRUKTUR PORTABLE ATAU MOBILE SEPERTI HALNYA BOX, GUDANG DIATAS SKID, TRAILER ATAU SEMI TRAILER YANG TAHAN TERHADAP API, PENCURIAN, PERUBAHAN MUSIM, DAN BERVENTILASI.

    BERDASARKAN PENGGUNAANNYA DIBEDAKAN MENJADI 2 TIPE (OUTDOOR DAN INDOOR)

    TIPE 3 STRUKTUR PORTABLE ATAU SERING DISEBUT DAY BOX DIPERGUNAKAN UNTUK TEMPAT PENYIMPANAN SEMENTARA.

    TIPE 3 INI HARUS TAHAN API, PENCURIAN DAN PERUBAHAN MUSIM. (TIDAK HARUS TAHAN PELURU)

    DALAM KONDISI TERISI HANDAK GUDANG TIPE 3 HARUS DALAM KONDISI TERJAGA.

    TIPE SPESIFIK . . . . . . . . . . .

  • TIPE GUDANG SPESIFIK . . . .

    TYPE 4 HARUS PERMANEN, PORTABLE ATAU STRUKTUR YANG DAPAT BERGERAK SEPERTI HALNYA BANGUNAN, IGLOO, BOX, SEMI TRAILLER ATAU MOBIL CONTAINER LAINNYA YANG TAHAN TERHADAP API, PENCURIAN DAN PERUBAHAN CUACA.

    (TIDAK HARUS TAHAN PELURU)

    TIPE 5 - HARUS PERMANEN, PORTABLE ATAU STRUKTUR YANG DAPAT BERGERAK SEPERTI HALNYA BANGUNAN, IGLOO, BOX, KERANJANG, TANGKI, SEMI TRAILER, BULK TRAILER, TANK TRAILER, BULK TRUCK, TANK TRUCK ATAU MOBIL CONTAINER LAINNYA YANG HARUS TAHAN TERHADAP PENCURIAN.

    VENTILASI TIDAK DIPERLUKAN, DAN BAHAN-BAHAN FERROUS

    METAL TIDAK PERLU DILAPISI DENGAN MATERIAL NON- SPARKING.

  • DINDING DAN PINTU HARUS TAHAN PELURU

    ATAP BAGIAN LUAR HARUS TAHAN API

    APABILA GUDANG DIBUAT DI DEKAT LERENG, MAKA ATAP ATAU LANGIT-LANGIT HARUS

    DIBUAT DARI KONSTRUKSI TAHAN PELURU.

    PONDASI DAPAT DIBUAT DARI PASANGAN BATU ATAU BETON, KAYU ATAU METAL DAN HARUS DIBUAT SEPANJANG DINDING.APABILA MENGGUNAKAN PONDASI KAYU BAGIAN LUAR HARUS DILAPIS DENGAN METAL.

  • Sumber: Construction Guide for Storage Magazine - IME

  • Exteriors of Steel

    Sumber: Construction Guide for Storage Magazine - IME

  • KONSTRUKSI TIPE 1

    LANTAI HARUS DIBUAT DARI KAYU ATAU MATERIAL LAIN YANG SESUAI.

    LANTAI YANG DIBUAT DARI MATERIAL YANG MUNGKIN DAPAT MENIMBULKAN PERCIKAN API HARUS DILAPIS BAHAN PERMUKAAN YANG NONSPARKING ATAU PAKET-PAKET EXPLOSIVE HARUS DITEMPATKAN PADA PALET YANG TERBUAT DARI MATERIAL YANG TIDAK DAPAT MENIMBULKAN PERCIKAN API.

    MEMPUNYAI VENTILASI UNTUK MENCEGAH KELEMBABAN DANPEMANASAN MATERIAL EKSPLOSIVE.

    BUKAAN VENTILASI HARUS DIBERI KASA UNTUK MENCEGAH MASUKNYA BINATANG ATAU BUNGA API.

    DILETAKKAN PADA DINDING SISI BAWAH DAN DI BAGIAN ATAP ATAU DINDING SISI ATAS.

    LAPISAN KISI-KISI DIPASANG PADA BAGIAN DALAM, TIRAI PELINDUNG UNTUK MENCEGAH MASUKNYA BINATANG PENGERAT

    TINGGI LUBANG VENTILASI UMUMNYA 25 CM.

  • Sumber: Guide to the Safe Storage of Explosive Materials - IME

  • DUA KUNCI PINTU TANAM (MORTISE LOCK), ATAU

    DUA GEMBOK GANTUNG (PADLOCK) DENGAN DUA SANGKUTAN (HASPS AND STAPLES), YANG TERPISAH ATAU

    SATU KUNCI PINTU TANAM DAN SATU GEMBOK GANTUNG, ATAU

    SATU KUNCI PINTU TANAM YANG MENGGUNAKAN DUA KUNCI UNTUKMEMBUKA.

    THREE-POINT LOCK ATAU YANG SETARA YANG DAPAT MENGUNCI PINTU PADA RANGKANYA LEBIH DARI SATU TITIK

    KUNCI GEMBOK GANTUNG HARUS BAJA, MEMPUNYAI LIMA PASAK DAN SHACKLE DARI CASE-HARDENED 9.5 MM (3/8-IN.).

    SETIAP PINTU HARUS DILENGKAPI DENGAN SISTEM PENGUNCI

  • GUDANG DI LUAR, (OUTDOOR)

    KETENTUAN TAHAN PELURU UNTUK TIPE 2 OUTDOOR, ANTARA LAIN DINDING BAGIAN LUAR DAN PINTU HARUS DIBUAT DARI BAJA TEBAL MINIMUM 0,25 inch DAN DILAPIS SEKURANG-KURANGNYA 2 inch HARDWOOD.

    LANTAI DIBUAT DARI BAJA (FERROUS METAL) DAN HARUS DILAPIS DENGAN BAHAN PERMUKAAN YANG NON SPRAKING.

    GUDANG HARUS DISANGGA SEDEMIKIAN HINGGA LANTAI TIDAK LANGSUNG BERHUBUNGAN DENGAN TANAH.

    GUDANG DENGAN VOLUME < 0.766 m (1 yd) HARUS DIIKAT ERAT DENGAN OBJEK TETAP

    PENGUNCI SESUAI DENGAN GUDANG TIPE 1.

  • Sumber: http://www.walkersholdings.com/mags.htm

  • This Type 2 Explosives Magazine is a 900 square foot, modular design with double doors

    on one side. Some notable features are the arched roof, which eliminates the possibility of

    standing water; and our state of the art design with all supporting structural steel inside the

    walls. This feature provides a smooth exterior surface that can be coated completely. These

    features are directly responsible for our claim of double the service life of standard industry

    magazines.

    Sumber : USAexplosives.com

  • DI DALAM GEDUNG (INDOOR)

    GUDANG HARUS MEMILIKI RODA AGAR DAPAT DIPINDAHKAN DARI DALAM GEDUNG BILA KEADAAN DARURAT

    GUDANG DAPAT DIBUAT DARI KAYU KERAS TEBAL 51 MM (2 IN.), HARUS DILAPIS SEKURANG-KURANGNYA 26 gauge-SHEET METAL

    GUDANG YANG DIBUAT DARI METAL (12 gauge-SHEET METAL) HARUS DILAPIS DENGAN NON-SPARKING MATERIAL

    GUDANG TIPE 2 INDOOR TIDAK PERLU TAHAN PELURU APABILA BANGUNAN DIMANA GUDANG INI DISIMPAN TELAH DIKONSTRUKSI TAHAN DARI PENETRASI PELURU

  • DIBUAT DARI KONSTRUKSI BAJA

    SEKURANG-KURANGNYA 12-gauge

    STELL PLATE (2.66 mm), DILAPIS

    DENGAN PLYWOOD ATAU HARDBOAD

    TIPE MASONITE TEBAL 12.7 mm.

    PINTU DILENGKAPI DENGAN SATU

    KUNCI GEMBOK YANG MEMILIKI 5 GIGI

    DAN SHACKLE CASE-HARDENED STEEL

    9.5 mm

    ENGSEL PINTU HARUS DILAS ATAU

    DIKELING ATAU DIBAUT DENGAN MUR

    DI DALAM.

  • GUDANG HANDAK MENURUT NFPA 495

    CLASSIFICATION AND USE OF

    MAGAZINES / CONSTRUCTION

    FEATURES

    MAGAZINE TYPE

    1 2 3 4 5

    PERMANENT

    PORTABLE

    BULLET RESISTANT

    FIRE RESISTANT

    THEFT RESISTANT

    WEATHER RESISTANT

    VENTILATED

    X

    X

    X

    X

    X

    X

    X

    X

    X

    X

    X

    X

    X

    X

    X

    X

    X

    X

    X

    X

    X

    X

    X

    X

    X

    X

    X

    X

    X

    OVER-THE-ROAD TRUCKS OR SEMITRAILERS USED FOR TEMPORARY STORAGE AS TYPE 4 OR TYPE 5

    MAGAZINES SHALL NOT BE REQUIRED TO BE FIRE RESISTANT OR VENTILATED

    EACH DOOR OF A MOBILE TYPE 5 MAGAZINE SHALL BE EQUIPPED WITH AT LEAST ONE FIVE-TUMBLER

    PADLOCK HAVING A 9.5 MM (3/8 IN.) CASE-HARDENED SHACKLE. THE LOCK SHALL NOT BE REQUIRED

    TO BE HOODED.

    SUMBER NFPA 495, EXPLOSIVE MATERIALS CODE, 2010

  • KETENTUAN DINDING TAHAN PELURU

    (TAHAN PELURU = HARUS DAPAT MENAHAN PENETRASI PELURU DARI 150-GRAIN M2 YANG MEMPUNYAI KECEPATAN 824 MPS BILA DITEMBAKKAN DARI SENAPAN KALIBER 0.30 DARI JARAK 30.5 M (100 FT) TEGAK LURUS KE DINDING ATAU PINTU)

    STEEL EXTERIOR

    15.9 MM (5/8 IN.) STEEL WITH AN INTERIOR LINING OF NON SPARKING MATERIAL

    12.7 MM (1/2 IN.) STEEL WITH AN INTERIOR LINING OF PLYWOOD AT LEAST 9.5 MM (3/8 IN.) THICK

    9.5 MM (3/8 IN.) STEEL LINED WITH, 0NE OF THE FOLLOWING :

    - 50.8 MM (2 IN.) OF HARDWOOD- 76.2 MM (3 IN.) OF SOFTWOOD- 57.1 MM (2 IN.) OF PLYWOOD

    6.3 MM (1/4 IN.) STEEL LINED WITH, 0NE OF THE FOLLOWING :

    - 76.2 MM (3 IN.) OF HARDWOOD- 127 MM (5 IN.) OF SOFTWOOD- 133.3 MM (5 IN.) OF PLYWOOD- 38.1 MM (1 IN.) OF PLYWOOD WITH AN INTERMEDIATE LAYER OF 50.8 MM (2 IN.) OF HARDWOOD

  • KETENTUAN TAHAN PELURU, STEEL EXTERIOR

    4.8 MM (3/16 IN.) STEEL LINED WITH, 0NE OF THE FOLLOWING :

    - 101.6 MM (4 IN.) OF HARDWOOD

    - 177.8 MM (7 IN.) OF SOFTWOOD

    - 171.5 MM (6 IN.) OF PLYWOOD

    - 19 MM ( IN.) OF PLYWOOD WITH AN INTERMEDIATE LAYER OF 76.2 MM (3 IN.) OF HARDWOOD

    3.2 MM (1/8 IN.) STEEL LINED WITH, 0NE OF THE FOLLOWING :

    - 127 MM (5 IN.) OF HARDWOOD

    - 228.6 MM (9 IN.) OF SOFTWOOD

    - 19 MM ( IN.) OF PLYWOOD WITH AN INTERMEDIATE LAYER OF 101.6 MM (4 IN.) OF HHARDWOOD

    - TWO LAYER OF 19 MM ( IN.) PLYWOOD WITH AN INTERMEDIATE LAYER OF 92.1 MM ( 3 5/8 IN.) OF WELL-TAMPED DRY SAND OR SAND / CEMENT MIXTURE.

    Sumber: Construction Guide of Storage Magazine IME / NFPA 495

  • KETENTUAN DINDING TAHAN PELURU

    MASONRY EXTERIOR

    STANDARD 203.2 MM (8-IN.) CONCRETE BLOCK WITH VOIDS FILLED WITH WELL-TAMPED DRY SAND OR SAND /CEMENT MIXTURE

    STANDARD 203.2 MM (8-IN.) SOLID BRICK

    203.2 MM (8-IN.) SOLID CONCRETE

    TWO LAYERS OF 101.6 MM (4-IN.) CONCRETE BLOCK.

    SUMBER NFPA 495

  • KETENTUAN DINDING TAHAN PELURU

    FIRE-RESISTANT EXTERIOR

    THE EXTERIOR OF ANY TYPE OF FIRE-RESISTANT MATERIAL, WITH FOLLOWING

    - AN INTERIOR LINING OF 12.7 MM ( IN.) PLYWOOD PLACED SECURELY AGAINST AN INTERMEDIATE 101.6 MM (4-IN.) THICK LAYER OF SOLID CONCRETE BLOCK, SOLID-BRICK, OR SOLID CONCRETE.

    - AN INTERIOR LINING OF 19 MM ( IN.) PLYWOOD; A FIRST INTERMEDIATE LAYER OF 19 MM ( IN.) PLYWOOD, A SECOND INTERMEDIATE LAYER (3 5/8-IN.) WELL TAMPED DRY SAND OR SAND / CEMENT MIXTURE; A THIRD INTERMEDIATE LAYER OF 19 MM ( IN.) PLYWOOD; AND FOURTH INTERMEDIATE LAYER OF 50.8 MM (2-IN.) HARDWOOD OR 14 GAUGE STELL.

    - AN INTERMEDIATE (16-IN.) SPACE FILLED WITH WELL-TAMPED DRY SAND OR SAND /

    CEMENT MIXTURE.

  • - SEBAIKNYA PADA TANAH RATA DENGAN SISTIM DRAINASI YANG BAIK

    - SEMUA GUDANG KECUALI TIPE 3 HARUS MEMENUHI PERSYARATAN JARAK AMAN TERHADAP FASILITAS LAIN

  • CUPLIKAN DARI AMERICAN TABLE OF DISTANCE UNTUK

    GUDANG HANDAK

    BERAT HANDAK

    (KG)

    JARAK AMAN, DALAM METER

    GEDUNG YG

    DIHUNI

    JALA N KEND

    RAYA 3000/Hr

    GUDANG

    HANDAK YG

    LAIN

    15 - 20

    35 - 50

    80 - 100

    200 - 250

    450 - 500

    900 - 1.100

    2.300 - 2.800

    4.900 - 5.550

    10.000 - 12.000

    43,6

    58,2

    74,8

    100

    129

    165

    223

    277

    331

    87,8

    129

    158

    201

    252

    329

    449

    554

    610

    17,2

    23,0

    30,6

    40,2

    50,2

    57,8

    71,8

    83,1

    99,1

    34,5

    46,0

    61,1

    80,5

    100

    115

    144

    166

    198

    32,0

    42,7

    55,6

    74,4

    96,5

    124

    167

    214

    274

    64,1

    85,3

    111

    149

    193

    246

    334

    428

    548

    3,8

    4,9

    6,7

    9,1

    11,8

    14,5

    19,9

    25,8

    32,9

    7,7

    9,9

    13,4

    18,2

    23,6

    29,5

    39,8

    51,6

    65,8

    1. JARAK AMAN UNTUK INSTALASI GUDANG, GUDANG TIPE 3 TIDAK BERLAKU KETENTUAN INI.

    2. CUPLIKAN TABEL DARI NFPA 495, EDISI 2010

    APABILA KETENTUAN JARAK AMAN TIDAK DAPAT TERPENUHI, DAPAT MENGGUNAKAN

    QUANTITATIVE-RISK-ASSESMENT (QRA)

  • LAMPU PENERANGAN DIBUAT DI SETIAP SUDUT PAGAR

    GENERATOR UNTUK PENERANGAN DI TEMPATKAN MINIMUM 15 M DARI GUDANG

    INSTALASI LISTRIK HARUS MEMENUHI KETENTUAN NFPA 70, SEMUA STOP KONTAK DIPASANG DI LUAR GUDANG SEKURANG-KURANGNYA 7,6 M (25 ft).

    ELECTRIC SAFETY LANTERNS ATAU ELECTRIC SAFETY FLASHLIGHTS DAPAT DIPERGUNAKAN DI DALAM GUDANG (NFPA 495)

  • GUDANG HARUS DILENGKAPI DENGAN PENANGKAL PETIR DENGAN TAHANAN PENTANAHAN MAKSIMUM 5 OHM. PENANGKAL PETIR DITEMPATKAN TERPISAH DARI KONSTRUKSI GUDANG PADA JARAK MINIMUM 1,8 M. PENTANAHAN HARUS DIPERIKSA MINIMUM 6 BULAN SEKALI. (kk-03-djm)

    PENANGKAL PETIR DAPAT DIBUAT MENGACU KEPADA NFPA 780

    IME DAN NFPA - BONDING DAN GROUNDING UNTUK GUDANG BAHAN PELEDAK TIDAK DIPERLUKAN KECUALI UNTUK GUDANG YANG DIBUAT DARI METAL

  • BARRICADE ATAU TANGGUL, DIBUAT UNTUK MEMISAHKAN GUDANG YANG TERISI BAHAN PELEDAK DENGAN GUDANG YANG LAIN, BANGUNAN, JALAN RAYA ATAU REL KERETA API YANG DAPAT DIBUAT DARI TIMBUNAN TANAH BERBENTUK TRAPESIUM ATAU TANGGUL ARTIFICIAL :

    TANGGUL TANAH DAPAT DIMODIFIKASI DENGAN KONSTRUKSI TEMBOK PENAHAN DENGAN SLOP PADA SATU SISI ATAU TIPE LAIN.

    JALAN MASUK TIDAK BOLEH BERHADAPAN LANGSUNG DENGAN PINTU GUDANG.

    TANGGUL HARUS TERPISAH DARI GUDANG.

    GUDANG YANG TERTUTUP TANAH TIDAK DAPAT DIPERHITUNGKAN SEBAGAI TANGGUL. (27CFR555)

  • TANGGUL TANAH YANG DIBUAT TIMBUNAN TANAH BERBENTUK TRAPESIUM :

    HARUS DIBUAT DARI MATERIAL TANAH YANG KOHESIVE DAN DIPADATKAN,

    BEBAS DARI BAHAN ORGANIK, KOTORAN / SAMPAH

    BATUAN YANG LEBIH BERAT DARI 5 KG ATAU LEBIH BESAR DARI 15 CM TIDAK DIIZINKAN.

    BAGIAN PERMUKAAN HARUS DIBUAT SEDEMIKIAN UNTUK MENCEGAH EROSI

    TINGGI TANGGUL MIN. 2 M DAN 20 CM DI ATAS TIMBUNAN HANDAK

    UNTUK TINGGI < 6 M (20 FT) -- CREST / BERM > 3 FT

    > 6 M (20 FT) -- CREST / BERM > 5 FT.

    TANGGUL TANAH DAPAT DIMODIFIKASI DENGAN KONSTRUKSI TEMBOK PENAHAN DENGAN SLOP PADA SATU SISI ATAU TIPE LAIN.

  • Barricading can significantly reduce the required minimum

    distances under some Tables of Distances.

    Sumber: http://www.atf.gov/explosives/how-to/explosive-storage-

    requirements.html

  • BARRICADES / TANGGUL

    2

    CREST MIN. 3 FT.

    SUMBER AF REGULATION 127-100, US AIR FORCE

  • BARRICADES / TANGGUL

    2

    CREST MIN. 3 FT.

  • STACK

    STACK

  • 'Bunker' to the west of the high explosive magazines - Lords Bridge Air Ammunition Park

    This was built in the late 1980s to house the COAST telescope.

    The earth cover was provided to reduce temperature fluctuations inside.

    Photo by Nick Catford

    Sumber: http://www.subbrit.org.uk

  • KESIMPULAN

    BU / BUT WAJIB MENJAMIN KESELAMATAN, KESEHATAN KERJA DAN PENGELOLAAN LINGKUNGAN HIDUP (UU No. 22 Th. 2001)

    DALAM MEMBANGUN GUDANG HANDAK, HARUS MEMPERHATIKAN KAIDAH KESELAMATAN (KONSTRUKSI, JARAK AMAN, INSPEKSI), STANDAR DAN KAIDAH KETEKNIKAN YANG BAIK SERTA MENDAPAT

    PERSETUJUAN KEPALA INSPEKSI TAMBANG MIGAS

    STANDAR INTERNASIONAL DAPAT DIACU