28
ALRAR INLET SEPERATION AND BOOSTING FACILITIES,ALGERIA PETROFAC PROJECT NO. : JI-2020 HV & MV CABLE SIZING B1 Issued For Client Approval MVG MJ KJ / VSB KRM/MTS Rev Date Reason for Issue Prepared By Checked By Approved by Project Approval Project Code Discipline Code Document Type Sequence No Bilingual Identifier Rev. J08423A E AC 15051 B1

Hv & Mv Cable Sizing

Embed Size (px)

DESCRIPTION

HV & MV CABLE SIZING, ELECTRICAL CABLE SIZING

Citation preview

HV & MV CABLE SIZINGJ08423A-E-AC-15051, REV B1.__________________________________________________________________________________________

ALRAR INLET SEPERATION AND BOOSTING FACILITIES,ALGERIAPETROFAC PROJECT NO. : JI-2020

HV & MV CABLE SIZING

B1Issued For Client ApprovalMVGMJKJ / VSBKRM/MTS

RevDateReason for IssuePrepared ByChecked ByApproved byProject Approval

Project CodeDiscipline CodeDocument TypeSequence NoBilingualIdentifierRev.

J08423AEAC15051B1

Bir Seba Field DevelopmentDoc. No.:PVEP-ALG-BRS-PR-G-401

STANDARD DOCUMENT FORMATDate:28 July 2008

Rev.:Q1

REVISION HISTORYRev.SectionDescription of Revision

B1

B1

B1

B1

B1

B1

B1

B1

B1

B1

HOLDS

HoldSectionDescription of Hold

TABLE OF CONTENTSGLOSSARY41CODES AND STANDARDS61.1General61.2Order of Precedence61.3Algerian Government Requirements61.4Project Documents61.5International Codes and Standards62SCOPE83NOTES94GENERAL CRITERIA104.1Site Conditions104.2Cable Parameters104.2.166kV Power Cables104.2.25.5kV Power Cables116 ALLOWABLE VOLTAGE DROPS127CABLE derating factors137.1HV cable Derating Factors137.2MV cable Derating Factors147.2.1Laying Conditions: Laid in Air147.2.2Laying Conditions: Buried in trench168CABLE SIZING CALCULATIONS198.1Basis for Calculations198.266kV Cable Sizing208.35.5kV Cable Sizing20

GLOSSARYA.C.Alternating CurrentCDegrees CentigradeAWA Aluminium Wire ArmourCAContracting AuthorityEIEnergy InstituteEPCEngineering, Procurement and ConstructionEMCElectromagnetic CompatibilityGISGas Insulated Switchgearhhour (60 minutes)H.V.High Voltage M.V.Medium Voltage HzHertz (frequency)IECInternational Electrotechnical CommissionIPIngress ProtectionISOInternational Standards OrganisationkgkilogrammekmkilometrekWkilowattmmetrep.f.Power FactorS.I.Le Systeme International dUnites (metric system)SPLSound Pressure LevelVVoltsWWattsXLPE Cross-Linked Polyethylene

CODES AND STANDARDSProject DocumentsProject Documents consist of the following:Document NumberDescription

J08423A-E-PH-15001Electrical Design Philosophy

J08423A-E-SP-15110Electrical Power & Control Cable Specification

International Codes and StandardsThe Codes & Standards referred in order to perform the cable sizing calculations are as listed below:Document NumberDescription

IEC 60183Guide to the Selection of High-Voltage Cables

IEC 60228Conductors of Insulated Cables

IEC 60287Electrical cables - calculation of the current rating

IEC 60331Test on Electric Cables under Fire Conditions - Circuit Integrity

IEC 60332Test on Electric Cables under Fire Conditions

IEC 60502 All partsPower Cables with Extruded Insulation

IEC 60364Electrical Installations of Buildings

SCOPE The document covers the sizing of all HV (66kV) & MV (5.5kV) cables used in electrical power distribution.The purpose of this document is to determine the Electrical HV & MV Cable sizes Vis-a-Vis the installation methods used in Alrar Inlet Separation and Boosting facilities Project in Algeria.

GENERAL CRITERIASite ConditionsThe following outdoor site conditions have been used as the basis for cable sizing:Maximum Ambient Air Temperature + 55 C

Minimum Ambient Air Temperature - 5 C

Normal Design Temperature + 55 C

Soil Temperature + 35 C

Soil Thermal Resistivity 2.5 K-m/W (Hold- 1)

Depth of laying for HV & MV cables 1000 mm

Cable Parameters66kV Power CablesCable Type:XLPE/PVC/AWA/PVC 66kV rating flame retardant for single coreRated Voltage:38 / 66kV System Voltage:66kV: 3 phase, 3 wires A.C.Service:Power distribution Construction:Conductors;Annealed stranded plain copper (Class 2), compacted circular or milliken (segmented compacted circular)Core Screen:Extruded, non-metallic, semi-conducting compoundInsulation:XLPEInsulation Screen:Semi-conducting compoundMetallic Screen:Corrugated aluminium or lead alloy Core Identification:1 core = BlackRadial Water Barrier:Semi conducting non-woven water swellable tapeLaying Up:Cores to be laid up together with non-hygroscopic fillersArmouring:Single layer aluminium wire armour.Over sheath:Extruded PVC or XLPE Colour = redFire Performance:Cable shall meet the requirements of IEC 60332-1 and IEC 60332-3-22 (category C)

5.5kV Power CablesCable Type:XLPE/PVC/SWA/PVC 6.6kV rating flame retardant for multi core cables & XLPE/PVC/AWA/PVC 6.6kV rating flame retardant for single core cables.Rated Voltage:3.8 / 6.6kV System Voltage:5.5kV: 3 phase, 3 wires A.C., high resistance earthedService:Power distribution Construction:Conductors;Annealed stranded plain copper (Class 2), circular or shaped sectionCore Screen:Extruded, non-metallic, semi-conducting tape in combination with a copper tape of 3mm thicknessInsulation:XLPEInsulation Screen:Semi-conducting layer: Extruded, cold strippableMetal layer: Copper tape or wireCore Identification:1 core = black3 core = brown, black, grey. Coloured strips will be used under copper tape screen. Natural colour of outer semi conductor material is BlackLaying Up:Cores to be laid up together with non-hygroscopic fillersBedding:Extruded PVC Armouring:Multi core cables - single layer of galvanised steel wire armour. Single core cables - single layer of non-magnetic aluminium wiresOver sheath:Extruded PVC Colour = redFire Performance:Cable shall meet the requirements of IEC 60332 part1 and IEC 60332 part 3 category C (and have an acid gas emission of not greater than 17% and oxygen index of 30% (minimum)Comment:Cable shall be suitable for use on a system which, under fault conditions, is operated for a short time with one phase earthed, provided it does not exceed 8 hours on any single occasion and a total duration of 125 hours during any 12 month period.

Limiting / Permissible (Max.) conductor temperature under rated current carrying conditions: 90CLimiting / Permissible (Max.) conductor temperature under short circuit conditions: 250C

6 ALLOWABLE VOLTAGE DROPSPermissible Cable Voltage DropsFeedersFrom GIS (HV SWGR) to Transformer : 1% of supply voltageFrom MV SWGR to Transformer : 1% of supply voltageMotor Feeders (under motor rated conditions)Under Running Conditions (from MV SWGR to Motor) : 5% of motor rated voltageUnder Starting Conditions (from MV SWGR to Motor) : 15% of motor rated voltage

1. CABLE SIZING PHILOSOPHYSizing CriteriaCable sizing shall take into account the following parameters:a)Current carrying capacity of cable. b)De-rating factors for current carrying capacities depending on cable type and method of installation.c)Voltage drop in the cable/circuit run.d)Short circuit withstand capacity of cable.Current Carrying CapacityCurrent ratings for cables installed In Air, Direct Buried and In single Way Ducts, are detailed in the HV & MV Cable Data Sheets J08423A-E-DS-15210 &. The maximum continuous current ratings detailed in the Electrical Cable Data Sheets take into consideration the following cable derating factors:a. Cables installed In Air Ambient Temperature Grouping of cablesb. Cables Direct Buried Ground Temperature Depth of Laying Thermal Resistivity of Soil Grouping of cablesc. Cables In single Way Ducts Ground Temperature Depth of Laying Thermal Resistivity of Soil. Grouping of cablesThe cable derating factors applied to the Electrical Cable Data Sheets are based on the Prysmian cable catalogues. Details on the cable derating factors are given below in section 6.3.

HV cable Derating Factors Ground Temperature (C1)The rating factors due to the ground temperature for XLPE cables laid direct in the ground taken from Polycab catalogue is shown below:

Thermal resistivity of soil (C2)The rating factors due to the thermal resistivity of soil taken from Polycab catalogue is shown below:

Depth of Laying (C3)The rating factors due to the depth of laying taken from Polycab catalogue is shown below:

Spacing of cables (C4)The rating factors due to the grouping taken from Polycab catalogue is shown below:

0. MV cable Derating Factors Ambient Air Temperature (C1)

The rating factors due to the ground temperature for XLPE cables laid direct in the ground taken from Polycab catalogue is shown below:

Ground Temperature (C1)The rating factors due to the ground temperature for cables laid direct in the ground taken from IEC 60502-2 are shown below:

Depth of Laying (C2)The rating factors due to the depth of laying taken from IEC 60502-2 is shown below:

Thermal resistivity of soil (C3)The rating factors due to the thermal resistivity of soil taken from IEC 60502-2 are:Spacing of cables (C4)The rating factors due to the grouping taken from IEC 60502-2 are shown below:

Spacing of cables (C4)

C4 for a grouping of 4 cables in a group at spacing of 150 mm is taken from the table B.22 of IEC 60502-2.

Overall Derating factors

Overall Derating FactorThe overall derating factor for MV Multi-core cables areas shown below:Voltage/ Cable TypeIn AirDirect Buried

CABLE SIZING CALCULATIONSBasis for CalculationsCables are sized in accordance with whichever of the following criteria gives the largest cable cross sectional area requirement: Continuous current carrying capacity Short circuit current carrying capacity Volt drop at full loadIn addition, some degree of standardisation in cable size may be applied to avoid having to purchase short lengths of particular cables.The continuous current carrying capacity for the different cross sectional areas and different installation conditions are as per the manufacturers data. The continuous current ratings will generally consider two basic installation methods i.e. in air (on ladder racks or trays) and direct buried. In assessing the continuous current carrying capability, the calculations in this report assume no additional bunching factor need to be applied. However, additional de-rating may be needed in certain cases after the exact laying conditions are finalised.The 1 second short circuit withstands are indicated on the attached typical cable manufacturers data tables and is based on the below equation:k2 S2 = I2 t (1)For XLPE insulated copper cables with a short circuit temperature rise from 90C to 250C, k factor is 143 (XLPE copper multi core cables). Conversion of the 1 second values to different times is given as:I12 t1 = I22 t2 (2)The volt drop at full load is assessed from the following calculation:V.D. (ph-N basis) = I Rph cos + I Xph sin (3)Where, k -143 (for copper)S -cross sectional areaI1 -Cable short circuit current (Refer Attachment 4)I2-Higher than the bus Short Circuit currentt1-Time in Sect2-Fault Clearing time in SecRph -Cable Resistance (Ohms/km)Xph-Cable Reactance (Ohms/km)cos-Power FactorThe values for Rph and Xph for a given cable are calculated from the per km values respectively given in Attachment 4 typical cable manufacturers data tables. The Rph value is for operation at 90C. Typically 66kV & 5.5kV cables are sized on continuous current and short circuit withstand capability. A minimum cable size is needed for short circuit withstand for cables protected by circuit breakers. The minimum size depends on the maximum short circuit current and the anticipated fault clearance time. For this report the 66kV & 5.5kV short circuit current is taken as the switchboard rated value of 25kA & 40kA rms respectively. Fault clearance times are taken as:For 5.5kV system:Breaker Operating Time

60 ms

Relay operating time50 ms

5PCT error margin50 ms

Safety Margin60 ms

Total Fault Clearing Time220 ms

It is assumed that the switchboard rated fault current is sustained at the switchboard rating but in practice there will be a rapid decrement in fault current due to decaying generator and motor contributions to the fault current. Consequently the design will incorporate a safety margin.66kV Cable Sizing Cable sizing is based upon typical manufacturers data. After finalisation of cable vendor the selection of high voltage cable shall be in accordance with IEC 60183 and the actual cable manufacturers data.After identifying the minimum cables size to satisfy the cable short circuit withstand capacity, the cable size is selected in accordance with continuous current based on equipment rating or maximum volt drop, whichever is higher.5.5kV Cable Sizing Cable sizing is based upon IEC 60502-2 and typical manufacturers data. After finalisation of cable vendor the selection of high voltage cable shall be in accordance with IEC 60183 and the actual cable manufacturers data.After identifying the minimum cables size to satisfy the cable short circuit withstand capacity, the cable size is selected in accordance with continuous current based on equipment rating or maximum volt drop, whichever is higher.

Gas Turbine Generator Incomer H-EW-081101& H-EW-081201(5.5 kV)Generator Rating 3.15MVA, 5.5kVa) Minimum Conductor Sizing for short CircuitMinimum cross section area of cable S = I t / k (ref Equation 1)The maximum short circuit current in the generator cable, I, can be taken as the switchgear fault level less the generator short circuit contribution (based on 12% impedance) i.e. I = (31.5 - 2.75)kA = 28.75 kAt = 0.75 s (generator breaker protection operating time)k = 143 Hence min. cross section of cable S = 28.75k x 0.75 / 143 = 174 mm2 Next nearest conductor size available is= 185 mm2 (Cu, XLPE)b) Sizing based on continuous currentFull load current = 330 A De-rated current = 330 A/0.63 (Direct Buried, 2 circuits, as per 7.3.6) = 523.8 AProposed cable size = 3 C x 185mm2, Cu conductorCable Ampacity (Laid in Ground) = 436 A ( Ref. Table -9)Min number of cables required = 2 Runs x 3C x 185mm2 c) % Voltage drop calculation%Voltage drop = (1.732 x I x L x (R Cos + X Sin) / (NxVx1000)) x100Where,I - Load current (330 A)L - Cable Route length (150m)R - Resistance of cable (0.128) for 185 mm2, refer to attachment 4X - Reactance of cable (0.0881) for 185 mm2, refer to attachment 4Cos - Power factor, 0.8 N - No. of Runs (2)V - Voltage (5.5kV)% V.D. = (1.732x330x150x(0.128x0.8+0.0881x0.6)/(2x5500x1000))x100 = 0.00121 x 100= 0.121 % which is acceptable ( as per the clause 7.4)Hence selected cable size = 2 Runs x 3C x 185mm2

_________________________________________________________________________________ Page 11 of 20