Click here to load reader
Upload
duongtram
View
213
Download
0
Embed Size (px)
Citation preview
IT 20 ANSWERS – 15 JUNE 2010 1
IT 20 – ELECTRICAL INSPECTOR EXAMINATION
ANSWER SCHEDULE Notes:1. (1 mark) means that the preceding statement/answer earns 1 mark. 2. This schedule sets out the expected answers to the examination questions. The marker can
exercise their discretion and decide on the overall accuracy of any answer that is presented in the candidate’s own words.
3. Symbols and terms - alternatives Power W or P Voltage V or E or U Phase Active
Question 1 Marks Reference Marking notes
(a) Low voltage is any voltage between 50V a.c. and 1000V a.c.
Standard low voltage is a nominal voltage of 230V between phase and neutral.
(1 mark) ER 2
ESR 4
(b) Suitable warning notices affixed at the means of disconnection
Locking of the means of disconnection
(1 mark) ER 34
OR
Suitable notices warning against connection
Must use the locking facility if available
ESR 106 ESR 106
(c) Any TWO of: (1 mark)
The repair or replacement of a faulty conductor:
The repair or replacement of a damaged conductor:
The replacement of a fuse carrier with a circuit breaker appropriate to the rating of the electrical circuit in which the replacement is being made:
The replacement of any fitting with a fitting of an appropriate size, type, and rating for the electrical circuit:
The installation of revenue meters and associated load control fittings of mains.
ER 39(2)
OR
IT 20 ANSWERS – 15 JUNE 2010 2
Question 1 Marks Reference Marking notes
Work done on an installation by a person acting under the exemption in section 79 of the Act unless regulation 64 requires the work to be certified
The repair or replacement of a faulty conductor:
The repair or replacement of a damaged conductor:
The replacement of a fuse carrier with a circuit breaker appropriate to the rating of the electrical circuit in which the replacement is being made:
The replacement of any fitting with a fitting of an appropriate size, type, and rating for the electrical circuit:
The installation of revenue meters and associated load control fittings of mains.
ESR 66(3)
(d) 5 years (1 mark) ER 46(2)(e)
ESR 75(1)(b)
(e) Any ONE of (1 mark)
NZS 3019 ER 97(4)
AS/NZS 3001 ESR 78(2)
(f) Any TWO of:
• The use of a key or tool is required.
• An interlocking device is fitted.
• An intermediate barrier is provided.
(1 mark) AS/NZS 3000:
2000: 1.7.3.4.2
2007: 1.5.4.4b
(g) ANY ONE of from AS/NZS 3000: (1 mark)
Where the circuit is supplied from an isolating transformer complying with AS/NZS 3108
The source of current is so selected that the output is separated from the input by means of double insulation or equivalent.
2000: 1.7.4.5.2
OR
IT 20 ANSWERS – 15 JUNE 2010 3
Question 1 Marks Reference Marking notes
Where the circuit is supplied from an isolating transformer complying with AS/NZS 61558 so that the output is separated from the input by double insulation or equivalent
A generator output that it is installed so that the output is separated from the frame of the generator.
An isolated inverter complying with AS/NZS 4762.
2007: 7.4.2
(h) Any TWO of:
Where the electrical equipment operates under conditions of fluctuating or intermittent loading, or a definite duty cycle
Where the electrical installation is large and complex
Where special types of occupancy exist.
(1 mark)
AS/NZS 3000:
2000: 1.8.3.3
2007: 2.2.2(b)
(i) The nominal voltage shall not exceed 12 V a.c. or 30 V ripple-free d.c.; and
The supply source shall be installed outside Zone 0; and
As an SELV or PELV system.
(1 mark) AS/NZS 3000:
2000: 7.2.4.5(a)
2007: 6.3.4.5(a)(ii), (A), (B), (C)
(j) Bare aerial conductors
(1 mark) AS/NZS 3000:
2000: Table 3.8
2007: Table 3.8
(k) Any ONE of from AS/NZS 3000 (1 mark)
Will not be affected by the method of hosing, materials used, temperature and pressure of the hosing medium.
Does not provide pockets or channels in which moisture might accumulate or through which it might pass into electrical equipment.
2000: 7.5.4.2
OR
IT 20 ANSWERS – 15 JUNE 2010 4
Question 1 Marks Reference Marking notes
Will not be affected by the method of hosing, materials used, temperature and pressure of the hosing medium.
Is protected against moisture that might accumulate.
Does not provide pockets or channels in which moisture might accumulate or through which it might pass into electrical equipment.
2007: 6.7.4.3
(l) Any TWO of:
Flameproof equipment Ex “d”
Pressurized rooms or enclosures Ex “p”
Increased Safety Ex “e”
Intrinsically Safe Ex “i”
Special protection Ex “s”
Non-sparking Ex “n”
Ventilation Ex “v”
Encapsulation Ex “m”
Powder filling Ex “q”
Oil immersion Ex ‘o”
(1 mark)
AS/NZS 2381.1:2005
Table 3.2
(m) (i) 4m (½ mark) NZECP 34: 9.2.1(a)
(ii) 7.5m (½ mark) NZECP 34:
Table 2
(n) (i) 2.5 mm2 (½ mark) ECP 51: Table 3
(ii) 6 mm2 (½ mark) ECP 51: Table 3
(o) To prevent movement if a high prospective short-circuit current fault occurs.
(1 mark) GK
(p) Any ONE of: (1 mark) GK
The neutral must have a high resistance joint
There is a fault in an adjacent installation
IT 20 ANSWERS – 15 JUNE 2010 5
Question 1 Marks Reference Marking notes
(q) Any TWO of:
Any metal not normally live could be live at up to 230V.
The main switch does not isolate the incoming supply for the installation.
A fire hazard could exist at any high resistance joint in the MEN system or if the neutral bar insulation is inadequate.
(1 mark) GK
(r) Any ONE of:
A Type A RCD
The RCD is sensitive to residual a.c. current and residual pulsating d.c. current
(1 mark)
GK
(s) Any TWO of:
Reduced tariff
Lower current on the installation equipment
Less cable losses in the installation
(1 mark)
GK
(t) (i) 30 mA (½ mark) GK
(ii) 10 mA (½ mark) GK
IT 20 ANSWERS – 15 JUNE 2010 6
Question 2 Marks Reference Marking notes
(a) The mains
The main switchboard
(1 mark) ER 41(1)(c)
ESR 70(1)(c)
(b) (i) MEN connection.
Earth electrode.
Earthing conductors, e.g. size, identification.
Connections, joints and terminations.
Protection against external influences.
(2½ marks) AS/NZS 3000:
2000:6.2.2(f)
2007: 8.2.2(f)
(ii) Continuity of the earthing system
Insulation resistance.
Polarity.
Correct circuit connections
Fault loop impedance
(2½ marks) AS/NZS 3000:
2000: 6.3.3.1
OR
Continuity of the earthing system
Insulation resistance.
Polarity.
Correct circuit connections
Earth fault loop impedance
Operation of RCDs
AS/NZS 3000:
2007: 8.3.3
(c) Any FOUR of: (4 marks)
Sight the requisite certificate of compliance
ER 43A(b)
The polarity of the supply is correct ER 43A(c)
The phase rotation of the supply is correct
ER 43A(c)
The supply protection is correctly rated.
ER 43A(d)
The revenue meters and associated load control equipment are safe.
ER 43A(e)
Verify that there is a main earthing system, if the supply is from an MEN system,
ER 43A(f)
OR
The polarity of the supply is correct ESR 73 (2)(a)(i)
IT 20 ANSWERS – 15 JUNE 2010 7
Question 2 Marks Reference Marking notes
The phase rotation of the supply is correct
ESR 73 (2)(a)(i)
The protection of the supply is correctly rated.
ESR 73 (2)(a)(ii)
The installation is compatible with the supply system
ESR 73 (2)(a)(iii)
If the supply is from an MEN system, verify that there is a main earthing system
ESR 73 (2)(a)(iv)
The revenue meters have a declaration of conformity
Or
The revenue meters are verified as being electrically safe
ESR 73 (2)(a)(i)(ii)
Sight a certificate of compliance ESR 73 (2)(b)
Give a certificate of compliance (for the inspection work)
ESR 73 (2)(c)
IT 20 ANSWERS – 15 JUNE 2010 8
Question 3 Marks Reference Marking notes
(a) (i) 11.5V (½ mark) ER 53(3)
ESR 59(4)
(ii) 20V (½ mark) ER 53(3)
ESR 59(4)
(b) (i) 300C (½ mark) AS/NZS 3000:
2000: 3.3.2
2007: 3.3.2.1
(ii) 150C
(½ mark) AS/NZS 3000:
2000: 3.3.2
2007: 3.3.2.1
(c) (i) Any TWO of: (2 marks) GK
To determine the prospective short circuit current at any point in an electrical installation.
To ensure that the installed circuit protection is of the correct type and breaking capacity and will operate in the maximum specified time under fault conditions.
To verify that the impedance of the fault circuit is low enough to operate the electrical protection under fault conditions.
(ii) Commencing at the active terminal of the socket outlet
Through the active conductors of the final subcircuit, mains an distribution to the star point of the transformer
(1 mark)
GK
Through the star point of the transformer and the transformer winding, the distribution neutral and the mains neutral to the neutral bar on the switchboard.
(1 mark)
GK
IT 20 ANSWERS – 15 JUNE 2010 9
Question 3 Marks Reference Marking notes
Through the neutral bar on the switchboard, MEN link, earth bar through the protective earthing conductor to the socket outlet
(2 marks)
GK
(d) PSSC = kVA
V x √3 %Z
(½ mark) GK
= 1200 x 103
400 x √3 x 0.04
(½ mark) GK
= 43,302.54A (1 mark) GK
IT 20 ANSWERS – 15 JUNE 2010 10
Question 4 Marks Reference Marking notes
(a) I(FL) = P
V
(½ mark)
= 9,000
230
(½ mark)
= 39.13 A (1 mark)
(b) From table 9, column 12 a 16 mm2 is rated for 46 amps.
(½ mark)
From table 27(1), the derating factor is 0.88.
(½ mark)
Applying the derating factor = 46 x 0.88 = 40.48A.
(½ mark)
Therefore a 16 mm2 cable will satisfy the load requirements.
(1 mark)
(c) Maximum volt drop permitted = 230 x 0.01 = 2.3V
(½ mark)
Solution
From table 42, a 16 mm2 cable, with an operating temperature of 75 0C has an mV/A.m of 2.43
(½ mark)
Converted to single phase = 2.43 x 1.155 = 2.8067 mV/A.m
(1 mark)
VD = V/A.m x amps x metres
1000
(½ mark)
= 2.8067 x 30 x 39.13
1000
(½ mark)
= 3.29V (½ mark)
Alternative Solution
V/A.m = VD x 1000
L x A x (1Φ con. factor)
= 2.3 x 1000
30 x 39.19 x 1.155
= 1.696
From table 42, a 25 mm2 cable, with an operating temperature of 75 0C has an mV/A.m of 1.54
Therefore, a 25 mm2 cable will satisfy the voltage drop requirements.
(1 mark)
IT 20 ANSWERS – 15 JUNE 2010 11
Question 4 Marks Reference Marking notes
(d) (i) A 25 mm2 copper cable will satisfy both the load and voltage drop requirements.
(½ mark)
(ii) Yes
AS/NZS 3000:2000: Table B5.1
AS/NZS 3000:2007: Table B1
(½ mark)
IT 20 ANSWERS – 15 JUNE 2010 12
Question 5 Marks Reference Marking notes
(a) (i) Correctly connected distribution line (½ mark)
(ii) Correctly connected pole fuse (½ mark)
(iii) Correctly connected transposition (½ mark)
(b) I = V
R
(½ mark)
= 230
10
(½ mark)
= 23A (1 mark)
P = V x I (½ mark)
= 230 x 23 (½ mark)
= 5290W (1 mark)
(c) No (½ mark)
The reverse polarity is not detected by the revenue meter
(1 mark)
(d) No (½ mark)
Any ONE of:
- The impedance of the fault loop is too high.
- The fault current flowing is too low to operate the smallest fuse in the fault circuit.
(1 mark)
(e) (i) 0 volts (½ mark)
(ii) A shock hazard occurs because the neutral is live in respect to effective earthing
(1 mark)
IT 20 ANSWERS – 15 JUNE 2010 13
Question 6 Marks Reference Marking notes
(a) (i) The figure has to show a barrier (curtain or door) fitted to the shower
(½ mark)
(ii) To limit the extent of Zone 1 of the shower
(1½ marks)
(b) (i) Correctly drawn Zone 0 of the shower
(½ mark) AS/NZS 3000:
2000 :Figs 7.1A(e) and 7.1
C(a)
2007:Figs 6.7 and 6.10.
Correctly drawn Zone 1 of the shower
(½ mark) AS/NZS 3000:
2000 :Figs 7.1A(e) and 7.1
C(a)
2007:Figs 6.7 and 6.10.
Correctly drawn Zone 2 of the shower
(½ mark) AS/NZS 3000:
2000 :Figs 7.1A(e) and 7.1
C(a)
2007:Figs 6.7 and 6.10.
Correctly drawn Zone 3 of the shower
(½ mark) AS/NZS 3000:
2000 :Figs 7.1A(e) and 7.1
C(a)
2007:Figs 6.7 and 6.10.
(ii) Correctly drawn Zone 0 of the basin
(½ mark) AS/NZS 3000:
2000 :Figs 7.1A(e) and 7.1
C(a)
2007:Figs 6.7 and 6.10.
IT 20 ANSWERS – 15 JUNE 2010 14
Question 6 Marks Reference Marking notes
Correctly drawn Zone 2 of the basin
(½ mark) AS/NZS 3000:
2000 :Figs 7.1A(e) and 7.1
C(a)
2007:Figs 6.7 and 6.10.
(c) (i) The figure has to show the light switch:
* In Zone 2 of the shower.
or
* In Zone 3 of the shower.
(½ mark) AS/NZS 3000:
2000: Figure 7.1A(e)
2007: Figure 6.9 (½ mark)
No marks can be awarded for part (c) if Zone 0 or Zone 1 is given as an answer for (c)(i)
Being accessible when entering the ensuite.
(½ mark)
(ii) For the answer given in (c)(i) either:
Zone 2 - The switch must be rated IPX 4
Zone 3 - No IP rating required
(½ mark) AS/NZS 3000:
2000: 7.1.4.1(b)
2007: 6.2.4.1(b)
(iii) The switch must be at least 0.3m above the floor.
(½ mark) AS/NZS 3000:
2000: 7.1.4.3
2007: 6.2.4.3
(d) (i) The figure has to show the towel rail and permanent connection unit in:
In Zone 2 of the shower.
or
In Zone 3 of the shower.
(½ mark) AS/NZS 3000:
2000: Figure 7.1A(e)
2007: Figure 6.9
No marks can be awarded for part (d) if Zone 0 or Zone 1 is given as an answer for (d)(i)
(ii) For the answer given in (d)(i) either:
Zone 2 The towel rail and permanent connection unit must be rated IPX 4
Zone 3 No IP rating required
(½ mark) AS/NZS 3000:
2000: 7.1.4.1(b)
2007: 6.2.4.1(b)
IT 20 ANSWERS – 15 JUNE 2010 15
Question 6 Marks Reference Marking notes
(iii) The permanent connection unit must be at least 0.3m above the floor.
(½ mark) AS/NZS 3000:
2000: 7.1.4.3
2007: 6.2.4.3
(e) (i) The figure has to show the socket outlet in:
In Zone 3 of the shower
or
Outside Zone 2 of the basin.
(½ mark) AS/NZS 3000:
2000: Figure 7.1A(e)
2007: Figure 6.9
No marks can be awarded for part (e) if Zone 0 or Zone 1 is given as an answer for (e)(i)
(ii) For the answer given in (d)(i) either:
Zone 3 – no IP rating required
or
Outside Zone 2 of the hand basin - no IP rating required
(½ mark) AS/NZS 3000:
2000: 7.1.4.1(b)
2007: 6.2.4.1(b)
(iii) RCD protected or supplied from an isolated supply
(½ mark)
AS/NZS 3000:
2000: 7.1.4.2(c)
2007: 6.2.4.2(c)
IT 20 ANSWERS – 15 JUNE 2010 16
Question 7 Marks Reference Marking notes
(a) It does not inject sufficient current into the fault loop.
(½ mark) GK
To provide an accurate low impedance reading.
(½ mark) GK
(b) Improvement beyond 0.95 may cause resonance to occur
(1 mark) GK
Resulting in high circulating voltages and currents between the capacitive and inductive loads.
(1 mark)
GK
Answers related to cost; e.g., “cost of the extra capacitance is not economical” award a ½ mark
(c) (i) kVA = kW
pf
(½ mark)
GK
= 860
0.86
(½ mark)
= 1,000kVA (1 mark)
(ii) Q = √S2 – P2 (½ mark) GK
= √10002 – 8602 (½ mark)
= 510.3 kVAr (1 mark)
(iii) Cos-1 0.86 = 30.680 (½ mark) GK
Cos-2 0.95 = 18.20 (½ mark)
Q = P(TanΦ1 – TanΦ2) (½ mark)
= 860 (Tan 30.68 – Tan 18.2)
(½ mark)
= 224.7kVAr (1 mark)
IT 20 ANSWERS – 15 JUNE 2010 17
Question 8 Marks Reference Marking notes
(a) (i) 30 amps (Accept answers between 24A and 32A)
(1 mark) GK
(ii) Any ONE of:
To ensure that the protective device will operate within 400ms
To ensure the protection of persons or property from step and touch potentials
To protect property from fire & heat damage
(1 mark)
GK
(b) (i) It has a fusing factor between 1.25 and 1.5
(1 mark) GK
(ii) gG type (1 mark) GK
(c) IPSC = V
ZL
(½ mark)
GK
= 230V
0.18Ω
(½ mark)
= 1278A (1 mark)
(d) (i) 415 AC 80 GK
415V is the maximum voltage (½ mark)
the fuse can withstand without flashover.
(½ mark)
80,000A is the maximum prospective short circuit current and
(½ mark)
the fuse can safely interrupt (½ mark)
(ii) 6kA GK
is the maximum prospective short circuit current
(½ mark)
the circuit breaker can safely interrupt
(½ mark)
(iii) 63A GK
is the maximum current the fuse can continuously carry
(½ mark)
without deterioration. (½ mark)
IT 20 ANSWERS – 15 JUNE 2010 18
Question 9 Marks Reference Marking notes
(a) (i) This is the time it takes the fuse to interrupt the current flow
(1 mark) GK
(ii) This is the time it takes to interrupt the flow of current and extinguish the flame.
(1 mark)
GK
(b) Discrimination occurs when: GK
when the cut off time (1 mark)
of the fuse protecting the distribution board
(1 mark)
is greater than (1 mark)
the total clearing time (1 mark)
of the fuse protecting the final subcircuit.
(1 mark)
(c) 160A (1 mark) GK
The 160A fuse has a pre-arcing time of 62 (I2 x 10 3 )A
(1 mark)
which is greater than the total clearing time rating of the 100A fuse.
(1 mark)