164
Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two Rivers, Wl 54241 NM C 920.388.2560 920.755.2321 Committed to Nuclear Excellence Kewaunee / Point Beach Nuclear Operated by Nuclear Management Company, LLC NRC-02-015 February 22, 2002 10CFR50.55a U.S. Nuclear Regulatory Commission Attention: Document Control Desk Washington, D.C. 20555 Ladies and Gentlemen: Docket 50-305 Operating License Kewaunee Nuclear Power Plant 2001 Inservice Inspection (ISI) Summary Report As required by ASME Boiler and Pressure Vessel Code, Section XI; Code of Federal Regulation 1OCFR50.55a; and Wisconsin Administrative Code, Subchapter V ILHR 41.55(3) and ILHR 41.56; various ISI examinations were performed as part of the 2001 Refueling Outage. The outage took place from September 24, 2001 through December 4, 2001; i.e. closing of G1. This letter transmits the Inservice Inspection Summary Report as required by paragraph IWA-6230 of Section XI. Two separate ASME Section XI inservice examination programs are implemented at the KNPP. One program is for pressure retaining piping/vessel and component supports and the other program for the metal containment. The 2001 refueling outage constituted the first inspection year of the third period of the third interval for the piping/vessel and component support program, including preservice examinations associated with steam generator replacement. The 2001 refueling outage was also the first inspection year of the second period of the first interval for the metal containment program. Examinations for the piping/vessel and component support program, including preservice examinations associated with steam generator replacement, were performed in accordance with the ASME Boiler and Pressure Vessel Code Section XI 1989 Edition. Examinations for the metal containment program were performed in accordance with the 1992 Edition up to and including the 1992 Addenda of Section XI of the ASME Boiler and Pressure Vessel Code. These requirements were implemented in accordance with the "Kewaunee Nuclear Power Plant Third Ten-Year Inservice Inspection (ISI) Program 1994-2004," "Kewaunee Nuclear Power Plant First 10-Year Inservice Inspection Class MC (ISI) Program 1996-2006," Plant Technical Specifications, and nondestructive examination procedures.

Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

  • Upload
    others

  • View
    9

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road

Kewaunee, Wl 54216-9511 Two Rivers, Wl 54241

NM C 920.388.2560 920.755.2321

Committed to Nuclear Excellence Kewaunee / Point Beach Nuclear Operated by Nuclear Management Company, LLC

NRC-02-015

February 22, 2002 10CFR50.55a

U.S. Nuclear Regulatory Commission Attention: Document Control Desk Washington, D.C. 20555

Ladies and Gentlemen:

Docket 50-305 Operating License Kewaunee Nuclear Power Plant 2001 Inservice Inspection (ISI) Summary Report

As required by ASME Boiler and Pressure Vessel Code, Section XI; Code of Federal Regulation 1OCFR50.55a; and Wisconsin Administrative Code, Subchapter V ILHR 41.55(3) and ILHR 41.56; various ISI examinations were performed as part of the 2001 Refueling Outage. The outage took place from September 24, 2001 through December 4, 2001; i.e. closing of G1. This letter transmits the Inservice Inspection Summary Report as required by paragraph IWA-6230 of Section XI.

Two separate ASME Section XI inservice examination programs are implemented at the KNPP. One program is for pressure retaining piping/vessel and component supports and the other program for the metal containment. The 2001 refueling outage constituted the first inspection year of the third period of the third interval for the piping/vessel and component support program, including preservice examinations associated with steam generator replacement. The 2001 refueling outage was also the first inspection year of the second period of the first interval for the metal containment program. Examinations for the piping/vessel and component support program, including preservice examinations associated with steam generator replacement, were performed in accordance with the ASME Boiler and Pressure Vessel Code Section XI 1989 Edition. Examinations for the metal containment program were performed in accordance with the 1992 Edition up to and including the 1992 Addenda of Section XI of the ASME Boiler and Pressure Vessel Code. These requirements were implemented in accordance with the "Kewaunee Nuclear Power Plant Third Ten-Year Inservice Inspection (ISI) Program 1994-2004," "Kewaunee Nuclear Power Plant First 10-Year Inservice Inspection Class MC (ISI) Program 1996-2006," Plant Technical Specifications, and nondestructive examination procedures.

Page 2: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

Docket 50-305 NRC-02-015 February 22, 2002 Page 2

The following items were examined for Class 1, Class 2, Class 3 Components and their supports:

1. Reactor Vessel Closure Head Flange Weld 2. Reactor Vessel Closure Head Studs, Nuts, Washers and Control Rod Drive Mechanisms 3. Pressurizer Circumferential and Longitudinal Welds 4. Steam Generator Head Circumferential Weld, Nozzle Inside Radius Sections and Nozzle To

Shell Weld 5. Reactor Coolant Pump Main Flange Bolting and No. 1 Seal Housing Bolting 6. Seal Water Injection Filter Shell Circumferential Weld 7. Letdown Heat Exchanger Head Circumferential Weld 8. Charging Pump Pulsation Dampener Head Circumferential Weld 9. Class 1 Valve Bodies

10. Class 1 and Class 2 Piping Welds 11. Class 1 Piping Integrally Welded Attachment 12. Class 2 Piping Integrally Welded Attachments 13. Class 2 Safety Injection Pump Casing Weld and Welded Attachments 14. Class 1, Class 2 and Class 3 Piping and Component Supports and Hangers 15. Class 1 and Class 2 Reactor Vessel Conoseal Bolting, Pressurizer Manway Bolting, Flange

Bolting and Valve Bonnet Bolting 16. Class 1 System Leakage Test 17. Class 2 and Class 3 System Inservice and Functional System Pressure Tests

The following items were examined for the Replacement Steam Generators:

1. Replacement Steam Generators: Tubesheet to Head Welds, Nozzle Inside Radius Sections, Nozzle to Safe End Butt Welds, Primary Side Manway Bolting, Integrally Welded Attachments, Shell Circumferential Welds, Tubesheet to Shell Welds and Class 1 Support Components

2. New Class 1 Reactor Coolant Piping Welds 3. New and Replacement Class 2 Main Steam and Feedwater Piping Welds 4. Reexamination of Existing Steam Generator, Circumferential Welds SG-W2 and SG-W10 to

verify previously recorded Ultrasonic Planar Indications 5. Existing 16", 8" and 1" Feedwater Inside Diameter Surfaces 6. Existing Steam Generator Inside Diameter Feedwater Nozzle Inner Radius and Shell

Circumferential Welds 7. Existing Steam Generator Class 2 Supports

Page 3: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

Docket 50-305 NRC-02-015 February 22, 2002 Page 3

The following items were examined for the Class MC Reactor Building Containment Vessel:

1. Accessible Surface Areas 2. Longitudinal Welds and Circumferential Welds 3. Sleeve to Bellows Welds 4. Flange Welds 5. Seals and Gaskets 6. Moisture Barriers 7. Dissimilar Metal Welds 8. Bolted Connections 9. Containment Penetration Bellows

10. Airlocks

The following items were examined in accordance with Kewaunee Nuclear Power Plant Technical Specifications:

1. Eddy Current Testing of Replacement Steam Generators 2. Functional Testing, Disassembly and Overhaul of Steam Generator 900 KIP Hydraulic

Snubbers

In addition, the following examinations were performed in excess of ASME Boiler and Pressure Vessel Code Section XI 1989 Edition Requirements and included:

1. Portions of the Service Water System were radiographed for wall loss, pits, nodules, and sand, mud or other sediments.

2. Balance of plant piping subject to erosion/corrosion was examined by radiographic, ultransonic, and visual techniques.

Page 4: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

Docket 50-305 NRC-02-015 February 22, 2002 Page 4

Please find attached a copy of the following documentation that summarizes the inservice inspection activities and results for the Kewaunee Nuclear Power Plant 2001 Refueling Outage.

1. Summary of recordable indications and a description of how they were dispositioned (Attachment 1)

2. Summary of Class 1 and 2 Repairs and Replacements of Components 1 inch in diameter or smaller (Attachment 2)

3. Form NIS-1 Owner's Report for Inservice Inspections of Class 1, Class 2, and Class 3 Components (Attachment 3)

4. Form NIS-I Owner's Report for Inservice Inspections for Class MC Components (Attachment 4) 5. Form NIS-I Owner's Report for Inservice Inspections of Replacement Steam Generators

(Attachment 5) 6. Form NIS-2 Owner's Report for Repair or Replacements (74 Total) (Attachment 6) 7. Examination Summary for Scheduled and Augmented Inservice Inspection (ISI) Program

(Attachment 7) 8. Examination Summary for Inservice Inspection (ISI) Class MC Program (Attachment 8) 9. Examination Summary for Preservice Inspection (PSI) of Steam Generators (Attachment 9)

10. Examination Summary for Replacement Steam Generator Eddy Current (Attachment 10) 11. Examination Summary for Steam Generator 900 KIP Hydraulic Snubbers (Attachment 11) 12. A summary of examinations which were limited by geometric, metallurgical, or design/access

restrictions and their associated data sheets (Attachment 12)

The final reports for each of these examinations are on file in the QA/QC Records Vault at the Kewaunee Nuclear Power Plant. These records are available for review as deemed necessary.

Additional Comments

The next Refueling Outage at the Kewaunee Nuclear Power Plant is tentatively scheduled for April 4, 2003 through April 30, 2003.

Sincerely,

Thomas Coutu

Manager-Kewaunee Plant

PEB/CAT

Attach. cc - U.S. NRC - Region III (w/o attach)

U.S. NRC - Senior Resident Inspector (w/o attach)

Page 5: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

ATTACHMENT 1

Letter from T. Coutu (NMC)

To

Document Control Desk (NRC)

Dated

February 22, 2002

Summary of Recordable Indications and Description of Disposition

Page 6: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

Docket 50-305 NRC-02-015 February 22, 2002 Attachment 1, Page 1

TABLE 1

TYPE OR LOCATION OF RECORDABLE i O INDICATION (RI) METHOD NO. OF RI'S

Reactor Vessel Closure Head Flange Weld Surface (MT) 1 Weld Steam Generator Circumferential Head Weld Volumetric (UT) 1 Weld Seal Water Injection Filter Shell Weld Volumetric (UT) 1 Weld Piping Integrally Welded Attachment Surface (PT) 1 Weld Piping Circumferential Butt Weld Surface (PT) 1 Weld Piping Socket Weld Surface (PT) 1 Weld Reactor Vessel Conoseal Bolting Visual (VT-3) 1 Conoseal RC Pump No. 1 Seal Housing Bolting Visual (VT-1) 1 Pump Pressurizer Manway Bolting Visual (VT-3) 1 Manway Component Supports and Hangers Visual (VT-3) 31 Supports Valve Bonnet Bolting Visual (VT-1) 1 Valve Valve Bonnet Bolting Visual (VT-3) 6 Valves System Pressure Tests Visual (VT-2) 51 Items Replacement Steam Generator Integrally Welded Surface (MT) 1 Weld Attachment SG-1B-23B Replacement Steam Generator Tubesheet To Head Weld Volumetric (UT) 1 Weld SG-W32 Replacement Steam Generator Primary Side Manway SG- Visual (VT-i) 1 Stud 1B-CLMWB Replacement Steam Generator Tubesheet To Shell Weld Volumetric (UT) I Weld SG-W31 Existing Steam Generator Feedwater Nozzle Inner Radius Surface (MT) 1 Nozzle SG-IR8 Existing Steam Generator Feedwater Nozzle Inner Radius Surface (MT) & 1 Nozzle SG-IR16 Visual (VT-1) Existing Steam Generator Circumferential Welds SG-W2 Volumetric (UT) 2 Welds and SG-W10 Existing 16", 8" and 1" Feedwater Piping FW-W27BC Surface (MT) 1 ID Section Existing 16", 8", and 1" Feedwater Piping FW-W55BC Surface (MT) & 1 ID Section

Visual (VT-1) Reactor Building Containment Vessel General Visual 11 Plates Reactor Building Containment Vessel Moisture Barriers VT-3 5 Plates Reactor Building Containment Vessel Emergency Airlock VT-1 1 Bolt

Page 7: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

Docket 50-305 NRC-02-015 February 22, 2002 Attachment 1, Page 2

Disposition of Class 1, Class 2, and Class 3 indications have been completed in accordance with the rules of ASME Boiler and Pressure Vessel Code Section XI 1989 Edition and ASME Boiler and Pressure Vessel Code Section XI 1992 Edition up to and including 1992 Addenda for Class MC Components. Applicable codes, standards, and engineering criteria were used to disposition indications associated with the non-code-required examinations. Recordable indications for Class 1, Class 2, Class 3 and Class MC have been dispositioned as summarized below:

1. A 0.125" long linear indication was recorded on the Reactor Vessel Closure Head Flange Weld RV-W12 during performance of magnetic particle examination. This linear indication was acceptable per ASME Boiler and Pressure Vessel Code Section XI 1989 Edition Table IWB-3510-3.

2. A spot indication on Steam Generator 1B Circumferential Head Weld SG-W9 was recorded during performance of ultrasonic examination. This ultrasonic spot indication was acceptable per ASME Boiler and Pressure Vessel Code Section XI 1989 Edition Table IWC-3510-1.

3. Five (5)laminar indications combined into four (4) laminar indications due to proximity of the indications. The indications are on seal water injection filter IA circumferential shell weld AFSI-Wl and were identified during performance of ultrasonic examinations. These laminar indications were acceptable per ASME Boiler and Pressure Vessel Code Section XI 1989 Edition Table IWC-3510-2 and were typical of laminations recorded on seal water injection filters 1A and 1B during Refueling Outages 1982, 1986, 1988, 1992 and 1998.

4. Three (3) rounded indications (0.625", 0.125" and 0.1875" in diameter) were recorded on 2" piping integrally welded attachment RSI-H72 during performance of liquid penetrant examinations. These three (3) rounded indications were acceptable per ASME Boiler and Pressure Vessel Code Section III 1989 Edition Section NC-5352(b).

5. A 0.125" long linear indication and a 0.125" rounded indication were recorded on 6" diameter Circumferential Butt Weld ICS-W43 during performance of liquid penetrant examinations. The 0.125" long linear indication was acceptable per ASME Boiler and Pressure Vessel Code Section XI 1989 Edition Table IWB-3514-2. The 0.125" rounded indication was acceptable per ASME Boiler and Pressure Vessel Code Section III 1989 Edition Section NC-5352.

6. A 0.55" long linear indication on 2" diameter socket weld SI-W6S was recorded during performance of liquid penetrant examinations. This linear indication was unacceptable per ASME Boiler and Pressure Vessel Code Section XI 1989 Edition Table IWB-3514-2. The linear indication was removed under Work Order 01-016342 by light filing with a jewelers file, reexamined and accepted with no indications.

Page 8: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

Docket 50-305 NRC-02-015 February 22, 2002 Attachment 1, Page 3

7. Visual (VT-1, VT-2 and VT-3) indications were recorded on reactor vessel conoseal bolting, reactor coolant Pump No. 1 seal housing bolting, pressurizer manway bolting, valve bonnet bolting, piping supports and hangers and during system pressure tests. The indications were either (1) evaluated and accepted or (2) repaired, reexamined and accepted by: Nuclear Management Company, LLC - Maintenance, Quality Control, Engineering and Technical Support or Inservice Inspection Personnel and reviewed by the Authorized Nuclear Inservice Inspector.

8. Two (2) separate linear indications on replacement steam generator 1B integrally welded attachment SG-1B-23B were recorded during performance of magnetic particle examinations. These two linear indications due to their close proximity to each other were classified as one linear indication with a length of 0.21875." This linear indication was acceptable per ASME Boiler and Pressure Vessel Code Section XI 1989 Edition Sections IWB-3516.1, IWB-3510.3 and IWB-3510-3.

9. Ultrasonic recordable indications at three separate locations on replacement steam generator lB tubesheet to head weld SG-W32 were noted during performance of manual ultrasonic examinations. These three separate planar indications were acceptable per ASME Boiler and Pressure Vessel Code Section XI 1989 Edition Table IWB-3510-1.

10. One visual indication was recorded by the VT-1 method on replacement steam generator 1B primary side manway stud SG-1B-CLMWB#17. Although this primary manway stud was acceptable per ASME Boiler and Pressure Vessel Code Section XI 1989 Edition Section IWB-3517.1 (b), a new VT-1 acceptable replacement stud was installed.

11. Ultrasonic recordable indication at one location on replacement steam generator 11B tubesheet to shell weld SG-W31 was noted during performance of manual ultrasonic examination. This planar indication was acceptable per ASME Boiler and Pressure Vessel Code Section XI 1989 Edition Table IWC-3510-1.

12. Recordable indications on the existing steam generator lB feedwater nozzle inside radius section SG-IR8 were recorded during augmented examination by magnetic particle. These indications were repaired by Bechtel Corporation under Bechtel's NCR's and Kewaunee Nuclear Power Plant Work Orders as part of replacement steam generator activities.

13. Recordable indications on the existing steam generator 1A feedwater nozzle inside radius section SG-IR16 were recorded during augmented examinations by magnetic particle and visual (VT-1) methods. These indications were repaired by Bechtel Corporation under Bechtel's NCR's and Kewaunee Nuclear Power Plant Work Orders as part of replacement steam generator activities.

Page 9: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

Docket 50-305 NRC-02-015 February 22, 2002 Attachment 1, Page 4

14/15. Prior to severing the existing steam generators and following welding the replacement steam generators to the existing steam generators a manual ultrasonic examination was performed on the existing circumferential shell welds SG-W2 and SG-W10 to ensure that there was no growth in the previously recorded planar indications. These indications were recorded in 1991 for SGW2 and in 1991 and 1996 for SG-Wl0. All indications previously recorded as well as new indications recorded due to amplitude recording criteria change were acceptable either by ASME Boiler and Pressure Vessel Code Section XI 1989 acceptance standards or by fracture analysis as provided in Westinghouse Electric Corporation WCAP 11476 Rev.3 Handbook on Flaw Evaluation, Kewaunee Unit 1 Steam Generator Upper Shell to Cone Weld, May 1991, and evaluation by Kewaunee Nuclear Power Plant during 1996 and 2001 Refueling Outages.

16. Recordable indications on Loop A existing 16", 8" and 1" feedwater piping inner diameter surface for FW-W27BC were recorded during augmented magnetic particle examinations. These indications were repaired by Bechtel Corporation under Kewaunee Nuclear Power Plant Work Orders generated during steam generator replacement activities.

17. Recordable indications on Loop B existing 16", 8" and 1" feedwater piping inner diameter Surface for FW-W55BC were recorded during augmented examinations by magnetic particle and visual (VT-1) methods. These indications were repaired by Bechtel Corporation under Kewaunee Nuclear Power Plant Work Orders generated during steam generator replacement activities.

18. General visual indication consisting of a 4" x 8" surface defect was recorded on Plate 155. This surface defect was previously recorded and accepted in 1998 and showed no change in dimension or surface condition during the 2001 Refueling Outage.

19. General visual indication consisting of a slight inward bulge on Plates 74, 75, and 83 was recorded. The slight inward bulge was evaluated by Engineering and accepted under Kewaunee Nulcear Power Plant Specification TS-1052, Addendum No. 4, Item No. 19 Section 10.3 - Shell Tolerance.

20. General visual indication consisting of slight outward bulges on Plates 144, 145, 146, 147 and 148 were recorded. The slight outward bulges were evaluated and accepted by Engineering Analysis.

21. General visual indications consisting of weld deposits on Plate 62 and arc strikes on Plate 99 were recorded and are acceptable per ASME Boiler and Pressure Vessel Code Section XI 1992 Edition 1992 Addenda.

22. VT-3 indications consisting of lack of bonding and tears were recorded in the moisture barriers on Plates 62, 64, 65, 66 and 67 and were repaired under Work Order 0 1-018045.

23. A VT-I indication on an emergency airlock bolt was recorded and was repaired under Work Order 01-018283.

Page 10: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

ATTACHMENT 2

Letter from T. Coutu (NMC)

To

Document Control Desk (NRC)

Dated

February 22, 2002

Summary of Class 1 and 2 Repairs and Replacement of Components 1 inch in Diameter or Smaller

Page 11: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

Docket 50-305 NRC-02-015 February 22, 2002 Attachment 2, Page 1

The following summarizes the repairs and replacements performed following the 2000 Refueling Outage and during the 2001 Refueling Outage by grinding, buffing, filing, cutting or welding on the Class 1 and Class 2 pressure boundary. These repairs and replacements are in addition to those itemized on the attached Forms "NIS-2 Owner's Report for Repairs or Replacements."

Component Class Reference Repair/Replacement Method 3/4" Valve PS-2A 1 XK-100-10 Cutting and Welding of Replacement

Valve 3/4" Valve PS-30 1 XK-100-10 Cutting and Welding of Replacement

Valve 1" Valve RC-45A 1 XK-100-10 Cutting and Welding of Replacement

Valve and Piping 1" Valve RC-45B 1 XK-100-10 Cutting and Welding of Replacement

Valve and Piping Replacement Steam 1 XK-100-10 Repair by Welding Fillet Weld Generator 1B 1/2" Internal Nozzle Drain Line 3/4" Valve 1 XK-100-35 Cutting and Welding of Replacement CVC-21070-1 Valve Replacement Steam 2 M-203 Buffing and Grinding involving Metal Generators 1A and Removal for Arc Strikes, Gouges and 1B: 2", 1" and 3/4" Weld Spatter Piping Replacement Steam 2 M-205 Machining involving Metal Removal for Generators 1A and Pitting 1B Secondary Side Hand Holes

Page 12: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

ATTACHMENT 3

Letter from T. Coutu (NMC)

To

Document Control Desk (NRC)

Dated

February 22, 2002

FORM NIS- 1 Owner's Report for Inservice Inspections of Class 1, Class 2, Class 3 Components

Page 13: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

Page 1 of 9

FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONS AS REQUIRED BY THE PROVISIONS OF THE ASME CODE RULES

1. OWNER - WISCONSIN PUBLIC SERVICE CORPORATION, 700 NORTH ADAMS,

P.O. BOX 19001, GREEN BAY, WISCONSIN 54307- 9001

2. PLANT - KEWAUNEE, N490 HIGHWAY 42, KEWAUNEE, WISCONSIN 54216-9511

3. PLANT UNIT - NO. 1

4. OWNER CERTIFICATE OF AUTHORIZATION - N/A

5. COMMERCIAL SERVICE DATE - JUNE 16,1974

6. NATIONAL BOARD NUMBER FOR UNIT - N/A

7. COMPONENTS INSPECTED -

COMPONENT OR APPURTENANCE

Reactor Vessel RV

Pressurizer PZR

Steam Generator SG1A

Steam Generator SGlB

Excess Letdown Heat Exchanger AHEL-1A

Excess Letdown Heat Exchanger AHEL-1B

Class 1 Piping

Reactor Coolant Pump RCP-1A

Reactor Coolant Pump RCP-1B

Residual Heat Exchanger AHRSI-IA

MANUFACTURER OR INSTALLER

Combustion Engineering

Westinghouse

Westinghouse/ Ansaldo Energia Milano

Westinghouse/ Ansaldo Energia Milano

Sentry

Sentry

Texas Pipe Bending

Westinghouse

Westinghouse

Joseph Oat and Sons

MANUFACTURER OR INSTALLER

SERIAL NO.

CE69202

1151

1141/0202

1142/0201

3996-5E

3996-6E

STATE OR PROVINCE NO.

U11480

U11402

U11400

U11401

U11407

U11408

NATIONAL BOARD NO.

21010

68-23

68-28/151

68-29/150

364

365

1A-1-618J871GO1

1B-2-618J871G02

1817-1E U11046 344

Page 14: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

Page 2 of 9

FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONS AS REQUIRED BY THE PROVISIONS OF THE ASME CODE RULES

1. OWNER - WISCONSIN PUBLIC SERVICE CORPORATION, 700 NORTH ADAMS,

P.O. BOX 19001, GREEN BAY, WISCONSIN 54307- 9001

2. PLANT - KEWAUNEE, N490 HIGHWAY 42, KEWAUNEE, WISCONSIN 54216-9511

3. PLANT UNIT - NO. 1

4. OWNER CERTIFICATE OF AUTHORIZATION - N/A

5. COMMERCIAL SERVICE DATE - JUNE 16, 1974

6. NATIONAL BOARD NUMBER FOR UNIT - N/A

7. COMPONENTS INSPECTED -

COMPONENT OR APPURTENANCE

Residual Heat Exchanger AHRS2-1B

Charging Pump Pulsation Dampener APD-1A

Charging Pump Pulsation Dampener APD-1B

Charging Pump Pulsation Dampener APD-1C

Seal Water Heat Exchanger AHSW

Volume Control Tank VCT

Regenerative Heat Exchanger ARG

Letdown Heat Exchanger AHLD

MANUFACTURER OR INSTALLER

Joseph Oat and Sons

Greer Hydraulics

Greer Hydraulics

Greer Hydraulics

Atlas

Joseph Oat and Sons

Joseph Oat and Sons

Atlas

MANUFACTURER OR INSTALLER

SERIAL NO.

1817-1F

STATE OR PROVINCE NO.

U11424

NATIONAL BOARD NO.

345

GNI-1848

GNI-1846

GNI-1847

734

1787-1C

1831-13

1206

U11404

U11425

U11409 U11410 U11411

U11405

596

376

413 414 415

1031

Page 15: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

Page 3 of 9

FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONS AS REQUIRED BY THE PROVISIONS OF THE ASME CODE RULES

1. OWNER - WISCONSIN PUBLIC SERVICE CORPORATION, 700 NORTH ADAMS, P.O. BOX 19001, GREEN BAY, WISCONSIN 54307- 9001

2. PLANT - KEWAUNEE, N490 HIGHWAY 42, KEWAUNEE, WISCONSIN 54216-9511

3. PLANT UNIT - NO. 1

4. OWNER CERTIFICATE OF AUTHORIZATION - N/A

5. COMMERCIAL SERVICE DATE - JUNE 16,1974

6. NATIONAL BOARD NUMBER FOR UNIT - N/A

7. COMPONENTS INSPECTED -

COMPONENT OR APPURTENANCE

Seal Water Injection Filter AFSI-1A

Seal Water Injection Filter AFSI-1B

Reactor Coolant Filter AFRC

Seal Water Filter AFSW

Class 2 Piping

Charging Pump APCH-1A

Charging Pump APCH-1B

Charging Pump APCH-1C

Charging Pump APCH-1A Suction Stabilizer

MANUFACTURER OR INSTALLER

Commercial Filters

Commercial Filters

AMF Cuno

AMF Cuno

Texas Pipe Bending

Ajax Iron Works

Ajax Iron Works

Ajax Iron Works

Greer Hydraulics

MANUFACTURER OR INSTALLER

SERIAL NO.STATE OR

PROVINCE NO.

101072

101073

121

123

NATIONAL BOARD NO.

1172

1173

2616

2618

6578

6576

6577

GH1-10234 568

Page 16: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

Page 4 of 9

FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONS AS REQUIRED BY THE PROVISIONS OF THE ASME CODE RULES

1. OWNER - WISCONSIN PUBLIC SERVICE CORPORATION, 700 NORTH ADAMS,

P.O. BOX 19001, GREEN BAY, WISCONSIN 54307- 9001

2. PLANT - KEWAUNEE, N490 HIGHWAY 42, KEWAUNEE, WISCONSIN 54216-9511

3. PLANT UNIT - NO. 1

4. OWNER CERTIFICATE OF AUTHORIZATION - N/A

5. COMMERCIAL SERVICE DATE - JUNE 16,1974

6. NATIONAL BOARD NUMBER FOR UNIT - N/A

7. COMPONENTS INSPECTED -

COMPONENT OR APPURTENANCE

Charging Pump APCH-1B Suction Stablizer

Charging Pump APCH-1C Suction Stablizer

Residual Heat Removal Pump APRHI-IA

Residual Heat Removal Pump APRH2-1B

Refueling Water Storage Tank

Diesel Generator AHDG-1A Cooling Water Exchangers (2)

Diesel Generator AHDG-1B Cooling Water Exchangers (2)

MANUFACTURER OR INSTALLER

Greer Hydraulics

Greer Hydraulics

Byron Jackson

Byron Jackson

General American Transportation Company

ITT Standard Corp.

ITT Standard Corp.

MANUFACTURER OR INSTALLER

SERIAL NO.STATE OR

PROVINCE NO.NATIONAL BOARD NO.

569GH1-10235

GH1-10236

681N0277

681N0276

C-8297/1969

750797-01-2 &

750797-01-3

750797-01-1 &

750797-01-4

570

Page 17: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

Page 5 of 9

FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONS AS REQUIRED BY THE PROVISIONS OF THE ASME CODE RULES

1. OWNER - WISCONSIN PUBLIC SERVICE CORPORATION, 700 NORTH ADAMS,

P.O. BOX 19001, GREEN BAY, WISCONSIN 54307- 9001

2. PLANT - KEWAUNEE, N490 HIGHWAY 42, KEWAUNEE, WISCONSIN 54216-9511

3. PLANT UNIT - NO. 1

4. OWNER CERTIFICATE OF AUTHORIZATION - N/A

5. COMMERCIAL SERVICE DATE - JUNE 16,1974

6. NATIONAL BOARD NUMBER FOR UNIT - N/A

7. COMPONENTS INSPECTED -

COMPONENT OR APPURTENANCE

Auxiliary Feedwater Pump APFM-1A Motor Driven

Auxiliary Feedwater Pump APFM-1B Motor Driven

Auxiliary Feedwater Pump APFT Turbine Driven

Class 3 Piping

Containment Fan Cooler AHCF-1A

Containment Fan Cooler AHCF-1B

MANUFACTURER OR INSTALLER

Pacific Pump

Pacific Pump

Pacific Pump

Texas Pipe Bending

Joy Manufacturing and American Air Filter

Joy Manufacturing and American Air Filter

MANUFACTURER OR INSTALLER

SERIAL NO.STATE OR

PROVINCE NO.NATIONAL BOARD NO.

46573

46574

46575

GF14402

GF14399

Page 18: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

Page 6 of 9

FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONS AS REQUIRED BY THE PROVISIONS OF THE ASME CODE RULES

1. OWNER - WISCONSIN PUBLIC SERVICE CORPORATION, 700 NORTH ADAMS,

P.O. BOX 19001, GREEN BAY, WISCONSIN 54307- 9001

2. PLANT - KEWAUNEE, N490 HIGHWAY 42, KEWAUNEE, WISCONSIN 54216-9511

3. PLANT UNIT - NO. 1

4. OWNER CERTIFICATE OF AUTHORIZATION - N/A

5. COMMERCIAL SERVICE DATE - JUNE 16, 1974

6. NATIONAL BOARD NUMBER FOR UNIT - N/A

7. COMPONENTS INSPECTED -

COMPONENT OR APPURTENANCE

Containment Fan Cooler AHCF-1C

Containment Fan Cooler AHCF-1D

Safety Injection Pump APSI-1A

Safety Injection Pump APSI-1B

Safety Injection Pump Lube Oil Cooler AHSC-1A

Safety Injection Pump Lube Oil Cooler AHSC-1B

Safety Injection Pump Heat Exchangers (2) AHSC-1A

MANUFACTURER OR INSTALLER

Joy Manufacturing and American Air Filter

Joy Manufacturing and American Air Filter

Bingham Pump

Bingham Pump

Thermxchanger

Thermxchanger

Borg Warner

MANUFACTURER OR INSTALLER

SERIAL NO.STATE OR

PROVINCE NO.NATIONAL BOARD NO.

GF14401

GF14400

290696

290697

X10199A2

X10199A3

854030:854030

Page 19: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

Page 7 of 9

FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONS AS REQUIRED BY THE PROVISIONS OF THE ASME CODE RULES

1. OWNER - WISCONSIN PUBLIC SERVICE CORPORATION, 700 NORTH ADAMS, P.O. BOX 19001, GREEN BAY, WISCONSIN 54307- 9001

2. PLANT - KEWAUNEE, N490 HIGHWAY 42, KEWAUNEE, WISCONSIN 54216-9511

3. PLANT UNIT - NO. 1

4. OWNER CERTIFICATE OF AUTHORIZATION - N/A

5. COMMERCIAL SERVICE DATE - JUNE 16, 1974

6. NATIONAL BOARD NUMBER FOR UNIT - N/A

7. COMPONENTS INSPECTED -

COMPONENT OR APPURTENANCE

Safety Injection Pump Heat Exchangers (2) AHSC-1B

Residual Heat Removal Pump AHRLRP-1A Shaft Seal Heat Exchanger

Residual Heat Removal Pump AHRHRP-1B Shaft Seal Heat Exchanger

Accumulator Tank ACC-1A

Accumulator Tank ACC-1B

Containment Spray Pump APCS-1A

Containment Spray Pump APCS-1B

Containment Spray Pump AIPCS-1A Gland Seal Cooler

MANUFACTURER OR INSTALLER

Borg Warner

Borg Warner

Borg Warner

Wyatt

Wyatt

Ingersoll Rand

Ingersoll Rand

Helliflow

MANUFACTURER OR INSTALLER

SERIAL NO.

854030:854030

681N0276

681N0276

H-5645-69

H-5644-69

0670-74

0670-75

49486938

STATE OR PROVINCE NO.

NATIONAL BOARD NO.

U11397

U11398

Page 20: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

Page 8 of 9

FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONS AS REQUIRED BY THE PROVISIONS OF THE ASME CODE RULES

1. OWNER - WISCONSIN PUBLIC SERVICE CORPORATION, 700 NORTH ADAMS,

P.O. BOX 19001, GREEN BAY, WISCONSIN 54307- 9001

2. PLANT - KEWAUNEE, N490 HIGHWAY 42, KEWAUNEE, WISCONSIN 54216-9511

3. PLANT UNIT - NO. 1

4. OWNER CERTIFICATE OF AUTHORIZATION - N/A

5. COMMERCIAL SERVICE DATE - JUNE 16, 1974

6. NATIONAL BOARD NUMBER FOR UNIT - N/A

7. COMPONENTS INSPECTED -

COMPONENT OR APPURTENANCE

Containment Spray Pump APCS-1B Gland Seal Cooler

Component Cooling Pump APCC-1A

Component Cooling Pump APCC-1B

Service Water Pump APSW-1A1

Service Water Pump APSW-1A2

Service Water Pump APSW-1B1

Service Water Pump APSW-1B2

Spent Fuel Pool Heat Exchanger AHSF

Main Steam Moisture Separator

Spent Fuel Pool Pump APSF-1A

MANUFACTURER OR INSTALLER

Helliflow

Ingersoll Dresser Pump Flow Serv.

Ingersoll Dresser Pump Flow Serv.

Worthington Pump

Worthington Pump

Worthington Pump

Worthington Pump

Struther Wells

Wright Austin

Gould Pumps

MANUFACTURER OR INSTALLER

SERIAL NO.

6080694

0600009

0600010

VTP27737

75 TU-1719-1

VTP27736

VTP27739

1-68-06-1519

6230

STATE OR NATIONAL PROVINCE NO. BOARD NO.

U11445

X.R. 6008

786A519.1

Page 21: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

Page 9 of 9

FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONS AS REQUIRED BY THE PROVISIONS OF THE ASME CODE RULES

1. OWNER - WISCONSIN PUBLIC SERVICE CORPORATION, 700 NORTH ADAMS,

P.O. BOX 19001, GREEN BAY, WISCONSIN 54307- 9001

2. PLANT - KEWAUNEE, N490 HIGHWAY 42, KEWAUNEE, WISCONSIN 54216-9511

3. PLANT UNIT - NO. 1

4. OWNER CERTIFICATE OF AUTHORIZATION - N/A

5. COMMERCIAL SERVICE DATE - JUNE 16, 1974

6. NATIONAL BOARD NUMBER FOR UNIT - N/A

7. COMPONENTS INSPECTED -

COMPONENT OR APPURTENANCE

Spent Fuel Pool Pump APSF-1B

Service Water Pump Strainer ASSW-1A1

Service Water Pump Strainer ASSW-1A2

Service Water Pump Strainer ASSW-1B1

Service Water Pump Strainer ASSW-1B2

Component Cooling Heat Exchanger AHCC1-IA

Component Cooling Heat Exchanger AHCC2-1B

MANUFACTURER OR INSTALLER

Gould Pumps

S.P. Kinney Engineers

S.P. Kinney Engineers

S.P. Kinney Engineers

S.P. Kinney Engineers

Engineers and Fabricators

Engineers and Fabricators

MANUFACTURER OR INSTALLER

SERIAL NO.

786A519.2

2278

2279

2280

2281

S-15748-A

S-15748-B

STATE OR PROVINCE NO.

U11426

U11427

NATIONAL BOARD NO.

1139

1140

Page 22: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

FORM NIS-1 (Back)

8. Examination Dates March 27,2001 to December 6, 2001

9. Inspection Period Identification 3rd

10. Inspection Interval Identification 3rd

1989 None 11. Applicable Edition of Section XI 1989 Addenda

12. Date/Revision of Inspection Plan November 27,2000/Revision 2

13. Abstract of Examinations and Tests. Include a list of examinations and tests and a statement concerning status of work required for the Inspection Plan. Reference Tab C

14. Abstract of Results of Examinations and Tests. Reference Tab B and Tab F

15. Abstract of Corrective Measures. Reference Tab B and Tab F

Utilization of ASME Boiler and Pressure Vessel Code Section XI: Code Cases N-416-1, N-416-2, N-460, N-491, N-498 and N-498-1.

We certify that a) the statements made in this report are correct, b) the examinations and tests meet the Inspection Plan

as required by the ASME Code, Section XI, and c) corrective measures taken conform to the rules of the ASMIE Code, Section X.

Certificate of Authorization No. (if applicable) '",/-' Expiration Date

Date .- K o Signed W Z -4A1e.. , cua-'u J 20 Owner

By~- A

CERTIFICATE OF INSERVICE INSPECTION

I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and

the State or Province of W1 I.OwNSiA and employed by NAxt-r-Fato SrmA, Lci', -r" of 4AA'rgoi•o C.-. have inspected the components described in this Owner's Report during the period

AfAR•,.4 ,'-7, ,avo/ to -e, , , and state that to the best of my knowledge and belief, the

Owner has performed examinations and tests and taken corrective measures described in this Owner's Report in accordance

with the Inspection Plan and as required by the ASME Code, Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning

the examinations, tests, and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor

his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or

connected with this inspection.

4 ,-__ Commissions A"'72 / eo190s/ 11( -4 -•'T / s

6Signature National Board, State. Province, and Endorsements

Date A3 A

Page 23: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

ATTACHMENT 4

Letter from T. Coutu (NMC)

To

Document Control Desk (NRC)

Dated

February 22, 2002

FORM NIS- 1 Owner's Report for Inservice Inspections for Class MC Compenents

Page 24: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONS AS REQUIRED BY THE PROVISIONS OF THE ASME CODE RULES

1. OWNER - WISCONSIN PUBLIC SERVICE CORPORATION, 700 NORTH ADAMS,

P.O. BOX 19001, GREEN BAY, WISCONSIN 54307- 9001

2. PLANT - KEWAUNEE, N490 HIGHWAY 42, KEWAUNEE, WISCONSIN 54216-9511

3. PLANT UNIT - NO. 1

4. OWNER CERTIFICATE OF AUTHORIZATION - N/A

5. COMMERCIAL SERVICE DATE - JUNE 16,1974

6. NATIONAL BOARD NUMBER FOR UNIT - N/A

7. COMPONENTS INSPECTED -

COMPONENT OR APPURTENANCE

Reactor Building Containment Vessel

Personnel Airlock

MANUFACTURER OR INSTALLER

Chicago Bridge and Iron Company

Chicago Bridge and Iron Company

MANUFACTURER OR INSTALLER

SERIAL NO.

C4454

C4454

STATE OR NATIONAL PROVINCE NO. BOARD NO.

U11423

U11423

Page 25: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

FORM NIS-1 (Back)

8, Examination Dates September 18, 2001 to December 4, 2001

9. Inspection Period Identification

10. Inspection Interval Identification

2nd

1st

1992 1992 11. Applicable Edition of Section XI ______________Addenda _____________

12. Date/Revision of Inspection Plan September 26, 2000/Revision 1

13. Abstract of Examinations and Tests. Include a list of examinations and tests and a statement concerning status of work required

for the Inspection Plan. Reference Tab C

14. Abstract of Results of Examinations and Tests. Reference Tab B and Tab F

15. Abstract of Corrective Measures. Reference Tab B and Tab F

We certify that a) the statements made in this report are correct, b) the examinations and tests meet the Inspection Plan

as required by the ASME Code, Section XI, and c) corrective measures taken conform to the rules of the ASME Code, Section

)a.

Certificate of Authorization No. (if applicable)

Date A a Q3 Signed J 2,1,WI

Expiration Date

p 5 6-j~c_ e-cOwner

By

National Board. State, Province. and Endorsements

CERTIFICATE OF INSERVICE INSPECTION

I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and

the State or Province of __ _ ___ ___ ___and employed by //A r10F*e ) ,7-6AbM13 It- r f

/4CAR7"FI C r have inspected the components described in this Owner's Report during the period Rdi001 t /e IOV, 200 ' , and state that to the best of my knowledge and belief, the

Owner has performed examinations and tests and taken corrective measures described in this Owner's Report in accordance

with the Inspection Plan and as required by the ASME Code, Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning

the examinations, tests, and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor

his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or

con:a with t inspecion.

Commissions ,,.'4 " '/A./S / 2" , 'V, '4

Page 26: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

ATTACHMENT 5

Letter from T. Coutu (NMC)

To

Document Control Desk (NRC)

Dated

February 22, 2002

FORM NIS-1 Owner's Report for Inservice Inspections of Replacement Steam Generators

Page 27: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

Page 1 of 2

FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONS AS REQUIRED BY THE PROVISIONS OF THE ASME CODE RULES

1. OWNER - WISCONSIN PUBLIC SERVICE CORPORATION, 700 NORTH ADAMS,

P.O. BOX 19001, GREEN BAY, WISCONSIN 54307- 9001

2. PLANT - KEWAUNEE, N490 HIGHWAY 42, KEWAUNEE, WISCONSIN 54216-9511

3. PLANT UNIT - NO. 1

4. OWNER CERTIFICATE OF AUTHORIZATION - N/A

5. COMMERCIAL SERVICE DATE - JUNE 16, 1974

6. NATIONAL BOARD NUMBER FOR UNIT - N/A

7. COMPONENTS INSPECTED -

COMPONENT OR APPURTENANCE

Steam Generator SG1A

Steam Generator SG1B

Steam Generator SG1A

Steam Generator SGlB

Steam Generator IA Safe End Welds

Steam Generator 1B Safe End Welds

Class 1 Reactor Coolant Piping Installation Welds

Class 2 Main Steam Piping Installation Welds

MANUFACTURER OR INSTALLER

Ansaldo Energia Milano

Ansaldo Energia Milano

Westinghouse

Westinghouse

Ansaldo Energia Milano

Ansaldo Energia Milano

Bechtel Corporation

Bechtel Corporation

MANUFACTURER OR INSTALLER

SERIAL NO.

0202

0201

1141

1142

NA

NA

NA

NA

STATE OR PROVINCE NO.

U11400

U11401

U11400

U11401

NA

NA

NA

NA

NATIONAL BOARD NO.

151

150

68-28

68-29

NA

NA

NA

NA

Page 28: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

Page 2 of 2

FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONS AS REQUIRED BY THE PROVISIONS OF THE ASME CODE RULES

1. OWNER - WISCONSIN PUBLIC SERVICE CORPORATION, 700 NORTH ADAMS,

P.O. BOX 19001, GREEN BAY, WISCONSIN 54307- 9001

2. PLANT - KEWAUNEE, N490 HIGHWAY 42, KEWAUNEE, WISCONSIN 54216-9511

3. PLANT UNIT - NO. 1

4. OWNER CERTIFICATE OF AUTHORIZATION - N/A

5. COMMERCIAL SERVICE DATE - JUNE 16,1974

6. NATIONAL BOARD NUMBER FOR UNIT - N/A

7. COMPONENTS INSPECTED -

COMPONENT OR APPURTENANCE

Class 2 Feedwater Piping Installation Welds

Class 2 Feedwater Nozzle Adapter and Nozzle to Pipe Installation Welds

MANUFACTURER OR INSTALLER

Bechtel Corporation

Bechtel Corporation

MANUFACTURER OR INSTALLER

SERIAL NO.

NA

NA

STATE OR PROVINCE NO.

NA

NA

NATIONAL BOARD NO.

NA

NA

Page 29: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

FORM NIS-1 (Back)

8. Examination Dates June 4, 2001 December 4, 2001

9. Inspection Period Identification 3rd

10. Inspection Interval Identification 3rd

1989 None

11. Applicable Edition of Section XI 1989 Addenda

12. Date/Revision of Inspection Plan November 27, 2000/Revision 2

13. Abstract of Examinations and Tests. Include a list of examinations and tests and a statement concerning status of work required

for the Inspection Plan. Reference Tab C

14. Abstract of Results of Examinations and Tests. Reference Tab B and Tab F

15. Abstract of Corrective Measures. Reference Tab B and Tab F

Utilization of ASME Boiler and Pressure Vessel Code Section XI: Code Cases

N-416-2 and N-460.

We certify that a) the statements made in this report are correct, b) the examinations and tests meet the Inspection Plan

as required by the ASME Code, Section XI, and c) corrective measures taken conform to the rules of the ASME Code, Section

XI.

Certificate of Authorization No. (if applicable) Expiration Date /

Date a\.JA4 CC, A.VQ3~ *QO Signed C-)J I I'~ L~. By J Owner

CERTIFICATE OF INSERVICE INSPECTION

I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and

the State or Province of 0A:i.o C-0 "T I,.- and employed by HA./,-rgao ST4Mi Boller CTr. of

4-e1-/o,'e-) r r" have inspected the components described in this Owner's Report during the period

,&,Tte, ,, ,0 O/ to A '9 "/, and state that to the best of my knowledge and belief, the

Owner has performed examinations and tests and taken corrective measures described in this Owner's Report in accordance

with the Inspection Plan and as required by the ASME Code, Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning

the examinations, tests, and corrective measures described in this Owner's Report. Furthermore. neither the Inspector nor

his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or

cone wit this inspection.

Commissions / 7 9" V/ Al/.S /OO"at XZ !ý 4., A J

c, .Actor's Signature National Board. State. Province. and Endorsements

V

Page 30: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

ATTACHMENT 6

Letter from T. Coutu (NMC)

To

Document Control Desk (NRC)

Dated

February 22, 2002

FORM NIS-2 Owner's Report for Repair or Replacement (74 Total)

Page 31: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section Xl

1. Owner Wisconsin Public Service Corporation

700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001

2. Plant Kewaunee Nuclear Power Plant

N490 HWY 42 Kewaunee, WI 54216-9511

3. Work Performed By Nuclear Management Company, LLC

700 First Street, Hudson. Wisconsin 54016

4. Identification of System 33 Class 2 SAFETY INJECTION

5. (a) Applicable Construction Code B31.1-1967

(b) Applicable Edition of Section X1 Utilized for Repairs or Replacements 1989

6. Identification of Components Repaired or Replaced and Replacement Components

Name of

Manufacturer

ITT GRINNELL VALVE COMPANY

Manufacturer Serial No.

NA

National Board No.

NA

Other ID

NA

Date 11/1/2001

Sheet 1 of 2

Unit No. 1

Work Order 01-016956

Type Code Sym. Stamp N..A

Authorization No. NA

Expiration Date NA

Code Case NA

Year Built

1967

Repaired, ASMERepaired,

Replaced, or Replacement

REPAIRED

7. Description of Work REPAIR CLASS 2 SAFETY INJECTION SYSTEM 2" HANGER RSI-H70 DUE TO MISSING JAM NUT.

8. Tests conducted Hydrostatic

Other DJD Pneumatic

Pressure

F Nominal Operating Pressure

psi Test Temp.

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

Name of

Component

RSI-H70

ASME Code

Stamped

N

D: deg. F

Exempt 17

N

Page 32: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

NIS-2 (Back)

Sheet 2 of 2

Date: 11/1/2001

Name of Component: RSI-H70

Work Order Number: 01-016956

.20 _____

Certificate of Compliance

We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the

ASME Code Section XL. Repair or Replacement

Type Code Symbol Stamp NA

Certificate of Authorization No. NA Expiration Date NA

Signed & Date 20 0A

Owner or Owner's Designee, Title

Certificate of INSERVICE INSPECTION

I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors

and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT

have inspected the components described in the Owner's Report during the period 7-;5'i0" to /-3/1 , and state that

to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described

in this Owners Report in accordance with the requirements of the ASME Code, Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning

the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor

his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising

from or connected with this inspection.

• • • Commissions NB7741, I, N, IS, A WIS 100024

National Board, State, Province, and Endorsementspectors nature

Page 33: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT

As Required by the Provisions of the ASME Code Section XI

1. Owner Wisconsin Public Service Corporation

700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001

2. Plant Kewaunee Nuclear Power Plant

N490 HWY 42 Kewaunee, WI 54216-9511

3. Work Performed By Nuclear Management Company, LLC

700 First Street, Hudson, Wisconsin 54016

4. Identification of System 33 Class 2 SAFETY INJECTION

5. (a) Applicable Construction Code B31.1-1967

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989

6. Identification of Components Repaired or Replaced and Replacement Components

Name of

Component

RSI-H73

Name of Manufacturer

ITT GRINNELL VALVE COMPANY

Manufacturer Serial No.

NA

National Board No.

NA NA 1967 XtzHAIh(tU '4

Other ID

Date 11/1/2001

Sheet 1 of 2

Unit No. 1

Work Order 01-016956

Type Code Sym. Stamp NA

Authorization No. NA

Expiration Date N.A

Code Case NAA

Year Built

Repaired, A�M �Repairedl, Replaced, or

Replacement

7. Description of Work REPAIR CLASS 2 SAFETY INJECTION SYSTEM 2" HANGER RSI-H73 DUE TO UNSPREAD COTTER PIN.

8. Tests conducted Hydrostatic

Other n

El Pneumatic

Pressure

Elpsi

Nominal Operating Pressure

Test Temp.

--] Exempt

deg. F

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

ASME Code Stamped

REPAIREDNA 1967NA

Page 34: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

NIS-2 (Back)

Sheet 2 of 2

Date: . 11/1/2001

Name of Component: RSI-H73

Work Order Number: 01-016956

Certificate of Compliance

We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the

ASME Code Section XI. Repair or Replacement

Type Code Symbol Stamp NA

Certificate of Authorization No. NA Expiration Date NA

Signed ZSA4•V . •Jg? A o it. J OL, M Date ,20 L

Owner or Owner's Designee, Title

Certificate of INSERVICE INSPECTION

I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors

and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT

have inspected the components described in the Owner's Report during the period 7- ,T-" to /- -3/-02., and state that

to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described

in this Owner's Report in accordance with the requirements of the ASME Code, Section XL.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning

the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor

his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising

from or connected with this inspection.

s uCommissions NB7741, I, N, IS, A WIS 100024

pectors Signature National Board, State, Province, and Endorsements

Date .-• 20 o'-

Page 35: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT

As Required by the Provisions of the ASME Code Section XI

1. Owner Wisconsin Public Service Corporation Date 11/1

700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001 Sheet 1

2. Plant Kewaunee Nuclear Power Plant Unit No.

N490 HWY 42 Kewaunee. WI 54216-9511 Work Order

3. Work Performed By Nuclear Management Company, LLC Type Code

700 First Street, Hudson, Wisconsin 54016 Authorizatio

4. Identification of System 33 Class 2_ SAFETY INJECTION Expiration D

5. (a) Applicable Construction Code B31.1-1967 Code Case

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989

6. Identification of Components Repaired or Replaced and Replacement Components

Name of

Component

RSI-H74

Name of

Manufacturer

ITT GRINNELL VALVE COMPANY

Manufacturer Serial No.

NA

National Board No.

NA

Other ID

NA 1967 REPAII�U

Year Built

/2001 of 2

1

01-016956

Sym. Stamp NA

nNo. NA

late NA

NA

Repa•ired, Replaced, or Replacement

7. Description of Work REPAIR CLASS 2 SAFETY INJECTION 2" HANGER RSI-H74 DUE TO LOOSE NUT.

8. Tests conducted Hydrostatic

Other D

Pneumatic F

Pressure

Nominal Operating Pressure

psi Test Temp.

El Exempt [-7 deg. F

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

M�IYI�

Code Stamped

REPAIRED1967NA

Page 36: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

NIS-2 (Back)

Sheet 2 of 2

Date: 11/1/2001

Name of Component: RSI-H74

Work Order Number: 01-016956

Certificate of Compliance

We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the

ASME Code Section Xl. Repair or Replacement

Type Code Symbol Stamp NA

Certificate of Authorization No. NA Expiration Date NA

Signed 44& L-"O Date 4Ak M ,20 0

Owner or Owner's Designee, Title

Certificate of INSERVICE INSPECTION

I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors

and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT

have inspected the components described in the Owner's Report during the period 7--V-1V to /-•i"-2,, and state that

to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described

in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning

the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor

his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising

from or connected with this inspection.

4 12 .,0 Commissions NB7741, I, N, IS, A WIS 100024

Dae-20 ___

National Board, State, Province, and Endorsementst nspector's ,2nature

Page 37: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT

As Required by the Provisions of the ASME Code Section XI

1. Owner Wisconsin Public Service Corporation

700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001

2. Plant Kewaunee Nuclear Power Plant

N490 HWY 42 Kewaunee, WI 54216-9511

3. Work Performed By Nuclear Management Company, LLC

700 First Street, Hudson. Wisconsin 54016

4. Identification of System 05A Class 2 FEEDWATER

5. (a) Applicable Construction Code B31.1-1967

(b) Applicable Edition of Section X1 Utilized for Repairs or Replacements 1989

6. Identification of Components Repaired or Replaced and Replacement Components

Name of

Component

FDW-H170

Name of Manufacturer

ITT GRINNEL COMPANY

Manufacturer Serial No.

NF

National Board No.

NA

Other ID

NA 1967 REPAI RED N

Date 11/16/2001

Sheet 1 of 2

Unit No. 1

Work Order 01-018043

Type Code Sym. Stamp NA

Authorization No. NA

Expiration Date NNA

Code Case NA

Year Built

Nep�I[�u, MOIViE

Repaired, Replaced, or Replacement

7. Description of Work REPAIR CLASS 2 FEEDWATER SYSTEM 16" SUPPORT FDW-H170 DUE TO LOOSE NUTS.

8. Tests conducted Hydrostatic F

Other DPneumatic D-]Pressure

Nominal Operating Pressure

psi Test Temp.

1:1 Exempt E'

deg. F

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

Code Stamped

REPAI RED IN1967NA

Page 38: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

NIS-2 (Back)

Sheet 2 of 2

Date: 11/16/2001

Name of Component: FDW-H170

Work Order Number: 01-018043

Date / 20 -__ _

Certificate of Compliance

We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the

ASME Code Section Xl. Repair or Replacement

Type Code Symbol Stamp NA

Certificate of Authorization No. NA Expiration Date NA

Signed PC/W.t"J .VJ.,l.W.dI0, V2l"J Date • ,20 a

Owner or Owner's Designee, Title

Certificate of INSERVICE INSPECTION

I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors

and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT

have inspected the components described in the Owner's Report during the period 7-.2)VP to /-/-#1, and state that

to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described

in this Owners Report in accordance with the requirements of the ASME Code, Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning

the examinations and corrective measures described in this Owners Report. Furthermore, neither the Inspector nor

his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising

from or connected with this inspection.

""-" Commissions NB7741, I, N, IS, A WIS 100024

ýnspectors ý4nature National Board, State, Province, and Endorsements

Page 39: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section XI

1. Owner Wisconsin Public Service Corporation

700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001

2. Plant Kewaunee Nuclear Power Plant

N490 HWY 42 Kewaunee, WI 54216-9511

3. Work Performed By Nuclear Management Company, LLC

700 First Street, Hudson, Wisconsin 54016

4. Identification of System 05B Class 2 AUXILIARY FEEDWATER

5. (a) Applicable Construction Code B31.1-1967

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989

6. Identification of Components Repaired or Replaced and Replacement Components

Name of

Component

FDW-H39

Name of Manufacturer

ITT GRINNEL COMPANY

Manufacturer Serial No.

NA

National Board No.

NA

Other ID

NA 1967 REPAIRED N

Date 11/16/2001

Sheet 1 of 2

Unit No. 1

Work Order 01-018044

Type Code Sym. Stamp N.A

Authorization No. NA

Expiration Date NA

Code Case NA

Year Built

Repaired, ASMERepaired,

Replaced, or Replacement

7. Description of Work REPAIR CLASS 2 AUXILIARY FEEDWATER SYSTEM 3" HANGER FDW-H39 DUE TO LOOSE NUT ON PIPE CLAMP.

8. Tests conducted Hydrostatic

Other F

El Pneumatic

Pressure

Nominal Operating Pressure

psi Test Temp.

D: deg. F

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

ASME Code Stamped

Exempt []

REPAIRED N1967NA

Page 40: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

NIS-2 (Back)

Sheet 2 of 2

Date: 11/16/2001

Name of Component: FDW-H39

Work Order Number: 01-018044

Certificate of Compliance

We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the

ASME Code Section XI. Repair or Replacement

Type Code Symbol Stamp NA

Certificate of Authorization No. NA Expiration Date NA

Signed Y g%/e, /1kA/1A41WJ5KZ1 MAMA owrj Looj&ýDate _ 20 OX I Owner or Owner's Designee, Title

Certificate of INSERVICE INSPECTION

I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors

and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT

have inspected the components described in the Owner's Report during the period 7- 2y-i" to /- 31-OZ , and state that

to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described

in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning

the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor

his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising

from or connected with this inspection.

Commissions NB7741, I, N, IS, A WIS 100024

Inspector's S;(nature National Board, State, Province, and Endorsements

Date-e / ,20 D

Page 41: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT

As Required by the Provisions of the ASME Code Section XI

1. Owner Wisconsin Public Service Corporation

700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001

2. Plant Kewaunee Nuclear Power Plant

N490 HWY 42 Kewaunee, WI 54216-9511

3. Work Performed By Nuclear Management Company, LLC

700 First Street, Hudson, Wisconsin 54016

4. Identification of System 05B Class 2 AUXILIARY FEEDWATER

5. (a) Applicable Construction Code B31.1-1967

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989

6. Identification of Components Repaired or Replaced and Replacement Components

Name of Component

FDW-H43

Name of Manufacturer

ITT GRINNEL COMPANY

Manufacturer Serial No.

NA

National Board No.

NA NA 1967 K�HAl�U I"

Other ID

Date 11/15/2001

Sheet 1 of 2

Unit No. 1

Work Order 01-018044

Type Code Sym. Stamp NA.

Authorization No. NA

Expiration Date NA

Code Case NA

Year Built

Repaired, ASM ERepaired, Replaced, or

Replacement

7. Description of Work REPAIR CLASS 2 AUXILAIRY FEEDWATER SYSTEM 3" HANGER FDW-H43 DUE TO LOOSE NUT ON THE PIPE

CLAMP.

8. Tests conducted Hydrostatic ]

Other [Pneumatic Li Pressure

Nominal Operating Pressure

psi Test Temp.

n Exempt r•

deg. F

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

ASME Code Stamped

REPAIRED INNA 1967NA

Page 42: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

NIS-2 (Back)

Sheet 2 of 2

Date: 11/15/2001

Name of Component: FDW-H43

Work Order Number: 01-018044

Certificate of Compliance

We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the

ASME Code Section XI. Repair or Replacement

Type Code Symbol Stamp NA

Certificate of Authorization No. NA Expiration Date NA

Signed Date__ ___ __ _2Dat 2 tQ

Owner or Owner's Designee, Title U

Certificate of INSERVICE INSPECTION

I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors

and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT

have inspected the components described in the Owner's Report during the period '7-o.rOe to 1-3t-OZ , and state that

to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described

in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning

the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor

his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising

from or connected with this inspection.

Commissions NB7741, I, N, IS, A WIS 100024

Inspector Signature National Board, State, Province, and Endorsements

Date / 20 0 L"

Page 43: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section X1

1. Owner Wisconsin Public Service Corporation

700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001

2. Plant Kewaunee Nuclear Power Plant

N490 HWY 42 Kewaunee. WI 54216-9511

3. Work Performed By Nuclear Management Company, LLC

700 First Street, Hudson, Wisconsin 54016

4. Identification of System 05B Class 2 AUXILIARY FEEDWATER

5. (a) Applicable Construction Code B31.1-1967

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989

6. Identification of Components Repaired or Replaced and Replacement Components

Name of

Component

FDW-H44

Name of

Manufacturer

ITT GRINNEL COMPANY

Manufacturer Serial No.

NA

National Board No.

NA

Other ID

NA

Date 11/16/2001

Sheet 1 of 2

Unit No. 1

Work Order 01-018044

Type Code Sym. Stamp NA

Authorization No. NA

Expiration Date NA

Code Case NA

Year Built

1967

Repaired, ASMERepaired,

Replaced, or Replacement

REPAIRED

7. Description of Work REPAIR CLASS 2 AUXILAIRY FEEDWATER SYSTEM 3" HANGER FDW-H44 DUE TO LOOSE NUT ON THE PIPE

CLAMP.

8. Tests conducted Hydrostatic

Other D

Pneumatic

Pressure

Nominal Operating Pressure

psi Test Temp.

0l deg. F

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

ASME Code

Stamped

N

Exempt El

N

Page 44: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

NIS-2 (Back)

Sheet 2 of 2

Date: 11/16/2001

Name of Component: FDW-H44

Work Order Number: 01-018044

Certificate of Compliance

We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the

ASME Code Section XI. Repair or Replacement

Type Code Symbol Stamp NA

Certificate of Authorization No. NA Expiration Date NA

Signed Iý ?,- Date••".i~at•-/--'4•P • (0.l~'l4/ Dh6t4 ,20 OcL

Owner or Owner's Designee, Title

Certificate of INSERVICE INSPECTION

I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors

and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT

have inspected the components described in the Owner's Report during the period '7--F-7 to / -• ,and state that

to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described

in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning

the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor

his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising

from or connected with this inspection.

•4, Commissions NB7741, I, N, IS, A WIS 100024

nspector's Signa ure National Board, State, Province, and Endorsements

Date / 20 ___'-

Page 45: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section XI

1. Owner Wisconsin Public Service Corooration

700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001

2. Plant Kewaunee Nuclear Power Plant

N490 HWY 42 Kewaunee, WI 54216-9511

3. Work Performed By Nuclear Management Company, LLC

700 First Street, Hudson, Wisconsin 54016

4. Identification of System 89A Class MC BUILDINGS - STRUCTURES

5. (a) Applicable Construction Code SEC. Il-CL.B-1965W

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1992 ADDENDA

6. Identification of Components Repaired or Replaced and Replacement Components

Name of

Component

RBCV

Name of

Manufacturer

CHICAGO BRIDGE AND IRON

Manufacturer Serial No.

C4454

National Board No.

NA

Other ID

1S-0002

Date 11/24/2001

Sheet 1 of 2

Unit No. 1

Work Order 01-018045

Type Code Sym. Stamp N.•A

Authorization No. NA

Expiration Date NA

Code Case NA

Year Built

1969

Repaired, Replaced, or Replacement

REPAIRED

7. Description of Work REPAIR CLASS MC (METAL CONTAINMENT) REACTOR BUILDING CONTAINMENT VESSEL MOISTURE BARRIER

BONDING BETWEEN ELEVATION 606' AND METAL CONTAINMENT.

8. Tests conducted Hydrostatic

Other 1

Dl Pneumatic

Pressure

D- Nominal Operating Pressure

psi Test Temp.

Exempt Li

deg. F

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

ASME Code

Stamped

Y

Page 46: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

NIS-2 (Back)

Sheet 2 of 2

Date: 11/24/2001

Name of Component: RBCV

Work Order Number: 01-018045

Certificate of Compliance

We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the

ASME Code Section XI. Repair or Replacement

Type Code Symbol Stamp NA

Certificate of Authorization No. NA Expiration Date NA

Signed.20

Owner or Owner's Designee, Title

Certificate of INSERVICE INSPECTION

I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors

and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT

have inspected the components described in the Owner's Report during the period T'7-Ar'- to /-31-03-, and state that

to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described

in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning

the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor

his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising

from or connected with this inspection.

Commissions NB7741, I, N, IS, A WIS 100024

nspector's nature National Board, State, Province, and Endorsements

Date / ,20 D,..

Page 47: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT

As Required by the Provisions of the ASME Code Section XI

1. Owner Wisconsin Public Service Corporation

700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001

2. Plant Kewaunee Nuclear Power Plant

N490 HWY 42 Kewaunee. WI 54216-9511

3. Work Performed By Nuclear Management Company, LLC

700 First Street, Hudson, Wisconsin 54016

4. Identification of System 33 Class 1 SAFETY INJECTION

5. (a) Applicable Construction Code B16.5-1967

(b) Applicable Edition of Section Xi Utilized for Repairs or Replacements 1989

6. Identification of Components Repaired or Replaced and Replacement Components

Name of

Component

S1-13B

Name of Manufacturer

VELAN VALVE CORPORATION

Manufacturer Serial No.

NF

National Board No.

NA

Other ID

S1116-002 1967 R�PLAC�M�N I N

Date 12/1/2001

Sheet 1 of 2

Unit No. 1

Work Order 01-018277

Type Code Sym. Stamp NA

Authorization No. NA

Expiration Date NA

Code Case NA

Year Built

I�p�ir�u, P.�IVIE

Repaired, Replaced, or Replacement

7. Description of Work REPAIR CLASS 1 6" SAFETY INJECTION SYSTEM VALVE SI-13B DUE TO 4 PIN HOLE LEAKS IN THE SEAL WELD

INCLUDING REPLACING 4 STUDS.

8. Tests conducted Hydrostatic El

Other D]Pneumatic "

Pressure 2240 psi

Nominal Operating Pressure

Test Temp. f55 deg. F

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

Code Stamped

Exempt F

REPLACEMENT N1967S1 116-002

Page 48: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

NIS-2 (Back)

Sheet 2 of 2

Date: 12/1/2001

Name of Component: S1-13B

Work Order Number: 01-018277

Certificate of Compliance

We Certify that the statements made in the report are correct and this REPLACEMENT conforms to the rules of the

ASME Code Section Xl. Repair or Replacement

Type Code Symbol Stamp NA

Certificate of Authorization No. NA Expiration Date NA

Signed &UN44 . •d w Date L 20 Q

Owner or Owner's Designee, Title

Certificate of INSERVICE INSPECTION

I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors

and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT

have inspected the components described in the Owner's Report during the period 7-15r-,90' to /- 3 /-, and state that

to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described

in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning

the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor

his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising

from or connected with this inspection.

Commissions NB7741, I1 N, IS, A WIS 100024

Inspector's ignature National Board, State, Province, and Endorsements

Date / ,20 0,__

Page 49: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section XI

1. Owner Wisconsin Public Service Corporation

700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001

2. Plant Kewaunee Nuclear Power Plant

N490 HWY 42 Kewaunee, WI 54216-9511

3. Work Performed By Nuclear Management Company, LLC

700 First Street. Hudson, Wisconsin 54016

4. Identification of System 89A Class MC BUILDINGS - STRUCTURES

5. (a) Applicable Construction Code SEC. III-CL.B-1965W

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1992 ADDENDA

6. Identification of Components Repaired or Replaced and Replacement Components

Name of

Component

EMRG. AIRLOCK

Name of Manufacturer

CHICAGO BRIDGE AND IRON

Manufacturer Serial No.

C4454

National Board No.

NA 1S-0002 1969 t�.MAI �tU I

Other ID

Date 11/21/2001

Sheet 1 of 2

Unit No. 1

Work Order 01-018283

Type Code Sym. Stamp NA

Authorization No. NA

Expiration Date NA

Code Case NA

Year Built

Repaired, ASMERepaired, Replaced, or

Replacement

7. Description of Work REPAIR CLASS MC METAL CONATINMENT EMERGENCY AIRLOCK DUE TO BOLT NOT FLUSH WITH SURFACE.

8. Tests conducted Hydrostatic

Other F"

El Pneumatic

Pressure

R7psi

Nominal Operating Pressure

Test Temp.

Exempt Li

deg. F

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

ASME Code Stamped

REPAIRED ,f1S-0002 1969NA

Page 50: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

NIS-2 (Back)

Sheet 2 of 2

Date: 11/21/2001

Name of Component: EMRG. AIRLOCK

Work Order Number: 01-018283

Certificate of Compliance

We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the

ASME Code Section XI. Repair or Replacement

Type Code Symbol Stamp NA

Certificate of Authorization No. NA Expiration Date NA

Signed • • ••1 Date - " ,20 Oý

Owner or Owner's Designee, Title

Certificate of INSERVICE INSPECTION

I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors

and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT

have inspected the components described in the Owner's Report during the period 7-23-'o to -3/-,2. , and state that

to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described

in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning

the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor

his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising

from or connected with this inspection.

7ýý .-,Commissions NB7741, 1, N, IS, A WIS 100024

pector's Si" ature National Board, State, Province, and Endorsements

Date ; -.1"- .20 __ _._.

Page 51: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section XI

1. Owner Wisconsin Public Service Corporation

700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001

2. Plant Kewaunee Nuclear Power Plant

N490 HWY 42 Kewaunee, WI 54216-9511

3. Work Performed By Nuclear Management Company, LLC

700 First Street, Hudson, Wisconsin 54016

4. Identification of System 33 Class 1 SAFETY INJECTION

5. (a) Applicable Construction Code B16.5-1967

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989

6. Identification of Components Repaired or Replaced and Replacement Components

Name of

Component

S1-13B

Name of

Manufacturer

VELAN VALVE CORPORATION

Manufacturer Serial No.

NF

National Board No.

NA

Other ID

S1116-002

Date 12/1/2001

Sheet 1 of 2

Unit No. 1

Work Order 01-018402

Type Code Sym. Stamp NA

Authorization No. NA

Expiration Date NA

Code Case NA

Year Built

1967 REPAIRED N

Repaired, ASMERepaired,

Replaced, or Replacement

7. Description of Work REMOVE GOUGES AND PREPARE GASKET SURFACE OF CLASS 1 SAFETY INJECTION SYSTEM 6" VALVE SI

13B BONNET SURFACE.

8. Tests conducted Hydrostatic

Other j

Pneumatic El Pressure 2240 psi

Nominal Operating Pressure

Test Temp. 551 deg. F

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

ASME Code

Stamped

Exempt

REPAIRED N1967

Page 52: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

NIS-2 (Back)

Sheet 2 of 2

Date: 12/1/2001

Name of Component: SI-13B

Work Order Number: 01-018402

Certificate of Compliance

We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the

ASME Code Section XI. Repair or Replacement

Type Code Symbol Stamp NA

Certificate of Authorization No. NA Expiration Date NA

Signed Owwvf Date .20 "

Owner or Owner's Designee, Title

Certificate of INSERVICE INSPECTION

I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors

and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT

have inspected the components described in the Owner's Report during the period "7-21o-ap to __3_-9__ , and state that

to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described

in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning

the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor

his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising

from or connected with this inspection.

Commissions NB7741, 1, N, IS, A WIS 100024

Inspectors ignature National Board, State, Province, and Endorsements

Da tee 20 99,A

Page 53: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT

As Required by the Provisions of the ASME Code Section XI

1. Owner Wisconsin Public Service Corporation

700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001

2. Plant Kewaunee Nuclear Power Plant

N490 HWY 42 Kewaunee. WI 54216-9511

3. Work Performed By Nuclear Management Company, LLC

700 First Street, Hudson, Wisconsin 54016

4. Identification of System 34 Class 2 RESIDUAL HEAT REMOVAL

5. (a) Applicable Construction Code B31.1-1967

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989

6. Identification of Components Repaired or Replaced and Replacement Components

Name of

Manufacturer

ITT GRINNELL VALVE COMPANY

Manufacturer Serial No.

NA

National Board No.

NA

Other ID

NA

Date 11/26/2001

Sheet 1 of 2

Unit No. 1

Work Order 01-018522

Type Code Sym. Stamp NA.

Authorization No. NA

Expiration Date NA

Code Case NNA

Year Built

1967 REPAIRED N

Hepaired, A�MLRepaired, Replaced, or

Replacement

7. Description of Work REPAIR CLASS 2 RESIDUAL HEAT REMOVAL SYSTEM 8" HANGER RHR-H18 DUE TO LOAD SETTING OF SCALE.

8. Tests conducted Hydrostatic "

Other n

Pneumatic -

Pressure

Nominal Operating Pressure

psi Test Temp.

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

Name of

Component

RHR-H18

ASME Code Stamped

D: deg. F

Exempt El

REPAIRED IN1967

Page 54: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

NIS-2 (Back)

Sheet 2 of 2

Date: 11/26/2001

Name of Component: RHR-H18

Work Order Number: 01-018522

Certificate of Compliance

We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the

ASME Code Section Xl. Repair or Replacement

Type Code Symbol Stamp NA

Certificate of Authorization No. NA Expiration Date NA

Signed P - -- eOU Date 20 0

Owner or Owner's Designee, Title

Certificate of INSERVICE INSPECTION

I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors

and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT

have inspected the components described in the Owner's Report during the period 7-0.S'- C.V to ________ , and state that

to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described

in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning

the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor

his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising

from or connected with this inspection.

,1 -ý7ý Commissions NB7741, I, N, IS, A WIS 100024

National Board, State, Province, and Endorsements-- lnspector's S(nature

Date- ,'/ ,20 9 5La7

Page 55: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT

As Required by the Provisions of the ASME Code Section Xl

1. Owner Wisconsin Public Service Corporation

700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001

2. Plant Kewaunee Nuclear Power Plant

N490 HWY 42 Kewaunee, WI 54216-9511

3. Work Performed By Nuclear Management Company, LLC

700 First Street, Hudson, Wisconsin 54016

4. Identification of System 34 Class 2 RESIDUAL HEAT REMOVAL

5. (a) Applicable Construction Code B31.1-1967

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989

6. Identification of Components Repaired or Replaced and Replacement Components

Name of

Component

RHR-H24

Name of

Manufacturer

ITT GRINNELL VALVE COMPANY

Manufacturer Serial No.

NA

National Board No.

NA

Other ID

NA 1967 REPAIRED N

Date 11/26/2001

Sheet I of 2

Unit No. 1

Work Order 01-018522

Type Code Sym. Stamp N__A

Authorization No. NA

Expiration Date NA

Code Case NA

Year Built

Kepalreo, A�M �Repaired, Replaced, or

Replacement

7. Description of Work REPAIR CLASS 2 RESIDUAL HEAT REMOVAL SYSTEM 8" HANGER RHR-H24 DUE TO MISALIGNMENT OF

SUPPORT.

8. Tests conducted Hydrostatic

Other F]

Pneumatic F1 Pressure

Nominal Operating Pressure

psi Test Temp.

D: deg. F

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

Code Stamped

Exempt E

REPAIRED NNA 1967

Page 56: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

NIS-2 (Back)

Sheet 2 of 2

Date: 11/26/2001

Name of Component: RHR-H24

Work Order Number: 01-018522

Certificate of Compliance

We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the

ASME Code Section Xl. Repair or Replacement

Type Code Symbol Stamp NA

Certificate of Authorization No. NA Expiration Date NA

Signed Date 20 0.1

Owner or Owner's Designee, Title

Certificate of INSERVICE INSPECTION

I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors

and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT

have inspected the components described in the Owner's Report during the period 7-,Sr-6' to /- .3/'-OZ , and state that

to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described

in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning

the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor

his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising

from or connected with this inspection.

nsp C .Commissions NB7741, I, N, IS, A WIS 100024

nspector's Sig re National Board, State, Province, and Endorsements

Da ate7• •4 20 0

Page 57: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section XI

1. Owner Wisconsin Public Service Corporation

700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001

2. Plant Kewaunee Nuclear Power Plant

N490 HWY 42 Kewaunee, WI 54216-9511

3. Work Performed By Nuclear Management Company, LLC

700 First Street, Hudson, Wisconsin 54016

4. Identification of System 33 Class 1 SAFETY INJECTION

5. (a) Applicable Construction Code B31.1-1967

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989

6. Identification of Components Repaired or Replaced and Replacement Components

Name of

Component

RSI-H7

Name of Manufacturer

ITT GRINNELL VALVE CO.

Manufacturer Serial No.

NA

National Board No.

NA

Other ID

NA 1967 REPAIRED N

Date 11/26/2001

Sheet 1 of 2

Unit No. 1

Work Order 01-018525

Type Code Sym. Stamp NA

Authorization No. NA

Expiration Date NA

Code Case NA

Year Built

Repaired, ASMERepaired,

Replaced, or Replacement

7. Description of Work REPAIR CLASS 1 SAFETY INJECTION SYSTEM 2" SUPPORT RSI-H7 DUE TO DAMAGED SPRING CAN.

8. Tests conducted Hydrostatic []

Other F

Pneumatic R

Pressure

Nominal Operating Pressure

psi Test Temp.

D3 deg. F

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

ASME Code Stamped

Exempt 17

REPAIRED N1967NA

Page 58: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

NIS-2 (Back)

Sheet 2 of 2

Date: 11/26/2001

Name of Component: RSI-H7

Work Order Number: 01-018525

Certificate of Compliance

We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the

ASME Code Section XI. Repair or Replacement

Type Code Symbol Stamp NA

Certificate of Authorization No. NA Expiration Date NA

Signed /4.,6 t I.TIVA•OffN ,O"m,. Date JA,20 _.L_

Owner or Owner's Designee, Title

Certificate of INSERVICE INSPECTION

I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors

and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT

have inspected the components described in the Owner's Report during the period I.- 29.'-P to /- 3/-0 ZI., and state that

to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described

in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning

the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor

his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising

from or connected with this inspection.

9 sp tCommissions NB7741, I, N, IS, A WIS 100024

ospector's SiLgature National Board, State, Province, and Endorsements

Date 20 01:4-

Page 59: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section XI

1. Owner Wisconsin Public Service Corporation

700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001

2. Plant Kewaunee Nuclear Power Plant

N490 HWY 42 Kewaunee, WI 54216-9511

3. Work Performed By Nuclear Management Company, LLC

700 First Street. Hudson, Wisconsin 54016

4. Identification of System 34 Class 2 RESIDUAL HEAT REMOVAL

5. (a) Applicable Construction Code B31.1-1967

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989

6. Identification of Components Repaired or Replaced and Replacement Components

Name of

Component

RHR-3B

Name of

Manufacturer

CRANE COMPANY

Manufacturer Serial No.

NF

National Board No.

NA

Date 12/19/2001

Sheet 1 of 2

Unit No. 1

Work Order 01-018670

Type Code Sym. Stamp NA

Authorization No. NA

Expiration Date NA

Code Case NA

Other Year ID Built

AC034-002 1972 REPAIRED N

ICepaireu, M�IVI�

R~epaired, Replaced, or Replacement

7. Description of Work REPAIR BONNET TO BODY LEAK BY TORQUING BOLTING ON CLASS 2 RESIDUAL HEAT REMOVAL SYSTEM 8"

VALVE RHR-3B.

8. Tests conducted Hydrostatic

Other D

R Pneumatic

Pressure

D Nominal Operating Pressure

psi Test Temp.

E] deg. F

9. Remarks NOT APPLICABLE.

Applicable Manufacturers Data Reports to be Attached

Code Stamped

Exempt F•

REPAIRED NAC034-002 1972

Page 60: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

NIS-2 (Back)

Sheet 2 of 2

Date: 12/19/2001

Name of Component: RHR-3B

Work Order Number: 01-018670

Certificate of Compliance

We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the

ASME Code Section XI. Repair or Replacement

Type Code Symbol Stamp NA

Certificate of Authorization No. NA Expiration Date NA

Signed (O Date 20 Q2 Owner or Owner's Designee, Title

Certificate of INSERVICE INSPECTION

I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors

and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT

have inspected the components described in the Owner's Report during the period 7-;r-00 to I/-3zNC , and state that

to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described

in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning

the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor

his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising

from or connected with this inspection.

Commissions NB7741, I, N, IS, A WIS 100024

Inspecors naNational Board, State, Province, and Endorsements

Date d, ,/ ,20 O,-P

Page 61: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section Xl

1. Owner Wisconsin Public Service Corporation

700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001

2. Plant Kewaunee Nuclear Power Plant

N490 HWY 42 Kewaunee, WI 54216-9511

3. Work Performed By Nuclear Management Company, LLC

700 First Street, Hudson, Wisconsin 54016

4. Identification of System 33 Class 2 SAFETY INJECTION

5. (a) Applicable Construction Code B16.5-1967

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989

6. Identification of Components Repaired or Replaced and Replacement Components

Name of

Component

SI-9B

Name of Manufacturer

VELAN VALVE CORPORATION

Manufacturer Serial No.

NA

National Board No.

NA

Other ID

S1012-002

Date 12/1/2001

Sheet 1 of 2

Unit No. 1

Work Order 97-212982

Type Code Sym. Stamp NA

Authorization No. NA

Expiration Date NA

Code Case NA

Year Built

1967

Repaired, Replaced, or Replacement

REPAIRED

7. Description of Work OPEN FOR REPACKING CLASS 2 SAFETY INJECTION SYSTEM 3" VALVE SI-9B.

8. Tests conducted Hydrostatic F] Other n

Pneumatic F Nominal Operating Pressure r

Pressure 2190 psi Test Temp. 551 deg. F

9. Remarks NOT APPLICABLE.

Applicable Manufacturers Data Reports to be Attached

ASME Code

Stamped

N

Exempt 1

N

Page 62: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

NIS-2 (Back)

Sheet 2 of 2

Date:. 12/1/2001

Name of Component: SI-9B

Work Order Number: 97-212982

Certificate of Compliance

We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the

ASME Code Section XI. Repair or Replacement

Type Code Symbol Stamp NA

Certificate of Authorization No. NA Expiration Date NA

Signed 7&ifL 4c A C L ft•• L4A, v, Date te kLM4AMJ 20 0_.

Owner or Owner's Designee, Title

Certificate of INSERVICE INSPECTION

I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors

and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT

have inspected the components described in the Owner's Report during the period -I- 2r-,O9 to b }-.,,, and state that

to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described

in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning

the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor

his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising

from or connected with this inspection.

X • .Commissions NB7741, I, N, IS, A WIS 100024

(--ýpectors Sign ure National Board, State, Province, and Endorsements

Date / ,20 0 "-

Page 63: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section Xl

1. Owner Wisconsin Public Service Corporation

700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001

2. Plant Kewaunee Nuclear Power Plant

N490 HWY 42 Kewaunee. WI 54216-9511

3. Work Performed By Nuclear Management Company, LLC

700 First Street, Hudson, Wisconsin 54016

4. Identification of System 36 Class 1 REACTOR COOLANT

5. (a) Applicable Construction Code B16.5-1967

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989

6. Identification of Components Repaired or Replaced and Replacement Components

Name of

Component

LD-3

Name of

Manufacturer

MASONEILAN INTERNATIONAL

Manufacturer Serial No.

H46695-1-2

National Board No.

NA

Date 12/3/2001

Sheet 1 of 2

Unit No. 1

Work Order 00-003219

Type Code Sym. Stamp NA

Authorization No. INA

Expiration Date NA

Code Case NA

Other Year ID Built

RC011-002 1970

Repaired, ASMERepaired,

Replaced, or Replacement

REPLACED N

7. Description of Work DISASSEMBLE AND INSPECT CLASS 1 REACTOR COOLANT SYSTEM 2" VALVE LD-3 AND REPLACE 8 STUDS

AND 8 NUTS.

8. Tests conducted Hydrostatic F]

Other F]Pneumatic n Nominal Operating Pressure E'

Pressure 2240 psi Test Temp. 551 deg. F

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

ASME Code

Stamped

Exempt El

REPLACED N

Page 64: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

NIS-2 (Back)

Sheet 2 of 2

Date: 12/3/2001

Name of Component: LD-3

Work Order Number: 00-003219

Certificate of Compliance

We Certify that the statements made in the report are correct and this REPLACED conforms to the rules of the

ASME Code Section Xl. Repair or Replacement

Type Code Symbol Stamp NA

Certificate of Authorization No. NA Expiration Date NA

Date 20 0=1

Owner or Owner's Designee, Title

Certificate of INSERVICE INSPECTION

I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors

and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT

have inspected the components described in the Owner's Report during the period ,1-5-O 0 to /-3-bZ, and state that

to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described

in this Owners Report in accordance with the requirements of the ASME Code, Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning

the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor

his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising

from or connected with this inspection.

Commissions NB7741, I, N, IS, A WIS 100024

4/setors Sign6(ure National Board, State, Province, and Endorsements

Date 1' 20 T,

Page 65: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section XI

1. Owner Wisconsin Public Service Corooration

700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001

2. Plant Kewaunee Nuclear Power Plant

N490 HWY 42 Kewaunee, WI 54216-9511

3. Work Performed By Nuclear Management Company, LLC

700 First Street, Hudson, Wisconsin 54016

4. Identification of System 05A Class 2 FEEDWATER

5. (a) Applicable Construction Code NA

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989

6. Identification of Components Repaired or Replaced and Replacement Components

Name of

Component

SG-AH-1

Name of

Manufacturer

MCDOWELL WELLMAN

Manufacturer Serial No.

25.12620.004-1

National

Board No.

NA

Other

ID

1S-0066

Date 12/3/2001

Sheet 1 of 2

Unit No. 1

Work Order 00-004319

Type Code Sym. Stamp NA

Authorization No. NA

Expiration Date NA

Code Case NA

Year Built

1971

Repaired, Replaced, or Replacement

REPLACEMENT

7. Description of Work REBUILD 900 KIP HYDRAULIC SNUBBER ON CLASS 2 MAIN STEAM AND STEAM DUMP SYSTEM STEAM GENEARTOR IA.

8. Tests conducted Hydrostatic

Other L]-l Pneumatic

Pressure

-1DNominal Operating Pressure

psi Test Temp.

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

ASME Code

Stamped

N

D: deg. F

Exempt FR

Page 66: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

NIS-2 (Back)

Sheet 2 of 2

Date: 12/3/2001

Name of Component: SG-AH-1

Work Order Number: 00-004319

Certificate of Compliance

We Certify that the statements made in the report are correct and this REPLACEMENT conforms to the rules of the

ASME Code Section XI. Repair or Replacement

Type Code Symbol Stamp NA

Certificate of Authorization No. NA Expiration Date NA

Signed & "9LAdJ ZM5dAA, &ti-L" ' Owner or Owner's Designee, Title

Date 20 0,;0

Certificate of INSERVICE INSPECTION

I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors

and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT

have inspected the components described in the Owner's Report during the period 745r-', to /--,/I-Z , and state that

to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described

in this Owners Report in accordance with the requirements of the ASME Code, Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning

the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor

his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising

from or connected with this inspection.

Commissions NB7741, 1, N, IS, A WIS 100024

Inspector's S~i ature National Board, State, Province, and Endorsements

Date 6A"• / 20 0,70

Page 67: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section Xl

1. Owner Wisconsin Public Service Corporation

700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001

2. Plant Kewaunee Nuclear Power Plant

N490 HWY 42 Kewaunee. WI 54216-9511

3. Work Performed By Nuclear Management Company, LLC

700 First Street, Hudson, Wisconsin 54016

4. Identification of System 05A Class 2 FEEDWATER

5. (a) Applicable Construction Code NA

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989

6. Identification of Components Repaired or Replaced and Replacement Components

Name of

Component

Name of Manufacturer

Manufacturer Serial No.

National Board No.

Other ID

Date 12/3/2001

Sheet 1 of 2

Unit No. 1

Work Order 00-004319

Type Code Sym. Stamp NA

Authorization No. NA

Expiration Date NA

Code Case NA

Year Built

Repaired, ASMERepaired,

Replaced, or Replacement

25.12620.004-7 NA 1S-0066 1971 REPLACEMENT N

7. Description of Work REBUILD 900 KIP HYDRAULIC SNUBBER ON CLASS 2 MAIN STEAM AND STEAM DUMP SYSTEM STEAM

GENERATOR lB.

8. Tests conducted Hydrostatic El

Other r--

Pneumatic

Pressure

El Nominal Operating Pressure

psi Test Temp.

-- Exempt 17

deg. F

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

SG-AH-2 MCDOWELL WELLMAN

ASME Code

Stamped

REPLACEMENT N

Page 68: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

NIS-2 (Back)

Sheet 2 of 2

Date: 12/3/2001

Name of Component: SG-AH-2

Work Order Number: 00-004319

Certificate of Compliance

We Certify that the statements made in the report are correct and this REPLACEMENT conforms to the rules of the

ASME Code Section XI. Repair or Replacement

Type Code Symbol Stamp NA

Certificate of Authorization No. NA Expiration Date NA

Signed , ewr-m- -, "* LO1 f, Date ,20 0

Owner or Owner's Designee, Title

Certificate of INSERVICE INSPECTION

I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors

and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT

have inspected the components described in the Owner's Report during the period 17-2- -0O to /- J/o-02, and state that

to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described

in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning

the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor

his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising

from or connected with this inspection.

Commissions NB7741, 1, N, IS, A WIS 100024

Unspector's Siglature National Board, State, Province, and Endorsements

Date .20 '

Page 69: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section Xl

1. Owner Wisconsin Public Service Corporation

700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001

2. Plant Kewaunee Nuclear Power Plant

N490 HWY 42 Kewaunee, WI 54216-9511

3. Work Performed By Nuclear Management Company, LLC

700 First Street. Hudson, Wisconsin 54016

4. Identification of System 35 Class 2 CHEMICAL AND VOLUME CONTROL

5. (a) Applicable Construction Code NA

(b) Applicable Edition of Section X1 Utilized for Repairs or Replacements 1989

6. Identification of Components Repaired or Replaced and Replacement Components

Name of

Manufacturer

AJAX IRON WORKS

Manufacturer Serial No.

6576

National

Board No.

NA

Other ID

00076

Date 2/26/2001

Sheet 1 of 2

Unit No. 1

Work Order 01-001998

Type Code Sym. Stamp NA

Authorization No. NA

Expiration Date NA

Code Case NA

Year Built

1967

Repaired, Replaced, or Replacement

REPAIRED

7. Description of Work REPAIR CLASS 2 CHEMICAL AND VOLUME CONTROL SYSTEM CHARGING PUMP 1B SUCTION VALVE.

8. Tests conducted Hydrostatic

Other DE- Pneumatic 1 Nominal Operating Pressure El

Pressure 26 psi Test Temp. 115 deg. F

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

Name of

Component

APCH-11B

ASME Code

Stamped

N

Exempt 1:]

Page 70: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

NIS-2 (Back)

Sheet 2 of 2

Date: 2/26/2001

Name of Component: APCH-1 B

Work Order Number: 01-001998

Certificate of Compliance

We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the

ASME Code Section XI. Repair or Replacement

Type Code Symbol Stamp NA

Certificate of Authorization No. NA Expiration Date NA

Signed k &*SaNdUft4U Date 200 ;6

Owner or Owner's Designee, Title

Certificate of INSERVICE INSPECTION

I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors

and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT

have inspected the components described in the Owner's Report during the period 1-7-r-00 to 1-3/1-2 , and state that

to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described

in this Owners Report in accordance with the requirements of the ASME Code, Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning

the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor

his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising

from or connected with this inspection.

Commissions NB7741, I, N, IS, A WIS 100024

Inspector's Si ature National Board, State, Province, and Endorsements

Date a20 0 ;t-

Page 71: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section XI

1. Owner Wisconsin Public Service Corporation

700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001

2. Plant Kewaunee Nuclear Power Plant

N490 HWY 42 Kewaunee. WI 54216-9511

3. Work Performed By Nuclear Management Company, LLC

700 First Street, Hudson, Wisconsin 54016

4. Identification of System 36 Class 1 REACTOR COOLANT

5. (a) Applicable Construction Code B31.1-1967

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989

6. Identification of Components Repaired or Replaced and Replacement Components

Name of

Manufacturer

PCIENERGY SERVICES

Manufacturer Serial No.

110/1M

National

Board No.

NA

Other

ID

NA

Date 12/3/2001

Sheet 1 of 2

Unit No. 1

Work Order 01-002115

Type Code Sym. Stamp NA

Authorization No. NA

Expiration Date NA

Code Case N-416-2

Year Built

2001

Repaired, Replaced, or Replacement

REPLACED

7. Description of Work REPLACED WELD FOR CLASS 1 REACTOR COOLANT SYSTEM STEAM GENERATOR 1A NOZZLE TO SAFE END WELD

8. Tests conducted Hydrostatic

Other r-

Pneumatic r-

Pressure 2240 psi

Nominal Operating Pressure r7

Test Temp. 551 deg. F

Applicable Manufacturer's Data Reports to be Attached

Name of

Component

RC-W76DM

ASME Code

Stamped

N

Exempt 11

9. Remarks UTILIZATION OF ASME BOILER AND PRESSURE VESSEL CODE SECTION XI: CODE CASE N-416-2 PER NRC APPROVAL OF RELIEF REQUEST RR-G-4.

Page 72: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

NIS-2 (Back)

Sheet 2 of 2

Date: * 12/3/2001

Name of Component: RC-W76DM

Work Order Number: 01-002115

Certificate of Compliance

We Certify that the statements made in the report are correct and this REPLACED conforms to the rules of the

ASME Code Section XI. Repair or Replacement

Type Code Symbol Stamp NA

Certificate of Authorization No. NA Expiration Date NA

Signed ; % &4,0~ 7eýP 04& -0M-

Owner or Owner's Designee, Title

Date 20 0

Certificate of INSERVICE INSPECTION

1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors

and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT

have inspected the components described in the Owner's Report during the period *1,2f-l to /- 3/1#2.., and state that

to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described

in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning

the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor

his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising

from or connected with this inspection.

4 lns c7 &Commissions NB7741, I, N, IS, A WIS 100024

Inspector's Si National Board, State, Province, and Endorsements

Date f I ,20 0 Z

Page 73: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section Xl

1. Owner Wisconsin Public Service Corporation

700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001

2. Plant Kewaunee Nuclear Power Plant

N490 HWY 42 Kewaunee. WI 54216-9511

3. Work Performed By Nuclear Management Company, LLC

700 First Street, Hudson, Wisconsin 54016

4. Identification of System 36 Class 1 REACTOR COOLANT

5. (a) Applicable Construction Code B31.1-1967

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989

6. Identification of Components Repaired or Replaced and Replacement Components

Name of

Manufacturer

PCI ENERGY SERVICES

Manufacturer Serial No.

NA

National Board No.

NA

Other ID

NA

Date 12/3/2001

Sheet 1 of 2

Unit No. 1

Work Order 01-002115

Type Code Sym. Stamp NA

Authorization No. NA

Expiration Date NA

Code Case N-416-2

Year Built

2001

Repaired, Replaced, or Replacement

REPLACED

7. Description of Work REPLACED WELD FOR CLASS 1 REACTOR COOLANT SYSTEM STEAM GENERATOR 1A NOZZLE TO SAFE END.

8. Tests conductedHydrostatic El Other D

Pneumatic Nominal Operating Pressure

Pressure 2240 psi Test Temp. 551 deg. F

Applicable Manufacturer's Data Reports to be Attached

Name of

Component

RC-W77DM

ASME Code

Stamped

N

Exempt 1

9. Remarks UTILIZATION OF ASME BOILER AND PRESSURE VESSEL CODE SECTION XI: CODE CASE N-416-2 PER NRC APPROVAL OF RELIEF REQUEST RR-G-2.

Page 74: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

NIS-2 (Back)

Sheet 2 of 2

Date: 12/3/2001

Name of Component: RC-W77DM

Work Order Number: 01-002115

Certificate of Compliance

We Certify that the statements made in the report are correct and this REPLACED conforms to the rules of the

ASME Code Section XI. Repair or Replacement

Type Code Symbol Stamp NA

Certificate of Authorization No. NA Expiration Date NA

Signed &14" Date 4 20 oA Owner or Owner's Designee, Title

Certificate of INSERVICE INSPECTION

I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors

and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT

have inspected the components described in the Owner's Report during the period 7-4U'-00 to /°.3 I'V2, and state that

to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described

in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning

the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor

his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising

from or connected with this inspection.

Commissions NB7741, I, N, IS, A WIS 100024

nspector's Sigrature National Board, State, Province, and Endorsements

Date .• • 20 "-0-

Page 75: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section Xl

1. Owner Wisconsin Public Service Corporation

700 North Adams P.O.Box 19001 Green Bay. WI 54307-9001

2. Plant Kewaunee Nuclear Power Plant

N490 HWY 42 Kewaunee. WI 54216-9511

3. Work Performed By Nuclear Management Company, LLC

700 First Street, Hudson. Wisconsin 54016

4. Identification of System 36 Class 1 REACTOR COOLANT

5. (a) Applicable Construction Code B31.1-1967

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989

6. Identification of Components Repaired or Replaced and Replacement Components

Name of

Component

RC-W78DM

Name of

Manufacturer

PCIENERGY SERVICES

Manufacturer Serial No.

110/2

National Board No.

NA

Other ID

NA

Date 12/3/2001

Sheet 1 of 2

Unit No. 1

Work Order 01-002115

Type Code Sym. Stamp NA

Authorization No. NA

Expiration Date NA

Code Case N-416-2

Year Built

2001

Repaired, ASM�Repaired,

Replaced, or Replacement

REPLACED N

7. Description of Work REPLACED WELD FOR CLASS 1 REACTOR COOLANT SYTEM STEAM GENERATOR 1B NOZZLE TO SAFE END

WELD.

8. Tests conducted Hydrostatic

Other D

Pneumatic F

Pressure 2240 psi

Nominal Operating Pressure L

Test Temp. 55_1 deg. F

9. Remarks UTILIZATION OF ASME BOILER AND PRESSURE VESSEL CODE SECTION XI: CODE CASE N-416-2 PER NRC APPROVAL

OF RELIEF REQUEST RR-G-4.

Applicable Manufacturer's Data Reports to be Attached

ASME Code Stamped

Exempt

REPLACED N

Page 76: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

NIS-2 (Back)

Sheet 2 of 2

Date:. 12/3/2001

Name of Component: RC-W78DM

Work Order Number: 01-002115

Certificate of Compliance

We Certify that the statements made in the report are correct and this REPLACED conforms to the rules of the

ASME Code Section XI. Repair or Replacement

Type Code Symbol Stamp NA

Certificate of Authorization No. NA Expiration Date NA

Signed , R lOr. Date ,n 4 20 0.

Owner or Owner's Designee, Title

Certificate of INSERVICE INSPECTION

I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors

and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT

have inspected the components described in the Owner's Report during the period __-_______ to /- 31-07-, and state that

to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described

in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning

the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor

his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising

from or connected with this inspection.

Commissions NB7741, 1, N, IS, A WIS 100024

Inspectors ,nature National Board, State, Province, and Endorsements

Date . / ,20 •''-

Page 77: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section XI

1. Owner Wisconsin Public Service Corporation

700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001

2. Plant Kewaunee Nuclear Power Plant

N490 HWY 42 Kewaunee, WI 54216-9511

3. Work Performed By Nuclear Manaqement Company, LLC

700 First Street, Hudson, Wisconsin 54016

4. Identification of System 36 Class 1 REACTOR COOLANT

5. (a) Applicable Construction Code B31.1-1967

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989

6. Identification of Components Repaired or Replaced and Replacement Components

Name of

Component

RC-W79DM

Name of Manufacturer

PCIENERGY SERVICES

Manufacturer Serial No.

110/1

National

Board No.

NA

Other ID

NA

Date 12/3/2001

Sheet 1 of 2

Unit No. 1

Work Order 01-002115

Type Code Sym. Stamp N.AA

Authorization No. NA

Expiration Date NA

Code Case N-416-2

Year Built

2001

Repaired, Replaced, or Replacement

REPLACED

7. Description of Work REPLACED WELD FOR CLASS 1 REACTOR COOLANT SYSTEM STEAM GENERATOR 1B NOZZLE TO SAFE END.

8. Tests conducted Hydrostatic

Other D

rF Pneumatic F Nominal Operating Pressure E

Pressure 2240 psi Test Temp. 551 deg. F

Exempt 1

9. Remarks UTILIZATION OF ASME BOILER AND PRESSURE VESSEL CODE SECTION XI: CODE CASE N-416-2 PER NRC APPROVAL OF RELIEF REQUEST RR-G-4.

Applicable Manufacturer's Data Reports to be Attached

ASME Code

Stamped

N

Page 78: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

NIS-2 (Back)

Sheet 2 of 2

Date:. 12/3/2001

Name of Component: RC-W79DM

Work Order Number: 01-002115

Certificate of Compliance

We Certify that the statements made in the report are correct and this REPLACED conforms to the rules of the

ASME Code Section XI. Repair or Replacement

Type Code Symbol Stamp NA

Certificate of Authorization No. NA Expiration Date NA

Signed && I1IWA W &OnL~n dUM" Date 20 01

Owner or Owner's Designee, Title

Certificate of INSERVICE INSPECTION

I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors

and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT

have inspected the components described in the Owner's Report during the period 72 to ,/-3/-, and state that

to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described

in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning

the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor

his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising

from or connected with this inspection.

Commissions NB7741, 1, N, IS, A WIS 100024

rInspector's Si ature National Board, State, Province, and Endorsements

Date ." • 20 D ,

Page 79: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section XI

1. Owner Wisconsin Public Service Corporation

700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001

2. Plant Kewaunee Nuclear Power Plant

N490 HWY 42 Kewaunee, WI 54216-9511

3. Work Performed By Nuclear Management Company, LLC

700 First Street, Hudson, Wisconsin 54016

4. Identification of System 34 Class 2 RESIDUAL HEAT REMOVAL

5. (a) Applicable Construction Code SECTION III CLASS 2

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989

6. Identification of Components Repaired or Replaced and Replacement Components

Date 12/11/2001

Sheet 1 of 2

Unit No. 1

Work Order 01-003411

Type Code Sym. Stamp NA

Authorization No. NA

Expiration Date NA

Code Case NA

Repaired, ASME

Name of Name of Manufacturer National Other Year Replaced, or Code

Component Manufacturer Serial No. Board No. ID Built Replacement Stamped

RHR-33-1 CROSBY VALVE AND GAGE N62651-00-0001 NA ACl 15-001 1978 REPAIRED N

COMPANY

7. Description of Work REMOVE FOR TESTING CLASS 2 RESIDUAL HEAT REMOVAL SYSTEM 4" VALVE RHR-33-1.

8. Tests conducted Hydrostatic

Other F

EI Pneumatic 1"1 Nominal Operating Pressure El

Pressure 150 psi Test Temp. 60 deg. F

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

Exempt 1

Page 80: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

NIS-2 (Back)

Sheet 2 of 2

Date: 12/1/2001

Name of Component: RHR-33-1

Work Order Number: 01-003411

Certificate of Compliance

We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the

ASME Code Section XI. Repair or Replacement

Type Code Symbol Stamp NA

Certificate of Authorization No. NA Expiration Date NA

Signed &V4ii CA194 Date 1-1 -20 Q Owner or Owner's Designee, Title

Certificate of INSERVICE INSPECTION

I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors

and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT

have inspected the components described in the Owner's Report during the period 97I,.-v, to /-3/- 0 Z., and state that

to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described

in this Owners Report in accordance with the requirements of the ASME Code, Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning

the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor

his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising

from or connected with this inspection.

24 ,Commissions NB7741, 1, N, IS, A WIS 100024

lnspector'sSiaature National Board, State, Province, and Endorsements

Date ,C / 20 0

Page 81: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section X1

1. Owner Wisconsin Public Service Corporation

700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001

2. Plant Kewaunee Nuclear Power Plant

N490 HWY 42 Kewaunee, WI 54216-9511

3. Work Performed By Nuclear Management Company, LLC

700 First Street, Hudson, Wisconsin 54016

4. Identification of System 34 Class 2 RESIDUAL HEAT REMOVAL

5. (a) Applicable Construction Code B31.1-1967

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989

6. Identification of Components Repaired or Replaced and Replacement Components

Name of

Manufacturer

CROSBY ASHTON GAGE COMPANY

Manufacturer Serial No.

NF

National

Board No.

NA

Date 12/1/2001

Sheet 1 of 2

Unit No. 1

Work Order 01-003412

Type Code Sym. Stamp N..A

Authorization No. NA

Expiration Date NA

Code Case NA

Other Year

ID Built

AC107-001 1971

Repaired,

Replaced, or Replacement

REPAIRED

7. Description of Work REMOVE FOR TESTING CLASS 2 RESIDUAL HEAT REMOVAL SYSTEM 2" VALVE RHR-33.

8. Tests conducted Hydrostatic []

Other n

Pneumatic Nominal Operating Pressure

Pressure 150 psi Test Temp. 60 deg. F

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

Name of

Component

RHR-33

ASME Code

Stamped

N

Exempt 1

Page 82: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

NIS-2 (Back)

Sheet 2 of 2

Date:. 12/1/2001

Name of Component: RHR-33

Work Order Number: 01-003412

Certificate of Compliance

We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the

ASME Code Section XI. Repair or Replacement

Type Code Symbol Stamp NA

Certificate of Authorization No. NA Expiration Date NA

Signed . If-.A 4eI4A., L Date .q 1 ,20 O.1

Owner or Owner's Designee, Title

Certificate of INSERVICE INSPECTION

I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors

and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT

have inspected the components described in the Owner's Report during the period ?7-2,r-a to/- 3/-# 2- , and state that

to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described

in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning

the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor

his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising

from or connected with this inspection.

SCommissions NB7741, , N, IS, A WIS 100024

Inspector's Sigjture National Board, State, Province, and Endorsements

Date ,20 9'9;-

Page 83: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section Xl

1. Owner Wisconsin Public Service Corporation

700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001

2. Plant Kewaunee Nuclear Power Plant

N490 HWY 42 Kewaunee, WI 54216-9511

3. Work Performed By Nuclear Management Company, LLC

700 First Street. Hudson, Wisconsin 54016

4. Identification of System 23 Class 2 CONTAINMENT SPRAY

5. (a) Applicable Construction Code B16.5-1967

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989

6. Identification of Components Repaired or Replaced and Replacement Components

Name of

Manufacturer

WILLIAM POWELL CO.

Manufacturer Serial No.

NF

National Board No.

NA

Date 11/26/2001

Sheet 1 of 2

Unit No. 1

Work Order 01-004985

Type Code Sym. Stamp NA

Authorization No. NA

Expiration Date NA

Code Case NA

Other Year ID Built

ICS022-001 1968

Repaired, ASMERepaired,

Replaced, or Replacement

REPAIRED N

7. Description of Work OPEN FOR INSPECTION CLASS 2 CONTAINMENT SPRAY 2" VALVE Cl-1003.

8. Tests conducted Hydrostatic

Other F

Pneumatic F] Pressure 31 psi

Nominal Operating Pressure M

Test Temp. 69.6 deg. F

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

Name of

Component

Cl-1003

ASME Code

Stamped

Exempt 1

REPAIRED N

Page 84: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

NIS-2 (Back)

Sheet 2 of 2

Date: .11/26/2001

Name of Component: C1-1003

Work Order Number: 01-004985

Certificate of Compliance

We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the

ASME Code Section Xl. Repair or Replacement

Type Code Symbol Stamp NA

Certificate of Authorization No. NA Expiration Date NA

Signed . a e &.a 4..'2%, AoLv ,.lý c 4 Date 6uomi 20

Owner or Owner's Designee, Title

Certificate of INSERVICE INSPECTION

I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors

and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT

have inspected the components described in the Owner's Report during the period Y-Ar-a to -3d JJ-, and state that

to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described

in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning

the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor

his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising

from or connected with this inspection.

&ýý "= -1,.,.•Commissions NB7741, I, N, IS, A WIS 100024

Inspector's jgnature National Board, State, Province, and Endorsements

Date / ,20

Page 85: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section XI

1. Owner Wisconsin Public Service Corporation

700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001

2. Plant Kewaunee Nuclear Power Plant

N490 HWY 42 Kewaunee, WI 54216-9511

3. Work Performed By Nuclear Management Company, LLC

700 First Street, Hudson, Wisconsin 54016

4. Identification of System 33 Class 1 SAFETY INJECTION

5. (a) Applicable Construction Code B16.5-1967

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989

6. Identification of Components Repaired or Replaced and Replacement Components

Name of

Manufacturer

ANCHOR/DARLING ENTERPRISES

Manufacturer Serial No.

11542-13

National Board No.

NA

Other ID

SIl15-003

Date 12/3/2001

Sheet 1 of 2

Unit No. 1

Work Order 01-005010

Type Code Sym. Stamp NA

Authorization No. NA

Expiration Date NA

Code Case NA

Year Built

1970

Repaired, Replaced, or Replacement

REPAIRED

7. Description of Work OPEN FOR INSPECTION CLASS 1 SAFETY INJECTION SYSTEM 12" VALVE SI-21A.

8. Tests conducted Hydrostatic

Other F

Pneumatic

Pressure 2240 psi

Nominal Operating Pressure

Test Temp. 551 deg. F

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

Name of

Component

SI-21A

ASME Code

Stamped

N

Exempt 1--

Page 86: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

NIS-2 (Back)

Sheet 2 of 2

Date:. 12/3/2001

Name of Component: SI-21A

Work Order Number: 01-005010

Certificate of Compliance

We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the

ASME Code Section XI. Repair or Replacement

Type Code Symbol Stamp NA

Certificate of Authorization No. NA Expiration Date NA

Signed ,, 'e• . -L'-•4 0 ,X A Date 20 Q, 1

Owner or Owner's Designee, Title

Certificate of INSERVICE INSPECTION

I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors

and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT

have inspected the components described in the Owner's Report during the period 1 ,-Knev to -,,31/'2, and state that

to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described

in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning

the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor

his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising

from or connected with this inspection.

lnp ,Commissions NB7741, I, N, IS, A WIS 100024

Inspector'si ature National Board, State, Province, and Endorsements

Date -- :4 ,20 Z

Page 87: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section XI

1. Owner Wisconsin Public Service Corporation

700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001

2. Plant Kewaunee Nuclear Power Plant

N490 HWY 42 Kewaunee. WI 54216-9511

3. Work Performed By Nuclear Management Company, LLC

700 First Street, Hudson, Wisconsin 54016

4. Identification of System 33 Class 1 SAFETY INJECTION

5. (a) Applicable Construction Code B16.5-1967

(b) Applicable Edition of Section X1 Utilized for Repairs or Replacements 1989

6. Identification of Components Repaired or Replaced and Replacement Components

Name of Manufacturer

Manufacturer Serial No.

ANCHOR/DARLING VALVE NF COMPANY

National Board No.

NA

Other

ID

S1115-004

Date 12/3/2001

Sheet 1 of 2

Unit No. 1

Work Order 01-005011

Type Code Sym. Stamp NA

Authorization No. NA

Expiration Date NA

Code Case NA

Year Built

1970

Repaired, Replaced, or Replacement

REPAIRED

7. Description of Work OPEN FOR INSPECTION CLASS 1 SAFETY INJECTION SYSTEM 12" VALVE SI-21B.

8. Tests conducted Hydrostatic

Other DlF Pneumatic r-1 Nominal Operating Pressure El

Pressure 2240 psi Test Temp. a55 deg. F

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

Name of

Component

SI-21 B

ASME Code

Stamped

N

Exempt 1]

Page 88: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

NIS-2 (Back)

Sheet 2 of 2

Date: 12/3/2001

Name of Component: SI-21B

Work Order Number: 01-005011

Date / 20

Certificate of Compliance

We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the

ASME Code Section XI. Repair or Replacement

Type Code Symbol Stamp NA

Certificate of Authorization No. NA Expiration Date NA

Signed I4.•, Date. ,4gADt 20 OZ Owner or Owner's Designee, Title

Certificate of INSERVICE INSPECTION

I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors

and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT

have inspected the components described in the Owner's Report during the period __-2___O' to 14/4O2-, and state that

to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described

in this Owners Report in accordance with the requirements of the ASME Code, Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning

the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor

his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising

from or connected with this inspection.

ý_ -Commissions NB7741, 1, N, IS, A WIS 100024

National Board, State, Province, and Endorsements_.Inspector's Signature

Page 89: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section XI

1. Owner Wisconsin Public Service Corporation

700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001

2. Plant Kewaunee Nuclear Power Plant

N490 HWY 42 Kewaunee, WI 54216-9511

3. Work Performed By Nuclear Management Company, LLC

700 First Street, Hudson, Wisconsin 54016

4. Identification of System 33 Class 1 SAFETY INJECTION

5. (a) Applicable Construction Code B16.5-1967

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989

6. Identification of Components Repaired or Replaced and Replacement Components

Name of

Manufacturer

ANCHOR/DARLING ENTERPRISES

Manufacturer Serial No.

NF

National Board No.

NA

Other ID

S1115-001

Date 11/26/2001

Sheet 1 of 2

Unit No. 1

Work Order 01-005012

Type Code Sym. Stamp N._A

Authorization No. NA

Expiration Date NA

Code Case NA

Year Built

1970

Repaired, Replaced, or

Replacement

REPAIRED

7. Description of Work OPEN FOR INSPECTION CLASS 1 SAFETY INJECTION SYSTEM 12" VALVE SI-22A.

8. Tests conducted Hydrostatic

Other F

Pneumatic F

Pressure 750 psi

Nominal Operating Pressure =.

Test Temp. 63 deg. F

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

Name of

Component

SI-22A

ASME Code

Stamped

N

Exempt 1"-

Page 90: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

NIS-2 (Back)

Sheet 2 of 2

Date: .11/26/2001

Name of Component: SI-22A

Work Order Number: 01-005012

Certificate of Compliance

We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the

ASME Code Section XI. Repair or Replacement

Type Code Symbol Stamp NA

Certificate of Authorization No. NA Expiration Date NA

Signed LJ6 •0 •..IW .A fPA"?1 l'1, Date 20 0-1

Owner or Owner's Designee, Title

Certificate of INSERVICE INSPECTION

I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors

and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT

have inspected the components described in the Owner's Report during the pedod _'__"__ to /-3/"6-a, and state that

to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described

in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning

the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor

his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising

from or connected with this inspection.

SCommissions NB7741, I, N, IS, A WIS 100024

Inspector's nature National Board, State, Province, and Endorsements

Date 2 ,20 9

Page 91: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions for the ASME Code Section XI

1. Owner: Wisconsin Public Service Corporation 700 North Adams P.O. Box 19001 Green Bay, WI 54307-9001

2. Plant: Kewaunee Nuclear Power Plant N490 HWY 42 Kewaunee WI 54216-9511

Date: 12/12/01

Sheet: 1 of 3

Unit: No.1

Work Order#: SEE BELOW

WORK ORDER WP&IR DESCRIPTION 01-007152 M-FCU-385 REMOVE AND RECONNECT SW

PIPING TO CFCU'S

Work Performed by: Bechtel Construction

Identification of System: 02 Class: 3 Name: SERVICE WATER

(a) Applicable Construction Code: USAS B31.1, 1967 Ed. , No Add. C

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements: 1989, No Add. C

Identification of Components Repaired or Replaced and Replacement Components:

ode Case: N/A

ode Case: N/A

Name of Name of Manufacturer National Other Year Repaired, ASME Component Manufacturer Serial No. Board Identification Built Replaced, Code

No. or Stamped Replacement Yes/No

See continuation sheet, page 3

7. Description of Work: REMOVE AND REINSTALL SERVICE WATER SYSTEM CONTAINMENT COOLING

CONTAINMENT FAN COIL UNITS C AND D AND ASSOCIATED SERVICE WATER LINES

8. Tests Conducted: Hydrostatic E] Pneumatic [j Nominal Operating Pressure Z Exempt E]

Other: El Pressure: 92 psi Test Temp: 44.2 0 F

Page 1 of`3

3.

4.

5.

6.

Page 92: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

Date: 12/12/01

Name of Component: SERVICE WATER

Work Order Number: 01-007152

CERTIFICATE OF INSERVICE INSPECTION

I, the undersigned, holding a valid commission issued by the National Board of Boiler Pressure Vessel Inspectors

and the State or Providence of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of

Hartford, CT have inspected the components described in this Owner's Report during the period 0 -Uf

to I , and state that to the best of my knowledge and belief, the Owner has performed

examinations and taken corrective measures described in this Owner's Report in accordance with the

requirements of the ASME Code, Section XI

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or

implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore,

neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or

of loss of any kind arising from or connected with this inspection.

(Robert T. Ward)_ _ _ _ Commissions ' I(•A4 '

Inspector's Signature National Board, State, Province, and Endorsements

Date: /a-/•- 2001

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS

Page 2 of 3

CERTIFICATE OF COMPLIANCE

We certify that the statements made in the report are correct and this repair and replacement conforms to the rules of the ASME Code, Section XI repair or replacement.

Type Code Symbol Stamp

Certificate of Authorization No. N/A Expiration Date N/A

Signed: Date/--Date Owner or Owner's Designee, Title

N/A

Page 93: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

Continuation Sheet

Name of Component SERVICE WATER

Work Order Number: 01-007152

Name of Name of Manufacturer National Other Year Repaired ASME Component Manufacturer Serial No. Board Identification: Built Replaced Code

No. Or Stamped Replacement Yes/No

CFCU C INLET N/A N/A N/A N/A N/A REPAIRED NO PIPING CFCU C OUTLET N/A N/A N/A N/A N/A REPAIRED NO PIPING CFCU D INLET N/A N/A N/A N/A N/A REPAIRED NO PIPING CFCU D OUTLET N/A N/A N/A N/A N/A REPAIRED NO PIPING 5/8" BOLTS MACKSON N/A N/A HT USY87951 N/A REPLACEMENT NO

5/8" NUT MACKSON N/A N/A HT 7307732 N/A REPLACEMENT NO

5/8" STUD MACKSON N/A N/A HT M60635 N/A REPLACEMENT NO

t t -t 1 1

t �- I I t

I* ± I I

f + I 1

+ I I 1-

Page 3 of 3

Page 94: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions for the ASME Code Section XI

1. Owner: Wisconsin Public Service Corporation 700 North Adams P.O. Box 19001 Green Bay, WI 54307-9001

2. Plant: Kewaunee Nuclear Power PlantN490 HWY 42 Kt.w•Ni•e WI 54216-9511

Date: 12/12/01

Sheet: 1 of 5

Unit : No.1

Work Order#: SEE BELOW

WORK ORDER WP&IR DESCRIPTION 01-008137 M-ULR-311 Remove & Modify Upper

Lateral

Work Performed by: Bechtel Construction

Identification of System: 05A Class: 2 Name: "A" Upper Lateral inclu'

Snubber

(a) Applicable Construction Code: USAS B31.1, 1967 Ed. , No Add.

(b) Applicable Edition of Section Xl Utilized for Repairs or Replacements: 1989, No Add.

Identification of Components Repaired or Replaced and Replacement Components:

ding Spring Cans &

Code Case: N/A

Code Case: N/A

Name of Name of Manufacturer National Other Year Repaired, ASME

Component Manufacturer Serial No. Board Identification Built Replaced, Code

No. or Stamped Replacement Yes/No

See continuation sheet, page 3

8. Description of Work: Repaired Upper Lateral Restraint and replacement of bolting and shims for upper lateral

9. Tests Conducted: Hydrostatic [] Pneumatic [] Nominal Operating Pressure F1 Exempt 0

Other: r] Pressure: psi Test Temp -F

Page 1 of 5

3.

4.

5.

6.

7.

Page 95: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

Date: 12/12/01

Name of Component: UPPER LATERAL RESTRAINT SYSTEM.

Work Order Number: 01-008137

CERTIFICATE OF COMPLIANCE

We certify that the statements made in the report are correct and this repair and replacement conforms to the rules of the ASME Code, Section XI repair or replacement.

Type Code Symbol Stamp N/A

Certificate of Authorization No. N/A Expiration Date N/A

Signed: Yi, c -,:4-.e ,Sv,- Date -! Owner or Owner's Designee, Title

CERTIFICATE OF INSERVICE INSPECTION

I, the undersigned, holding a valid commission issued by the National Board of Boiler Pressure Vessel Inspectors

and the State or Providence of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of

Hartford, CT have inspected the components described in this Owner's Report during the period n9-/1?2•!

to [t- ,oci , and state that to the best of my knowledge and belief, the Owner has performed

examinations and taken corrective measures described in this Owner's Report in accordance with the

requirements of the ASME Code, Section XI

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or

implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore,

neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or

of loss of any kind arising from or connected with this inspection.

(Robert T. Ward) Commissions t,• a3 SS•"-i)A-; PYft •,'

lnspeot6Fýs Signature/ National Board, State, Province, and Endorsements

Date: r -/% 20 cý .

Page 2 of 5

Page 96: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS

Continuation Sheet

Name of Name of Manufacturer National Other Year Repaired ASME Component Manufacturer Serial No. Board Identification: Built Replaced Code

No. Or Stamped Replacement Yes/No

"A" Hydraulic McDowell 25.12620.004-1 N/A IS-0066 1971 Repaired No Snubber Wellman "A" Upper Lateral N/A N/A N/A N/A N/A Repaired No Ring Girder Splice Plate, Ring Colonial Ht. No. 412H07 N/A N/A 2001 Replacement No Girder, ASTM A588, Gr. A Splice Plate Bolt, Colonial HT No. 10187- N/A N/A 2001 Replacement No ASTM A540, RYE Gr.B23, Cl. 2 Splice Plate Heavy Colonial Ht. No. 8994464 N/A N/A 2001 Replacement No Hex. Nuts, A194, Trace Code SBG Gr. 2H Splice Plate Colonial Ht. No. Y85307 N/A N/A 2001 Replacement No Washers, F436 Trace Code SBH Splice Plate Heavy Colonial Ht. No. S42483 N/A N/A 2001 Replacement No Hex Nuts, A 194, Trace Code I UV Gr. 2H Bumper Plate, A588 Colonial Ht. No. BI S6214 N/A N/A 2001 Replacement No GR A Side Bumper Colonial Ht. No. l B518 N/A N/A 2001 Replacement No Bearing Plate, A588 3" Threaded Rod, Colonial Ht. No. 8991820 N/A N/A 2001 Replacement No A540 Gr. B23, Cl. 2 V" Hex. Nut, A563 Colonial Ht. No. 34467PJ N/A N/A 2001 Replacement No Washer, F436 Colonial Ht. No. 107494 N/A N/A 2001 Replacement No Side Bumper Shim, Colonial Ht. No. EIF023- N/A N/A 2001 Replacement No A36 A12 Side Bumper Shim, Colonial Ht. No. E1GI 19- N/A N/A 2001 Replacement No A36 A16 Side Bumper Shim, Colonial Ht. No. EIG 119- N/A N/A 2001 Replacement No A36 A16 Side Bumper Shim, Colonial Ht. No. B1F669- N/A N/A 2001 Replacement No A36 C16 Side Bumper Shim, Colonial Ht. No. T2866 N/A N/A 2001 Replacement No A36 Side Bumper Shim, Colonial Ht. No. A1C202- N/A N/A 2001 Replacement No A36 B20 Side Bumper Shim, Colonial Ht. No. A1D370- N/A N/A 2001 Replacement No A36 B32 Side Bumper Shim, Colonial Ht. No. B1E825- N/A N/A 2001 Replacement No A36 B16

Side Bumper Shim, Colonial Ht. No. B11F555- N/A N/A 2001 Replacement No A36 C23 Side Bumper Shim, Colonial Ht. No. 64595 N/A N/A 2001 Replacement No A109 CI010 Side Bumper Shim, Colonial Ht. No. Y07405 N/A N/A 2001 Replacement No A109 CI010 Side Bumper Shim, Colonial Ht. No. 65747 N/A N/A 2001 Replacement No A109 CI010 Side Bumper Shim, Colonial Ht. No. M06708 N/A N/A 2001 Replacement No A109 CI010 Upper Lateral Ring Colonial Ht. No. N/A N/A 2001 Replacement No Plate, A36 A1T128'3 3/8" Threaded Rod, Colonial Ht. No. 813953 N/A N/A 2001 Replacement No A307, Gr. A

Page 3 of 5

Page 97: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS

Continuation Sheet

Name of Name of Manufacturer National Other Year Repaired ASME Component Manufacturer Serial No. Board Identification: Built Replaced Code

No. Or Stamped Replacement Yes/No

Heavy Hex Nuts, Colonial Ht. No. A61415 N/A N/A 2001 Replacement No A563, Gr. A Std. Washer, F436, Colonial Ht. No. B16294 N/A N/A 2001 Replacement No Type 1 Upper Lateral Ring Colonial Ht. No. A1U1599 N/A N/A 2001 Replacement No Plate Shim, A36 Upper Lateral Ring Colonial Ht. No. BIP5527 N/A N/A 2001 Replacement No Plate Shim, A36 Upper Lateral Ring Colonial Ht. No AOR0914 N/A N/A 2001 Replacement No Plate Shim, A36 Upper Lateral Ring Colonial Ht. No 7467439 N/A N/A 2001 Replacement No Plate Shim, A36 Upper Lateral Ring Colonial Ht. No 1A353 N/A N/A 2001 Replacement No Plate Shim, A36 3/8" Hex Hd. Bolt, Colonial Ht. No. 8878678 N/A N/A 2001 Replacement No A307-97 3/8" Std. Washer, Colonial Ht. No. B 16294 N/A N/A 2001 Replacement No F436 Type I Ring Girder Shim, Colonial Ht. No. 1E479 N/A N/A 2001 Replacement No A36 Ring Girder Shim, Colonial Ht. No. 1E744-A N/A N/A 2001 Replacement No A36 Ring Girder Shim, Colonial Ht. No. 2A6386- N/A N/A 2001 Replacement No A36 C Ring Girder Shim, Colonial Ht. No. 2A6593- N/A N/A 2001 Replacement No A36 C

Ring Girder Shim, Colonial Ht. No. 4151614 N/A N/A 2001 Replacement No A109-CR1010 Ring Girder Shim, Colonial Ht. No. A86743 N/A N/A 2001 Replacement No A109-CRIOIO Ring Girder Shim, Colonial Ht. No. 4151614 N/A N/A 2001 Replacement No A109-CRIOIO Ring Girder Shim, Colonial Ht. No. R4747 N/A N/A 2001 Replacement No A36 Flat Bar Backing KNPP JB8913 N/A QADC 0 1-349 2001 Replacement No Strip, A36 Ring Girder Shim, Colonial Ht. No. 4125164 N/A N/A 2001 Replacement No A109-CRIOO1 Back Bumper Colonial MRR-01030 N/A N/A 2001 Replacement No Bearing Plate and Pipes ¾" Threaded Rod, Colonial Ht. No. 8991820 N/A N/A 2001 Replacement No A540 Gr B23, C12 ¾/4" Nut, A563 Colonial 31167PJ N/A N/A 2001 Replacement No

3/4" Washer, F436 Colonial 107494 N/A N/A 2001 Replacement No

Back Bumper Shim, Colonial E1F023-A12 N/A N/A 2001 Replacement No A36 Back Bumper Shim, Colonial EIGI 19-A16 N/A N/A 2001 Replacement No A36 Back Bumper Shim, Colonial B1F669-C16 N/A N/A 2001 Replacement No A36 Back Bumper Shim, Colonial T2866 N/A N/A 2001 Replacement No A36 I

Page 4 of 5

Page 98: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS

Continuation Sheet

Name of Name of Manufacturer National Other Year Repaired ASME Component Manufacturer Serial No. Board Identification: Built Replaced Code

No. Or Stamped Replacement Yes/No

Back Bumper Shim, Colonial A1C202-B20 N/A N/A 2001 Replacement No A36 Back Bumper Shim, Colonial A 1D370-B23 N/A N/A 2001 Replacement No A36 Back Bumper Shim, Colonial B1E825-B16 N/A N/A 2001 Replacement No A36 Back Bumper Shim, Colonial B1F555-C23 N/A N/A 2001 Replacement No A36 Back Bumper Shim, Colonial 64595 N/A N/A 2001 Replacement No A36 Back Bumper Shim, Colonial Y07405 N/A N/A 2001 Replacement No A36 Back Bumper Shim, Colonial 65747 N/A N/A 2001 Replacement No A36 Ring Girder Shim, Colonial Ht. No. 2A6386- N/A N/A 2001 Replacement No A36 E Ring Girder Shim, Colonial Ht. No. 2A6593- N/A N/A 2001 Replacement No A36 E Snubber Bracket Colonial Ht No C0453 N/A N/A 2001 Replacement No Shim

Page 5 of 5

Page 99: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions for the ASME Code Section XI

1. Owner: Wisconsin Public Service Corporation700 North Adams P.O. Box 19001 Green Bay, WI 54307-9001

Date: 12/12/01

Sheet: 1 of 2

2. Plant: Kewaunee Nuclear Power PlantN490 HWY 42 K4.waiine. Wl 54216-9511I

Unit: No. 1

Work Order#: SEE BELOW

WORK ORDER WP&IR DESCRIPTION 01-013145 M-SGA-362 REMOVE SHIPPING COVER 01-013376 M-SDS-322 SEVER STEAM DOME 01-008136 M-SDA-370 REFURBISH STEAM DOME 01-013376 M-SDA-372 RE-INSTALL STEAM DOME

3.

4.

5.

6.

Work Performed by: Bechtel Construction

Identification of System: 05/06 Class: 2 Name: "A" Steam Generator Secondary Side

(a) Applicable Construction Code: USAS B31.1, 1967 Ed. , No Add. Code Case:

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements: 1989, No Add. Code Case:

Identification of Components Repaired or Replaced and Replacement Components:

N/A

N-416-2

Name of Name of Manufacturer National Other Year Repaired, ASME

Component Manufacturer Serial No. Board Identification Built Replaced, Code No. or Stamped

Replacement Yes/No

Steam Dome Westinghouse 1141 68-28 N/A 1970 Repaired Yes

Replacement SG Ansaldo 202 151 N/A 2000 Replacement Yes Lower assembly Feedwater Nozzle PCI FW # 1 N/A MRR-01019 2001 Replacement No

Adaptor Main Steam Flow Ansaldo N/A N/A QADC-01-041 2000 Replacement No

Limiter

_________________ I _______________ ______________ _________ '. ________________ ..- _____ -

7. Description of Work: Prep New lower assembly for Steam Dome installation, Remove Steam Dome from

the Old Lower Assembly, Refurbish the Feedwater Nozzle, Install the Main Steam Flow Limiter, Install the

Steam Dome on the New Lower Assembly

8. Tests Conducted: Hydrostatic El Pneumatic El Nominal Operating Pressure *

Other: E] Pressure: 1040 psi Test Temp: 549.35°F

* NOTE: The Secondary Side Hydrotest was conducted at NOP per Code Case N-416- 2

Exempt E]

Page 1 of2

Kewaunee WI 54216-9511

Page 100: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

Date: 12/12/01

Name of Component: SG # A

Work Order Number: 01-013145, 01-008136, 01-013376.

CERTIFICATE OF COMPLIANCE

We certify that the statements made in the report are correct and this repair and replacement conforms to the rules of the ASME Code, Section XI repair or replacement.

Type Code Symbol Stamp N/A

Certificate of Authorization No. N/A

Signed: -- ' 1(uf% /

Expiration Date N/A

Date (.

uwner or uwner s uesigjnee, I We

CERTIFICATE OF INSERVICE INSPECTION

I, the undersigned, holding a valid commission issued by the National Board of Boiler Pressure Vessel Inspectors

and the State or Providence of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of

Hartford, CT have inspected the components described in this Owner's Report during the periodn'-/7Z-

to I- t'p , and state that to the best of my knowledge and belief, the Owner has performed

examinations and taken corrective measures described in this Owner's Report in accordance with the

requirements of the ASME Code, Section XI

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or

implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore,

neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or

of loss of any kind arising from or connected with this inspection.

(Robert T. Ward) Commissions f t n ý • </ 'I I/a.(

Inspector s Signature/ National Board, State, Province, and Endorsements

Date: 200\

Page 2 of 2

Page 101: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions for the ASME Code Section XI

1. Owner: Wisconsin Public Service Corporation 700 North Adams P.O. Box 19001 Green Bay, WI 54307-9001

2. Plant: Kewaunee Nuclear Power PlantN490 HWY 42 Kp~w•inp.• WI 54216-9511I

Date: 12/12/01

Sheet: 1 of 4

Unit: No.1

Work Order# : SEE BELOW

WORK ORDER WP&IR DESCRIPTION 01-013376 M-LLR-314 Replace Upper Col.

Adapters and Reshim Lower Lateral Restraint

3.

4.

5.

6.

Work Performed by: Bechtel Construction

Identification of System: 36 Class: 1 Name: "B" Col. Adapter Plates and Lower Lateral Shims

(a) Applicable Construction Code: USAS B31.1, 1967 Ed., No Add. Code Case: N/A

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements: 1989, No Add. Code Case: N/A

Identification of Components Repaired or Replaced and Replacement Components:

Name of Name of Manufacturer National Other Year Repaired, ASME Component Manufacturer Serial No. Board Identification Built Replaced, Code

No. or Stamped Replacement Yes/No

See continuation sheet, page 3

7. Description of Work: Replaced steam generator support upper column adapters and removed and restored

lower lateral support bumper guides to the steam generator and shimmed the adjacent support bumper steel.

Exempt 0

Page 1 of 4

8. Tests Conducted: Hydrostatic E] Pneumatic E Nominal Operating Pressure El

Other: [] Pressure: psi Test Temp

Kewaunee WI 54216-9511

Page 102: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

Date: 12/12/01

Name of Component: "B" Upper Col. Adapter Plates and Reshim Lower Lateral Restraint.

Work Order Number: 01-013376

CERTIFICATE OF COMPLIANCE

We certify that the statements made in the report are correct and this repair and replacement conforms to the rules of the ASME Code, Section XI repair or replacement.

Type Code Symbol Stamp N/A

Certificate of Authorization No. N/A

Signed: KA%• , . -5,,Owner or Owner's Desianec

Expiration Date N/A

Dateý.2.//,Mw

CERTIFICATE OF INSERVICE INSPECTION

I, the undersigned, holding a valid commission issued by the National Board of Boiler Pressure Vessel Inspectors

and the State or Providence of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of

Hartford, CT have inspected the components described in this Owner's Report during the period 05 -,/ti1

to . - , and state that to the best of my knowledge and belief, the Owner has performed

examinations and taken corrective measures described in this Owner's Report in accordance with the

requirements of the ASME Code, Section XI

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or

implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore,

neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or

of loss of any kind arising from or connected with this inspection.

(Robert T. Ward)__ Commissions ^'-Z3 ii c c•V('i9V'

Inspector's Signature/ National Board, State, Province, and Endorsements

Date [1 1 2001

Page 2 of 4

•. I Itl•

Page 103: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS

Continuation Sheet

Name of Name of Manufacturer National Other Year Repaired ASME

Component Manufacturer Serial No. Board Identification: Built Replaced Code No. Or Stamped

Replacement Yes/No

Shims Colonial Ht. No. 4125164 N/A N/A 2001 Replacement No

Shims Colonial Ht. No. A86743 N/A N/A 2001 Replacement No

Shims Colonial Ht. No. 4151614 N/A N/A 2001 Replacement No

Shims Colonial Ht. No. 2A6593- N/A N/A 2001 Replacement No

A

Shims Colonial Ht. No. T 1273-A N/A N/A 2001 Replacement No

Shims Colonial Ht. No. 1 E802 N/A N/A 2001 Replacement No

Shims Colonial Ht. No. R6759 N/A N/A 2001 Replacement No

Shims Colonial Ht. No. 2A6387- N/A N/A 2001 Replacement No A

Shims Colonial Ht. No. R6791 N/A N/A 2001 Replacement No

Shims Colonial Ht. No. 2A6593- N/A N/A 2001 Replacement No

E

Shims Colonial Ht. No. 2A6386- N/A N/A 2001 Replacement No D

Shims Colonial Ht. No. 2A6384- N/A N/A 2001 Replacement No A

Shims Colonial Ht. No. TI273-B N/A N/A 2001 Replacement No

Shims Colonial Ht. No. R4747 N/A N/A 2001 Replacement No

Shims Colonial Ht. No. 1E803 N/A N/A 2001 Replacement No

Shims Colonial Ht. No. R6791 N/A N/A 2001 Replacement No

Shims Colonial Ht. No. 1E542 N/A N/A 2001 Replacement No

1" Bolts A325 Colonial Ht. No. 706907 N/A N/A 2001 Replacement No

1" Bolts A325 Colonial Ht. No. 213265 N/A N/A 2001 Replacement No

1" Flat Washers Colonial Ht. No. B28393 N/A N/A 2001 Replacement No

F436-93

I" Hex. Hd. Nuts Colonial Ht. No. S41165 N/A N/A 2001 Replacement No

A194 Gr. 2H ¾" Bolt, A-490 Colonial Ht. No. 8996654 N/A N/A 2001 Replacement No

¾" Lockwashers Colonial Ht. No. 43739D N/A N/A 2001 Replacement No

B 18.21 S.G. Col. Adapter Colonial Fabricated N/A MRR 01042 2001 Replacement No

A588 Assembly

Page 3 of 4

Page 104: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

Name of Name of Manufacturer National Other Year Repaired ASME

Component Manufacturer Serial No. Board Identification: Built Replaced Code

No. Or Stamped Replacement Yes/No

S.G. Col. Adapter Colonial Ht. No. N/A N/A 2001 Replacement No

Pin AISI 4340 8996496C0477 2 0 R p a e n N

S.G. Col. Adapter Colonial Ht. No. N/A N/A 2001 Replacement No

Pin Washer A-588, 803M62250 Gr. A S.G. Col. Adapter Colonial Ht. No. 255029 N/A N/A 2001 Replacement No

Pin Washer Bolts Trace Code I UX A-325 S.G. Adapter Col. Colonial Ht. No. 10618 N/A N/A 2001 Replacement No

Adapter Bolts A- Trace No. IUU 54 0, G r. B 23 , C l. 2 2001_R place entN

S.G. Adapter Col. Colonial Ht. No. S42483, N/A N/A 2001 Replacement No

Jam Nuts, SA307 Trace No. IUY Gr. B S.G. Adapter Col. Colonial Ht. No. 8994464 N/A N/A 2001 Replacement No

Heavy Hex. Nut, Ht Code SBG SA 194 Gr. 2H

S.G. Col. Adapter Colonial Ht. No. 8997945 N/A N/A 2001 Replacement No

Washers AISI 4150 Trace Code I UW I-- I

I. I* -I- I 1

_______ I + I I 1

_______ I F + I I 1

_________ F F I I I 1

_______ I F I I I t

_ _ _ _ _ I I

I I I -1I

Page 4 of 4

Page 105: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions for the ASME Code Section XI

1. Owner: Wisconsin Public Service Corporation 700 North Adams P.O. Box 19001 Green Bay, WI 54307-9001

2. Plant: Kewaunee Nuclear Power Plant N490 HWY 42 Kewaunee, WI 54216-9511

Date: 12/13/01

Sheet: 1 of 2

Unit: No. 1

Work Order#: SEE BELOW

WORK ORDER WP&IR DESCRIPTION 01-008135 M-BDA-382 S.G. "A" BLOWDOWN CUT / REWELD 01-008135 M-BDB-383 S.G. "B" BLOWDOWN CUT / REWELD 01-013145 M-SGA-364 S.G. "A" SMALL BORENOZZLE PREPS 01-013145 M-SGB-365 S.G. "B" SMALL BORE NOZZLE PREPS

3. Work Performed by: Bechtel Construction

4. Identification of System: 07 Class: 2 Name: BLOWDOWN

5. (a) Applicable Construction Code: USAS B31.1, 1967 Ed. , No Add.

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements: 1989, No Add.

Code Case: N/A

Code Case: N-416-2

6. Identification of Components Repaired or Replaced and Replacement Components:

Name of Name of Manufacturer National Other Year Repaired, ASME Component Manufacturer Serial No. Board Identification Built Replaced, Code

No. or Stamped Replacement Yes/No

SG LOOP-A N/A N/A N/A N/A N/A Repaired No BLOWDOWN PIPING SG LOOP-A ANSALDO 202 151 N/A 2000 Replacement Yes LOWER ASSY BLOWDOWN NOZZLE SG LOOP-B N/A N/A N/A N/A N/A Repaired No BLOWDOWN PIPING SG LOOP-B ANSALDO 201 150 N/A 2000 Replacement Yes LOWER ASSY BLOWDOWN NOZZLE

7. Description of Work: TEMPORARY REMOVAL OF EXISTING BLOWDOWN PIPING AT EACH STEAM

GENERATOR OUTLET NOZZLE AND PREPERATION OF BLOWDOWN NOZZLES ON NEW STEAM

GENERATOR LOWER ASSEMBLIES. ALL PIPING WAS PREPARED AND REINSTALLED BY WELDING.

8. Tests Conducted: Hydrostatic F] Pneumatic E] Nominal Operating Pressure [* Exempt rl

Other: [] Pressure: A-1040 psi / B-1030 psi Test Temp: A-549.35°F / B-548.17°F

* NOTE: The Secondary Side Hydrotest was conducted at NOP per Code Case N-416- 2

Page 1 of2

Page 106: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

Date: 12/13/01

Name of Component: BLOWDOWN

Work Order Number: 01-008135

CERTIFICATE OF COMPLIANCE

We certify that the statements made in the report are correct and this repair and replacement conforms to the rules of the ASME Code, Section XI repair or replacement.

N/AType Code Symbol Stamp

Certificate of Authorization No. N/A Expiration Date N/A

Signed: • 4• Ak•qJftR SA-,cz5'"-Owner or Owner's Designee, Title

CERTIFICATE OF INSERVICE INSPECTION

I, the undersigned, holding a valid commission issued by the National Board of Boiler Pressure Vessel Inspectors

and the State or Providence of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of

Hartford, CT have inspected the components described in this Owner's Report during the period 65 -I>"-•

to 1 tI ' \ , and state that to the best of my knowledge and belief, the Owner has performed

examinations and taken corrective measures described in this Owner's Report in accordance with the

requirements of the ASME Code, Section XI

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or

implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore,

neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or

of loss of any kind arising from or connected with this inspection.

(Robert T. Ward) Commissions r,3 ii S-) A,.Qi L-'- /( Y 9

Inspect& 'SIgf' ture National Board, State, Province, and Endorsements

Date: ___ _ .2001

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS

Continuation Sheet

Page 2 of 2

Date I/j*a/K L

Page 107: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions for the ASME Code Section XI

1. Owner: Wisconsin Public Service Corporation700 North Adams P.O. Box 19001 Green Bay, WI 54307-9001

Date: 12/13/01

Sheet: 1 of 5

2. Plant: Kewaunee Nuclear Power PlantN490 HWY 42 IKowai~n•. WI 54216-9511

Unit: No. 1

Work Order#: SEE BELOW

WORK ORDER WP&IR DESCRIPTION 01-008137 M-ULR-312 Remove & Modify Upper

Lateral

3. Work Performed by: Bechtel Construction

4. Identification of System: 5A Class: 2 Name: "B" Upper Lateral inclu

Snubber

5. (a) Applicable Construction Code: USAS B31.1, 1967 Ed., No Add.

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements: 1989, No Add.

6. Identification of Components Repaired or Replaced and Replacement Components:

ding Spring Cans &

Code Case: N/A

Code Case: N/A

Name of Name of Manufacturer National Other Year Repaired, ASM: Component Manufacturer Serial No. Board Identification Built Replaced, Code

No. or Stamped Replacement Yes/No

See continuation sheet, page 3 1

4- -k I F I

4- 4- 4 1 F I

4- I I F I

__________ .1. _________ L ________ A ______ i __________ L ___ J

7. Description of Work: Repaired Upper Lateral Restraint and replacement of bolting and shims for upper lateral

8. Tests Conducted: Hydrostatic E] Pneumatic E] Nominal Operating Pressure n Exempt Z

Other: n Pressure: psi Test Temp oF.

Page 1 of 5

Kewaunee WI 54216-9511

Page 108: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

Date: 12/13/01

Name of Component: UPPER LATERAL RESTRAINT SYSTEM.

Work Order Number: 01-008137

CERTIFICATE OF COMPLIANCE

We certify that the statements made in the report are correct and this repair and replacement conforms to the rules of the ASME Code, Section XI repair or replacement.

Type Code Symbol Stamp N/A

Certificate of Authorization No. N/A

Signed: 2L4 ý KL-pPpmq;ýSý

Expiration Date N/A

Date / i/ol"Owner or Owner's Designee, Title

CERTIFICATE OF INSERVICE INSPECTION

I, the undersigned, holding a valid commission issued by the National Board of Boiler Pressure Vessel Inspectors

and the State or Providence of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of

Hartford, CT have inspected the components described in this Owner's Report during the period C9-/'f2"rl

to - K-'0"• , and state that to the best of my knowledge and belief, the Owner has performed

examinations and taken corrective measures described in this Owner's Report in accordance with the

requirements of the ASME Code, Section XI

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or

implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore,

neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or

of loss of any kind arising from or connected wi this inspection.

(Robert T. Ward) Commissions p / i-•?ApJ/? L-j •"/i('$'

Inspec sSignature/ National Board, State, Province, and Endorsements

Date: 2001

Page 2 of 5

Page 109: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

Name of Component

"B" Hydraulic Snubber "B" Upper Lateral Ring Girder Splice Plate, Ring Girder, ASTM A588, Gr. A Splice Plate Bolt, ASTM A540, Gr.B23, Cl. 2 Splice Plate Heavy Hex. Nuts, A194, Gr. 2H Splice Plate Washers, F436 Splice Plate Heavy Hex Nuts, A 194, Gr. 2H Bumper Plate, A588 Side Bumper Bearing Plate, A588 ¾" Threaded Rod, A540 Gr. B23, Cl. 2 ¾" Hex. Nut, A563 Washer, F436 Side Bumper Shim, A36 Side Bumper Shim, A36 Side Bumper Shim, A36 Side Bumper Shim, A36 Side Bumper Shim, A36 Side Bumper Shim, A36 Side Bumper Shim, A36 Side Bumper Shim, A36 Side Bumper Shim, A36 Side Bumper Shim, A109 CIO10 Side Bumper Shim, A109 C1010 Side Bumper Shim, A109 CI010 Side Bumper Shim, A109 CI010 Washer Plate, A36

Upper Lateral Ring Plate, A36

Nai Ma

N/A

N/A

Col

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS

Continuation Sheet

me of Manufacturer National Other Year Re

nufacturer Serial No. Board Identification: Built Re No. Or

Re

N/A N/A N/A N/A Re

k N/A N/A N/A N/A Re

onial Ht. No. 412H07 N/A N/A 2001 Re

Colonial

Colonial

Colonial

Colonial

Colonial Colonial

Colonial

Colonial Colonial Colonial

Colonial

Colonial

Colonial

Colonial

Colonial

Colonial

Colonial

Colonial

Colonial

Colonial

Colonial

Colonial

Colonial

Colonial

HT No. 10187RYE

Ht. No. 8994464 Trace Code SBG

Ht. No. Y85307 Trace Code SBH Ht. No. S42483 Trace Code I UV

Ht. No. BIS6214 Ht. No. 1B518

Ht. No. 8991820

Ht. No. 34467PJ Ht. No. 107494 Ht. No. EIF023A12 Ht. No. E1GI19A16 Ht. No. EIG119A16 Ht. No. B1F669C16 Ht. No. T2866

Ht. No. Al C202B20 Ht. No. A1D370B32 Ht. No. BIE825B16 Ht. No. BIF555C23 Ht. No. 64595

Ht. No. Y07405

Ht. No. 65747

Ht. No. M06708

Ht. No. 404875

Ht. No. A1T1203

N/A N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A N/A N/A N/A

N/A N/A

N/A N/A N/A N/A N/A N/A

N/A N/A

N/A N/A

N/A N/A

N/A N/A

N/A N/A

N/A N/A

N/A N/A

N/A N/A

N/A N/A

N/A N/A

N/A N/A

N/A N/A

N/A N/A

N/A N/A

Re

paired placed

placement

paired

paired

placement

placement F

ASME Code Stamped Yes/No No

No

No

No

No

No

No

No No

No

No No No

No

No

No

No

No

No

No

No

No

No

No

No

No

No

Page 3 of 5

Re2001

2001

2001

2001

2001 2001

2001

2001 2001 2001

2001

2001

2001

2001

2001

2001

2001

2001

2001

2001

2001

2001

2001

2001

Replacement

Replacement

Replacement

Replacement Replacement

Replacement

Replacement Replacement Replacement

Replacement

Replacement

Replacement

Replacement

Replacement

Replacement

Replacement

Replacement

Replacement

Replacement

Replacement

Replacement

Replacement

Replacement

Page 110: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS

Continuation Sheet

Name of Name of Manufacturer National Other Year Repaired ASME Component Manufacturer Serial No. Board Identification: Built Replaced Code

No. Or Stamped Replacement Yes/No

3/8" Threaded Rod, Colonial Ht. No. 813953 N/A N/A 2001 Replacement No A307, Gr. A

Heavy Hex Nuts, Colonial Ht. No. A61415 N/A N/A 2001 Replacement No A563, Gr. A

Std. Washer, F436, Colonial Ht. No. B 16294 N/A N/A 2001 Replacement No Type I Upper Lateral Ring Colonial Ht. No. AIU1599 N/A N/A 2001 Replacement No Plate Shim, A36

Upper Lateral Ring Colonial Ht. No. BIP5527 N/A N/A 2001 Replacement No Plate Shim, A36

3/8" Hex Hd. Bolt, Colonial Ht. No. 8878678 N/A N/A 2001 Replacement No A307-97 3/8" Std. Washer, Colonial Ht. No. B16294 N/A N/A 2001 Replacement No F436 Type I Ring Girder Shim, Colonial Ht. No. 1E479 N/A N/A 2001 Replacement No A36 Ring Girder Shim, Colonial Ht. No. 1 E744 N/A N/A 2001 Replacement No A36 Ring Girder Shim, Colonial Ht. No. 2A6386- N/A N/A 2001 Replacement No A36 C Ring Girder Shim, Colonial Ht. No. 2A6593- N/A N/A 2001 Replacement No A36 C Ring Girder Shim, Colonial Ht. No. 4151614 N/A N/A 2001 Replacement No A109-CRI010 Ring Girder Shim, Colonial Ht. No. A86743 N/A N/A 2001 Replacement No

A109-CRIOIO Ring Girder Shim, Colonial Ht. No. R4747 N/A N/A 2001 Replacement No A36 Flat Bar Backing KNPP JB8913 N/A QADC 01-349 2001 Replacement No Strip, A36 Ring Girder Shim, Colonial Ht. No. 4125164 N/A N/A 2001 Replacement No A109-CRIOIO Back Bumper Colonial MRR-01030 N/A N/A 2001 Replacement No Bearing Plate and Pipes ¾" Threaded Rod, Colonial Ht. No. 8991820 N/A N/A 2001 Replacement No A540 Gr B23, C12 ¾" Nut, A563 Colonial 31167PJ N/A N/A 2001 Replacement No

¾" Washer, F436 Colonial 107494 N/A N/A 2001 Replacement No

Back Bumper Shim, Colonial E1F023-A12 N/A N/A 2001 Replacement No A36 Back Bumper Shim, Colonial EIGI 19-A16 N/A N/A 2001 Replacement No

A36 Back Bumper Shim, Colonial BIF669-C16 N/A N/A 2001 Replacement No A36 Back Bumper Shim, Colonial T2866 N/A N/A 2001 Replacement No A36 Back Bumper Shim, Colonial A1C202-B20 N/A N/A 2001 Replacement No A36

Back Bumper Shim, Colonial A1D370-B23 N/A N/A 2001 Replacement No A36 Back Bumper Shim, Colonial B1E825-B16 N/A N/A 2001 Replacement No A36

Page 4 of 5

Page 111: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS

Continuation Sheet

Name of Name of Manufacturer National Other Year Repaired ASME

Component Manufacturer Serial No. Board Identification: Built Replaced Code No. Or Stamped

Replacement Yes/No

Back Bumper Shim, Colonial BIF555-C23 N/A N/A 2001 Replacement No

A36 Back Bumper Shim, Colonial 64595 N/A N/A 2001 Replacement No

A36 Back Bumper Shim, Colonial Y07405 N/A N/A 2001 Replacement No

A36 Back Bumper Shim, Colonial 65747 N/A N/A 2001 Replacement No

A36 Ring Girder Shim, Colonial Ht. No. 2A6386- N/A N/A 2001 Replacement No

A36 E

Ring Girder Shim, Colonial Ht. No. 2A6593- N/A N/A 2001 Replacement No

A36 E

¾" Nut, A563-93 Colonial 107494 N/A N/A 2001 Replacement No

TYPE 1 1 1

Page 5 of 5

Page 112: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS

As Required by the Provisions for the ASME Code Section XI

1. Owner: Wisconsin Public Service Corporation 700 North Adams P.O. Box 19001 Green Bay, WI 54307-9001

2. Plant: Kewaunee Nuclear Power Plant N490 HWY 42 Kewaunee WI 54216-9511

Date: 12/12/01

Sheet: 1 of 2

Unit: No.1

Work Order#: SEE BELOW

WORK ORDER WP&IR DESCRIPTION 01-013145 M-SGB-363 REMOVE SHIPPING COVER 01-013376 M-SDS-323 SEVER STEAM DOME 01-008136 M-SDB-371 REFURBISH STEAM DOME

01-013376 M-SDB-373 RE-INSTALL STEAM DOME

3. Work Performed by: Bechtel Construction

4. Identification of System: 05/06 Class: 2 Name: "B" Steam Generator Secondary Side

5. (a) Applicable Construction Code: USAS B31.1, 1967 Ed. , No Add. Code Case: N/A

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements: 1989, No Add.

6. Identification of Components Repaired or Replaced and Replacement Components:

Name of Name of Manufacturer National Other Year

Component Manufacturer Serial No. Board Identification Built No.

Steam Dome Westinghouse 1142 68-29 N/A 1970

Code Case: N-416-2

Repaired, Replaced, or Replacement Repaired

Replacement SG Ansaldo 201 150 N/A 2000 Replacemen Lower assembly Feedwater Nozzle PCI FW# 2 N/A MRR-01019 2001 Replacemen

Adaptor I.. ,,,, l. .

Main Steam Flow Ansaldo N/A N/A Limiter

It

t

ASME Code Stamped Yes/No Yes

Yes

No

No

7. Description of Work: Prep New lower assembly for Steam Dome installation, Remove Steam Dome from the

Old Lower Assembly, Refurbish the Feedwater Nozzle, Install the Main Steam Flow Limiter, Install the Steam

Dome on the Niew Lower seby

8. Tests Conducted: Hydrostatic E] Pneumatic El Nominal Operating Pressure Z* Exempt [1

Pressure: 1030 psi Test Temp 548.17 OF

* NOTE: The Secondary Side Hydrotest was conducted at NOP per Code Case N-416- 2

Page 1 of 2

Other: M]

Rep ace,./ ,L!31 t nIQAUL;-U - -04-1 /-UUU

uome

on me New LOWS[ /•55•lllUly.

Page 113: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

Date: 12/12/01

Name of Component: SG # B

Work Order Number: 01-013145, 01-013376, 01-008136.

CERTIFICATE OF COMPLIANCE

We certify that the statements made in the report are correct and this repair and replacement conforms to the rules of the ASME Code, Section XI repair or replacement.

Type Code Symbol Stamp N/A

Certificate of Authorization No. N/A Expiration Date

Signed: 4--Jp- Q -. D Owner or Owner's Designee, Title

N/A

ate___________

Page 2 of 2

CERTIFICATE OF INSERVICE INSPECTION

I, the undersigned, holding a valid commission issued by the National Board of Boiler Pressure Vessel Inspectors

and the State or Providence of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of

Hartford, CT have inspected the components described in this Owner's Report during the period (tc-)L/"-0

to "I -' - I , and state that to the best of my knowledge and belief, the Owner has performed

examinations and taken corrective measures described in this Owner's Report in accordance with the

requirements of the ASME Code, Section XA

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or

implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore,

neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or

of loss of any kind arising from or connected with this inspection.

(Robert T. Ward) Commissions &;& (/S5"5) tJ5F Q q iLc 4' Inspector ifgnature/ National Board, State, Province, and Endorsements

Date: I~-I•200\

Page 114: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions for the ASME Code Section XI

1. Owner: Wisconsin Public Service Corporation 700 North Adams P.O. Box 19001 Green Bay, WI 54307-9001

2. Plant: Kewaunee Nuclear Power Plant N490 HWY 42 Kewaunee, WI 54216-9511

Date: 12/13/01

Sheet: 1 of 3

Unit: No.1

Work Order#: SEE BELOW

WORK ORDER WP&IR DESCRIPTION 01-008139 M-FWA-380 S.G. "A" FW /AFW CUT OUT AND WELD 01-008139 M-FWB-381 S.G. "B" FW /AFW CUT OUT AND WELD

3. Work Performed by: Bechtel Construction

4. Identification of System: 05A/05B Class: 2 Name: FEEDWATER / AFW

5. (a) Applicable Construction Code: USAS B31.1, 1967 Ed. , No Add. Code Case: N/A

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements: 1989, No Add.

6. Identification of Components Repaired or Replaced and Replacement Components:

Code Case: N-416-2

Name of Name of Manufacturer National Other Year Repaired, ASME

Component Manufacturer Serial No. Board Identification Built Replaced, Code No. or Stamped

Replacement Yes/No

SEE CONTINUATION, SHEET 3

7. Description of Work: TEMPORARY REMOVAL OF EXISTING FEEDWATER PIPING AT EACH STEAM

GENERATOR OUTLET NOZZLE. TEMPORARY REMOVAL OF EXISTING AUXILLARY FEEDWATER

PIPING AT THE MAIN FEEDWATER BRANCH AT EACH STEAM GENERATOR. WELD REPAIRS ON BOTH

REMOVED FEEDWATER SPOOLS AND REPLACEMENT OF FEEDWATER VENT VALVE ASSEMBLY

(FW-80 A / B) CONNECTIONS USING NEW SOCKOLET AND INSERT REDUCER FITTINGS. ALL PIPING

WAS PREPARED AND REINSTALLED BY WELDING

8. Tests Conducted: Hydrostatic Fl Pneumatic El Nominal Operating Pressure [* Exempt E]

Other: F] Pressure: [A-FW 1040 psi / AFW 1040 psi] [ B-FW 1030 psi / AFW 1030 psi]

Test Temp: [A-FW 549.351F / AFW 57 0F] [B-FW 548.17'F / AFW 57°F]

* NOTE: The Secondary Side Hydrotest was conducted at NOP per Code Case N-416- 2

Page 1 of 3

Page 115: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

Date: 12/13/01

Name of Component: FEEDWATER / AUXILLARY FEEDWATER

Work Order Number: 01-008139

CERTIFICATE OF COMPLIANCE

We certify that the statements made in the report are correct and this repair and replacement

conforms to the rules of the ASME Code, Section XI repair or replacement.

Type Code Symbol Stamp N/A

Certificate of Authorization No. N/A Expiration Date

Signed: o4L',- AP4UP-•P DS'or flun,�r'� n�inn�A Title

N/A

ate/ 41sl(

CERTIFICATE OF INSERVICE INSPECTION

I, the undersigned, holding a valid commission issued by the National Board of Boiler Pressure Vessel Inspectors

and the State or Providence of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of

Hartford, CT have inspected the components described in this Owner's Report during the period 09-f!)-f I

to I (- ?P-C, , and state that to the best of my knowledge and belief, the Owner has performed

examinations and taken corrective measures described in this Owner's Report in accordance with the

requirements of the ASME Code, Section XI

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or

implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore,

neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or

of loss of any kind arising from or connected with this inspection.

(Robert T. Ward) Commissions • A tV ) A1- .-A.' ? c/-1/'

Inspector's Signature National Board, State, Province, and Endorsements

Date: t 0) -r 20O0

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS

Continuation Sheet

Page 2 of 3

/

Page 116: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

Name of Name of Manufacturer National Other Year Repaired ASME Component Manufacturer Serial No. Board Identification: Built Replaced Code

No. Or Stamped Replacement Yes/No

SG LOOP-A N/A N/A N/A N/A N/A REPAIRED YES FEEDWATER SG LOOP-A N/A N/A N/A N/A N/A REPAIRED YES AUXILLARY FEEDWATER SG LOOP-B N/A N/A N/A N/A N/A REPAIRED YES FEEDWATER

SG LOOP-B N/A N/A N/A N/A N/A REPAIRED YES AUXILLARY FEEDWATER

SOCKOLET N/A N/A N/A HT# 2016 ANB REPLACEMENT NO

16"X 2" QADC 01-408

REDUCING N/A N/A N/A HT# 1566 ANB REPLACEMENT NO INSERT 2" X 1"

QADC 01-408

Page 3 of 3

Page 117: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions for the ASME Code Section XI

1. Owner: Wisconsin Public Service Corporation 700 North Adams P.O. Box 19001 Green Bay, WI 54307-9001

2. Plant: Kewaunee Nuclear Power Plant N490 HWY 42 Kewaunee WI 54216-9511

3.

4.

5.

6.

Date: 12/12/01

Sheet: 1 of 2

Unit: No.1

Work Order#: SEE BELOW

WORK ORDER WP&IR DESCRIPTION 01-005474 M-IWR-394 S.G. "A" INSTALL

LEVEL INSTR. WIDE RANGE

01-005474 M-IWR-395 S.G. "B" INSTALL LEVEL INSTR. WIDE RANGE

Work Performed by: Bechtel Construction

Identification of System: 06 Class: 2 Name: MAIN STEAM AND STEAM DUMP

(a) Applicable Construction Code: USAS B31.1. 1967 Ed. , No Add. Code Case: N/A

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements: 1989, No Add. Code Case: N-416-2

Identification of Components Repaired or Replaced and Replacement Components:

Name of Name of Manufacturer National Other Year Repaired, ASME

Component Manufacturer Serial No. Board Identification Built Replaced, Code

No. or Stamped Replacement Yes/No

CONDENSATE KNPP N/A N/A QADC 01-393 2001 REPLACEMENT NO

POT HT 85188

7. Description of Work: INSTALL NEW UPPER WIDE RANGE TAP, CONDENSATE POT AND TUBING.

8. Tests Conducted: Hydrostatic Dl Pneumatic [I Nominal Operating Pressure Z* Exempt E]

Other: E] Pressure: A-1 040 psi / B-1 030 psi Test Temp: A-549.35°F / B-548.17°F

* NOTE: The Secondary Side Hydrotest was conducted at NOP per Code Case N-416- 2

Page 1 of 2

Page 118: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

Date: 12/12/01

Name of Component: MAIN STEAM AND STEAM DUMP

Work Order Number: 01-005474

CERTIFICATE OF COMPLIANCE

We certify that the statements made in the report are correct and this repair and replacement

conforms to the rules of the ASME Code, Section XI repair or replacement.

Type Code Symbol Stamp N/A

Certificate of Authorization No. N/A Expiration Date N/A

Signed: • • -/%•,"' 1F•,L k-, TIA Date Owner or Owner's Designee, Title

CERTIFICATE OF INSERVICE INSPECTION

I, the undersigned, holding a valid commission issued by the National Board of Boiler Pressure Vessel Inspectors

and the State or Providence of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of

Hartford, CT have inspected the components described in this Owner's Report during the period OC -0--31

to I I 3- 1•• ý , and state that to the best of my knowledge and belief, the Owner has performed

examinations and taken corrective measures described in this Owner's Report in accordance with the

requirements of the ASME Code, Section XI

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or

implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore,

neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or

of loss of any kind arising from or connected with this inspection.

(Robert T. Ward) Commissions 0J1% 1 55") A4 UL-37- o) 4/..y

Inspector's Signature National Board, State, Province, and Endorsements

Date: t• 20-X).

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS

Continuation Sheet

Page 2 of 2

Page 119: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions for the ASME Code Section XI

1. Owner: Wisconsin Public Service Corporation 700 North Adams P.O. Box 19001 Green Bay, WI 54307-9001

2. Plant: Kewaunee Nuclear Power Plant N490 HWY 42 Kewaunee Wl 54216-9511

Date: 12/12/01

Sheet: 1 of 2

Unit: No.1

Work Order#: SEE BELOW

WORK ORDER WP&IR DESCRIPTION 01-008141 M-MSA-350 S.G. "A" MS CUT OUT AND WELD 01-008141 M-MSB-351 S.G. "B" MS CUT OUT AND WELD

3. Work Performed by: Bechtel Construction

4. Identification of System: 06 Class: 2 Name: MAIN STEAM

5. (a) Applicable Construction Code: USAS B31.1, 1967 Ed. ,No Add.

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements: 1989, No Add.

6. Identification of Components Repaired or Replaced and Replacement Components:

Code Case: N/A

Code Case: N-416-2

Name of Name of Manufacturer National Other Year Repaired, ASME Component Manufacturer Serial No. Board Identification Built Replaced, Code

No. or Stamped Replacement Yes/No

SG LOOP-A N/A N/A N/A N/A N/A REPAIRED YES MAIN STEAM SG LOOP-B N/A N/A N/A N/A N/A REPAIRED YES MAIN STEAM 1 "GAMMA PORT COLONIAL HT # 87261 N/A N/A 2000 REPLACEMENT NO PLUG X 1" LG MACHINE HT CODE A696 GR C COMPANY, INC. AEM 1 "GAMMA PORT WFI HT # 8998228 N/A N/A 2001 REPLACEMENT NO PLUG X 2" LG INTERNATIONAL HT CODE A696 GR C 297YNB

7. Description of Work: TEMPORARY REMOVAL OF EXISTING MAIN STEAM PIPING AT EACH STEAM

GENERATOR OUTLET NOZZLE. EXISTING PIPING WAS PREPARED AND REINSTALLED BY WELDING.

REINSTALLATION INCLUDES ADDITION OF TWO NEW RADIOGRAPHY GAMMA PORTS AND PLUGS

PER LOOP.

8. Tests Conducted: Hydrostatic E] Pneumatic E] Nominal Operating Pressure * Exempt E]

Other: 0 Pressure: A-1 040 psi/ B-1 030 psi Test Temp: A-549.35°F / B-548.17°F

* NOTE: The Secondary Side Hydrotest was conducted at NOP per Code Case N-416- 2

Page 1 of`2

Page 120: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

Date: 12/12/01

Name of Component: MAIN STEAM

Work Order Number: 01-008141

CERTIFICATE OF COMPLIANCE

We certify that the statements made in the report are correct and this repair and replacement

conforms to the rules of the ASME Code, Section X1 repair or replacement.

Type Code Symbol Stamp N/A

Certificate of Authorization No. N/A Expiration Date N/A

Signed: 7,, "• -- , " .Date " Owner or Owner's Designee, Title

CERTIFICATE OF INSERVICE INSPECTION

I, the undersigned, holding a valid commission issued by the National Board of Boiler Pressure Vessel Inspectors

and the State or Providence of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of

Hartford, CT have inspected the components described in this Owner's Report during the period p9-/?-oj

to /I- ?-,- , and state that to the best of my knowledge and belief, the Owner has performed

examinations and taken corrective measures described in this Owner's Report in accordance with the

requirements of the ASME Code, Section XI

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or

implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore,

neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or

of loss of any kind arising from or connected with this inspection.

(Robert T. Ward) CommissionstX3_ii&ý) A,,.; cT Y6/,

Inspec s Signature National Board, State, Province, and Endorsements

Date: h. "1 '• 20kO _

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS

Continuation Sheet

Page 2 of 2

Page 121: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS

As Required by the Provisions for the ASME Code Section XI

1. Owner: Wisconsin Public Service Corporation 700 North Adams P.O. Box 19001 Green Bay, WI 54307-9001

2. Plant: Kewaunee Nuclear Power Plant N490 HWY 42 Kewaunee WI 54216-9511

Date: 12/12/01

Sheet: 1 of 2

Unit: No.1

Work Order#: SEE BELOW

WORK ORDER WP&IR DESCRIPTION 01-008137 M-RCS-366 S.G. "A" RCS CUT OUT

AND WELD

01-008133 M-RCS-360 S.G. "A" RCS NOZZLE PREP

3. Work Performed by: Bechtel Construction

4. Identification of System: 36 Class: 1 Name: REACTOR COOLANT

5. (a) Applicable Construction Code: USAS B31.1, 1967 Ed. ,No Add. Code Case: N/A

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements: 1989, No Add. Code Case: N-416-2

6. Identification of Components Repaired or Replaced and Replacement Components:

Name of Name of Manufacturer National Other Year Repaired, ASME

Component Manufacturer Serial No. Board Identification Built Replaced, Code

No. or Stamped Replacement Yes/No

STEAM WESTINGHOUSE 1141 68-28 NONE 1970 REPAIRED YES

GENERATOR STEAM ANSALDO 202 151 QADC-00-376 2000 REPLACEMENT YES

GENERATOR 11/2" CAP WESTINGHOUSE N/A N/A HT# 8000913, N/A REPLACEMENT NO

SCREW HT CODE RVP

1 1/2" CAP WESTINGHOUSE N/A N/A HT 204394, N/A REPLACEMENT NO

SCREW HT CODE SAZ

7. Description of Work: THE EXISTING WESTINGHOUSE LOWER ASSEMBLY WAS SEVERED FROM

REACTOR COOLANT PIPING. A NEW LOWER ASSEMBLY WAS PREPARED. INSTALLED. AND

CONNECTED TO THE REACTOR COOLANT PIPING BY WELDING.

8. Tests Conducted: Hydrostatic E] Pneumatic El Nominal Operating Pressure * Exempt El

Other: El Pressure: 2240 psi Test Temp: 551 .1OF

* NOTE: The Primary Side Hydrotest was conducted at NOP per Code Case N-416- 2

Page 1 of 2

Page 122: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

Date: 12/12/01

Name of Component: REACTOR COOLANT

Work Order Number: 01-008137, 01-008133

CERTIFICATE OF COMPLIANCE

We certify that the statements made in the report are correct and this repair and replacement conforms to the rules of the ASME Code, Section XI repair or replacement.

Type Code Symbol Stamp N/A

Certificate of Authorization No. N/A

Signed: .4--- 1 .. "£ K 4fA ac- -I*>v

Expiration Date N/A

Date /I/'cfOwner or Owner's DesiQnee, Title

CERTIFICATE OF INSERVICE INSPECTION

I, the undersigned, holding a valid commission issued by the National Board of Boiler Pressure Vessel Inspectors

and the State or Providence of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of

Hartford, CT have inspected the components described in this Owner's Report during the period 09-//9

to ___- ____, and state that to the best of my knowledge and belief, the Owner has performed

examinations and taken corrective measures described in this Owner's Report in accordance with the

requirements of the ASME Code, Section Xl

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or

implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore,

neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or

of loss of any kind arising from or connected with this inspection.

(Robert T. Ward) Commissions S.)3115S'7,JJ. U•.- 3 2(&'1

InspecteA -Signature National Board, State, Province, and Endorsements

Date: to-r% 2001

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS

Continuation Sheet

Page 2 of 2

f

Page 123: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS

As Required by the Provisions for the ASME Code Section XI

1. Owner: Wisconsin Public Service Corporation 700 North Adams P.O. Box 19001 Green Bay, WI 54307-9001

2. Plant: Kewaunee Nuclear Power Plant N490 HWY 42 Kewaunee WI 54216-9511

3. Work Performed by: Bechtel Construction

4. Identification of System: 36 Class:

5. (a) Applicable Construction Code: USAS B31.1, 1967 E

(b) Applicable Edition of Section X1 Utilized for Repairs or

6. Identification of Components Repaired or Replaced

Name of Name of Manufacturer P

Component Manufacturer Serial No. E

STEAM WESTINGHOUSE 1142 6 GENERATOR STEAM ANSALDO 201 1

GENERATOR 11/2" CAP WESTINGHOUSE N/A h SCREW 11/2' CAP WESTINGHOUSE N/A SCREW

Date: 12/12/01

Sheet: 1 of 2

Unit: No.1

Work Order#: SEE BELOW

WORK ORDER WP&IR DESCRIPTION 01-008137 M-RCS-367 S.G. "B" RCS CUT OUT

AND WELD

01-008133 M-RCS-361 S.G. "B" RCS NOZZLE PREP

1 Name: REACTOR COOLANT

-d. ,No Add. Code Case: N/A

Replacements: 1989, No Add. Code Case: N-416-2

and Replacement Components:

Jational Other Year Repaired, ASMIE Board Identification Built Replaced, Code 0o. or Stamped

Replacement Yes/No

8-29 NONE 1970 REPAIRED YES

50 QADC 00376 2000 REPLACEMENT YES

N/A HT# 8000913, N/A REPLACEMENT NO HT CODE RVP

VA HT 204394, N/A REPLACEMENT NO HT CODE SAZ

7. Description of Work: THE EXISTING WESTINGHOUSE LOWER ASSEMBLY WAS SEVERED FROM

REACTOR COOLANT PIPING. A NEW LOWER ASSEMBLY WAS PREPARED, INSTALLED, AND

CONNECTED TO THE REACTOR COOLANT PIPING BY WELDING.

8. Tests Conducted: Hydrostatic E] Pneumatic E] Nominal Operating Pressure [ Exempt El

Other: E] Pressure: 2240 psi Test Temp: 551 .1F

* NOTE: The Primary Side Hydrotest was conducted at NOP per Code Case N-416- 2

Page 1 of 2

Page 124: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

Date: 12/12/01

Name of Component: REACTOR COOLANT

Work Order Number: 01-008137, 01-008133

CERTIFICATE OF COMPLIANCE

We certify that the statements made in the report are correct and this repair and replacement

conforms to the rules of the ASME Code, Section Xl repair or replacement.

Type Code Symbol Stamp N/A

Certificate of Authorization No. N/A

Signed: A /4t-/ P4.r &- '_

Expiration Date N/A

Date 1!ý/ 7 /

Owner or Owner's Designee, I tle

CERTIFICATE OF INSERVICE INSPECTION

I, the undersigned, holding a valid commission issued by the National Board of Boiler Pressure Vessel Inspectors

and the State or Providence of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of

Hartford, CT have inspected the components described in this Owner's Report during the period 05/-0- I

to P , and state that to the best of my knowledge and belief, the Owner has performed

examinations and taken corrective measures described in this Owner's Report in accordance with the

requirements of the ASME Code, Section XI

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or

implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore,

neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or

of loss of any kind arising from or connected with this inspection.

(Robert T. Ward) Commissions AA Ill'S'2dIJ; G"-s P'V(- Y..iA

Ins p(ýsSig nature National Board, State, Province, and Endorsements

Date: 200(

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS

Continuation Sheet

Page 2 of 2

Page 125: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions for the ASME Code Section XI

1. Owner: Wisconsin Public Service Corporation 700 North Adams P.O. Box 19001 Green Bay, WI 54307-9001

2. Plant: Kewaunee Nuclear Power Plant N490 HWY 42 Kewaunee WI 54216-9511

3.

4.

5.

6.

Date: 12/12/01

Sheet: 1of 4

Unit: No.1

Work Order# : SEE BELOW

WORK ORDER WP&IR DESCRIPTION 01-013376 M-LLR-313 Replace Upper Col.

Adapters and Reshim Lower Lateral Restraint

Work Performed by: Bechtel Construction

Identification of System: 36 Class: 1 Name: "A" Col. Adapter Plates and Lower Lateral Shims

(a) Applicable Construction Code: USAS B31.1, 1967 Ed. ,No Add. Code Case: N/A

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements: 1989, No Add. Code Case: N/A

Identification of Components Repaired or Replaced and Replacement Components:

Name of Name of Manufacturer National Other Year Repaired, ASME Component Manufacturer Serial No. Board Identification Built Replaced, Code

No. or Stamped Replacement Yes/No

See continuation sheet, page 3

7. Description of Work: Replaced steam generator support upper column adapters and removed and restored

lower lateral suDport bumper guides to the steam generator and shimmed the adiacent support bumper steel.

Exempt Z

OF

Page 1 of 4

8. Tests Conducted: Hydrostatic [] Pneumatic E] Nominal Operating Pressure El

Other: [] Pressure: psi Test Temp

Page 126: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

Date: 12/12/01

Name of Component: "A" Upper Col. Adapter Plates and Reshim Lower Lateral Restraint.

Work Order Number: 01-0133760

CERTIFICATE OF COMPLIANCE

We certify that the statements made in the report are correct and this repair and replacement conforms to the rules of the ASME Code, Section Xl repair or replacement.

Type Code Symbol Stamp N/A

Certificate of Authorization No. N/A Expiration Date N/A

Signed: . - ,, eH $--V Date 4 I , Owner or Owner's Designee, Title

CERTIFICATE OF INSERVICE INSPECTION

I, the undersigned, holding a valid commission issued by the National Board of Boiler Pressure Vessel Inspectors

and the State or Providence of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of

Hartford, CT have inspected the components described in this Owner's Report during the period C')C -/ ) -0i1

to I and state that to the best of my knowledge and belief, the Owner has performed

examinations and taken corrective measures described in this Owner's Report in accordance with the

requirements of the ASME Code, Section XI

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or

implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore,

neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or

of loss of any kind arising from or connected with this inspection.

(Robert T. Ward) Commissions 6 ii -),,4

Inspecti_'s-gfiature National Board, State, Province, and Endorsements

Date: - Is 2001

Page 2 of 4

Page 127: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS

Continuation Sheet

Name of Component

Shims

Shims

Shims

Shims

Shims

Shims

Shims

Shims

Shims

Shims

Shims

Shims

Shims

Shims

V" Bolts A325

I" Bolts A325

1" Flat Washers F436-93 I" Hex. Hd. Nuts A194 Gr. 2H ¾" Lockwashers B18.21 S.G. Col. Adapter A588 S.G. Col. Adapter Pin AISI 4340 S.G. Col. Adapter Pin Washer A-588, Gr. A S.G. Col. Adapter Pin Washer Bolts A-325

Name of Manufacturer Manufacturer Serial No.

Colonial Ht. No. 264344

Colonial Ht. No. 812J3592

Colonial Ht. No. 4126617

Colonial Ht. No. 4122060

Colonial Ht. No. 4155918

Colonial Ht. No. 4125164

Colonial Ht. No. A86743

Colonial Ht. No. 4151614

Colonial Ht. No. 2A6593A

Colonial Ht. No. T1273-A

Colonial Ht. No. I E802

Colonial Ht. No. R6759

Colonial Ht. No. R6791

Colonial Ht. No. I E542

Colonial Ht. No. 706907

Colonial Ht. No. 213265

Colonial Ht. No. B28393

Colonial Ht. No. S41165

Colonial Ht. No. 43739D

Colonial Fabricated Assembly

Colonial Ht. No. 8996496C0477

Colonial Ht. No. 803M62250

Colonial Ht. No. 255029 Trace Code I UX

National Other Board Identification. No.

N/A N/A

N/A N/A

N/A N/A

N/A N/A

N/A N/A

N/A N/A

N/A N/A

N/A N/A

N/A N/A

N/A N/A

N/A N/A

N/A N/A

N/A N/A

N/A N/A

N/A N/A

N/A N/A

N/A N/A

N/A N/A

N/A N/A

N/A MRR 1042

N/A N/A

N/A N/A

N/A N/A

Year Built

2001

2001

2001

2001

2001

2001

2001

2001

2001

2001

2001

2001

2001

2001

2001

2001

2001

2001

2001

2001

2001

2001

2001 I Replacement

Page 3 of 4

Repaired Replaced Or Replacement Replacement

Replacement

Replacement

Replacement

Replacement

Replacement

Replacement

Replacement

Replacement

Replacement

Replacement

Replacement

Replacement

Replacement

Replacement

Replacement

Replacement

Replacement

Replacement

Replacement

Replacement

Replacement

ASME Code Stamped Yes/No No

No

No

No

No

No

No

No

No

No

No

No

No

No

No

No

No

No

No

No

No

No

No

Page 128: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

Name of Name of Manufacturer National Other Year Repaired ASME Component Manufacturer Serial No. Board Identification: Built Replaced Code

No. Or Stamped Replacement Yes/No

S.G. Adapter Col. Colonial Ht. No. 10618 N/A N/A 2001 Replacement No Adapter Bolts A- Trace No. IUU 540, Gr. B23, Cl. 2 S.G. Adapter Col. Colonial Ht. No. S42483, N/A N/A 2001 Replacement No Jam Nuts, SA307 Trace No. 1UY Gr. B

S.G. Adapter Col. Colonial Ht. No. 8994464 N/A N/A 2001 Replacement No Heavy Hex. Nut, Ht Code SBG SA 194 Gr. 2H

S.G. Col. Adapter Colonial Ht. No. 8997945 N/A N/A 2001 Replacement No Washers AISI 4150 Trace Code 1UW

%" Hex Head Bolt, Colonial 8996654 N/A N/A 2001 Replacement No

A-490

___________ I 4 4 + +

4 4 ± t t

4 4 ± ± t

4 4 + I t

+ *1� 1 T

I I [ 1 1 F

Page 4 of 4

Page 129: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section Xl

1. Owner Wisconsin Public Service Corporation

700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001

2. Plant Kewaunee Nuclear Power Plant

N490 HWY 42 Kewaunee, WI 54216-9511

3. Work Performed By Nuclear Management Company, LLC

700 First Street, Hudson, Wisconsin 54016

4. Identification of System 33 Class 1 SAFETY INJECTION

5. (a) Applicable Construction Code B16.5-1967

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989

6. Identification of Components Repaired or Replaced and Replacement Components

Name of Manufacturer

Manufacturer Serial No.

ANCHOR/DARLING VALVE NF COMPANY

National Board No.

NA

Other ID

S1115-002

Date 11/26/2001

Sheet 1 of 2

Unit No. 1

Work Order 01-005013

Type Code Sym. Stamp NA

Authorization No. NA

Expiration Date NA

Code Case NA

Year Built

1970

Repaired, Replaced, or Replacement

REPLACEMENT

7. Description of Work OPEN FOR INSPECTION CLASS 1 SAFETY INJECTION SYSTEM 12" VALVE SI-22B AND REPLACEMENT OF 1

VALVE BONNET STUD.

8. Tests conducted Hydrostatic

Other DR Pneumatic r] Nominal Operating Pressure E

Pressure 750 psi Test Temp. 63 deg. F

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

Name of

Component

SI-22B

ASME Code

Stamped

N

Exempt 1

Page 130: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

NIS-2 (Back)

Sheet 2 of 2

Date: 11/26/2001

Name of Component: SI-22B

Work Order Number: 01-005013

Certificate of Compliance

We Certify that the statements made in the report are correct and this REPLACEMENT conforms to the rules of the

ASME Code Section XI. Repair or Replacement

Type Code Symbol Stamp NA

Certificate of Authorization No. NA Expiration Date NA

Signed £/ffiM geJ~g9U A &OW14 Date

Owner or Owner's Designee, Title

Certificate of INSERVICE INSPECTION

I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors

and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT

have inspected the components described in the Owner's Report during the period -74 S-D 0 to / - 31-0 2-, and state that

to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described

in this Owners Report in accordance with the requirements of the ASME Code, Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning

the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor

his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising

from or connected with this inspection.

7 i 4-1, Commissions NB7741, 1, N, IS, A WIS 100024

Inspector' Signature National Board, State, Province, and Endorsements

Date a, t- A , / - ,20 01.

Page 131: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section XI

1. Owner Wisconsin Public Service Corporation

700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001

2. Plant Kewaunee Nuclear Power Plant

N490 HWY 42 Kewaunee, WI 54216-9511

3. Work Performed By Nuclear Management Company, LLC

700 First Street, Hudson, Wisconsin 54016

4. Identification of System 34 Class 2 RESIDUAL HEAT REMOVAL

5. (a) Applicable Construction Code NA

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989

6. Identification of Components Repaired or Replaced and Replacement Components

Name of

Component

APRH1-IA

Name of

Manufacturer

BRYON JACKSON

Manufacturer Serial No.

681N0277

National Board No.

NA

Other ID

00127

Date 11/27/2001

Sheet 1 of 2

Unit No. 1

Work Order 01-005020

Type Code Sym. Stamp N._A

Authorization No. NA

Expiration Date NA

Code Case NA

Year Built

1970

Repaired, Replaced, or

Replacement

REPAIRED

7. Description of Work INSPECT AND REBUILD CLASS 2 RESIDUAL HEAT REMOVAL SYSTEM RESIDUAL HEAT REMOVAL PUMP 1A.

8. Tests conducted Hydrostatic

Other F

7] Pneumatic El Pressure 375 psi

Nominal Operating Pressure =l

Test Temp. 341 deg. F

9. Remarks NOT APPLICABLE

Applicable Manufacturer's Data Reports to be Attached

ASME Code

Stamped

N

Exempt 1

Page 132: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

NIS-2 (Back)

Sheet 2 of 2

Date: 11/27/2001

Name of Component: APRH1-IA

Work Order Number: 01-005020

Certificate of Compliance

We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the

ASME Code Section Xl. Repair or Replacement

Type Code Symbol Stamp NA

Certificate of Authorization No. NA Expiration Date NA

Signed e, C.4 V .. m&Aot. ae6.ý D4ateL 20 Z

Owner or Owner's Designee, Title

Certificate of INSERVICE INSPECTION

I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors

and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT

have inspected the components described in the Owner's Report during the period -1-A,-0o to /- 3 /-0Z , and state that

to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described

in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, conceming

the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor

his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising

from or connected with this inspection.

Commissions NB7741, I, N, IS, A WIS 100024

Inspector's ignature National Board, State, Province, and Endorsements

Date / 20 e .

Page 133: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section Xl

1. Owner Wisconsin Public Service Corporation

700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001

2. Plant Kewaunee Nuclear Power Plant

N490 HWY 42 Kewaunee, WI 54216-9511

3. Work Performed By Nuclear Management Company, LLC

700 First Street. Hudson, Wisconsin 54016

4. Identification of System 35 Class 2 CHEMICAL AND VOLUME CONTROL

5. (a) Applicable Construction Code B31.1-1967

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989

6. Identification of Components Repaired or Replaced and Replacement Components

Name of

Component

LD-13

Name of

Manufacturer

CROSBY VALVE & GAGE CO.

Manufacturer Serial No.

NF

National

Board No.

NA

Other ID

CS014-001

Date 11/2912001

Sheet 1 of 2

Unit No. 1

Work Order 01-005030

Type Code Sym. Stamp N.A

Authorization No. NA

Expiration Date NA

Code Case NA

Year Built

1971

Repaired, Replaced, or Replacement

REPAIRED

7. Description of Work REMOVE FOR TESTING CLASS 2 CHEMICAL AND VOLUME CONTROL SYSTEM 2" VALVE LD-13.

8. Tests conducted Hydrostatic L] Other D

Pneumatic F Nominal Operating Pressure El Pressure 84 psi Test Temp. 87 deg. F

9. Remarks NOT APPLICABLE.

Applicable Manufacturers Data Reports to be Attached

ASME Code

Stamped

N

Exempt [:

Page 134: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

NIS-2 (Back)

Sheet 2 of 2

Date: 11/29/2001

Name of Component: LD-13

Work Order Number: 01-005030

Certificate of Compliance

We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the

ASME Code Section XI. Repair or Replacement

Type Code Symbol Stamp NA

Certificate of Authorization No. NA Expiration Date NA

Signed 6k ý__.• ( y-,4- Date 4_ ! ,20 O.L OV - O DeXi Owner or Owner's Designee, Title

Certificate of INSERVICE INSPECTION

I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors

and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT

have inspected the components described in the Owner's Report during the period 1-2S-- 0 to /- 3/- 01, and state that

to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described

in this Owners Report in accordance with the requirements of the ASME Code, Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning

the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor

his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising

from or connected with this inspection.

7 4 1 Commissions NB7741, I, N, IS, A WIS 100024

nspector'Sqnature National Board, State, Province, and Endorsements

Date / ,20 02

Page 135: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section Xl

1. Owner Wisconsin Public Service Corporation

700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001

2. Plant Kewaunee Nuclear Power Plant

N490 HWY 42 Kewaunee, WI 54216-9511

3. Work Performed By Nuclear Management Company, LLC

700 First Street, Hudson, Wisconsin 54016

4. Identification of System 35 Class 2 CHEMICAL AND VOLUME CONTROL

5. (a) Applicable Construction Code B31.1-1967

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989

6. Identification of Components Repaired or Replaced and Replacement Components

Date 11/29/2001

Sheet 1 of 2

Unit No. 1

Work Order 01-005031

Type Code Sym. Stamp NA

Authorization No. NA

Expiration Date NA

Code Case NA

Repaired, ASME Name of Name of Manufacturer National Other Year Replaced, or Code

Component Manufacturer Serial No. Board No. ID Built Replacement Stamped

LD-5 CROSBY ASHTON GAGE NF NA CS109-001 1970 REPAIRED N CO.

7. Description of Work REMOVE FOR TESTING CLASS 2 CHEMICAL AND VOLUME CONTROL SYSTEM 2" VALVE LD-5.

8. Tests conducted Hydrostatic

Other F

--1 Pneumatic E Pressure 500 psi

Nominal Operating Pressure 17

Test Temp. 250 deg. F

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

Exempt 1:1

Page 136: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

NIS-2 (Back)

Sheet 2 of 2

Date: 11/29/2001

Name of Component: LD-5

Work Order Number: 01-005031

Certificate of Compliance

We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the

ASME Code Section Xl. Repair or Replacement

Type Code Symbol Stamp NA

Certificate of Authorization No. NA Expiration Date NA

Signed l.e/,aI £. .T-,44Q/LA Date L- 20 OQ

Owner or Owner's Designee, Title

Certificate of INSERVICE INSPECTION

I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors

and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT

have inspected the components described in the Owner's Report during the period 7-,aS-0 O to /-/'-O3.- , and state that

to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described

in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning

the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor

his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising

from or connected with this inspection.

Commissions NB7741, I, N, IS, A WIS 100024

Inspector' Signature National Board, State, Province, and Endorsements

Date 2 • .•,• / ,20 1,,-

Page 137: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT

As Required by the Provisions of the ASME Code Section Xl

1. Owner Wisconsin Public Service Corporation

700 North Adams P.O.Box 19001 Green Bay. WI 54307-9001

2. Plant Kewaunee Nuclear Power Plant

N490 HWY 42 Kewaunee. WI 54216-9511

3. Work Performed By Nuclear Management Company, LLC

700 First Street, Hudson, Wisconsin 54016

4. Identification of System 36 Class 1 REACTOR COOLANT

5. (a) Applicable Construction Code ASME 111-1968

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989

6. Identification of Components Repaired or Replaced and Replacement Components

Date 12/4/2001

Sheet 1 of 2

Unit No. 1

Work Order 01-005033

Type Code Sym. Stamp N._A

Authorization No. NA

Expiration Date NA

Code Case NA

Name of Manufacturer

Manufacturer Serial No.

CROSBY, ASHTON GAGE NF COMPANY

National Board No.

NA

Other Year ID Built

RCOO8-001 1972 REPLAL�M�N N

��p�I1-�u,Repaired, Replaced, or

Replacement

7. Description of Work REMOVE CLASS 1 REACTOR COOLANT SYSTEM 6" VALVE PR-3A FOR TESTING AND REPLACING DICS INSERT.

8. Tests conducted Hydrostatic

Other ElEl Pneumatic F

Pressure 2240 psi

Nominal Operating Pressure E

Test Temp. 5_1 deg. F

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

Name of

Component

PR-3A

Code Stamped

Exempt [-1

REPLACEME=NT NRC008-001 1972

Page 138: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

NIS-2 (Back)

Sheet 2 of 2

Date: . 12/4/2001

Name of Component: PR-3A

Work Order Number: 01-005033

Certificate of Compliance

We Certify that the statements made in the report are correct and this REPLACEMENT conforms to the rules of the

ASME Code Section XI. Repair or Replacement

Type Code Symbol Stamp NA

Certificate of Authorization No. NA Expiration Date NA

Signed _____, ______________ Date • g 20 0-1

Owner or Owner's Designee, Title

Certificate of INSERVICE INSPECTION

I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors

and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT

have inspected the components described in the Owner's Report during the period -7-"2S-oO to /- ,/-0,Z , and state that

to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described

in this Owners Report in accordance with the requirements of the ASME Code, Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning

the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor

his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising

from or connected with this inspection.

4 = "Commissions NB7741, I, N, IS, A WIS 100024

Inspector's Signature National Board, State, Province, and Endorsements

Date ,20 O

Page 139: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section XI

1. Owner Wisconsin Public Service Corporation

700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001

2. Plant Kewaunee Nuclear Power Plant

N490 HWY 42 Kewaunee, WI 54216-9511

3. Work Performed By Nuclear Management Company, LLC

700 First Street, Hudson, Wisconsin 54016

4. Identification of System 05B Class 2 AUXILIARY FEEDWATER

5. (a) Applicable Construction Code B31.1-1967

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989

6. Identification of Components Repaired or Replaced and Replacement Components

Name of

Component

AFW-4B

Name of

Manufacturer

WILLIAM POWELL CO.

Manufacturer Serial No.

61208

National Board No.

NA

Other ID

F015-002

Date 12/20/2001

Sheet 1 of 2

Unit No. 1

Work Order 01-005272

Type Code Sym. Stamp N.A

Authorization No. NA

Expiration Date NA

Code Case NA

Year Built

1972

Repaired, Replaced, or Replacement

REPAIRED

7. Description of Work REPAIR CLASS 2 AUXILARY FEEDWATER SYSTEM 3" VALVE AFW-4B DUE TO IMPROPER SEATING.

8. Tests conducted Hydrostatic

Other D]LI Pneumatic F Nominal Operating Pressure F]

Pressure 1030 psi Test Temp. 57 deg. F

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

ASME Code

Stamped

N

Exempt 1

N

Page 140: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

NIS-2 (Back)

Sheet 2 of 2

Date: .12/20/2001

Name of Component: AFW-4B

Work Order Number: 01-005272

Certificate of Compliance

We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the

ASME Code Section Xl. Repair or Replacement

Type Code Symbol Stamp NA

Certificate of Authorization No. NA Expiration Date NA

Signed Date •'o ,20 _._20 _

Owner or Owner's Designee, Title

Certificate of INSERVICE INSPECTION

I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors

and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT

have inspected the components described in the Owner's Report during the period I-•,• 00 to ,/-,/9•2 , and state that

to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described

in this Owners Report in accordance with the requirements of the ASME Code, Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning

the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor

his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising

from or connected with this inspection.

ln "Commissions NB7741, I, N, IS, A WIS 100024

Inspector's ignature National Board, State, Province, and Endorsements

Date t ,20 6-.

Page 141: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section XI

1. Owner Wisconsin Public Service Corporation

700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001

2. Plant Kewaunee Nuclear Power Plant

N490 HWY 42 Kewaunee. WI 54216-9511

3. Work Performed By Nuclear Management Company, LLC

700 First Street, Hudson, Wisconsin 54016

4. Identification of System 05B Class 2 AUXILIARY FEEDWATER

5. (a) Applicable Construction Code B31.1-1967

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989

6. Identification of Components Repaired or Replaced and Replacement Components

Name of Manufacturer

WILLIAM POWELL CO.

Manufacturer Serial No.

NF

National

Board No.

NA

Other

ID

FO15-001

Date 12/20/2001

Sheet 1 of 2

Unit No. 1

Work Order 01-005273

Type Code Sym. Stamp NA

Authorization No. NA

Expiration Date NA

Code Case NA

Year Built

1972

Repaired, Replaced, or Replacement

REPAIRED

7. Description of Work REPAIR CLASS 2 AUXILIARY FEEDWATER SYSTEM 3" VALVE AFW-4A DUE TO IMPROPER SEATING.

8. Tests conducted Hydrostatic [

Other D

Pneumatic Nominal Operating Pressure =V

Pressure 1040 psi Test Temp. 57 deg. F

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

Name of

Component

AFW-4A

ASME Code

Stamped

N

Exempt 1

Page 142: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

NIS-2 (Back)

Sheet 2 of 2

Date: •12/20/2001

Name of Component: AFW-4A

Work Order Number: 01-005273

Certificate of Compliance

We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the

ASME Code Section XI. Repair or Replacement

Type Code Symbol Stamp NA

Certificate of Authorization No. NA Expiration Date NA

Signed PXfluO-A.l 1Z n Ou -v Date 2 0,20

Owner or Owner's Designee, Title

Certificate of INSERVICE INSPECTION

I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors

and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT

have inspected the components described in the Owner's Report during the period 9÷S'• 00 to / -3/OV , and state that

to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described

in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning

the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor

his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising

from or connected with this inspection.

Commissions NB7741, 1, N, IS, A WIS 100024

Inspector'signature National Board, State, Province, and Endorsements

Date f -/ ,20 1PZ

Page 143: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section Xl

1. Owner Wisconsin Public Service Corporation

700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001

2. Plant Kewaunee Nuclear Power Plant

N490 HWY 42 Kewaunee, WI 54216-9511

3. Work Performed By Nuclear Management Company, LLC

700 First Street, Hudson, Wisconsin 54016

4. Identification of System 23 Class 2 CONTAINMENT SPRAY

5. (a) Applicable Construction Code B16.5-1967

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989

6. Identification of Components Repaired or Replaced and Replacement Components

Name of

Component

ICS-2B

Name of

Manufacturer

CRANE VALVE CO.

Manufacturer Serial No.

NF

National Board No.

NA

Date 12/3/2001

Sheet I of 2

Unit No. 1

Work Order 01-007182

Type Code Sym. Stamp N__A

Authorization No. NA

Expiration Date NA

Code Case NA

Other Year ID Built

ICS002-002 1970

Repaired, ASMERepaired,

Replaced, or Replacement

REPAIRED N

7. Description of Work OPEN FOR MAINTAENANCE CLASS 2 INTERNAL CONTAINMENT SPRAY 8" VALVE ICS-2B.

8. Tests conducted Hydrostatic E

Other RI

Pneumatic r- Nominal Operating Pressure FX

Pressure 30 psi Test Temp. 70.4 deg. F

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

ASME Code

Stamped

Exempt 1"1

REPAIRED N

Page 144: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

NIS-2 (Back)

Sheet 2 of 2

Date: 12/3/2001

Name of Component: ICS-2B

Work Order Number: 01-007182

Certificate of Compliance

We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the

ASME Code Section XL. Repair or Replacement

Type Code Symbol Stamp NA

Certificate of Authorization No. NA Expiration Date NA

Signed / / 4 'f,0Jfl- Date ,20 02

Owner or Owner's Designee, Title

Certificate of INSERVICE INSPECTION

I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors

and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT

have inspected the components described in the Owner's Report during the period '7--2S-9 to /-3/ -02, and state that

to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described

in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning

the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor

his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising

from or connected with this inspection.

Commissions NB7741, I, N, IS, A WIS 100024

Inspectors Signature National Board, State, Province, and Endorsements

Date / 20 _.___,20_

Page 145: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section Xl

1. Owner Wisconsin Public Service Corporation

700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001

2. Plant Kewaunee Nuclear Power Plant

N490 HWY 42 Kewaunee, WI 54216-9511

3. Work Performed By Nuclear Management Company, LLC

700 First Street, Hudson, Wisconsin 54016

4. Identification of System 23 Class 2 CONTAINMENT SPRAY

5. (a) Applicable Construction Code B16.5-1967

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989

6. Identification of Components Repaired or Replaced and Replacement Components

Name of

Component

ICS-2A

Name of

Manufacturer

CRANE VALVE CO.

Manufacturer Serial No.

NF

National Board No.

NA

Date 12/3/2001

Sheet 1 of 2

Unit No. 1

Work Order 01-007183

Type Code Sym. Stamp N__AA

Authorization No. NA

Expiration Date NA

Code Case NA

Other Year

ID Built

ICS002-001 1970

Repaired, Replaced, or Replacement

REPAIRED

7. Description of Work OPEN FOR MAINTENANCE CLASS 2 INTERNAL CONTAINMENT SPRAY 8" VALVE ICS-2B.

8. Tests conducted Hydrostatic

Other D--1-1 Pneumatic 1:1 Nominal Operating Pressure IE

Pressure 30 psi Test Temp. 70.4 deg. F

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

ASME Code

Stamped

N

Exempt 1

Page 146: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

NIS-2 (Back) Sheet 2 of 2

Date: 12/3/2001

Name of Component: ICS-2A

Work Order Number: 01-007183

Certificate of Compliance

We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the

ASME Code Section XI. Repair or Replacement

Type Code Symbol Stamp NA

Certificate of Authorization No. NA Expiration Date NA

Signed _.D ••e•J L.'i 20 0 _

Owner or Owner's Designee, Title

Certificate of INSERVICE INSPECTION

I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors

and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT

have inspected the components described in the Owner's Report during the period '7-;,'5-' 0 to I-3 / -V2 , and state that

to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described

in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning

the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor

his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising

from or connected with this inspection.

ie, -7 .Commissions NB7741, I, N, IS, A WIS 100024

U p oiorsSignature National Board, State, Province, and Endorsements

Da te- .20 01

Page 147: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section XI

1. Owner Wisconsin Public Service Corporation

700 North Adams P.O.Box 19001 Green Bay. WI 54307-9001

2. Plant Kewaunee Nuclear Power Plant

N490 HWY 42 Kewaunee, WI 54216-9511

3. Work Performed By Nuclear Management Company, LLC

700 First Street, Hudson, Wisconsin 54016

4. Identification of System 23 Class 2 CONTAINMENT SPRAY

5. (a) Applicable Construction Code B16.5-1967

(b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 1989

6. Identification of Components Repaired or Replaced and Replacement Components

Name of Component

RHR-400B

Name of Manufacturer

CRANE COMPANY

Manufacturer Serial No.

NA

National Board No.

NA

Date 1/14/2002

Sheet 1 of 2

Unit No. I

Work Order 01-007184

Type Code Sym. Stamp NA..

Authorization No. NA

Expiration Date NA

Code Case NA

Other Year ID Built

ICS006-006 1970

Repaired, ASMERepaired,

Replaced, or Replacement

REPAIRED

7. Description of Work OPEN FOR MAINTENANCE CLASS 2 INTERNAL CONTAINMENT SPRAY 6" VALVE RHR-400B DUE TO POSSIBLE

DISC TO SEAT GALLING.

8. Tests conducted Hydrostatic

Other

Pneumatic Nominal Operating Pressure rl

Pressure 144 psi Test Temp. 87 deg. F

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

ASME Code

Stamped

N

Exempt r-1

Page 148: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

NIS-2 (Back)

Sheet 2 of 2

Date: 1/14/2002

Name of Component: RHR-400B

Work Order Number: 01-007184

Certificate of Compliance

We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the

ASME Code Section Xi. Repair or Replacement

Type Code Symbol Stamp NA

Certificate of Authorization No. NA Expiration Date NA

Signed f, Date6MAAAM,20 •

Owner or Owner's Designee, Title

Certificate of INSERVICE INSPECTION

I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors

and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT

have inspected the components described in the Owner's Report during the period I-2S'CD 0 to /J/,OZ , and state that

to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described

in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning

the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor

his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising

from or connected with this inspection.

;,2 s 7 a44 • Commissions NB7741, I, N, IS, A WIS 100024

(5 p 5iature National Board, State, Province, and Endorsements

Date ,20 #-1-_

Page 149: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT

As Required by the Provisions of the ASME Code Section XI

1. Owner Wisconsin Public Service Corporation

700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001

2. Plant Kewaunee Nuclear Power Plant

N490 HWY 42 Kewaunee. WI 54216-9511

3. Work Performed By Nuclear Management Company, LLC

700 First Street, Hudson, Wisconsin 54016

4. Identification of System 23 Class 2 CONTAINMENT SPRAY

5. (a) Applicable Construction Code B16.5-1967

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989

6. Identification of Components Repaired or Replaced and Replacement Components

Name of Component

RHR-400A

Name of Manufacturer

CRANE COMPANY

Manufacturer Serial No.

NF

National Board No.

NA

Date 12/20/2001

Sheet I of 2

Unit No. 1

Work Order 01-007185

Type Code Sym. Stamp NA

Authorization No. NA

Expiration Date NNA

Code Case NA

Other Year ID Built

1C5006-005 1970 REPAIRED N

Kepalrea,Repaired, Replaced, or

Replacement

7. Description of Work OPEN FOR MAINTENENCE CLASS 2 INTERNAL CONTAINMENT SPRAY SYSTEM 6" VALVE RHR-400A DUE TO

POSSIBLE DISC TO SEAT GALLING.

8. Tests conducted Hydrostatic Dl Other F

Pneumatic Nominal Operating Pressure r7

Pressure 375 psi Test Temp. 341 deg. F

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

Code Stamped

Exempt F

REPAIRED NICS006-005 1970

Page 150: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

NIS-2 (Back)

Sheet 2 of 2

Date: 12/20/2001

Name of Component: RHR-400A

Work Order Number: 01-007185

Certificate of Compliance

We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the

ASME Code Section XI. Repair or Replacement

Type Code Symbol Stamp NA

Certificate of Authorization No. NA Expiration Date NA

Signed Date < 20 0A

Owner or Owner's Designee, Title

Certificate of INSERVICE INSPECTION

I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors

and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT

have inspected the components described in the Owner's Report during the period '7-1S"-00 to /-$1-t2,, and state that

to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described

in this Owners Report in accordance with the requirements of the ASME Code, Section XL.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning

the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor

his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising

from or connected with this inspection.

Commissions NB7741, I, N, IS, A WIS 100024

pectors Signature National Board, State, Province, and Endorsements

Date / 20 J0

Page 151: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section XI

1. Owner Wisconsin Public Service Corporation

700 North Adams P.O.Box 19001 Green Bay. WI 54307-9001

2. Plant Kewaunee Nuclear Power Plant

N490 HWY 42 Kewaunee, WI 54216-9511

3. Work Performed By Nuclear Management Company, LLC

700 First Street, Hudson, Wisconsin 54016

4. Identification of System 23 Class 2 CONTAINMENT SPRAY

5. (a) Applicable Construction Code B16.5-1967

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989

6. Identification of Components Repaired or Replaced and Replacement Components

Name of Component

ICS-5B

Name of Manufacturer

CRANE VALVE CO.

Manufacturer Serial No.

NF

National Board No.

NA

Date 11/9/2001

Sheet 1 of 2

Unit No. 1

Work Order 01-007186

Type Code Sym. Stamp NAA

Authorization No. NA

Expiration Date NA

Code Case NA

Other Year

ID Built

ICS006-003 1970

Repaired, Replaced, or Replacement

REPAIRED

7. Description of Work OPEN FOR REPAIR CLASS 2 CONTAINMENT SPRAY SYSTEM 6" VALVE ICS-5B DUE TO DISC TO SEAT GALLING.

8. Tests conducted Hydrostatic

Other DD- Pneumatic

Pressure

D Nominal Operating Pressure n

280 psi Test Temp. 75 deg. F

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

ASME Code

Stamped

N

Exempt F

Page 152: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

NIS-2 (Back)

Sheet 2 of 2

Date:. 11/9/2001

Name of Component: ICS-5B

Work Order Number: 01-007186

,20 6

Certificate of Compliance

We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the

ASME Code Section XI. Repair or Replacement

Type Code Symbol Stamp NA

Certificate of Authorization No. NA Expiration Date NA

Signed A &Q lT'/c,2*. A•A•h acW•U t Date 4 ,20 0.1

Owner or Owner's Designee, Title

Certificate of INSERVICE INSPECTION

I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors

and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT

have inspected the components described in the Owners Report during the period 7_-_'_o to I/-'S-, and state that

to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described

in this Owners Report in accordance with the requirements of the ASME Code, Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning

the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor

his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising

from or connected with this inspection.

w o--: Commissions NB7741, I, N, IS, A WIS 100024

National Board, State, Province, and Endorsements

SInspector's iignature

Page 153: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section Xl

1. Owner Wisconsin Public Service Corporation

700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001

2. Plant Kewaunee Nuclear Power Plant

N490 HWY 42 Kewaunee. WI 54216-9511

3. Work Performed By Nuclear Management Company, LLC

700 First Street, Hudson. Wisconsin 54016

4. Identification of System 23 Class 2 CONTAINMENT SPRAY

5. (a) Applicable Construction Code B16.5-1967

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989

6. Identification of Components Repaired or Replaced and Replacement Components

Name of

Component

ICS-6B

Name of

Manufacturer

CRANE VALVE CO.

Manufacturer Serial No.

NF

National

Board No.

NA

Date 11/9/2001

Sheet 1 of 2

Unit No. 1

Work Order 01-007187

Type Code Sym. Stamp NA

Authorization No. NA

Expiration Date NA

Code Case NA

Other Year ID Built

ICS006-004 1970

Repaired, Replaced, or Replacement

REPAIRED

7. Description of Work OPEN FOR MAINTENANCE CLASS 2 CONTAINMENT SPRAY SYSTEM 6" VALVE ICS-6B DUE TO DISC TO SEAT GALLING.

8. Tests conducted Hydrostatic

Other ElEl Pneumatic Nominal Operating Pressure I•

Pressure 280 psi Test Temp. Z5 deg. F

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

ASME Code

Stamped

N

Exempt 1

Page 154: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

NIS-2 (Back)

Sheet 2 of 2

Date: 11/9/2001

Name of Component: ICS-6B

Work Order Number: 01-007187

Certificate of Compliance

We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the

ASME Code Section Xl. Repair or Replacement

Type Code Symbol Stamp NA

Certificate of Authorization No. NA Expiration Date NA

Signed eI "a, &JV.AnJ AAJ Date l i ,20 0O.1 Owner or Owner's Designee, Title

Certificate of INSERVICE INSPECTION

I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors

and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT

have inspected the components described in the Owner's Report during the period '7- 2Y-,0 to /-JI/-0 X, and state that

to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described

in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning

the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor

his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising

from or connected with this inspection.

S44 ,Commissions NB7741, I, N, IS, A WIS 100024

Date ,20 60.1

National Board, State, Province, and EndorsementsV Inspector's 11gnature

Page 155: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section XI

1. Owner Wisconsin Public Service Corporation

700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001

2. Plant Kewaunee Nuclear Power Plant

N490 HWY 42 Kewaunee, WI 54216-9511

3. Work Performed By Nuclear Management Company, LLC

700 First Street, Hudson, Wisconsin 54016

4. Identification of System 33 Class 1 SAFETY INJECTION

5. (a) Applicable Construction Code B16.5-1967

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989

6. Identification of Components Repaired or Replaced and Replacement Components

Name of

Component

SI-304A

Name of

Manufacturer

VELAN VALVE CORPORATION

Manufacturer Serial No.

NF

National Board No.

NA

Other ID

SI116-005

Date 9/7/2001

Sheet 1 of 2

Unit No. 1

Work Order 01-013239

Type Code Sym. Stamp NA

Authorization No. NA

Expiration Date NA

Code Case NA

Year Built

1967

Repaired, Replaced, or Replacement

REPAIRED

7. Description of Work TORQUE BOLTING ON CLASS 1 SAFETY INJECTION SYSTEM 6" VALVE SI-304A DUE TO EVIDENCE OF LEAKAGE.

8. Tests conducted Hydrostatic

Other --

F Pneumatic

Pressure

D Nominal Operating Pressure

0 psi Test Temp.

1:1 Exempt El

0 deg. F

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

ASME Code

Stamped

N

Page 156: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

NIS-2 (Back)

Sheet 2 of 2

Date: 9/7/2001

Name of Component: SI-304A

Work Order Number: 01-013239

Da tetej 20 ~

Certificate of Compliance

We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the

ASME Code Section XI. Repair or Replacement

Type Code Symbol Stamp NA

Certificate of Authorization No. NA Expiration Date NA

Signed Date 20 C.

Owner or Owner's Designee, Title

Certificate of INSERVICE INSPECTION

I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors

and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT

have inspected the components described in the Owner's Report during the period 7t.4"O to /-3/-#;L , and state that

to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described

in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning

the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor

his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising

from or connected with this inspection.

A ?-3" 7~t",Commissions NB7741, 1, N, IS, A WIS 100024

National Board, State, Province, and EndorsementsI" Inspecr's Signature

Page 157: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section XI

1. Owner Wisconsin Public Service Corporation

700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001

2. Plant Kewaunee Nuclear Power Plant

N490 HWY 42 Kewaunee, WI 54216-9511

3. Work Performed By Nuclear Management Company, LLC

700 First Street, Hudson, Wisconsin 54016

4. Identification of System 35 Class 2 CHEMICAL AND VOLUME CONTROL

5. (a) Applicable Construction Code B31.1-1967

(b) Applicable Edition of Section X1 Utilized for Repairs or Replacements 1989

6. Identification of Components Repaired or Replaced and Replacement Components

Name of

Manufacturer

GRINNELL FIRE PROTECTION SYSTEMS

Manufacturer Serial No.

NF

National

Board No.

NA

Date 8/20/2001

Sheet 1 of 2

Unit No. 1

Work Order 01-013438

Type Code Sym. Stamp N.A

Authorization No. NA

Expiration Date NA

Code Case NA

Other Year ID Built

CS033-005 1973

Repaired, Replaced, or Replacement

REPAIRED

7. Description of Work TORQUE BOLTING ON CLASS 2 CHEMICAL AND VOLUME CONTROL SYSTEM 3" VALVE CVC-4C DUE TO BODY TO BONNET LEAK.

8. Tests conducted Hydrostatic

Other F

1I- Pneumatic

Pressure

L] Nominal Operating Pressure El

23 psi Test Temp. 11_5 deg. F

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

Name of

Component

CVC-4C

ASME Code

Stamped

N

Exempt El

Page 158: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

NIS-2 (Back)

Sheet 2 of 2

Date: 8/20/2001

Name of Component: CVC-4C

Work Order Number: 01-013438

Certificate of Compliance

We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the

ASME Code Section Xl. Repair or Replacement

Type Code Symbol Stamp NA

Certificate of Authorization No. NA Expiration Date NA

Signed 1CA AAX.L.A ,7T- t CJ* Date 20 6,20

Owner or Owner's Designee, Title

Certificate of INSERVICE INSPECTION

I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors

and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT

have inspected the components described in the Owner's Report during the period 74--'O0 to /-3/-D2- , and state that

to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described

in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning

the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor

his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising

from or connected with this inspection.

Commissions NB7741, 1, N, IS, A WIS 100024

Inspectors Signature National Board, State, Province, and Endorsements

Date 20 O;

Page 159: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section XI

1. Owner Wisconsin Public Service Corporation

700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001

2. Plant Kewaunee Nuclear Power Plant

N490 HWY 42 Kewaunee, WI 54216-9511

3. Work Performed By Nuclear Management Company, LLC

700 First Street, Hudson, Wisconsin 54016

4. Identification of System 34 Class 2 RESIDUAL HEAT REMOVAL

5. (a) Applicable Construction Code B31.1-1967

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989

6. Identification of Components Repaired or Replaced and Replacement Components

Name of

Component

RHR-100B

Name of Manufacturer

CRANE VALVE CO.

Manufacturer Serial No.

NF

National

Board No.

NA

Date 11/21/2001

Sheet 1 of 2

Unit No. 1

Work Order 01-014566

Type Code Sym. Stamp N A

Authorization No. NA

Expiration Date NA

Code Case NA

Other Year

ID Built

AC010-008 1972

Repaired,

Replaced, or Replacement

REPAIRED

7. Description of Work OPEN FOR REPAIR CLASS 2 RESIDUAL HEAT REMOVAL SYSTEM 8" VALVE RHR-100B.

8. Tests conducted Hydrostatic

Other DPneumatic 1 Nominal Operating Pressure El

Pressure 114 psi Test Temp. 87 deg. F

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

ASME Code

Stamped

N

Exempt LI

Page 160: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

NIS-2 (Back)

Sheet 2 of 2

Date: .11/21/2001

Name of Component: RHR-100B

Work Order Number: 01-014566

Date / 20 2

Certificate of Compliance

We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the

ASME Code Section XI. Repair or Replacement

Type Code Symbol Stamp NA

Certificate of Authorization No. NA Expiration Date NA

Signed __.JA CA)Jt Date .20 0 ca,

Owner or Owner's Designee, Title

Certificate of INSERVICE INSPECTION

I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors

and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT

have inspected the components described in the Owner's Report during the period 74So-' to 3/ 1'- 2-, and state that

to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described

in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning

the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor

his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising

from or connected with this inspection.

Commissions NB7741, I, N, IS, A WIS 100024

National Board, State, Province, and Endorsementsa.nspector's'gnature

Page 161: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section XI

1. Owner Wisconsin Public Service Corporation

700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001

2. Plant Kewaunee Nuclear Power Plant

N490 HWY 42 Kewaunee, WI 54216-9511

3. Work Performed By Nuclear Management Company, LLC

700 First Street, Hudson, Wisconsin 54016

4. Identification of System 34 Class 2 RESIDUAL HEAT REMOVAL

5. (a) Applicable Construction Code B31.1-1967

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989

6. Identification of Components Repaired or Replaced and Replacement Components

Name of

Component

RHR-100A

Name of

Manufacturer

CRANE VALVE COMPANY

Manufacturer Serial No.

NF

National Board No.

NA

Date 11/27/2001

Sheet 1 of 2

Unit No. 1

Work Order 01-014567

Type Code Sym. Stamp NA

Authorization No. NA

Expiration Date NA

Code Case NA

Other Year

ID Built

AC010-007 1972

Repaired, Replaced, or Replacement

REPAIRED

7. Description of Work REPAIR CLASS 2 RESIDUAL HEAT REMOVAL SYSTEM 8" VALVE RHR-100A.

8. Tests conducted Hydrostatic

Other 1:

LII Pneumatic

Pressure 340 psi

Nominal Operating Pressure L

Test Temp. 189 deg. F

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

ASME Code

Stamped

N

Exempt 1

Page 162: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

NIS-2 (Back)

Sheet 2 of 2

Date: .11/27/2001

Name of Component: RHR-100A

Work Order Number: 01-014567

Certificate of Compliance

We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the

ASME Code Section XI. Repair or Replacement

Type Code Symbol Stamp NA

Certificate of Authorization No. NA Expiration Date NA

Signed 1k: •W A 0LN 111. flh1, Date 20 0.__

Owner or Owner's Designee, Title

Certificate of INSERVICE INSPECTION

I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors

and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT

have inspected the components described in the Owner's Report during the period '7-;S'00 to I 3/'-0Z, and state that

to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described

in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning

the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor

his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising

from or connected with this inspection.

A ý nCommissions NB7741, I, N, IS, A WIS 100024

Inspe or's Signature National Board, State, Province, and Endorsements

Date - ••. 20 -0

Page 163: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section XI

1. Owner Wisconsin Public Service Corporation

700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001

2. Plant Kewaunee Nuclear Power Plant

N490 HWY 42 Kewaunee, WI 54216-9511

3. Work Performed By Nuclear Management Company, LLC

700 First Street, Hudson. Wisconsin 54016

4. Identification of System 35 Class 2 CHEMICAL AND VOLUME CONTROL

5. (a) Applicable Construction Code NA

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989

6. Identification of Components Repaired or Replaced and Replacement Components

Name of

Manufacturer

AJAX IRON WORKS

Manufacturer Serial No.

6577

National Board No.

NA

Other ID

00077

Date 9/5/2001

Sheet 1 of 2

Unit No. 1

Work Order 01-014609

Type Code Sym. Stamp N.A

Authorization No. NA

Expiration Date NA

Code Case NNA

Year Built

1967

Repaired, Replaced, or Replacement

REPAIRED

7. Description of Work REPAIR CLASS 2 CHEMICAL AND VOLUME CONTROL SYSTEM CHARGING PUMP 1C (SUCTION VALVE REPAIR).

8. Tests conducted Hydrostatic

Other R

Pneumatic 1: Nominal Operating Pressure El

Pressure 20 psi Test Temp. 112 deg. F

9. Remarks NOT APPLICABLE

Applicable Manufacturer's Data Reports to be Attached

Name of

Component

APCH-1C

ASME Code

Stamped

N

Exempt El

Page 164: Kewaunee Nuclear Power Plant Point Beach Nuclear Plant NM C · Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, Wl 54216-9511 Two

NIS-2 (Back)

Sheet 2 of 2

Date: 9/5/2001

Name of Component: APCH-1C

Work Order Number: 01-014609

Certificate of Compliance

We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the

ASME Code Section XI. Repair or Replacement

Type Code Symbol Stamp NA

Certificate of Authorization No. NA Expiration Date NA

Signed " e•. 640-•pao• Date • ,20 0 Owner or Owner's Designee, Title

Certificate of INSERVICE INSPECTION

I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors

and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT

have inspected the components described in the Owner's Report during the period 1- 2r-0 0 to /__3_-_ 2_, and state that

to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described

in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning

the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor

his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising

from or connected with this inspection.

lns Jtr Commissions NB7741, I, N, IS, A WIS 100024

Inspector's Signature National Board, State, Province, and Endorsements

Date / 20 0 ,