Kohler Tt1584PIM

Embed Size (px)

DESCRIPTION

Kohler Power Generation PIM Installation Manual

Citation preview

  • INSTALLATION INSTRUCTIONS

    TT-1584 2/12a

    Original Issue Date: 2/12

    Model: 14RESA/RESAL, 20RESA/RESAL, and 48RCL

    Market: Residential/Light Commercial

    Subject: Programmable Interface Module (PIM) Kits GM81529-KP1-QS

    Introduction

    The optional Programmable Interface Module (PIM)

    provides two programmable inputs and six

    programmable outputs for connection to

    customer-supplied equipment. The PIM operates only

    with generator sets equipped with the Kohler RDC2 or

    DC2 controller, including the following models:

    14RESA/RESAL

    20RESA/RESAL

    48RCL

    ThePIM ismounted in aNEMA3Renclosure, which can

    be installed indoors or outdoors. The PIM with

    enclosure is shown in Figure 1. For outdoor installation,

    use watertight conduit hubs.

    ADV--8199

    Figure 1 Programmable Interface Module (cover

    removed for illustration)

    Inputs and outputs are factory-set to theevents shown in

    Figure 7. The inputs and outputs 3--6 can be changed

    using a laptop computer connected to the RDC2 or DC2

    controller and Kohler SiteTech software . SiteTech is

    available to Kohler-authorized distributors.

    A maximum of three accessory modules can be

    connected to the generator set. Accessorymodules can

    include one programmable interface module (PIM), one

    Model RXT transfer switch, and/or one load control

    module (LCM).

    Read the entire installation procedure and compare the

    kit parts with the parts list at the end of this publication

    before beginning installation. Perform the steps in the

    order shown.

    OnCue Remote Monitoring and

    Control

    The Kohler OnCue Generator Management System

    can be used to monitor the PIM inputs and outputs.

    OnCue can also be used to remotely control PIMoutputs

    3 through 6. For example, connect output 3 to the storm

    shutters on your vacation home and label it Storm

    Shutters in the Power Chain view in OnCue. When bad

    weather is forecast, you can use your computer to close

    the storm shutters from a remote location.

    The OnCue kit is available from Kohler-authorized

    distributors and dealers. See TP-6796, OnCue

    Software Operation Manual, for instructions to connect

    the generator set to the Internet and use OnCue on a

    personal computer.

  • 2 TT-1584 2/12a

    Safety Precautions

    Observe the following safety precautionswhile installing

    the kit.

    Accidental starting.Can cause severe injury or death.

    Disconnect the battery cables beforeworking on the generator set.

    Remove the negative (--) lead firstwhen disconnecting the battery.Reconnect the negative (--) lead lastwhen reconnecting the battery.

    WARNING

    Disabling the generator set. Accidental starting can

    cause severe injury or death. Before working on thegenerator set or equipment connected to the set, disable thegenerator set as follows: (1) Press the generator set off/resetbutton to shut down the generator set. (2) Disconnect thepower to the battery charger, if equipped. (3) Remove thebattery cables, negative (--) lead first. Reconnect the negative

    (--) lead last when reconnecting the battery. Follow theseprecautions to prevent the starting of the generator set by theremote start/stop switch.

    Hazardous voltage.Will cause severe injury or death.

    Disconnect all power sources beforeopening the enclosure.

    DANGER

    Installation Procedure

    1. Press the OFF button on the generator sets

    RDC2/DC2 controller.

    2. Disconnect the utility power to the generator set.

    3. Disconnect the generator set engine starting

    battery(ies), negative (--) lead first.

    4. Remove the PIM enclosure cover. Cover the PIM

    circuit board to protect it from metal chips and

    debris.

    5. Cut holes in the PIMenclosure for the generator set

    communication leads and input and output leads.

    For outdoor installation, use weather-tight conduit

    connectors.

    Note: Use separate conduit for the low-voltage

    communication leads to the generator set

    controller. To ensure separation of circuits

    per NEC requirements, route low-voltage

    AC and DC wiring separately from

    line-voltage wiring.

    6. Mount the PIM enclosure to a wall. See the

    dimension drawing in Figure 26 for the mounting

    hole size and locations.

    Note: The mounting holes have gaskets to seal

    out moisture. Use washers with the

    mounting screws to protect the gaskets.

    7. Connect A, B, PWR, andCOMon connector P10 to

    the corresponding generator set connectors. See

    Figure 2 through Figure 5. Use Belden #9402

    (4-conductor) or equivalent 20 AWG shielded,

    twisted-pair cable. The maximum cable length is

    61 m (200 ft.).

    Note: If a longer cable run is required, or if

    additional accessories such as a transfer

    switch or a load control module (LCM) are

    used, seeCommunication Connectionswith

    Additional Accessories on page 5.

    1

    ADV-7876

    1. Customer connection terminal block

    Figure 2 14/20RESA Terminal Block Location

  • TT-1584 2/12a 3

    1

    tp6809

    1. Customer connection terminal block

    Note: Access panel removed for illustration.

    Figure 3 Model 48RCL Terminal Block Location

    5

    1. TB4, relay 3 and relay 4 connections

    2. P10, connection to generator set3. TB2, input 1 and input 2 connections

    4. LED1, online

    5. TB3, relay 1 and relay 2 connections6. TB5, relay 5 and relay 6 connections

    7. LED2, power

    6

    ADV--8199

    1

    3

    2

    4

    7

    Figure 4 PIM Circuit Board Connections and LEDs

    Generator Set

    Connect one end of each cable shieldto GROUND at the generator set.

    Leave one end of each cable shielddisconnected at the last device.

    PIM1

    COM

    PWR

    B

    A

    1. Communication cable Belden #9402 or equivalent 20 AWG shielded, twisted-pair cable

    GND

    A

    B

    COM

    PWR

    3

    4

    TB1

    NOTE: See Figure 2 or Figure 3 for the terminal block

    location on the generator set. Check the decal on thegenerator set for terminal block connections.

    RBUS

    12 VDC

    Figure 5 PIM Communication Connections to Generator Set

  • 4 TT-1584 2/12a

    8. Connect customer equipment to inputs 1 and 2 on

    TB2 on the PIM circuit board. See Figure 6 for the

    cable size. See the wiring diagram in Figure 27.

    9. Connect customer equipment to output relays 1

    through 6 on TB3, TB4, and TB5. Note the

    factory-default output settings shown in Figure 7.

    Refer to the wiring diagram in Figure 27 and

    connect to each relays normally open or normally

    closed contacts as required.

    10. Turn the locking tab out so that the enclosure door

    can be secured with a padlock.

    11. Install the door and secure with the door screw.

    Lock the enclosure door with a padlock to prevent

    unauthorized entry.

    12. Reconnect the generator set engine starting

    battery, negative (--) lead last.

    13. Reconnect utility power to the generator set.

    14. Press the AUTO button on the generator set

    controller.

    PIM Connection Specifications

    Input Rating 10 mA @ 12 VDC dry contact

    Output Relay Rating 10 A @ 120 VAC

    Wire Size 12--24 AWG

    Screw Torque 7 in. lbs

    Figure 6 Input/Output Connection Specifications

    15. Note the factory-assigned functions for the digital

    outputs shown in Figure 7. Use a personal

    computer connected to theRDC2or DC2 controller

    and Kohler SiteTech software to change the

    input and output functions, if necessary. Available

    input and output functions are listed in Figure 16

    and Figure 17. See TP-6701, SiteTech Software

    Operation Manual, for instructions.

    PIM Connection SiteTech Name

    DefaultSetting(Event)

    Input 1 TB2 IN1 Digital Input B1 None

    Input 2 TB2 IN2 Digital Input B2 None

    Output 1 TB3

    Relay 1

    Digital Output B1 Generator

    Running

    Output 2 TB3

    Relay 2

    Digital Output B2 Common Fault

    Output 3 TB4

    Relay 3

    Digital Output B3 Low Battery

    Voltage

    Output 4 TB4

    Relay 4

    Digital Output B4 Not in Auto

    Output 5 TB5

    Relay 5

    Digital Output B5 Cooldown

    Output 6 TB5

    Relay 6

    Digital Output B6 Normal Source

    Failure

    Figure 7 Inputs and Outputs

  • TT-1584 2/12a 5

    Communication Connections with

    Additional Accessories

    See Figure 9 through Figure 14 for connection options

    with up to three accessory modules. Accessory

    modules can include one Model RXT transfer switch,

    one programmable interface module (PIM), and/or one

    load control module (LCM).

    See Figure 8 for the maximum total cable length with 1,

    2, or 3 accessory modules per cable run.

    Use Belden #9402 (4-conductor) or equivalent

    20 AWG shielded, twisted-pair cable. Note the shield

    connections shown in Figure 9.

    If longer cable runs are required, #12--14 AWG wire

    can be used for the COMand PWR connections. The

    maximum total cable length is the value shown for

    #12 or #14 AWGwire in Figure 8. The 20 AWG cable

    used for communication connections A and B (only)

    can be as long as 152 m (500 ft.).

    Cable (TB1--PWR and COM)

    Maximum length per run, meters (ft.)

    Number of Modules (ATS, PIM, and LCM) per Run

    1 Module 2 Modules 3 Modules

    Belden #9402 or equivalent 20AWG 61 (200) 31 (100) 21 (67)

    14 AWG 152 (500) 152 (500) 122 (400)

    12 AWG 152 (500) 152 (500) 152 (500)

    Figure 8 Total Cable Lengths with Accessory Modules Connected

    PIM

    LCM

    Generator Set

    COM

    PWR

    COM

    PWR

    B

    A

    B

    A

    COM

    PWR

    B

    A

    Connect one end of each cable shieldto GROUND at the generator set.

    Leave one end of each cable shield disconnected at the last device.

    RXT1

    COM

    PWR

    B

    A

    COM

    PWR

    B

    A

    Connect shields togetheras shown.

    1. Communication cable Belden #9402 or equivalent

    20 AWG shielded, twisted-pair cable

    GND

    A

    B

    COM

    PWR

    3

    4

    TB1

    NOTES:

    See thegeneratorset InstallationManual for terminal

    block location on generator set. Check the decal on

    the generator set for terminal block connections.

    See Figure 8 for maximum total cable length per run

    (1 run shown)

    Current transformer must be installed on theemergency source leads.

    RBUS

    12 VDCCOM

    PWR

    A

    B

    Figure 9 Communication Connection Details with Model RXT Transfer Switch

  • 6 TT-1584 2/12a

    LCM

    Generator Set

    COM

    PWR

    B

    A

    Connect one end of each cable shieldto GROUND at the generator set.

    Leave one end of each cable shield disconnected at the last device.

    PIM1

    COM

    PWR

    B

    A

    COM

    PWR

    B

    A

    Connect shields togetheras shown.

    1. Communication cable Belden #9402 or equivalent 20 AWG

    shielded, twisted-pair cable2. Engine start leads 3 and 4. See the ATS manual for cable

    size specifications.

    GND

    A

    B

    COM

    PWR

    3

    4

    TB1

    NOTES:

    See thegeneratorset InstallationManual for terminal

    block location on generator set. Check the decal on

    the generator set for terminal block connections.

    See Figure 8 for maximum total cable length per run

    (1 run shown)

    Current transformer must be installed on theemergency source leads.

    RBUS

    12 VDCCOM

    PWR

    A

    B

    ATSModels RDTor RSB

    2

    2 4

    3

    Figure 10 Connection Details with Model RDT or RSB Transfer Switch

  • TT-1584 2/12a 7

    NOTES:

    See the generator set Installation Manual for terminal block location on

    generator set. Check the decal on the generator set for terminal block

    connections.

    See Figure 8 for maximum total cable length per run (3 runs with 1module

    each shown).

    See Figure 9 for communication connection detail (A and B, PWR andCOM).

    Use splices or wire nuts to collect multiple leads for connection to the

    generator set terminal block. See Figure 12.

    1. Belden #9402 or equivalent, 20 AWG shielded cable with 2 twisted pairs tp6803

    PIM

    LCM

    RXT ATS

    Generator Set

    TB1

    1

    1

    1

    Figure 11 Accessory Module Connections, Star Configuration (three cable runs with one module each)

    1

    tp6803

    1. Splice

    Generator Set

    Generator Set Terminal Block TB1.See the generator set Installation Manual for location.Check the decal on the generator set for terminal block connections.

    COM

    PWR

    B

    A

    Connect all of the shield leads on thisend to GROUND at the generator set.

    COM

    PWR

    B

    A

    To GROUND

    9402 CABLE

    9402 CABLE

    A

    B

    COM

    PWR

    3

    4

    TB1

    RBUS

    12 VDC

    GND

    Figure 12 Multiple Connections to the Generator Set

  • 8 TT-1584 2/12a

    1. Belden #9402 or equivalent, 20 AWG shielded cable with 2 twisted pairs tp6803

    PIM

    LCM

    RXT ATS1

    1

    1

    Generator Set

    TB1

    NOTES:

    See the generator set Installation Manual for terminal block

    locationongenerator set. Check thedecalon thegenerator set for

    terminal block connections.

    See Figure 8 for maximum total cable length with12 or 14 AWG wire.

    See Figure 9 for communication connection (A and B, PWR andCOM) detail. Connect the cable shield to ground at the generator

    set.

    Figure 13 Accessory Module Connections (two cable runs with one and two modules shown)

    1. Belden #9402 or equivalent, 20 AWG shielded cable (use one pair); or

    Belden #8762 or equivalent 20 AWG shielded cable2. 12--14 AWG wire

    tp6803

    PIM

    LCM

    RXT ATS

    1

    1

    1

    Generator Set A and BPWRCOM 2

    2

    22

    2

    2

    A and B

    A and B

    A and B

    PWRCOM

    PWRCOM

    PWRCOM

    NOTES:

    See the generator set Installation Manual for terminal block location on

    generator set. Check the decal on the generator set for terminal block

    connections.

    SeeFigure 8 formaximum total cable length with 12 or 14 AWGwire. (1

    run with 3 modules shown).

    See Figure 9 for communication connection (A and B) detail. Connectthe cable shield to ground at the generator set.

    Figure 14 Accessory Module Connections with 12--14 AWG Power Leads (one cable run with three modules

    shown)

  • TT-1584 2/12a 9

    PIM Inputs and Outputs

    Connect customer-supplied equipment to the PIM input

    and output connections. Connect to the normally open

    or normally closed output contacts as required for the

    application. See the wiring diagram for connection

    details.

    Run/Common Fault Outputs

    The first two PIM outputs are factory-set to Generator

    Running and Common Fault. See Figure 7. The

    generator running output is activated when the

    generator set is running. The common fault output is

    activated on a fault.

    Changing Input and Output Settings

    Use a laptop computer connected to the RDC2 or DC2

    controller and running Kohler SiteTech software to

    change the event settings for factory-set inputs and

    outputs. Be sure to select Digital Inputs B1--B2 and

    Digital Outputs B1--B6 in SiteTech. See Figure 7 and

    Figure 15. Digital Inputs A1--A2 and Digital Outputs

    A1--A2 and B7--B12 do not apply to the PIM.

    Note: SiteTech software is available to

    Kohler-authorized distributors.

    The available programmable input and digital output

    functions are listed in Figure 16 and Figure 17. At

    installation, note the input and output connections.

    Then use Kohler SiteTech software to assign the

    corresponding input and output functions if they are

    different than the defaults shown in Figure 7.

    1

    tt15841. PIM Digital Input B1 settings

    2. PIM Digital Output B3 settings

    2

    Figure 15 SiteTech Screen, Input and Output

    Settings

    Input Level

    Auxiliary Input Shutdown

    Auxiliary Input Warning

    Battery Charger Fault Warning

    Chicago Code Active Notice

    Engine Fuel Level Critically High Warning

    Engine Fuel Level High Warning

    Engine Fuel Level Low Warning

    Engine Fuel Level Low Shutdown

    Engine Oil Level Low Warning

    Engine Oil Level Low Shutdown

    Fuel Pressure Low Warning

    Fuel Tank Leak Shutdown

    Fuel Tank Leak Warning

    Ground Fault Input Warning

    Remote Reset Status

    * Some inputs do not apply to all models.

    Figure 16 Programmable Inputs

  • 10 TT-1584 2/12a

    Digital Output Level * 14/20 48

    AC Sensing Lost W

    AC Sensing Lost S

    Alternator Protection S NA NA

    Always Off N

    Always On N

    ATS Fail To Transfer W

    ATS Fail To Transfer S NA NA

    ATS Phase RotationMismatch (3-phase only)

    W NA

    Auxiliary Input W

    Auxiliary Input S

    Battery Charger Fault W

    Battery Voltage High W

    Battery Voltage Low W

    Chicago Code Active N

    Common Fault N

    Common Warning W

    Cranking Voltage Low W

    ECM Communication Loss S NA

    Emergency Power SystemSupplying Load

    N

    Emergency Stop S NA

    Engine Coolant Level Low S NA

    Engine CoolantTemperature High

    W NA

    Engine CoolantTemperature High

    S NA

    Engine CoolantTemperature Low

    W NA

    Engine CoolantTemperature No Signal

    S NA

    Engine Cooldown Active N

    Engine Fuel LevelCritically High

    W

    Engine Fuel Level High W

    Engine Fuel Level Low W

    Engine Fuel Level Low S

    Engine Oil Level Low W

    Engine Oil Level Low S

    Engine Oil Pressure Low W NA

    Engine Oil Pressure Low S

    Engine Oil Pressure NoSignal

    S NA

    Engine Speed High S

    Engine Speed Low S

    Engine Start Aid Active N

    Engine Start Delay Active N

    Digital Output Level * 14/20 48

    Fuel Pressure Low W

    Fuel Spill N

    Fuel Tank Leak S

    Fuel Tank Leak W

    Generator Frequency High S

    Generator Frequency Low S

    Generator Running N

    Generator True TotalPower High

    S NA NA

    Generator Voltage L1--L2High

    S

    Generator Voltage L1--L2Low

    S

    Generator Voltage L2--L3High (3-phase only)

    S NA

    Generator Voltage L2--L3Low (3-phase only)

    S NA

    Generator Voltage L3--L1High (3-phase only)

    S NA

    Generator Voltage L3--L1Low (3-phase only)

    S NA

    Ground Fault Input W

    Load Priority1 Shed ** Status NA NA

    Load Priority2 Shed ** Status NA NA

    Load Priority3 Shed ** Status NA NA

    Load Priority4 Shed ** Status NA NA

    Load Priority5 Shed ** Status NA NA

    Load Priority6 Shed ** Status NA NA

    Locked Rotor S

    Low Fuel N

    Maximum AlternatorCurrent Low

    S NA NA

    Minor Fault N

    NFPA 110 Alarm Active N

    Not In Auto W

    Over Crank S

    Speed Sensor Fault S

    System Ready N

    * Level: N = Notice, S = Shutdown, W = Warning

    Indicates output is remotely controlled through OnCue

    Model RXT ATS required

    From a digital input

    Any of several conditions

    ** LCM required

    NA: Not applicable for these models

    Figure 17 Programmable Digital Outputs

  • TT-1584 2/12a 11

    PIM Status Menu on the RDC2

    Controller

    The RDC2 controller displays PIM input and output

    status in the menu shown in Figure 18. This is a status

    display menu only. Input and output settings cannot be

    changed from the RDC2 controllers user interface.

    Refer to the generator set Operation Manual for

    instructions to navigate the RDC2 menus, if necessary.

    tp6810

    PIMStatus:

    PIM 1 ---->

  • 12 TT-1584 2/12a

    OnCue Remote Monitoring and

    Control

    The Kohler OnCue Generator Management System

    can be used to monitor the PIM inputs and outputs with

    your PC or laptop computer. OnCue can also be used to

    remotely control PIM outputs 3 through 6 and to change

    the output labels in OnCues Power Chain view.

    Note: PIM outputs 1 and 2 are factory-set to Run and

    Common Fault They are controlled by the

    generator set and cannot be controlled remotely

    through OnCue.

    OnCue communicates with the PIM through the RDC2

    or DC2 controller on the generator set. See the

    generator set Installation Manual for instructions to

    connect the generator set to the Internet.

    The OnCue kit is available from Kohler authorized

    distributors and dealers. See TP-6796, OnCue

    Software Operation Manual, for instructions to use

    OnCue on a personal computer.

    Remote Control Example

    1. Connect output 3 to the storm shutters on your

    vacation home.

    2. Use OnCue to connect to the generator set

    controller and select the Power Chain view.

    3. Select Edit Mode in the toolbar at the top of the

    OnCue screen.

    4. On the picture of the the PIM, click on the label for

    output 3 and type in Storm Shutters.

    5. Select Control Mode in the toolbar at the top of the

    screen.

    6. On the picture of the the PIM, click on Storm

    Shutters to turn the output on or off. The status

    indicator flashes for about 5 seconds and then

    changes to show the new status: green for on or

    gray for off.

    When you click on an output in OnCues control mode,

    the event setting changes from its original setting to On

    or Off. The output can then only be controlled with

    OnCue. It will no longer be controlled by the generator

    set.

    Kohler SiteTech software can be used to set the

    outputs back to generator-controlled events, if

    necessary. SiteTech is available to Kohler-authorized

    distributors.

    1

    1. Edit mode and control mode selections

    2. PIM outputs for remote control

    2

    Figure 19 OnCue Power Chain View

  • TT-1584 2/12a 13

    TroubleshootingUse the flowcharts in Figure 20 through Figure 22 to

    diagnose problems with the PIM operation.

    Also see the next section, Verify that the Controller

    Recognizes the PIM.

    Check PIM outputstatus in controller

    menu. SeeFigure 18.

    Verify that only onePIM is connected.

    Online LED may have adefect but does not affect

    operation. Continuechecking functionality.

    Check communication A & Bconnections at:1) PIM2) Genset connectionterminal block

    Online LED Blinking

    NO

    YES

    NO NO

    NO

    NO

    NO

    YES

    YES

    YES

    YES

    YES

    YES

    YES

    NO

    PIM notresponding

    Power LEDSteady ON? *

    Online LEDSteady ON? *

    Verify correct versionof PC software is

    installed

    Device shown onSiteTech/OnCue?

    Verify I/O parametersare set up for desired

    functionality

    Number of errors andtimeouts steady?See Figure 25.

    PIM ID does notchange over time.

    LED blinking fasterthan once/second?

    Ensure the cable runs fromgenset to PIM are withinspecifications (cable size andlength)

    If problems persist, contactthe Kohler GeneratorService Department.

    Go to Figure 21.

    Go to Figure 22.

    * See Figure 4 for LED locations on the PIM circuit board.

    Figure 20 PIM Troubleshooting Chart, Part 1 of 3

  • 14 TT-1584 2/12a

    Is voltage lowbut not zero?

    Check the cable sizeand length to verifythey are within therange shown in

    Figure 8.

    Check for 10--16 VDCat the PWR and COMconnections on the

    generator set.

    Check the wire runfrom generator set to

    PIM.

    NONO

    YES

    YES

    Check voltage to thecontroller. See controllertroubleshootinginformation and wiringdiagrams in the generatorset service manual.

    Check connectionsfrom controller to

    customer connectionson generator set.YES

    Power LED may have adefect but does not affect

    operation. Continuechecking functionality.

    Voltage between10 and 16 VDC?

    Check power connection at:1) PIM2) Genset connectionterminal block3) Starting battery

    NO

    Power LEDis not lit

    Figure 21 PIM Troubleshooting, Part 2 of 3, Troubleshooting Power to the PIM

    Functions correctlyonly if connected

    individually.

    NO

    YESYES

    PIM functions correctlyonly after cycling power.

    If problems persist, contactthe Kohler GeneratorService Department.

    Disconnect RBUSmodules and verify thatSiteTech/OnCue showsno devices connected.

    Verify that the maximumnumber of allowed devices

    is not exceeded.

    Verify that each deviceserial number is different.

    NO

    YES

    YES

    YES

    YES

    Verify that the USB cableis not connected to

    generator controller duringpower cycles.

    Verify that all devices areseen by SiteTech afterindividual connection

    sequence.

    Figure 22 PIM Troubleshooting Chart, Part 3 of 3

  • TT-1584 2/12a 15

    Verify that the Controller Recognizes the PIM

    There are two ways to verify that the RDC2 controller

    recognizes the PIM.

    On the RDC2 controller, navigate to the Networking

    Menu and check the number of modules connected

    and the information for remote devices. See

    Figure 23 and Figure 24.

    For the RDC2 or DC2 controller, use a laptop

    computer connected to the controllers USB port and

    KohlerOnCue or SiteTech software to check that

    the PIM appears in the Power Chain view. See

    Figure 19. In the Parameters view, check that the

    RBUS network screen shows the correct number of

    RBUS devices connected (RXT transfer switch, PIM,

    and LCM, if used). See Figure 25.

    tp6804

    Modules Connected:3

    Module Timeouts:1234

    Net Cycle Time:123ms

    Module Errors:1234

    < ---- Return

    RDRemote ---->Devices

    See Figure 24.

    Networking---->

    Information

    Networking---->

    Status

    RBUS ---->Information

    Configuration

    Figure 23 RDC2 Controller Menu, Networking Information

  • 16 TT-1584 2/12a

    tp6810

    Device Status:Connected

    RD

    Firmware Ver.:122

    ModBus ID:12

    S/N: XXXXXXXXX

    Return ---->

    S/N: XXXXXXXXX

    Comm. Errors:12345

    Comm. Timeouts:12345

    ...

    Connected:MM/DD/YY 12:12

  • TT-1584 2/12a 17

    Figure 25 RBUS Device Parameters in OnCue or SiteTech

    Parts List

    Programmable Interface Module (PIM)

    Kit: GM81529-KP1-QS

    Qty. Description Part Number

    1 PIM, Assy NEMA 3R GM81529-1

    1 Installation Instructions TT-1584

    Diagrams and Drawings

    The PIM dimension drawing, wiring diagram, and

    schematic are shown on the following pages.

  • 18 TT-1584 2/12a

    Figure 26 Dimension Drawing ADV-8199

  • TT-1584 2/12a 19

    Figure 27 Wiring Diagram, GM84085

  • 20 TT-1584 2/12a

    Figure 28 Schematic Diagram, GM84086