EN LC 502 control unit for ProFlex progressive centralized lubrication systems 1 2 3 Version 02 Operating instructions

LC 502 control unit for ProFlex EN perating instructions ... · Press “arrow key left ... Pro Flex Mono Flex Duo Flex Line 1 Line 2 Input 1 Input 2 Input 3 Disabled CycCount MCCount

  • Upload
    others

  • View
    5

  • Download
    0

Embed Size (px)

Citation preview

Page 1: LC 502 control unit for ProFlex EN perating instructions ... · Press “arrow key left ... Pro Flex Mono Flex Duo Flex Line 1 Line 2 Input 1 Input 2 Input 3 Disabled CycCount MCCount

ENLC 502 control unit for ProFlex progressive centralized lubrication systems

1

2

3

Version 02

Operating instructions

Page 2: LC 502 control unit for ProFlex EN perating instructions ... · Press “arrow key left ... Pro Flex Mono Flex Duo Flex Line 1 Line 2 Input 1 Input 2 Input 3 Disabled CycCount MCCount

Page 2 EN

Table of contents

1. Display and control elements of control screen 3

1.1 LC502 control screen 3

2. Display and operating menu 5

2.1 Base menu 5

2.1.1 Main menu 5

2.2 Info -Information mode 6

2.3 Conig.-Conigurationmode 83. Menu structure 10

3.1 Menu structure of Info 10

3.2 MenustructureofConigurations 11 3.3 MenustructureofConigurations- Edit(standardprogramming) 12 3.4 Menu structure of Status 13

4. LC502- Factory settings on a progressive

centralized lubrication system 14

4.1 Generaldesignofaprogressive centralized lubrication system 14

4.1.2Systemdesign 14 4.2 Generalsysteminputsonaprogressive centralized lubrication system 15

4.3.1 Control inputs 17

4.3 FactoryassignmentofLC502control inputs 17

4.4 Generalsystemoutputsonaprogressive centralizedlubricationsystem 18 4.5 FactoryassignmentofLC502control outputs 20

4.5.1 Control outputs 20

5. Options for customer adjustment 20

5.1 Coniguringthepausetimes,runtimes, and dwell times 20

5.2 Numberoftrialattempts(enabling blockmode) 23 5.3 Limitingandmonitoringthepump usingacycleswitch 24 5.4 Specifyingtheruntimelimitationthrough numberofagitatorrotations 26 5.5 Additionaloptionalsettings(menudisplay dependingonpumpconiguration) 286. Options for customer adjustment of a

progressive centralized lubrication

system with two main lines 30

7. Status display 31

7.1 Status-Displayofcurrentdevicestatus 31 7.2 Lub - Runtimes of lubrication process 32

7.3 Readingtheenabledinputs 32 7.4 Read error times of lubrication process 36

7.5 Read electrical states of inputs and outputs 37

7.6 Read connection states of inputs and outputs 38 7.7 Readambienttemperatureonthe control unit 39

8. Basic settings 40

8.1 Basicinitializationofcontrolunit 40 8.2 Controlunitresetfunction 41 8.3 Resettheuserpassword 42

9. Control ports 43

9.1 KFGL 43

9.1.1KFGLpumpforindustrialapplications, 43 9.1.2KFGLpumpwithgreasefollowerplate, 44 9.1.3 KFGL pump for industrial applications orwithgreasefollowerplate 45 9.1.4KFGLpumpforvehiclelubrication 4610. Operational and pump faults 47

10.1 Operational malfunctions 47

10.2 System errors 47

10.3 Display errors 47

10.4 Deleteerrornotiication 47 10.5 Errortypes 48 10.6Errornotiication 4911. LC502 menu displays 51

12. Technical data for LC502 control unit 57

12.1 BasicsettingsofLC502 57

Page 3: LC 502 control unit for ProFlex EN perating instructions ... · Press “arrow key left ... Pro Flex Mono Flex Duo Flex Line 1 Line 2 Input 1 Input 2 Input 3 Disabled CycCount MCCount

Page 3 EN

1. Display and control elements of control screen

1.1 LC502 control screen

The display and control unit is protected from water splashes and mechanical damage by a transparent plastic cover. The cover must be removed to program the unit and then remounted afterwards.

LC502 control screen

1

2

3

Display and control elements of control screen

Drawing Description Function

Display Menu display Displays values and parameters Error notification

Error LED Displays fault notification Red LED flashes = error detected Red LED lights up = fault on a signal input, no error detected on pump control unit (error is outside pump)

PAUSE LED Indicates pause time Yellow LED lights up = active pump pause time on at least one main line

CONTACT LED Indicates contact time (pump operation) Green LED lights up = active pump runtime

1 = Output 1 2 = Output 2

Indicates pump output 1 to 2 LED on output 1 or 2 lights up = pump output 1 or 2 is switched on. Lubricant is delivered via the indicated line (1 or 2)

3 = Inputs Indicates all signal inputs LED lights up = signal change on input port The LED lights up for approx. 1 second each time the signal on the input port changes.

ENTER key Confirm selection Confirm entry and values

2

1

3

1. Display and control elements of control screen

General notes in documentation

Note

Prompts an action Usedforitemizing Providesadditionalinformation

Page 4: LC 502 control unit for ProFlex EN perating instructions ... · Press “arrow key left ... Pro Flex Mono Flex Duo Flex Line 1 Line 2 Input 1 Input 2 Input 3 Disabled CycCount MCCount

Page 4 EN

Display and control elements of control screen

Drawing Description Function

Operator keys Operator keys Go to menu selection (navigation) Edit numerical values

Operator keys Operator keys for menu selection (navigation)(arrow key up/down/left)Go to the selected menu based on direction of arrow

Operator keys for changing numerical values(arrow key up/down) The numerical value is incremented/decremented based on direction of arrow.Press <arrow key right> or <arrow key left> to move the cursor position to the adjacent digit. To exit the editor window without saving the current change, press the key again after reaching the last digit.

Pressing <arrow key up> increments the selected digit by one.Pressing <arrow key down> decrements the selected digit by one.The input value for seconds and minutes can be between 0 and 59; a value between 0 and 65535 can be programmed for hours.

Operator key for editing numerical values(arrow key right) Pressing the key moves the cursor one position to the right. If the cursor is on the right edge, the edit window closes and the changes are discarded.

DK key Pressing triggers an interim lubrication. Error notifications are acknowledged and deleted Actuations while in configuration mode are ignored.

1. Display and control elements of control screen

Page 5: LC 502 control unit for ProFlex EN perating instructions ... · Press “arrow key left ... Pro Flex Mono Flex Duo Flex Line 1 Line 2 Input 1 Input 2 Input 3 Disabled CycCount MCCount

Page 5 EN

1

2

3

1

2

3

Device display - Base menu

2.1 Base menu

The control unit's display has three rows of eight characters each. Only three options are shown in menu windows containing more than three available choices. Press the <up/down> arrow keys to access further options.

Configure a setting on the device involves con-secutively opening multiple menu windows. The current device setting is then stored with a black mark.

Not all possible options are displayed in the settings. Only settings that are available and permitted for the selected device type (ProFlex, MonoFlex, or DuoFlex) and the current device settings are shown.

The first menu level shows language selection. The language that is currently selected flashes. Upon confirmation, the main menu will be dis-played in the selected language.

2. Display and operating menu

2.1.1 Main menu

Device display - Main menu

The main menu shows the following options: Device-specific information Device configuration Status information

Note

TheServicemenuselectionispass-word-protected and can only be

accessed by SKF employees.

2. Display and operating menu

Page 6: LC 502 control unit for ProFlex EN perating instructions ... · Press “arrow key left ... Pro Flex Mono Flex Duo Flex Line 1 Line 2 Input 1 Input 2 Input 3 Disabled CycCount MCCount

Page 6 EN

Base and main menu

Step Key Display Description

1 Entry mask/language selectionThe German version is active by default (flashing).Press the <arrow key up> to switch to the English version. Press the Enter key to confirm.

2 Main menu

Service

English

Deutsch

Info

Conig

Status

Main menu items

Display Description

Info Displaydevice-speciicdatasuchasserialnumberorirmwareConfig.uration ParameterconigurationStatus Display current status of control unit

Service ServicemenuMenulevelonlyenabledforSKFservicepersonnel

2. Display and operating menu

2.2 Info - Information mode

Information mode is used to query the hard-ware identification code and the runtimes stored thus far for the system, motor, and err time (system runtime, motor runtime, error time).

Note

No values can be entered or modiied in information mode.

Selection in information mode is per-formed by briely pressing one of the

keys.

Display

1

2

3

Page 7: LC 502 control unit for ProFlex EN perating instructions ... · Press “arrow key left ... Pro Flex Mono Flex Duo Flex Line 1 Line 2 Input 1 Input 2 Input 3 Disabled CycCount MCCount

Page 7 EN2. Display and operating menu

Information mode

Step Key Display Description

1 Entry mask/language selectionThe German version is active by default (flashing).Press “arrow key up” to switch to the English version. Press the ENTER key.

2 Main menuPress the ENTER key to go to the Info menu.

3 Info menu

You can switch between menu items using <arrow key up> and <arrow key down>.

Press the ENTER key to go to the selected sub-menu.

Press the ENTER key.

4 Serial Each control unit has an assigned serial number that can be viewed by pressing the ENTER key.Firmware This is the current version number of the software and can be viewed by pressing the ENTER key.Sys time This displays the total running time (on-time) of the control unit in hours, minutes, and seconds. Mot time This displays the total runtime of the pump motor in hours, minutes, and seconds. Err timeThis displays the total time of the current error (if present). If there is no error, the aggregate time of all detected errors is displayed.

Press the <arrow key left> to return to the main menu. Press <arrow key left>.

Mot time

Err time

English

Deutsch

Info

Conig

Status

Serial

Firmware

Sys time

Sys time

ØØØØØhØØm ØØs

Mot time

ØØØØØhØØm ØØs

Err time

ØØØØØhØØm ØØs

Page 8: LC 502 control unit for ProFlex EN perating instructions ... · Press “arrow key left ... Pro Flex Mono Flex Duo Flex Line 1 Line 2 Input 1 Input 2 Input 3 Disabled CycCount MCCount

Page 8 EN

2.3 Conig. - Coniguration mode

Configuration mode is started by selecting <Config.> in the main menu and pressing the ENTER key. The system first queries whether you want to edit or simply view the configura-tion data. The password will be queried if you want to modify the configuration data.

Note

Afterenteringthecorrectpassword,allcurrentlyrunninglubricationproce-

duresarestoppedandtheconigurationmode starts.

If the configuration data will be viewed and not modified, the Config. menu will appear upon confirmation by pressing the ENTER key. No changes can be made in this mode.

Selection in coniguration mode is performed by briely pressing one of the

keys.

2. Display and operating menu

Configuration menu, Table 1 of 2

Step Key Display Description

1 Entry mask/language selection

The German version is active by default (flashing).Press “arrow key up” to switch to the English version. Press the ENTER key.

2 Main menu

Select “Config.” using the arrow key. Press the ENTER key to enter the Config. menu.

3 Config. menu

ViewPress the ENTER key to enter the configuration menus. There, you can access configurations for:

System Settings Inputs Outputs The configuration or selection that is currently

active flashes.No entries or changes can be made in display mode.

English

Deutsch

Info

Conig

Status

View

Edit

Page 9: LC 502 control unit for ProFlex EN perating instructions ... · Press “arrow key left ... Pro Flex Mono Flex Duo Flex Line 1 Line 2 Input 1 Input 2 Input 3 Disabled CycCount MCCount

Page 9 EN2. Display and operating menu

Configuration menu, Table 2 of 2

Step Key Display Description

4 Edit Press the ENTER key to enter the password prompt menu. Press the ENTER key.

5 Password menu

The following password prompt prevents modifications by unauthorized persons. Press <arrow key up> to increment the number by 1, up to 9. Press <arrow key down> to decrement the number by 1, down to 0. Press <arrow key right> to move to the next password number (max. 7). Press the ENTER key. Press the ENTER key to enable the following Config. menus.

or: Press “arrow key left” to cancel entry and return to the main menu.

6 Configuration sub-menu selection

Press the ENTER key to enter the Config. menu.

Password

00000000

New Pwd

Outputs

Default

Reset

System

Settings

Inputs

ViewEdit

Page 10: LC 502 control unit for ProFlex EN perating instructions ... · Press “arrow key left ... Pro Flex Mono Flex Duo Flex Line 1 Line 2 Input 1 Input 2 Input 3 Disabled CycCount MCCount

Page 10 EN

3. Menu structure

3.1 Menu structure of Info

3. Menu structure

InfoConfig.Status

Service

1

23

English

Deutsch

SerialFirmwareSys time

Mot timeErr time

Sys timeØØØØØhØØm ØØ s

ØØØ-ØØØ-ØØØ-LØv1.Ø.a.1

ØØØØØØØØØØØØ

Mot timeØØØØØhØØm ØØ s

Err timeØØØØØhØØm ØØ s

Page 11: LC 502 control unit for ProFlex EN perating instructions ... · Press “arrow key left ... Pro Flex Mono Flex Duo Flex Line 1 Line 2 Input 1 Input 2 Input 3 Disabled CycCount MCCount

Page 11 EN

InfoConfig.Status

Service

1

23

English

Deutsch

ViewEdit

SystemSettingsInputs

Outputs

Pro FlexMono FlexDuo Flex

Line 1Line 2

Input 1Input 2Input 3

DisabledCycCountMCCount.

Level SWExtern DKExtDelay

Input 4

ExtStop

Output 1Output 2ErrorOut

FunctionPolarityDisabled

Valves

N OpenN Closed

TimeTrialsValves

PauseRuntime

PauseØØØØØhØØm ØØs

Line 1 (2)TrialsØØØØØ

Runtime ØØØØØhØØm ØØs

AgitatorMechanicAnalogue

Capacit.

N OpenN Closed

Output 1 (2)

NoneMCCount.2

Line 1 (2)MCCount.2ØØØØØ

MCNumberCyclesDelayer

Input 1 (2-4)MonitorImm. StopCol. Stop

Line 1 (2)Input 1 (2-4)ØØØØØ

ExtStop

NoneInput 1 (2-4)

FunctionType 1)Polarity 2)

N OpenN Closed

3.2 Menu structure of Conigurations - View

3. Menu structure

1) The <Type> display menu is only shown (enabled) when the fill level indicator <Level SW> is activated.

2) The <Polarity> display menu is only shown (enabled) when the following are activated:

On the monitoring devices' inputs: 1. Extension delay <ExtDelay>

2. Stopper <ExtStop>, on outputs: 1. Valves <Valve>

Page 12: LC 502 control unit for ProFlex EN perating instructions ... · Press “arrow key left ... Pro Flex Mono Flex Duo Flex Line 1 Line 2 Input 1 Input 2 Input 3 Disabled CycCount MCCount

Page 12 EN

3.3 Menu structure of Conigurations - Edit (standard programming)

Counter-machine contact

Passwort ØØØØØØØØ

CancelSpeiche.

InfoConfig.Status

Service

1

23

English

Deutsch

ViewEdit

SystemSettingsInputs

OutputsDefaultReset

Pro Flex

Mono FlexDuo Flex

Line 1

Strang 2

TimeTrialsCycles

PauseØØØØØhØØm ØØs

Line 1 (2)TrialsØØØØØ

Line 1 (2)Input 1 (2)ØØØØØ

RotationMCNumberDelayer

Input 1Input 2

Stopper

NoneInput 2

Neue Pwd

CancelSpeiche.

ResetØØØØØØØØ

Dwell

Pause2ØØØØØhØØm ØØs

DwellØØØØØhØØm ØØs

Block mode

MonitorSof. stopWar. stop

Input 4Mon + StopImm. stop

Line 1 (2)Input 4 ØØØØØ

Strang 1 (2)MCCount 2 ØØØØØ

Cycle switch

Agitator rotations

Options for customer adjustment

Delayer= Pause time extensionStopper = Error input

Hours of operation

Runtime ØØØØØhØØm ØØs

PauseRuntimePause 2

NoneMCCount 2

3. Menu structure

Page 13: LC 502 control unit for ProFlex EN perating instructions ... · Press “arrow key left ... Pro Flex Mono Flex Duo Flex Line 1 Line 2 Input 1 Input 2 Input 3 Disabled CycCount MCCount

Page 13 EN

3.4 Menu structure of Status

3) For a list of possible fault signals <Errors>, see Chapter 5, Operational and pump faults.

3. Menu structure

LubErrorsIO State

IO Conn.Temp.

Line 1LubtimeInputs

Lubetime/Pause ØØØØØhØØm ØØs

Input 1Input 2Input 3

Input 4

None3)

1 2 3 4 M 1 20 0 0 0 0 0 0

1 2 3 4 M 1 2

Temp.23°C

InfoConfig.Status

Service

1

23

English

Deutsch

CyclesEX ØRC Ø

����� ������ ���

MCNumberEX ØRC Ø

Machine contact counter menu

RotationEX ØRC Ø

Level SW menu

Extern DK

Ø

External pressure switch menu

ExtDelay

Ø

Pause delay time menu

ExtStop

Ø

Stop input menu

Page 14: LC 502 control unit for ProFlex EN perating instructions ... · Press “arrow key left ... Pro Flex Mono Flex Duo Flex Line 1 Line 2 Input 1 Input 2 Input 3 Disabled CycCount MCCount

Page 14 EN4. LC502- Factory settings on a progressive centralized lubrication system

4. LC502- Factory settings on a progressive centralized lubrication system

1

2

3

4.1 General design of a progressive

centralized lubrication system

7

9

10

6

43

2

1

Progressive system with cycle switch

1 KFGL unit 6 Fault indicator light 11 Lubrication lines

2 Pump element with pres-sure regulating valve

7

Main lines12 Two-way distributor

(179-990-700)3

LC502 display8

Master distributor4 Connector plug for

inputs, outputs, and monitoring

9

cycle switch

5 Power supply 10 Secondary distributor

5

8

10

11Thefollowingdescriptionappliestoaprogressivecentralizedlubricationsystemforindustrialusewithone main

line(mainline1). Fill level monitoring is performed by a mechanical ill level switch <Agitator>; this system version is therefore only suitable for greases up to NLGI Grade 2.

12A B

4.1.2 System design

A main lubrication line (7) leads from the pump element (2) to the master distributor (8). From there, secondary lubrication lines lead to both secondary distributors (10). The second-ary distributors are connected to the lubrication points by lubrication lines (11). The pump fill level is monitored by a pump-side mechanical fill level switch <Agitator>; the main line is monitored by a cycle switch (9). Error notifications can be shown via an external indicator lamp (6).

Page 15: LC 502 control unit for ProFlex EN perating instructions ... · Press “arrow key left ... Pro Flex Mono Flex Duo Flex Line 1 Line 2 Input 1 Input 2 Input 3 Disabled CycCount MCCount

Page 15 EN

4.2 General system inputs on a progressive centralized lubrication system

Requirement: The Configuration menu was pre-selected in the Main menu.

4. LC502- Factory settings on a progressive centralized lubrication system

System inputs, Table 1 of 2

Step Key Display Description

1 Select inputs 1 to 4

The Inputs configuration menu is already selected. Press the ENTER key; you will then enter the following Input menu Press the ENTER key; you will then enter the following Input 1 menu

or: You can switch the input menus between input 1 to input 4 using the <arrow keys up/down>. Select input 2, input 3, or input 4 using <arrow key down>.

Press the ENTER key. You will then enter the following Function menu.

The types of monitoring and functions that can be assigned to inputs 1 to 4 are listed in the follow-ing Function menu. By default, the inputs and their function are configured as described in Chapter 4.3, Factory assignment of LC502 control inputs. Input 1 => <CycCount>, Input 2 => <Disabled>Input 3 => <External DK>Input 4 => <Level SW>, type <Agitator>.

Inputs

OutputsDefault

Input 4

Input 1

Input 2

Input 3

Function

TypePolarity

1

2

3

Page 16: LC 502 control unit for ProFlex EN perating instructions ... · Press “arrow key left ... Pro Flex Mono Flex Duo Flex Line 1 Line 2 Input 1 Input 2 Input 3 Disabled CycCount MCCount

Page 16 EN

System inputs, Table 2 of 2

Step Key Display Description

2 Assign a function to the selected input

The following are available for selection:Disabled = No monitoring system enabledCycCounter = Cycle switch (on distributor, counts the number of completed cycles)MCCounter = Machine contact counter (external counter)Level SW = Pump fill level monitoring (pump reservoir)Extern DK = External pressure switch for interim lubricationExtension delay = Function of an input as pause time extension inputExtStop = Error input (function selection and assignment for the main line that will be stopped in the event of an error)

Press <arrow key up/down> to assign the function to the selected input. Press the ENTER key. Press <arrow key left> to exit the menu. After making a selection, you will return to the Function menu. Depending on the input assignment, the

Type, Polarity, and p-Active menu items will be enabled in addition to the Function menu item.

2.1 Assign the <Type> switch type and function <Polarity> to the assigned input

You will return to the Function menu. Depending on the function assignment (Step 2), the following are available:

Function Type Polarity Disabled - -CycCount -MC Counter - -Level SW Agitator Agitator rotations (W1) - Mechanic Mechanical fill level switch N Open/N Closed Capacitive Capacitive fill level switch - Analogue Analog fill level switch, 0-100% display, 8 levels -ExternDK - -ExtDelay - N Open/N ClosedExtStop - N Open/N Closed

Disabled

CycCount

MC Count

Level SW

Extern DK

ExtDelay

ExtStop

Analogue

Agitator

MechanicCapacit.

FunctionType

Polarity

4. LC502- Factory settings on a progressive centralized lubrication system

Page 17: LC 502 control unit for ProFlex EN perating instructions ... · Press “arrow key left ... Pro Flex Mono Flex Duo Flex Line 1 Line 2 Input 1 Input 2 Input 3 Disabled CycCount MCCount

Page 17 EN

4.3.1 Control inputs

The ProFlex standard pump contains a maxi-mum of 4 control inputs. By default, they are assigned as follows:

Input 1

Functional monitoring of the main line by

cycle switch

The main line is monitored by a cycle switch (<CycCount> attached to the master distribu-tor. This switch transmits movement of the distributor piston during the pump runtime <Runtime> to the LC502 control unit as a number of cycles. The LC502 control unit compares the received (counted) cycles <RX> to the expected (programmed) cycles <EX>. If the received cycles are attained in a pre-pro-grammed pump runtime <Runtime>, the pump switches off and enters the pro-grammed pause time <Pause>. <Input 1> => <Function> <CycCount>

Input 2

-Cycle Counter 2

This input is used for the cycle switch in main line 2 on systems with two main lines. <Input 2> => <Disabled>

Input 3

External DK (pressure switch)

External pressure switches can be used to trigger a custom interim lubrication indepen-dent of the LC502's settings. <Input 3> => <External DK>

Input 4

Fill level monitoring of pump reservoir

A fill level switch (W1) on the agitator can con-trol and monitor the pumps. This switch counts the rotations of the agitator and sends this information to the control unit. This allows the pump runtime to be ended after the pre-set number of rotations is achieved. On pro-gressive centralized lubrication systems, this switch is used to monitor the fill level of the lubricant. <Input 4> => <Function> => <Level SW>, type <Agitator>

4.3 Factory assignment of LC502 control inputs

4. LC502- Factory settings on a progressive centralized lubrication system

Page 18: LC 502 control unit for ProFlex EN perating instructions ... · Press “arrow key left ... Pro Flex Mono Flex Duo Flex Line 1 Line 2 Input 1 Input 2 Input 3 Disabled CycCount MCCount

Page 18 EN

System outputs, Table 1 of 2

Step Key Display Description

1 Select outputs 1 to 2

Select outputs using <arrow key down>. Press the ENTER key; you will then enter the following outputs menu

You can switch the output menus between output 1, output 2, or error output using <arrow keys up/down>.

Select between output 1 and output 2 using <arrow keys up/down>.

Note The error output has a different menu structure than outputs 1 and 2. This is described in Step 3.

Press the ENTER key; you will then enter the following Function menu

The outputs are enabled or disabled (valve switching) in the following Function menu.After making a selection, you will return to the Function menu. If a valve has been assigned to the out-put, an additional menu item, <Polarity>, is added below the <Function> menu item.This setting is described in Step 2.1 (Polarity). By default, output 1 and output 2 on a ProFlex centralized lubrication system with one main line are switched to <Disabled>. On a system with two main lines, the outputs are assigned to valve 1 and valve 2.

4.4 General system outputs on a progressive centralized lubrication system

Inputs

Outputs

Default

Output 1

Output 2

ErrorOut

Function

Polarity

Requirement: The Configuration menu was pre-selected in the Config menu.

4. LC502- Factory settings on a progressive centralized lubrication system

1

2

3

Page 19: LC 502 control unit for ProFlex EN perating instructions ... · Press “arrow key left ... Pro Flex Mono Flex Duo Flex Line 1 Line 2 Input 1 Input 2 Input 3 Disabled CycCount MCCount

Page 19 EN

System outputs, Table 2 of 2

Step Key Display Description

2 Activating the changeover valve, output 1/output 2

You will enter the menu for activating the changeover valve.The following are available for selection:

Disabled = No changeover valve connection, valve is not enabled Valve = Enable the changeover valve Select the menu item using <arrow keys up/down>. Press the ENTER key to confirm the selection. Press <arrow key left> to exit the menu.

2.1 Polarity of the changeover valve

Select Polarity using <arrow key down>. Press the ENTER key to confirm the input.

You will enter the N Open/N Closed menu.The following are available for selection:

N Open = Make function in which the contact closes when the switching point is reached. N Closed = Break function in which the contact opens when the switching point is reached. Select the type using <arrow keys up/down>. Press the ENTER key to confirm the selection. Press <arrow key left> to exit the menu.

3 Select the error output

Select Error Output using <arrow key down>. Press the ENTER key; you will then enter the following Error Output-N Open/N Closed menu Choose between make function and break function using <arrow keys up/down>. Press the ENTER key to confirm the selection. Press <arrow key left> to exit the menu.

You will return to the previous selection menu.

Function

Polarity

N Open

N Closed

Disabled

Valve

Output 1

Output 2

ErrorOutN Closed

N Open

4. LC502- Factory settings on a progressive centralized lubrication system

Page 20: LC 502 control unit for ProFlex EN perating instructions ... · Press “arrow key left ... Pro Flex Mono Flex Duo Flex Line 1 Line 2 Input 1 Input 2 Input 3 Disabled CycCount MCCount

Page 20 EN

5. Options for customer adjustment

5.1 Coniguring the pause times, runtimes, and dwell times

Requirement: The Configuration menu was pre-selected in the

Config menu.

4. LC502- Factory settings on a progressive centralized lubrication system / 5. Options for customer adjustment

4.5 Factory assignment of LC502 control

outputs

4.5.1 Control outputs

The ProFlex standard pump contains a maxi-mum of 2 control outputs. plus an error out-put for triggering a possible fault signal. By default, they are assigned as follows: Output 1 and Output 2 = Disabled

On a system with two main lines, a change-over valve is assigned to each of the two out-puts for pressure build-up/pressure relief of line 1 and line 2. Error Output = N Closed

If an error is present, an output signal is is-sued to an external evaluation device/display via this error output. The output is programmed as a normally closed contact.

<Pause> stands for the programmed pause time of the control unit for a full cycle. During this time, the pump does not feed any lubri-cant. <Runtime> stands for the programmed pump runtime for a cycle. During this time, the pump feeds lubricant. After the pause time elapses, the pump run-time starts again.

Both menu items are only enabled

when a value has been entered

in the menu <Trials> (block mode).

<Pause2> stands for the pause time in block mode. It is the time between runtime and dwell time as well as between the dwell intervals.

<Dwell time> If a pump dwell time has been programmed, once the runtime elapses and in the absence of cycles the control unit enters pause time 2 <Pause2> and then the dwell time. The pump continues to feed until the dwell time ends. Thereafter, the control unit returns to pause time 2. After this time elaps-es, it returns to dwell time (when <Trials> = 2). If the pump receives the outstanding cycles in the interim, the control unit immediately en-ters the regular pause time <Pause>.

Block mode<Pause2> <Dwell time>

1

2

3

Page 21: LC 502 control unit for ProFlex EN perating instructions ... · Press “arrow key left ... Pro Flex Mono Flex Duo Flex Line 1 Line 2 Input 1 Input 2 Input 3 Disabled CycCount MCCount

Page 21 EN5. Options for customer adjustment

Pause times, runtimes, and dwell times, Table 1 of 2

Step Key Display Description

1 Select the <Line1> main line Select the Settings menu item using <arrow key down>.

Press the ENTER key; you will then enter the following parameter adjustment menu main line 1

In a system with two main lines, an additional menu item for <Line 2> is available for selection. Its menus are structured identically to Line 1 described below.

2 Enter the parameters for system times <Time>

The Time parameter menu is already selected. Press the ENTER key; you will then enter the following Time menu

3 Configure the pause time

<Pause> stands for the pause time; <Runtime> stands for the pump runtime.If the system is configured for Trials (step 5)= block mode, an additional pause time <Pause 2> and dwell time <Dwell> are shown, the times for trial = block mode.

The Pause parameter menu is already selected.

Press the ENTER key; you will then enter the following Pause menu

A pause time of 1 hour is set by default.

Enter pause time using numerical pad

Press the ENTER key to confirm the input and exit the edit window. Go to the end of the line using <arrow key right> or <arrow key left> then press the arrow key again

to exit the menu (even without applying the change).

SystemSettings

InputsLine 1

Line 2

Rotation

Time

TrialsCycles

Pause

Runtime

Pause2

Pause

ØØØØØhØØm ØØs

Page 22: LC 502 control unit for ProFlex EN perating instructions ... · Press “arrow key left ... Pro Flex Mono Flex Duo Flex Line 1 Line 2 Input 1 Input 2 Input 3 Disabled CycCount MCCount

Page 22 EN

Pause times, runtimes, and dwell times, Table 1 of 2

Step Key Display Description

4

Configure the runtime

Press the ENTER key; you will then enter the following Runtime menu

A runtime of 4 minutes is set by default.

Enter runtime using numerical pad

Press the ENTER key to confirm the input and exit the edit window. Go to the end of the line using <arrow key right> or <arrow key left> then press the arrow key again to

exit the menu (even without applying the change).

5 Configure Pause2 (pause time in block mode)

If the system is configured for Trials = block mode, an additional pause time <Pause 2> and dwell time <Dwell> are shown, the times for trial = block mode.

A pause time 2 of 15 minutes is set by default.

Press the ENTER key to confirm the input and exit the edit window. Go to the end of the line using <arrow key right> or <arrow key left> then press the arrow key again to

exit the menu (even without applying the change).

6 Configure the Dwell time (runtime in block mode)

A dwell time of 4 minutes is set by default.

Press the ENTER key to confirm the input and exit the edit window.

Go to the end of the line using <arrow key right> or <arrow key left> then press the arrow key again to exit the menu (even without applying the change).

Pause

Runtime

Pause2

Pause

Runtime

Pause2

Pause2

ØØØØØhØØm ØØs

Runtime

ØØØØØhØØm ØØs

Pause

Runtime

Pause2Dwell

Dwell time

ØØØØØhØØm ØØs

5. Options for customer adjustment

Page 23: LC 502 control unit for ProFlex EN perating instructions ... · Press “arrow key left ... Pro Flex Mono Flex Duo Flex Line 1 Line 2 Input 1 Input 2 Input 3 Disabled CycCount MCCount

Page 23 EN5. Options for customer adjustment

5.2 Number of trial attempts (enabling block mode)

Requirement: The Configuration menu was pre-selected in the Config menu.

If the system is configured for Trials => Block mode, the menu Pause times, run times, and dwell times(Chapter5.1) will show an additional pause time <Pause 2> and dwell time <Dwell>, the setting times for trials = block mode.

In the Trials menu items, only the number of trial attempts is entered for the event that there are outstanding cycles once the actual pump runtime elapses. Block mode ensures that lubrication continues to be performed in the absence of a cycle signal. This is set via the menu items Pause2 and Dwell and for a time until the corresponding number of cycles has been reached or the number of trials has been worked through.

Number of trial attempts

Step Key Display Description

1 Select the <Line1> main line Select the Settings menu item using <arrow key

down>.

Press the ENTER key; you will then enter the following parameter adjustment menu main line 1

In a system with two main lines, an additional menu item for <Line 2> is available for selection. Its menus are structured identically to Line 1 described below.

2 Configure the number of trial attempts for Pause2 and Dwell (block mode)

Select the Trials menu item using <arrow key down>.

Enter the input value (number of trials) using <arrow keys> Press the ENTER key to confirm the input. Go to the end of the line using <arrow key

right> or <arrow key left> then press the arrow key again to exit the menu.

SystemSettings

InputsLine 1

Line 2

Time

Trials

CyclesLine 1

Trials

ØØØØØ

1

2

3

Page 24: LC 502 control unit for ProFlex EN perating instructions ... · Press “arrow key left ... Pro Flex Mono Flex Duo Flex Line 1 Line 2 Input 1 Input 2 Input 3 Disabled CycCount MCCount

Page 24 EN

5.3 Limiting and monitoring the pump using a cycle switch

Requirement: The Configuration menu was pre-selected in the Config menu.

By default, the centralized lubrication system is monitored by one or more cycle switches. This is usually attached to the main distributor and transmits the number of delivery strokes performed to the LC502. The cycles are evalu-ated via the <Monitor> menu or alternately via the <Imm. Stop> or <Col. Stop> menu. The menu <Monitor> is enabled by default. Here, the number of cycles that must be attained during the pump runtime is specified. If block mode is enabled (see Chapter 5.2) and the target value is not achieved during the pump runtime, the block mode is enabled using <Pause2> and <Dwell time>. A report is gen-erated if cycles are missing at the end of the runtime and (if applicable) block mode.

Enter and enable lubricating cycles, Table 1 of 2

Step Key Display Description

1 Select the <Line1> main line Select the Settings menu item using <arrow key

down>.

Press the ENTER key; you will then enter the following parameter adjustment menu main line 1

In a system with two main lines, an additional menu item for <Line 2> is available for selection. Its menus are structured identically to Line 1 described below.

2 Configure the cycle times

Select the Cycles menu item using <arrow key down>. Press the ENTER key to confirm the input. You will enter the Input menu.

By default, input 1 is line 1; on a system with two main lines, line 2 = input 2 At input selection, select the input menu using

<arrow key up/down>. Press the ENTER key to confirm the selection.

SystemSettings

InputsLine 1

Line 2

Time

Trials

Cycles

Input 1..4

5. Options for customer adjustment

1

2

3

Page 25: LC 502 control unit for ProFlex EN perating instructions ... · Press “arrow key left ... Pro Flex Mono Flex Duo Flex Line 1 Line 2 Input 1 Input 2 Input 3 Disabled CycCount MCCount

Page 25 EN

Enter and enable lubricating cycles, Table 2 of 2

Step Key Display Description

3

+

You will enter the Monitor / Imm. Stop / Col. Stop. menu for example for input 1; assigned by default for cycle switch.

By default, Monitor, =Entry of number of cycles to be monitored, is enabled

Monitor = Entry of the number of cycles to be monitored in the pump runtime. A report is generated if cycles are missing at the end of the runtime and (if applicable) block mode.

Select Monitor using <arrow key down>. Press the ENTER key; you will then enter the selected menu Enter the input value using <arrow keys up/down>

Alternately, the Imm. Stop or Col. Stop menu items can be enabled instead of <Monitor>.

Immediate Stop (only enabled when multiple cycle switches are used for each main line)Enter the number of cycles that causes an immediate stop of the main line once the first set value is attained. Missing cycles on other inputs (cycle switches) are ignored, i.e. no error is generated if cycles are missing on other inputs.

Collective Stop: (only enabled when multiple cycle switches are used for each main line)The main line will be stopped once the last set value is attained.

Select <Monitor>, <Imm. Stop>, or <Col. Stop> using the <arrow key up/down> Press the ENTER key; you will then enter the selected menu Enter the input value using <arrow keys up/down> Press the ENTER key to confirm the input. Press <arrow key right/left> to exit the menu.

Monitor

Imm. Stop

Col. Stop

Imm. Stop

Col. Stop

Line 1

Input 1

ØØØØ

5. Options for customer adjustment

Page 26: LC 502 control unit for ProFlex EN perating instructions ... · Press “arrow key left ... Pro Flex Mono Flex Duo Flex Line 1 Line 2 Input 1 Input 2 Input 3 Disabled CycCount MCCount

Page 26 EN

Speciication of runtime limit, Table 1 of 2Step Key Display Description

1 Set the agitator rotations <Rotation> to limit runtime

You will enter the following Rotations sub-menu.The input that was assigned to the pump agita-tor will be displayed.This is input 4 on the standard pump.

Press the ENTER key to confirm the selection.

You will enter the following Mon+Stop/Imm. Stop sub-menu

Valvesp-switchRotation

Input 4

5.4 Specifying the runtime limitation through number of agitator rotations

< Rotation> By default, the quantity of lubri-cant delivered is monitored by the number of agitator rotations. Two options are available under the Rotation menu: <Mon+Stop> The runtime is limited by the number of agitator rotations (input 4, agitator) with simultaneous monitoring of the system using a cycle switch (input 1, p-switch). A fault is reported if cycles are missing. <Imm. Stop> As soon as the anticipated rota-tions are attained on the input (input 4), the lubrication procedure is stopped.

Requirement: The Configuration menu was pre-selected in the Config menu.

5. Options for customer adjustment

1

2

3

Page 27: LC 502 control unit for ProFlex EN perating instructions ... · Press “arrow key left ... Pro Flex Mono Flex Duo Flex Line 1 Line 2 Input 1 Input 2 Input 3 Disabled CycCount MCCount

Page 27 EN

Speciication of runtime limit, Table 2 of 2Step Key Display Description

2 Activate the stop input for agitator <Mon+Stop> <Imm. Stop>

You will enter the Stop menu, for example for input 4; assigned by default for W1 control.

Mon+Stop settingThis setting limits the runtime using the number of agitator rotations while simultaneously monitoring the system using a cycle switch. An error is generated in the event of missing cycles.

Immediate stop settingAs soon as the anticipated rotations are attained on the input, the lubrication procedure is stopped. When pressure monitoring is used, an error is not generated if pressure has not yet been built up.

Select <Mon+Stop> or <Imm. Stop> using <arrow key up/down>.

Press the ENTER key; you will then enter the selected menu

Enter the input value using <arrow keys up/down>

Press the ENTER key to confirm the input.

Go to the end of the line using <arrow key right> or <arrow key left> then press the arrow key again to exit the menu.

Mon+Stop

Imm. Stop

Mon+StopImm. Stop

5. Options for customer adjustment

or

Page 28: LC 502 control unit for ProFlex EN perating instructions ... · Press “arrow key left ... Pro Flex Mono Flex Duo Flex Line 1 Line 2 Input 1 Input 2 Input 3 Disabled CycCount MCCount

Page 28 EN

5.5 Additional optional settings(menudisplaydependingonpumpconiguration)

The following menus can be enabled depending on how the inputs are used:

Requirement: The Configuration menu was pre-selected in the Config menu.

5. Options for customer adjustment

1

2

3

<ExtDelay> (pause extension):

If the pause extension is activated, and the si-gnal is active at the respective input, then the pause time of the lubrication system will be interrupted for as long as the signal remains active. Once the signal ends, the pump will re-sume the normal lubrication operation.

If the system is currently in run time, then this will first be concluded before the pause exten-sion takes effect.

< ExtStop> (Stop input) :

If the stop input is activated, and if the signal is active at the respective input, then the lubrication system will stop at once. The lubrication cycle will be interrupted for as long as the signal is active. Once the signal ends, the pump will resume the normal lubrication cycle.

The stop input stops the system, no matter whether it is currently in pause or run time.

In the case of MonoFlex systems which are currently in run time, the pressure increase is interrupted and the remaining run time is possibly not sufficient to build the pressure up completely once again. This leads to an error message

Page 29: LC 502 control unit for ProFlex EN perating instructions ... · Press “arrow key left ... Pro Flex Mono Flex Duo Flex Line 1 Line 2 Input 1 Input 2 Input 3 Disabled CycCount MCCount

Page 29 EN5. Options for customer adjustment

Additional optional settings

Step Key Display Description

Activate the delay extension for main line 1 (main line 2) <ExtDelay> You will enter the following sub-menu Pause delay time

The input to which the extension delay was assigned will be displayed.for example input 2.The <None> menu item = not assigned to any input.

Select using <arrow key up/down>. Press the ENTER key to confirm the selection. Press <arrow key left>; you will return to the menu for the main line.

Activate the stopper input for main line 1 (main line 2) <Stopper> You will enter the following sub-menu for stopper input (immediate stop on active signal).

The input that was configured as a stopper will be displayed.for example input 2.The <None> menu item = not assigned to any output.

Select using <arrow key up/down>. Press the ENTER key to confirm the selection. Press <arrow key left>; you will return to the menu for the main line.

Enable and enter the cycles for machine contact input <MCCount>

Select <None> or <MCCount1-4> using <arrow key up/down>. Press the ENTER key to confirm the selection. Press <arrow key left>. If <None> is selected, you will return to the MCNumber menu. If MCCount1-4 is selected, you will enter the following menu for the counter.

If <None> was selected, the selection is marked upon confirmation.If the MC control input was selected, the edit window will appear upon confirmation. The minimum num-ber of pulses for starting a lubrication cycle can now be entered. Zero is ignored. The current MC control input is highlighted when you exit the edit window.

MCNumberExternal DKExtDelayNoneMCCount 1-4

Line 1MCCount1-4ØØØØØ

Valvesp-switchExtDelay

None

Input 2-4

Valvesp-switchExtStop

None

Input 2-4

Page 30: LC 502 control unit for ProFlex EN perating instructions ... · Press “arrow key left ... Pro Flex Mono Flex Duo Flex Line 1 Line 2 Input 1 Input 2 Input 3 Disabled CycCount MCCount

Page 30 EN

6. Options for customer adjustment of a progressive centralized lubrication system with two main lines

Compared to a progressive system with one main line, controlling a progressive system with two main lines requires two changeover valves that control both lines independently of each other.

By default, Output 1 (line1) and Output 2 (line 2) are assigned to the two valves and their function <Polarity> is defined as <N Open> for both. The options for customer adjustment of a sys-tem with two main lines are identical to those of a system with one main line. In a system with two main lines, <Line 2> is displayed in addition to <Line 1> under the Settings configuration menu. You must change from <Line 1> to <Line 2> prior to selecting the adjustable menu items.

Options for customer adjustment of main line 2

Step Key Display Description

1 Select the <Line2> main line Select the Settings menu item using <arrow key

down>.

Press the ENTER key; you will then enter the fol-lowing menu for main line 1. Select the <Line 2> menu item using <arrow key

down>.

Press the ENTER key; you will then enter the following parameter adjustment menu for main line 2 <Line 2>

The adjustment options for main line 2 are iden-tical with those for main line 1.

The adjustment options are described in Chapter 5.

See Chapter 5, Options for customer adjustment.

SystemSettings

InputsLine 1Line 2

6. Options for customer adjustment of a progressive centralized lubrication system with two main lines

Requirement: The Configuration menu was pre-selected in the Config menu.

1

2

3

Page 31: LC 502 control unit for ProFlex EN perating instructions ... · Press “arrow key left ... Pro Flex Mono Flex Duo Flex Line 1 Line 2 Input 1 Input 2 Input 3 Disabled CycCount MCCount

Page 31 EN

7. Status display

The status mode is started by selecting <Status> in the main menu and pressing the ENTER key. The control unit can show the state and connection status of inputs and out-puts, all errors encountered, and the ambient temperature of the control unit, as well as the current status of the lubrication process. The data are recorded data and therefore can-not be edited.

Selection in status mode is performed by briely pressing one of the keys.

Configuration menu

Step Key Display Description

1 Entry mask/language selection

The German version is active by default (flashing).Press “arrow key up” to switch to the English version. Press the ENTER key.

2 Main menu

Select “Status” using the arrow key. Press the ENTER key to enter the Status

menu. Press the ENTER key.

3 Device status menu

In the device status menu, you can view the con-figurations for:

Lub = Runtimes for each enabled line Errors = Display of current system errors IO State = Electrical state of inputs and

outputs IO Conn. = Connection states of inputs and

outputs Temp = Query ambient temperature

The currently enabled selection flashes. Entries and changes cannot be made in the device status mode.

English

Deutsch

InfoConig

Status

IO Conn.Temp.

Lub

ErrorsIO State

Display the current control status

7. Status display

7.1 Status - Display of current device

status

1

2

3

Page 32: LC 502 control unit for ProFlex EN perating instructions ... · Press “arrow key left ... Pro Flex Mono Flex Duo Flex Line 1 Line 2 Input 1 Input 2 Input 3 Disabled CycCount MCCount

Page 32 EN

1

2

3

Runtimes and pause times, Table 1 of 4

Step Key Display Description

1 Runtimes of lubrication process

The Lub menu item is already enabled (flashing). Press the ENTER key. You will enter the selected menu <Line>.

Select Line 1 or Line 2 using <arrow key up/down>. Press the ENTER key. You will enter the selected menu <Settings for

Line 1>.

2 View active lubrication time or pause time

The Lubtime menu item (active lubrication time or pause time) is already activated (flashing). Press the ENTER key.

Depending on the active state of the selected main line, the display will show either the remain-ing runtime or the remaining pause time.

The runtime and/or pause time is programmed (specified) in the <Config> menu, <Settings>, <Line 1>. Press <arrow key left> to exit the menu. You will return to the previous menu.

7.2 Lub - Runtimes of lubrication process

The lubrication procedure is performed in multiple phases: in pump runtime, delay time, pause, and immediately. The remaining run-times are displayed for each line (Line 1/Line 2). All enabled lines are displayed in the <Lub> sub-menu. Use the <arrow keys up/down> to select the line whose data you want to view. Press the ENTER key to go to the following sub-menu. In the <Lubtime> menu item, you can view the currently remaining runtime or the currently remaining pause time of the lu-bricant process. In the <Inputs> menu item, you can view the inputs assigned to the selected main line.

Lub

ErrorsIO State

Line 1

Line 2

Lubtime

Inputs

PauseØØØØØhØØm ØØs

RuntimeØØØØØhØØm ØØs

Lub

ErrorsIO State

7. Status display

7.3 Reading the enabled inputs

Page 33: LC 502 control unit for ProFlex EN perating instructions ... · Press “arrow key left ... Pro Flex Mono Flex Duo Flex Line 1 Line 2 Input 1 Input 2 Input 3 Disabled CycCount MCCount

Page 33 EN

Runtimes and pause times, Table 2 of 4

Step Key Display Description

3 View active lubrication time or pause time

Select the <Inputs> menu item using <arrow key down> Press the ENTER key to confirm the selection.

You will enter the Inputs sub-menu.

Select <Input 1 (2 or 3 or 4)> using <arrow key up/down> Press the ENTER key to confirm the selection. You will enter the selected menu <Input 1> (2 or 3 or 4).

3.1 CycCount - Read the number of cycles of the monitoring system (cycle switch on master distributor)MCCount - Read the number of machine contacts of the monitoring system

Machine contact pulses <MCCount> are also treated as cycles.

The inputs were already programmed (specified) for the selected main line (1 to 2) in the <Config> menu, <Settings>, <Line1>, see Chapter 2.3.4. If a cycle switch (Cyc) was assigned to the input, the following values can be read:

EX = Expected cycles RX = Cycles counted thus far

Press <arrow key left> to exit the menu. You will return to the previous menu.

Lubtime

Inputs

Cycles

EX Ø

RX Ø

Input 4

Input 1

Input 2

Input 3

or

MCNumber

EX Ø

RX Ø

7. Status display

Page 34: LC 502 control unit for ProFlex EN perating instructions ... · Press “arrow key left ... Pro Flex Mono Flex Duo Flex Line 1 Line 2 Input 1 Input 2 Input 3 Disabled CycCount MCCount

Page 34 EN

Runtimes and pause times, Table 3 of 4

Step Key Display Description

3.2 Monitor fill level sensors

The inputs were already programmed (specified) for the selected main line (1 to 2) in the <Config> menu, <Settings>, <Line1>. See Chapter 2.3.4. If the selected input is configured as a fill level sensor, the rotations of the agitator can be counted if a mechanical switch is used. The status of the output signal can be observed when using capacitive sensors.

If the input was assigned as a rotating agitator, the following values can be read: EX = Expected rotations RX = Rotations counted thus far.

If the input was assigned as a mechanical changeover switch, the status of the output signal isdisplayed:

0 = Inactive signal 1 = Active signal

If the input was assigned as a capacitive changeover switch, the status of the output signal is displayed:

0 = Inactive signal 1 = Active signal

If the input was assigned as an analog switch, the status of the output signal is displayed in %: 0 -100% = Current fill level

Press <arrow key left> to exit the menu. You will return to the previous menu.

Rotation

EX Ø

RX Ø

Level SW

Ø

or

Level SW

~ Ø%

or

or

7. Status display

Page 35: LC 502 control unit for ProFlex EN perating instructions ... · Press “arrow key left ... Pro Flex Mono Flex Duo Flex Line 1 Line 2 Input 1 Input 2 Input 3 Disabled CycCount MCCount

Page 35 EN

Runtimes and pause times, Table 4 of 4

Step Key Display Description

3.2 Monitor fill level sensors

The inputs were already programmed (specified) for the selected main line (1 to 4) in the <Config> menu, <Settings>, <Line1>. See Chapter 2.3.4. The rotations of the agitator can be counted if the selected input is configured as a fill level switch and the switch is a rotating agitator switch (W1). The status of the output signal can be observed when using capacitive sensors.

If the input was assigned as an external pressure switch, the current state (0/1) of the pressure switch can be displayed.

Press <arrow key left> to exit the menu. You will return to the previous menu <Status>.

External DKØ

or

7. Status display

Page 36: LC 502 control unit for ProFlex EN perating instructions ... · Press “arrow key left ... Pro Flex Mono Flex Duo Flex Line 1 Line 2 Input 1 Input 2 Input 3 Disabled CycCount MCCount

Page 36 EN

1

2

3

Read fault times

Step Key Display Description

1 Runtimes of lubrication process

Select the Errors menu item using <arrow key down> Press the ENTER key to confirm the selection. You will enter the selected menu Errors.

The possible errors and their remedies are list-ed in the chapter <Errors, causes, and remedies>.

Press the key to clear all errors and restart the lubrication process on all main lines.

Press the key Press <arrow key left> to exit the menu. You will return to the previous menu <Status>.

7.4 Read error times of lubrication process

Lub

Errors

IO State

None

Requirement: The <Status> menu was pre-selected in the

main menu (Chapter 2.1.1). The control unit is capable of detecting various system errors. The control unit activates the red LED as soon as an error is detected. In some cases, the affected main line or all main lines are deactivated. Current errors are dis-played as follows: Select the device status <Status> in the main menu, followed by the error menu <Errors> in the Status sub-menu. Upon confirmation, the sources of all identified errors will be displayed. The error that you wish to inspect can be selected in the menu and displayed in detail.

7. Status display

LubErrors

IO State

Page 37: LC 502 control unit for ProFlex EN perating instructions ... · Press “arrow key left ... Pro Flex Mono Flex Duo Flex Line 1 Line 2 Input 1 Input 2 Input 3 Disabled CycCount MCCount

Page 37 EN

1

2

3

Electrical state of inputs and outputs

Step Key Display Description

1 States of inputs and outputs

Select the IO State menu item using <arrow key down> Press the ENTER key to confirm the selection.

You will enter the selected menu for the electri-cal state of inputs and outputs.

2 IO state of inputs and outputs

Menu displays the programmed control inputs (max. 4)and control outputs (max. 2 + motor)

Connection representing an output

Connection representing an input

1 2 3 4 1 2 = Numbers of pump connections M = Motor connection

0 = Connection with no (negative) voltage 1 = Connection with positive voltage Press <arrow key left> to exit the menu.

You will return to the previous menu <Status>.

IO Conn.

Temp

7.5 Read electrical states of inputs and outputs

Lub

Errors

IO StateRequirement: The <Status> menu was pre-selected in the

main menu (Chapter 2.1.1).

The electrical states of inputs and outputs can be viewed.

represents an output and represents an input.

The second line contains the number of the output or input.

The electrical state of an output or input is displayed as 0 if there is no voltage at the output or input; it is 1 if there is sufficient measurable voltage.

1 2 3 4 M 1 20 0 0 0 0 0 0

7. Status display

LubErrorsIO State

Page 38: LC 502 control unit for ProFlex EN perating instructions ... · Press “arrow key left ... Pro Flex Mono Flex Duo Flex Line 1 Line 2 Input 1 Input 2 Input 3 Disabled CycCount MCCount

Page 38 EN

1

2

3

Electrical state of inputs and outputs

Step Key Display Description

1 Connect inputs and outputs

Select the IO Conn. menu item using <arrow key down> Press the ENTER key to confirm the selection. You will enter the selected menu for the electri-

cal connection of inputs and outputs.

2 IO connection of inputs and outputs

Menu displays the electrical state of control inputs, control outputs, and the motor connection.

Connection representing an output

Connection representing an input

1 2 3 4 1 2 = Numbers of pump connections M = Motor connection

= Connection connected

= Connection not connected Press <arrow key left> to exit the menu. You will return to the previous menu <Status>.

7.6 Read connection states of inputs and outputs

Lub

Errors

IO State

Requirement: The <Status> menu was pre-selected in the

main menu (Chapter 2.1.1).

Connection states of inputs and outputs can be viewed.

represents an output and represents an input.

The second line contains the number of the output or input.

stands for a connection and stands for an interruption.

IO Conn.

Temp

1 2 3 4 M 1 2

7. Status display

LubErrorsIO State

IO Conn.

Temp

Page 39: LC 502 control unit for ProFlex EN perating instructions ... · Press “arrow key left ... Pro Flex Mono Flex Duo Flex Line 1 Line 2 Input 1 Input 2 Input 3 Disabled CycCount MCCount

Page 39 EN

1

2

3

Ambient temperature of control unit

Step Key Display Description

1 Read ambient temperature

Select the Temp menu item using <arrow key down> Press the ENTER key to confirm the selection. You will enter the selected menu for the ambi-

ent temperature on the control unit.

2 Temperature display

menu shows the ambient temperature of the control unit. Press <arrow key left> to exit the menu. You will return to the previous menu <Status>.

7.7 Read ambient temperature on the control unit

Lub

Errors

IO State

Requirement: The <Status> menu was pre-selected in the

main menu (Chapter 2.1.1).

The control unit is equipped with a tempera-ture sensor for measuring the ambient tem-perature (pump). If the temperature is too high or too low, all lubrication processes will be halted and resumed only once the tempera-ture has normalized.

The limit for low temperature is below -40°C and the limit for high temperature is over +80°C. The limits can only be modified by the manufacturer.

IO Conn.

Temp

Temp

Ø Ø C°

7. Status display

LubErrorsIO State

IO Conn.

Temp

Page 40: LC 502 control unit for ProFlex EN perating instructions ... · Press “arrow key left ... Pro Flex Mono Flex Duo Flex Line 1 Line 2 Input 1 Input 2 Input 3 Disabled CycCount MCCount

Page 40 EN

8.1 Basic initialization of control unit

Basic initialization

Step Key Display Description

1 Basic initializationThe basic initialization menu is used to restore the default factory settings.

Select <Default> from the main configuration menu Press the ENTER key to confirm the selection Select <Cancel> to abort the procedure

or: Select <Save> to continue the restore of the factory settings Press the ENTER key to confirm the selection

Upon confirmation, all previous settings will be overwritten with factory settings if <Save> was selected.Cancel

Save

SystemSettingsInputs

OutputsDefault

Reset

8. Basic settings

8. Basic settings

Restoring default factory settings

1

2

3

Page 41: LC 502 control unit for ProFlex EN perating instructions ... · Press “arrow key left ... Pro Flex Mono Flex Duo Flex Line 1 Line 2 Input 1 Input 2 Input 3 Disabled CycCount MCCount

Page 41 EN

8.2 Control unit reset function

Control unit reset function

Step Key Display Description

1 Basic initialization

Select <Reset> from the main configuration menu Press the ENTER key to confirm the selection. Select <Cancel> to abort the procedure

or: Select <Save> to continue the basic initialization of the selected system Press the ENTER key to confirm the selection.

Upon confirmation, all previous settings will be overwritten with the default settings for the selected system if <Save> was selected.

CancelSave

SystemSettingsInputs

OutputsDefault

Reset

8. Basic settings

Reset to original basic settings

1

2

3

Page 42: LC 502 control unit for ProFlex EN perating instructions ... · Press “arrow key left ... Pro Flex Mono Flex Duo Flex Line 1 Line 2 Input 1 Input 2 Input 3 Disabled CycCount MCCount

Page 42 EN

8.3 Reset the user password

Password change

Step Key Display Description

1 Basic initialization

Select the <New Pwd> menu item using <arrow key down>. Press the ENTER key. You will enter the following Password sub-menu.

2

Old password:00000000

Password menu The user password is accessed in the Password menu. This password can be used to edit user

settings. Enter new password Press the ENTER key to apply the new password

or:

Ignore changes and return to the previous menu To exit the edit window, press the left key when the cursor is on the left edge or press the right key

when the cursor is on the right edge. You will return to the previous menu.

ResetØØØØØØØØ

SystemSettingsInputsOutputs

DefaultResetDefault

ResetNew Pwd

The user password is factory pre-set to “0” digits. Only numerals between 0 and 9 are permitted.

8. Basic settings

1

2

3

Page 43: LC 502 control unit for ProFlex EN perating instructions ... · Press “arrow key left ... Pro Flex Mono Flex Duo Flex Line 1 Line 2 Input 1 Input 2 Input 3 Disabled CycCount MCCount

Page 43 EN

9. Control ports

9.1 KFGL

9. Control ports

9.1.1 KFGL pump for industrial applications, 24 VDC

KFGL pump for industrial applications, 24 VDC

Out�

� �

Faul

t

� �

Out�

� �

2

3

1

operating voltageBetriebsspannung

24VDC

1+ 2-

Output 1 (Out 1) 1

Standard design= Disabled

system w/ two main lines

Pin 3: Valve (-)

Pin 4: Valve (+)

Error output (Fault) 3

Pin 3: Fault notification (-)

Pin 4: Fault notification (+)

Input 1 (In 1) 4

Pin 1: Cycle switch 1 (+)

Pin 4: Cycle switch 1 (-)

Input 2 (In 2) 5

Pin 1: Cycle switch 2 (+)

Pin 4: Cycle switch 2 (-)

Input 3 (In 3) 6

Pin 1: External DK (+)

Pin 4: External DK (-)

Output 2 (Out 1) 2

Standard design= Disabled

system w/ two main lines

Pin 3: Valve (-)

Pin 4: Valve (+)

1

Page 44: LC 502 control unit for ProFlex EN perating instructions ... · Press “arrow key left ... Pro Flex Mono Flex Duo Flex Line 1 Line 2 Input 1 Input 2 Input 3 Disabled CycCount MCCount

Page 44 EN9. Control ports

9.1.2 KFGL pump with grease follower plate, 24 VDC

operating voltageBetriebsspannung

24VDC

2

3

1

1+ 2-

(Level-switch)In 4

Out 2

In 2

Faul

t

In 3

Out 1

In 1

KFGL pump with grease follower plate, 24 VDC

Output 1 (Out 1) 1

Standard design= Disabled

system w/ two main lines

Pin 3: Valve (-)

Pin 4: Valve (+)

Error output (Fault) 3

Pin 3: Fault notification (-)

Pin 4: Fault notification (+)

Input 1 (In 1) 4

Pin 1: Cycle switch 1 (+)

Pin 4: Cycle switch 1 (-)

Input 2 (In 2) 5

Pin 1: Cycle switch 2 (+)

Pin 4: Cycle switch 2 (-)

Input 3 (In 3) 6

Pin 1: External DK (+)

Pin 4: External DK (-)

Output 2 (Out 1) 2

Standard design= Disabled

system w/ two main lines

Pin 3: Valve (-)

Pin 4: Valve (+)

1

Input 4 (In 4) 7

Pin 1: Fill level (+)

Pin 2: Fill level (-)

7

Page 45: LC 502 control unit for ProFlex EN perating instructions ... · Press “arrow key left ... Pro Flex Mono Flex Duo Flex Line 1 Line 2 Input 1 Input 2 Input 3 Disabled CycCount MCCount

Page 45 EN

9.1.3 KFGL pump for industrial applications or with grease follower plate, 230 VAC

9. Control ports

Industrial applications or with grease follower plate, 230 VAC

2

3

1

AK

J

B

L CM

H

G F E

D

AK

J

B

L CM

H

G F E

D

SpannungsversorgungPin 1: L1Pin 2: N

Power

AKJ

B

LCM

H

GFE

D

3

2

4

1

Output 1 (Out 1)

Pin G: Not programmed (-)

Pin H: Not programmed (+)

Output 2 (Out 2)

Pin J: Not programmed (-)

Pin K: Not programmed (+)

Error output (Fault)

Pin L: Fault notification (-)

Pin M: Fault notification (+)

Input 1 (In 1)

Pin B: Cycle switch 1 (+)

Pin A: Cycle switch 1 (-)

Input 2 (In 2)

Pin D: Not programmed (+)

Pin C: Not programmed (-)

Input 3 (In 3)

Pin F: External DK (+)

Pin E: External DK (-)

Error output (Fault)

Pin 3: Fault notification (-)

Pin 4: Fault notification (+)

Input 1 (In 1)

Pin 1: Cycle switch 1 (+)

Pin 4: Cycle switch 1 (-)

Output 1 (Out 1)

Pin 2: Not programmed (+)

Pin 3: Not programmed (-)

Input 2 (In 2)

Pin 1: Not programmed (+)

Pin 4: Not programmed (-)

Output 2 (Out 2)

Pin 2: Not programmed (+)

Pin 3: Not programmed (-)

Input 3 (In 3)

Pin 1: External DK (+)

Pin 4: External DK (-)

1

2

3

4

1 2

3 4

Page 46: LC 502 control unit for ProFlex EN perating instructions ... · Press “arrow key left ... Pro Flex Mono Flex Duo Flex Line 1 Line 2 Input 1 Input 2 Input 3 Disabled CycCount MCCount

Page 46 EN9. Control ports

9.1.4 KFGL pump for vehicle lubrication, 12 VDC, 24 VDC

4

31

5

6

27

In 3Power

FaultOu

t 2

In 2

Out 1

In 1

KFGL pump for vehicle lubrication, 12 VDC, 24 VDC

Power supply 5

Pin 1: OV (-)

Pin 2: 12/24 VDC (+)Error output (Fault)

Pin 3: Fault notification (-)

Pin 4: Fault notification (+)Input 3 (In 3)

Pin 5: External DK (-)

Pin 6: External DK (+)

Output 1 (Out 1) 1

Standard design= Disabled

system w/ two main lines

Pin 3: Valve (-)

Pin 4: Valve (+)

Input 1 (In 1) 3

Pin 1: Cycle switch 1 (+)

Pin 4: Cycle switch 1 (-)

Input 2 (In 2) 4

Pin 1: Cycle switch 2 (+)

Pin 4: Cycle switch 2 (-)

Output 2 (Out 1) 2

Standard design= Disabled

system w/ two main lines

Pin 3: Valve (-)

Pin 4: Valve (+)

Page 47: LC 502 control unit for ProFlex EN perating instructions ... · Press “arrow key left ... Pro Flex Mono Flex Duo Flex Line 1 Line 2 Input 1 Input 2 Input 3 Disabled CycCount MCCount

Page 47 EN

1

2

3

10. Operational and pump faults

10.1 Operational malfunctions

10.2 System errors

The LC502 control unit is capable of detecting various system errors. The control unit acti-vates the red LED and causes it to flash as soon as an error is detected. In some cases, the affected main line or all main lines are de-activated. Current errors are displayed as fol-lows: Select the device status <Status> in the main menu, followed by the error menu <Errors> in the Status sub-menu. Upon con-firmation, the sources of all identified errors will be displayed. The error that you wish to inspect can be selected in the menu and dis-played in detail.

10.4 Delete error notiication

All error notiications can be acknowledged and cleared using the key. This restarts the lubrication process on all lines. This can be performed by an external pressure switch (DK) if necessary.

Note!

Determineandremedythecauseoferrorsbeforedeletingerrornotiica-

tions.Theuserisliablefordamagesresultingfromoperatingthemachinewithoutlubrication.

10.3 Display errors

Select the error display menu.

Step Key Display

1

2

3

English

Deutsch

InfoConig Status

LubErrors

IO State

10. Operational and pump faults

LubErrorsIO State

Page 48: LC 502 control unit for ProFlex EN perating instructions ... · Press “arrow key left ... Pro Flex Mono Flex Duo Flex Line 1 Line 2 Input 1 Input 2 Input 3 Disabled CycCount MCCount

Page 48 EN10. Operational and pump faults

Error types

Error type Definition Display Example of error Response by control unit

Warning

Malfunction

A problem has occurred that does not affect the operational sequence but can lead to an operational malfunction if not remedied.

An error has occurred that affects the proper functioning of the lubrication system.

The lubrication points may

not be supplied with adequate

lubrication because a malfunc-

tion has affected the proper

functioning of the lubrication

system. Malfunctions must al-

ways be remedied immediately.

- LED lights up and remains constant

- LED flashes

Fill level in the reservoir sinks to the level of the pre-warning sensor (only on systems equipped and configured with this functionality).

Insufficient number of piston detector signals from a lubrication segment during the pump runtime

An error notification is generated Operation continues as normal.

1. Block mode up to configured number of trials2. - If the piston detector signal has still not been received, the valve is closed and an error notification is generated.

10.5 Error types

Depending on the severity of the error, the control unit issues either a warning or a malfunction notiication (see following table).

Page 49: LC 502 control unit for ProFlex EN perating instructions ... · Press “arrow key left ... Pro Flex Mono Flex Duo Flex Line 1 Line 2 Input 1 Input 2 Input 3 Disabled CycCount MCCount

Page 49 EN

1

2

3

10. Operational and pump faults

10.6 Error notiication

Lub

ErrorsIO State

Displayed error notifications

Error notification Category Possible cause Rectification

Current error Malfunction The measured motor current has gone below the limit.

• Check electrical connections • Replace pump motor

Tank gauge error(error in fill level indicator)

Malfunction The mechanical fill level sensor does not mea-sure pulses after more than 25 seconds, although the pump motor is on. The analog or capacitive fill level sensor indi-cates that the tank is empty.

Connection interrupted or tank empty

• Inspect the mechanical fill level switch (W1) for proper function and replace if necessary

• Check fill level and refill if necessary

• Inspect the connection of the fill level switch

Temperature error Warning This error is reported if the temperature rises above or falls below the maximum or minimum operating temperature, respectively.

• Change the ambient conditions so that a permissible operating temperature is achieved for the control unit/pump

Output error Malfunction This error is reported if a short circuit or line break is detected at the output. This is a connec-tion error in both cases. To display the specifics of the error, first select the affected output.

• Inspect the affected output connections for short circuit or line break and rewire if necessary.

Page 50: LC 502 control unit for ProFlex EN perating instructions ... · Press “arrow key left ... Pro Flex Mono Flex Duo Flex Line 1 Line 2 Input 1 Input 2 Input 3 Disabled CycCount MCCount

Page 50 EN10. Operational and pump faults

Displayed error notifications

Error notification Category Possible cause Rectification

Input error

- Connection error

- Cycle error

Malfunction Different signal sources can be connected to a single input. Errors that are detected on an input can therefore have various causes. A list of possible input errors follows:

Connection errors are reported if the signal source configured for the input must conduct closed-circuit current but the measured cur-rent is below the expected minimum value. The problem may lie in a cycle switch or an analog or capacitive fill level monitoring sensor.

Progressive systems can monitor the lubri-cation process using cycle switches. At the end of the pump runtime and the dwell time (if applicable), a check is performed as to whether all expected cycles were counted. If expected cycles are missing, a cycle error will be issued on the inputs with missing cycles.

• Inspect electrical lines and connections of the affected input and replace if necessary

• Inspect cycle switch or fill level switch of the affected input and replace if necessary

• Check the master distributor of the affected input, replace if necessary

• Inspect cycle switch of the affected input and replace if necessary

• Check entry of the programmed number of cycles; it must be proportionate to the pump runtime.

Page 51: LC 502 control unit for ProFlex EN perating instructions ... · Press “arrow key left ... Pro Flex Mono Flex Duo Flex Line 1 Line 2 Input 1 Input 2 Input 3 Disabled CycCount MCCount

Page 51 EN

11. LC502 menu displays

The following menu displays are based on the full programming options of the LC502 control unit. The list therefore contains the menus for ProFlex, MonoFlex, and DuoFlex.

11. LC502 menu display

Menu displays, Table 1 of 6

English Deutsch Description

English - English language selection

- Deutsch German language selection

Info Info Device information menu

Config Konfig Configuration menu

Status Status Device status menu

Service Service Menu reserved for SKF, used for locking important settings

Serial Serie Nr Menu selection for the serial number

Firmware Firmware Menu selection for identifying the program on the control unit

Sys time Sys Zeit Total runtime of the control unit

Mot time Mot Zeit Total runtime of the motor

Err time Störzeit Total time that the current error has been present If there is currently no error state, the display shows the sum time of all errors detected thus far

View Anzeigen Menu selection for configuration view Changes cannot be made. Password is not required.

Edit Ändern Menu selection for editing the configuration

Page 52: LC 502 control unit for ProFlex EN perating instructions ... · Press “arrow key left ... Pro Flex Mono Flex Duo Flex Line 1 Line 2 Input 1 Input 2 Input 3 Disabled CycCount MCCount

Page 52 EN11. LC502 menu display

Menu displays, Table 2 of 6

English Deutsch Description

Password Passwort Password entry

System System Menu selection for viewing/editing the mode of operation

Settings Einstel. Menu selection for configuring parameters

Inputs Eingänge Menu selection for configuring inputs

Outputs Ausgänge Menu selection for configuring outputs

Default Grundini Menu selection for restoring default settings

Reset Reset Menu selection for resetting (clearing) the device

New Pwd Neue Pwd Menu selection for changing the user password

ProFlex ProFlex Menu selection for progressive lubrication

MonoFlex MonoFlex Menu selection for single-line lubrication

DuoFlex DuoFlex Menu selection for dual-line lubrication

Line 1/2 Strang 1/2 Main line

Time Zeit Menu selection for configuring lubrication times

Valves Ventile Menu selection for valve assignments

Trials Wiederho Repeat attempts in block mode

p-switch p-Schalt Pressure switch assignment menu

p-Diff p-Diff Differential pressure on dual-line systems

Cyc-type Zyk. Typ Cycle type (half/full cycle) for dual-line lubrication

Delayer Verzöger Input for pause time extension (function selection and assignment for the main line whose pause time will be halted)

Page 53: LC 502 control unit for ProFlex EN perating instructions ... · Press “arrow key left ... Pro Flex Mono Flex Duo Flex Line 1 Line 2 Input 1 Input 2 Input 3 Disabled CycCount MCCount

Page 53 EN

Menu displays, Table 3 of 6

English Deutsch Description

ExtStop Stopeing Error input (function selection and assignment for the main line that will be stopped in the event of an error)

MCNumber MCZyklen MC (machine contact input) (function selection and assignment for the main line that will be controlled)

Cycles Zyklen Selection of cycle inputs that are monitored, including for rotations of the agitator

Pause Pause Pause time

Runtime Laufzeit Pump runtime for the current main line

Pause 2 Pause 2 Pause time in block mode (if cycles are absent and a new attempt is started until they are received)

Dwell Nachlauf Dwell time in block mode and on single-line and dual-line systems. This is also displayed for enabling/dis-abling the dwell time.

Release Entlast. Menu selection for the input with the pressure release sensor or for the output with the pressure relief valve

Buildup Aufbau Menu selection for the input with the pressure buildup sensor or for the output with the pressure buildup valve

Valve 1/2 Ventil 1/2 Valve 1/2 on a dual-line system

Output 1/2 Ausgang 1/2 Output port 1 and 2

Input 1 - 4 Eingang 1 - 4 Input port 1 to 4

None Kein This is selected if no other selection has been made

p-swit 1/2 p-sch 1/2 Pressure switch for line 1/2 in dual-line systems

Disabled Inaktiv The selection in the previous menu window is not enabled

Enabled Aktiv The selection in the previous menu window is enabled

Half Halb Cycle type in dual-line systems (half lubrication cycle)

Full Voll Cycle type in dual-line systems (full lubrication cycle)

11. LC502 menu display

Page 54: LC 502 control unit for ProFlex EN perating instructions ... · Press “arrow key left ... Pro Flex Mono Flex Duo Flex Line 1 Line 2 Input 1 Input 2 Input 3 Disabled CycCount MCCount

Page 54 EN

Menu displays, Table 4 of 6

English Deutsch Description

MCCount1 to MCCount4

MCZähl. 1 bis MCZähl. 4 Selection of MC control input for the affected line

Mon+Stop Mon+Stop Runtime limitation based on agitator rotations, with monitoring by cycle switch. An error is reported when the pre-set value is reached and cycles are missing.

Monitor Monitor Cycle switches that are monitored during pump runtime. A report is generated if cycles are missing at the end of the runtime and (if applicable) block mode.

Imm. Stop (immediate stop)

Sof. Stop (Sofort Stopp) Lubrication is stopped as soon as the expected cycles are received on the input. No report is gener-ated if cycles are missing on other inputs. This function is also used for the agitator.

Col. Stopp(collective stop)

War. Stopp(Warten und stopp)

An input with this setting monitors other inputs. Lubrication is stopped as soon as the last expected cycle is received on the input and on all other inputs. The input with this setting waits for the last missing cycle on other inputs before it stops lubrication. A report is generated if cycles are missing at the end of the runtime and (if applicable) block mode.

Function Funktion Selection for configuring the function of inputs and outputs

Type Typ Signal type of an input or output (analog/digital)

Polarity Polung Signal polarity: This specifies whether the active signal conducts positive (N Open) or negative (N Closed) voltage.

Limits Grenzw. Limit values for analog signals

CycCount Zyk Zähl Function of an input as cycle switch

MCCount MC Zähl. Function of an input as machine contact

Level SW Füllhöhe Function of an input as fill level monitoring sensor. This is also used to show errors from the fill level monitoring sensor.

p-switch p-Schalt Function of an input as pressure switch

11. LC502 menu display

Page 55: LC 502 control unit for ProFlex EN perating instructions ... · Press “arrow key left ... Pro Flex Mono Flex Duo Flex Line 1 Line 2 Input 1 Input 2 Input 3 Disabled CycCount MCCount

Page 55 EN

Menu displays, Table 5 of 6

English Deutsch Description

ExternDK ExternDK Function of an input as DK input

ExtDelay Pausever Function of an input as pause time extension input

ExtStop Stopeing Function of an input as stopper input

Analogue Analog Analog input or output

Digital Digital Digital input or output

N Closed(normally closed)

Öffner Signal polarity of an input or output as normally closed. The signal conducts positive voltage in a disabled state and negative voltage in an enabled state.

N Open(normally open)

Schließer Signal polarity of an input or output as normally open. The signal conducts positive voltage in an enabled state and negative voltage in a disabled state.

p-Active p-Aktiv Analog active value on an input

ErrorOut Störausg Error output signal. This is activated if an error is present.

Valve SW Ventil Function of an output as valve control signal

Cancel Abbruch Menu selection for canceling or ignoring the selected operation

Save Speiche. Menu selection for saving changes to the configuration

Lub Lub Menu selection for displaying the current status of the lubrication process

Errors Fehler Menu selection for displaying current errors

11. LC502 menu display

Page 56: LC 502 control unit for ProFlex EN perating instructions ... · Press “arrow key left ... Pro Flex Mono Flex Duo Flex Line 1 Line 2 Input 1 Input 2 Input 3 Disabled CycCount MCCount

Page 56 EN

Menu displays, Table 6 of 6

English Deutsch Description

IO State IO Zust. Menu selection for displaying the state of inputs and outputs

IO Conn. IO Verb. Menu selection for displaying the connection state of inputs and outputs

Temp. Temp. Menu selection for displaying the current system temperature or temperature errors

Lubtime Lubzeit Menu selection for displaying the current status and remaining time of the lubrication process

Rotation Drehung Rotations of the agitator

No Error Kein Error display when no error has been detected

Current Strom Error display for a motor current error

Pressure Druck This is used to display pressure errors.

Represents an input

Represents an output

Represents an open connection

Represents a closed connection

ResetPwd ResetPwd Menu selection for editing the user password

Unlocked Stellbar Menu selection for enabling a mode of operation or inputs and outputs

Locked Gesperrt Menu selection for blocking a mode of operation or inputs and outputs

11. LC502 menu display

Page 57: LC 502 control unit for ProFlex EN perating instructions ... · Press “arrow key left ... Pro Flex Mono Flex Duo Flex Line 1 Line 2 Input 1 Input 2 Input 3 Disabled CycCount MCCount

Page 57 EN

12. Technical data for LC502 control unit

12. Technical data for LC502 control unit

12.1 Basic settings of LC 502

Pause time: 00001h, 00m, 00s corresponds to a pause time of 1 hours

Pump runtime: 00000h, 04m, 00s corresponds to a pump runtime of 4 minutes

Rotation: 10 corresponds to 10 agitator rotations

Trials: 2 corresponds to two trial cycles within the dwell time, each with a:

Pause2: 00001h, 00m, 00s corresponds to a pause time of 1 hour within the dwell time

Dwell time: 00000h, 04m, 00s corresponds to a dwell time of 4 minutes

Page 58: LC 502 control unit for ProFlex EN perating instructions ... · Press “arrow key left ... Pro Flex Mono Flex Duo Flex Line 1 Line 2 Input 1 Input 2 Input 3 Disabled CycCount MCCount

951-180-005-EN

SKF Lubrication Systems Germany GmbH 2.Industriestrasse4·68766Hockenheim·Germany Tel.+49(0)620527-0·Fax+49(0)620527-101

www.skf.com/lubrication

SKF Lubrication Systems Germany GmbH Motzener Strasse 35/37 · 12277 Berlin · Germany

PF 970444 · 12704 Berlin · Germany Tel.+49(0)3072002-0·Fax+49(0)3072002-111

www.skf.com/lubrication

The contents of this publication are the copyright of the publisher and may not be reproduced in

whole or in part without permission of SKF Lubrication Systems Germany GmbH. Every care has

been taken to ensure the accuracy of the information contained in this publication. However, no

liability can be accepted for any loss or damage whether direct, indirect or consequential, arising

out of use of the information contained herein.

If the component is supplied together with the applicable component lifecycle manual, that manual

must be read and followed. Not all lubricants can be fed using centralized lubrication systems.

SKF can, on request, inspect the suitability of the lubricants selected by the user for pumping in

centralized lubrication systems. Lubrication systems and their components manufactured by SKF

are not approved for use in conjunction with gases, liquefied gases, pressurized gases in solution,

vapors or such fluids whose vapor pressure exceeds normal atmospheric pressure (1013 mbar) by

more than 0.5 bar at their maximum permissible temperature.

Particular attention is called to the fact that hazardous materials of any kind, especially the mate-

rials classified as hazardous by EC Directive 67/548/EEC, Article 2, Para. 2, may only be filled into

SKF centralized lubrication systems and components and delivered and/or distributed with such

systems and components after consulting with and obtaining written approval from SKF.