Lecture1b-Three Phase Systems

Embed Size (px)

Citation preview

  • 8/19/2019 Lecture1b-Three Phase Systems

    1/13

    1/03/20

    School of Electrical Engineering & telecommunications

    ELEC4612 – Power System Analysis

    Lecture 1b: Three Phase Systems

    Dr Jayashri Ravishankar 

    Properties of 3-phase Systems

    • Three-phase systems have either three or four conductors.

    • There are three-phase conductors identified as A, B, and C.

    • There is sometimes a fourth conductor, whichis the neutral.

    • The three phases are 120 degrees out of phase with each other (360 divided by 3).

  • 8/19/2019 Lecture1b-Three Phase Systems

    2/13

    1/03/20

    Balanced 3-phase systems

    1. All 3 sources are represented by a set of balanced 3-phase variables

    2. All loads are 3-phase with equal impedances

    3. Line impedances are equal in all 3 phases

    Using “phase a” as a reference, the voltage in

    three phases can be described as follows:

      0°

      120°  240° 120°

     Advantages of 3-phase

    • The rating of 3-phase machines are 150%

    greater than 1-phase machines of similar frame

    size.

    • The power delivered by a 1-phase system

    pulsates and falls to zero. The 3-phase power 

    never falls to zero and approximately remains

    the same at any instant.

    • A 3-phase system needs three conductors;however, each conductor is only 75% the size

    of the equivalent kVA rated 1-phase conductors.

  • 8/19/2019 Lecture1b-Three Phase Systems

    3/13

    1/03/20

    1-phase Vs 3-phase Power 

    Wye/Star – Connection (Y)

     

      

     

    30||3

    2

    3

    2

    1||||

    )120sin120(cos1||

    120||0||

     ph

     ph ph

     ph

     ph ph

    bnanab

     jV V 

     jV 

    V V 

    V V V 

    210||3

    90||3

     phca

     phbc

    V V 

    V V 

     ph L ph L   I  I V V      &3

    Reference

    Phase voltageLine voltage

    Phase current

    Line current

  • 8/19/2019 Lecture1b-Three Phase Systems

    4/13

    1/03/20

    Delta - Connection ( )

     ph L

     ph L

     I  I 

    V V 

    3

     

    Phase voltage

    Line voltage

    Phase current

    Line current

      30||3   ph L   I  I 

    Line & Phase Values

  • 8/19/2019 Lecture1b-Three Phase Systems

    5/13

    1/03/20

     -Y Transformation

    3-phase Power 

    Total instantaneous power absorbed into load =

    instantaneous power in each phase

    Under balanced conditions the average power,

          Total average power,

     balanced 

    3

    source

     balanced 

    3

    load 

    a

     b

    c

    abv

    bcvbi

    ai

    ci

    +

    +

     _ 

     _ 

     balanced 

    3

    source

     balanced 

    3

    load 

    a

     b

    c

    abv

    bcvbi

    ai

    ci

    +

    +

     _ 

     _ 

    3   an a bn b cn c p t v t i t v t i t v t i t    

    ∅        3 √3

  • 8/19/2019 Lecture1b-Three Phase Systems

    6/13

    1/03/20

    Example 1.1

     Assume a -connected load is supplied from a 313.8 kV (L-L) source with Z = 10020Calculate the power consumed.

    © 2012 Cengage Learning Engineering. All Rights Reserved.

    13.8 0

    13.8 0

    13.8 0

    ab

    bc

    ca

    V kV 

    V kV 

    V kV 

    Method 1

    © 2012 Cengage Learning Engineering. All Rights Reserved.

    *

    138 20 138 0

    239 50 amps

    239 170 amps 239 0 amps

    3 3 13.8 0 kV 138 amps

    5.7 MVA5.37 1.95 MVA

     pf cos20 lagging

    a ab ca

    b c

    ab ab

     I I I 

     I I 

    S V I 

     j

    13.8 0138 20

    138 140 138 0

    ab

    bc ca

    kV  I amps

     I amps I amps

  • 8/19/2019 Lecture1b-Three Phase Systems

    7/13

    1/03/20

    Method 2

       13.80°10020°

      138 20°

        13.8

      138 20°x 3 239 20°

    3   3 x13800 x 239 5.71 MW

    OR 3  3 x13800 x 138 5.71 MW

    Example 1.2

      480

    8  60

      60 x 3 104

      240

    3  138.57

      138.57

    6  23

  • 8/19/2019 Lecture1b-Three Phase Systems

    8/13

    1/03/20

    Example 1.3

      6 x 6

    18  2

      4||2 1.333

    ?

      440

    3  254.03

      254.03

    1.333   .

      4 4

    4 x 4

    4   12   12||6 4

      440 ;  

     440

    4   110   110 x 3  .

    Example 1.4

     A 3-phase line has an impedance of 2+j4   as shown in the figure. The linefeeds two balanced loads that are connected in parallel. The first load is Y-

    connected and has an impedance of 30+j40    per phase. The second load is-connected and has an impedance of 60-j45 . The line is energised at thesending end from a 3-phase balanced supply of line voltage 207.85 V. Taking

    phase voltage Va as reference, determine:

    (a) The current, real power and reactive power drawn from the supply.

    (b) The line voltage at the combined loads.

    (c) The current per phase in each load.

    (d) The total real and reactive powers in each load and the line.

  • 8/19/2019 Lecture1b-Three Phase Systems

    9/13

    1/03/20

  • 8/19/2019 Lecture1b-Three Phase Systems

    10/13

    1/03/20

  • 8/19/2019 Lecture1b-Three Phase Systems

    11/13

    1/03/20

    Summary

    • The voltages of a three-phase system are 120°out of phase with each other.

    • The two types of three-phase connections arewye and delta.

    • In a wye connection, the phase voltage is lessthan the line voltage by a factor of 1.732. Thephase current and the line current are thesame.

    • In a delta connection, the phase voltage is thesame as the line voltage. The phase current isless than the line current by a factor of 1.732.

  • 8/19/2019 Lecture1b-Three Phase Systems

    12/13

    1/03/20

    Exercise 1.1

    1. A single-phase voltage source with V = 100130   voltsdelivers a current I = 1010 A, which leaves the positiveterminal of the source. Calculate the source real and

    reactive power, and state whether the source delivers or 

    absorbs each of these. What is the type of the source?

     Ans: - 500 W, + 866 VAR

    2. An industrial plant consisting primarily of induction motor 

    loads absorbs 500 kW at 0.6 pf lag. (a) Compute the

    required kVA rating of a shunt capacitor to improve the

    power factor to 0.9 lag. (b) Calculate the resulting pf if a

    synchronous motor rated 500 HP with 90% efficiency

    operating at rated load and at upf is added to the plantinstead of the capacitor. Assume constant voltage. 1 HP =

    0.746 kW. Ans: (a) 424.5kVA (b) 0.808 lag

    Exercise 1.1

    3. Three loads are connected in parallel across a single-

    phase source voltage of 240 V (RMS). Load 1 absorbs

    12 kW and 6.667 kVAR; Load 2 absorbs 4 kVA at 0.96

    pf lead; Load 3 absorbs 15 kW at upf. Calculate the

    values of R and X, for the three parallel loads, for two

    cases: (a) Series combination of R and X, and (b)

    parallel combination of R and X.

     Ans: (a) R = 1.809 , X = 0.325 

    (b) R = 1.868 , X = 10.384 

  • 8/19/2019 Lecture1b-Three Phase Systems

    13/13

    1/03/20

    Exercise 1.2

    ?

    1. Find the current from the alternator.

     Ans: 61.45 A

    2. Two balanced Y-connected loads, one drawing 10 kW at 0.8

    pf lag and the other 15 kW at 0.9 pf leading, are connected

    in parallel and supplied by a balanced three-phase Y-

    connected, 480-V source. (a) Determine the source current.

    (b) If the load neutrals are connected to the source neutral

    by a zero-ohm neutral wire through an ammeter, what will

    the ammeter read? Ans: (a) 30.07 A (b) 0

    Exercise 1.2

    3. A three-phase line with an impedance of (0.2+j0.1) /phfeeds three balanced three-phase loads connected in

    parallel. Load 1: Absorbs a total of 150 kW and 120

    kVAR; Load 2: Delta connected with an impedance of 

    (150-j48) /ph; Load 3: 120 kVA at 0.6 pf leading. If theline-to-neutral voltage at the load end of the line is

    2000V (RMS), determine the magnitude of the line-to-

    line voltage at the source end of the line.

     Ans: 3478.62V