Recommended safety, installation, operating &charging procedures for Rolls LFP (LiFePO4) batteries.
LFPBATTERY
OPERATINGMANUAL
2
1. Safety 3 1.1 Warnings, Cautions and Notes 3 1.2 General Warning 3 1.3 Fire Risk 3 1.4 Electric Shock Risk 3 1.5 Chemical Risk 4 1.6Do’s 4 1.7DoNot’s 4 1.8 DC Motor Connection 4 1.9 Transportation Warning 42. Battery Operating Limits 5 2.1 Maximum Battery Operating Limits 5 2.2 Recommended Battery Operating Limits 53. Design Features & Components 6 3.1 Battery Management System (BMS) 6 3.2 Fuse 6 3.3 Terminals 64. Handling 65. Installation 7 5.1 Tools 7 5.2 Battery Location 7 5.3 Securing Battery 7
5.4 Installation 7 5.5 Parallel Battery Wiring 86. Networking 9 6.1 Rolls LFP Network 9 6.2ConfigurationwithPowerConversion andMonitoringDevices 97. Operation 9 7.1 On-Off / Reset 9 7.2 Charging 10 7.3ChargeCurve 10 7.4 Discharging 11 7.5 Storage 118. Protection and Faults 129.Service&Maintenance 13 9.1 Inspection 13 9.2 Firmware Updates 1310. Troubleshooting 13 10.1 Battery Will Not Turn On 1311. Recycling and Disposal 1312.S24-2800LFPTechnicalSpecifications 1413.S48-6650LFPTechnicalSpecifications 15
S24-2800LFP S48-6650LFP
3
1. Safety1.1 Warnings, Cautions, Notes and Symbols
Do not throw battery in the garbage. Do not dispose in fire.
Use personal protective equipment when working with batteries.
Additional information concerning important procedures and features of the battery. Read all the instructions before installation, operation and maintenance.
This product must be recycled and is made of recycled products.
• TheRollsLFPBatteryhasaBatteryManagementSystem(BMS)withintegratedsolidstaterelaytoreducetheriskoffire.• Primarysuppressionforalithiumbatteryfireiswater,thesecondarysuppressionisCO2,powderandhalon.
1.2 General Warning
1.3 Fire Risk
1.4 Electric Shock Risk
For wet and electrically uninsulated working conditions, electric shock risk is high, and can cause injury and death.
WARNING!
Important information regarding possible personal injury.
Important information regarding possible equipment damage.
Additional information concerning important procedures and features of the battery.
WARNING!
CAUTION!
NOTE!
It is important to operate the device with care to avoid undesirable consequences.
CAUTION!
Do not disassemble or modify the battery. If the battery housing is damaged, do not touch exposed contents.
CAUTION!
Risk of fire - No user serviceable parts inside.
WARNING!
MODEL
S24-2800LFP 24 V 29.2 V
S48-6650LFP 48 V 58.4 V
Maximum System Voltage
Nominal System Voltage
4
• Do protect terminals from short circuit before, during, and after installation•Dowearelectricallyinsulatedgloves• Do use electrically insulated tools• Do wear eye protection• Do wear safety toe boots / shoes• Do handle battery carefully• Do secure battery safely• Do always assume battery terminals are energized
1.5 Chemical Risk
1.6 Do’s
1.7 Do Not’s
1.8 DC Motor Connection
1.9 Transportation
Lithium batteries are a chemical risk if misoperated, mishandled or abused.
WARNING!
• Do not immerse battery in water• Do not lift or carry the battery during usage or operation• Do not operate or store battery outside of operating limits• Do not short circuit battery• Do not puncture battery•Donotexposebatterytoflames,orincinerate• Do not open battery case or disassemble battery• Do not wear rings, watches, bracelets or necklaces when handling or working near battery• Do not drop or crush battery• Do not lift battery by the terminal cables•Donotvibratebattery•Donotexposebatterytowaterorotherfluids• Do not expose battery to direct sunlight• Do not dispose of battery• Do not connect with other types of batteries• Do not expose battery to high temperatures• Do not install with other battery types or brands
Direct connection to DC motors, without proper safety protection including motor controllers, and external motor voltageclampingsystems(suchashighpoweranti-paralleldiodesorbrakingresistorsystems),mayresultindamage to the internal battery pack protection system which may result in unsafe situations. Please consult Rolls Battery Technical Support before directly connecting any motor loads.
Ifthebatteryisnotinstalledinequipment,itmustbetransportedintheoriginalpackageorequivalent.
Batteries are tested according to UN Handbook of Tests and Criteria, part III, sub section 38.3 (ST/SG/AC. 10/11/Rev.5).FortransportthebatteriesbelongtocategoryUN3480,Class9.
5
• Do protect terminals from short circuit before, during, and after installation•Dowearelectricallyinsulatedgloves• Do use electrically insulated tools• Do wear eye protection• Do wear safety toe boots / shoes• Do handle battery carefully• Do secure battery safely• Do always assume battery terminals are energized
2. Battery Operating Limits
2.1 Maximum Battery Operating Limits
2.2 Recommended Battery Operating Limits
Nominal Interruption Time - Peak Current Characteristic of Rolls LFP BMS
• Do not immerse battery in water• Do not lift or carry the battery during usage or operation• Do not operate or store battery outside of operating limits• Do not short circuit battery• Do not puncture battery•Donotexposebatterytoflames,orincinerate• Do not open battery case or disassemble battery• Do not wear rings, watches, bracelets or necklaces when handling or working near battery• Do not drop or crush battery• Do not lift battery by the terminal cables•Donotvibratebattery•Donotexposebatterytowaterorotherfluids• Do not expose battery to direct sunlight• Do not dispose of battery• Do not connect with other types of batteries• Do not expose battery to high temperatures• Do not install with other battery types or brands
The battery should not be operated outside the Maximum Operating Limits, the BMS will open its internal relay and disconnect the battery if any of the following limits are exceeded.
Although the battery is capable of performing up to the Maximum Battery Operating Limits noted, the following settings are recommended to maximize battery health and account for unforeseen external conditions.
*EffectsofACRipplemustbetakenintoconsiderationwhensizingandconfiguringyoursystem.
Maximum Operating Limit
Continuous Charge Current*
Continuous Discharge Current*
Charge Voltage
Operating Voltage (Min / Max)
Charge Temperature (Min / Max)
Discharge Temperature (Min / Max)
Storage Temperature (Min / Max)
130 Adc
130 Adc
54.4 V
44.8 V / 58.4 V
110 Adc
110 Adc
27.2 V
22.4 V / 29.2 V
0°C / 45°C (32°F / 113°F)
-20°C / 50°C (-4°F / 122°F)
-20°C / 45°C (-4°F / 113°F)
S48-6650LFPS24-2800LFP
600
500
400
300
200
100
0150 200 250 300 350 400
Intentional bypassing of BMS to operate the battery outside maximum and minimum limits voids warranty.
NOTE!
6
Recommended Operating Settings
Max Continuous Charge Current
Max Continuous Discharge Current
Charge Voltage (Bulk/Absorb)
Charge Voltage (Float)
Low Voltage Disconnect
Operating Temperature
< 92 A
< 92 A
54.4 V
53.6 V
48 V
< 78 A
< 78 A
27.2 V
26.8 V
24 V
20°C (68°F)
S48-6650LFPS24-2800LFP
3. Design Features & Components
3.1 Battery Management System (BMS)
BMS Monitor •Cellmodulevoltage •Batteryvoltage • Battery current • Battery temperature • Battery state of charge (SOC) Module Balancing • BMS performs balancing of cell modules
Protection & Fault Management • BMS sounds buzzer when fault limits are reached • BMS generates fault when maximum operating limits are reached •Faulteventscauseswitchtoopenandbatterytoshutdownaftera120sdelay
Communication Ports • BMS has an isolated USB and CAN communication.
Data Logging • Monitoring data •Faultandwarningevents •LoggeddataisaccessedusingthedashboardsoftwareviatheUSBport(Win32,Win64supported)
3.2 Fuse
Fuseprovidesback-upover-currentprotection. •Ablownfuserequiresreplacementbyaqualifiedinstaller. Contact Rolls Battery Technical Support for assistance.
3.3 Terminals
Terminals are button-type, M8 female.
4. Handling
• Battery should be set to off • Battery cables should be disconnected • Battery terminals should be protected • Battery handle should be used to lift battery • Battery should be handled by two people or mechanical lift equipment
Read Safety Section before handling the battery. WARNING!
7
5.1 Tools
• Insulated tools must be used • Voltmeter • Post cleaner and wire brush •Personalprotectiveequipment
5.2 Battery Location
Locatethebatteriesclosetotheinverterinordertominimizethelengthofthebatterycables.Careshouldbetakentoensureadequateclearanceabovethebatteriesismaintainedforaccesstobothbatteryandinverterconnectionsanddisconnects.ARollsBatteryWall-MountBracket(WMB-S48-6650LFP)isavailableforusewithRollsLFPS48-6650LFPmodel.
RollsLFPBatteryperformanceandservicelifewillbeoptimizedwhentheyareoperatedinanambienttemperatureof15°Cto25°C(59°Fto77°F).Careshouldbetakentoensurethatthebattery’stemperatureis>0°C(32°F)duringcharging.
5.3 Securing Battery
•Batterycanbestrappedinplacewithnon-conductivenylonstraps •Batterymayhaveholddownbracketsatthebaseofthebattery •ARollsBatteryLFPWall-MountBracket(WMB-S48-6650LFP)isavailableforusewithmodelS48-6650LFP
5.4 Installation
Batterycablesmustbesizedtothespecificationsrequiredbytheinvertercharger,andCoppermustcompressionbeinstalledluginaccordancewiththeM8”bolt(suppliedwithbattery)standardssetbytheauthorityhavinglocaljurisdiction.Donot use or install a battery temperature sensor. •ConfirmthatbatteryissettoOFF • If the battery circuit has a disconnect - open the disconnect to isolate battery • Cable connection points should also be kept clean •Broken,frayed,brittle,kinkedorcutcablesshouldneverbeused •Securethenewbattery-becarefulnottogroundtheterminalstoanymetalmounting,fixture,orbodypart •Connectbatterycables-connectthegroundcablelasttoavoidsparking • Terminals are button-type, M8 female - recommended torque is 9.0 Nm (6.64 ft-lb) • If the battery circuit has a disconnect - close disconnect to reconnect the battery • Set the battery to ON
All cable ends must be connected to battery terminals without any washers between terminal bushings and cable ends.
NOTE!
Read Safety Section before handling the battery.
Do not install Rolls LFP batteries in series. Select the appropriate Rolls LFP battery model for the voltage of your system.
WARNING!
CAUTION!
5. Installation
8
Terminal burnout is caused by: • Discharge currents exceeding allowable limits • Improper cable installation • Improper cable sizing • Improper terminal torque
5.5 Parallel Battery Wiring
To ensure proper balancing and load sharing between parallel batteries refer to the wiring diagram below. Lithium batteries areverysensitivetovoltageandundersizedbatterycableswillimpedebatteryandsystemperformance.Thethickness(crosssection)ofcableusedshouldexceedtherecommendedminimumfortheinverterchargerinstallationwheneverpossible.
Fiveormorebatteriesinparallelshouldbeinstalledusingabusbarconfiguration.Inabusbarconfigurationallbatterycablesetsshouldbethesamelengthregardlessofthebattery’sproximitytothebusbar(orcombinerbox).
Actualwiringrequirementsmayvary.Consultwiththeauthorityhavinglocaljurisdiction.
Without exception, product experiencing terminal burn out will not be replaced or repaired under warranty.
NOTE!
LOAD / CHARGER LOAD / CHARGER
LOAD / CHARGERLOAD / CHARGER
CHARGER CHARGER
INSTALLATION USING BUSBAR
LOAD CHARGER CHARGER LOAD
LOAD LOAD
All parallel cables should be the same length. All parallel cables should be the same length.
All parallel cables should be the same length. All parallel cables should be the same length.
All cables should be the same length.
INSTALLATION USING CABLES
9
6. Networking
6.1 Rolls LFP Network
TheAEBusisutilizedbyallnetworkedRollsLFPbatteriestocoordinateallvoltage,temperature,andcurrentdata.Network Terminators are required for proper functioning of the Rolls LFP network. Care should be taken to ensure they are installed properly.
6.2 Configuration with Power Conversion and Monitoring Devices
RollsLFPbatteriesmustbesetuptoworkwithPowerConversionandMonitoringdevicesineitheranOpenLooporClosedLoopconfiguration.ThechargeanddischargesettingsinaOpenLoopconfigurationaresetupthroughthecontrollerforthePowerConversiondeviceatthetimeofinstallation.InaClosedLoopconfiguration,chargeanddischargesettingsaredynamicallycontrolledbytheBMSoftheRollsLFPBatteryoveraconnectionwiththePowerConversiondevicenetwork.ClosedLoopcommunicationwithaPowerConversiondevicenetworkrequirestheuseofaRollsLFPConnectdeviceavailablefromyourRollsBatteryLFPbatterydistributorordealer.
ForClosedLoopandOpenLoopconfigurationdetailspleaserefertotheappropriateApplicationNoteforyourPowerConversiondeviceavailablefromtherollsbattery.comwebsite,orcontactyourRollsBatteryproviderforassistance.
Note:SchneiderElectricConextbrandeddevicescommunicateoverXanbusformingaClosedLoopconfigurationusingtheXanbusportlocatedontheRollsLFPbatteryanddonotrequiretheuseofaRollsLFPConnectdevice.RefertoApplicationNote885-0013ClosedLoopIntegrationwithXanbusEnabledSchneiderElectricConextProducts,fordetailed instructions.
7. Operation
7.1 On–Off / Reset
• To set the battery to ON press and hold switch for 2-3 seconds • To set the battery to OFF press and hold switch for 2-3 seconds
LOAD / CHARGER LOAD / CHARGER
LOAD / CHARGERLOAD / CHARGER
CHARGER CHARGER
INSTALLATION USING BUSBAR
LOAD CHARGER CHARGER LOAD
LOAD LOAD
All parallel cables should be the same length. All parallel cables should be the same length.
All parallel cables should be the same length. All parallel cables should be the same length.
All cables should be the same length.
INSTALLATION USING CABLES
Review operating limits. CAUTION!
10
7.2 Charging
BeforechargingthebatterymakesuretoreadandunderstandtheinstructionsthatcomewiththePowerConversiondevice.NeverattempttochargeabatterywithoutfirstreviewingandunderstandingtheinstructionsforthePowerConversiondevicebeing used. Do not use or install a battery temperature sensor.
1.ConnectthePowerConversiondevice’schargerleadstothebattery. 2. Ensure the charger and battery side connections are tight. 3. Set the charger to ON 4. Set the battery to ON
Spikesarefast,shortdurationelectricaltransientsinvoltage(voltagespikes),current(currentspikes),ortransferredenergy(energy spikes) in an electrical circuit. Voltage spikes usually happen when the AC/DC adapter is plugged in, or charge currentiscutoffquickly.Multivoltagechargersareconstructedusingtransformersthatmaybecapableofproducingspikesthat exceed the maximum ratings of the Rolls LFP battery. You must ensure that the charger being supplied: •Meetstherecommendedchargecurve •IncapableofexceedingRollsspecifiedmaximumterminalvoltages
7.3 Charge Curve
1. Charge at constant current to 3.4 V per cell module (Bulk). 2.Maintainconstantvoltage3.4Vpercellmodule(Absorption). 3. Terminate when charge current drops below 2A. 4. Optional Float at 3.35V per cell module (Float).
Always make sure the chargers charging curve meets the battery’s charging requirement; never charge a visibly damaged battery; never charge a frozen
battery.
CAUTION!
NOT ALL CHARGERS ARE CAPABLE OF CHARGING LITHIUM BATTERIES CONFIRM that your chosen charger is incapable of producing transient spikes
thatexceedthepublishedterminalvoltagelimitsforthebattery.
CAUTION!
11
Do not charge battery higher than 3.4 V per cell module.
Recommended charge current is 0.5C
Do not discharge battery below recommended minimum operating voltages.
Do not store a discharged battery. Recharge battery after every use. Batteries that have self-discharged to a
severely discharge state are not recoverable.
Do not discharge battery at rates greater than recommended operating currents.
CAUTION!
NOTE!
NOTE!
CAUTION!
NOTE!
Model I1 U1 U2
S24-2800LFP
S48-6650LFP
110 Adc maximum
130 Adc maximum
8S 27.2 VI2≤2A
26.8 V
16S 54.4 V 53.6 V
Cell Modules in Series
Termination Charge Current
7.4 Discharging
• Set the battery to ON • Set the load to ON •Recommendedlowvoltagecutoff:24V|48V
7.5 Storage
Systems should be stored out of direct sunlight in compliance with the following temperature conditions:
Batteriesshouldbeputintostorageat80%SOCandcheckedevery180daystoensuretheSOCdoesnotfallbelow20%.Self-dischargefrom80%-20%SOCaverages3%/monthat25°C/77°F.At20%SOCthebatterywillfullyself-dischargeinapproximately 2 months.
Minimum Storage Temperature -20°C / -4°F
Maximum Storage Temperature 45°C / 113°F
12
8. Protection & Faults
• BMS generates faults when maximum operating limits are reached. • BMS sounds a buzzer when fault limits are triggered. • BMS monitors the following information for faults and warning: 1.Cellmodulevoltage 2. Battery current 3. Battery temperature
Refer to device technical specification tables at the end of this manual for Fault Limits.
NOTE!
High Temperature
High Voltage
OverCurrent
Low SOC
Low Voltage
Inaccurate SOC displayed by PowerConversionsystem
Low Temperature
• Stop discharge or charge•Leavethebatterytocool
• If charging, stop the charge•Confirmproperchargealgorithmisbeingused
• Reduce current
• Stop discharge• Charge the battery
• Do not discharge the battery - if any discharge current is detected, this will force the battery into Low Voltage Fault
•ChargethebatteryinLowVoltageRecovery-ifnochargecurrentisdetected within 2 minutes the BMS will set the battery to OFF
•BatteryvoltagebasedSOCcalculationsprovidedbyPowerConversionsystemsdonotworkproperlywithLithiumbatteryvoltage.
• Use a Rolls LFP Discharge Indicator to display accurate SOC. To communicateaccurateSOCinaclosedloopPowerConversionsystem use a Rolls LFP Connect
• Stop discharge or charge
CORRECTIVE ACTIONS
13
9. Service & Maintenance
Batteries should be carefully inspected on a regular basis in order to detect and correct potential problems before they do harm.Thisroutineshouldbestartedwhenthebatteriesarefirstreceived.
9.1 Inspection
• Inspect for cracks in the battery casing •Checkbatteryterminalsandconnectionstomakesuretheyareclean,freeofdirt,fluidsandcorrosion • All battery cables and their connections should be tight, intact, and NOT broken or frayed • Replace any damaged batteries • Replace any damaged cables • Ensure correct torque (9.0 Nm) is used for the terminal bolts
9.2 Firmware Updates
VisitRollsBatteryTechnicalResourcespageatwww.rollsbattery.com/technical-resourcesforthelatestfirmware.Firmwareupdatesshouldbecompletedbyaqualifiedinstaller.ContactRollsBatteryTechnicalSupportforassistance.
10. Troubleshooting
10.1 Battery Will Not Turn On
11. Recycling and Disposal
Batteries must not be mixed with domestic or industrial waste. Rolls Battery LFP batteries are recyclable and must be processedthrougharecognizedrecyclingagencyordealer.PleasecontactRollsBatteryoryourservicingdistributorordealer for details.
Symptom
Symptom
Symptom
Description
Description
Description
Action
Action
Action
Does the battery turn on for a short time then turns itself off?
Doesthebatteryappeartoturnon,buthasnovoltageatitsterminals?
Was the battery left on or stored for extended periods of time?
ThebatteryislikelyinalowvoltageorlowSOC.
The battery fuse is likely blown.
The battery will turn itself off at 5% SOC. If left sitting at a low SOC, the battery mayhavedischargeditselfcompletelyandcannotbeused.
Connect to charger and turn on the battery.
Replace fuse. Contact Rolls Battery Technical Support for assistance.
Do not use. Replace and recycle.
14
12. S24-2800LFP TECHNICAL SPECIFICATIONS
Fuse 150 A Internal Fuse.
current protection
Fault Limits
Nominal Voltage
Discharge Protection
Charge Protection
LowTemperature - Discharge Protection
Low Temperature - Charge Protection
Under Voltage Protection
Cell Chemistry
Cell Modules
Self-Discharge 25°C / 77°F
25.6 V
< -20°C/-4°F for 120s
< -20°C/-4°F for 120s
module for 60s
< 2.5 V in any cell module for 5s
LiFePO4
8S 22P
20-25% SOC (battery off)
Charge Voltage 27.2 V
Maximum Voltage 29.2 V
Nominal Capacity 110 Ah
Minimum Voltage 20 V
Nominal Energy 2816 Wh
Max Continuous Charge Current
110 Adc
Max Continuous Discharge Current
110 Adc
Battery Dimensions (HxWxD)
Battery Weight
Shipping Dimensions (HxWxD)
Shipping Weight
Terminal
Terminal Hardware
Terminal Torque
Case Material
Enclosure IP Rating
Charge Temperature RangeDischargeTemperature Range
Storage Temperature Range
276 x 347.5 x 329.5 mm
40 kg
470 x 430 x 390 mm
48.4 kg
M8
M8 Stainless Steel Bolt, Flat Washer, Lock Washer (Supplied)
9.0 Nm
Powder Coated Cold Rolled Steel
IP 55
0°C/45°C (32°F/113°F)
-20°C/50°C (-4°F/122°F)
-20°C/45°C (-4°F/113°F)
Battery Management System (BMS)
Cell Balancing
Non-Volatile Memory
Lifetime Logged Data
Lifetime Logged Data
Communication Connectors
Integrated, with Solid State Relay (SSR)
Yes
• Time
• Balancing, Fault andRelay State
• Battery SOC, Current,Voltage,Temperature
• Charge Energy In/Out
• Isolated USB• Isolated CAN (AEBus)
USB Type A FemaleRJ45 Jack x2
UN 38.3, IEC 62133 UL1973
Pin 3 AEBus CAN GNDPin 4 AEBus CAN LowPin 5 AEBus CAN HighPin 6 AEBus + 5V
RJ45 AEBus
Nominal Energy
15
13. S48-6650LFP TECHNICAL SPECIFICATIONS
Fuse 150 A Internal Fuse.
current protection
Fault Limits
Nominal Voltage
Discharge Protection
Charge Protection
LowTemperature - Discharge Protection
Low Temperature - Charge Protection
Under Voltage Protection
Cell Chemistry
Cell Modules
Self-Discharge 25°C / 77°F
51.2 V
< -20°C/-4°F for 120s
< -20°C/-4°F for 120s
module for 60s
< 2.5 V in any cell module for 5s
LiFePO4
16S 26P
20-25% SOC (battery off)
Charge Voltage 54.4 V
Maximum Voltage 58.42 V
Nominal Capacity 130 Ah
Minimum Voltage 40 V
Nominal Energy 6656 Wh
Max Continuous Charge Current
130 Adc
Max Continuous Discharge Current
130 Adc
Battery Dimensions (HxWxD)
Battery Weight
Shipping Dimensions (HxWxD)
Shipping Weight
Terminal
Terminal Hardware
Terminal Torque
Case Material
Enclosure IP Rating
Charge Temperature RangeDischargeTemperature Range
Storage Temperature Range
375 x 347.5 x 471.5 mm
87 kg
570 x 440 x 570 mm
98.9 kg
M8
M8 Stainless Steel Bolt, Flat Washer, Lock Washer (Supplied)
9.0 Nm
Powder Coated Cold Rolled Steel
IP 55
0°C/45°C (32°F/113°F)
-20°C/50°C (-4°F/122°F)
-20°C/45°C (-4°F/113°F)
Battery Management System (BMS)
Cell Balancing
Non-Volatile Memory
Lifetime Logged Data
Lifetime Logged Data
Communication Connectors
Integrated, with Solid State Relay (SSR)
Yes
• Time
• Balancing, Fault andRelay State
• Battery SOC, Current,Voltage,Temperature
• Charge Energy In/Out
• Isolated USB• Isolated CAN (AEBus)
USB Type A FemaleRJ45 Jack x2
UN 38.3, IEC62133 UL1973
Pin 3 AEBus CAN GNDPin 4 AEBus CAN LowPin 5 AEBus CAN HighPin 6 AEBus + 5V
RJ45 AEBus