Machinery Space

Fine Water Spray

Nozzles and Valves

Marine MED Approved

Page 2: Machinery Space Fine Water Spray Nozzles and Valvesvidaps.dk/wp-content/uploads/150714-1-Flyer-Marine-TF_LA.pdf · Machinery Space Fine Water Spray Nozzles and Valves Marine MED Approved

We reserve the right to alter the information without further notice. Images and diagrams are for information only and may not be accurate.

VID Fire-Kill Aps

Svalbardvej 13 I DK-5700 Svendborg I Ph. +45 6262 1024

Fax. +45 6262 3661 I Mail: [email protected] I Web: www.vid.eu

© VID Fire-Kill 2015

Total Flooding Bilge

Model B1 Open Horizontal

Low-Pressure Fine Water Spray Nozzle

DnV-GL and LR Type approval and DnV-GL MED-B EC Type

Examination Certificate for machinery space and cargo pump

room in accordance with IMO MSC Circ. 1165 as amended by

MSC.1/Cic.1269 and MSC.1/Circ.1386.

Min. operation time: 30 min including 1% AFFF

Water pressure: 6—16 bar

Max spacing: 1,5 m x 2 m

Max. height bilge: 1 m

Nozzle inst. Height: 0,3 m to 0,6

Process connection: 1/2” BSP / 1/2” BSP-T / 1/2” NPT

Material: Brass with NiSn

Stainless steel

Filter: AISI 316

Total Flooding

Model K6 Open Pendent

Low-Pressure Fine Water Spray Nozzle

DnV-GL and LR Type approval and DnV-GL MED-B EC Type

Examination Certificate for machinery space and cargo pump

room in accordance with IMO MSC Circ. 1165 as amended by

MSC.1/Cic.1269 and MSC.1/Circ.1386.

Volume: 4520 m3 5036 m3

Min. operation time: 30 min

Water pressure: 8—16 bar 9—16 Bar

Max spacing: 3 m x 3 m 3 m x 3 m

Max. height: 10 m 10 m

Process connection: 1/2” BSP / 1/2” BSP-T / 1/2” NPT

Material: Brass with NiSn

Stainless steel

Filter: AISI 316

Model C-EL Dry Pipe Zone Valve for

Low-Pressure Water Mist System

The VID Fire-Kill Model C-EL Electrically Operated Control

Valve is a series of FM Approved robust and reliable deluge,

angle positioned, pilot controlled valves created entirely in

Stainless Steel (316L) and designed for operating in open

deluge systems as a zone valve or a full flooding/deluge valve,

capable of functioning under harsh conditions and designed

to be connected to systems where no corrosion is allowed.

Max. working press.: 232 psi 16 Bar

Test pressure: 348 psi 24 Bar

Voltage: 24 VDC /8W NC solenoid

24 VDC / 10W Impulse solenoid

Dimension: 2” and 3” DN50 and DN80

INNOVATIVE FIRE PROTECTION SOLUTIONS

Local Application

Model K6 Open Pendent

Low-Pressure Fine Water Spray Nozzle

DnV-GL and LR Type approval and LR MED-B EC Type Exami-

nation Certificate for local application in accordance with

IMO MSC Circ. 1387 as amended by MSC.1/Cic.1269 and

MSC.1/Circ.1386.

Min. operation time: 20 min

Water pressure: 12,5—16 bar

Max spacing: 1,5 m x 1,5 m

Max. distance to object: 11 m

Min. distance to object: 0,75 m

Process connection: 1/2” BSP / 1/2” BSP-T / 1/2” NPT

Material: Brass with NiSn

Stainless steel

Filter: AISI 316