Upload
others
View
2
Download
0
Embed Size (px)
Citation preview
17-1099-IR-DRAFT-JWA.doc
May 10, 2018 (Revised August 22, 2018) Ponderosa Management 4876 Barefoot Resort Bridge Road, Suite C North Myrtle Beach, South Carolina 29582 Attention: Ms. Kelly White Reference: Structural Engineering Services
Barefoot Resort and Golf Beach Cabana Complex Clubhouse and Site Structural Inspection and Assessment Becht Engineering BT Project Number: 17-1099
Dear Ms. White:
On February 22nd and 23rd, 2018, James Anderson, PE, Principal Engineer of this
office, conducted a site visit to the Barefoot Resort and Golf Beach Cabana
Complex in North Myrtle Beach, South Carolina. The purpose of our site visit was
to inspect and document the construction and condition of the
Clubhouse/Cabana Structure. Our observations, opinions and recommendations
follow a brief description of the structure and site layout. It is our understanding
that you have requested these inspection and assessment services as they relate
to an overall rehabilitation/maintenance program.
General
The Barefoot Resort Beach Cabana Complex is located at 4611 S. Ocean
Boulevard in North Myrtle Beach, South Carolina. The complex backs to the
Atlantic Ocean and faces S. Ocean Boulevard to the north. The structure is a
two-level, timber framed structure that is supported on timber piles and concrete
grade beams. The lower level is an open floor plan constructed of concrete slab
on grade with breakaway walls at the sides. The second level is constructed of
timber joists supported on engineered timber girders that bear on timber piles
below. The roof framing is timber post-and-beam construction. There is a
staircase to the second level at the front of the building, with a landing and two
opposing lower flights to grade. There is a second, U-shaped staircase at the rear
of the building. The turnaround between the upper and lower flights is also a pier
access to the beach area. There is a 2-level deck at the rear of the building,
Ms. Kelly White
Barefoot Resort & Golf Beach Cabana 2 May 10, 2018
17-1099-IR-DRAFT-JWA.doc
accessed from the upper level of the cabana structure, or from the rear stairway.
There is an elevator with a timber framed lead ramp for accessibility access to the
upper level located at the left (west) side of the building.
The cladding and trim materials for the clubhouse consist of standing seam metal
roofing, fiber-cement siding in both clapboard and shake styles, painted timber
trim elements and stucco finishes at the lower level (breakaway walls). The
decking materials used throughout the building are 5/4 thickness composite
planks.
There are gated (keyfob-access) pavered parking areas located to the north and
south of S. Ocean Boulevard.
In preparation of this report and prior to our site inspections, we were provided
with copies of signed and sealed design drawings for the clubhouse, including
the following.
Architectural drawings prepared by Carter Architecture, Inc. and dated
February 8, 2002.
Structural Engineering drawings prepared by Georgetown Construction
Services (GCS) and dated January 30, 2002.
Electrical Engineering Drawings prepared by Rast and Associates, Inc. and
dated January 30, 2002.
Plumbing Engineering Drawings prepared by Rast and Associates, Inc. and
dated January 30, 2002.
Onsite we met with you, your Director of Maintenance and an
Engineering/Maintenance Staff person, who provided us with a brief history of
pertinent information, and assisted us with stepladder movement and access to
gated areas.
Our inspection program was visual in nature and was limited to those
elements/areas that were reasonably visually accessible from grade or via ladder.
Observations
Generally, the structure is in sound condition with no signs of significant shifting,
settlement or structural distress. The visible timber framing elements (joists, rafters,
beams, girders, piles) were in generally fair to good condition. They appear to be
Ms. Kelly White
Barefoot Resort & Golf Beach Cabana 3 May 10, 2018
17-1099-IR-DRAFT-JWA.doc
normally weathered for their age and exposure. Reportedly, an engineered
laminated veneer lumber (LVL) girder connection failed at a post connection at
the interior (south) post support for the rear landing. At the time of our inspection,
the connection was restored by installation of a new hanger, in addition to
installation of a timber post beneath that end of the girder.
We observed the joist framing to be in fair condition, with no significant signs of
structural distress or deflection. We observed the floor joist framing throughout the
structure to be single joists at 16” on center.
We observed several ancillary timber structural or trim components which were
moderately to severely locally deteriorated. The observed deteriorated elements
are typically timber balustrades of a guardrail system or trim elements.
The connections between structural elements, whether by dowel-type fastening
(nails, screws, etc.), or by pre-manufactured hangers or connector plates are
typically in fair to poor condition, typified by moderate to severe levels of
corrosion. It is our understanding that many of the premanufactured hangers
have been replaced over time.
The decking is attached with screw fasteners, some of which are significantly
corroded and/or overdriven, resulting in “mushroomed” penetrations in the
decking. At each stair way, the treads and risers are constructed of composite
decking, which spans between two outer stringers and supported at the mid-span
by a single interior stringer.
We observed a visible downward sag at the cupola portion of the ridge at the
roof. There are noticeable gaps at joints between framing members of the
cupola structure. We did not observe any fastener hardware or connections of
these members, such as hangers or angles.
Drawing Review
According to Sheet S3 of the Structural Engineering Drawings, the cabana
structure was designed in accordance with the 2000 International Building Code
(IBC), with the following live loads listed:
Roof: 16 PSF (pounds per square foot)
Attic: 20 PSF
Ms. Kelly White
Barefoot Resort & Golf Beach Cabana 4 May 10, 2018
17-1099-IR-DRAFT-JWA.doc
Floor: 40 PSF
Wind: 130 mph (Exposure C)
The framing plan shown on Sheet S2 and Detail G of Sheet S3 depict knee braces
installed between the piers and dropped girders at the perimeter side walls of the
main structure.
The joist framing for the floor/deck areas of the cabana are listed as single (or
double) nominal 2x sawn lumber joists of varying depths as follows:
- Double 2x12s @ 16” on center at the front most (northern) main building area
(16’-6” span)
- Double 2x12s @ 16” on center at the upper level deck at the rear of the main
building (12’-6” span)
- Single 2x10s @ 16” on center at the lower level deck at the rear of the upper
level deck. There are two spans of joists at this area, 10’-6” and 9’-6” from
front to back respectively.
The roof construction is depicted as heavy timber posts-and-beams and the roof
sheathing is depicted as 5/8” plywood over tongue and groove decking. The
floor sheathing is depicted as ¾” Sturd-i-floor or ½” CDX grade subfloor. Full depth
blocking is depicted at the gable ends of the roof and floor framing bays.
The structural drawings do not depict any information for the construction of the
stair ways, the boardwalk at the rear of the cabana structure, or the post
connections/anchorage for guardrails throughout the building.
Conclusions and Recommendations
1. The building code under which the cupola was designed is the 2000
International Building Code (IBC2000). Table 1607.1 of IBC2000 lists the
minimum uniformly distributed live loads for structures and their
occupancies. Because the cabana structure is considered a “public
room” (including the attached deck areas, which shall be designed
according to the occupancy served) the minimum uniform live load which
should be considered for design is 100 PSF. We analyzed the existing joist
framing in each framing bay for a live loading of both 40 PSF (as designed)
and 100 PSF (as required). The results of our analyses indicate that the
existing joist framing is adequate to support a 40 PSF live load, but
inadequate to support a live load of 100 PSF. The existing floor framing is
Ms. Kelly White
Barefoot Resort & Golf Beach Cabana 5 May 10, 2018
17-1099-IR-DRAFT-JWA.doc
not adequate to support the code prescribed minimum live loads. We
recommend additional sister joists be installed alongside the existing joists.
We also recommend that intermediate blocking be installed between joists,
as required by Section 2308.8.5 of IBC2000. We have also analyzed the
existing piles for their capacity to support the additional framing and live
load and our analysis indicates that they are adequate to support the
revised/additional loadings.
Our probable cost estimate for this work is approximately $22/SF or
$50,000.00.
2. The hardware (nails, screws, fasteners, straps and hangers) throughout the
Cabana are fairly to severely corroded. Many of the severely corroded
hangers and fasteners are deteriorated beyond their useful service life and
should be replaced immediately. Additionally, we recommend that all
remaining fasteners be replaced with a corrosion-resistant coating (Z-Max
by Simpson, e.g.) or with stainless steel or corrosion resistant materials.
We recommend installation of fasteners, straps and hold-downs where
specified in the design drawings. Specifically, at the cupola connection to
the roof framing. We recommend the installation of visible (external)
hangers at the roof rafter to wall structure connections. The depicted
connection is concealed after installation of the roof sheathing and we
were unable to verify its installation during our inspection. We observed
several toe-nailed connections at the rafter to plate connection, which are
an inadequate means of a structural connection.
Our probable cost estimate for this work is approximately $10,000.00, much
of which can be achieved during installation of the sistered framing in item
1, above (hangers, etc.).
3. The design drawings depict knee bracing at the upper floor level of the
main cabana structure which was not installed. Knee bracing is depicted
in Detail G/S3 and located on Drawing S2 of the design drawings. We
recommend installation of lateral bracing, such as the depicted knee
bracing, at the upper floor framing level.
Our probable cost estimate for this work is approximately $3,000.00.
Ms. Kelly White
Barefoot Resort & Golf Beach Cabana 6 May 10, 2018
17-1099-IR-DRAFT-JWA.doc
4. The design drawings do not depict a structural connection at the base of
the guardrail posts. Because the guardrail posts are part of a life-safety
element or system, we recommend installation of appropriate
post/guardrail connections, such as additional blocking and dowel-type
fasteners below the decking.
Our probable cost estimate for this work is approximately $2,500.00.
5. Detail G1/A300 of the Architectural drawings depict the installation of 2x
composite stair treads over 2x12 stringers spaced at a maximum of 16” on
center. The stairs are typically constructed using three 2x stringers, resulting
in a spacing of approximately 20”. We recommend the installation of stair
tread material which is capable of supporting the intended live loads at the
constructed spans.
Our probable cost estimate for this work is approximately $20,000.00.
6. The observed breakaway wall panels are not intended to be mechanically
connected at their side edges to the piers/piles. However, because some
of the breakaway wall panels serve as exterior walls to storage and/or
mechanical rooms, we recommend these joints be sealed to prevent
rodent/insect infiltration.
Our probable cost estimate for this work is approximately $1,500.00.
It is our understanding that our inspection services were requested as it relates to
intended improvements or modifications to the existing building in order to
comply with building codes and regulations. According to the City of North
Myrtle Beach Building Department Official, a “substantial improvement” to a
building is defined as
Any combination of repairs, reconstruction, alteration, or
improvements to a building, taking place during a five year period,
in which the cumulative cost equals or exceeds fifty (50) percent of
the market value of the building. Substantial improvement of a non-
conforming building is prohibited. The term does not apply to
improvements required by health, sanitary, or fire and life safety
codes which are solely necessary to assure safe living conditions.
Ms. Kelly White
Barefoot Resort & Golf Beach Cabana 7 May 10, 2018
17-1099-IR-DRAFT-JWA.doc
Our probable cost estimates for the above recommendations sum to
approximately $87,000.00. Including a 15% increase for design and
contingencies, our probable cost budget estimate for this work is $100,000.00.
Considering that many of the repairs recommended above are primarily related
to life safety issues, it is our opinion that the existing structure is viable for
continued use as intended with a continued program of maintenance and minor
repairs.
Any narrative recommendations made in our report are not a substitute for
engineering construction documents. Detailed design drawings are required for
the proper installation of structural elements. Please be advised that if our
recommendations are implemented without design drawings, we are to be held
harmless for deficiencies arising from work proceeding without our direction.
Under these conditions, we are to be held harmless for any defects in the work
and/or its effects on any property or persons.
This report was prepared for, and is for the exclusive use of, our client and is not
intended for any other purpose. Our observations, conclusions and
recommendations are based on information available at the time of our
inspections. Should additional information become available, we reserve the
right to determine the relevance and effect(s), if any, of the new information on
our conclusions and recommendations, and to revise our opinions, conclusions
and recommendations as necessary, if warranted.
We appreciate this opportunity to provide our structural engineering services. If
you have any questions or comments, please do not hesitate to call.
Very truly yours, BECHT ENGINEERING BT, INC.
James W. Anderson, PE Principal Engineer
Ms. Kelly White
Barefoot Resort & Golf Beach Cabana 8 May 10, 2018
17-1099-IR-DRAFT-JWA.doc
Figure (1) – Aerial view of the Barefoot Resort & Golf Beach Cabana Site. S. Ocean Boulevard is towards the top and the Atlantic Ocean (not visible) is to the
south.
Ms. Kelly White
Barefoot Resort & Golf Beach Cabana 9 May 10, 2018
17-1099-IR-DRAFT-JWA.doc
Photo 1 – Front (North) elevation of the cabana structure.
Ms. Kelly White
Barefoot Resort & Golf Beach Cabana 10 May 10, 2018
17-1099-IR-DRAFT-JWA.doc
Figure 2 – Framing Plan for the Cabana, Shown on Sheet S2. Green arrow
indicates location/direction of Photo Number 9.
Knee Brace Notation Dbl Joist Framing Notation
Joist Bay 1 (Cabana)
Joist Bay 2 (Upper Deck)
Joist Bay 3 (Lower Deck)
Joist Bay 4 (Lower Deck)
Ms. Kelly White
Barefoot Resort & Golf Beach Cabana 11 May 10, 2018
17-1099-IR-DRAFT-JWA.doc
Figure 3 – Detail G (Knee Brace/Dropped Girder Connection on Sheet S3.
Ms. Kelly White
Barefoot Resort & Golf Beach Cabana 12 May 10, 2018
17-1099-IR-DRAFT-JWA.doc
Photo 2 – Joist Framing (single joists). Engineered girder is to left in photo and railing post anchorage is indicated. Photo of joists in Bay 2, taken looking east.
Ms. Kelly White
Barefoot Resort & Golf Beach Cabana 13 May 10, 2018
17-1099-IR-DRAFT-JWA.doc
Photo 3 – example of corroded fasteners at railing connection.
Ms. Kelly White
Barefoot Resort & Golf Beach Cabana 14 May 10, 2018
17-1099-IR-DRAFT-JWA.doc
Photo 4 – Example of severely corroded joist straps at dropped girder.
Ms. Kelly White
Barefoot Resort & Golf Beach Cabana 15 May 10, 2018
17-1099-IR-DRAFT-JWA.doc
Photo 5 – Example of toe-nailed roof rafter to wall connection. Note moderate corrosion of fasteners.
Ms. Kelly White
Barefoot Resort & Golf Beach Cabana 16 May 10, 2018
17-1099-IR-DRAFT-JWA.doc
Photo 6 – Example of corroded, overdriven or missing deck fasteners.
Ms. Kelly White
Barefoot Resort & Golf Beach Cabana 17 May 10, 2018
17-1099-IR-DRAFT-JWA.doc
Photo 7 – Ridge at roof showing visible downward deflection at cupola structure. (Arrows indicate direction of slope at ridge, not to scale.) Line included for
additional reference.
Ms. Kelly White
Barefoot Resort & Golf Beach Cabana 18 May 10, 2018
17-1099-IR-DRAFT-JWA.doc
Photo 8 – Example of “mushroomed” decking and (overdriven/improper) fasteners at elevator landing area.
Ms. Kelly White
Barefoot Resort & Golf Beach Cabana 19 May 10, 2018
17-1099-IR-DRAFT-JWA.doc
Photo 9 – example of lack of knee (lateral) bracing at pile/girder connections. Photo location shown on Figure 2.
Ms. Kelly White
Barefoot Resort & Golf Beach Cabana 20 May 10, 2018
17-1099-IR-DRAFT-JWA.doc
Photo 10 – Example of gap between breakaway panels and timber piles.
NISSAN OWNERS MANUALS