2 Features Choice of 4 inverse time curves and 3 definite time ranges by switched selection. Wide setting range of 0.05 x I n to 2.4 x I n in steps of 0.05 x I n . Time multiplier range 0.05 to 1 on all seven characteristics. Separate led indicators provided on each measuring board to show time delayed and instantaneous operations. Led start indicators provided to facilitate testing. Separate output contacts provided for time delayed phase fault, instantaneous phase fault, time delayed earth fault and instantaneous earth fault operations. Low ac burden. Suitable for use with separate direction relay. Accurately follows time curves to BS142 and IEC255. High resetting ratio. Fast resetting time. Positive, calibrated settings by means of switches. Internal dc auxiliary power supply operating over a wide input range. Separate test mode with trip test feature. Indication of power to the measuring board. Non-volatile memory for time delayed and instantaneous led indicators. Midos Figure 1: Relay type MCGG 62 withdrawn from case. Models available MCGG 22 Single phase overcurrent with instantaneous element. MCGG 42 Two phase overcurrent with instantaneous elements. MCGG 52 Two phase overcurrent plus earth fault with instantaneous elements. MCGG 53 Two phase overcurrent (with polyphase measurement) plus earth fault with instantaneous elements. MCGG 62 Three phase overcurrent with instantaneous elements. MCGG 63 Three phase overcurrent (with polyphase measurement), with instantaneous element. MCGG 82 Three phase overcurrent plus earth fault with instantaneous elements. Associated publications: Midos System R6001 Directional Relay R6003 3 Phase 2 Phase Single Phase Measuring Case Model overcurrent overcurrent or earthfault boards size inst inst inst MCGG 22 1 4 MCGG 42 2 6 MCGG 52 3 8 MCGG 53 2 8 MCGG 62 3 6 MCGG 63 1 6 MCGG 82 4 8 Type MCGG 22, 42, 52, 53, 62, 63 & 82 Overcurrent Relay for Phase and Earth Faults

MCGG OCR

Embed Size (px)

Citation preview

Page 1: MCGG OCR

Midos

Figure 1: Relay type MCGG 62 withdrawn from case.

Type MCGG 22, 42, 52,53, 62, 63 & 82Overcurrent Relay forPhase and Earth Faults

Features

Choice of 4 inverse time curvesand 3 definite time ranges byswitched selection.

Wide setting range of 0.05 x In to2.4 x In in steps of 0.05 x In.

Time multiplier range 0.05 to 1 onall seven characteristics.

Separate led indicators providedon each measuring board to showtime delayed and instantaneousoperations.

Led start indicators provided tofacilitate testing.

Separate output contacts providedfor time delayed phase fault,instantaneous phase fault, timedelayed earth fault andinstantaneous earth faultoperations.

Low ac burden.

Suitable for use with separatedirection relay.

Accurately follows time curves toBS142 and IEC255.

High resetting ratio.

Fast resetting time.

Positive, calibrated settings bymeans of switches.

Internal dc auxiliary power supplyoperating over a wide input range.

Separate test mode with trip testfeature.

Indication of power to themeasuring board.

Non-volatile memory for timedelayed and instantaneous ledindicators.

2

Models available

MCGG 22

Single phase overcurrent withinstantaneous element.

MCGG 42

Two phase overcurrent withinstantaneous elements.

MCGG 52

Two phase overcurrent plus earth faultwith instantaneous elements.

MCGG 53

Two phase overcurrent (withpolyphase measurement) plus earthfault with instantaneous elements.

MCGG 62

Three phase overcurrent withinstantaneous elements.

MCGG 63

Three phase overcurrent (withpolyphase measurement), withinstantaneous element.

MCGG 82

Three phase overcurrent plus earthfault with instantaneous elements.

Associated publications:

Midos System R6001Directional Relay R6003

3 Phase 2 Phase Single Phase Measuring CaseModel overcurrent overcurrent or earthfault boards size

† inst † inst † instMCGG 22 1 4MCGG 42 2 6MCGG 52 3 8MCGG 53 2 8MCGG 62 3 6MCGG 63 1 6MCGG 82 4 8

Page 2: MCGG OCR

Switch position Operating(0) (1) characteristic

Trip test

Standard inverse sec SI

Very inverse sec VI

Extremely inverse sec EI

Long time earth fault sec LT

Definite time 2 seconds D2

Definite time 4 seconds D4

Definite time 8 seconds D8

Table1: Operating time characteristics with corresponding switch positions.

t =0.14

(I0.02 – 1)

t =13.5(I – 1)

t =80

(I2 – 1)

t =120

(I – 1)

Application

The relay can be used in applicationswhere time graded overcurrent andearth fault protection is required.

The relay can be used to provideselective protection for overhead andunderground distribution feeders.Other applications include back-upprotection for transformers, generatorsand HV feeder circuits and theprotection of neutral earthing resistors.

With all the current/timecharacteristics available on one relay,a standard relay can be orderedbefore detailed co-ordination studiesare carried out – a distinct advantagefor complex systems. Also, changes insystem configuration can be readilyaccommodated.

An instantaneous element with lowtransient overreach is incorporatedwithin each phase or earth faultmeasuring board. This can be easilydisabled in applications where it isnot required.

For applications where theinstantaneous earth fault element isrequired to have a sensitive settingwhilst remaining stable on heavythrough faults the use of a stabilisingresistor is recommended. The currenttransformers for this application mustsatisfy the criteria detailed under‘Current transformer requirements’ inTechnical Data.

The total impedance of the relay andthe series stabilising resistor is usuallylow enough to prevent the currenttransformers developing voltages over2kV during maximum internal faults,but in some applications a non-linearresistor is required to limit this voltage.

Non-standard resistance values andnon-linear voltage limiting devices areavailable.

Description

This range of MCGG relays isdesigned so that versions areavailable with separate measuringboards for each phase or earth faultinput; alternatively, phase inputs maybe combined on to one board forpolyphase measurement (see table).These boards, together with the othercircuits of the relay, are contained in

a single plug-in module which issupplied in a size 4, 6 or 8 Midoscase. The case incorporates one ortwo terminal blocks for externalconnections. Removal of the moduleautomatically short circuits the currenttransformer connections by means ofsafety contacts within the caseterminal block. For added security,when the module is removed, the ctcircuits are short circuited before theconnections to the output contacts andthe dc supply are broken. The relayuses solid state techniques, eachmeasuring board utilising a micro-computer as a basic circuit element.The current measurement, whetherperformed on a single phase orpolyphase input, is performed via ananalogue-to-digital converter.Application diagrams are provided inFigures 2 to 8 (inclusive) showingtypical wiring configurations.

Each measuring board has a built-in‘power off’ memory feature for thetime delayed and instantaneous ledindicators.

Power to each measuring board maybe tested whilst the relay is in service.without affecting the currentmeasurement. A test mode is alsoavailable to carry out a trip test on the

output relays. During this test, currentmeasurement is inhibited.

When required, directional controlcan be exercised over the relay byconnecting an output contact fromdirection relay type METI to theterminals provided.

Separate output contacts, capable ofcircuit breaker tripping, are providedfor time delayed phase faults,instantaneous phase faults, timedelayed earth fault and instantaneousearth fault operations.

Relay settings

Separate setting switches for eachmeasuring board are provided on therelay frontplate. These are used toselect the required time/currentcharacteristic, current and timemultiplier settings.

Selection of time characteristics

The current/time characteristicselection is carried out by means ofthree switches (identified by symbol on the nameplate).

Table 1 gives the basic operatingcharacteristic and the settings of theswitches.

3

Page 3: MCGG OCR

Time multiplier setting

The time given by each of theoperating characteristics must bemultiplied by the time multiplier togive the actual operating time of therelay. This control is marked xt = Σwhere Σ is the sum of all the switchpositions.

The range of multiplication is from0.05x to 1.0x in steps of 0.025.

This acts as a conventional timemultiplier on the current dependentcharacteristics and gives the followingtime ranges for the definite timecharacteristics.

Operating Time rangecharacteristicss s2 0.1 to 2.0 in 0.05s steps4 0.2 to 4.0 in 0.1s steps8 0.4 to 8.0 in 0.2s steps

Figure 2: Type MCGG 22 nameplate

Current setting

Time delayed element

The current setting control is markedIs = Σ x In where Is is the currentsetting in amps, Σ is the sum of all theswitch positions and In is the relayrated current in amps.

4

Figure 3: Application diagram (10 MCGGSingle phase with instantaneous e

Notes:1. (a) CT sh

before(b) Short termin(c) Long termin

B

C

DirectioncontrolPhA

(See Note 3)

P2 P1A

(See Note 4)

S2 S1

(See Note

Vx+

Module terminal blockviewed from rear

Case earth

1 2

5 67 89 10

13 14

15 16

23 2426

27 28

Each measuring board provides asetting range of 0.05 x In to 2.4 x Inin steps of 0.05 x In.

Instantaneous element

The setting control of theinstantaneous element is markedIinst = Σ x Is where Σ is the sum of theswitch positions and Is is the timedelayed element setting.

When all switches are set to the left(at zero), or when the lowest switch isset to infinity regardless of thepositions of the other five switches, theinstantaneous feature is renderedinoperable. The range of adjustmentof finite settings is from 1x to 31x inunity steps.

Trip test

Current measurement is inhibited bysetting the curve selection switches to111. This causes all three led to flashonce per second. If the reset pushbutton is then pressed forapproximately six seconds, bothoutput relays associated with thatmeasuring board will operate.

22 02): static modular overcurent relay type MClement.

orting links make (b) and (c) disconnect.als break before (c).als

2. When directional control is required thof the directional relays should be conneContacts must close to inhibit overcurre

3. Earthing connections (CTs) are typical o4. CT connections are typical only.

A

C BPhase rotation

26

TMSsetting

Instsetting

Curveselection

IsµCPhA

24

23

27

28

Time delayeInst. trip

Inputcircuit

Ph

Currentsetting

PhI>Is

MCGG 22

al

IA

14

13

2)

VE

VEPowersupplycircuits

Case earth connection

Power supply healthy test

If, whilst the relay is in service, thereset button is pressed, all the ledsare iluminated, indicating that thereis power to the measuring boards.The leds are reset on releasing thepush button. During this test, normalcurrent measurement is not inhibited.

GG 22.

e contactscted as shown.nt relay.nly.

Indicatorreset

d trip

Outputcircuits

Ph

RL12

RL22

15

9

8

10

16

RL2–1

RL2–2

Phase faultinstantaneoustrip outputcontacts

1

5

7

6

2

RL1–1

RL1–2

Phase faulttime delayedtrip outputcontacts

Page 4: MCGG OCR

5

Figure 4: Application diagram (10 MCGG 42 03): static modular overcurent relay type MCGG 42.Two phase with instantaneous element.

Figure 5: Application diagram (10 MCGG 52 03): static modular overcurent relay type MCGG 52.Two phase plus earth fault with instantaneous elements.

Notes:1. (a) CT shorting links make

before (b) and (c) disconnect.(b) Short terminals break before (c).(c) Long terminals

2. When directional control is required the contactsof the directional relays should be connected as shown.Contacts must close to inhibit overcurrent relay.

3. Earthing connections are typical only.4. CT connections are typical only.

TMSsetting

Instsetting

Curveselection

IsµCPhA

Indicatorreset

49

50

21

22

TMSsetting

Instsetting

Curveselection

IsµCPhC

45

46

25

26

Time delayed tripInst. trip

Timedelayed tripInst. trip

Inputcircuit

Ph

Currentsetting

PhI>Is

Inputcircuit

Ph

Currentsetting

PhI>Is

42

38

36

37

41

RL2–1

RL2–2

Phase faultinstantaneoustrip outputcontacts

30

34

35

33

29

RL1–1

RL1–2

Phase faulttime delayedtrip outputcontacts

MCGG 42

DirectionalcontrolPhA

(See Note 2)IA

DirectionalcontrolPhC

IC

P2 P1A

B

C

(See Note 4)

A

C BPhase rotation

S2 S1

23

24

27

28

Module terminal blockviewed from rear

(with integral case earth strap)

Case earth

5 67 8

13 14

15 16

1 23 4

9 1011 12

17 18

19 20

21 22

23 24

25 26

27 28

33 34

35 36

41 42

29 30

37 38

45 46

47 48

49 50

RL12

RL22

Outputcircuits

Ph

1

(See Note 3)

14

13

Vx+VE

–VEPowersupplycircuits

Case earth connection

Phase rotation

3. Earthing connections are typical only.4. CT connections are typical only.

A

C B

IsµCPhA

Indicatorreset

49

50

21

22

Time delayed tripInst. trip

Inputcircuit

Ph

Current setting

PhI>Is

Phase faultinstantaneoustrip outputcontacts

Phase faulttime delayedtrip outputcontacts

MCGG 52

DirectionalcontrolPhA

(See Note 2)

IA

P2A

B

C

(See Note 4)

S2 S1TMS

settingInst

settingCurve

selection

8

1

5

7

6

2

RL3–1

RL3–2

Earth faulttime delayedtrip outputcontacts

30

34

35

33

29

RL1–1

RL1–2

41

38

36

37

42

RL2–1

RL2–2

15

9

10

16

RL4–1

RL4–2

Earth faultinstantaneoustrip outputcontacts

Outputcircuits

Directionalcontrol

E/F

IsµC

43

44

27

28

Time delayed tripInst. trip

Inputcircuit

Currentsetting I>Is

E/F

TMSsetting

Instsetting

Curveselection

IsµCPhC

45

46

25

26

Timedelayed trip

Inst. trip

Inputcircuit

Ph

Currentsetting

PhI>Is

DirectionalcontrolPhC

IC

TMSsetting

Instsetting

Curveselection

RL32

RL42

Outputcircuits

Ph

RL12

RL22

23

24

Module terminal blockviewed from rear

(with integral case earth strap)

Case earth

5 67 8

13 14

15 16

1 23 4

9 1011 12

17 18

19 20

21 22

23 24

25 26

27 28

33 34

35 36

41 42

29 30

37 38

45 46

47 48

49 50

43 44

P1

Notes:1. (a) CT shorting links make

before (b) and (c) disconnect.(b) Short terminals break before (c).(c) Long terminals

2. When directional control is required the contactsof the directional relays should be connected as shown.Contacts must close to inhibit overcurrent relay.

17

(See Note 3)

14

13

Vx+VE

–VEPowersupplycircuits

Case earth connection

Page 5: MCGG OCR

6

Figure 6: Application diagram (10 MCGG 53 02): static modular overcurent relay type MCGG 53.Two phase (with polyphase measurement), plus earth fault with instantaneous elements.

Notes:1. (a) CT shorting links make

before (b) and (c) disconnect.(b) Short terminals break before (c).(c) Long terminals

2. When directional control is required the contactsof the directional relays should be connected as shown.Contacts must close to inhibit overcurrent relay.

Phase rotation

3. Earthing connections are typical only.4. CT connections are typical only.

A

C B

IsµCPh

Indicatorreset

49

50

21

22

Time delayed tripInst. trip

Inputcircuit

Ph

Current setting

Ph

I>Is

Phase faultinstantaneoustrip outputcontacts

Phase faulttime delayedtrip outputcontacts

MCGG 53

DirectionalcontrolPhA

(See Note 2)

IA

P2A

B

C

(See Note 4)

S2 S1TMS

settingInst

settingCurve

selection

8

1

5

7

6

2

RL3–1

RL3–2

Earth faulttime delayedtrip outputcontacts

30

34

35

33

29

RL1–1

RL1–2

42

38

36

37

41

RL2–1

RL2–2

15

9

10

16

RL4–1

RL4–2

Earth faultinstantaneoustrip outputcontacts

Outputcircuits

Directionalcontrol

E/F

IsµC

43

44

27

28

Time delayed tripInst. trip

Inputcircuit

Currentsetting

I>Is

E/F

TMSsetting

Instsetting

Curveselection

45

46

25

26

DirectionalcontrolPhC

IC

RL32

RL42

Outputcircuits

Ph

RL12

RL22

23

24

Module terminal blockviewed from rear

(with integral case earth strap

Case earth

5 67 8

13 14

15 16

1 23 4

9 1011 12

17 18

19 20

21 22

23 24

25 26

27 28

33 34

35 36

41 42

29 30

37 38

45 46

47 48

49 50

43 44

P1

17

(See Note 3)

14

13

Vx+VE

–VEPowersupplycircuits

Case earth connection

Notes:1. (a) CT shorting links make

before (b) and (c) disconnect.(b) Short terminals break before (c).(c) Long terminals

2. When directional control is required the contactsof the directional relays should be connected as shown.Contacts must close to inhibit overcurrent relay.

Phase rotation

3. Earthing connections are typical only.4. CT connections are typical only.

A

C B

IsµCPhA

Indicatorreset

49

50

21

22

Time delayed tripInst. trip

Inputcircuit

Ph

Current setting

PhI>Is

Phase faultinstantaneoustrip outputcontacts

Phase faulttime delayedtrip outputcontacts

MCGG 62

DirectionalcontrolPhA

(See Note 2)

IA

P2A

B

C

(See Note 4)

S2 S1TMS

settingInst

settingCurve

selection

30

34

35

33

29

RL1–1

RL1–2

42

38

36

37

41

RL2–1

RL2–2

DirectionalcontrolPhC

Is

45

46

25

26

Time delayed tripInst. trip

Inputcircuit

Ph

Currentsetting

PhI>Is

IC

TMSsetting

Instsetting

Curveselection

IsµCPhB

47

48

23

24

Timedelayed trip

Inst. trip

Inputcircuit

Ph

Currentsetting

PhI>Is

Directionalcontrol

PhB

IB

TMSsetting

Instsetting

Curveselection

Outputcircuits

Ph

RL12

RL22

Module terminal blockviewed from rear

(with integral case earth strap)

Case earth

13 14

1

21 22

23 24

25 26

27 28

33 34

35 36

41 42

29 30

37 38

45 46

47 48

49 50

P1

µCPhC

1

(See Note 3)

14

13

Vx+VE

–VEPowersupplycircuits

Case earth connection

27

28

Figure 7: Application diagram (10 MCGG 62 03): static modular overcurent relay type MCGG 62.Three phase with instantaneous element.

Page 6: MCGG OCR

7

Figure 9: Application diagram (10 MCGG 82 03): static modular overcurent relay type MCGG 82.Three phase plus earth fault with instantaneous elements (4 wire system).

Figure 8: Application diagram (10 MCGG 63 02): static modular overcurent relay type MCGG 63.Three phase (with polyphase measurement) with instantaneous element.

Notes:1. (a) CT shorting links make

before (b) and (c) disconnect.(b) Short terminals break before (c).(c) Long terminals

2. When directional control is required the contactsof the directional relays should be connected as shown.Contacts must close to inhibit overcurrent relay.

Phase rotation

3. Earthing connections are typical only.4. CT connections are typical only.

A

C B

IsµCPh

Indicatorreset

49

50

21

22

Time delayed tripInst. trip

Current setting

Ph

I>Is

Phase faultinstantaneoustrip outputcontacts

Phase faulttime delayedtrip outputcontacts

MCGG 63

DirectionalcontrolPhA

(See Note 2)

IA

P2A

B

C

(See Note 4)

S2 S1TMS

settingInst

settingCurve

selection

30

34

35

33

29

RL1–1

RL1–2

42

38

36

37

41

RL2–1

RL2–2DirectionalcontrolPhC

45

46

25

26Inputcircuit

IC

47

48

23

24

Directionalcontrol

PhB

IB

Outputcircuits

Ph

RL12

RL22

Module terminal blockviewed from rear

(with integral case earth strap)

Case earth

5 67 8

13 14

15 16

1 23 4

9 1011 12

17 18

19 20

21 22

23 24

25 26

27 28

33 34

35 36

41 42

29 30

37 38

45 46

47 48

49 50

27

28

P1

1

(See Note 3)

14

13

Vx+VE

–VEPowersupplycircuits

Case earth connection

Phase rotation

A

C B

IsµCPhA

Indicatorreset

49

50

21

22

Time delayed tripInst. trip

Input circuitPh

Current settingPh I>Is

Outputcircuits

Ph

MCGG 82

DirectionalcontrolPhA

(See Note 2)

IA

P2 P1ABC

(See Note 4)

S2 S1

TMSsetting

Instsetting

Curveselection

IsµCPhB

47

48

23

24

Time delayed tripInst. trip

Input circuitPh

Current settingPh I>Is

Directionalcontrol

PhB

IB

TMSsetting

Instsetting

Curveselection

IsµCPhC

45

46

25

26

Time delayed trip

Inst. trip

Input circuitPh

Current settingPh I>Is

Directionalcontrol

phase PhC

IC

TMSsetting

Instsetting

Curveselection

IsµCE/F

43

44

27

28

Time delayed trip

Inst. trip

Input circuitE/F

Current settingE/F I>Is

Directionalcontrol E/F

TMSsetting

Instsetting

Curveselection

Outputcircuits

E/F

RL12

RL22

RL32

RL42

N

8

1

5

7

6

2

RL3–1

RL3–2

30

34

35

33

29

RL1–1

RL1–2

42

38

36

37

41

RL2–1

RL2–2

15

9

10

16

RL4–1

RL4–2

Phase faultinstantaneoustrip outputcontacts

Phase faulttime delayedtrip outputcontacts

Earth faulttime delayedtrip outputcontacts

Earth faultinstantaneoustrip outputcontacts

Notes:1. (a) CT shorting links make

before (b) and (c) disconnect.(b) Short terminals break before (c).(c) Long terminals.

2. When directional control is required the contactsof the directional relays should be connected as shown.Contacts must close to inhibit overcurrent relay.

3. Earthing connections are typical only.4. CT connections are typical only.

17

(See Note 3)

14

13

Vx+VE

–VEPowersupplycircuits

Case earth connection

Module terminal blockviewed from rear

(with integral case earth strap)

Case earth

5 67 8

13 14

15 16

1 23 4

9 1011 12

17 18

19 20

21 22

23 24

25 26

27 28

33 34

35 36

41 42

29 30

37 38

45 46

47 48

49 50

43 44

Page 7: MCGG OCR

8

Technical Data

Ratings AC Current (In) 1A or 5A

Frequency 50/60Hz

DC Supply (Vx) 24/54V, 48/125Vor 110/250V

Burdens

AC Burden Less than 0.25 VA for 1A relays andless than 0.5VA for 5A relays, at unitypower factor and at rated current onany setting.

The impedance of the relays over thewhole of the setting range (5% to240% rated current) is less than0.25Ω for 1A relays and less than0.02Ω for 5A relays and isindependent of current.

DC Burden Relay Relay typerating

MCGG MCGG MCGG MCGG

22, 63 42, 53 52, 62 82

24/54 1.5W 2.5W 3.0W 4.0W

48/125 2.0W 3.0W 3.5W 4.5W

110/250 2.5W 3.5W 4.0W 5.0W

The figures above are maxima underquiescent conditions. With outputelements operated they are increasedby up to 2.5W per element.

Current transformer requirements

Relay and ct Nominal Accuracy Accuracy Limiting leadsecondary rating output class limit current resistance –(A) (VA) (X rated current) one way (ohms)

1 2.5 10P 20 1

5 7.5 10P 20 0.15

Note: For 5A applications with longer leads, the ct rating can be increased insteps of 2.5VA where each step of 2.5VA is equivalent to additional0.06Ω lead resistance.

Instantaneous earth fault element

For installations where the earth fault element is required to have a sensitivesetting whilst remaining stable on heavy through faults, the use of a stabilisingresistor is recommended, the value of which will vary according to the specificapplication. If assistance is required in selecting the appropriate value,please consult the Applications Department of GEC ALSTHOM T&D Protection& Control.

Setting ranges Time delayed settings (Is), phase/earth fault measuring range: 5% to240% of In in 5% steps.Instantaneous setting (Iinst)1 x –31 x Is in 1 x 1s steps

Page 8: MCGG OCR

100

10

1.0

0.11 10 100

Definite 2 seconds

Definite 4 seconds

Definite 8 seconds

Longtime standbyearth faultt = 120

I – 1Standard inverse

t = 0.14I0.02 – 1

Very inverse

t = 13.5I – 1

Extremely inverse

t = 80I2 – 1

I( x Is)Current (multiple of setting)

Ope

ratin

g tim

e t (

seco

nds)

Figure 10: Time delayed overcurrent element – operation time characteristics.

Operating time

Time delayed element Shown in Figure 10

Operating characteristicsselectable to give: Standard inverse IDMT

Very inverse IDMTExtremely inverse IDMTLong time earth fault IDMTDefinite time 2s, 4s, 8s

Time multiplier setting 0.05 to 1.0 in 0.025 steps(applicable to all time characteristics)

Instantaneous elements Shown in Figure 11For settings of 5 x Is and above:<35ms at 2x instantaneous setting

Accuracy – reference conditions

Current setting (Is) Reference range 0.05In to 2.4In forMCGG 22, 42, 52, 62, 82 and E/Felement of MCGG53.

0.2In to 2.4In for phase faultelements of MCGG 53 and 63.

Input current Time characteristic Reference range

Standard inverseVery inverse 2 x Is to 31 x IsLong time inverse

Extremely inverse 2 x Is to 20 x Is

Definite time 1.3 x Is to 31 x Is

Ambient temperature 20°C

9

Page 9: MCGG OCR

10

240

220

200

180

160

140

120

100

80

60

40

20

01

Ope

ratin

g tim

e (m

s)

5-31

Figure 11: MCGG instantaneous opera

Frequency 50Hz to 60Hz

Time multiplier setting 1x

DC auxiliary voltage Reference ranges 24V to 54V48V to 125V110V to 250V

Accuracy – influencing quantities

Time multiplier On settings 0.05 to 1.0 ±2% or±30ms whichever is the greater

Ambient temperatureOperative range –25°C to +55°C

Variations over this rangeSetting current ±5%

Time characteristic Time variation

Standard inverseVery inverse ±5%Long time inverse

Extremely inverse ±7.5%

Definite time ±3%

FrequencySetting current ±1% over the range 47-62Hz

Operating time ±2% or ±30ms whichever is thegreater, over the range 47–52Hz or57–62Hz.

DC auxiliary voltage Vx dc(V) Operative range (V)

24/54 19 – 6048/125 37.5 – 150110/250 87.5 – 300

4Is

10 100

Current (multiple of instantaneous setting)

Iinst = 1Is

2Is3Is

Is

ting times (various settings).

Page 10: MCGG OCR

Variations over these rangesSetting current ±1%Operating time ±2% or ±30ms whichever is greater

Accuracy – general

Current setting

Time delayed element 1.0 x Is to 1.1 x Is

Instantaneous elements Iinst = 1 x Is 1.0 x Iinst to 1.1 x Iinst

All other settings Iinst ±5%

Operating time

Time characteristic Accuracy

Standard inverseVery inverse ±5%Long time inverse

Extremely inverse ±7.5% ±30ms whichever is greater

Definite time ±3%

Repeatability(within basic accuracy claim)

Pick-up current better than ±1%

Operating time better than ±2% or ±30ms whicheveris greater.

Overshoot time Less than 30ms (when the inputcurrent is reduced from any valuewithin the operative range to zero).

Resetting current Time delayed and instantaneouselements: not less than 95% of timedelayed current setting.

Resetting and disengaging times Less than 70ms (when the inputcurrent is reduced from any valuewithin the operative range to zero).

Transient overreach System time constant up to 30ms:5%

(instantaneous elements) System time constant up to 100ms:12%

Thermal withstand

Continuous withstand 2 x Is or 2.6 x In whichever is lower,with a minimum of 1 x In

Short time withstand For 1s: 100 x In with 400A maximum

For 3s: 57 x In with 230A maximum

Operation indicators Each measuring board is fitted withtwo red led indicators, one showingtime delayed operation and the othershowing instantaneus operation.The reset button provided on thefrontplate resets all the operationindicators.

The green timer start indicatorilluminates when the input currentexceeds the setting current Is tofacilitate testing of the module.This indicator is self resetting.

Led covers are available to eliminateany undesired led indication.

11

Page 11: MCGG OCR

12

Contacts

Changeover MakeMCGG 52, 53, 82 Phase fault time delayed element 1 1

Phase fault instantaneous element 1 1

Earth fault time delayed element 1 1

Earth fault instantaneous element 1 1

MCGG 22, 42, 62, 63 Time delayed element 1 1

Instantaneous element 1 1

Contact ratings

Make and carry for 0.2s 7500VA subject to maxima of 30Aand 300V ac or dc

Carry continuously 5A ac or dc

Break ac – 1250VA subject todc – 50W resistive maxima of25W, L/R = 0.04s 5A and 300V

Durability

Loaded contact 10,000 operations minimum

Unloaded contact 100,000 operations minimum

Directional control Directional control can be exercisedover each pole individually byconnecting the output contact of arelay type METI across appropriatecase terminals.

Relay type Direction control terminals

MCGG 22 23,24MCGG 42 45, 46, 49, 50MCGG 52, 53 43 to 46, 49, 50MCGG 62, 63 45 to 50MCGG 82 43 to 50

Note: The directional control circuits are isolated from all other circuits but areelectrically connected to the relay case. These circuits must not, therefore,be insulation or impulse tested to the case.

High voltage withstand

Dielectric withstandIEC 255-5: 1977 2.0kV rms for 1 minute between all

case terminals connected together andthe case earth terminal, with theexception of the directional controlterminals.

2.0kV rms for 1 minute betweenterminals of independent circuits, withterminals on each independent circuitconnected together.

1kV rms for 1 minute across opencontacts of output relays.

High voltage impulseIEC 255-5: 1977 Three positive and three negative

impulses of 5kV peak, 1.2/50µs, 0.5Jbetween all terminals and case earthand between adjacent terminals, withthe exception of the directional controlterminals, (see note).

Page 12: MCGG OCR

Electrical environment

High frequency disturbanceIEC 255-22-1: 1988 Class III 2.5kV peak between independent

circuits and case.

1.0kV peak across terminals of thesame circuit.

Note: The directional control terminalscomply with class II and will withstand1kV peak between all independentcircuits, and 500V peak across thedirectional control terminals.

DC supply interruptionIEC 255-11: 1979 The unit will withstand a 10ms

interruption in the auxiliary supply,under normal operating conditions,without de-energising.

AC ripple on dc supplyIEC 255-11: 1979 The unit will witstand 12% ac ripple

on the dc supply.

Fast transient disturbanceIEC 255-22-4: 1992 Class IV 4.0kV, 2.5kHz applied directly to

auxiliary supply.IEC 801-4: 1988 Level 4 4.0kV, 5.0kHz applied directly to

all inputs.

Electrostatic dischargeIEC 255-22-2: 1989 Class II 4.0kV discharge in air with cover

in placeIEC 801-2: 1991 Level 2 4.0kV point contact discharge with

cover removed.

Surge immunityIEC 1000-4-5: 1995 Level 4 4.0kV peak, 1.2/50µs between all

groups and case earth.2.0kV peak, 1.2/50µs betweenterminals of each group.

EMC compliance89/336/EEC Compliance with the EuropeanEN50081-2: 1994 Commission Directive on EMC isEN50082-2: 1995 claimed via the Technical Construction

File route. Generic Standardswere used to establish conformity.

Product safety73/23/EEC Compliance with the European

Commission Low Voltage Directive.

EN 61010-1: 1993/A2: 1995 Compliance is demonstrated byEN 60950: 1992/A3: 1995 reference to generic safety standards.

Atmospheric environment

TemperatureIEC 255-6: 1988 Storage and transit –25°C to +70°C

Operating –25°C to +55°CIEC 68-2-1: 1990 ColdIEC 68-2-2: 1974 Dry heat

HumidityIEC 68-2-3: 1969 56 days at 93% RH and 40°C

Enclosure protectionIEC 529: 1989 IP50 (dust protected)

13

Page 13: MCGG OCR

14

Mechanical environment

VibrationIEC 255-21-1: 1988 Response Class 1

Endurance Class 1

Figure 12: Case outline size 4.

97

177

Push buttonprojection 10 max.

32 21225 min.

157 max.

11103

99

52

23.54 holes 4.4

168 159

Panel cut-out:Flush mounting fixing details.

All dimensions in mm.

Flush mounting.

Cases

MCGG 22 Size 4

MCGG 42 Size 6

MCGG 62 Size 6

MCGG 63 Size 6

MCGG 52 Size 8

MCGG 53 Size 8

MCGG 82 Size 8

The dimensions of the cases are shown in Figures 12, 13 and 14.

Information Required with Order

Relay type (see models available).

Rated current and frequency.

DC auxiliary voltage range.

Requirement for led cover partGJ0280 001.

(These self adhesive led covers can besupplied to cover the instantaneousled when used in auto-recloseapplications as the leds remain onduring normal use).

Page 14: MCGG OCR

Figure 13: Case outline size 6.

Figure 14: Case outline size 8.

149

177

Push buttonprojection 10 max.

32 21225 min.

157 max.

155

151

103.6

23.54 holes 4.4

168 159

Panel cut-out:Flush mounting fixing details.

All dimensions in mm.

Flush mounting. 11

200

177

Push buttonprojection 10 max.

32 21225 min.

157 max.

11206

203

155.4

244 holes 4.4

168 159

Panel cut-out:Flush mounting fixing details.

All dimensions in mm.Flush mounting.

15