DS110

OUTSULATION® PLUS MD SYSTEM®

An Exterior Wall Insulation and Finish System With Moisture Drainage That Incorporates Continuous Insulation and An Air/Water-Resistive Barrier

Outsulation Plus MD System Installation Details

Page 2: Outsulation Plus MD System Installation Detailscms.dryvit.com/media/304806/opmd-ds110-all-in-one.pdf · step #1 step #2 step #3 step #4 opening preparation - outsulation® plus md

NOTE

DETAIL

TABLE OF CONTENTSDETAIL

OUTSULATION PLUS MD SYSTEM OPMD 0.0.01

OUTSULATION PLUS MD SYSTEM OPMD 0.0.01a

STARTER BOARD OPTION

AWRB APPLICATION OPMD 0.0.02

OPENING PREPARATION- OPMD 0.0.03

AQUAFLASH® SYSTEM OPTION

OPENING PREPARATION- OPMD 0.0.04

BACKSTOP® NT™ OPTION

OPENING FLASHING INTEGRATION OPMD 0.0.05

INSIDE/OUTSIDE CORNERS OPMD 0.0.06

OUTSIDE CORNER - HIGH IMPACT OPMD 0.0.07

GRADE TERMINATION OPMD 0.0.08

TERMNATION AT CONCRETE CURB OPMD 0.0.09

TERMINATION AT ADA COMPLIANT OPMD 0.0.10

SIDEWALK

EPS PREPARATION AT OPMD 0.0.11

WALL PENETRATIONS

STOREFRONT WINDOW SILL - JAMB OPMD 0.0.12

SELF FLASHING WINDOW SILL - JAMB OPMD 0.0.13

STOREFRONT AND FLANGED OPMD 0.0.14

WINDOW HEAD

HEAD J-TRACK OPTION OPMD 0.0.15

TERMINATION AT OPMD 0.0.16

WOOD FRAMED DECK

TERMINATION AT OPMD 0.0.17

WATERPROOF DECK

PREPARATION AT PARAPET/ OPMD 0.0.18

WALL INTERSECTION

TERMINATION AT PARAPET - OPMD 0.0.19

CAP FLASHING

TERMINATION AT PARAPET - OPMD 0.0.20

SOLID SUBSTRATE

TERMINATION AT SLOPED ROOF OPMD 0.0.21

TERMINATION AT ROOF STOP OPMD 0.0.22

FLASHING

VERTICAL WALL/ SUSPENDED OPMD 0.0.23

SOFFIT TRANSITION

TRANSITION AT SOFFIT/ OPMD 0.0.24

FASCIA INTERSECTION

FASCIA/ UNINSULATED SOFFIT OPMD 0.0.25

TRANSITION

TERMINATION AT OPMD 0.0.26

UNINSULATED SOFFIT VENT

HORIZONTAL SLIP JOINT OPMD 0.0.27

WITHOUT WEEPS

HORIZONTAL SLIP JOINT OPMD 0.0.28

WITH WEEPS

HORIZONTAL JOINT - OPMD 0.0.29

SUBSTRATE CHANGE

HORIZONTAL TERMINATION OPMD 0.0.30

AT STONE VENEER

HORIZONTAL TERMINATION OPMD 0.0.31

AT STUCCO

HORIZONTAL TERMINATION OPMD 0.0.32

AT WOOD SIDING

VERTICAL EXPANSION JOINT- OPMD 0.0.33

EIFS

THROUGH-WALL EXPANSION JOINT OPMD 0.0.34

VERTICAL EXPANSION JOINT - OPMD 0.0.35

FLUSH OPTION

VERTICAL EXPANSION JOINT - OPMD 0.0.36

RECESSED OPTION

VERTICAL EXPANSION JOINT - OPMD 0.0.37

DOUBLE SEAL OPTION

VERTICAL TERMINATION OPMD 0.0.38

AT STONE VENEER

PENETRATIONS OPMD 0.0.39

SIGN ATTACHMENT OPMD 0.0.40

AESTHETIC REVEALS OPMD 0.0.41

RECESSED GRAPHICS OPMD 0.0.42

PROJECTING GRAPHICS OPMD 0.0.43

EPS SHAPES OPMD 0.0.44

DRYVIT MAKES NO REPRESENTATION REGARDING

CONFORMITY OF ITS SUGGESTIONS TO MODEL BUILDING

CODES, ENGINEERING CRITERIA, SPECIFIC APPLICATIONS,

OR PROJECT LOCATIONS. ALL COMPONENTS INDICATED

IN ILLUSTRATIONS, AS WELL AS OTHERS THAT MAY BE

REQUIRED FOR THE INTEGRITY OF THE SYSTEM SHALL BE

DESIGNED, DETAILED, AND ENGINEERED BY

REPRESENTATIVES OF THE ARCHITECT, OWNER, OR

CONTRACTOR TO BE IN CONFORMANCE WITH MODEL

CODES, ARCHITECTURAL, AND ENGINEERING

REQUIREMENTS PERTAINING TO SPECIFIC BUILDING

PROJECTS.

DRYVIT MAKES NO WARRANTY, EXPRESSED OR IMPLIED,

AS TO THE ARCHITECTURAL DESIGN, ENGINEERING, OR

WORKMANSHIP OF PROJECTS UTILIZING DRYVIT SYSTEMS

OR PRODUCTS.

THE LIABILITIES OF DRYVIT SHALL BE AS STATED IN THE

OUTSULATION PLUS MD LIMITED COMMERCIAL

WARRANTY. CONTACT DRYVIT FOR A FULL AND

COMPLETE COPY OF THE WARRANTY.

Outsulation® Plus MD System®The architecture, engineering, and design of the project using the

Dryvit products is the responsibility of the project's design

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

and Dryvit specifically disclaims any liability for the use of this detail

and for the architecture, design, engineering or workmanship of any

project. The project design professional determines, in its sole

discretion, whether this detail or a functionally equivalent detail is

best suited for the project. Use of a functionally equivalent detail does

not violate Dryvit's warranty. This detail is subject to change without

notice. Contact Dryvit to ensure you have the most recent version.

©

Dryvit Systems, Inc.

Issued: 7/2018

Page 3: Outsulation Plus MD System Installation Detailscms.dryvit.com/media/304806/opmd-ds110-all-in-one.pdf · step #1 step #2 step #3 step #4 opening preparation - outsulation® plus md

DRYVIT ADHESIVE IN VERTICAL NOTCHED

TROWEL CONFIGURATION APPLIED TO

BACK OF EPS

Outsulation® Plus MD System®

OPMD 0.0.01

Outsulation Plus MD System

NOTE:

1. DRYVIT RECOMMENDS THAT GROUND

FLOOR APPLICATIONS AND ALL FACADES

EXPOSED TO ABNORMAL STRESS, HIGH

TRAFFIC, OR DELIBERATE IMPACT HAVE

THE BASE COAT REINFORCED WITH

PANZER® MESH PRIOR TO STANDARD OR

STANDARD PLUS MESH. LOCATION OF

HIGH IMPACT ZONES SHOULD BE

INDICATED ON CONTRACT DRAWINGS.

2. AS AN OPTION DRYVIT DRAINAGE

TRACK™ CAN BE USED AT SYSTEM

TERMINATION AT GRADE, REFER TO

OPMD 0.0.08 FOR CONFIGURATION.

3. DRYVIT DRAINAGE TRACK SHALL ONLY

BE USED AT GRADE LEVEL TERMINATIONS.

NORMAL IMPACT

HIGH IMPACT

EPS INSULATION BOARD

APPROVED SUBSTRATE

DRYVIT AIR/WATER-RESISTIVE BARRIER COATING

DRYVIT BASE COAT

DRYVIT REINFORCING MESH

EMBEDDED IN DRYVIT BASE COAT

DRYVIT BASE COAT

DRYVIT FINISH

DRYVIT ADHESIVE IN VERTICAL NOTCHED TROWEL

CONFIGURATION APPLIED TO BACK OF EPS

DRYVIT DRAINAGE STRIP™ ADHERED WITH DABS

OF DRYVIT AP ADHESIVE (SEE NOTES 2 AND 3)

EPS INSULATION BOARD

APPROVED SUBSTRATE

DRYVIT AIR/WATER - RESISTIVE BARRIER COATING

DRYVIT BASE COAT

DRYVIT REINFORCING MESH

EMBEDDED IN DRYVIT BASE COAT

DRYVIT BASE COAT

DRYVIT FINISH

FRAMING BY OTHERS

DRYVIT DRAINAGE STRIP ADHERED WITH DABS

OF DRYVIT AP ADHESIVE (SEE NOTES 2 AND 3)

DRYVIT PANZER REINFORCING MESH

DRYVIT BASE COAT

OUTSULATION

PLUS MD SYSTEM

BY OTHERS

FRAMING BY OTHERS

©

The architecture, engineering, and design of the project using the

Dryvit products is the responsibility of the project's design

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

and Dryvit specifically disclaims any liability for the use of this detail

and for the architecture, design, engineering or workmanship of any

project. The project design professional determines, in its sole

discretion, whether this detail or a functionally equivalent detail is

best suited for the project. Use of a functionally equivalent detail does

not violate Dryvit's warranty. This detail is subject to change without

notice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc.

Issued: 10/2016

Page 4: Outsulation Plus MD System Installation Detailscms.dryvit.com/media/304806/opmd-ds110-all-in-one.pdf · step #1 step #2 step #3 step #4 opening preparation - outsulation® plus md

Outsulation® Plus MD System®

OPMD 0.0.01a

NOTE:

1. DRYVIT RECOMMENDS THAT GROUND

FLOOR APPLICATIONS AND ALL FACADES

EXPOSED TO ABNORMAL STRESS, HIGH

TRAFFIC, OR DELIBERATE IMPACT HAVE

THE BASE COAT REINFORCED WITH

PANZER® MESH PRIOR TO STANDARD OR

STANDARD PLUS MESH. LOCATION OF

HIGH IMPACT ZONES SHOULD BE

INDICATED ON CONTRACT DRAWINGS.

NORMAL IMPACT

ULTRA HIGH

IMPACT

BY OTHERS

FRAMING BY OTHERS

©

Dryvit Systems, Inc.

Issued: 07/2018

The architecture, engineering, and design of the project using the

Dryvit products is the responsibility of the project's design

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

and Dryvit specifically disclaims any liability for the use of this detail

and for the architecture, design, engineering or workmanship of any

project. The project design professional determines, in its sole

discretion, whether this detail or a functionally equivalent detail is

best suited for the project. Use of a functionally equivalent detail does

not violate Dryvit's warranty. This detail is subject to change without

notice. Contact Dryvit to ensure you have the most recent version.

Outsulation Plus MD System

Starter Board Option

APPROVED SUBSTRATE

DRYVIT BASE COAT

OUTSULATION

PLUS MD SYSTEM

EPS INSULATION BOARD

DRYVIT AIR/WATER-RESISTIVE BARRIER COATING

DRYVIT BASE COAT

DRYVIT REINFORCING MESH

EMBEDDED IN DRYVIT BASE COAT

DRYVIT BASE COAT

DRYVIT FINISH

DRYVIT ADHESIVE IN VERTICAL NOTCHED TROWEL

CONFIGURATION APPLIED TO BACK OF EPS

DRYVIT SHAPES BY ACROCORE PRE-BASE

COATED STARTER BOARD OR APPROVED EQUAL

EPS INSULATION BOARD

APPROVED SUBSTRATE

DRYVIT AIR/WATER - RESISTIVE BARRIER COATING

DRYVIT BASE COAT

DRYVIT REINFORCING MESH

EMBEDDED IN DRYVIT BASE COAT

DRYVIT FINISH

FRAMING BY OTHERS

DRYVIT ADHESIVE IN VERTICAL NOTCHED

TROWEL CONFIGURATION APPLIED TO

BACK OF EPS

DRYVIT PANZER REINFORCING MESH

DRYVIT BASE COAT

DRYVIT SHAPES BY ACROCORE PRE-BASE

COATED STARTER BOARD OR APPROVED EQUAL

Page 5: Outsulation Plus MD System Installation Detailscms.dryvit.com/media/304806/opmd-ds110-all-in-one.pdf · step #1 step #2 step #3 step #4 opening preparation - outsulation® plus md

DRYVIT BACKSTOP® NT™ - TEXTURE

APPROVED SUBSTRATE

FRAMING BY OTHERS

Outsulation® Plus MD System®

OPMD 0.0.02

NOTE:1. FOR ADDITIONAL AIR/WATER-RESISTIVEBARRIER DETAILS, REFER TO DRYVITPUBLICATION DS840.

DRYVIT BACKSTOP NT - TEXTUREOVER DRYVIT GRID TAPE™

AWRB Application

DRYVIT AIR/WATER - RESISTIVEBARRIER COATING

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc. Issued: 10/2016

Page 6: Outsulation Plus MD System Installation Detailscms.dryvit.com/media/304806/opmd-ds110-all-in-one.pdf · step #1 step #2 step #3 step #4 opening preparation - outsulation® plus md

STEP #1 STEP #2

STEP #4STEP #3

Opening Preparation -AquaFlash® System OptionOutsulation® Plus MD System®

OPMD 0.0.03

NOTE:1. DRYVIT AQUAFLASH SHALL EXTEND TOINTERIOR FACE OF OPENING.

2. REFER TO HEAD, SILL AND JAMB DETAILSFOR FLASHING INTEGRATION.

3. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHING TAPE™MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.

4. INSTALL WINDOW UNIT AND ASSOCIATEDFLASHINGS PER MANUFACTURER'SRECOMMENDATIONS, CODE REQUIREMENTS ANDPROJECT DOCUMENTS.

5. AQUAFLASH SYSTEM CONSISTS OF AQUAFLASHMESH AND AQUAFLASH LIQUID.

6. FOR ADDITIONAL AIR/WATER-RESISTIVE BARRIERDETAILS, REFER TO DRYVIT PUBLICATION DS840.

5

INSTALL DIAGONAL STRIP OF DRYVITAQUAFLASH MESH AT CORNERSAND EMBED IN AQUAFLASH LIQUID(SEE NOTES 1 AND 3)

APPLY DRYVIT AQUAFLASH®SYSTEM (SEE NOTES 1 AND 3)

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

INSTALL DRYVIT AQUAFLASHSYSTEM AT HEADS(SEE NOTES 1, 3 AND 4)

INSTALL DRYVIT AQUAFLASHSYSTEM AT JAMBS(SEE NOTES 1 AND 3)

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc.Issued: 10/2016

Page 7: Outsulation Plus MD System Installation Detailscms.dryvit.com/media/304806/opmd-ds110-all-in-one.pdf · step #1 step #2 step #3 step #4 opening preparation - outsulation® plus md

OPMD 0.0.04

STEP #1

Outsulation® Plus MD System®

STEP #2

APPLY DRYVIT GRID TAPE™(SEE NOTES 1 AND 2)

TROWEL APPLY DRYVITBACKSTOP NT-TEXTURE(SEE NOTE 2)

6" (153 MM) MIN.(TYP.)

STEP #3

APPLY DRYVIT AQUAFLASH®SYSTEM (SEE NOTES 2, 3 AND 5)

STEP #4

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING APPLIED TOFACE OF WALL (SEE NOTE 5)

NOTE:1. APPLY DRYVIT GRID TAPE ON HEAD, JAMB, ANDCORNERS OF OPENINGS AND SHEATHING JOINTS.

2. TROWEL APPLY DRYVIT BACKSTOP NT-TEXTUREOVER THE DRYVIT GRID TAPE ALL THE WAY TO INSIDEFACE OF OPENING. ALL VOIDS MUST BE FILLED;MULTIPLE PASSES MAY BE REQUIRED. AS AN OPTION,DRYVIT GRID TAPE AND DRYVIT BACKSTOP NT-TEXTUREMAY ALSO BE APPLIED AT THE SILL PRIOR TO DRYVITAQUAFLASH SYSTEM OR FLASHING TAPE APPLICATION.

3. DRYVIT FLASHING TAPE SURFACE CONDITIONER™AND DRYVIT FLASHING TAPE™ MAY BE USED IN LIEU OFDRYVIT AQUAFLASH SYSTEM AT SILL, INCLUDINGCORNER SPLICES.

4. INSTALL WINDOW UNIT AND ASSOCIATEDFLASHINGS PER MANUFACTURER'SRECOMMENDATIONS, CODE REQUIREMENTSAND PROJECT DOCUMENTS.

5. REFER TO HEAD, SILL, AND JAMB DETAILSFOR FLASHING INTEGRATION.

6. FOR ADDITIONAL AIR/WATER-RESISTIVEBARRIER DETAILS, REFER TO DRYVITPUBLICATION DS840.

Opening Preparation -Backstop® NT™ Option

4" (102 MM) MIN.(TYP.)

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc.Issued: 10/2016

Page 8: Outsulation Plus MD System Installation Detailscms.dryvit.com/media/304806/opmd-ds110-all-in-one.pdf · step #1 step #2 step #3 step #4 opening preparation - outsulation® plus md

OPMD 0.0.05

STEP #1

Opening Flashing IntegrationOutsulation® Plus MD System®

REFER TO OPMD 0.0.03, AND OPMD 0.0.04FOR PREPARATION OF OPENING PRIORTO FLASHING INSTALLATION

STEP #2 STEP #3

REFER TO OPMD 0.0.12 &OPMD 0.0.13 FOR JAMBDETAIL

NOTE:1. REFER TO OPMD 0.0.12 AND OPMD 0.0.13FOR INTEGRATION OF FLASHING.

2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.

3. FOR ADDITIONAL AIR/WATER-RESISTIVEBARRIER DETAILS, REFER TO DRYVITPUBLICATION DS840.

INSTALL WINDOW UNIT ANDASSOCIATED FLASHINGS ANDAPPLY DRYVIT AQUAFLASHSYSTEM OVER VERTICAL LEG OFFLASHING (SEE NOTES 1 AND 2)

APPLY DRYVIT AQUAFLASH®SYSTEM SPLICES LAPPING OVERLIP OF SILL PAN FLASHING.(SEE NOTES 1 AND 2)

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc.Issued: 10/2016

Page 9: Outsulation Plus MD System Installation Detailscms.dryvit.com/media/304806/opmd-ds110-all-in-one.pdf · step #1 step #2 step #3 step #4 opening preparation - outsulation® plus md

OPMD 0.0.06

Inside/Outside CornersOutsulation® Plus MD System®

8"(203 MM)

MIN. MUST OVERLAP8" (203 MM) MIN.

(SEE NOTE 3)

MUST OVERLAP8" (203 MM) MIN.

(SEE NOTES 2, 3 AND 4) 8"(203 MM)

MIN.

NOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER®MESH PRIOR TO STANDARD OR STANDARDPLUS MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ONCONTRACT DRAWINGS.

2. DOUBLE WRAP OUTSIDE CORNERS WITHREINFORCING MESH OR USE CORNER MESH.

3. DO NOT LAP REINFORCING MESH WITHIN8" (203 MM) OF A CORNER.

4. OUTSIDE INSULATION BOARD EDGESSHALL BE OFFSET.

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

APPROVED SUBSTRATE

DRYVIT BACKSTOP® NT™-TEXTUREOVER DRYVIT GRID TAPE™

DRYVIT BASE COAT

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

DRYVIT ADHESIVE IN VERTICAL NOTCHED TROWELCONFIGURATION APPLIED TO BACK OF EPS

EPS INSULATION

DRYVIT FINISH

DRYVIT BASE COAT

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

DRYVIT BASE COAT

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

EPS INSULATION

APPROVED SUBSTRATE

DRYVIT ADHESIVE IN VERTICAL NOTCHED TROWELCONFIGURATION APPLIED TO BACK OF EPS

DRYVIT BACKSTOP NT-TEXTUREOVER DRYVIT GRID TAPE

DRYVIT FINISH

DRYVIT BASE COAT

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc.Issued: 10/2016

Page 10: Outsulation Plus MD System Installation Detailscms.dryvit.com/media/304806/opmd-ds110-all-in-one.pdf · step #1 step #2 step #3 step #4 opening preparation - outsulation® plus md

OPMD 0.0.07

Outside Corner-High Impact

8"(203 MM)

MIN.

NOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARDOR STANDARD PLUS MESH. LOCATION OFHIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.

2. OUTSIDE INSULATION BOARD EDGESSHALL BE OFFSET.

DRYVIT FINISH

DRYVITBACKSTOP® NT™-TEXTUREOVER DRYVIT GRID TAPE™

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

DRYVIT ADHESIVE IN VERTICALNOTCHED TROWELCONFIGURATION APPLIEDTO BACK OF EPS

APPROVED SUBSTRATE

DRYVIT BASE COAT

DRYVIT PANZER 20REINFORCING MESH EMBEDDEDIN DRYVIT BASE COAT

DRYVIT STANDARDREINFORCING MESHOVERLAP 8" (203 MM) MIN.AT CORNER

EPS INSULATION

DRYVIT BASE COAT

DRYVIT CORNER MESH™

8"(203 MM)

MIN.

Outsulation® Plus MD System®

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc.Issued: 10/2016

Page 11: Outsulation Plus MD System Installation Detailscms.dryvit.com/media/304806/opmd-ds110-all-in-one.pdf · step #1 step #2 step #3 step #4 opening preparation - outsulation® plus md

8" (203 MM)MIN.

Outsulation® Plus MD System® Grade Termination

2'-0" (610 MM)MAX.

(SEE NOTE 2)

OPMD 0.0.08

OUTSULATION PLUSMD SYSTEM

BY OTHERS

NOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD ORSTANDARD PLUS MESH. LOCATION OFHIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.

2. EXPANSION JOINT IS REQUIRED ALONGTOP OF FOUNDATION IF 2'-0" (610 MM) DIMENSION IS EXCEEDED.

3. ENSURE BOTTOM EDGE OF DRAINAGESTRIP IS LEFT FREE TO DRAIN.

4. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.

DRYVIT DETAIL MESH® WRAPPEDTO BACKSIDE OF EPS MIN. 2" (51 MM)

EPS INSULATION

DRYVIT BASE COAT

DRYVIT AQUAFLASH® SYSTEM (SEE NOTE 4)

SLOPE GRADE AWAYFROM FOUNDATION WALL

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

DRYVIT BACKSTOP® NT™-TEXTUREOVER DRYVIT GRID TAPE™

DRYVIT DRAINAGE STRIP™ ADHEREDWITH DABS OF DRYVIT AP ADHESIVE(SEE NOTE 3)

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

DRYVIT ADHESIVE IN VERTICAL NOTCHEDTROWEL CONFIGURATION APPLIED TO

BACK OF EPS

APPROVED SUBSTRATE

5. DRAINAGE TRACK USAGE IS LIMITED TOTHE BASE OF THE SYSTEM AT FINISHEDGRADE LEVEL.

6. LIGHTLY SAND SURFACE OF DRAINAGETRACK TO MAXIMIZE ADHESION.

8" (203 MM)MIN.

DRAINAGETRACK OPTION

2'-0" (610 MM)MAX.

(SEE NOTE 2)

SEE NOTES 4,5 & 6)

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc.Issued: 10/2016

Page 12: Outsulation Plus MD System Installation Detailscms.dryvit.com/media/304806/opmd-ds110-all-in-one.pdf · step #1 step #2 step #3 step #4 opening preparation - outsulation® plus md

Outsulation® Plus MD System® Termination At Concrete Curb

OPMD 0.0.09

BY OTHERS

DRYVIT FINISH

DRYVIT REINFORCINGMESH EMBEDDED INDRYVIT BASE COAT

EPS INSULATION

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

DRYVIT ADHESIVE IN VERTICAL NOTCHEDTROWEL CONFIGURATION APPLIED TO

BACK OF EPS

APPROVED SUBSTRATE

NOTE:1. DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSED TOABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIOR TOSTANDARD OR STANDARD PLUS MESH. LOCATIONOF HIGH IMPACT ZONES SHOULD BE INDICATED ONCONTRACT DRAWINGS.

2. ENSURE BOTTOM EDGE OF DRAINAGE STRIP ISLEFT FREE TO DRAIN.

3. LIGHTLY SAND SURFACE OF DRAINAGETRACK TO MAXIMIZE ADHESION.

4. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.

5. DRYVIT DRAINAGE TRACK SHALL ONLY BEUSED AT GRADE LEVEL TERMINATIONS.

DRAINAGETRACK OPTION

DRYVIT AQUAFLASH SYSTEM ORDRYVIT BACKSTOP NT-TEXTURE OVER

GRID TAPE (SEE NOTES 3, 4 AND 5)

DRYVIT DRAINAGE TRACKSET IN DRYVIT AP ADHESIVE

OUTSULATIONPLUS MD SYSTEM

DRYVIT BASE COAT

2" (51 MM) MIN.

DRYVIT DRAINAGE STRIP™ ADHERED WITHDABS OF DRYVIT AP ADHESIVE (SEE NOTE 2)

DRYVIT AQUAFLASH® SYSTEM

DRYVIT BACKSTOP® NT™TEXTURE OVER DRYVIT

GRID TAPE™

DRYVIT DETAIL MESH® WRAPPEDTO BACKSIDE OF EPS MIN. 2" (51 MM)

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc.Issued: 10/2016

Page 13: Outsulation Plus MD System Installation Detailscms.dryvit.com/media/304806/opmd-ds110-all-in-one.pdf · step #1 step #2 step #3 step #4 opening preparation - outsulation® plus md

Termination At ADA Compliant Sidewalk

OPMD 0.0.10

NOTE:

1. DRYVIT RECOMMENDS THAT GROUND FLOOR

APPLICATIONS AND ALL FACADES EXPOSED TO

ABNORMAL STRESS, HIGH TRAFFIC, OR

DELIBERATE IMPACT HAVE THE BASE COAT

REINFORCED WITH PANZER® MESH PRIOR TO

STANDARD OR STANDARD PLUS MESH.

LOCATION OF HIGH IMPACT ZONES SHOULD BE

INDICATED ON CONTRACT DRAWINGS.

2. USE OF THIS DETAIL IS LIMITED TO

SLAB-ON-GRADE APPLICATIONS.

3. INCORPORATE MEASURES TO PROTECT

STRUCTURE FROM MOISTURE INTRUSION,

DAMPNESS, AND FROST HEAVE.

OUTSULATION PLUS

MD SYSTEM

BY OTHERS

DRYVIT FINISH

DRYVIT STANDARD REINFORCING

MESH EMBEDDED IN DRYVIT BASE

COAT

EPS INSULATION

DRYVIT AIR/WATER-RESISTIVE

BARRIER COATING

DRYVIT ADHESIVE APPLIED IN

VERTICAL NOTCHED TROWEL

CONFIGURATION TO BACK OF EPS

APPROVED SUBSTRATE

DRYVIT BASE COAT

3/4" (19 MM) MIN. (SEE NOTE 4)

DRYVIT BASE COAT

DRYVIT DETAIL MESH® WRAPPED TO

BACKSIDE OF EPS MIN. 2" (51 MM)

DRYVIT AQUAFLASH® SYSTEM

METAL PROTECTION SHEET,

BY OTHERS

ADA COMPLIANT SIDEWALK SLOPED

AWAY FOR POSITIVE DRAINAGE

FULLY ADHERED FOUNDATION

WATERPROOFING MEMBRANE,

BY OTHERS

COMPRESSIBLE FILLER BOARD,

BY OTHERS

2" (51 MM) MAX.

OVERLAP

DRYVIT DRAINAGE STRIP™ ADHERED WITH

DABS OF DRYVIT AP ADHESIVE

Outsulation® Plus MD System®4. TO PREVENT DEBRIS ACCUMULATION, IT IS

RECOMMENDED TO TERMINATE SYSTEM 2"

ABOVE SIDEWALK.

©

The architecture, engineering, and design of the project using the

Dryvit products is the responsibility of the project's design

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

and Dryvit specifically disclaims any liability for the use of this detail

and for the architecture, design, engineering or workmanship of any

project. The project design professional determines, in its sole

discretion, whether this detail or a functionally equivalent detail is

best suited for the project. Use of a functionally equivalent detail does

not violate Dryvit's warranty. This detail is subject to change without

notice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc.

Issued: 10/2016

Page 14: Outsulation Plus MD System Installation Detailscms.dryvit.com/media/304806/opmd-ds110-all-in-one.pdf · step #1 step #2 step #3 step #4 opening preparation - outsulation® plus md

EPS INSULATION(SEE NOTE 2)

DRYVIT DETAIL MESH® WRAPPEDTO BACKSIDE OF EPS MIN. 2" (51 MM)

DRYVIT DETAIL REINFORCING MESH9 1/2" (241 MM) X 12" (305 MM) (TYP.)(SEE NOTE 3)

OPMD 0.0.11

EPS Preparation At Wall PenetrationsOutsulation® Plus MD System®NOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARDOR STANDARD PLUS MESH. LOCATION OFHIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.

2. LOCATE INSULATION BOARDS SUCHTHAT BOARD EDGES DO NOT ALIGN WITHCORNERS OF PENETRATION.

3. APPLY A PIECE OF 9 1/2" (241 MM) X 12"(305 MM) DETAIL REINFORCING MESHDIAGONALLY AT EACH CORNER.

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc. Issued: 10/2016

Page 15: Outsulation Plus MD System Installation Detailscms.dryvit.com/media/304806/opmd-ds110-all-in-one.pdf · step #1 step #2 step #3 step #4 opening preparation - outsulation® plus md

Storefront Window Sill - JambOutsulation® Plus MD System®NOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER®MESH PRIOR TO STANDARD OR STANDARDPLUS MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ONCONTRACT DRAWINGS.

2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.

3. DRYVIT BACKSTOP® NT-TEXTURE OVERGRID TAPE™ IS AN ALTERNATIVE OPTIONAT JAMB AND HEAD CONDITION PERDETAIL OPMD 0.0.04.

4. EDGE WRAPPING METHOD ISACCEPTABLE AT SILL AND JAMB IN LIEUOF BACK WRAPPING. DRYVITREINFORCING MESH MUST BE FULLYEMBEDDED IN DRYVIT BASE COAT AT EPSEDGE AND MUST EXTEND ONTOSUBSTRATE 2" (51 MM) MIN.

OPMD 0.0.12

2 1/2"(64 MM) MIN.

1/2" (12.7 MM)

SILL PAN FLASHINGDETAIL

AIR SEAL PER MANUFACTURER'SREQUIREMENTS, BY OTHERS

DRYVIT COMPATIBLESEALANT, BY OTHERS

WRAP DRYVIT DETAILMESH® 2" (51 MM) MIN.

AT BACKSIDE OF EPS(SEE NOTE 4)

CONTINUOUS FLASHING, BYOTHERS, TURN UP 1/2" (12.7 MM) MIN.AT JAMBS - SEE DETAIL BELOW

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

DRYVIT FINISH

DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATIONAPPLIED TO BACK OF EPS

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

DRYVIT BASE COAT

DRYVIT COMPATIBLESEALANT, BY OTHERS

DRYVIT AQUAFLASH®SYSTEM (SEE NOTE 2)

EPS INSULATION BOARD

EPS SHAPE (OPTIONAL)

DRYVIT BASE COAT

APPROVED SUBSTRATE

DRYVITAIR/WATER-RESISTIVE

BARRIER COATING

WRAP DRYVIT DETAIL MESH® 2" (51 MM) MIN. AT BACKSIDE OF EPS(SEE NOTE 4)

SLOPED SHIM ASREQUIRED, BY OTHERS

3/4" MIN.(19 MM )DRYVIT AQUAFLASH® SYSTEM(SEE NOTE 2 AND 3)

FRAMING BY OTHERS

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc. Issued: 10/2016

Page 16: Outsulation Plus MD System Installation Detailscms.dryvit.com/media/304806/opmd-ds110-all-in-one.pdf · step #1 step #2 step #3 step #4 opening preparation - outsulation® plus md

OPMD 0.0.13

Self Flashing Window Sill - Jamb

FRAMING BY OTHERS

DRYVIT AQUAFLASH® SYSTEM(SEE NOTES 2 AND 3)

NOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER®MESH PRIOR TO STANDARD OR STANDARDPLUS MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ONCONTRACT DRAWINGS.

2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.

3. DRYVIT BACKSTOP® NT™-TEXTURE OVERDRYVIT GRID TAPE™ IS AN ALTERNATIVEOPTION AT JAMB AND HEAD CONDITION PERDETAIL OPMD 0.0.04.

4. ADHESIVE ONLY APPLICATION IS ACCEPTABLEWHEN USING DRYVIT AQUAFLASH SYSTEM.

5. EDGE WRAPPING METHOD IS ACCEPTABLE INLIEU OF BACK WRAPPING. DRYVIT REINFORCINGMESH MUST BE FULLY EMBEDDED IN DRYVITBASE COAT AT EPS EDGE AND EXTEND ONTOSUBSTRATE 2" (51 MM) MIN.

APPROVED SUBSTRATE

SILL PAN FLASHING,BY OTHERS

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

DRYVIT BASE COAT

DRYVIT FINISH

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

DRYVIT COMPATIBLE SEALANT,BY OTHERS

DRYVIT DEMANDIT® OR COLOR PRIME™ON SURFACE(S) TO RECEIVE SEALANT

DRYVIT DETAIL MESHWRAPPED TO BACKSIDE

OF EPS MIN. 2" (51 MM)

EPS INSULATION

DRYVIT DETAIL MESH® WRAPPED TOBACKSIDE OF EPS MIN. 2" (51 MM)

DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATIONAPPLIED TO BACK OF EPS

3/4" (19 MM ) MIN.

3/4"(19 MM) MIN.

DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL

CONFIGURATION

EPS SHAPE (OPTIONAL)

TRANSITION FLASHING,BY OTHERS

DRYVIT AQUAFLASHSYSTEM (SEE NOTE 2)

DRYVIT COMPATIBLESEALANT, BY OTHERS

PROVIDE AIR SEAL, BY OTHERS,AROUND INTERIOR OF WINDOW

PER WINDOW MANUFACTURER'SREQUIREMENTS

Outsulation® Plus MD System®

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc. Issued: 10/2016

Page 17: Outsulation Plus MD System Installation Detailscms.dryvit.com/media/304806/opmd-ds110-all-in-one.pdf · step #1 step #2 step #3 step #4 opening preparation - outsulation® plus md

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

OPMD 0.0.14

Storefront and Flanged Window Head

APPROVED SUBSTRATE

DRYVIT COMPATIBLE SEALANTWITH CLOSED CELL BACKERROD AND WEEP TUBES EVERY24" (610 MM). BY OTHERS

SEALANT AND FLASHING,BY OTHERS

3/4" (19 MM)

DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATIONAPPLIED TO BACK OF EPS

EPS INSULATION BOARD

DRYVIT BASE COAT

DRYVIT AQUAFLASH® SYSTEMOR DRYVIT BACKSTOP® NT™TEXTURE OVER DRYVIT GRID

TAPE™ (SEE NOTE 2)

DRYVIT AQUAFLASH® SYSTEMOVER CONTINUOUS FLASHINGWITH END DAMS

AIR SEAL PERMANUFACTURER'SREQUIREMENTS,BY OTHERS

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT(SEE NOTE 1)

DRYVIT DETAIL MESH® WRAPPEDTO BACKSIDE OF EPS MIN. 2" (51 MM)

DRYVIT DEMANDIT® OR COLOR PRIME™ON SURFACE(S) TO RECEIVE SEALANT

DRYVIT FINISH

EPS SHAPE (OPTIONAL)

OUTSULATIONPLUS MD SYSTEM

BY OTHERS

FLANGED WINDOW

WINDOWINTEGRALFLASHING

STOREFRONT WINDOW

DRYVIT DRAINAGE STRIP™ ADHEREDWITH DABS OF DRYVIT AP ADHESIVE

NOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD ORSTANDARD PLUS MESH. LOCATION OFHIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.

2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OFDRYVIT AQUAFLASH SYSTEM.

Outsulation® Plus MD System®

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc. Issued: 10/2016

Page 18: Outsulation Plus MD System Installation Detailscms.dryvit.com/media/304806/opmd-ds110-all-in-one.pdf · step #1 step #2 step #3 step #4 opening preparation - outsulation® plus md

OPMD 0.0.15

OUTSULATION PLUSMD SYSTEM

BY OTHERS

Head J-Track OptionOutsulation® Plus MD System®

EPS INSULATION

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

DRYVIT ADHESIVE INVERTICAL NOTCHED TROWELCONFIGURATION APPLIED TOBACK OF EPS

APPROVED SUBSTRATE

J-TRACK ATTACHED WITHDRYVIT AP ADHESIVE (SEE NOTE 2 AND 3)

SEALANT, BY OTHERS

DRYVIT AQUAFLASH® SYSTEMOR DRYVIT BACKSTOP® NT™TEXTURE OVER DRYVIT GRID

TAPE™ (SEE NOTE 4)

DRYVIT COMPATIBLE SEALANTWITH CLOSED CELL BACKER ROD,BY OTHERS

DRYVIT FINISH

DRYVIT REINFORCINGMESH EMBEDDED INDRYVIT BASE COAT

DRYVIT BASE COAT

3/4" (19 MM) MIN.

4. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.

3/4" (19 MM)

6" (152 MM)

6" (152 MM)

NOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER®MESH PRIOR TO STANDARD OR STANDARDPLUS MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ONCONTRACT DRAWINGS.

2. LIGHTLY SAND SURFACE OF J-TRACK TOMAXIMIZE ADHESION.

3. LENGTH OF TRACK NOT TO EXCEED 10 FT.(3.O M)

DRYVIT DEMANDIT® ORCOLOR PRIME ON SURFACESTO RECEIVE SEALANT

DRYVIT DETAIL MESH®WRAPPED TO BACKSIDEOF EPS MIN. 2" (51 MM)

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc. Issued: 10/2016

Page 19: Outsulation Plus MD System Installation Detailscms.dryvit.com/media/304806/opmd-ds110-all-in-one.pdf · step #1 step #2 step #3 step #4 opening preparation - outsulation® plus md

OPMD 0.0.16

Termination at Wood Framed DeckOutsulation® Plus MD System®NOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD ORSTANDARD PLUS MESH. LOCATION OFHIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.

2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.

3. DETAIL DOES NOT APPLY TO CANTILEVEREDDECKS. CANTILEVERED DECKS REQUIRE JOBSPECIFIC FLASHING DETAILS.

2" (51 MM)MIN.

FLASHING NO. 2, BY OTHERS

FLASHING NO. 3, BY OTHERS

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

APPROVED SUBSTRATE

DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATIONAPPLIED TO BACK OF EPS

1" (25 MM)MIN.

2-1/2"(64 MM)MIN.

DRYVIT COMPATIBLESEALANT, BY OTHERS

FLASHING NO. 1,BY OTHERS

DECK BOARD

END JOIST

DRYVIT DEMANDIT®OR COLOR PRIME™ON SURFACE(S) TORECEIVE SEALANT

2" (51 MM) MIN.

DRYVIT COMPATIBLESEALANT WITH BOND

BREAKER, BY OTHERS

DRYVIT DETAIL MESH® WRAPPED TOBACKSIDE OF EPS MIN. 2" (51 MM)

DRYVIT DRAINAGE STRIP™ADHERED WITH DABS OFDRYVIT AP ADHESIVE

DRYVIT FINISH

DRYVIT AQUAFLASH® SYSTEM OVERCONTINUOUS FLASHING (NOTE 2)

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

DRYVIT BASE COAT

EPS INSULATION BOARD

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc. Issued: 10/2016

Page 20: Outsulation Plus MD System Installation Detailscms.dryvit.com/media/304806/opmd-ds110-all-in-one.pdf · step #1 step #2 step #3 step #4 opening preparation - outsulation® plus md

Outsulation® Plus MD System® Termination at Waterproof Deck

OPMD 0.0.17

NOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD ORSTANDARD PLUS MESH. LOCATION OFHIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.

2. ENSURE BOTTOM EDGE OF DRAINAGESTRIP IS LEFT FREE TO DRAIN.

DRYVIT ADHESIVE IN VERTICAL NOTCHEDTROWEL CONFIGURATION APPLIED TOBACK OF EPS

DRYVIT DETAIL MESH® WRAPPEDTO BACKSIDE OF EPS MIN. 2" (51 MM )

SLOPE CONCRETE DECK SURFACEAWAY FROM VERTICAL WALL

2" (51 MM)MIN.

DRYVIT FINISH

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

DRYVIT DRAINAGE STRIP™ADHERED WITH DABS OF DRYVITAP ADHESIVE (SEE NOTE 2)

EPS INSULATION BOARD

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

DRYVIT BASE COAT

COMPATIBLE WATERPROOF DECKCOATING, BY OTHERS

CANT STRIP, BY OTHERS

FRAMING BYOTHERS

APPROVEDSUBSTRATE

OUTSULATIONPLUS MD SYSTEM

BY OTHERS

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc.Issued: 10/2016

Page 21: Outsulation Plus MD System Installation Detailscms.dryvit.com/media/304806/opmd-ds110-all-in-one.pdf · step #1 step #2 step #3 step #4 opening preparation - outsulation® plus md

Outsulation® Plus MD System® Preparation At Parapet/ Wall Intersection

OPMD 0.0.18

NOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER®MESH PRIOR TO STANDARD OR STANDARDPLUS MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ONCONTRACT DRAWINGS.

2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.

APPROVED SUBSTRATE

FRAMING BY OTHERS

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

FLASHING SLEEVE,BY OTHERS

DRYVIT AQUAFLASH®SYSTEM (SEE NOTE 2)

8"(203 MM)

DRYVIT AQUAFLASH®SYSTEM (SEE NOTE 2)

STEP #1 STEP #2

STEP #3

6"(152 MM)

6"(152 MM)

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc. Issued: 10/2016

Page 22: Outsulation Plus MD System Installation Detailscms.dryvit.com/media/304806/opmd-ds110-all-in-one.pdf · step #1 step #2 step #3 step #4 opening preparation - outsulation® plus md

Outsulation® Plus MD System® Termination At Parapet - Cap Flashing

ROOFASSEMBLY

OPMD 0.0.19

NOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER®MESH PRIOR TO STANDARD OR STANDARDPLUS MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ONCONTRACT DRAWINGS.

2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.

EPS SHAPE OPTION(SEE NOTE 4)

EPS INSULATION BOARD

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

DRYVIT DETAIL MESH®WRAPPED TO BACKSIDEOF EPS MIN. 2" (51 MM)(SEE NOTE 3)

DRYVIT FINISH

ROOF ASSEMBLY, BY OTHERS

2 1/2" (64 MM) MIN.

DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATION

APPLIED TO BACK OF EPS

FRAMING,BY OTHERS

DRYVIT AQUAFLASH®SYSTEM (SEE NOTE 2)

METAL CAP FLASHING,BY OTHERS

DRYVIT BASE COAT

APPROVED SUBSTRATE

DRYVIT REINFORCING MESH EMBEDDEDIN DRYVIT BASE COAT

DRYVIT COMPATIBLE SEALANT,BY OTHERS

3. EDGE WRAPPING METHOD IS ACCEPTABLEIN LIEU OF BACK WRAPPING. DRYVITREINFORCING MESH MUST BE FULLYEMBEDDED IN DRYVIT BASE COAT AT EPSEDGE AND EXTEND ONTO SUBSTRATE 2"(51 MM) MIN.

4. MAXIMUM THICKNESS OF EPS BUILT OUTSHAPES SHALL NOT EXCEED 13" (330 MM) ATANY POINT MEASURED FROM THESUBSTRATE.

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc. Issued: 10/2016

Page 23: Outsulation Plus MD System Installation Detailscms.dryvit.com/media/304806/opmd-ds110-all-in-one.pdf · step #1 step #2 step #3 step #4 opening preparation - outsulation® plus md
Page 24: Outsulation Plus MD System Installation Detailscms.dryvit.com/media/304806/opmd-ds110-all-in-one.pdf · step #1 step #2 step #3 step #4 opening preparation - outsulation® plus md

2"(51 MM)

MIN.

OPMD 0.0.21

Termination at Sloped RoofOutsulation® Plus MD System®

3/4"(19 MM)

MIN.

110

100

ROOF DIVERTER(SEE NOTE 2)

12"(305 MM)

6"(152 MM)

6"(152 MM)

DRYVIT FINISH

NOTE:1. EXTEND DIVERTER FLASHING (KICKOUT)A MINIMUM OF 1" (25 MM) BEYOND FACEOF THE SYSTEM.

2. ROOF DIVERTER TO BE MADE FROMCORROSION RESISTANT MATERIAL MIN.24 GAGE WITH WATER TIGHT SEAMS.

3. EXTEND ROOFING UNDERLAYMENT5" (127 MM) UP VERTICAL WALL BEHINDMETAL FLASHING.

4. METAL FLASHINGS ARE 10" (254 MM) X2" (51 MM) LONGER THAN THE EXPOSEDPORTION OF THE ROOFING SHINGLE AND AREBENT IN HALF TO ALLOW FOR TWO 5" (127 MM)LEGS. ALTHOUGH NOT SHOWN, METALFLASHINGS ARE STEP FLASHED(INTERWOVEN) WITH ROOFING SHINGLES.

5. FOR ADDITIONAL SLOPED ROOF DETAILS,REFER TO DRYVIT PUBLICATION DS106.

6. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.

DRYVIT AIR/WATER-RESISTIVE BARRIER COATINGDRYVIT ADHESIVE IN VERTICAL NOTCHED TROWELCONFIGURATION APPLIED TO BACK OF EPSEPS INSULATION BOARDDRYVIT BASE COAT

DRYVIT REINFORCING MESH EMBEDDED IN DRYVIT BASE COATDRYVIT AQUAFLASH® SYSTEM OVER FLASHING (SEE NOTE 6)DRYVIT DRAINAGE STRIP™ ADHERED WITHDABS OF DRYVIT AP ADHESIVEDRYVIT DETAIL MESH® WRAPPED TO BACKSIDEOF EPS MIN. 2" (51 MM)

ROOF STEP FLASHING, BY OTHERS (SEE NOTE 4)

ROOFING SHINGLES

ROOFING UNDERLAYMENT, BY OTHERS(SEE NOTE 3)

DRYVIT COMPATIBLE SEALANTWITH BOND BREAKER, BY OTHERS)

DRYVIT DEMANDIT® OR COLOR PRIME™ON SURFACE(S) TO RECEIVE SEALANT

GUTTER SYSTEM SLOPED AWAY FROM WALL

ROOF DIVERTER FLASHING, BY OTHERS(SEE NOTE 1 & 2)

FRAMING BYOTHERS

APPROVEDSUBSTRATE

OUTSULATION PLUS MD SYSTEM

BY OTHERS

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc.Issued: 10/2016

Page 25: Outsulation Plus MD System Installation Detailscms.dryvit.com/media/304806/opmd-ds110-all-in-one.pdf · step #1 step #2 step #3 step #4 opening preparation - outsulation® plus md

2" (51 MM) MIN.

OPMD 0.0.22

Termination at Roof Stop Flashing

3/4"(19 MM)

MIN.

NOTE:1. EXTEND ROOF STOP FLASHING 1" (25 MM)MINIMUM BEYOND FACE OF THE SYSTEM.

2. ROOF STOP TO BE MADE FROM CORROSIONRESISTANT MATERIAL MIN. 24 GAGE WITHWATER TIGHT SEAMS.

3. EXTEND ROOFING UNDERLAYMENT5" (127 MM) UP VERTICAL WALL BEHINDMETAL FLASHING.

DRIP EDGE FLASHING, BY OTHERS

DRYVIT FINISH

DRYVIT REINFORCING MESH EMBEDDED IN DRYVIT BASE COAT

DRYVIT AQUAFLASH® SYSTEM OVER FLASHINGS (SEE NOTE 4)

FRAMING BY OTHERS

APPROVED SUBSTRATE

DRYVIT ADHESIVE IN VERTICAL NOTCHED TROWELCONFIGURATION APPLIED TO BACK OF EPS

EPS INSULATION BOARD

DRYVIT BASE COAT

DRYVIT AIR/WATER-RESISTIVE BARRIER COATING

DRYVIT DETAIL MESH® WRAPPED TO BACKSIDEOF EPS MIN. 2" (51 MM)

ROOF/WALL FLASHING, BY OTHERS

ROOFING, BY OTHERS

DRYVIT COMPATIBLE SEALANTWITH BOND BREAKER, BY OTHERS

DRYVIT DEMANDIT® OR COLOR PRIME™ON SURFACE(S) TO RECEIVE SEALANT

ROOF STOP FLASHING, BY OTHERS(SEE NOTE 2)

ROOFING UNDERLAYMENT, BY OTHERS(SEE NOTE 3)

DRYVIT DRAINAGE STRIP™ ADHERED WITHDABS OF DRYVIT AP ADHESIVE

Outsulation® Plus MD System®4. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.

OUTSULATION PLUS MDSYSTEM

BY OTHERS

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc. Issued: 10/2016

Page 26: Outsulation Plus MD System Installation Detailscms.dryvit.com/media/304806/opmd-ds110-all-in-one.pdf · step #1 step #2 step #3 step #4 opening preparation - outsulation® plus md

OPMD 0.0.23

Vertical Wall/ Suspended Soffit TransitionOutsulation® Plus MD System®NOTE:1. DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSED TOABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIOR TOSTANDARD OR STANDARD PLUS MESH.LOCATION OF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.

2. DRYVIT DEMANDIT® OR COLOR PRIME™ON SURFACES TO RECEIVE SEALANT.

3. DRYVIT AIR/WATER-RESISTIVE BARRIER ISREQUIRED OVER VERTICAL SUBSTRATES.APPLICATION OVER HORIZONTAL SOFFITSUBSTRATE IS OPTIONAL UNLESS REQUIRED ASPART OF A CONTINUOUS AIR BARRIER SYSTEM.

4. SEALANT JOINT IS REQUIRED FOR SUSPENDEDSOFFITS. OPTIONAL FOR RIGIDLY FRAMED.

3/4" (19 MM) MIN.

DRYVIT DETAIL MESH® WRAPPED TOBACKSIDE OF EPS MIN. 2" (51 MM)

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

DRYVIT ADHESIVEAPPLIED TO BACK OF EPS

DRYVIT BASE COAT

EPS INSULATION BOARD

DRYVIT FINISH

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING (SEE NOTE 3)

APPROVED SUBSTRATE

FRAMING BY OTHERS

DRYVIT COMPATIBLE SEALANT WITHCLOSED CELL BACKER ROD, BY OTHERS(SEE NOTE 2 AND 4)

DRYVIT AQUAFLASH® SYSTEM

DRYVIT COMPATIBLE SEALANTWITH CLOSED CELL BACKER ROD,

BY OTHERS (SEE NOTE 2 AND 4)

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc. Issued: 10/2016

Page 27: Outsulation Plus MD System Installation Detailscms.dryvit.com/media/304806/opmd-ds110-all-in-one.pdf · step #1 step #2 step #3 step #4 opening preparation - outsulation® plus md

OPMD 0.0.24

Transition At Soffit/ Fascia IntersectionOutsulation® Plus MD System®NOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD ORSTANDARD PLUS MESH. LOCATION OFHIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.

2. ENSURE BOTTOM EDGE OF DRAINAGESTRIP IS LEFT FREE TO DRAIN.

3. DRYVIT AIR/WATER-RESISTIVE BARRIER ISREQUIRED OVER VERTICAL SUBSTRATES,APPLICATION OVER HORIZONTAL SOFFITSUBSTRATE IS OPTIONAL UNLESS REQUIRED ASPART OF A CONTINUOUS AIR BARRIER SYSTEM.

FRAMING BY OTHERS

APPROVED SUBSTRATE

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

DRYVIT BASE COAT

EPS INSULATION BOARD

DRYVIT FINISH

DRYVIT AIR/WATER-RESISTIVE BARRIERCOATING (SEE NOTE 3)

DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATIONAPPLIED TO BACK OF EPS

DRYVIT FINISH

DRYVIT ADHESIVEAPPLIED TO BACK

OF EPS

DRYVIT DRAINAGE STRIP™ADHERED WITH DABS OF DRYVIT

AP ADHESIVE (SEE NOTE 2)

DRYVIT DETAIL MESH® WRAPPEDTO BACKSIDE OF EPS MIN. 2" (51 MM)

DRYVIT BACKSTOP® NT™-TEXTUREOVER DRYVIT GRID TAPE™

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc.Issued: 10/2016

Page 28: Outsulation Plus MD System Installation Detailscms.dryvit.com/media/304806/opmd-ds110-all-in-one.pdf · step #1 step #2 step #3 step #4 opening preparation - outsulation® plus md

OPMD 0.0.25

Outsulation® Plus MD System® Fascia/ Uninsulated Soffit Transition

NOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD ORSTANDARD PLUS MESH. LOCATION OFHIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.

2. SOFFITS WITHOUT EPS INSULATIONREQUIRE EXPANSION JOINTS EVERY20 FT (6 M).

3. REFER TO DRYVIT PUBLICATION DS 173 FORSPECIFIC REQUIREMENTS FOR SOFFIT AREAS.

4. BOTTOM EDGE OF DRYVIT DRAINAGE STRIPSHALL BE MASKED DURING INSTALLATION TOPREVENT CLOGGING OF DRAINAGE CHANNELS.

DRYVIT DRAINAGE STRIP™ADHERED WITH DABS OF DRYVITAP ADHESIVE (SEE NOTE 4)

DRYVIT BACKSTOP® NT-TEXTURE™OVER DRYVIT GRID TAPE™

FRAMING BY OTHERS

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATIONAPPLIED TO BACK OF EPS

DRYVIT BASE COAT

EPS INSULATION BOARD

DRYVIT DETAIL MESH® WRAPPEDTO BACKSIDE OF EPS MIN. 2" (51 MM)

DRYVIT FINISH

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

APPROVED SUBSTRATE

1" (25 MM) MAX.

CASING BEAD, BY OTHERS

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc. Issued: 10/2016

Page 29: Outsulation Plus MD System Installation Detailscms.dryvit.com/media/304806/opmd-ds110-all-in-one.pdf · step #1 step #2 step #3 step #4 opening preparation - outsulation® plus md

OPMD 0.0.26

Termination at Uninsulated Soffit VentOutsulation® Plus MD System®

FRAMING, BY OTHERS

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

APPROVED SUBSTRATE

DRYVIT FINISH

NOTE:1. CONTROL JOINTS ARE RECOMMENDEDEVERY 20 FT (6.1 M).

2. REFER TO DRYVIT PUBLICATION DS173FOR SPECIFIC REQUIREMENTS FORSOFFIT AREAS.

3. SEAL ALL BUTT JOINTS,INTERSECTIONS, AND ENDS OF VENTSWITH COMPATIBLE SEALANT.

4. SEE DRYVIT PUBLICATION DS842 FORADDITIONAL DIRECT APPLIED DETAILS.

DRYVIT BASE COAT

DRYVIT BASE COAT

SOFFIT VENT, BY OTHERS

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc.Issued: 10/2016

Page 30: Outsulation Plus MD System Installation Detailscms.dryvit.com/media/304806/opmd-ds110-all-in-one.pdf · step #1 step #2 step #3 step #4 opening preparation - outsulation® plus md

BY OTHERS

Outsulation® Plus MD System®

OPMD 0.0.27

Horizontal Slip Joint without WeepsNOTE:1. DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSED TOABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIOR TOSTANDARD OR STANDARD PLUS MESH.LOCATION OF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.

2. LOCATE EXTERNAL SEALANT JOINT WITHIN2" (51 MM) OF BREAK IN SHEATHING.

3. EXPANSION JOINT IN THE OUTSULATIONPLUS MD SYSTEM IS NECESSARY WHERESIGNIFICANT DIFFERENTIAL MOVEMENT ISEXPECTED AT FLOOR LINES.

4. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHING TAPE™MAY BE USED IN LIEU OF DRYVIT AQUAFLASHSYSTEM OVER PREPARED JOINT.

5. SEALANT SHOULD NOT BE IN DIRECT CONTACTWITH ASPHALTIC ADHESIVE ON DRYVIT FLASHINGTAPE. COVER DRYVIT FLASHING TAPE LAPS WITHPOLYETHYLENE TAPE OR BACKER ROD.

6. FOR STEEL FRAMED CONSTRUCTION:EXPANSION JOINT IS INTENDED TOACCOMMODATE MOVEMENT AT SLIIPCONNECTION. FOR WOOD FRAMEDCONSTRUCTION: EXPANSION JOINT IS INTENDEDTO ACCOMMODATE CROSS GRAIN SHRINKAGEFOR FLOOR BEAMS.

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

APPROVED SUBSTRATE

DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATION

APPLIED TO BACK OF EPS

DRYVIT DETAIL MESH®WRAPPED TO BACKSIDE OFEPS MIN. 2" (51 MM)

CLOSED CELL BACKERROD, BY OTHERS

(SEE NOTE 2)

DRYVIT AQUAFLASH®SYSTEM (SEE NOTE 4)

SLIP TYPECONNECTION(SEE NOTE 6)

3/4" (19 MM) MIN.

OUTSULATIONPLUS MD SYSTEM

DRYVIT BASE COAT

DRYVIT REINFORCINGMESH EMBEDDED INDRYVIT BASE COAT

DRYVIT FINISH

DRYVIT DETAIL MESH®WRAPPED TO BACKSIDEOF EPS MIN. 2" (51 MM)

EPS INSULATION BOARD

SLOPE SURFACEOUTSIDE OF SEALANT 1:5MIN. OUTWARD TO DRAIN

DRYVIT COMPATIBLESEALANT WITH CLOSEDCELL BACKER ROD, BYOTHERS (SEE NOTE 5)

DRYVIT DEMANDIT® OR COLOR PRIME™ON SURFACES TO RECEIVE SEALANT

DRYVIT DRAINAGE STRIP™ ADHEREDWITH DABS OF DRYVIT AP ADHESIVEALONG TOP OF STRIP ONLY

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc. Issued: 10/2016

Page 31: Outsulation Plus MD System Installation Detailscms.dryvit.com/media/304806/opmd-ds110-all-in-one.pdf · step #1 step #2 step #3 step #4 opening preparation - outsulation® plus md

Outsulation® Plus MD System®

OPMD 0.0.28

Horizontal Slip Joint with Weeps

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

APPROVED SUBSTRATE

DRYVIT AQUAFLASH SYSTEM(SEE NOTE 4 AND 5)

CLOSED CELL BACKERROD, BY OTHERS

(SEE NOTE 3) DRYVIT DEMANDIT® OR COLOR PRIME™ON SURFACES TO RECEIVE SEALANT

DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATION

APPLIED TO BACK OF EPS

WEEPS AT 2'-0" O.C., BY OTHERS

NOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD ORSTANDARD PLUS MESH. LOCATION OFHIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.

2. EXPANSION JOINT IN THE OUTSULATIONPLUS MD SYSTEM IS NECESSARY WHERESIGNIFICANT DIFFERENTIAL MOVEMENT ISEXPECTED AT FLOOR LINES.

3. LOCATE EXTERNAL SEALANT JOINTWITHIN 2" (51 MM) OF BREAK IN SHEATHING.

4. STOP AQUAFLASH SHORT OF SEALANTBOND LINE.

5. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.

6. FOR STEEL FRAMED CONSTRUCTION:EXPANSION JOINT IS INTENDED TOACCOMMODATE MOVEMENT AT SLIIPCONNECTION. FOR WOOD FRAMEDCONSTRUCTION: EXPANSION JOINT ISINTENDED TO ACCOMMODATE CROSSGRAIN SHRINKAGE FOR FLOOR BEAMS.

SLIP TYPECONNECTION(SEE NOTE 6)

SLOPE SURFACE 1:5 MIN.OUTWARD TO DRAIN

OUTSULATIONPLUS MDSYSTEM

BY OTHERS

DRYVIT DETAIL MESH®WRAPPED TO BACKSIDE

OF EPS MIN. 2" (51 MM) DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

DRYVIT BASE COAT

DRYVIT REINFORCINGMESH EMBEDDED INDRYVIT BASE COAT

EPS INSULATION BOARD

DRYVIT FINISH

DRYVIT DETAIL MESH®WRAPPED TO BACKSIDEOF EPS MIN. 2" (51 MM)

3/4" (19 MM) MIN.

DRYVIT COMPATIBLE SEALANTWITH CLOSED CELL BACKERROD, BY OTHERS (SEE NOTE 3)

DRYVIT AQUAFLASH®SYSTEM (SEE NOTE 5)

DRYVIT DRAINAGE STRIP™ ADHERED WITH DABS OFDRYVIT AP ADHESIVE ALONG TOP OF STRIP ONLY

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc. Issued: 10/2016

Page 32: Outsulation Plus MD System Installation Detailscms.dryvit.com/media/304806/opmd-ds110-all-in-one.pdf · step #1 step #2 step #3 step #4 opening preparation - outsulation® plus md

OUTSULATION PLUSMD SYSTEM

BY OTHERS

Outsulation® Plus MD System®

OPMD 0.0.29

Horizontal Joint - Substrate ChangeNOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER®MESH PRIOR TO STANDARD OR STANDARDPLUS MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ONCONTRACT DRAWINGS.

2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM OVER PREPAREDJOINT AT CHANGE IN SUBSTRATE.

3. SEALANT SHALL NOT BE IN DIRECTCONTACT WITH ASPHALTIC ADHESIVE ONDRYVIT FLASHING TAPE. COVER DRYVITFLASHING TAPE LAPS WITH POLYETHYLENETAPE OR BACKER ROD.

4. REFER TO DETAIL OPMD 0.0.28 FORCONFIGURATION REQUIRING WEEPS.

3/4" (19 MM ) MIN.

4

DRYVIT DRAINAGE STRIP™™ADHERED WITH DABS OFDRYVIT AP ADHESIVE ALONGTOP OF STRIP ONLY

DRYVIT DEMANDIT® OR COLORPRIME™ ON SURFACES TORECEIVE SEALANT

DRYVIT COMPATIBLE SEALANTWITH CLOSED CELL BACKERROD, BY OTHERS (SEE NOTE 3)

SLOPE SURFACE OUTSIDE OFSEALANT 1:5 MIN. OUTWARDTO DRAIN

DRYVIT FINISH

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

DRYVIT BASE COAT

DRYVIT DETAIL MESH®WRAPPED TO BACKSIDEOF EPS MIN. 2" (51 MM)

EPS INSULATION BOARD

FRAMING

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

DRYVIT ADHESIVE IN VERTICAL NOTCHEDTROWEL CONFIGURATION APPLIED TO

BACK OF EPS

APPROVED SUBSTRATE

DRYVIT BACKSTOP® NT™-TEXTUREOVER GRID TAPE™

DRYVIT AQUAFLASH® SYSTEM(SEE NOTE 2)

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc. Issued: 10/2016

Page 33: Outsulation Plus MD System Installation Detailscms.dryvit.com/media/304806/opmd-ds110-all-in-one.pdf · step #1 step #2 step #3 step #4 opening preparation - outsulation® plus md

Outsulation® Plus MD System®

OPMD 0.0.30

Horizontal Termination at Stone VeneerNOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD ORSTANDARD PLUS MESH. LOCATION OF HIGHIMPACT ZONES SHOULD BE INDICATED ONCONTRACT DRAWINGS.

2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.

3. FOR INSTALLATION OF DRYVITAIR/WATER-RESISTIVE BARRIER COATINGBENEATH CLADDINGS OTHER THAN DRYVITEIFS, REFER TO DRYVIT PUBLICATION DS840.

CONTINUOUS FLASHING,BY OTHERS

SEALANT WITH BOND BREAKER,BY OTHERS

FRAMING BY OTHERS

DRYVIT AQUAFLASH® SYSTEM(SEE NOTE 2)

APPROVED SUBSTRATE

PAPER BACKED EXPANDED METAL LATHOR OTHER SLIP SHEET, BY OTHERS

DRYVIT DRAINAGE STRIP™™ADHERED WITH DABS OFDRYVIT AP ADHESIVE

DRYVIT DEMANDIT® OR COLORPRIME™ ON SURFACE(S) TORECEIVE SEALANT

DRYVIT COMPATIBLE SEALANTWITH CLOSED CELL BACKERROD AND WEEP TUBES EVERY24" (610 MM). BY OTHERS

STONE VENEER SYSTEM,BY OTHERS

DRYVIT ADHESIVE IN VERTICALNOTCHED TROWELCONFIGURATION APPLIED TOBACK OF EPS

DRYVIT FINISH

DRYVIT BASE COAT

DRYVIT REINFORCINGMESH EMBEDDED INDRYVIT BASE COAT

DRYVIT DETAIL MESH®WRAPPED TO BACKSIDEOF EPS MIN. 2" (51 MM)

EPS INSULATION BOARD

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING EXTENDEDBEHIND FLASHING (SEE NOTE 3)

3/4" (19 MM) MIN.

OUTSULATIONPLUS MD SYSTEM

BY OTHERS

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc. Issued: 10/2016

Page 34: Outsulation Plus MD System Installation Detailscms.dryvit.com/media/304806/opmd-ds110-all-in-one.pdf · step #1 step #2 step #3 step #4 opening preparation - outsulation® plus md

Outsulation® Plus MD System®

OPMD 0.0.31

Horizontal Termination at StuccoNOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD ORSTANDARD PLUS MESH. LOCATION OF HIGHIMPACT ZONES SHOULD BE INDICATED ONCONTRACT DRAWINGS.

2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.

3. FOR INSTALLATION OF DRYVITAIR/WATER-RESISTIVE BARRIERCOATING BENEATH CLADDINGS OTHERTHAN DRYVIT EIFS, REFER TO DRYVITPUBLICATION DS840.

DRYVIT DRAINAGE STRIP™ADHERED WITH DABS OFDRYVIT AP ADHESIVE

DRYVIT DEMANDIT® OR COLORPRIME™ ON SURFACE(S) TORECEIVE SEALANT

DRYVIT FINISHDRYVIT BASE COAT

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

DRYVIT DETAIL MESH®WRAPPED TO BACKSIDEOF EPS MIN. 2" (51 MM)

DRYVIT COMPATIBLE SEALANTWITH CLOSED CELL BACKER RODAND WEEP TUBES EVERY24" (610 MM), BY OTHERS

CONTINUOUS FLASHING,BY OTHERS

FRAMING BY OTHERS

DRYVIT AQUAFLASH® SYSTEM(SEE NOTE 2)

APPROVED SUBSTRATE

SEALANT WITH BOND BREAKER,BY OTHERS

CEMENT PLASTER,BY OTHERS

PAPER BACKED EXPANDED METAL LATHOR OTHER SLIP SHEET, BY OTHERS

3/4" (19 MM) MIN.

DRYVIT ADHESIVE IN VERTICALNOTCHED TROWELCONFIGURATION APPLIED TOBACK OF EPSEPS INSULATION BOARD

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING EXTENDEDBEHIND FLASHING (SEE NOTE 3)

OUTSULATIONPLUS MD SYSTEM

BY OTHERS

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc. Issued: 10/2016

Page 35: Outsulation Plus MD System Installation Detailscms.dryvit.com/media/304806/opmd-ds110-all-in-one.pdf · step #1 step #2 step #3 step #4 opening preparation - outsulation® plus md

Outsulation® Plus MD System®

OPMD 0.0.32

Horizontal Termination at Wood Siding

FRAMING BY OTHERS

DRYVIT AQUAFLASH® SYSTEM(SEE NOTE 2)

APPROVED SUBSTRATE

SEALANT WITH BOND BREAKER,BY OTHERS

LAP SIDING, BY OTHERS

DRYVIT COMPATIBLE SEALANTWITH CLOSED CELL BACKERROD AND WEEP TUBES EVERY24" (610 MM). BY OTHERS

CONTINUOUS FLASHING,BY OTHERS

DRYVIT DRAINAGE STRIP™ADHERED WITH DABS OFDRYVIT AP ADHESIVE

DRYVIT DEMANDIT® OR COLORPRIME™ ON SURFACE(S) TORECEIVE SEALANT

3/4" (19 MM) MIN.

NOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARDOR STANDARD PLUS MESH. LOCATIONOF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.

2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.

3. FOR INSTALLATION OF DRYVITAIR/WATER-RESISTIVE BARRIER COATINGBENEATH CLADDINGS OTHER THAN DRYVITEIFS, REFER TO DRYVIT PUBLICATION DS840.

DRYVIT FINISH

DRYVIT BASE COAT

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

DRYVIT DETAIL MESH®WRAPPED TO BACKSIDEOF EPS MIN. 2" (51 MM)

DRYVIT ADHESIVE IN VERTICALNOTCHED TROWELCONFIGURATION APPLIED TOBACK OF EPSEPS INSULATION BOARD

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING EXTENDEDBEHIND FLASHING (SEE NOTE 3)

OUTSULATIONPLUS MD SYSTEM

BY OTHERS

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc.Issued: 10/2016

Page 36: Outsulation Plus MD System Installation Detailscms.dryvit.com/media/304806/opmd-ds110-all-in-one.pdf · step #1 step #2 step #3 step #4 opening preparation - outsulation® plus md

OPMD 0.0.33

Outsulation® Plus MD System® Vertical Expansion Joint - EIFS

3/4" (19 MM) MIN.

NOTE:1. DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSED TOABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIOR TOSTANDARD OR STANDARD PLUS MESH.LOCATION OF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.

2. EIFS EXPANSION JOINTS ARE REQUIRED INCONTINUOUS ELEVATIONS AT INTERVALS NOTEXCEEDING 75 FT (23 M).

3

DRYVIT BASE COAT

DRYVIT DETAIL MESH®WRAPPED TO BACKSIDEOF EPS MIN. 2" (51 MM)

DRYVIT DEMANDIT® OR COLORPRIME™ ON SURFACES TORECEIVE SEALANT

DRYVIT FINISH

DRYVIT COMPATIBLESEALANT WITH CLOSED CELLBACKER ROD, BY OTHERS

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

FRAMING BY OTHERS

APPROVED SUBSTRATE

DRYVIT ADHESIVE IN VERTICALNOTCHED TROWELCONFIGURATION APPLIED TOBACK OF EPSEPS INSULATION BOARD

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING EXTENDEDBEHIND FLASHING (SEE NOTE 3)

OUTSULATIONPLUS MD SYSTEM

BY OTHERS

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc.Issued: 10/2016

Page 37: Outsulation Plus MD System Installation Detailscms.dryvit.com/media/304806/opmd-ds110-all-in-one.pdf · step #1 step #2 step #3 step #4 opening preparation - outsulation® plus md

OPMD 0.0.34

Outsulation® Plus MD System® Through-Wall Expansion Joint

NOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD ORSTANDARD PLUS MESH. LOCATION OFHIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.

2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.

3. SEALANT SHALL NOT BE IN DIRECT CONTACTWITH ASPHALTIC ADHESIVE ON DRYVITFLASHING TAPE. COVER DRYVIT FLASHINGTAPE LAPS WITH POLYETHYLENE TAPE ORBACKER ROD.

4. LOCATE EXTERNAL SEALANT JOINT WITHIN2" (51 MM) OF SUBSTRATE JOINT.

DRYVIT DEMANDIT® OR COLOR PRIME™ON SURFACES TO RECEIVE SEALANT

DRYVIT FINISH

DRYVIT COMPATIBLE SEALANT WITH CLOSEDCELL BACKER ROD, BY OTHERS (SEE NOTE 3)

FRAMING BY OTHERS

DRYVIT AIR/WATER-RESISTIVE BARRIER COATING

APPROVED SUBSTRATE

DRYVIT ADHESIVE IN VERTICAL NOTCHED TROWELCONFIGURATION APPLIED TO BACK OF EPS

DRYVIT BASE COAT

DRYVIT DETAIL MESH® WRAPPED TOBACKSIDE OF EPS MIN. 2" (51 MM )

EPS INSULATION BOARD

DRYVIT REINFORCING MESH EMBEDDEDIN DRYVIT BASE COAT

DRYVIT AIR/WATER-RESISTIVE BARRIER COATING

DRYVIT ADHESIVE IN VERTICAL NOTCHED TROWELCONFIGURATION APPLIED TO BACK OF EPS

OPTIONAL SECONDARY SEAL, BY OTHERS

DRYVIT DEMANDIT OR COLOR PRIME ONSURFACES TO RECEIVE SEALANT

DRYVIT COMPATIBLE SEALANT WITH CLOSEDCELL BACKER ROD, BY OTHERS (SEE NOTE 3)

DRYVIT DETAIL MESH WRAPPED TOBACKSIDE OF EPS MIN. 2" (51 MM)

DRYVIT AQUAFLASH SYSTEM (SEE NOTE 2)

OPTIONAL SECONDARY SEAL, BY OTHERS

CLOSED CELL BACKER ROD, BY OTHERS (SEE NOTE 4)

DRYVIT AQUAFLASH® SYSTEM (SEE NOTE 2)

3/4" (19 MM) MIN.

3/4" (19 MM ) MIN.

FRAMING BY OTHERS

APPROVED SUBSTRATE

DRYVIT FINISH

DRYVIT BASE COAT

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

EPS INSULATION BOARD

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc. Issued: 10/2016

Page 38: Outsulation Plus MD System Installation Detailscms.dryvit.com/media/304806/opmd-ds110-all-in-one.pdf · step #1 step #2 step #3 step #4 opening preparation - outsulation® plus md

OPMD 0.0.35

Outsulation® Plus MD System® Vertical Expansion Joint - Flush Option

3/4" (19 MM) MIN.

NOTE:

1. DRYVIT RECOMMENDS THAT GROUND

FLOOR APPLICATIONS AND ALL FACADES

EXPOSED TO ABNORMAL STRESS, HIGH

TRAFFIC, OR DELIBERATE IMPACT HAVE

THE BASE COAT REINFORCED WITH

PANZER® MESH PRIOR TO STANDARD OR

STANDARD PLUS MESH. LOCATION OF

HIGH IMPACT ZONES SHOULD BE

INDICATED ON CONTRACT DRAWINGS.

2. DRYVIT FLASHING TAPE SURFACE

CONDITIONER™ AND DRYVIT FLASHING

TAPE™ MAY BE USED IN LIEU OF DRYVIT

AQUAFLASH SYSTEM.

3. SEALANT SHALL NOT BE IN DIRECT

CONTACT WITH ASPHALTIC ADHESIVE ON

DRYVIT FLASHING TAPE. COVER DRYVIT

FLASHING TAPE LAPS WITH POLYETHYLENE

TAPE OR BACKER ROD.

DRYVIT AQUAFLASH®

SYSTEM (SEE NOTE 2)

FRAMING BY OTHERS

APPROVED SUBSTRATE

DRYVIT BASE COAT

DRYVIT DETAIL MESH®

WRAPPED TO BACKSIDE

OF EPS MIN. 2" (51 MM)

DRYVIT DEMANDIT® OR COLOR

PRIME™ ON SURFACES TO

RECEIVE SEALANT

DRYVIT FINISH

DRYVIT COMPATIBLE

SEALANT WITH CLOSED CELL

BACKER ROD, BY OTHERS

(SEE NOTE 3)

DRYVIT BACKSTOP® NT™-

TEXTURE OVER DRYVIT

GRID TAPE™

DRYVIT AIR/WATER-RESISTIVE

BARRIER COATING

DRYVIT ADHESIVE IN

VERTICAL NOTCHED TROWEL

CONFIGURATION APPLIED TO

BACK OF EPS

EPS INSULATION BOARD

DRYVIT REINFORCING MESH

EMBEDDED IN DRYVIT BASE COAT

©

The architecture, engineering, and design of the project using the

Dryvit products is the responsibility of the project's design

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

and Dryvit specifically disclaims any liability for the use of this detail

and for the architecture, design, engineering or workmanship of any

project. The project design professional determines, in its sole

discretion, whether this detail or a functionally equivalent detail is

best suited for the project. Use of a functionally equivalent detail does

not violate Dryvit's warranty. This detail is subject to change without

notice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc.

Issued: 10/2016

Page 39: Outsulation Plus MD System Installation Detailscms.dryvit.com/media/304806/opmd-ds110-all-in-one.pdf · step #1 step #2 step #3 step #4 opening preparation - outsulation® plus md

OPMD 0.0.36

Outsulation® Plus MD System® Vertical Expansion Joint - Recessed Option

3/4" (19 MM) MIN.

NOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD ORSTANDARD PLUS MESH. LOCATION OF HIGHIMPACT ZONES SHOULD BE INDICATED ONCONTRACT DRAWINGS.

2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.

3. SEALANT SHALL NOT BE IN DIRECTCONTACT WITH ASPHALTIC ADHESIVE ONDRYVIT FLASHING TAPE. COVER DRYVITFLASHING TAPE LAPS WITH POLYETHYLENETAPE OR BACKER ROD.

DRYVIT AQUAFLASH® SYSTEM(SEE NOTE 2)

FRAMING BY OTHERS

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

APPROVED SUBSTRATE

DRYVIT ADHESIVE INVERTICAL NOTCHED TROWELCONFIGURATION APPLIED TOBACK OF EPS

DRYVIT BASE COAT

DRYVIT DETAIL MESH®WRAPPED TO BACKSIDEOF EPS MIN. 2" (51 MM)

EPS INSULATION BOARD

DRYVIT DEMANDIT® OR COLORPRIME™ ON SURFACES TORECEIVE SEALANT

DRYVIT FINISH

DRYVIT COMPATIBLESEALANT WITH CLOSED CELLBACKER ROD, BY OTHERS(SEE NOTE 3)

DRYVIT BACKSTOP® NT™-TEXTURE OVER DRYVIT

GRID TAPE™

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc. Issued: 10/2016

Page 40: Outsulation Plus MD System Installation Detailscms.dryvit.com/media/304806/opmd-ds110-all-in-one.pdf · step #1 step #2 step #3 step #4 opening preparation - outsulation® plus md

OPMD 0.0.37

Outsulation® Plus MD System®

3/4" (19 MM) MIN.

Vertical Expansion Joint - Double Seal Option

REAR SEAL

FACE SEAL

VENT

NOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER®MESH PRIOR TO STANDARD OR STANDARDPLUS MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ONCONTRACT DRAWINGS.

2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.

3. SEALANT SHALL NOT BE IN DIRECTCONTACT WITH ASPHALTIC ADHESIVE ONDRYVIT FLASHING TAPE. COVER DRYVITFLASHING TAPE LAPS WITH POLYETHYLENETAPE OR BACKER ROD.

APPROVED SUBSTRATE

DRYVIT BASE COAT

DRYVIT DETAIL MESH®WRAPPED TO BACKSIDEOF EPS MIN. 2" (51 MM)

DRYVIT DEMANDIT® OR COLORPRIME™ ON SURFACES TORECEIVE SEALANT

DRYVIT FINISH

DRYVIT COMPATIBLESEALANT WITH CLOSED CELLBACKER ROD, BY OTHERS(SEE NOTE 3)

REAR SEAL

FACE SEAL

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

DRYVIT ADHESIVE INVERTICAL NOTCHED TROWELCONFIGURATION APPLIED TOBACK OF EPS

EPS INSULATION BOARD

VENT

DRYVIT AQUAFLASH®SYSTEM (SEE NOTE 2)

FRAMING BY OTHERS

DRYVIT BACKSTOP® NT™-TEXTURE OVER DRYVIT

GRID TAPE™

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc. Issued: 10/2016

Page 41: Outsulation Plus MD System Installation Detailscms.dryvit.com/media/304806/opmd-ds110-all-in-one.pdf · step #1 step #2 step #3 step #4 opening preparation - outsulation® plus md

OPMD 0.0.38

Outsulation® Plus MD System®

3/4" (19 MM) MIN.

Vertical Termination At Stone Veneer

NOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD ORSTANDARD PLUS MESH. LOCATION OFHIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.

2. FOR INSTALLATION OF DRYVITAIR/WATER-RESISTIVE BARRIER COATINGBENEATH CLADDINGS OTHER THANDRYVIT EIFS, REFER TO DRYVITPUBLICATION DS840.

FRAMING BY OTHERS

APPROVED SUBSTRATE

DRYVIT BASE COAT

DRYVIT DETAIL MESH®WRAPPED TO BACKSIDEOF EPS MIN. 2" (51 MM)

DRYVIT DEMANDIT® OR COLORPRIME™ ON SURFACES TORECEIVE SEALANT

DRYVIT FINISH

DRYVIT COMPATIBLESEALANT WITH CLOSED CELLBACKER ROD, BY OTHERS

BEDDING COAT AND STONEVENEER SYSTEM, BY OTHERS

DRYVIT REINFORCING MESHEMBEDDED IN BASE COAT

PAPER BACKED EXPANDEDMETAL LATH, BY OTHERS

ANGLE STOP FOR STONEVENEER SYSTEM, BY OTHERS

DRYVIT ADHESIVE IN VERTICALNOTCHED TROWELCONFIGURATION APPLIED TOBACK OF EPSEPS INSULATION BOARD

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING EXTENDEDBEHIND ANGLE STOP (SEE NOTE 2)

OUTSULATIONPLUS MD SYSTEM

BY OTHERS

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc.Issued: 10/2016

Page 42: Outsulation Plus MD System Installation Detailscms.dryvit.com/media/304806/opmd-ds110-all-in-one.pdf · step #1 step #2 step #3 step #4 opening preparation - outsulation® plus md

Outsulation® Plus MD System®

OPMD 0.0.39

PenetrationsNOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD ORSTANDARD PLUS MESH. LOCATION OFHIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.

2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.

3. SEALANT SHALL NOT BE IN DIRECTCONTACT WITH ASPHALTIC ADHESIVE ONDRYVIT FLASHING TAPE. COVER DRYVITFLASHING TAPE LAPS WITH POLYETHYLENETAPE OR BACKER ROD.

3/4" (19 MM) MIN.

EPS INSULATION BOARD

APPROVED SUBSTRATE

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

DRYVIT BASE COAT

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

DRYVIT FINISH

DRYVIT ADHESIVE IN VERTICAL NOTCHEDTROWEL CONFIGURATION APPLIED TOBACK OF EPS

OPTIONAL SECONDARY SEAL, BY OTHERS

FRAMING BY OTHERS

DRYVIT COMPATIBLE SEALANT WITHCLOSED CELL BACKER ROD, BY OTHERS(SEE NOTE 3)

DRYVIT DEMANDIT OR COLOR PRIMEON SURFACES TO RECEIVE SEALANT

DRYVIT DETAIL MESH® WRAPPEDTO BACKSIDE OF EPS MIN. 2"(51 MM)

DRYVIT AQUAFLASH® SYSTEM(SEE NOTE 2)

OUTSULATION PLUS MDSYSTEM

BY OTHERS

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc. Issued: 10/2016

Page 43: Outsulation Plus MD System Installation Detailscms.dryvit.com/media/304806/opmd-ds110-all-in-one.pdf · step #1 step #2 step #3 step #4 opening preparation - outsulation® plus md

OPMD 0.0.40

Sign AttachmentOutsulation® Plus MD System®NOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER®MESH PRIOR TO STANDARD OR STANDARDPLUS MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ONCONTRACT DRAWINGS.

2. PERIMETER OF PIPE SLEEVE IS SEALED TOPREVENT WATER ENTRY INTO WALL.

1/2" (12.7 MM) MIN.

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

DRYVIT BASE COAT

DRYVIT FINISH

SCREW/BOLT ATTACHMENT TO BUILDINGFRAMING/BLOCKING, BY OTHERS

NEOPRENE WASHER, BY OTHERS

SIGN FIXTURE, BY OTHERS

DRYVIT COMPATIBLE SEALANT AND BONDBREAKER TAPE, BY OTHERS (SEE NOTE 2)

NON-CORROSIVE PIPE SLEEVE, BYOTHERS, SET IN SEALANT

BLOCKING, SECURED TO FRAMING

FRAMING BY OTHERS

APPROVED SUBSTRATE

DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATIONAPPLIED TO BACK OF EPS

EPS INSULATION BOARD

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

OUTSULATIONPLUS MD SYSTEM

BY OTHERS

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc. Issued: 10/2016

Page 44: Outsulation Plus MD System Installation Detailscms.dryvit.com/media/304806/opmd-ds110-all-in-one.pdf · step #1 step #2 step #3 step #4 opening preparation - outsulation® plus md

Outsulation® Plus MD System®

OPMD 0.0.41

Aesthetic Reveals

NOTE:

1. DRYVIT RECOMMENDS THAT GROUND

FLOOR APPLICATIONS AND ALL FACADES

EXPOSED TO ABNORMAL STRESS, HIGH

TRAFFIC, OR DELIBERATE IMPACT HAVE

THE BASE COAT REINFORCED WITH

PANZER® MESH PRIOR TO STANDARD OR

STANDARD PLUS MESH. LOCATION OF

HIGH IMPACT ZONES SHOULD BE

INDICATED ON CONTRACT DRAWINGS.

2. SLOPE BOTTOM EDGE OF REVEAL FOR

POSITIVE DRAINAGE.

EPS INSULATION BOARD

DRYVIT BASE COAT

DRYVIT REINFORCING MESH EMBEDDED

IN DRYVIT BASE COAT

DRYVIT FINISH

3/4" (19 MM) MIN.

DRYVIT DETAIL MESH® EMBEDDED IN DRYVIT BASE

COAT. OVERLAP REINFORCING MESH 2 1/2" (64 MM)

DRYVIT BASE COAT

2 1/2" (64 MM)

2 1/2" (64 MM)

DRYVIT DETAIL MESH® OVERLAPED 2 1/2" (64 MM)

DRYVIT AIR/WATER-RESISTIVE BARRIER COATING

DRYVIT ADHESIVE IN VERTICAL NOTCHED TROWEL

CONFIGURATION APPLIED TO BACK OF EPS

OUTSULATION PLUS MD

SYSTEM

BY OTHERS

FRAMING BY OTHERS

APPROVED SUBSTRATE

©

The architecture, engineering, and design of the project using the

Dryvit products is the responsibility of the project's design

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

and Dryvit specifically disclaims any liability for the use of this detail

and for the architecture, design, engineering or workmanship of any

project. The project design professional determines, in its sole

discretion, whether this detail or a functionally equivalent detail is

best suited for the project. Use of a functionally equivalent detail does

not violate Dryvit's warranty. This detail is subject to change without

notice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc.

Issued: 10/2016

Page 45: Outsulation Plus MD System Installation Detailscms.dryvit.com/media/304806/opmd-ds110-all-in-one.pdf · step #1 step #2 step #3 step #4 opening preparation - outsulation® plus md

Outsulation® Plus MD System®

OPMD 0.0.42

Recessed Graphics

EPS INSULATION BOARD

APPROVED SUBSTRATE

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

DRYVIT BASE COAT

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

DRYVIT FINISH

FRAMING BY OTHERS

DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATION

APPLIED TO BACK OF EPS

DRYVIT BASE COAT

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

DRYVIT FINISH

BY OTHERS

3/4" (19 MM) MIN.OUTSULATION

PLUS MD SYSTEM

OVERLAP 2 1/2" (64 MM)

EPS INSULATION BOARD

APPROVED SUBSTRATE

DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATION

APPLIED TO BACK OF EPS

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

SLOPE GRAPHIC FORPOSITIVE DRAINAGE

BY OTHERS

OUTSULATION PLUSMD SYSTEM

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc.Issued: 10/2016

Page 46: Outsulation Plus MD System Installation Detailscms.dryvit.com/media/304806/opmd-ds110-all-in-one.pdf · step #1 step #2 step #3 step #4 opening preparation - outsulation® plus md

Outsulation® Plus MD System®

OPMD 0.0.43

Projecting Graphics

NOTE:

1. MAXIMUM THICKNESS OF EPS BUILT

OUT SHAPES SHALL NOT EXCEED

13 INCHES (330 MM) AT ANY POINT

MEASURED FROM THE SUBSTRATE.

BY OTHERS

OUTSULATION PLUS MD

SYSTEM

OVERLAP MESH

2 1/2"(64 MM )

SLOPE GRAPHIC FOR

POSITIVE DRAINAGE

EPS INSULATION BOARD

APPROVED SUBSTRATE

DRYVIT AIR/WATER-RESISTIVE

BARRIER COATING

DRYVIT BASE COAT

DRYVIT REINFORCING MESH

EMBEDDED IN DRYVIT BASE COAT

DRYVIT FINISH

DRYVIT ADHESIVE IN VERTICAL

NOTCHED TROWEL CONFIGURATION

APPLIED TO BACK OF EPS

DRYVIT ADHESIVE

EPS INSULATION BOARD

APPROVED SUBSTRATE

DRYVIT AIR/WATER-RESISTIVE

BARRIER COATING

DRYVIT BASE COAT

DRYVIT REINFORCING MESH

EMBEDDED IN DRYVIT BASE COAT

DRYVIT FINISH

FRAMING BY OTHERS

DRYVIT ADHESIVE IN VERTICAL

NOTCHED TROWEL CONFIGURATION

APPLIED TO BACK OF EPS

EPS SHAPE (SEE NOTE 1)

OUTSULATION PLUS

MD SYSTEM

BY OTHERS

©

The architecture, engineering, and design of the project using the

Dryvit products is the responsibility of the project's design

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

and Dryvit specifically disclaims any liability for the use of this detail

and for the architecture, design, engineering or workmanship of any

project. The project design professional determines, in its sole

discretion, whether this detail or a functionally equivalent detail is

best suited for the project. Use of a functionally equivalent detail does

not violate Dryvit's warranty. This detail is subject to change without

notice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc.

Issued: 10/2016

Page 47: Outsulation Plus MD System Installation Detailscms.dryvit.com/media/304806/opmd-ds110-all-in-one.pdf · step #1 step #2 step #3 step #4 opening preparation - outsulation® plus md

OPMD 0.0.44

EPS Shapes

BYOTHERS

OUTSULATION PLUS MDSYSTEM

OVERLAP MESH2 1/2" (64 MM) MIN.

DRYVIT ADHESIVE APPLIED TO BACKOF EPS SHAPE

EPS SHAPE MEETING DRYVITSPECIFICATION DS131 (SEE NOTE 1)

FRAMING BY OTHERS

DRYVIT ADHESIVE APPLIED IN VERTICALNOTCHED TROWEL CONFIGURATION TO BACK OF

INSULATION BOARD

EPS INSULATION BOARD

APPROVED SUBSTRATE

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

DRYVIT BASE COAT

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

DRYVIT DETAIL MESH OVERLAPONTO EXISTING TO BEFEATHERED OUT FLAT PRIOR TOFINISH APPLICATION

NOTES:1. MAXIMUM THICKNESS OF EPS BUILT OUTSHAPES SHALL NOT EXCEED 13" (330 MM)AT ANY POINT MEASURED FROM THESUBSTRATE.

DRYVIT FINISH

SLOPE SURFACE 6:12MIN. FOR POSITIVEDRAINAGE. MAXIMUMLENGTH OF SLOPEDSURFACE IS 12" (305 MM)

Outsulation® Plus MD System®

OUTSULATION PLUSMD SYSTEM

BY OTHERS

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.