Paloma Manual

Embed Size (px)

Citation preview

  • 8/13/2019 Paloma Manual

    1/40

    Indoor Water Heater

    Outdoor Water Heater

    FOR YOUR SAFETY!

    Do not store or use gasoline or otherflammable vapors or liquids or other

    combustible materials in the vicinity of this

    or any other appliance. To do so may resultin an explosion or fire.

    WHAT TO DO IF YOU SMELL GAS

    l Do not try to light any appliance.

    l Do not touch any electrical switch; do not

    use any phone in your building.

    l Immediately call your gas supplier

    from a neighbors phone. Follow the

    gas suppliers instructions.

    l If you cannot reach your gas supplier, call

    the fire department.

    l Do not return to your home until authorized

    by the gas supplier or fire department.

    Improper installation, adjustment,alteration, service or maintenance can cause

    property damage, personal injury or death.

    Refer to this manual. Installation and service

    must be performed by a qualified installer,

    service agency or the gas supplier.

    WARNING: If the information in these instructions is not followed exactly,a fire or explosion may result, causing property damage, personal injury or death.

    The purpose of this manual is twofold: one, to provide the installer with

    the basic directions and recommendations for the proper installation and

    adjustment of the water heater; and two, to the owneroperator, to

    explain the features, operation, safety precautions, maintenance and

    troubleshooting of the water heater. This manual also includes a parts

    list.

    It is very important that all persons who are expected to install, operate

    or adjust this water heater read the instructions carefully so they may

    understand how to perform these operations. If you dont understand

    these instructions or any terms within it, seek professional assistance.

    Any questions regarding the operation, maintenance, service or

    warranty of this water heater should be directed to the seller from whom

    it was purchased, local distributor or Paloma.

    Do not destroy this manual. Please read carefully and keep in a safe

    place for future reference.

    Recognize this symbol as an indication of Important Safety

    Information!

    California Proposition 65 Warning: This product contains

    chemicals known to the State of California to cause cancer, birth

    defects or other reproductive harm.

    Installation and Operating Instruction ManualWith Installation Instructions for the Installer

    Tankless Water Heater

    DESIGN

    Warning: This water heater is not suitablefor use in manufactured (mobile) homes!

    Indoor and Outdoor GasR

    Models:PH-28R IFSN (Natural Gas); PH-28R IFSP (L.P. Gas): Residential Indoor

    PH-28R OFN (Natural Gas); PH-28R OFP (L.P. Gas): Residential Outdoor

  • 8/13/2019 Paloma Manual

    2/40

    Safety Information

    Safety Precautions. . . . . . . 36

    LP Gas Models . . . . . . . . . . . 5

    Installation Instructions

    Location, Outdoor. . . . . . . . . . 7

    Location, Indoor . . . . . . . . . 8, 9

    Venting . . . . . . . . . . . . . . 10-15

    Water Connections. . . . . 16-18

    Gas Supply. . . . . . . . . . . . . . 19

    High Altitude. . . . . . . . . . . . . 19

    Remote Control . . . . . . . 20, 21

    Electrical Connection . . . . . . 22

    Typical Installation. . . . . . . . 23

    Pipe Insulation . . . . . . . . . . . 24

    Installation Checklist . . . . . . 25

    Operating Instructions

    Lighting Instructions . . . . . . 26

    Water Temperature. . . . . 27, 28

    Care and CleaningMaintenance. . . . . . . . . . . . . 29

    Housekeeping . . . . . . . . 29, 30

    Vent Inspection . . . . . . . . . . . 30

    Burner Inspection . . . . . . . . 30

    Extended Shut-Down. . . . . . 30

    Draining . . . . . . . . . . . . . . . . 31

    Freeze Protection . . . . . . . . . 31

    Troubleshooting TipsBefore You Call

    For Service . . . . . . . . . . 32, 33

    Customer Service

    Parts List . . . . . . . . . . . . . . . 34

    If You Need Service . . . . . . . 36

    Inside you will find many helpful hints on how to use and

    maintain your water heater properly. A little preventive care onyour part can save you time and money over the life of your

    water heater.

    Youll find many answers to common problems in the

    Troubleshooting Guide. If you review the chart of

    Troubleshooting Tips first, you may not need to call for service.

    READ THIS MANUAL

    FOR YOUR RECORDS

    Write the model and serial numbers here:

    #

    #You can find them on a label on the appliance.

    Staple sales slip or cancelled check here.

    Proof of the original purchase date is needed to obtain service

    under the warranty.

    Your safety and the safety of others are very important. There

    are many important safety messages in this manual and onyour appliance. Always read and obey all safety messages.

    This is the safety alert symbol. Recognize this symbol

    as an indication of Important Safety Information!

    This symbol alerts you to potential hazards that can

    kill or hurt you and others.

    All safety messages will follow the safety alert symbol and

    either the word DANGER, WARNING, CAUTION

    or NOTICE.

    These words mean:

    DANGER An imminently hazardous situationthat will result in death or seriousinjury.

    WARNING A potentially hazardous situation thatcould result in death or serious injuryand/or damage to property.

    CAUTION A potentially hazardous situation thatmay result in minor or moderateinjury.

    Notice: Attention is called to observe aspecified procedure or maintaina specific condition.

    READ THE SAFETY INFORMATION

    Qualified Installers Only!

    Dip Switch Adjustment. . . . 35Warranty ..........................37, 38

  • 8/13/2019 Paloma Manual

    3/40

    Be sure to read and understand the entire Instruction Manual before attempting to install or operate this

    water heater. It may save you time and money. Pay particular attention to the Safety Instructions. Failure to

    follow these warnings could result in serious bodily injury or death. Should you have problems understanding

    the instructions in this manual, or have any questions, STOP, and get help from a qualified service technician,

    or the local gas utility.

    IMPORTANT SAFETY INFORMATION.READ ALL INSTRUCTIONS BEFORE USING.

    Failure to install and properly vent the water heater to the outdoors as outlined in the

    Venting Section of the Installation Instructions in this manual can result in unsafe operation

    of the water heater. To avoid the risk of fire, explosion or asphyxiation from carbon

    monoxide, never operate this water heater unless it is properly vented and has an adequate

    air supply for proper operation.

    Be sure to inspect the vent outlet on the OUTDOOR water heater, or the vent terminal and

    the vent system on the INDOOR water heater for proper installation at initial start-up; and

    at least annually thereafter. Refer to the Care and Cleaning section of this manual for moreinformation regarding vent system inspection.

    DANGER!INSTALL AND PROPERLY VENT THE WATER HEATER

    Gasoline, as well as other flammable materials and liquids (adhesives, solvents, paint

    thinners etc.), and the vapors they produce are extremely dangerous. DO NOT handle, useor store gasoline or other flammable or combustible materials anywhere near or in the

    vicinity of a water heater or any other appliance. Be sure to read and follow the labels on

    the water heater, as well as the warnings printed in this manual. Failure to do so can result

    in property damage, bodily injury or death.

    WARNING!

    D A N G E R

    FLAMMABLES Flammable Vapors

    Water heater has a mainburner flame.The main burner flame:1. which can come on at any time and2. will ignite flammable vapors.

    Vapors:1. cannot be seen,2. are heavier than air,3. go a long way on the floor and4. can be carried from

    other rooms to themain burner flame byair currents.

    Vapors from flammableliquids will explode andcatch fire causing death orsevere burns.

    Do not use or store flammableproducts such as gasoline,solvents or adhesives in thesame room or area near thewater heater.

    Keep flammable products:1. far away from heater,2. in approved containers,3. tightly closed and4. out of children's reach.

    Installation:Do not install water heaterwhere flammable products willbe stored or used unless themain burner flame is at least

    18" above the floor. This willreduce, but not eliminate, therisk of vapors being ignitedby the main burner flame.

    Read and follow water heater warnings and instructions. Ifowners manual is missing, contact the retailer or manufacturer.

  • 8/13/2019 Paloma Manual

    4/40

    Time/Temperature Relationship in Scalds

    Water Temperature Time To Produce a Serious Burn

    120F (49C) More than 5 minutes

    125F (52C) 11/2 to 2 minutes

    130F (54C) About 30 seconds

    135F (57C) About 10 seconds

    140F (60C) Less than 5 seconds

    145F (63C) Less than 3 seconds

    150F (66C) About 11/2 seconds

    155F (68C) About 1 second

    Table courtesy of Shriners Burn Institute

    The chart shown above may be used as a guide indetermining the proper water temperature for your home.

    DANGER: Households with small children, disabled orelderly persons may require a 120F (49C) or lowertemperature setting to prevent contact with HOT water.

    Maximum water temperature occurs while burner is on.To find water temperature being delivered, turn on a hotwater faucet and place a thermometer in the water stream

    and read the thermometer. (See page 27 & 28 for moredetails.)

    The temperature of the water at the outlet of the waterheater can be regulated by setting the temperature onRemote Control. The remote control was set at 100F(38C) before it was shipped from the factory.

    The diagram to the bottom left illustrates the RemoteControl and how to adjust the water temperature.

    Notice: The factory setting allows operating temperaturesbetween 100F (38C) and 120F (49C). Temperaturesof up to 140F (60C) for Residential models and up to

    180F (82C) for Commercial models can be achievedwith the MAIN (UMC-117) remote control and a dipswitch adjustment. Only qualified service personnelshould perform this adjustment. Only factory authorizedremote control(s) should be used.

    Notice: When this water heater is supplying generalpurpose hot water requirements for use by individuals,a thermostatically controlled mixing valve for reducing

    point of use water temperature is recommended to reducethe risk of scald injury. Contact a licensed plumber or thelocal plumbing authority for further information.

    D A N G E R!

    HOT

    Water temperature over 125F cancause severe burns instantly ordeath from scalds.

    Children, disabled and elderly areat highest risk of being scalded.

    See instruction manual beforesetting temperature at waterheater.

    Feel water before bathing orshowering.

    Temperature limiting valves areavailable, see manual.

    BURN

    DANGER!WATER TEMPERATURE SETTING

    Safety and energy conservation are factors to be considered when selecting the watertemperature setting of a water heaters remote control. Water temperatures above

    125F (52C) can cause severe burns or death from scalding. Be sure to read and follow

    the warnings outlined on the label pictured below.

    IMPORTANT SAFETY INFORMATIONREAD ALL INSTRUCTIONS BEFORE USING.

    F

    PRIORITY

    POWERON/OFF

    100 102 104 106 108 110 112 114 116 118 120* 125 130 135 140 150 160 170 180 F

    Higher (Hotter) Lower (Cooler)

    38 39 40 41 42 43 44 46 47 48 49* 52 54 57 60 66 71 77 82 C

    Notice: Only commercial model water heaters can

    achieve temperatures up to 180F (82C).* Temperatures above 120F (49C) can be achieved

    by adjusting the dip switch See page 35 for dip

    Notice:

    Display

    showsF only.

  • 8/13/2019 Paloma Manual

    5/40

    Both LP and natural gas have an odorant added to aid in detecting a gas leak. Somepeople may not physically be able to smell or recognize this odorant. If you are unsure orunfamiliar with the smell of LP or natural gas, ask the gas supplier. Other conditions, such asodorant fade, which causes the odorant to diminish in intensity, can also hide or camouflagea gas leak.

    DANGER!NATURAL GAS AND LIQUEFIED PETROLEUM MODELS

    lWater heaters utilizing LP gas are different

    from natural gas models. A natural gas

    water heater will not function safely on LP

    gas and vice versa.

    l No attempt should ever be made to convert

    the water heater from natural gas to LP

    gas. To avoid possible equipment damage,personal injury or fire, do not connect the

    water heater to a fuel type not in

    accordance with the unit data plate;

    propane for propane units and natural gas

    for natural gas units. These units are notcertified for any other fuel type.

    l LP appliances should not be installed below

    grade (for example, in a basement) if suchinstallation is prohibited by federal, state

    and/or local laws, rules, regulations or

    customs.

    l Propane or LP gas must be used with greatcaution. It is heavier than air and will

    collect first in lower areas, making it hard

    to detect at nose level.

    l Before attempting to light the water heater,

    make sure to look and smell for gas leaks.

    Use a soapy solution to check all gas fittings

    and connections. Bubbling at a connection

    indicates a leak that must be corrected.When smelling to detect a gas leak, be sure

    to sniff near the floor also.

    l Gas detectors are recommended in LPand natural gas applications and their

    installation should be in accordance with

    the detector manufacturers

    recommendations and/or local laws,

    rules, regulations or customs.

    l It is recommended that more than one

    method, such as soapy solution, gas

    detectors, etc., be used to detect leaks

    in gas applications.

    Notice: If a gas leak is present or suspected:

    lDo notattempt to find the cause yourself.

    lDo nottry to light any appliance.

    lDo nottouch any electrical switch.

    lDo notuse any phone in your building.

    l Leave the building immediately and makesure your family and pets leave also.

    l Leave the doors open for ventilation and

    contact the gas supplier, a qualified serviceagency or the fire department.

    l Stay away from the building until the

    service call has been made, the leak iscorrected and a qualified agency has

    determined the area to be safe.

  • 8/13/2019 Paloma Manual

    6/40

    Have the installer show you the location of the gas shut-off valve and how to shut it offif necessary. Turn off the manual shut-off valve if the water heater has been subjectedto overheating, fire, flood, physical damage or if the gas supply fails to shut off.

    l Read this manual entirely before installing

    or operating the water heater.

    lUse this appliance only for its intendedpurpose as described in this Instruction

    Manual.

    l Be sure your appliance is properly installed

    in accordance with local codes and the

    provided installation instructions.

    l Do not attempt to repair or replace any

    part of your water heater unless it is

    specifically recommended in this manual.

    All other servicing should be referred to aqualified technician.

    SAFETY PRECAUTIONS

    IMPORTANT SAFETY INFORMATIONREAD ALL INSTRUCTIONS BEFORE USING.

    WARNING!For your safety, the information in this manual must be followed to minimize the risk

    of fire or explosion, electric shock, or to prevent property damage, personal injury or

    loss of life.

    FOR INSTALLATIONS IN THE STATE OF CALIFORNIA

    California Law requires that water heaters must be braced, anchored or strapped to resist

    falling or horizontal displacement due to earthquake motions. For water heaters up to 52

    gallon capacity, a brochure with generic earthquake bracing instructions can be obtained from:

    Office of the State Architect, 1102 Q Street, Suite 5100, Sacramento, CA 95814 or you may call

    916-445-8100 or ask a water heater dealer.

    However, applicable local codes shall govern installation. For residential water heaters

    of a capacity greater than 52 gallons or tankless-style, consult the local building jurisdiction

    code for acceptable bracing procedures.

    READ AND FOLLOW THIS SAFETY INFORMATION CAREFULLY.

    SAVE THESE INSTRUCTIONS

  • 8/13/2019 Paloma Manual

    7/40

    Installing the (OUTDOOR) water heater:

    This water heater must be installed in accordance with these instructions, local codes, utility companyrequirements and/or in the absence of local codes, use the latest edition of the American NationalStandard/National Fuel Gas Code. A copy can be purchased from either the American Gas Association, 400North Capitol Street Northwest, Washington, DC 20001 as ANSI standard Z223.1 or National Fire ProtectionAssociation, 1 Batterymarch Park, Quincy, MA 02269 as NFPA 54. In Canada, the latest edition of the CSAB149.1 Natural Gas and Propane Installation, and the Canadian Electrical Code, CSA C22.1 Part 1, in theabsence of local codes.

    Location of the OUTDOOR water heater

    The water heater shown on the left is forOUTDOOR installation ONLY!

    This water heater is an outdoor modeland must be mounted vertically. Itmust not be installed indoors or in aconfined space.

    The water heater should be installedclose to the most frequently used outletand its position chosen with safety andservice in mind.

    Make sure people (particular children,disabled, and elderly) will not touch thehot water outlet or the flue terminal.The flue terminal and air inlet must beclear of obstruction and shrubbery.

    The water heater should not be locatedin an area where leakage of the heatexchanger or connections will resultin damage to the area adjacent to itor to lower floors of the structure.

    A gas fired water heater or any otherappliance should not be installed ina space where liquids which give offflammable vapors are to be used or stored.Such liquids include gasoline, LP gas(butane or propane), paint or adhesivesand their thinners, solvents or removers.

    Because of natural air movement in aroom or other enclosed space, flammablevapors can be carried some distance fromwhere their liquids are being used orstored. The open flame of the waterheaters main burner can ignite these

    vapors, causing an explosion or fire whichmay result in severe burns, death or

    property damage.

    The water heater must be located so it is notsubject to physical damage, for example, bymoving vehicles, area flooding, etc.

    l The water heater should be installedvertically with the water, gas and powerconnections on the underside pointingtoward the ground.

    l Failure to properly install the water heateroutdoors as outlined in this manual canresult in unsafe operation.

    l Hot and cold water lines should be insulatedto conserve water and energy.

    l The water heater and water lines shouldbe protected from exposure to freezingtemperatures.

    l Do not install water heater where subjectto vibrations.

    l Do not install the water heater inRecreational Vehicles, Mobile Homes,

    Boats and other Watercrafts.l Do not install the water heater near

    vents for heating or cooling. A minimumof 4 feet should be maintained.

    lMinimum clearance from combustibleand noncombustible construction is1/2 (1.3 cm) sides, 0 rear (with support

    bracket); 12 (30 cm) from the bottom;12 (30 cm) from the front of the waterheater; (24 [61 cm] from frontrecommended for servicing purposes).If the clearances stated on the Instruction/Warning Label, located on the front panel

    of the heater differ, install the waterheater according to the clearances statedon the label.

    WARNING: Combustibleconstruction refers toadjacent walls and ceilingsand should not be confusedwith combustible orflammable products andmaterials. Combustibleand/or flammable productsand materials should neverbe stored in the vicinity ofthis or any gas appliance.

    min.

    1/2 "

    (1.3 cm)

    min.

    1/2 "

    (1.3 cm)

    min. 12" (30 cm)

    (24" (61 cm) minimum is

    recommended for service)

    Front = 12" (30 cm)Back = 0" (with support bracket)

    Side = 1/2" (1.3 cm)Bottom = 12" (30 cm)

    Minimum Clearance from Combustible and

    Non-Combustible Construction.

    Top: Do not install this water

    heater under an overhang less

    than 36 (91 cm) from its top.

    The area under the overhang

    must be open on 3 sides.

    CAUTION:Protect plastic, paint orother items sensitive to heatusing non-combustibleinsulation if these areexposed to the flue exhausteven though they may be

    more than 24 (61 cm) awayfrom the water heater.

  • 8/13/2019 Paloma Manual

    8/40

    WARNING: Follow vent

    manufacturers instruction

    while installing vent. If

    required, provide additionalclearances from vent to

    combustibles per vent

    manufacturers instruction.

    Installing the (INDOOR) water heater :

    This water heater must be installed in accordance with these instructions, local codes, utility companyrequirements and/or in the absence of local codes, use the latest edition of the American NationalStandard/National Fuel Gas Code. A copy can be purchased from either the American Gas Association, 400North Capitol Street Northwest, Washington, DC 20001 as ANSI standard Z223.1 or National Fire ProtectionAssociation, 1 Batterymarch Park, Quincy, MA 02269 as NFPA 54. In Canada, the latest edition of the CSAB149.1 Natural Gas and Propane Installation, and the Canadian Electrical Code, CSA C22.1 Part 1, in theabsence of local codes.

    Location of INDOOR Water Heater

    The water heater shown on the left is forINDOOR installation ONLY!

    The water heater should not be located in

    an area where leakage of the heat exchanger

    or connections will result in damage to the

    area adjacent to it or to lower floors of the

    structure.

    When such areas cannot be avoided, it is

    recommended that a suitable catch pan,

    adequately drained, must be installed under

    the water heater.

    The pan must not restrict combustion

    air flow.

    A gas fired water heater or any other appliance

    should not be installed in a space where

    liquids which give off flammable vapors are

    to be used or stored. Such liquids include

    gasoline, LP gas (butane or propane), paint

    or adhesives and their thinners, solvents

    or removers.

    Because of natural air movement in a room or

    other enclosed space, flammable vapors can be

    carried some distance from where their liquids

    are being used or stored. The open flame of

    the water heaters main burner can ignite these

    vapors causing an explosion or fire which may

    result in severe burns, death or property

    damage.

    The water heater must be located so it is not

    subject to physical damage, for example, by

    moving vehicles, area flooding, etc.

    If the water heater is installed in a garage, itshould be installed so that the direct ignition

    system and main burner are no less than 18

    inches (45 cm) above the garage floor.

    Raising the gas fired water heater will reduce

    BUT NOT eliminate the possibility of lighting

    the vapor of any flammable liquids which may

    be improperly stored or accidentally spilled.

    l The water heater should be installed as

    close as practical to the vent termination to

    minimize vent length and the number of

    elbows required for venting.

    l The water heater shouldbe installed withthe proper venting materials and terminationsuitable for Category III venting.

    l A fire stop plate should be installed at everypenetration of a floor or ceiling if the vent isnot running in a fire rated shaft.

    l Failure to install and properly vent thewater heater to the outdoors as outlinedin the Venting Section of this manualcan result in unsafe operation.

    l Long hot water lines should be insulated toconserve water and energy.

    l The water heater and water lines shouldbe protected from exposure to freezingtemperatures.

    l Do not install the water heater inbathrooms, bedrooms, any occupied roomsnormally kept closed, or in outdoor areas.

    l Do not install the water heater in small,poorly ventilated rooms, or in airtightrooms with air conditioning.

    l Do not install water heater where subjectto vibrations.

    l Do not install the water heater inRecreational Vehicles, Mobile Homes,Boats and other Watercrafts.

    l Do not install the water heater near ventsfor heating or cooling. A minimum of 4feet (1.2 m) should be maintained.

    l Minimum clearance from combustible andnon-combustible construction is 1/2 (1.3cm) sides, 0 rear (with support bracket);12 (30 cm) from the bottom; 12 (30 cm)from the front of the water heater; and 12(30 cm) from the top (24 [61 cm] fromfront and top is recommended for servicing

    purposes).

    l Maintain a minimum clearance of 3 (8 cm)around the vent pipe to combustible or non-combustible construction, unless otherwisespecified by vent manufacturer or installedin an enclosed space. If the clearances

    stated on the Instruction/Warning Label,located on the front panel of the heaterdiffer, install the water heater according

    WARNING: Combustible

    construction refers toadjacent walls and ceilingsand should not be confusedwith combustible orflammable products andmaterials. Combustibleand/or flammable productsand materials should neverbe stored in the vicinity ofthis or any gas appliance.

    min.

    1/2 "

    min.

    1/2 "

    min. 12"

    (24" (61 cm) minimum is

    recommended for service)

    Top = 12" (30 cm)

    Vent = 3"

    Front = 12" (30 cm)

    min. 3" min. 3"

    Back = 0" *

    Side = 1/2"

    Bottom = 12" (30 cm)

    (8 cm) (1.3 cm)

    (1.3 cm)(1.3 cm)(8 cm)(8 cm)

    (30 cm)

    Minimum Clearance from

    Combustible and

    Non-Combustible

    Construction.

    3 (8 cm) min

    3 (8 cm)min

    3 (8 cm)min

    Vent

    Pipe

  • 8/13/2019 Paloma Manual

    9/40

    Proper operation of the water heater requires air for combustion and ventilation. Provisions forcombustion and ventilation air must comply with referenced codes and standards.

    Combustion and Ventilation Air (Indoor Water Heater Only)

    NOTICE: If the water heater is installed in

    an unconfined space within a building of

    conventional frame, masonry or metal

    construction, infiltration air is normally

    adequate for proper combustion and

    ventilation. If the water heater is installed in

    a confined space, provisions for combustion

    and ventilation air must be made.

    A confined space is one having a volume

    of less than 50 cubic feet (1.4 m3) per

    1000 Btuh (0.3 kw) of the aggregate input

    of all appliances within that space.

    The air must be supplied through two

    permanent openings of equal area. Oneis to be located within 12 (30 cm) above

    the floor and the other is to be located

    within 12 (30 cm) below the ceiling.

    The minimum net free area of each opening

    must not be less than one square inch (6.5

    cm2) per 1000 Btuh (0.3 kw) of the total

    input rating of all the appliances in the

    enclosure (but not less than 100 square

    inches [650 cm2]) if each opening

    communicates with other unconfined areas

    inside the building. The above

    requirements shall be used unless:

    national, provincial, or local codes governthe requirement for these air openings.

    Buildings of unusually tight construction

    shall have the combustion and ventilation

    air supplied from outdoors, or a freely

    ventilated attic or crawl space.If air is supplied from outdoors, directly or

    through vertical ducts, there must be two

    openings located as specified above and

    each must have a minimum net free area

    of not less than one square inch

    (6.5 cm2) per 4000 Btuh (1.2 kw)of the

    total input rating of all the appliances in

    the enclosure.

    If horizontal ducts are used to

    communicate with the outdoors, each

    opening must have a minimum net free

    area of not less than one square inch

    (6.5 cm2) per 2000 Btuh (0.6 kw) of the

    total input rating of all the appliances in

    the enclosure. If ducts are used, the

    minimum dimensions of rectangular air

    ducts shall not be less than 3 (7.6 cm).

    NOTICE: If the duct openings which supply

    combustion and ventilation air are to be

    covered with a protective screen or grill, the

    net free area (openings in the material) of

    the covering material must be used in

    determining the size of the openings.

    Protective screening for the openings MUST

    NOT be smaller than 1/4 (0.64 cm) mesh to

    prevent clogging by lint or other debris.

    Additional installation information for TheCommonwealth of Massachusetts is locatedon page 36.

    Corrosive Atmospheres

    The air in beauty shops, dry cleaning

    establishments, photo processing labs,

    and storage areas for liquid and powdered

    bleaches or swimming pool chemicals

    often contains such halogenatedhydrocarbons.

    An air supply containing halogenated

    hydrocarbons may be safe to breathe,

    but when it passes through a gas flame,

    corrosive elements are released that

    will shorten the life of any gas burning

    appliance.

    Propellants from common spray cans

    or gas leaks from A/C and refrigeration

    equipment are highly corrosive afterpassing through a flame.

    The water heater warranty is voided when

    failure of the heater is due to operation in

    a corrosive atmosphere.

    NOTICE: The water heatershould not be installed nearan air supply containinghalogenated hydrocarbons.

    DANGER: OUTDOORwater heaters must notbe installed indoors orin a confined space.Install outdoor waterheaters outdoors only.

    Inspect Shipment

    Inspect the water heater for possible damage. Check the markings on the rating plate of

    the water heater to be certain the type of gas supplied corresponds to the water heater

    requirements. Verify all included parts are present (see below).

    Air openingsminimum200 sq. in.(1290 cm2).

    Min. 3(7.6 cm)

    Wood Screw x 5pcs.

    FOR YOUR SAFETY!

    Do not store oruse gasoline or otherflammable vapors or liquids orother

    combustiblematerialsinthevicinityofthisorany otherappliance. Todo so may result in anexplosion orfire.

    WHATTO DO IFYOU SMELLGAS

    l D li h li

    l If you cannot reach yourgas supplier, call

    the fire department.

    l Do not return to yourhome until authorizedby the gas supplierorfire department.

    Improperinstallation, adjustment,alteration, service ormaintenance can cause

    propertydamage personal injury ordeath

    !

    WARNING: If the information in these instructions is not followed exactly ,a fire orexplosion may result causing property damage, personal injury o rdeath.!

    Thepurpose of thismanual istwofold: one,to providet h einstallerwiththebasic directionsand recommendationsfortheproperinstallation and

    adjustmentofthe waterheater; andtwo,to theowneroperator, toexplain thefeatures,operation, safety precautions, maintenanceandtroubleshooting of thewaterheater. Thismanual also includes a partslist.

    It is imperativethat all personswho areexpected to install, operateoradjust this waterheaterread theinstructions carefully so they mayunderstand howto perform theseoper ations. If you dont understand

    these instructionsorany termswithin it, seek professional advice.

    Any questions regarding the operation, maintenance, service orwarrantyof thiswaterheatershould bedirected to thesellerfrom whom

    it was purchased.If additionalinformationisrequired, ref ert o t h esection on Howto Obtain ServiceAssistance.

    Do not destroy this manual. Pleaseread carefully and keep in a safe

    placeforfuture reference.

    Recognizethis symbol asan indication of Important SafetyInformation!

    California Proposition 65 Warning: This product containschemicals known to theStateof California to causecancer, birthdefectsorother reproductive harm.

    !

    !

    Use&CareManualWithInstallationInstructionsfortheI nstaller

    Water HeatersResidentialGas

    Warning: This waterheateris not suitable for

    use in manufactured (mobile) homes!

    Tankless

    F

    PRIORITY

    POWERON/OFF

  • 8/13/2019 Paloma Manual

    10/40

    Installing the (INDOOR) water heater:The water heater must be installed with a 4 diameter UL approved Category III Stainless Steel appliancevent pipe and an appropriate adapter.

    VentingThe installation of venting must comply

    with national codes, local codes and thevent manufacturers instructions.

    The water heater must be vented to theoutdoors as described in these instructions.DO NOT connect this water heater to achimney. It must be vented separately fromall other appliances.

    All vent components (adapters, pipe, elbows,terminals, etc.) should be UL 1738 CertifiedStainless Steel Venting Material(e.g. AL29-4C).

    The specified vent termination must be used.The termination should be a 90 elbow withscreen. (Refer to pages 14 and 15 for anexample of 90 termination)

    Use a vent pipe with an anti-disconnectionjoint.

    The use of a High Temperature Silicone(500F [260C]) may be required to sealvent connections. To prevent accidental gasexhaust leakage, apply a 1/4 (6 mm) wide

    bead approximately 1/4 (6 mm) from theend and another bead against the joint sideof the stop bead.

    Follow vent manufacturers installationinstructions and their recommendedclearances to combustibles.

    The unit can be vented either horizontallyor vertically.

    Vent pipe runs must be adequately supported

    along both horizontal and vertical runs.The maximum recommended unsupportedspan should be no more than five (5) feet(1.5 m). Support isolation hanging bandsshould be used. DO NOT use wire. (Seediagram below).

    Notes on pre-existing vent:

    If the water heater is being installed as areplacement for an existing water heater, athorough inspection of the existing ventingsystem must be performed prior to anyinstallation work. Verify that the correctmaterials, vent lengths and terminal locationsas detailed in this Instruction Manual have

    been met. Carefully inspect the entireventing system for any signs of cracks orfractures, particularly at the joints betweenelbows or other fittings and the straight runsof vent pipe. Check the system for signs ofsagging or other stresses in the joints as aresult of misalignment of any components inthe system. If any of these conditions arefound, they must be corrected in accordancewith the venting instructions in this manual

    before completing the installation andputting the water heater into service.

    DANGER: Failure toinstall the appliance vent

    adapter and properly ventthe water heater to theoutdoors as outlined in theVenting section of thismanual will result in unsafeoperation of the waterheater, causing death,serious injury, explosion,or fire. To avoid the riskof fire, explosion, orasphyxiation from carbonmonoxide, NEVER operatethe water heater unless it isproperly vented and hasadequate air supply forproper operation asoutlined in the Ventingsection of this manual.

    WARNING: Use 4UL approved Category IIIStainless Steel vent materialonly. No other ventmaterial is permitted.

    WARNING: Refer topage 8 for clearances tocombustible material.

    NO! YES!

    Venting LengthsMAXIMUM VENT LENGTH: Thesystem will not operate if there is excessiverestriction (pressure drop) in the ventingsystem. A maximum of 47 6 (14.4 m) vent

    pipe may be used provided there is only one90 elbow in the system. If additional elbowsare required: two elbows can be used with42 6 (13 m) and three elbows can be usedwith 37 6 (11.4 m).

    A 90 elbow is equivalent to 5 (1.5 m) ofstraight pipe. A 45 elbow is equivalent to2 6 (76 cm) of straight pipe.

    The termination elbow does not count as anelbow when determining total vent lengths.

    The vent can be installed with a slightdownward slope of 1/4 per foot ofhorizontal run toward the vent terminal (see

    diagram below). This ensures that anycondensate formed during operation of theunit is evacuated from the appliance.

    A 1/4 per foot upward slope is acceptablewhen it is not possible to vent with adownward slope; however, a UL approvedCategory III Stainless Steel condensate trapMUST be installed at the beginning of thehorizontal run. (See page 14 Example B:

    Typical Horizontal Termination w/ 1/4 perfoot UPWARD Slope or page 15, StandardVertical Vent Termination for examples).

    MINIMUM VENT LENGTH: The ventingmay be as short as 12 (30 cm), providedone vent termination is installed to theoutdoors through a sidewall, one 90 elbowis included in the installation and the wallthimble is installed.

    Notice: Make sure that the seam of the ventpipe in horizontal runs is toward the top ofthe installation (see diagram to the far left).

    Min. 3"

    (8 cm)

    Max. 2 feet(61 cm)

    1/4" per footdownward slope

    Vent Seam

    Number of

    90 elbows

    (bends)

    Maximum

    Length of

    Straight Pipe

    1

    2

    3

    47 6

    (14.4 m)

    42 6

    (13 m)

    37 6

    (11.4 m)

  • 8/13/2019 Paloma Manual

    11/40

    Venting Through Closed Spaces

    If the vent piping passes through a closed space, a minimum clearance of8 (20 cm) when installed horizontally or 6 (15 cm)when installedvertically should be maintained between the vent pipe and combustibles

    and noncombustibles. Be sure to follow local codes and ventmanufacturers installation instructions.

    For maintenance and inspection purposes, the following access panelsare required.

    l Two (2) inspection access panels large enough to allow access for

    venting inspection. One (1) of these access panels should be close

    to where the vent pipe enters the ceiling. The other access panel

    should be near the vent termination.

    l A ventilation access panel with a 16 in2 (103 cm2) opening should

    be provided every 10 ft (3 m).

    downward slope/4 per oot

    Ceiling

    Vent Pipe

    Wall Thimble

    Board

    Inspection

    FireStop

    Access Panel #1Inspection

    Access

    Panel #2

    Appliance Vent Adapter

    The water heater must be installedwith a UL 1738 approved Category IIIStainless Steel appliance vent adapter.

    Read the following instructions before

    installation.

    l Test fit the adapter over the water heater

    collar before proceeding. Adjust clamp as

    needed.

    l With an alcohol wipe, clean inside surface

    A of adapter and outside surface B of

    heater collar.

    l Apply 1/4 (6 mm) wide bead of high

    temperature silicone (500F [260C])

    around outside of heater collar B.

    l Slide adapter end A down over heater

    collar B as far as it will go.

    l Tighten the clamp around the collar.

    l Inspect the inside of the adapter to verify

    that the collar and adapter are sealed. If

    more sealant is required, apply sealant to a

    flat tool, then spread around the collar edge

    on inside of adapter.

    l Ensure that the clamp does not interfere

    with the damper shaft.

    NOTICE: Follow the appliance vent adapter

    manufacturers instructions.

    A

    B

    High Temp.

    Sealant

    Collar

    Appliance

    Vent Adapter

    Clamp

    Water Heater

    Exhaust

    Flow

    Draining the CondensateProvision should be made to collect anddispose of condensate from venting systems.

    When a water heater is vented horizontally,the vent pipe can have a DOWNWARD orUPWARD slope towards the termination. Ifan UPWARD slope is used, a condensate trapmust be installed as close as practical to thewater heater in order to prevent condensatefrom draining back into the water heater. SeeExamples A and B on page 14 forDOWNWARD and UPWARD slope forhorizontally vented water heaters.

    When a water heater is vented vertically, anUPWARD slope must always be used. Acondensate trap must be installed in thehorizontal section of the vent and as closeas practical to the water heater in order to

    prevent condensate from draining back intothe water heater. See the diagram on page 15showing UPWARD slope for verticallyvented water heaters.

    Always attach a drain hose to the drain fittingand plumb the hose to a sanitary sewer drain.

    A high temperature silicone tubing suitable foruse with acidic condensate and appropriate forthe temperature range should be used.

    The drain tube is fashioned into a pigtail trapand must be filled with water to prevent fluegases from emitting into the building prior to

    operating the appliance.

    CAUTION: Condensatemust drain away from thewater heater and shouldnot be allowed to drainback into any part of thevent system.

    WARNING: Failure toprovide a vent condensatedrain close to the appliancecould allow acidic flue gascondensate to enter intoappliance flueways, causingpremature failure of the

    appliance.

    CAUTION: Condensateis known to be acidic; referto local, state (provincial)or federal codes for properhandling and dischargemethods.

    CAUTION: Ensure that the

    appliance vent adapter is

    securely attached to the

    water heater collar.

  • 8/13/2019 Paloma Manual

    12/40

    D

    V

    V

    E

    FIXED

    CLOSED

    OPERAB

    LE

    OPERA

    BLEFIX

    ED

    CLOSED

    v

    v

    B

    L

    F

    C

    B

    v

    v

    v

    X

    B

    B

    BA

    J

    B

    I

    H

    Xv

    M

    K

    v

    G

    A

    The following information should be used for determining the proper location of the vent terminal

    for indoor and outdoor tankless water heaters.

    V VENT TERMINAL X AIR SUPPLY INLET AREA WHERE TERMINAL IS NOT PERMITTED

    Installing the water heater:

    Horizontal Vent Terminal Location

    * If clearances are not specified, then follow local installation codes and the requirement of the gas supplier.

    ** For condensing appliances: The vent for this appliance shall not terminate over public walkways, near soffit vents, crawl space vents, or other

    H = Clearance to each side of center

    line extended meter/regulator

    assembly. above

    3 feet (91 cm) within a height 15 feet

    (4.57 m) above the meter/regulator

    assembly.

    * *

    I = Clearance to service regulator vent

    outlet.3 feet (91 cm) * *

    J = Clearance to nonmechanical air

    supply inlet to the combustion air

    inlet to any building or other

    appliance.

    6 inches (15 cm) for appliances 10,000 Btuh (3kW)

    and < 100,000 Btuh (30kW), 36 inches

    (91 cm) for appliances > 100,000 Btuh

    (30kW).

    4 feet (1.2 m) below or to side of

    opening; 1 foot (300 mm) above

    opening.

    6 inches (15 cm) for appliances < 10,000

    Btuh (3 kW), 9 inches (23 cm) for

    appliances > 10,000 Btuh (3kW) and 50,000 Btuh (15kW).

    K = Clearance to mechanical air

    supply inlet.6 feet (1.83 m)

    3 feet (91 cm) above if within 10 feet

    (3 m) horizontally.

    3 feet (91 cm) above if within 10 feet

    (3 m) horizontally.

    L = Clearance above paved sidewalk

    or paved driveway located on

    public property.

    Not Allowed Not Allowed Not Allowed

    M = Clearance under veranda, porch,

    deck or balcony. Not Allowed Not Allowed Not Allowed

    Canadian Installations 1

    Indoor and OutdoorUS Installations 2

    Indoor

    US Installations 2

    Outdoor

    A= Clearance above grade, veranda,

    porch, deck or balcony.12 inches (30 cm) above anticipated

    snow level.

    12 inches (30 cm) above anticipated

    snow level.

    12 inches (30 cm) above anticipated

    snow level.

    B= Clearance to window or door that

    may be opened. 6 inches (15 cm) for appliances < 10,000

    Btuh (3 kW), 12 inches (30 cm) for

    appliances > 10,000 Btuh (3kW) and 100,000 Btuh (30kW).

    4 feet (1.2 m) below or to side of

    opening; 1 foot (300 mm) above

    opening.

    6 inches (15 cm) for appliances 10,000 Btuh (3kW)

    and < 50,000 Btuh (15kW), 12 inches

    (30 cm) for appliances > 50,000 Btuh

    (15kW).

    C= Clearance to permanently closedwindow.

    * * *

    D= Vertical Clearance to ventilated

    soffit located above the terminal

    within a horizontal distance of 2

    feet (61 cm) from the center line

    of the terminal.

    * * *

    E= Clearance to unventilated soffit. * * *

    F= Clearance to outside corner.* * *

    G= Clearance to corner. * * *

  • 8/13/2019 Paloma Manual

    13/40

    Additional Considerations

    Do NOT install vent terminal under any patio or deck.

    To help prevent moisture from freezing on walls and under

    eaves, do not locate vent terminal on the side of a building withprevailing winter winds.

    To help prevent water lines from freezing, do not locate ventterminal on the side of a building with prevailing winter winds.

    Do Not terminate vent directly on brick or masonry surfaces. A rustresistant sheet metal backing plate ( 1 x 1 foot)(30 x 30 cm) isrecommended behind vent. (See Figure.)

    Do NOT locate vent terminal too close to shrubbery, as flue gasesmay damage them.

    Caulk all cracks, seams and joints within six (6) feet (1.8 m) of ventterminal.

    Caulk around thimble face plate for weather tight seal.

    All painted surfaces should be primed to lessen the chance ofphysical damage. Painted surfaces will require maintenance.

    Insulate vent pipe of water heaters exposed to cold conditions(attics, crawl spaces, etc.) with inflammable material to help preventmoisture from accumulating in vent pipe. The insulation should berated for the temperature and should not contain substances thatcorrode the vent pipe.

    Do NOT extend exposed vent pipe of indoor water heaters outsideof building.

    Guard vent against accidental contact with people and pets.

    Install outdoor water heater such that air inlet and flue outlet isabove anticipated snow level.

    (1.8 m)

    If soffit vent is too close,block off and install newvent at another location

    Insidecorner

    Caulk

    Caulk

    Caulk

    6' (1.8 m)caulk zone orto edge ofwindow etc., startingwithin 6' (1.8 m)

    Rising moisture will collect under eaves

    4'

    6' (1.8 m) caulkzone

    6'

    (1.2 m) 12 (30 cm)

    WARNING: Moisture in the flue gas will condense as

    it leaves the vent terminal. In cold weather this condensate

    can freeze on the exterior wall, under the eaves and on

    surrounding objects. Some discoloration on the exterior of

    the building is to be expected. However, improper location

    or installation can result in severe damage to the structure

    or exterior finish of the building.

    Outdoor Water Heater

    Indoor Water Heater

    Inside

    Corner Caulk

    6(1.8 m)Caulk Zone

    If soffit vent is too close,

    block off and install new

    vent at another location.

    Caulk

    Caulk

    Rising moisture will

    collect under eaves.

    6

    4 Wall thimble face plate

    (1.8 m)

    6(1.8 m)Caulkzone or to edge of windowetc.,starting within 6(1.8 m).

    RTV silicone caulk

    (1.2 m)12(30 cm)

  • 8/13/2019 Paloma Manual

    14/40Example A: Typical Horizontal Termination

    / 1/4 f DOWNWARD Sl

    Installing the (INDOOR) water heater:

    Vent Horizontal Wall Thimble Installation

    An approved 4 inch (10 cm) Vent HorizontalWall Thimble must be used.

    The Wall Thimble requires mechanicalsupport from the wall sufficient to support anyincidental loads on the system. If the wall isnot sufficient enough to support the WallThimble, then appropriate additional framingand/or blocking is required.

    INSTALLATION PROCEDURE: Preparean opening for the Wall Thimble in the wall.The opening must be 6-1/2 (16 cm) indiameter for a 4 (10 cm) vent system.

    If there are not sufficient support membersto secure the Wall Thimble or if there is a

    semirigid foam insulation layer under thesheathing, appropriate fasteners must be usedto secure the Wall Thimble to the supportmembers.

    The Wall Thimble is designed to adapt toany wall thickness from 3-1/2 (9 cm) to6 (15 cm) thick. If the wall is thicker than6 (15 cm), the Wall Thimble may beextended using a piece of 6 (15 cm) diametersnaplock or welded seam galvanized pipe upto 6 (15 cm) long.

    Select the larger diameter half of the Wall

    Thimble for the outside of the wall.l Apply a continuous bead of high quality

    silicone or silicone/latex caulk on the insideof the outer flange. This will be the onlyweather seal to keep moisture outside the

    building. Ensure a sufficient seal is made.

    l Position this portion of the Wall Thimbleinto the prepared hole from the outside.Secure the assembly into the preparedopening using fasteners as indicated bysheathing or structural members, sealing thescrew heads with more caulking.

    Use four (4) hollow wall anchors, at least1/8 (.32 cm) in diameter and of appropriatelength for the thickness of the sheathing, if

    sheathing is particle board or othercomposite material. Use four (4) #10x1-1/4wood screws for plywood, solid woodsheathing or members. Use suitablemasonry anchors when passing throughsolid masonry walls. Reinstall thedecorative sheathing around the WallThimble. This assembly may be painted tomatch the exterior decor.

    l Attach a Paloma approved 4 (10 cm)screened, 90 elbow termination to thefemale end of a vent section or slipconnector. Use the method described in theVenting installation instructions providedwith the vent. Slide the vent in through the

    outside of the Thimble and seal the annularspace with a thick bead of caulk.

    l Slide the interior portion of the Thimbleinto the inside hole. Be certain the interiorand exterior Thimble halves overlap at least1 (2.5 cm). If insufficient overlap exists,extend the interior portion with single wallgalvanized pipe.

    l Secure the Wall Thimble to the interiorsheathing using suitable fasteners.

    l Secure the vent section or slip connectorthat protrudes through the Wall Thimble

    to the rest of the vent system as describedin the Venting installation instructions

    provided with the vent.

    l Proper support must be provided for thevent pipes as mentioned in the ventingsection.

    l Support method used should isolate thevent pipe from floor joist or other structuralmembers to help prevent the transmissionof noise and vibration.

    l Do not support, pin or otherwise secure theventing system in a way that restricts the

    normal thermal expansion and contractionof the chosen venting material.

    Inner ThimbleSection

    Outer ThimbleSection

    90 Elbow

    Outer

    Wall

    Inner ThimbleSection

    WaterHeater

    Outside Wall

    Side View

    Caulk forweather seal

    Inner Wall

    Outer ThimbleSection

    90 termination

    with screen

    VentPipe

    MountingBrackets

    Appliance

    Vent Adapter

    Side View

    Side View

    WARNING: Use ULapproved Category III ventmaterial only. No othervent material is permitted.

    CAUTION: Follow thevent manufacturersinstallation instructions asdesign might vary frommanufacturer tomanufacturer.

    VentAdapter

    SupportHanger

    Condensate Trap

    To Drain. Dispose ofcondensate in accordancewith local codes

    1/4" per foot upward slope

    3" (8 cm)Clearance

    2'(61 cm)

    Max

    VentAdapter

    3" (8 cm) Clearance

    SupportHanger

    1/4" per foot downward slope

    2'(61 cm)

    Max

    Example B: Typical Horizontal Termination

    / 1/4 f UPWARD Sl

  • 8/13/2019 Paloma Manual

    15/40

    Vertical Vent Installation

    A fire stop plate should be installed at everypenetration of a floor or ceiling if the vent isnot running in a fire-rated shaft. Maintain therecommended air space clearance tocombustible materials and building insulation.

    Once the vent terminal location has beendetermined, make a hole through the roof andinterior ceiling to accommodate the vent pipe.Complete the vent pipe installation to the

    water heaters vent connector fitting on thewater heater vent collar outlet. Supportvertical or horizontal runs as previouslymentioned. If required, use silicone sealantat the point the vent connector joins thewater heater.

    Install adequate flashing where the vent pipepasses through the roof. Determine the ventterminal height and install the vent pipeaccordingly. Refer to the diagram above for

    proper vent terminal height. Connect ventelbow onto vertical pipe through roof.Connect short piece of vent pipe(approximately 6 long [15 cm]) toelbow, and the terminal elbow with the

    protective screen.The vent roof system must terminate at least1 foot (30 cm) above the roof line and at least2 feet (61 cm) higher than any portion of the

    building within 10 feet (3 m).

    Install supports every 5 feet (1.5 m) verticallyalong the vent pipe route. Vertical supports

    are required after everytransition to vertical and arerequired after every offsetelbow. When the vent is free-standing and penetrates aroof/ceiling, another means of

    support must be used at asecond location.

    Follow the vent manufacturersrecommended installationinstructions provided with thevent purchased from themanufacturer.

    Chase Requires

    6" (15 cm) Clearance

    to Combustibles

    Firestop

    Firestop

    Roof Jack

    Adjustable

    Roof Flashing

    Vent

    Adapter

    3" (8 cm) Clearance

    Support

    HangerCondensate

    Trap

    To Drain. Dispose of

    condensate in accordance

    with local codes

    Storm

    Collar

    Support

    Clamp

    1/4" per foot upward slope

    2'

    (61 cm)

    Max

    Standard Vertical Vent Termination

    Vertical Vent Termination Location

    The location of the vent terminal depends on the followingminimum clearances and considerations (see diagram at left):

    Minimum twelve (12) inches (30 cm) above roof.2

    Minimum twelve (12) inches (30 cm) above anticipatedsnow level.

    Maximum twenty-four (24) inches (60 cm) above roof levelwithout additional support for vent.

    Four (4) feet (1.2 m) from any gable, dormer or otherroof structure with building interior access (i.e., vent,window, etc.).

    Ten (10) feet (3 m) from any forced air inlet to the building.Any fresh or make-up air inlet such as a dryer or furnacearea is considered to be a forced air inlet.3

    Min. 12" (30 cm)Above Roof1

    Min. 12" (30 cm)Above AnticipatedSnow Level

    Max. 24" (60 cm)Above Roof (WithoutAdditional Support)

    Vent PipeThrough Roof

    Elbow

    Termination Elboww/ Protective Screen

    Small (6 min) (15 cm)section of vent

    Notice: Only Palomaapproved terminationand parts should be usedduring installation.

    Notice: Follow vent

    manufacturers installationinstructions and theirrecommended clearances tocombustibles as required.

    Chase Requires

    6" (15 cm) Clearance

    to Combustibles

    Firestop

    Firestop

    Roof Jack

    Rain Cap

    AdjustableRoofFlashing

    Vent

    Adapter

    3" (8 cm) Clearance

    Support

    HangerCondensate

    Trap

    To Drain. Dispose of

    condensate in accordance

    to local codes

    Storm

    Collar

    Support

    Clamp

    1/4" per foot upward slope

    2'

    (61 cm)

    Max

    Alternate Vertical Vent Termination

    with Rain Cap

    Vent PipeVent Pipe

    2 For installations in Canada 18 (45.7 cm).3 For installations in Canada 6 (1.8 m).

    1 Min. 18 (46 cm) above roof for installations. in

    Canada.

  • 8/13/2019 Paloma Manual

    16/40

    Water Supply ConnectionsIMPORTANT: Do notapply heat to the HOT orCOLD water connections. Ifsweat connections are used,sweat tubing to adapterbefore fitting adapter to thewater connections onheater. Any heat applied tothe water supply fittingswill permanently damagethe internal componentsof the water heater.

    Mounting the Water Heater

    Make sure the location of the appliance allows

    for easy access and operation.

    Wall studs should be utilized when mounting

    the water heater to the wall. Alternately, a

    suitable piece of wood may be placed inside

    or outside of the wall to span the distance

    between the wall studs. Fasten the water

    heater mounting brackets to the wood.

    In case of dry wall or concrete wall, use

    drywall anchors or lag bolts.

    The water heater requires 120VAC/60Hz.

    Have a receptacle with ground terminal near

    the water heater. The length of the power

    supply cord is 10 feet (3 m) (indoor water

    heater only.)

    Install a wood screw for the upper bracket

    with a clearance of 1/8 (.32 cm) between the

    wall and the screw head. Hang the center of

    the upper bracket on the screw.

    Using a wood screw and a washer, affix the

    lower bracket to the wall (Left and Right).

    Repeat to affix the top bracket.

    The brackets can be adjusted to change the

    distance between the back of the appliance

    and the wall within the range of 3/8 (.95 cm)

    to 1-1/2 (3.8 cm).

    Loosen the adjustment screws of both the top

    and the bottom brackets to adjust the distance

    (See diagram below).

    Bracket

    BracketAdjustment Screws

    Adjustment ScrewsTOP

    BOTTOM

    Upper Bracket

    Washer

    Washer

    Wood

    Screw

    Wood

    Screw

    Wood

    Screw Lower Bracket

    1/8" (.32 cm)Clearance

    Plumbing should be carried out by a qualifiedplumber in accordance with local codes.

    Use approved plumbing materials only.

    The diameter of the pipe lines should be a

    minimum of 3/4(2 cm).

    To conserve energy and to prevent freezing,insulate both cold and hot water supplylines. DO NOT cover the drain or pressurerelief valve.

    To ensure proper operation of the waterheater, the following water pressure guidelinesshould be followed:

    l Operation of the water heater requires theminimum water pressure of 14 psi (97 kPa)and a minimum water flow rate of 0.66gpm (2.5 lpm).

    l A water pressure of 40 psi (276 kPa) isrequired to achieve maximum flow rate.

    Required Water Pressure = Min. OperatingWater Pressure (14 psi [97 kPa]) + PipePressure Loss + Faucet and ShowerPressure Loss + Safety Margin (more than5 psi [34 kPa]).

    l To supply hot water to upper floors,additional water pressure (0.44 psi/ft[10 kPa/m]) must be ensured. Themeasurement should be calculated by thedistance between the water inlet of thewater heater (ground level) to the hotwater faucet (upper floor level).

    l Well water systems should be set to ensurea minimum system pressure of 40 psi (276kPa). The pressure should remain stableduring the operation of the water heater.

    l When the water is supplied from a water

    supply tank, the height of the tank and thediameter of the pipes and their relation towater pressure should be taken into

    CAUTION:Reinforcement of the wall is

    required in case the wall isnot strong enough to holdthe appliance.

    Installing the water heater:

    Thermal Expansion

    A thermal expansion tank will be required if

    the water heater is installed in a closed loop

    system to prevent damage to heater, related

    piping and relief valve. Replacing the relief

    valve will not correct the problem! The

    expansion tank is designed with an air cushion

    built in that compresses as the system pressure

    increases, thereby relieving the over pressure

    condition and eliminating the repeated

    operation of the relief valve. Other methods of

    controlling thermal expansion are also

    available. Contact your installing contractor,

    water supplier or plumbing inspector for

    additional information regarding this subject.

  • 8/13/2019 Paloma Manual

    17/40

    Water Supply Connections, continued

    Notice: If the water flow resistance of ashower head is too high, the burner in thewater heater will fail to ignite. Keep the

    shower head clean from debris that couldcause additional pressure drop.

    Notice: If using mixing valves on theoutlet, choose one that prevents coldwater pressure from overcoming hot waterline pressure.

    Notice: If multiple water heaters areinstalled in a manifold system, the

    water piping must be in Parallel. Awater pressure of 40 psi (276 kPa) is

    recommended for each water heater forproper operation of the water heaters.

    Alternate Water Piping Arrangementwith Optional Valve Kit

    Valve kits may be purchased and installed asoptional items. Contact your distributor or

    place of purchase for details.They allow forone person full diagnostic testing and easeof flushing the system. The kit includes twofull port isolation valves, one for the coldside and one for the hot side. Refer to

    page 23.

    Install a shutoff valve near the inlet of thewater heater for service and draining

    purposes.It is not recommended to use pipes with

    smaller diameters than the water supply

    connection of the water heater.

    Before connecting the water supply pipe

    to the water heater, open the shutoff valve

    and clean out sand, debris, air, caulking

    material, etc. inside the pipe. Connect to

    the water inlet, then check water flow.

    Close the shutoff valve and clean the

    water filter.

    Be sure to connect the water inlet and the

    hot water outlet as shown on the water

    heater. If reversed, the water heater will

    not function.

    Installation of unions or flexible copper

    connections are recommended on the

    HOT and COLD water lines, so that the

    water heater may disconnect easily for

    servicing, if necessary.

    Install a Check Valve between the water

    heater and the water shutoff valve (see the

    top left diagram).

    The following should be addressed in

    regards to the HOT WATER OUTLET:

    l Connections between the water heaterand point(s) of use should be as short

    and direct as possible.

    l Local codes shall govern the exact type

    of pipe material that is to be used for

    water connections.

    l To conserve energy and minimize heat

    loss, insulation of hot water piping is

    recommended (see Hot and Cold Pipe

    Insulation Installation on page 24).

    Notice: The flow rate of hot water may

    vary when more than two faucets

    (appliances, fixtures, etc.) are being used

    simultaneously.

    Notice: The pipes MUST be completely

    drainable. If the hot water faucets are

    located at a point higher than the water

    heater, place a drain valve at the lowest

    point (see diagram at the left).

    Water Filter

    Check Valve

    Water Inlet

    Clean the

    Water Filter

    Water

    Nipple

    Air

    Relief

    Valve

    Hot

    Water

    Tap

    Drain Valve

    CAUTION: This water heatermust only be used with thefollowing water supply system

    conditions:

    lWith clean, potable water free

    of corrosive chemicals, sand,

    dirt or other contaminates.

    lWith inlet water temperatures

    above 32F (0C), but not

    exceeding 120F (49C) for

    Residential models and up to

    140F (60C) for Commercial

    models.

    l Free of lime and scale deposits.

    l DO NOT reverse the hotand cold water connections.

    The water heater will not

    operate.

    Notice: Use only teflon tape on cold

    and hot water connections and

    lines.

    This appliance is notintended for space heatingapplication. Do notconnect this heater towaterlines previouslyused for space heatingor non-potable waterdistribution. All waterpiping and components

    shall be suitable forpotable water.

  • 8/13/2019 Paloma Manual

    18/40

    Relief Valve

    A new pressure relief valve, complying

    with the Standard for Relief Valves and

    Automatic Gas Shut-Off Devices for Hot

    Water Supply Systems, ANSI Z21.22/

    CSA 4.4, must be installed at the hot water

    outlet connection of the water heater at the

    time of installation. Local codes shall

    govern the installation of relief valves.

    For safe operation of the water heater, be

    sure that:

    l The pressure rating of the relief valve

    must not exceed 150 psi (1034 kPa), the

    maximum working pressure of the water

    heater as marked on the rating plate.

    l The BTUH rating of the relief valve mustequal or exceed the BTUH input of the

    water heater as marked on its rating plate.

    lNo valve of any type should be installed

    between the relief valve and the water

    heater

    lDischarge from the relief valve should be

    piped to a suitable drain to eliminate

    potential water damage. Piping used should

    be of a type approved for the distribution of

    hot water.

    lHot and cold water lines should be

    insulated up to the water heater. Referto page 24 for details.

    l The discharge line must be NO

    SMALLER than the outlet of the relief

    valve and must pitch downward to allow

    complete drainage (by gravity) of the

    relief valve and discharge line.

    l The end of the discharge line should not

    be threaded or concealed and should be

    protected from freezing. No valve of any

    type, restriction or reducer coupling should

    be installed in the discharge line.

    Notice: Local codes govern the installation

    of relief valves. If local codes require that a

    temperature and pressure relief valve should

    be installed, the manufacturer recommends a

    type 40XL Watts T&Prelief valve or an

    equivalent model be used.

    Notice: Manual operation of relief valves

    should be performed at least once a year. Turn

    off the electrical power and gas shutoff valve.

    Lift and release lever on the relief valve and

    check the manual operation of the relief valve.

    You should take precaution to avoid contact

    with the hot water coming out of the relief

    valve and to prevent water damage.

    Notice: If the relief valve on the system

    discharges periodically, a problem exists and

    service to the water system is required.

    The vinyl tubing as shown is supplied only

    with indoor water heaters and connects to the

    drain valve located at the hot water outlet as

    shown in the diagram at left. Route the other

    end of the vinyl tubing to the drain pan or a

    suitable drain where leakage from the heaterwill not result in damage to the area adjacent

    to the heater or to lower floors of the structure.

    ReliefValve

    PressureReliefValve

    Discharge

    WaterShutoff

    DrainValve

    Valve

    Hot WaterSupply

    Union

    Outlet

    DrainTube tosuitabledrain

    ColdWaterSupplyInlet

    Line

    Notice: The above illustrates apressure-only relief valve. If localcodes require a combinationtemperature and pressure reliefvalve be installed, an extension

    piece may be needed to ensure thatthe valve probe is not directly inthe flow path of the water.

    Installing the water heater:

    Drain Valve

    shown on

    right without

    tubing (barb

    fitting on

    indoor models

    only)

    (indoormodelsonly)

  • 8/13/2019 Paloma Manual

    19/40

    This water heater is certified for installations up to 3,280feet (1000 m) above sea level. The input rating of thiswater heater is based on sea level operation. At higherelevations, the actual input rate may be lower than thevalue listed on the rating label.

    NOTICE: For installations above 3,280 feet (1,000 m)elevation, the Altitude Chip on the PC board must bereplaced. Do not install this water heater at elevationsabove 3,280 feet (1,000 m) without installing theproper Altitude Chip. Please contact your installer,local gas supplier, place of purchase or the CustomerService phone number as listed in this InstructionManual for more information

    High Altitude

    WARNING: Do not attempt to convert this water heater for use with a different type of gas other than the type shown

    on the rating plate. Such conversion could result in hazardous operating conditions.

    Gas Supply

    The supplied Manual Gas Appliance ShutoffValve must be installed at the gas connection of

    the water heater at the time of installation (see

    diagram to the left).

    The branch gas supply line to the water heater

    should be a minimum of 3/4 black steel pipe

    or other approved gas piping material.

    A ground joint union or ANSI design certified

    semi-rigid or flexible gas appliance connector

    should be installed in the gas line close to the

    water heater. The National Fuel Gas Code

    (NFGC) ANSI Z223.1 and CAN B149 code

    mandates a manual gas shut-off valve: See

    NFGC & B149 for complete instructions.

    If flexible connectors are used, the maximum

    length shall not exceed 36 (91 cm).

    If lever type gas shut offs are used, they shall

    be T-Handle type.

    Compound used on the threaded joints of the

    gas piping must be of the type resistant to the

    action of LP gas. Use compound sparingly on

    male threads only.

    A sediment trap should be installed at the

    bottom of the gas line.

    Do not use excessive force (over 31.5 ft lbs.[42.7 Nm]) in tightening the pipe, particularly if

    teflon pipe compound is used, as the unit may

    be damaged.

    The inlet gas pressure to the water heater must

    not exceed 10.5 w.c. (2.6 kPa) for natural or

    14 w.c. (3.5 kPa) for LP gas. For purposes

    of input adjustment, the minimum inlet gas

    pressure (with main burner on) is shown on the

    water heater rating plate. If high or low gas

    pressures are present, contact your gas supplier

    for correction.

    NOTICE: To ensure proper operation of the

    heater the gas pipe and gas meter must be

    sized correctly.

    Gas piping shall be in accordance with l ocal,

    utility company requirement and/or in the

    absence of local codes, use the latest edition

    of the National Fuel Gas Code. In Canada, t he

    latest edition of CSA B149.1 Natural Gas and

    Propane installation code.

    ManualGas

    SupplyLine

    Shutoff

    Manual GasApplianceShutoff

    Union

    Sediment Trap

    Cap

    (Valve)

    (Supplied)

    Leak TestingThe water heater and its gas connections must

    be leak tested at normal operating pressuresbefore it is placed in operation.

    Turn on the gas shut-off valve(s) to the

    water heater.

    Use a soapy water solution to test forleaks at all connections and fittings.Bubbles indicate a gas leak that must

    be corrected.

    The factory connections should also be leak

    tested after the water heater is placed in

    operation.

    Pressure Testing the Gas Supply System

    The water heater and its manual gas shut-offvalve must be disconnected from the gas

    supply piping system during any pressure

    testing of the system at pressures in excess

    of 1/2 psi (14 w.c. [3.5 kPa]).

    The water heater must be isolated from thegas piping system by closing the manual gas

    shut-off valve during any pressure testing of

    the gas supply piping at pressures equal to or

    less than 1/2 psi (14 w.c. [3.5 kPa]).

    WARNING: Never use

    an open flame to test for

    gas leaks, as property

    damage, personal injury,

    or death could result.

    WARNING: Install a

    gas pressure regulator, in

    the gas supply line, which

    does not exceed the

    maximum supply pressure.

    DO NOT use an industrial

    type gas regulator.

  • 8/13/2019 Paloma Manual

    20/40

    Remote Control Installation

    One (1) remote control is provided with thewater heater. Additional remote controls may

    be purchased separately. Up to three (3) remotecontrols can be used with this water heater.

    The following are considerations fordetermining the location of the remotecontrol(s):

    DO NOT install any remote controloutdoors or in areas where it can come incontact with water.

    Place remote control out of childrens reach. The remote control can be installed in

    convenient locations such as the kitchen,laundry room, utility room, or directly besidethe indoor water heater.

    Avoid areas where the remote control maybe exposed to heat, e.g. stove, ranges orheaters.

    Avoid areas where the remote control maybe subjected to oil and/or steamfrom cooking.

    Avoid areas where chemical agents (suchas thinner, benzine and alkalines) are used.

    Avoid areas of direct sunlight. The MAXIMUM distance between the water

    heater and the remote control installationlocation is limited to 195 feet (59 m) of wire.

    NOTICE: Only one of each type of remotecontrols can connect to the water heater.Therefore, a maximum of three controlscan connect to the water heater.

    No other manufacturers controls aresuitable for use with this water heater.

    DO NOT attempt to disassemble theremote control.

    WARNING: Field wiring connections and electrical grounding must comply with local codes, or inthe absence of local codes, with the latest edition of the National Electrical Code, ANSI/NFPA 70, orin Canada, Canadian Electrical Code, CSA C22.1 Part 1.

    Installing the Main Remote Control:

    Remote Control

    Model Number

    Remote Control

    Description

    Temperature

    Set Point RangeAvailability Models

    USC1-117 BATH 1100F - 120F

    (38C)-(49C)

    Optional

    (Sold Separately)

    Residential and

    Commercial

    USC2-117 BATH 2100F - 120F

    (38C)-(49C)

    Optional

    (Sold Separately)

    Residential and

    Commercial

    UMC-117 MAIN

    100F - 120F

    (38C)-(49C)

    Provided with

    Heater

    (Factory Default)

    Residential and

    Commercial

    125F - 140F

    (52C)-(60C)

    With Dip Switch

    AdjustmentResidential

    125F - 180F

    (52C)-(82C)

    With Dip Switch

    AdjustmentCommercial

    MIC-180

    Manifold

    System

    Manifold

    System------

    Optional

    Sold Separately

    Residential and

    Commercial

    NOTICE: The provided

    remote control will allow

    a maximum temperature

    setting of 120F (49C).

    Temperatures of up to 140F

    (60C) for Residential

    models and up to 180F

    (82C) for Commercial

    models can be achieved with

    the MAIN (UMC-117)

    remote control and a dipswitch adjustment. Only

    Commercial water heaters

    can achieve temperatures up

    to 180F (82C). Only

    qualified service personnel

    should perform this

    adjustment.

    NOTICE: If the water

    heaters are installed in a

    manifold system, the mainremote control connected to

    the manifold controller

    (MIC-180) has priority over

    the remote controls

    connected to the water

    heater.

    NOTICE: An optional cable

    (DUOnex Cable) can be

    purchased separately to

    manifold two heaters ofeither Residential or

    Commercial together.

  • 8/13/2019 Paloma Manual

    21/40

    WARNING: Field wiring connections and electrical grounding must comply with local codes, orin the absence of local codes, with the latest edition of the National Electrical Code, ANSI/NFPA 70,or in Canada, Canadian Electrical Code, CSA C22.1 Part 1.

    Remote Control

    Connection Terminals

    Gas Valve

    PCB

    18 AWG

    Extension

    Cable

    Clamp

    NOTICE: Extension cable

    can be any Type-T 18 AWG

    wire similar to a thermostat

    wire and need not be

    polarity sensitive.

    Do Not apply sealant to the

    remote control cable.

    It is not recommended to

    have wiring exposed.

    Remote Control Installation

    Connecting the MAIN (UMC-117 ) remotecontrol to the water heater:

    Drill a 1 (2.5 cm) to 1-1/2 (3.8 cm) holeat the proposed control location.

    Install the extension cable between thelocation of the remote control and thewater heater.

    Remove the base plate from the control. Feed the remote control extension cable

    through the central hole in the base plate. Fix the base plate to the wall usingsuitable screws and wall anchors.Ensure the projections on the base

    plate are pointing upward.

    Connect the remote control cables to theextension cable from the water heater.

    Place the remote control over thebase plate. Ensure the projections inthe base plate fit into the housings inthe remote control.

    Fix the control to the base plate at thebottom of the remote control using thescrew provided.

    Proceed to Connecting the remotecontrol to the water heater, to completeinstallation.

    Connecting the remote control to the waterheater:

    Ensure that the power to the water heaterhas been disconnected.

    Remove the front cover of the water heater. Insert the remote control extension cable

    through the hole at the bottom right handcorner of the water heater.

    Connect the wires to the terminals on

    the top right hand side of the PrintedCircuit Board (PCB) as shown indiagram to the left.

    NOTICE: The remote control wireconnection terminals are not polaritysensitive.

    Firmly tighten the terminal screws. Secure the remote control extension cable

    using the appropriate clamp.

    Replace the front cover of the water heater. Switch on the power supply to the water

    heater.

    Ensure proper operation of the remotecontrol and water heater.

    Remote

    Control

    Projections

    Suitable

    Wall Anchors

    Base Plate

    Screws

    Control

    Screw

    Extension

    CableWall

    Penetration

  • 8/13/2019 Paloma Manual

    22/40

    Installing the Main Remote Control:

    Electrical Connection

    POWER CORD

    (Indoor water heaters only):

    l The electric power supply requirement

    for this water heater is 120 VAC/60HZ,

    2 Amps.

    l The water heater comes with a three (3) pin

    power supply cord (INDOOR MODELS

    ONLY). Use only a power outlet with a

    ground terminal.

    l The installation of an electric leakage

    breaker is recommended.

    l Keep any excess of the power supply cord

    on the outside of the water heater.

    l If local codes require hardwiring, see

    instructions for Hardwiring the Electrical

    Connections.

    HARDWIRING THE ELECTRICAL

    CONNECTIONS

    (Indoor or Outdoor water heaters):

    l Wiring should be carried out by a qualified

    electrician in accordance with local codes.

    l The water heater requires 120 VAC/60Hz and

    should be properly grounded.

    l DO NOT connect grounding wire to water

    pipes, gas pipes, telephone cables, lightning

    conductor circuits and to grounding circuit

    of other equipment that carry a ground-faultinterrupter.

    l An ON/OFF switch must be provided and

    installed for the incoming 120VAC power.

    l Wire the water heater exactly as shown

    below. A wiring diagram is also found

    inside of the cover panel.

    l A green screw is provided in the junction

    box for a grounding connection.

    l Connect the live wire to black leg wire and

    the neutral wire to the white neutral wire.

    WARNING: Shock

    hazard line voltage is

    present. Before servicing

    the water heater, turn off

    the electrical power to the

    water heater at the main

    disconnect or circuit

    breaker. Failure to do so

    could result in severe

    personal injury or death.

    CAUTION: Labelall wires prior to

    disconnection when

    servicing controls. Wiring

    errors can cause improper

    and dangerous operation.

    Verify correct operation

    after servicing.

    On/Off

    Switch

    Junction

    Box

    Ground Screw

    Wire

    Connections

    WARNING: Field wiring connections and electrical grounding must comply with local codes, orin the absence of local codes, with the latest edition of the National Electrical Code, ANSI/NFPA 70,or in Canada, Canadian Electrical Code, CSA C22.1 Part 1.

  • 8/13/2019 Paloma Manual

    23/40

    Installing the water heater:

    Typical Installation of Water Heater(Venting Required for Indoor Models Only)

    To Hot Water

    Faucet(s)

    ReliefValveUnion

    Drain Valve

    6" (15 cm) Air Gap

    Manual Gas

    Appliance

    Shut-off(supplied)

    Sediment

    Trap

    Manual

    Gas Supply Line

    Shut-off

    Valve

    Union

    Cap

    Cold Water

    Supply

    Shut-off

    Valve

    Check

    Valve

    1/4" Per Foot Downward Pit

    90 Elbow

    Vent Adapter

    PowerSupplyCord

    Water Filter

    Drain Valve

    Drain

    Hose(To Suitable Drain)

    Discharge

    Line(To Suitable Drain)

    Air Intake

    Filter

    NOTICE: The National Fuel Gas Code (NFGC) and B149 mandates a manual gas shut-off valve: See

    NFGC/B149 for complete instructions. Local codes or plumbing authority requirements may vary from

    th i t ti di id d d t k d t th i t ti

    Vacuum Relief Valve

    (Not Supplied)

    If required, install per local codes

    and valve manufacturers

    instructions.Water InletWater

    OutletDrain

    Pressure Relief

    Valve

    Hot Water Service

    ValveCold Water

    Service Valve

    Alternate Water Piping Arrangement

    with Optional Valve Kit

    Discharge

    Line(To Suitable Drain)

    To Hot Water

    Faucet(s)

    Relief

    Val veUnion

    Drain Valve

    6" (15 cm) Air Gap

    Manual Gas

    Appliance

    Shut-off(supplied)

    Sediment

    Trap

    Manual

    Gas Supply Line

    Shut-off

    Val ve

    Union

    Cap

    Cold Water

    Supply

    Shut-off

    Val ve

    Check

    Val ve

    Water Filter

    Drain Valve

    On/Off

    Switch

    Conduit for

    Wiring to Unit

    Flue Terminal

    F

    PRIORITY

    POWERON/OFF

    Remote

    Control

    Indoor Models Outdoor Models

    Install indoors only.

  • 8/13/2019 Paloma Manual

    24/40

    Installing the water heater:

    For increased energy efficiency, use pipe

    insulation. Please install the insulation

    according to the diagram above, making sure

    to insulate all the way to the top. Do not

    cover any drain or pressure relief valve(s).

    Dos

    q Do follow all installation instructionscovered in this manual.

    q Do check inlet gas pressure to ensurethat it is within the range specified onthe rating plate.

    q Doprovide adequate air for combustionand ventilation as discussed in theInstruction Manual and the National FuelGas Code (CAN/CGA B149 in Canada).

    q Do maintain proper clearances tocombustibles and non-combustibles asspecified on the nameplate.

    q Do ensure that the venting system complieswith the guidelines found in the InstructionManual and National Fuel Gas Code(CAN/CGA B149 in Canada).

    qDo contact local gas company to ensure gasmeter and gas piping are adequately sized.

    q Do use teflon tape on water lineconnections and fittings.

    Donts

    q Dontblock or restrict Air IntakeOpening located on the front coverof the water heater.

    q Dont remove the front cover unlessabsolutely necessary. This should only bedone after being examined by a qualifiedservice technician.

    q Dont install this product where standing

    water may occur.q Dont use pipe dope on water line

    connections and fittings.

    During Installation of this water heater

    Hot and Cold Pipe Insulation Installation

    Insulation Blankets

    Insulation blankets, available to the generalpublic for external use on gas water heaters,are not necessary. The purpose of an

    insulation blanket is to reduce the standbyheat loss encountered with storage tankheaters. This water heater does not store watermaking an insulation blanket unnecessary.

    The manufacturers warranty does not coverany damage or defect caused by installation,attachment or use of any type of energysaving or other unapproved devices (otherthan those authorized by the manufacturer)into, onto or in conjunction with the waterheater. The use of unauthorized energy savingdevices may shorten the life of the waterheater and may endanger life and property.

    The manufacturer disclaims any responsibilityfor such loss or injury resulting from the useof such unauthorized devices.

    CAUTION: If local codes require theapplication of an external insulationblanket to this water heater, pay carefulattention to the following so as not torestrict the proper function and operationof the water heater:

    l Do not cover the air inlet, flue outlet or

    operating and warning labels attached to

    the water heater or attempt to relocate them

    on the exterior of insulation blanket.

    WARNING: If localcodes require externalapplication of insulation

    blanket kits themanufacturersinstructions includedwith the kit must becarefully followed.

    NOTICE: The hot and coldpipes should be insulated asshown to provide additionalfreeze protection.

    Water Inlet

    Pressure Relief

    Valve

    Drain Valve

    Hot Water Service

    Valve

    Cold Water

    Service ValveWARNING: In case the

    pipe insulation is not ratedfor the appropriateweather conditions installelectric heat tracing or

    equivalent to preventfreezing of the pipes. Donot insulate or block drainvalve on the hot outletfitting. If the pipes areallowed to freeze, the waterheater and the pipes maymalfunction or leak due tofreezing water.

    Pipe Insulation

  • 8/13/2019 Paloma Manual

    25/40

    A. OutdoorWater Heater Location

    q Outdoor water heaters must be installed outdoors.

    q Protected from freezing temperatures.

    B. Indoor Water Heater Location

    q Close to area of vent termination.

    q Indoors and protected from freezing temperatures.

    C. Outdoor and Indoor Water Heater Location

    q Proper clearance from combustible surfaces observed.

    q Sufficient fresh air supply for proper operation ofwater heater.

    q Air supply free of corrosive elements andflammable vapors.

    qProvisions made to protect area from water damage.

    q Sufficient room to service heater.

    q Combustible materials, such as clothing, cleaningmaterials, rags, etc. clear of the heater andvent piping.

    q Water heater is properly attached to the wall.

    D. Water Supply

    q Water supply has sufficient pressure.

    q Air purged from water heater and piping.

    q Water connections tight and free of leaks.

    q Water filter is clean and in place.

    q Materials used are as instructed in this manual.

    q Water pipes are insulated and protected fromfreezing.

    E. Gas Supply

    q Gas type matches rating plate.

    q Gas supply pressure is sufficient for the water heater.

    q Gas line equipped with shut-o