The Ins and Outs of Basic SchemaTIc SymBOlS BY HOWARD L. PEMPER, CMS A practical approach to reading and understanding the schematic diagrams used to explain how HVACR systems operate. Figure 1 ParT 3 Editor’s Note: Due to the length of Part 3 and the number of diagrams associated with it, this last part has been separated. To ensure all of the information gets into readers’ hands, a Part 4 has been added to the series and will appear in the May 2011 issue of RSES Journal. T he previous article discussed several com- ponents that are used on schematic dia- grams. Part 3 incorporates these elements into complete diagrams. The HVACR industry uses three basic diagrams for equipment. First, and probably least used, is the label diagram; then the installation diagram; and finally the one most often used is the ladder or schematic diagram. Figure 1 is an example of a very basic label diagram of a simple condensing unit. It has a contactor, condenser fan motor, pressure controls and terminal blocks. Note that the components are drawn as they would appear physically. The label diagram does not use symbols to represent parts. It relies on the physical description of the part itself. Figure 2 is a basic form of an installation dia- gram. It is primarily used for wiring one compo- nent to another. The thermostat to an air-condi- tioner as shown in Figure 2, are just the external terminals. It does not help in diagnosing any problems. As was stated in Part 1, most lines on an installation diagram are dashed. These nor- mally represent wires that are field-installed. www.rsesjournal.com www.rsesjournal.com 10 RSES Journal APRIL 2011 Figure 2 RUNGS OF A LADDER RUNGS OF A LADDER Figure 3 [Editor’s Note: The wrong diagrams for Figures 3 and 16 were printed in the April 2011 issue of RSES Journal . The figures have been corrected here in this electronic version of the feature.]

ParT 3 The Ins and Outs of Basic SchemaTIc SymBOlSFigure 4 Legend Figure 4 Figure 6 APC CAPACITOR CC COMPRESSOR CONTACTOR CCHR CRANKCASE HEATER CFM CONDENSER FAN MOTOR COMP COMPRESSOR

  • Upload
    others

  • View
    6

  • Download
    0

Embed Size (px)

Citation preview

  •  

     

    The Ins and Outs of Basic SchemaTIc SymBOlS

    B y H o w a r d L . P e m P e r , C m S

    a practical approach to reading and understanding the schematic diagrams used to explain how HVaCr systems operate.

    Figure 1

    ParT 3

    Editor’s Note: Due to the length of Part 3 and the number of diagrams associated with it, this last part has been separated. To ensure all of the information gets into readers’ hands, a Part 4 has been added to the series and will appear in the May 2011 issue of RSES Journal.

    The previous article discussed several com-ponents that are used on schematic dia-grams. Part 3 incorporates these elements into complete diagrams. The HVACR industry uses three basic diagrams for equipment. First, and probably least used, is the label diagram; then the installation diagram; and finally the one most often used is the ladder or schematic diagram.

    Figure 1 is an example of a very basic label diagram of a simple condensing unit. It has a contactor, condenser fan motor, pressure controls and terminal blocks. Note that the components are drawn as they would appear physically. The label diagram does not use symbols to represent parts. It relies on the physical description of the part itself.

    Figure 2 is a basic form of an installation dia-gram. It is primarily used for wiring one compo-nent to another. The thermostat to an air-condi-tioner as shown in Figure 2, are just the external terminals. It does not help in diagnosing any problems. As was stated in Part 1, most lines on an installation diagram are dashed. These nor-mally represent wires that are field-installed.

    w w w . r s e s j o u r n a l . c o mw w w . r s e s j o u r n a l . c o m10 RSES Journal APRIL 2011

    Figure 2

    RUNGS OF A LADDER

    RUNGS OF A LADDER

    Figure 3

     

     

       

    [Editor’s Note: The wrong diagrams for Figures 3 and 16 were printed in the April 2011 issue of RSES Journal. The figures have been corrected here in this electronic version of the feature.]

  •  

    "d"

    "e"

    "c"

    "a"

    "b"

    The Ins and Outs of Basic SchemaTIc SymBOlS

    w w w . r s e s j o u r n a l . c o m APRIL 2011 RSES Journal 11w w w . r s e s j o u r n a l . c o m

    Figure 4 Legend

    Figure 4

    Figure 6

    CAP CAPACITOR CC COMPRESSOR CONTACTOR CCHR CRANKCASE HEATER CFM CONDENSER FAN MOTOR COMP COMPRESSOR DISC DISCONNECT FPS FREEZE PROTECTION SWITCH FU FUSE GND GROUND GV GAS VALVE

    Figure 3 is the ladder diagram of Figure 1. The reason it is called a ladder diagram is because the components are normally drawn in a horizontal plane while the power sup-ply wires are vertical. Together, they look like rungs on a step ladder. These diagrams simplify the circuits, which will aid in diagnosing any electrical problem with the unit. The con-tactor coil C-1 controls the two sets of contacts marked C-1 terminals 11, 21, 12 and 22. These are at line-voltage poten-tial. The contactor coil C-1 is controlled by the terminals C and Y1 on the terminal block TB-2. These are connect-

    IFM INDOOR FAN MOTOR IFMR INDOOR FAN MOTOR RELAY IGNC IGNITION CONTROL IGNCR IGNITION CONTROL RELAY HPS HIGH PRESSURE SWITCH LPS LOW PRESSURE SWITCH LS LIMIT SWITCH RS ROLLOUT SWITCH TB TERMINAL BOARD TRAN TRANSFORMER

    ed to an external thermostat that is not shown. These are in the low-voltage circuit. The compressor is protected by the low-pressure switch LPS1 and the high-pressure switch HPS1. Note that the safety switches are wired in a series configuration.

    cOmPlex dIagramS In BaSIcSAt first glance, most schematics look complex, but isolat-ing or breaking them down into separate areas helps make troubleshooting easier. Figure 4 represents a generic pack-age rooftop gas/electric unit and is more complex, but can be broken down into four or five basic parts.

    The two most important divisions of a schematic that most manufacturers do not deviate from is the letter “a” at the top of Figure 4, normally considered the high-voltage section; and the letter “b,” usually the low-voltage section. The normal breaking point between the low and high volt-age of any schematic is a transformer, which is represented by the letter “e.” Remember there can be more than one transformer on a schematic, depending upon the equip-ment. The letter “c” is considered the line side of the dia-gram, which is normally where the controls and switches are drawn; and the letter “d” represents the load side where the power-consuming components are located. Several compo-nents on the diagram only have a letter next to them; each of which can be deciphered using an accompanying legend.

     

     

    Figure 5a

    Figure 5b

       

     

  •  

    w w w . r s e s j o u r n a l . c o mw w w . r s e s j o u r n a l . c o m12 RSES Journal APRIL 2011

    Figure 13

      Figure 14

     

     

     

     

    Figure 7

    Figure 11

    Figure 8

    Figure 12

    Figure 9

    Figure 10

     

     

     

     

     

     

    Now, to put all of these components together:The series of numbers listed vertically from the top of

    most diagrams to the bottom represents line-side numbering. In Figure 5a, line 1 is the disconnect switch; and in Fig-ure 5b, line 22 is the capacitor for the condenser-fan motor (CFM). Manufacturers will frequently use these line numbers when describing the sequence of operations.

    The numbers grouped together at specific points or at spe-cific loads on the right side of a diagram represent load-side numbering. In Figure 6, the numbers 10, 13, 17 and 21 de-pict the safety controls and the compressor contactor (CC). Each of these numbers represents a line that corresponds to a

    switch or control that the coil operates. Figure 7 shows the CC is controlling N/O contacts CC1 and CC2 to start the compressor; and CC4 at line 21 which is a N/O set of open contacts. This in turn energizes on the CFM, as is illustrated in Figure 8.

    Lastly, the compressor contactor CC also is controlling CC3 at line 17. Note that the number is underlined. Any time an underlined number on the load side of a schematic appears, it will indicate an N/C set of contacts. This switch will open when the compressor is energized, de-energizing the crankcase heater (CCHR) shown in Figure 9.

    The next controlling relay shown in Figure 10 is the indoor-fan-motor relay (IFMR), which is used to control the indoor-fan-motor’s speed from heating (low speed) to cooling (high speed). This device controls a single-pole double-throw (SPDT) set of contacts at lines 28 and 30. Note in Figure 4 line 28 by the IFMR is underlined, so is N/C and will switch over when the coil energized.

    The last controlling device is the ignition control (IGNC), which closes the gas valve (IGNCR2) at line 51, as illustrated in Figure 11. The IFM is turned on after a cer-tain period of time and turns on the fan at line 28. This is determined by the IGNCR1, shown in Figure 12. Note that

     

     

       

  • w w w . r s e s j o u r n a l . c o m APRIL 2011 RSES Journal 13w w w . r s e s j o u r n a l . c o m

    Figure 15  

    INDOOR OUTDOOR

     

    Figure 16

    Figure 17

    the controlling coil can be at a different position on the diagram than the contacts, as illustrated in the previous diagrams.

    The last item to connect to this unit to make it run would be a thermostat. Figure 13 is an illus-tration of a generic thermostat connected to TB-1.

    To facilitate the location of components used on schematics, some manufacturers will place a com-ponent layout diagram next to the wiring diagram. This speeds up finding a failed element or compo-nent of the circuit. Figure 14 is an example of a component diagram and a legend.

    Figure 15 is diagram of hypothetical generic heat-pump system. It is a combination of a ladder, installation and component diagram. Starting with the circuit on the right side at the top, we find that the compressor has a three-phase power sup-ply. It has a crankcase heater that is controlled by the contactor’s open contacts. Figure 16 illustrates that when the contacts are open, current flows through the crankcase heater (which per this leg-end is now referenced as CCHTR) and the com-pressor’s windings, maintaining enough temperature in the compressor to keep the oil and refrigerant separate. When the contactor’s contacts close the CCHTR is de-activated.

  • w w w . r s e s j o u r n a l . c o mw w w . r s e s j o u r n a l . c o m14 RSES Journal APRIL 2011

      Figure 19

    C . O R

    DFT . R C

    a

    d

    b

    e

    c

    f

    Editors Note: These points are from Figure 18 and 19.

      Figure 18

    Figure 17 illustrates the single-phase outdoor-fan motor (OFM). Note that the motor is energized when power is ap-plied to the compressor. However, this is a heat-pump system, and the fan motor must be off when in defrost. This is ac-complished with the N/C defrost relay (DR) contacts.

    The last item on the outdoor section of this heat pump is the printed circuit board PCB123456. This control’s defrost, reversing valve and the compressor are shown in Figure 18. There are a few items of note about the PCB. The first is some of the hardwired connections that are made to push on connectors right on the board, such as the reversing-valve solenoid (RVS). It is made to terminals O(a) and C(b). The DFT (defrost thermostat) is connected to the PCB at points R(c)and DFT(d). There are a number of devices that cannot be removed from the board and can be somewhat difficult to troubleshoot. Deciding which circuit controls each com-ponent can be figured out by inspecting the diagram of the PCB.

    The next series of hard-wired devices are the safety con-trols and the contactor, which are shown in Figure 19. The high-pressure switch is wired directly to the contactor and the low-pressure switch is wired to the PCB at R(e). The other side of the contactor is wired to the PCB at C(f).

    The indoor section of Figure 15 is shown more clearly in Figure 20, where several different circuits not yet discussed are incorporated in this portion of the system.

  •  

    w w w . r s e s j o u r n a l . c o m APRIL 2011 RSES Journal 15w w w . r s e s j o u r n a l . c o m

      Figure 21

    Figure 22

      Figure 20

    Figure 21 illustrates the operation of the first sequencer (SEQ-1), which has a two-fold function. The first is when W2 is energized and the SEQ-1 starts its timing process. Upon completion of the timing the contacts SEQ-1 close. This causes the HTR-1 is energized. Simultaneously, the fan motor (FM) is energized in medium speed. If more heat is required, the next two sequencers, SEQ-2 and SEQ-3, will be energized causing the heaters HTR-2 and HTR-3 to become energized, as is shown in Figure 22.

    Next month, Part 4 will break down the more complex schematic of a ficticious two-stage heating/cooling rooftop unit.