Upload
nevan
View
393
Download
48
Tags:
Embed Size (px)
DESCRIPTION
Programmable Logic Controllers Third Edition. Frank D. Petruzella McGraw-Hill. Chapter 7. Programming Timers. - PowerPoint PPT Presentation
Citation preview
Programmable Logic Controllers
Third Edition
Frank D. Petruzella
McGraw-Hill
Chapter 7
ProgrammingTimers
There are very few industrial control systems that do not need at least one or two timed functions. They are used toactivate or de-activate a device after a preset interval oftime.
Timers
Time delay relays and solid-state timers are used to provide a time delay. They may have displays, pots or other means of operator interface for time settings and electromechanical or solid state outputs.
Time Delay Relay
Solid-StateTimer
On-Delay Timing Relay
Operating coil
Instantaneous contacts
NO
NC
Nontimed contacts are controlled directly by the timer coil, as in a general-purpose control relay.
Time control contacts
NO
NC
Time adjustment
When the coil is energized, the timed contacts are are prevented from opening or closing until the time delay period has elapsed. However, when the coil is de-energized, the timed contacts return instantaneously to their normal state.
Normally open, timed closed contact (NOTC)
Contact is open when relay coil is de-energized
When relay is energized, there is a time delay in closing
Timed Contact Symbols
On-Delay Symbols
Normally closed, timed open contact (NCTO)
Contact is closed when relay coil is de-energized
When relay is energized, there is a time delay in opening
Normally open, timed open contacts (NOTO).
Contact is normallyopen when relay coilis de-energized.
When relay coil is energized, contact closes instantly.When relay coil is de-energized, there is a time delay before the contact opens.
Timed Contact Symbols
Off Delay Symbols
Normally closed, timed closed contacts (NCTC).
Contact is normallyclosed when relay coilis de-energized.
When relay coil is energized, contact opens instantly.
When relay coil is de-energized, there is a time delay before the contact closes.
On-Delay Relay Timer Circuit (NOTC Contact)
L1 L2S1
L1
Sequence of operation
10 s
S1 open, TD de-energized,TD1 open, L1 is off.
After 10 s, TD1 closes, L1 is switched on.
S1 closes, TD energizes,timing period starts,TD1 still open, L1 is still off.
S1 is opened, TD de-energizes, TD1 opens instantly, L1 is switched off.
10 s
OFF
ONInput
Output
Timing Diagram
On-Delay Relay Timer Circuit (NCTO Contact)
S1 open, TD de-energized,TD1 closed, L1 is on.
Sequence of operationL1 L2
L1
S1
10 s
After 10 s, TD1 opens,L1 is switched off.
S1 closes, TD energizes,timing period starts, TD1is still closed, L1 is still on.
L1 L2
S1 is opened, TD de-energizes,TD1 closes instantly, L1 isswitched on.
10 s
On
Off
Input
Output
Timing Diagram
Off-Delay Relay Timer Circuit (NOTO Contact)
L1 L2S1
L1
Sequence of operation
S1 open, TD de-energized,TD1 open, L1 is off.
S1 closes, TD energizes,TD1 closes instantly, L1 is switched on.
S1 is opened, TD de-energizes,timing period starts, TD1 isstill closed, L1 is still on.
10 s
After 10 s, TD1 opens, L1 isswitched off.
10 s
Input
OutputOff
On
Timing Diagram
Off-Delay Relay Timer Circuit (NCTC Contact)L1 L2
S1
L1
Sequence of operation
S1 open, TD de-energized,TD1 closed, L1 is on.
S1 closes, TD energizes,TD1 opens instantly, L1 is switched off.
S1 is opened, TD de-energizes, timingperiod starts, TD1 is stillopen, L1 is still off.
10 s
After 10 s, TD1 closes,L1 is switched on.
10 s
Input
Output On
Off
Timing Diagram
1. Timers are used to activate or de-activate adevice after a preset interval of time.(True/False)
2. With most timers the time delay period is fixedand can not be varied. (True/False)
3. ________ contacts are controlled directly by the timer coil, as in a general-purpose control relay.
(a) timed (c) instantaneous (b) NO (d) NC
4. When a relay timer coil is de-energized, the timed contacts return instantaneously to their normal state. (True/False)
5. Which of the following symbols represents a normally open timed closed contact?
6. Which of the following symbols represents a normally closed timed open contact?
7. The timed relay contact shown is designed to operate so that:
a. when the relay coil is energized, there is a time delay in closingb. when the relay coil is energized, there is a time delay in openingc. when the relay coil is de-energized, there is a time delay in closingd. when the relay coil is de-energized, there is a time delay in opening
8. The timing diagram shown is that of an
a. on-delay timer circuit (NOTC contact)b. on-delay timer circuit (NCTO contact)c. off-delay timer circuit (NCTC contact)d. off-delay timer circuit (NOTO contact)
10 s
Input
OutputOff
On
Timing Diagram
9. In the circuit shown, the light will stay off
a. as long as S1 is closedb. for 10 seconds after coil TD is energizedc. for 10 seconds after coil TD is de-energizedd. both a and c
L1 L2
S1
L1
10 s
10. In the circuit shown, the light will stay on
a. as long as S1 is closedb. as long as S1 is openc. for 10 seconds after S1 is closed d. both b and c
Programmed Timer Instructions
PLC timers are output instructions that provide the same functions as timing relays and solid state timers.
Some advantages of PLC timers:
their settings can be altered easily
the number of PLC timers used can be increased or decreased by programming changes without wiring changes
timer accuracy and repeatability are extremely high
RSLogic Timer Commands
Timer/Counter
TON
Command Name Description
TON Timer On-Delay Counts time base intervals when the instruction is “true”
RSLogic Timer Commands
Timer/Counter
Command Name Description
TOF
TOF Timer Off-Delay Counts time base intervals when the instruction is “false”
RSLogic Timer Commands
Command Name Description
RTO Retentive Timer ON
Counts time base intervals when the instruction is “true” and retains the accumulated value when the instruction goes "false" or when power cycle occurs
Timer/Counter
RTO RES
RES Reset When this instruction is "true" it resets the count of the RTO counter
Quantities Associated with the Timer Instruction
Preset Time – Represents the time duration of the timing circuit. For example, if a time delay of 10 s is required, the timer will have a preset of 10 s.
Accumulated Time – Represents the amount of time that has elapsed from the moment the timing coil became energized.
Time Base – Timers can typically be programmed withseveral different time bases: 1 s, 0.1 s, and 0.01 s are typical time bases. For example, if you enter 0.1 for the time base and 50 for the preset time the timer would have a 5 s delay (50 x 0.1 s = 5 s).
Coil-Formatted Timer Instruction
The timer assigned an address
XXX
TON
The type of timer is specified
Preset value PR:YYY Time base 0.1 s Accumulated value AC:000
Contact determines rung continuity
When the timer rung has logic continuity, the timer's accumulated value increases. When accumulated value equals the preset value, the output is energized and and the timed output contact associated with the output is closed. The timed contact can be used as many times as you wish throughout the program as a NO or NC contact.
Generic Block-Formatted Timer Instruction
Timers are most often represented by boxes in a ladder logic.
Preset timeTime baseAccumulated time
Retentive timer block
Control line controls the actual timing operation of the timer.Whenever this line is true the timer will time.
Reset line resets the the timer's accumulated value to zero.
Output line
The timer continuously compares its accumulated time with its preset time. Its output is logic 0 as long as the accumulated time is less than the preset time. When the two become equal the output changes to logic 1.
On-Delay Timer Instruction
The on-delay timer operates so that, when the rung containing the timer is true, the timer time-out period commences.
TimerInput
Rung condition
Timed period
False
True
On delaytime duration
Timed output bitFalse
OFF
True
ON
Timer Sequence
The timed output becomes true sometimes after the timer rung becomes true; hence the timer is said to have an on delay.
Allen-Bradley On-Delay Timer Instruction
Allen-Bradley PLC-5 and SLC-500 controller timer elements each take three data table words: the control word, preset word, and accumulated word.
The control word uses three control bits: Enable (EN) bit,Timer-Timing (TT) bit, and Done-Bit (DN).
TIMER TABLE
T4:0
/EN /TT /DN
0 0 0
Allen-Bradley On-Delay Timer Instruction
The Enable (EN) bit is true (has a status of 1) whenever the timer instruction is true. When the timer instruction is false, the enable bit is false (has a status of 0)
Enable bit false
TON
TIMER ON DELAYTimer T4:0 EN
EN
T4:0 Enable bit true
Allen-Bradley On-Delay Timer Instruction
The Timer-Timing (TT) bit is true whenever the accumulated value of the timer is changing, which means the timer is timing.
TIMER ON DELAY
TON
Timer T4:0Preset 50Accumulated 10
EN
TT
T4:0 Timer-Timing bit true
Allen-Bradley On-Delay Timer Instruction
The Done-Bit (DN) changes state whenever the accumulated value reaches the preset value. Its state depends on the type of timer being used.
TIMER ON DELAY
TON
Timer T4:0Preset 50Accumulated 10
EN
DN
T4:0
DN
Done-bit changes state
50
Allen-Bradley On-Delay Timer Instruction
The preset value (PRE) word is the set point of the timer, that is, the value up to which the timer will time.
The accumulated value (ACC) word is the value that increments as the timer is timing. The accumulated value will stop incrementing when its value reaches the preset value.
TIMER TABLE
T4:0
/EN /TT /DN .PRE .ACC
0 0 0 0 0
Allen-Bradley On-Delay Timer Instruction
TONTIMER ON DELAY
EN
DN
The information to be entered includes:
Timer T4:0
Timer number which must come from the timer file.
Time base 1.0
Time base which is expressed in seconds.
Preset 15
Preset value which is the length of the time delay.
Accumulated 0
Accumulated value which is normally entered as 0.
On-Delay Timer Program
Ladder Logic Program
L1 L2
Input A
Input A
T4:0
T4:0
T4:0
EN
TT
DN
TONTIMER ON DELAYTimer T4:0Time base 1.0Preset 10Accumulated 0
EN
DN
Output B
Output B
Output C
Output COutput D
Output D
G
R
Y
10
On-Delay Timer ProgramTiming Diagram
Input condition AOn
Off
Timer-enable bitOn
Off
Timer-timing bitOn
Off
Timer-done bitOn
Off
Timer accumulated value
0
4 s 4 s
On-Delay Timer Program
Timers are 3-word elements
Word
0
1
2
Word 0 is the control word
EN TT DN Internal use
Word 1 stores the preset value
Preset value PRE
Word 2 stores the accumulated value
Accumulated value ACC
On-Delay Timer With Instantaneous Output
Relay Ladder Schematic Diagram
L1 L2Stop Start
1TD
M
1TD-1(instantaneous contact)
1TD-2 (5 s)(timed contact)
1TD
On-Delay Timer With Instantaneous Output
Programmed Circuit
MotorMotor M
Internal relay
Internal relay
Stop
Stop
Start
Start
TimerPR: 5TB: 1 s Output
line
M
L1 L2
Inputs Output
Ladder logic program
Start-Up Warning Signal Circuit
Relay Ladder Schematic Diagram
L1 L2Start-upPB1
ResetPB2 CR1
CR1-1
CR1-2
1TD-1(10 s)
CR1-3
1TD
Horn
TONTIMER ON DELAYTimer T4:0Time base 1.0Preset 10Accumulated 0
InputsOutput
Ladder logic program
Programmed Circuit
Horn
Horn
Start-up
Reset
PB1
PB1
PB2
PB2
EN
DNT4:0
EN
DN
T4:0
EN
T4:0
Start-Up Warning Signal Circuit
10
Timed Closed Solenoid Value Program
Input
L1Switch
SW_1
SW_1
Ladder logic program Output
L2
Valve
Valve
EN
DN
timer_1.dn
TONTimer On DelayTimer timer_1Preset 12000 Accumulated 0
12000
Automatic Sequential Control System
Relay Ladder Schematic Diagram
L1 L2StopPB1
StartPB2 Lube oil
pump motorOL
M1
M1-1
PS1
(lube oilpressure switch)
Main drive motor
M2
OL
1TD
1TD-1(15 s)
Feedmotor
OL
M3
Automatic Sequential Control SystemProgrammed Circuit
Inputs Outputs
Ladder logic program
OL
OL
OL
M1
M1
M2M2
M3
M3
TONTIMER ON DELAYTimer T4:0Time base 1.0Preset 15Accumulated 0
PB1
PB1
PB2
PB2
PS1 PS1
EN
DN
M1
T4:0
DN
15
Off-Delay Programmed Timer
The off-delay timer (TOF) operation will keep the output energized for a period after the rung containing the timer has gone false.
EN
DN
TOFTIMER OFF DELAY
TIMER T4:3Time base 1.0Preset 15Accumulated 0
I:1.0/0
I:1.0/0
O:2.0/1
O:2.0/1T4:3/DN
PL
L1 L2Input OutputLadder logic program
S1
15
Off-Delay Programmed Timer
Timing Diagram
Input condition S1
True
False
Timed period
Off delaytimed duration
Timed output
O:2.0/1
True (logic 1)
False (logic 0)
Preset value = accumulated value
L1
Off-Delay Timer Used To Switch Motors Off Input
L2OutputLadder logic program
5000
10000
15000
Pneumatic Off-Delay Timer
Relay LadderSchematic Diagram
L1 L2
Programmed Pneumatic Off-Delay Timer
Equivalent Programmed Circuit
L1 L2
Input OutputsLadder logic program
5
Fluid Pumping Process
When the pump start button is pressed, the pump starts. The button can then be released and the pump continues to operate.
When the stop button is pushed, the pump stops.
Operation
Before starting, PS1 must be closed.
PS2 and PS3 must be closed for 5 s after the pump starts. If either PS2 or PS3 opens, the pump will shut off and will not not be able to start again for another 14 s.
Fluid Pumping Process Program
L1 L2
Inputs Output
Ladder logic program
50
Retentive Timer
A retentive timer accumulates time whenever the device receives power, and maintains the current time should power be removed from the device. Once the device accumulates time equal to its preset value, the contacts of the device change state. The retentive timer must be intentionally reset with a separate signal for the accumulated time to be reset.
Electromechnical Retentive Timer
Cam operatedcontact
Motor-drivencam
Once power is applied, the motor starts turning the cam. The positioning of the lobes determines the time it takes to activate the contacts. If power is removed from the motor, the shaft stops but does not reset.
Retentive On-Delay Timer Program
The PLC-programmed RETENTIVE ON-DELAY timer (RTO) operates in the same way as the nonretentive on-delay timer (TON), with one major exception. This is a retentive timer reset (RTR) instruction.
Unlike the TON, the RTO will hold its accumulated value when the timer rung goes false and will continue timing where it left off when the timer rung goes true again. This timer must be accompanied by a timer reset (RES) instruction to reset the accumulated value of the timer to zero.
Same address
Retentive On-Delay Timer Program
390
Retentive On-Delay Timing Chart
Enable bit is reset when input pushbutton PB1 is opened
Accum value retainedwhen rung goes false
Accum = Preset
When reset PB2 is closed, the T4:2/DN bit is reset to 0. Accumulated value is reset and held at zero until the reset pushbutton is opened.
Retentive On-delay Alarm Program
The purpose of the RTO timer is to detect whenever a piping system has sustained a cumulative overpressure condition of 60 s. At that point, a horn is sounded automatically. You can silence the alarm by switching the key switch to the rest position.
600000
L1L2Ladder logic program
Bearing Lubrication Program
Sequence Of Operation
To start the machine, the operator turns SW on. Before the motor shaft starts to turn, the bearings are supplied with oil by the pump for 10 s. The bearings also receive oil when the machine is running. When the operator turns SW off to stop the machine, the oil pump continues to supply oil for 15 s. A retentive timer is used to track the total running time of the pump. When the total running time is 3 h, the motor is shut down and a pilot light is turned on to indicate that the filter and oil need to be changed. A reset button is provided to reset the process after the filter and oil have been changed.
Bearing Lubrication Program
100
15
10800
Cascading Timers
The programming of two or more timers together is called cascading. Timers may be interconnected, or cascaded to satisfy any required control logic.
Three motors started automatically in sequence with a 20-s time delay between each motor startup.
Relay Schematic Diagram
Equivalent Time-Delayed Motor-Starting Program
20000
20000
Annunciator Flasher Circuit
Two timers can be interconnected to form an oscillator circuit. The oscillator logic is basically a timing circuit programmed to generate periodic output pulses of any duration. They can be used as part of an annunciator system to indicate an alarm condition.
The oscillator circuit output is programmed in series with the alarm condition. If the alarm condition is true, the appropriate output indicating light will flash.
Annunciator Flasher Circuit
Cascading of Timers for Longer Time Delays
30000
12000
Control of Traffic Lights in One Direction
A typical application for PLC timers is the control of traffic lights.
Control of Traffic in One DirectionSequence of Operation
Red 30 s
Amber 5 s
Green25 s
Control of Traffic Lights in One Direction
30
25
5
11. The timed contact of a PLC timer can onlybe used as a normally-open contact. (True/False)
12. The ______ bit operates the same as an instantaneous contact on a timer relay.
a. enable
b. done
c. timer-timing
d. timer number
13. The preset time of a PLC timer represents the amount of time that has elapsed from the momentthe timing coil became energized. (True/False)
14. If the preset time of a timer is 150 and the timebase is 0.1 seconds, the time-delay period wouldbe 1500 seconds. (True/False)
15. In general, the three different types of PLC timers are:
a. TON, TOF, and PRE
b. TON, TOF, and RTO
c. TON, ACC, and RTO
d. TT, EN, and DN
16. The amount of time for which a timer isprogrammed is called the
a. presetb. set pointc. Done Time (DN)d. accumulated time
17. The timer reset instruction must be addressed to the same address as the ______ instruction.
a. TON
b. TOF
c. RTO
d. EN
18. Which of the following statements is not true for a retentive on-delay timer?
a. The timer accumulates time when it is energized.
b.The timer requires a reset instruction to reset the accumulated value of the timer to zero.
c. The timer does not reset to zero when it is de-energized.
d. The reset input to the timer will not override the control input.
19. The timer instruction is:
a. an input instruction c. either a or b
b. an output instruction d. both a or b
20. The interconnection of timers is commonly called : a. grouping b. programming c. sequencing d. cascading
21. For the program shown, the pilot light will be:
a. on at all timesb. off at all timesc. switched on 15 s after the switch has been actuated from the open to the closed positiond. switched off 15 s after the switch has been actuated from the on to off position