16
SP-PP-0507 w/ Smart Connect™ Feature Submittal Package Potable Water Hydronic Heating Chilled Water Compressed Air Nitrogen N 2 Argon Low Pressure Steam Fire Protection Vacuum Argomac - K (welding gas) Corgon Oxygen O 2 (non medical) VIEGA One Company... One Partner... Delivering System Solutions. 301 N. Main, Floor 9 • Wichita, KS 67202 • Ph: 877-Viega-NA • Fax: 316-425-7618 • E-Mail: [email protected] • www.viega-na.com

ProPress System Submittal Package - Viega - Columbia · PDF fileTest Pressure 600 PSI Max. ... iv. excessive water pressure, corrosive substances, ... ProPress System Submittal Package

  • Upload
    doanthu

  • View
    245

  • Download
    3

Embed Size (px)

Citation preview

Page 1: ProPress System Submittal Package - Viega - Columbia · PDF fileTest Pressure 600 PSI Max. ... iv. excessive water pressure, corrosive substances, ... ProPress System Submittal Package

SP-PP-0507

w/ Smart Connect™ Feature

Submittal Package

®

Potable Water

Hydronic Heating

Chilled Water

Compressed Air

Nitrogen N2

Argon

Low Pressure Steam

Fire Protection

Vacuum

Argomac - K (welding gas)

Corgon

Oxygen O2 (non medical)

VIEGA • One Company... One Partner... Delivering System Solutions.301 N. Main, Floor 9 • Wichita, KS 67202 • Ph: 877-Viega-NA • Fax: 316-425-7618 • E-Mail: [email protected] • www.viega-na.com

Page 2: ProPress System Submittal Package - Viega - Columbia · PDF fileTest Pressure 600 PSI Max. ... iv. excessive water pressure, corrosive substances, ... ProPress System Submittal Package

DS-PP 0607 1 of 1

System Data Sheet

slooTgnisserPDIGDIR

ledo 0M 04-TC E-023 B-001

stlo vV 021 yrettaBv4.4 y1 rettaBv4.41

spm AA 2.5 A42 A42

thgieW )wajtuo/w .( sbl6.51 sbl5.01 sbl5.7

VIEGA • One Company... One Partner... Delivering System Solutions.301 N. Main, Floor 9 • Wichita, KS 67202 • Ph: 877-Viega-NA • Fax: 800-976-9817 • E-Mail: [email protected] • www.viega-na.com

System DescriptionProPress®, ProPress XL™ and ProPress XLC are safe, reliable, and economical copper pipe installation systems that use modern cold press connection technology for a wide assortment of more than 500 fittings in dimensions ranging from 1/2” to 4”.

ApplicationsTubing: K, L, and M hard copper tubing from 1/2” to 4” and soft copper tubing in1/2” to 1-1/4” diameters. All tubing must comply with the ASTM B88 standard. ProPress fittings are approved for installations in both above and below ground applications. Per code, local inspector approval must be obtained prior to installation below ground.

Operating Parameters:Operating Pressure 200 PSI Max.Test Pressure 600 PSI Max. Low Pressure Steam 15 PSI Max. Vacuum 29.2” Mercury Max. @ 68°FOperating Temperature 0°F - 250°F

Approved Applications:• Potable water• Hydronic heating (w/ Glycol)• Chilled water• Compressed Air (200 PSI Max.)• Non Medical Gases (140 PSI Max.)• Fire Sprinkler (175 PSI Max.)• Low Pressure Steam (15 PSI Max.)• Vacuum (29.2” Mercury Max. @ 68°F)

System Benefits• Fast and Easy to Use• Flameless• Permanent Connections• Wide Capacity from 1/2” to 4”• Large Selection of Fittings• Consistent Professional Appearance• Less Equipment Required• Environmentally Friendly Connection System• Versatility of Fittings and Tools for Variety of Applications

FittingsViega ProPress fittings are offered in 500+configurations including: Elbows, Couplings, Reducers, Tees, Reducing Tees, Threaded Adapters, Unions, Caps, and Flanges. All Threaded 1/2”- 2“ fittings are bronze.

Smart Connect™ (SC Feature)In ProPress 1/2”- 4” dimensions, the Smart Connect Feature assures leakage of liquids and/or gases from inside the system past the sealing element of an unpressed connection. The function of this feature is to provide the installer quick and easy identification of connec-tions which have not been pressed prior to putting the system into operation.

ToolsRIDGID offers three pressing tools for connecting ProPress fittings. • CT-400 Corded Tool (1/2” to 4”)• 320-E Battery powered Tool (1/2” to 4”)• 100-B Battery powered Tool (1/2” to 1”)• 1/2” to 4” fittings are pressed in 4-7 sec.

HistoryProPress has been used in Europe since the late 1980s and in the U.S. since the late 1990s for a variety of applica-tions. Backed by two plumbing leaders with over 175 years of combined excellence.

WarrantyViega ProPress products carry a 50-year warranty against defects in material and workmanship. The RIDGID Lifetime Warranty applies to tools, jaws and crimp rings from Ridge Tool Company.

Approvals and CertificatesNSF Internationalwww.nsf.org/business/search_listings/index.asp#mname (enter “Viega”)

IAPMOhttp://pld.iapmo.org/ (enter “Viega”)

ULhttp://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/gfilenbr.html (enter“ex6157”)

ABS(American Bureau of Shipping)http://www.eagle.org/typeapproval/contents.html (enter “Viega”)

CSA Internationalhttp://www.csa-international.org/product/(enter “Viega”)

INTERNATIONAL APPROVALS• Deutsch Verein des Gas-und Wasserfachese.V. (DVGW)• Lloyd’s Register (LLOYD’S)• Det Norske Veritas (DNV)• Registro Italiano Navale (RINA)• Bureau Veritas (BV)• KIWA

Compliant with• ICC International Plumbing Code• UPC Uniform Plumbing Code• PHCC National standard plumbing code• Florida Building Code, Volume IIPlumbing Code• NFPA 13,13D, and 13R

Contact your local Viega or RIDGID representative for details on local approvals

For more information on RIDGID products contact:Ridge Tool Company400 Clark Street, Elyria, Ohio 44036Demos, Literature: 800-769-7743Technical inquiries: 800-519-3456Availability: 888-743-4333Web: www.ridgid.com

Page 3: ProPress System Submittal Package - Viega - Columbia · PDF fileTest Pressure 600 PSI Max. ... iv. excessive water pressure, corrosive substances, ... ProPress System Submittal Package

Viega warrants that all Viega ProPress®Couplings (“Product”) shall be free from defectsin material or workmanship for a period of fifty(50) years from the date of installation of theProduct. Viega’s liability under this warranty islimited exclusively to the repair or replacement(at our option) of any Product that we find tocontain a defect in material or workmanship.Viega shall have no other liability for any otherloss or damage of any kind, including but notlimited to consequential damages, water damageor other damage to property, lost earnings orprofits, or business interruption.

Viega’s liability hereunder does not extendto any Product:a. not manufactured or sold by Viega;

b. used for any purpose other than authorizedby Viega;

c. not installed in accordance with applicableplumbing codes; or

d. damaged as a result of any of the following;

i. misuse, abuse or vandalism;

ii. natural disaster or Acts of God (includingwithout limitation flooding,windstorm, lightning, or earthquake);

iii. modifications, alterations or attachmentsto the Product not authorizedby Viega in writing;

iv. excessive water pressure, corrosivesubstances, or other damagingenvironment; or

v. freezing.

If a defect in our Product becomes apparentwithin the warranty period, Customer shallprovide written notification to Viega within thirty(30) days after such defect becomes or shouldbecome apparent. Viega shall have the option toinspect the Product at Customer’s premises or toauthorize return of the Product for inspection atViega’s facilities. No Product may be returnedwithout our written consent. Viega shall havesixty (60) business days following receipt ofnotice to determine whether the Product containsa defect in material or workmanship, and suchdetermination shall be final.

Viega’s liability hereunder is subjectto all of the following conditions:

1. the Product is installed by a licensedplumbing/mechnical contractor ortrained maintenance personnel inaccordance with all applicableinstallation instructions provided by oravailable from Viega;

2. the Product is not exposed totemperatures and/or pressures thatexceed the limitations andspecifications provided in theinstallation instructions or Productliterature;

3. the Product remains in its originallyinstalled location;

4. the Product is connected to functionalsupply line according to the authorizeduses for such products by Viega;

5. the Product shows no evidence oftampering, mishandling, neglect oraccidental damage;

6. the Product is installed in accordancewith applicable building and plumbingcode requirements; and

7. Customer fully complies with the claimprocedures set forth above.

THIS WARRANTY IS IN LIEU OF ALLOTHER WARRANTIES EXPRESS ORIMPLIED, INCLUDING WITHOUTLIMITATION IMPLIED WARRANTIES OFMERCHANTABILITY OR FITNESS. NOEMPLOYEE OF VIEGA, DISTRIBUTOR,AGENT, OR ANY OTHER PERSON ISAUTHORIZED TO AMEND THE TERMSOF THIS WARRANTY OR TOMAKE ANY OTHER WARRANTYON VIEGA’S BEHALF.

PROPRESS VIEGA LIMITED WARRANTY(COVERSPROPRESSFITTINGS)

Page 4: ProPress System Submittal Package - Viega - Columbia · PDF fileTest Pressure 600 PSI Max. ... iv. excessive water pressure, corrosive substances, ... ProPress System Submittal Package

789 Dixboro Road, Ann Arbor, Michigan 48105-9723 USA1-800-NSF-MARK 734-769-8010

www.nsf.org

FI20050414135936 J-00014536

NSF InternationalApril 14, 2005

This report shall not be reproduced, except in its entirety, without the written approval of NSF. This report does not represent NSF

Official NSF Listing, (www.nsf.org). The results relate only to those items tested. Certification or authorization to use the NSF Mark. Authorization to use the NSF Mark is limited to products appearing in the Company's

Page 1 of 5

TEST REPORT

Send To:VIEGA N.A., INC.PLUMBING AND HEATING SYSTEMS

GERMANY

ENNESTER WEG 9ATTENDORN 57439

Attn: MR. ANDREW GRANZOW

Thank you for having your product tested by NSF.

The enclosed report details the result of the testing performed on your product. Your program representative will

Reviewer:

be contacting you in the near future if there are any remaining issues concerning the status of this product.

Please do not hesitate to contact us if you have any immediate questions pertaining to your product.

CC:

Atabek Ciechanowski - Manager, Engineering Laboratory

Status: Pass

Sample Description:Test Type:

ProPress XL-CQQ - Qualification Testing

Plant:Customer:VIEGA GMBH & CO. KGPRODUCTION FACILITY ATTENDORNENNESTER WEG 9ATTENDORN 57439GERMANY

VIEGA N.A., INC.PLUMBING AND HEATING SYSTEMSENNESTER WEG 9ATTENDORN 57439GERMANY

Attn: MRS. FIONA HEINRICHSAttn: MR. ANDREW GRANZOW

PA Project: 227078

72320

72320 72322

130 - Mechanical Plumbing Products (including Section 9 of Standard 61) Program:MARK MAPILIProgram Rep:02 - EuropeRegion:

Page 5: ProPress System Submittal Package - Viega - Columbia · PDF fileTest Pressure 600 PSI Max. ... iv. excessive water pressure, corrosive substances, ... ProPress System Submittal Package

FI20050414135936 J-00014536This report shall not be reproduced, except in its entirety, without the written approval of NSF. This report does not represent NSF

Official NSF Listing, (www.nsf.org). The results relate only to those items tested. Certification or authorization to use the NSF Mark. Authorization to use the NSF Mark is limited to products appearing in the Company's

Page 2 of 5

Testing Parameter Result Units Entered On

Pressure:Duration:Temperature:Slippage:Required test pressure:Actual test pressure:Required test duration:Actual test duration:Required max. slippage:Actual max. slippage:Required leakage or damage:Actual leakage or damage:Unrestrained Pressure Test-73 degrees F

Pressure:Duration:Temperature:Slippage:Required test pressure:Actual test pressure:Required test duration:Actual test duration:Required max. slippage:Actual max. slippage:Required leakage or damage:Actual leakage or damage:Unrestrained Pressure Test-210 degrees F

Torque applied:Pressure:Duration:Temperature:Required torque:Actual torque:Required pressure:Actual pressure:Required duration:Actual duration:Evidence of cracking or slippage:Actual cracking or slippage:

6004

680.0146006004848

0.1570.014None

NoPass

60048208

0.0206006004848

0.1540.020None

NoPass

17740048681771774004004848

NoneNo

psihours

degrees Finches

psipsi

hourshoursinchesinches

psihours

degrees Finches

psipsi

hourshoursinchesinches

ft.*lbf.psi

hoursdegrees F

ft.*lbf.ft.*lbf.

psipsi

hourshours

Unrestrained Pressure Test - 73 degrees F

Unrestrained Pressure Test - 210 degrees F

Static Torsion Test

Engineering Lab

General Information

Standard: 0MP - MECHANICAL PLUMBING PRODUCTS PROGRAM

Sample Id: S-0000152314Description: ProPress XL-CSampled Date: 03/24/2005Received Date: 03/25/2005

Family Code AA

Performance Standard IAPMO PS-117

Trade Designation Viega ProPress

Page 6: ProPress System Submittal Package - Viega - Columbia · PDF fileTest Pressure 600 PSI Max. ... iv. excessive water pressure, corrosive substances, ... ProPress System Submittal Package

FI20050414135936 J-00014536This report shall not be reproduced, except in its entirety, without the written approval of NSF. This report does not represent NSF

Official NSF Listing, (www.nsf.org). The results relate only to those items tested. Certification or authorization to use the NSF Mark. Authorization to use the NSF Mark is limited to products appearing in the Company's

Page 3 of 5

Testing Parameter Result Units Entered On

Static Torsion Test

Load applied:Pressure:Duration:Temperature:Required load:Actual load:Required pressure:Actual pressure:Required duration:Actual duration:Evidence of leakage:Actual leakage:Bending Test

Initial vacuum:Final vacuum:Duration:Temperature:Required vacuum:Actual vacuum:Required test duration:Actual test duration:Required vacuum drop > 0.5 inch of Hg:Actual vacuum drop > 0.5 inch of Hg:Vacuum Test

Frequency:Initial pressure:Surge pressure:Cycles completed:Required cycles:Actual cycles:Required surge pressure:Actual surge pressure:Required leakage or damage:Actual leakage or damage:Water Hammer Test

Frequency:Deflection:Pressure:Duration:Required number of cycles:Actual number of cycles:Required pressure:Actual pressure:Required duration:Actual duration:

Pass

24040048682402404004004848

NoneNo

Pass

24.524.5

168

24.524.5

11

NoNo

Pass

0.536.5420.5100001000010000

400420.5None

NoPass

250.06540048

10000001000000

4004004848

lbs.psi

hoursdegrees F

lbs.lbs.psipsi

hourshours

inch of Hginch of Hg

hoursdegrees Finch of Hginch of Hg

hourshours

Hzpsipsi

cyclescyclescycles

psipsi

Hzinches

psihourscyclescycles

psipsi

hourshours

Bending Test

Vacuum Test

Water Hammer Test

Vibration Test

Engineering Lab ( Cont'd )

Sample Id: S-0000152314

Page 7: ProPress System Submittal Package - Viega - Columbia · PDF fileTest Pressure 600 PSI Max. ... iv. excessive water pressure, corrosive substances, ... ProPress System Submittal Package

FI20050414135936 J-00014536This report shall not be reproduced, except in its entirety, without the written approval of NSF. This report does not represent NSF

Official NSF Listing, (www.nsf.org). The results relate only to those items tested. Certification or authorization to use the NSF Mark. Authorization to use the NSF Mark is limited to products appearing in the Company's

Page 4 of 5

Testing Parameter Result Units Entered On

Evidence of leakage:Actual leakage:Vibration Test

Cold water cycle temperature:Hot water cycle temperature:Cold water pressure:Hot water pressure:Time at cold temperature:Time at hot temperature:Cycle change time:Required number of cycles:Actual number of cycles:Required leakage:Actual leakage:Spalling Test

Angle of torsion:Temperature:Pressure:Duration:Required number of cycles:Actual number of cycles:Required pressure:Actual pressure:Required duration:Actual duration:Evidence of leakage:Actual leakage:Dynamic Torsion Test

Angle of torsion:Temperature:Pressure:Duration:Required number of cycles:Actual number of cycles:Required pressure:Actual pressure:Required duration:Actual duration:Evidence of leakage:Actual leakage:Dynamic Torsion Test

NoneNo

Pass

6820814514515151.0

50005000None

NoPass

57340048

1000010000

4004004848

NoneNo

Pass

520840048

1000010000

4004004848

NoneNo

Pass

degrees Fdegrees F

psipsi

min.min.min.

cycles

degreedegrees F

psihours

psipsi

hourshours

degreedegrees F

psihours

psipsi

hourshours

Spalling Test

Dynamic Torsion Test

Dynamic Torsion Test

Engineering Lab ( Cont'd )

Sample Id: S-0000152314

Page 8: ProPress System Submittal Package - Viega - Columbia · PDF fileTest Pressure 600 PSI Max. ... iv. excessive water pressure, corrosive substances, ... ProPress System Submittal Package

FI20050414135936 Final_Std

J-00014536This report shall not be reproduced, except in its entirety, without the written approval of NSF. This report does not represent NSF

Official NSF Listing, (www.nsf.org). The results relate only to those items tested. Certification or authorization to use the NSF Mark. Authorization to use the NSF Mark is limited to products appearing in the Company's

*J-00014536* Page 5 of 5

References to Testing Procedures:

NSF Reference Parameter / Test Description---------------------------- --------------------------------------------------------------------------------------------------------------P1066P1067P1068P1069P1070P1071P1072P1073P1074

Unrestrained Pressure Test - 73 degrees FUnrestrained Pressure Test - 210 degrees FStatic Torsion TestBending TestVacuum TestWater Hammer TestVibration TestSpalling TestDynamic Torsion Test

Testing Laboratories:Id--------------

Address----------------------------------------

All work performed at: Witness TestingThe testing reported herein occurred atan offsite location and was witnessedby NSF International staff.

WT_TST

Page 9: ProPress System Submittal Package - Viega - Columbia · PDF fileTest Pressure 600 PSI Max. ... iv. excessive water pressure, corrosive substances, ... ProPress System Submittal Package
Page 10: ProPress System Submittal Package - Viega - Columbia · PDF fileTest Pressure 600 PSI Max. ... iv. excessive water pressure, corrosive substances, ... ProPress System Submittal Package
Page 11: ProPress System Submittal Package - Viega - Columbia · PDF fileTest Pressure 600 PSI Max. ... iv. excessive water pressure, corrosive substances, ... ProPress System Submittal Package
Page 12: ProPress System Submittal Package - Viega - Columbia · PDF fileTest Pressure 600 PSI Max. ... iv. excessive water pressure, corrosive substances, ... ProPress System Submittal Package
Page 13: ProPress System Submittal Package - Viega - Columbia · PDF fileTest Pressure 600 PSI Max. ... iv. excessive water pressure, corrosive substances, ... ProPress System Submittal Package
Page 14: ProPress System Submittal Package - Viega - Columbia · PDF fileTest Pressure 600 PSI Max. ... iv. excessive water pressure, corrosive substances, ... ProPress System Submittal Package

VIEGA • One Company... One Partner... Delivering System Solutions.301 N. Main, Floor 9 • Wichita, KS 67202 • Ph: 877-Viega-NA • Fax: 316-425-7618 • E-Mail: [email protected] • www.viega-na.com

Product InstructionsFor Types K, L and M Hard Copper Tubing in 1/2” to 2” and Soft Copper Tubing in 1/2” to 1-1/4”

PI-PP 0607 1 of 1

w/Smart Connect™ Feature

ProPress Insertion Depth Chart

Tube Size 1/2” 3/4” 1” 1-1/4” 1-1/2” 2”

Insertion Depth 3/4” 7/8” 7/8” 1” 1-7/16” 1-9/16”

Read and understand all instructions for installing ProPress fittings. Failure to follow allinstructions may result in extensive property damage, serious injury or death.

1. Cut copper tubing at right angles (using displacement type cutter or fine-toothed steel saw).2. Debur tubing on inside and outside to prevent cutting fitting seal.3. Check seal for correct fit. Do not use oils or lubricants. Use only ProPress Shiny Black EPDM or Dull Black FKM SealingElements.

4. While turning slightly, slide press fitting onto tubing to the fitting stop. Note: End of tubing must contact stop5. Mark insertion depth.6. Insert the appropriate jaw into the pressing tool and push in holding pin until it locks into place.7. Open the jaw and place at right angles on the fitting. Visually check insertion depth using mark on tubing.8. Start pressing process and hold the trigger until the jaw has engaged the fitting.9. After pressing, the jaw can be opened again.10. For applications requiring ProPress with FKM sealing elements, remove the factory installed EPDM sealing element and

replace with FKM sealing element.

Pressure Testing: Pressure testing is to be carried out in accordance with local codes. TheSmart Connect FeatureTM provides quick and easy identification of unpressed connectionsduring the pressure testing process. Unpressed connections are located by pressurizing thesystem with a maximum pressure range of 1/2-85 psi for gases and 15-85 psi for liquids. TheSC Feature is a special indentation in 1/2” to 2” dimensions located on the inside surface ofthe fitting near the sealing element. This indentation assures leakage of liquids and/or gasesfrom inside the system past the sealing element of an unpressed connection. The indentationis removed during the pressing process creating a leak-free, permanent connection.

1 2 3 4 5 6

7 8 9 10 11 12

Page 15: ProPress System Submittal Package - Viega - Columbia · PDF fileTest Pressure 600 PSI Max. ... iv. excessive water pressure, corrosive substances, ... ProPress System Submittal Package

VIEGA • One Company... One Partner... Delivering System Solutions.301 N. Main, Floor 9 • Wichita, KS 67202 • Ph: 877-Viega-NA • Fax: 316-425-7618 • E-Mail: [email protected] • www.viega-na.com

Product InstructionsCopper Fittings for Types K, L and M Hard Copper Tubing in 2-1/2” to 4”

PI-PP-XL-0607 1 of 1

XLw/Smart Connect™ Feature

Read, understand and follow all instructions for installing ProPress XL fittings. Failure tofollow all instructions may result in extensive property damage, serious injury or death.

1. Cut copper tubing at right angles using displacement type cutter or fine-toothed steel saw.2. Keep end of tubing a minimum of 4” away from the contact area of the vise to prevent possible damage to the tubing in thepress area.

3. Remove burr from inside and outside of tubing to prevent cutting sealing element.4. Mark proper insertion depth as indicated by the ProPress XL insertion depth chart. Improper insertion depth may result in animproper seal.

5. Check seal and grip ring for correct fit.6. While turning slightly, slide press fitting onto tubing to the marked depth. Do not use oils or lubricants.7. ProPress XL fitting connections must be performed with ProPress XL Rings and Actuator. Use of other ring set or actuator willresult in an improper connection. See Ridgid Operator’s Manual for proper tool instructions.

8. Open XL Ring and place at right angle on the fitting. XL Ring must be engaged on the fitting bead. Check insertion depth.9. With Actuator inserted into the tool, open the Actuator as shown.10. Place Actuator onto XL Ring and start pressing process. Hold the trigger until the Actuator has engaged the XL Ring. Keep

extremities and foreign objects away from XL Ring and Actuator during pressing operation to prevent injury or incompletepress.

11. Release Actuator from XL Ring and then remove the XL Ring from the fitting on completion of press. Remove elastic controlring from fitting indicating press has been performed.

12. For applications requiring ProPress XL with FKM sealing elements, remove the factory installed EPDM sealing element andreplace with FKM sealing element.

Pressure Testing: Pressure testing is to be carried out in accordance with local codes. ProPress XL alsoincludes the Smart Connect Feature providing quick and easy identification of unpressed connections duringthe pressure testing process. Unpressed connections are located by pressurizing the system with air or water.When testing with air the pressure range is 1/2 PSI to 85 PSI Maximum. When testing with water the pressurerange is 15 PSI to 85 PSI Maximum. The SC Feature is an integral part of the design of the fitting assuringleakage of liquids and/or gases from inside the system past the sealing element of an unpressed connection.The SC Feature is removed during the pressing process creating a leak-proof, permanent connection.

1 2 3 4 5 6

7 8 9 10 11 12

ProPress XL Insertion Depth Chart

Tube Size 2-1/2” 3” 4”

Insertion Depth 2-1/8” 2-1/8” 2-1/2”

Page 16: ProPress System Submittal Package - Viega - Columbia · PDF fileTest Pressure 600 PSI Max. ... iv. excessive water pressure, corrosive substances, ... ProPress System Submittal Package

VIEGA • One Company... One Partner... Delivering System Solutions.301 N. Main, Floor 9 • Wichita, KS 67202 • Ph: 877-Viega-NA • Fax: 316-425-7618 • E-Mail: [email protected] • www.viega-na.com

Product InstructionsCopper Fittings for Types K, L and M Hard Copper Tubing in 2-1/2” to 4”

PI-PP-XLC-0607 1 of 1

XL-Cw/Smart Connect™ Feature

Read, understand and follow all instructions for installing ProPress XL-C fittings. Failure tofollow all instructions may result in extensive property damage, serious injury or death.

1. Cut copper tubing at right angles using displacement type cutter or fine-toothed steel saw.2. Keep end of tubing a minimum of 4” away from the contact area of the vise to prevent possible damage to the tubing in thepress area.

3. Remove burr from inside and outside of tubing to prevent cutting sealing element.4. Mark proper insertion depth as indicated by the ProPress XL-C insertion depth chart. Improper insertion depth may result in animproper seal.

5. Check seal and grip ring for correct fit.6. Illustration demonstrates proper fit of grip ring, separation ring and sealing element. Use only ProPress Shiny Black EPDMsealing elements.

7. While turning slightly, slide press fitting onto tubing to the marked depth. Do not use oils or lubricants.8. ProPress XL-C fitting connections must be performed with ProPress XL-C Rings and V2 ACTUATOR. Use of ProPress XL Ringsand/or Actuator (for Bronze fittings) will result in an improper connection. See Ridgid Operator’s Manual for proper toolinstructions.

9. Open XL-C Ring and place at right angles on the fitting. XL-C Ring must be engaged on the fitting bead. Check insertion depth.10. With V2 ACTUATOR inserted into the tool, open the V2 ACTUATOR as shown and connect V2 ACTUATOR to the XL-C Ring.11. Place V2 ACTUATOR onto XL-C Ring and start pressing process. Hold the trigger until the Actuator has engaged the XL-C

Ring. Keep extremities and foreign objects away from XL-C Ring and V2 ACTUATOR during pressing operation to preventinjury or incomplete press.

12. Release V2 ACTUATOR from XL-C Ring and then remove the XL-C Ring from the fitting on completion of press. Remove elasticcontrol ring from fitting indicating press has been performed.

Pressure Testing: Pressure testing is to be carried out in accordance with local codes. ProPress XL-C alsoincludes the Smart Connect Feature providing quick and easy identification of unpressed connections duringthe pressure testing process. Unpressed connections are located by pressurizing the system with air or water.When testing with air the pressure range is 1/2 PSI to 85 PSI Maximum. When testing with water the pressurerange is 15 PSI to 85 PSI Maximum. The SC Feature is an integral part of the design of the fitting assuringleakage of liquids and/or gases from inside the system past the sealing element of an unpressed connection.The SC Feature is removed during the pressing process creating a leak-proof, permanent connection.

1 2 3 4 5 6

7 8 9 10 11 12

ProPress XL-C Insertion Depth Chart

Tube Size 2-1/2” 3” 4”

Insertion Depth 1-5/8” 1-7/8” 2-3/8”