PROTECTA ® FR PIPE WRAP INSTALLATION INSTRUCTIONS As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change product specifications without giving notice. All information contained in this document is given in good faith and is provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, are intended to be given as to the actual performance of the product mentioned or referred to herein and no liability whatsoever will be accepted for any loss, damage or injury arising from the use of the information given. Installation Instructions to ETA 14/0247 www.protecta.eu Polyseam Ltd 1 (7) 2014 8 22 Protecta ® FR Pipe Wrap is designed to maintain the fire resistance of fire separating walls and floors when these are breached by continuous plastic pipes or metal pipes with combustible insulation, and may be used in gypsum, masonry or concrete walls and concrete floors. Each pipe wrap consists of a graphite based reactive intumescent strip which reacts to heat and closes the opening left by the softening plastic pipe or pipe insulation in fire. The pipe wrap is installed completely around the pipes or insulation and secured with the self-adhesive tab. The annular space around the pipe wrap is sealed with Protecta ® EX Mortar or Protecta ® FR Board. Penetration type & max dimensions Minimum width and number of layers of pipe wrap Classification FLEXIBLE AND RIGID WALL CONSTRUCTIONS 100MM Ø110mm PVC-U & PVC-C pipe 50 x 3.6mm (2 layers) both sides E 120 U/C, C/C EI 90 U/C, C/C Ø125mm PVC-U & PVC-C pipe 50 x 5.4mm (3 layers) both sides E 120 U/C, C/C EI 90 U/C, C/C Ø160mm PVC-U & PVC-C pipe 50 x 7.2mm (4 layers) both sides E 120 U/C, C/C EI 90 U/C, C/C RIGID FLOOR CONSTRUCTIONS 150MM Ø110mm PVC-U & PVC-C pipe 75 x 1.8mm (1 layer), or 50 x 3.6mm (2 layers) soffit side EI 180 C/C Ø125mm PVC-U & PVC-C pipe 50 x 7.2mm (4 layers) soffit side EI 180 C/C Ø160mm PVC-U & PVC-C pipe 50 x 10.8mm (6 layers), or 75 x 5.4mm (3 layers) soffit side EI 180 C/C Please note: The minimum permitted separation between adjacent seals/apertures is 20cm. An aperture can include several services, and they may also be different. Services should be a minimum of 30mm from seal edges or other services so that the fire seals can be correctly fitted around each service. Services in floors require a minimum separation of 10cm from other services. The total amount of cross sections of services (including insulation) should not exceed 60% of the penetration area. Please see the Installation Instructions for the fire stopping system used with this product. Supporting construction: Flexible walls must have a minimum thickness of 100 mm and comprise steel studs lined on both faces with minimum 2 layers of 12.5 mm thick boards. The walls must also incorporate a full fill core insulation of stone wool (35kg/m 3 density). Rigid walls and floors must comprise concrete, aerated concrete or masonry, with a minimum density of 650 kg/m 3 . The service support must be classified in accordance with EN 13501-2 for the required fire resistance period. This Installation Instruction is based on the product’s European Technical Assessment, issued in accordance with regulation (EU) No 305/2011, on the basis of ETAG 026-2 and 3, edition 2011, used as European Assessment Document (EAD). 1. Fix a suitable pipe wrap around the service penetration and fasten with the tape as tightly as possible in order to prevent any excess opening between the pipe wrap and the service. 2. In floors, only one pipe wrap is required to be installed flush with the soffit so that the edge of the wrap is visible from the underside when back-filled. For walls it is normal to fit a wrap on both sides of the wall, again with the edge just visible. 3. Where wraps are installed in hollow core slabs or planks, the tubular voids should be filled with stone-wool insulation, normally the same thickness as the depth of the floor. 4. Once the wrap is securely installed, using a suitable shuttering board, cast around the pipe wrap with Protecta ® EX Mortar to the required depth. 5. The Protecta ® FR Pipe Wrap may be installed in a Protecta ® FR Board. Cut the hole around the penetrating service to be sealed slightly oversize so that the pipe wrap may be slid in to the middle of the board. Finally the end of the pipe wrap is sealed with Protecta ® FR Acrylic on both outer sides. 6. See the detail drawings of various installation methods on pages 2 to 7. GENERAL PRODUCT DESCRIPTION FIRE CLASSIFICATION - TABLE INSTALLATION TYPICAL DETAIL CERTIFICATION TYPICAL DETAIL

PROTECTA FR PIPE WRAP INSTALLATION …media.voog.com/0000/0041/4072/files/Protecta FR Pipe Wrap TDS.pdf · Detail Drawings Protecta® FR Pipe Wrap Installation Guide to ETA 14/0247

  • Upload
    ledang

  • View
    236

  • Download
    0

Embed Size (px)

Citation preview

PROTECTA® FR PIPE WRAP

INSTALLATION INSTRUCTIONS

As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change product specifications without giving notice. All information contained in this document is given in good faith and is provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, are intended to be given as to the actual performance of the product mentioned or referred to herein and no liability whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.

Installation Instructions to ETA 14/0247

www.protecta.euPolyseam Ltd

1 (7) 2014 8 22

Protecta® FR Pipe Wrap is designed to maintain the fire resistance of fire separating walls and floors when these are breached by continuous plastic pipes or metal pipes with combustible insulation, and may be used in gypsum, masonry or concrete walls and concrete floors. Each pipe wrap consists of a graphite based reactive intumescent strip which reacts to heat and closes the opening left by the softening plastic pipe or pipe insulation in fire. The pipe wrap is installed completely around the pipes or insulation and secured with the self-adhesive tab. The annular space around the pipe wrap is sealed with Protecta® EX Mortar or Protecta® FR Board.

Penetration type & max dimensions

Minimum width and number of layers of pipe wrap

Classification

FLEXIBLE AND RIGID WALL CONSTRUCTIONS ≥ 100MM ≤ Ø110mm PVC-U & PVC-C pipe

50 x 3.6mm (2 layers) both sides E 120 U/C, C/C EI 90 U/C, C/C

Ø125mm PVC-U & PVC-C pipe

50 x 5.4mm (3 layers) both sides E 120 U/C, C/C EI 90 U/C, C/C

Ø160mm PVC-U & PVC-C pipe

50 x 7.2mm (4 layers) both sides E 120 U/C, C/C EI 90 U/C, C/C

RIGID FLOOR CONSTRUCTIONS ≥ 150MM ≤ Ø110mm PVC-U & PVC-C pipe

75 x 1.8mm (1 layer), or 50 x 3.6mm (2 layers) soffit side

EI 180 C/C

Ø125mm PVC-U & PVC-C pipe

50 x 7.2mm (4 layers) soffit side EI 180 C/C

Ø160mm PVC-U & PVC-C pipe

50 x 10.8mm (6 layers), or 75 x 5.4mm (3 layers) soffit side

EI 180 C/C

Please note: The minimum permitted separation between adjacent seals/apertures is 20cm. An aperture can include several services, and they may also be different. Services should be a minimum of 30mm from seal edges or other services so that the fire seals can be correctly fitted around each service. Services in floors require a minimum separation of 10cm from other services. The total amount of cross sections of services (including insulation) should not exceed 60% of the penetration area. Please see the Installation Instructions for the fire stopping system used with this product. Supporting construction: Flexible walls must have a minimum thickness of 100 mm and comprise steel studs lined on both faces with minimum 2 layers of 12.5 mm thick boards. The walls must also incorporate a full fill core insulation of stone wool (35kg/m3 density). Rigid walls and floors must comprise concrete, aerated concrete or masonry, with a minimum density of 650 kg/m3. The service support must be classified in accordance with EN 13501-2 for the required fire resistance period.

This Installation Instruction is based on the product’s European Technical Assessment, issued in accordance with regulation (EU) No 305/2011, on the basis of ETAG 026-2 and 3, edition 2011, used as European Assessment Document (EAD).

1. Fix a suitable pipe wrap around the service penetration and

fasten with the tape as tightly as possible in order to prevent any excess opening between the pipe wrap and the service.

2. In floors, only one pipe wrap is required to be installed flush with the soffit so that the edge of the wrap is visible from the underside when back-filled. For walls it is normal to fit a wrap on both sides of the wall, again with the edge just visible.

3. Where wraps are installed in hollow core slabs or planks, the tubular voids should be filled with stone-wool insulation, normally the same thickness as the depth of the floor.

4. Once the wrap is securely installed, using a suitable shuttering board, cast around the pipe wrap with Protecta® EX Mortar to the required depth.

5. The Protecta® FR Pipe Wrap may be installed in a Protecta® FR Board. Cut the hole around the penetrating service to be sealed slightly oversize so that the pipe wrap may be slid in to the middle of the board. Finally the end of the pipe wrap is sealed with Protecta® FR Acrylic on both outer sides.

6. See the detail drawings of various installation methods on pages 2 to 7.

GENERAL PRODUCT DESCRIPTION

FIRE CLASSIFICATION - TABLE

INSTALLATION

TYPICAL DETAIL

CERTIFICATION

TYPICAL DETAIL

Detail Drawings Protecta® FR Pipe Wrap

Installation Guide to ETA 14/0247

www.protecta.euPolyseam Ltd tel.+44(0)1484421036

2 (7) 2014 8 22

As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change product specifications without giving notice. All information contained in this document is given in good faith and is provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, are intended to be given as to the actual performance of the product mentioned or referred to herein and no liability whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.

INSULATED STEEL PIPES FIRE RESISTANCE EI 180 (E 180)

RIGID FLOORS

INSULATED STEEL PIPES FIRE RESISTANCE EI 120 (E 180)

RIGID FLOORS

INSULATED STEEL PIPES FIRE RESISTANCE EI 45 (E 90)

RIGID FLOORS

INSULATED STEEL PIPES FIRE RESISTANCE EI 90 (E 90)

RIGID FLOORS

INSULATED STEEL PIPES FIRE RESISTANCE EI 120 (E180)

RIGID FLOORS

INSULATED COPPER PIPES FIRE RESISTANCE EI 180 (E 180)

RIGID FLOORS

Steel pipes ≤ Ø40mm

EX Mortar ≥ 100mm thick

Maximum aperture 1200 x 2400mm

Protecta Pipe Wrap 1 layer of 50mm wide fitted at soffit

13mm continuous elastomeric foam insulation

Steel pipes ≤ Ø165mm

EX Mortar ≥ 100mm thick

Maximum aperture 1200 x 2400mm

Protecta Pipe Wrap 1 layer of 50mm wide fitted at soffit

13-19mm continuous elastomeric foam insulation

Steel pipe ≤ Ø165mm

1 layer 60mm FR Board 2-SAll services and openings must be sealed with FR Acrylic both sides

Protecta Pipe Wrap 2 layers of 50mm wide

Maximum aperture 1200 x 2400mm

13mm continuous elastomeric foam insulation

Steel pipe ≤ Ø165mm

1 layer 60mm FR Board 2-SAll services and openings must be sealed with FR Acrylic both sides

Protecta Pipe Wrap 2 layers of 50mm wide

Maximum aperture 1200 x 2400mm

19mm continuous elastomeric foam insulation

Steel pipe ≤ Ø40mm

2 layers 60mm FR Board 2-SAll services and openings must be sealed with FR Acrylic both sides

Protecta Pipe Wrap 1 layer of 50mm wide

Maximum aperture 1200 x 2400mm

13mm continuous elastomeric foam insulation

Copper pipes≤ Ø12mm

EX Mortar ≥ 100mm thick

Maximum aperture 1200 x 2400mm

Protecta Pipe Wrap 2 layers of 50mm wide fitted at soffit

9mm continuous elastomeric foam insulation

Detail Drawings Protecta® FR Pipe Wrap

Installation Guide to ETA 14/0247

www.protecta.euPolyseam Ltd tel.+44(0)1484421036

3 (7) 2014 8 22

As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change product specifications without giving notice. All information contained in this document is given in good faith and is provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, are intended to be given as to the actual performance of the product mentioned or referred to herein and no liability whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.

INSULATED COPPER PIPES FIRE RESISTANCE EI 60 (E 180)

RIGID FLOORS

INSULATED COPPER PIPES FIRE RESISTANCE EI 60 (E 240)

RIGID FLOORS

INSULATED COPPER PIPES FIRE RESISTANCE EI 45 (E 180)

RIGID FLOORS

INSULATED ALUPEX COMPOSITE PIPES FIRE RESISTANCE EI 180 (E 180)

RIGID FLOORS

INSULATED ALUPEX COMPOSITE PIPES FIRE RESISTANCE EI 90 (E 180)

RIGID FLOORS

INSULATED ALUPEX COMPOSITE PIPES FIRE RESISTANCE EI 120 (E 120)

RIGID FLOORS

Copper pipes ≤ Ø54mm

EX Mortar ≥ 100mm thick

Maximum aperture 1200 x 2400mm

Protecta Pipe Wrap 2 layers of 50mm wide fitted at soffit

13-25mm continuous elastomeric foam insulation

Copper pipe ≤ Ø54mm

2 layers 60mm FR Board 1-SAll services and openings must be sealed with FR Acrylic both sides

Protecta Pipe Wrap 2 layers of 50mm wide

Maximum aperture 1200 x 2400mm

9-13mm continuous elastomeric foam insulation

Copper pipe ≤ Ø54mm

2 layers 60mm FR Board 1-SAll services and openings must be sealed with FR Acrylic both sides

Protecta Pipe Wrap 2 layers of 50mm wide

Maximum aperture 1200 x 2400mm

14-25mm continuous elastomeric foam insulation

Alupex pipes ≤ Ø16mm

EX Mortar ≥ 100mm thick

Maximum aperture 1200 x 2400mm

Protecta Pipe Wrap 2 layers of 50mm wide fitted at soffit

9mm continuous elastomeric foam insulation

Alupex pipes ≤ Ø75mm

EX Mortar ≥ 100mm thick

Maximum aperture 1200 x 2400mm

Protecta Pipe Wrap 2 layers of 50mm wide fitted at soffit

13-25mm continuous elastomeric foam insulation

Alupex pipe ≤ Ø75mm

2 layers 60mm FR Board 1-SAll services and openings must be sealed with FR Acrylic both sides

Protecta Pipe Wrap 2 layers of 50mm wide

Maximum aperture 1200 x 2400mm

9mm continuous elastomeric foam insulation

Detail Drawings Protecta® FR Pipe Wrap

Installation Guide to ETA 14/0247

www.protecta.euPolyseam Ltd tel.+44(0)1484421036

4 (7) 2014 8 22

As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change product specifications without giving notice. All information contained in this document is given in good faith and is provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, are intended to be given as to the actual performance of the product mentioned or referred to herein and no liability whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.

INSULATED ALUPEX COMPOSITE PIPES FIRE RESISTANCE EI 45 (E 60)

RIGID FLOORS

PLASTIC PIPES FIRE RESISTANCE EI 90 (E 90)

RIGID FLOORS

PLASTIC PIPES FIRE RESISTANCE EI 60-240

RIGID FLOORS

INSULATED STEEL PIPES FIRE RESISTANCE EI 240 (E 240)

MASONRY OR CONCRETE - WALLS

INSULATED STEEL PIPES FIRE RESISTANCE EI 60 (E 180)

MASONRY OR CONCRETE - WALLS

Alupex pipe ≤ Ø75mm

2 layers 60mm FR Board 1-SAll services and openings must be sealed with FR Acrylic both sides

Protecta Pipe Wrap 2 layers of 50mm wide

Maximum aperture 1200 x 2400mm

13-25mm continuous elastomeric foam insulation

PVC-U plastic pipe ≤ Ø110mm

1 layer 60mm FR Board 2-SAll services and openings must be sealed with FR Acrylic both sides Protecta Pipe Wrap

2 layers of 50mm wide

Maximum aperture 1200 x 2400mm

Services Wrap Maximum aperture

Classification

≤ Ø75mm PP 50 x 3.6mm (2 layers) 300x300mm EI 240 C/C ≤ Ø75mm PP 50 x 3.6mm (2 layers) 1200x2400mm EI 180 C/C ≤ Ø110mm PE, ABS & SAN+PVC 50 x 1.8mm (1 layer) 1200x2400mm EI 60 C/C ≤ Ø110mm PVC-U & PVC-C 75 x 1.8mm (1 layer) 1200x2400mm EI 180 C/C ≤ Ø110mm PVC-U & PVC-C 50 x 3.6mm (2 layers) 200x200mm EI 240 C/C ≤ Ø110mm PVC-U & PVC-C 50 x 3.6mm (2 layers) 1200x2400mm EI 180 C/C ≤ Ø125mm PE, ABS & SAN+PVC 75 x 3.6mm (2 layers) 1200x2400mm EI 180 C/C Ø125mm PVC-U & PVC-C 50 x 7.2mm (4 layers) 300x300mm EI 240 C/C Ø125mm PVC-U & PVC-C 50 x 7.2mm (4 layers) 1200x2400mm EI 180 C/C Ø160mm PE, ABS & SAN+PVC 75 x 7.2mm (4 layers) 1200x2400mm EI 180 C/C Ø160mm PVC-U & PVC-C 50 x 10.8mm (6 layers) 300x300mm EI 240 C/C Ø160mm PVC-U & PVC-C 50 x 10.8mm (6 layers) 1200x2400mm EI 180 C/C Ø160mm PVC-U & PVC-C 75 x 7.2mm (4 layers) 300x300mm EI 240 C/C Ø160mm PVC-U & PVC-C 75 x 5.4mm (3 layers) 1200x2400mm EI 180 C/C Ø200-250mm PE, ABS & SAN+PVC 75 x 12.6mm (7 layers) 1200x2400mm EI 180 C/C

Protecta FR Pipe Wrap to the bottom of the seal

Plastic pipe

Protecta EX Mortar ≥ 100mm thick

Steel pipes ≤ Ø40mm

13mm continuous elastomeric foam insulation

Maximum aperture 2400mm wide and 1200mm high

Protecta Pipe Wrap 2 layers of 50mm wide fitted central

EX Mortar ≥ 100mm thick

Steel pipes ≤ Ø165mm

13-25mm continuouselastomeric foam insulation

Maximum aperture 2400mm wide and 1200mm high

Protecta Pipe Wrap 2 layers of 50mm wide fitted central

EX Mortar ≥ 100mm thick

Detail Drawings Protecta® FR Pipe Wrap

Installation Guide to ETA 14/0247

www.protecta.euPolyseam Ltd tel.+44(0)1484421036

5 (7) 2014 8 22

As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change product specifications without giving notice. All information contained in this document is given in good faith and is provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, are intended to be given as to the actual performance of the product mentioned or referred to herein and no liability whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.

INSULATED STEEL PIPES FIRE RESISTANCE EI 45 (E 120)

MASONRY OR CONCRETE - WALLS

PLASTIC PIPES FIRE RESISTANCE EI 120 (E 120)

MASONRY OR CONCRETE - WALLS

INSULATED STEEL PIPES FIRE RESISTANCE EI 120 (E 120)

GYPSUM, MASONRY OR CONCRETE - WALLS

INSULATED STEEL PIPES FIRE RESISTANCE EI 60 (E 120)

GYPSUM, MASONRY OR CONCRETE - WALLS

INSULATED STEEL PIPES FIRE RESISTANCE EI 60 (E 120)

GYPSUM, MASONRY OR CONCRETE - WALLS

INSULATED STEEL PIPES FIRE RESISTANCE EI 120 (E 120)

GYPSUM, MASONRY OR CONCRETE - WALLS

Steel pipe ≤ Ø165mm

1 layer 60mm FR Board 2-S

9-25mm continuous elastomeric foam insulation

All services and openings must be sealed with FR Acrylic both sides

Maximum aperture 2400mm wide and 1200mm high

Protecta Pipe Wrap 1 layer of 50mm wide

PVC-U pipesØ315mm

Maximum aperture 2400mm wide and 1200mm high

Protecta Pipe Wrap 10 layers of 75mm wide fitted central

EX Mortar ≥ 100mm thick

Steel pipes ≤ Ø40mm

13mm continuous elastomeric foam insulation

Maximum aperture 2400mm wide and 1200mm high

Protecta Pipe Wrap 1 layer of 50mm wide fitted to both faces

EX Mortar ≥ 25mm thick on both sides 50mm stone wool

shutter ≥ 150kg/m3

Steel pipes ≤ Ø165mm

13mm continuous elastomeric foam insulation

Maximum aperture 2400mm wide and 1200mm high

Protecta Pipe Wrap 2 layers of 50mm wide fitted to both faces

EX Mortar ≥ 25mm thick on both sides 50mm stone wool

shutter ≥ 150kg/m3

Steel pipes ≤ Ø165mm

13-32mm continuous elastomeric foam insulation

Maximum aperture 2400mm wide and 1200mm high

Protecta Pipe Wrap 2 layers of 50mm wide fitted to both faces

EX Mortar ≥ 50mm thick on both sides

Steel pipe ≤ Ø40mm

13mm continuous elastomeric foam insulation

2 layers 50mm FR Board 1-S

All services or openings must be sealed with FR Acrylic both sides

Protecta Pipe Wraps 1 layer of 50mm wide middle or both sides

Maximum aperture 2400mm wide and 1200mm high

Detail Drawings Protecta® FR Pipe Wrap

Installation Guide to ETA 14/0247

www.protecta.euPolyseam Ltd tel.+44(0)1484421036

6 (7) 2014 8 22

As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change product specifications without giving notice. All information contained in this document is given in good faith and is provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, are intended to be given as to the actual performance of the product mentioned or referred to herein and no liability whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.

INSULATED STEEL PIPES FIRE RESISTANCE EI 60 (E 120)

GYPSUM, MASONRY OR CONCRETE - WALLS

INSULATED COPPER PIPES FIRE RESISTANCE EI 120 (E 120)

GYPSUM, MASONRY OR CONCRETE - WALLS

INSULATED COPPER PIPES FIRE RESISTANCE EI 120 (E 120)

GYPSUM, MASONRY OR CONCRETE - WALLS

INSULATED COPPER PIPES FIRE RESISTANCE EI 90 (E 120)

GYPSUM, MASONRY OR CONCRETE - WALLS

INSULATED COPPER PIPES FIRE RESISTANCE EI 60 (E 120)

GYPSUM, MASONRY OR CONCRETE - WALLS

INSULATED ALUPEX COMPOSITE PIPES FIRE RESISTANCE EI 120 (E 120)

GYPSUM, MASONRY OR CONCRETE - WALLS

Steel pipe ≤ Ø165mm

13-32mm continuous elastomeric foam insulation

2 layers 50mm FR Board 1-S

All services or openings must be sealed with FR Acrylic both sides

Protecta Pipe Wraps 2 layers of 50mm wide both sides

Maximum aperture 2400mm wide and 1200mm high

Copper pipe ≤ Ø54mm

9-25mm continuous elastomeric foam insulation

Maximum aperture 2400mm wide and 1200mm high

Protecta Pipe Wrap 2 layers of 50mm wide fitted to both faces

EX Mortar ≥ 25mm thick on both sides 50mm stone wool

shutter ≥ 150kg/m3

Copper pipe ≤ Ø12mm

9mm continuous elastomeric foam insulation

2 layers 50mm FR Board 1-S

All services or openings must be sealed with FR Acrylic both sides

Protecta Pipe Wraps 2 layers of 50mm wide both sides

Maximum aperture 2400mm wide and 1200mm high

Copper pipe ≤ Ø54mm

9-13mm continuous elastomeric foam insulation

2 layers 50mm FR Board 1-S

All services or openings must be sealed with FR Acrylic both sides

Protecta Pipe Wraps 2 layers of 50mm wide both sides

Maximum aperture 2400mm wide and 1200mm high

Copper pipe ≤ Ø54mm

14-25mm continuous elastomeric foam insulation

2 layers 50mm FR Board 1-S

All services or openings must be sealed with FR Acrylic both sides

Protecta Pipe Wraps 2 layers of 50mm wide both sides

Maximum aperture 2400mm wide and 1200mm high

Alupex pipe ≤ Ø75mm

9-25mm continuous elastomeric foam insulation

Maximum aperture 2400mm wide and 1200mm high

Protecta Pipe Wrap 2 layers of 50mm wide fitted to both faces

EX Mortar ≥ 25mm thick on both sides 50mm stone wool

shutter ≥ 150kg/m3

Detail Drawings Protecta® FR Pipe Wrap

Installation Guide to ETA 14/0247

www.protecta.euPolyseam Ltd tel.+44(0)1484421036

7 (7) 2014 8 22

As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change product specifications without giving notice. All information contained in this document is given in good faith and is provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, are intended to be given as to the actual performance of the product mentioned or referred to herein and no liability whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.

INSULATED ALUPEX COMPOSITE PIPES FIRE RESISTANCE EI 120 (E 120)

GYPSUM, MASONRY OR CONCRETE - WALLS

PLASTIC PIPES FIRE RESISTANCE EI 60-120

GYPSUM, MASONRY OR CONCRETE - WALLS

PLASTIC PIPES FIRE RESISTANCE EI 90-120

GYPSUM, MASONRY OR CONCRETE - WALLS

Alupex pipe ≤ Ø75mm

9-25mm continuous elastomeric foam insulation

2 layers 50mm FR Board 1-S

All services or openings must be sealed with FR Acrylic both sides

Protecta Pipe Wraps 2 layers of 50mm wide both sides

Maximum aperture 2400mm wide and 1200mm high

Protecta Pipe Wraps to both sides

Plastic pipe

Services Wrap Classification ≤ Ø40mm PVC-U & PVC-C 50 x 1.8mm (1 layer) E 120 U/C, C/U & EI 60 U/C, C/C ≤ Ø40mm PE, ABS & SAN+PVC 50 x 1.8mm (1 layer) EI 120 U/C, C/C ≤ Ø40mm PP 50 x 1.8mm (1 layer) EI 120 U/C, C/C ≤ 110mm PVC-U & PVC-C 50 x 3.6mm (2 layers) E 120 U/C, C/C & EI 90 U/C, C/C Ø41-110mm PE, ABS & SAN+PVC 50 x 3.6mm (2 layers) EI 60 U/C, C/C Ø41-110mm PP 50 x 3.6mm (2 layers) E 120 U/C, C/C & EI 90 U/C, C/C ≤ Ø125mm PVC-U & PVC-C 50 x 5.4mm (3 layers) EI 120 U/C, C/C ≤ Ø125mm PE, ABS & SAN+PVC 50 x 5.4mm (3 layers) EI 120 U/C, C/C Ø125mm PP 50 x 5.4mm (3 layers) E 120 U/C, C/C & EI 90 U/C, C/C Ø160mm PVC-U & PVC-C 50 x 7.2mm (4 layers) EI 60 U/C, C/C Ø160mm PE, ABS & SAN+PVC 50 x 7.2mm (4 layers) E 120 U/C, C/C & EI 90 U/C, C/C Ø160mm PP 50 x 7.2mm (4 layers) E 120 U/C, C/C & EI 60 U/C, C/C

Maximum aperture 2400mm wide and 1200mm high

2 layers 50mm FR Board 1-S

Protecta Pipe Wraps to both sides

Plastic pipe

All services or openings must be sealed with FR Acrylic both sides

Services Wrap Classification ≤ Ø40mm PVC-U & PVC-C 50 x 1.8mm (1 layer) EI 120 U/U, C/U, U/C, C/C ≤ Ø40mm PE, ABS & SAN+PVC 50 x 1.8mm (1 layer) EI 120 U/U, C/U, U/C, C/C ≤ Ø40mm PP 50 x 1.8mm (1 layer) EI 120 U/U, C/U, U/C, C/C Ø41-110mm PVC-U & PVC-C 50 x 3.6mm (2 layers) E 120 U/C, C/C & EI 90 U/C, C/C Ø41-110mm PE, ABS & SAN+PVC 50 x 3.6mm (2 layers) E 120 U/C, C/C & EI 90 U/C, C/C Ø41-110mm PP 50 x 3.6mm (2 layers) EI 90 U/U, C/U, U/C, C/C Ø125mm PVC-U & PVC-C 50 x 5.4mm (3 layers) E 120 U/C, C/C & EI 90 U/C, C/C Ø125mm PE, ABS & SAN+PVC 50 x 5.4mm (3 layers) E 120 U/C, C/C & EI 90 U/C, C/C Ø125mm PP 50 x 5.4mm (3 layers) E 120 U/C, C/C & EI 90 U/C, C/C Ø160mm PVC-U & PVC-C 50 x 7.2mm (4 layers) E 120 U/C, C/C & EI 90 U/C, C/C Ø160mm PE, ABS & SAN+PVC 50 x 7.2mm (4 layers) E 120 U/C, C/C & EI 90 U/C, C/C Ø160mm PP 50 x 7.2mm (4 layers) E 120 U/C, C/C & EI 90 U/C, C/C

Maximum aperture 2400mm wide and 1200mm high

EX Mortar ≥ 25mm thick on both sides of 50mm stone wool shutter ≥ 150kg/m3