© PHOENIX CONTACT - 12/2006 102858_02_en INTERFACE PSR-SCP- 24DC/SDC4/2X1/B PSR-SPP- 24DC/SDC4/2X1/B Data Sheet Description The PSR-...- 24DC/SDC4/2X1/B safety relay can be used in safety circuits according to DIN EN 60204-1/VDE 0113-1 and EN 954-1. Control is implemented via single or two-channel switches with N/O/N/C or N/C/N/C contacts (mechanical or elec- tronic) or via light grids. The device has an interface for the T-BUS DIN rail connector. This interface can be used for single-channel control and monitoring of extension units. For this function, a T-BUS connector with switchable con- tacts is required. Depending on the external wiring, the maximum safety cat- egory that can be achieved is safety category 2 or 4. The device has two enable current paths and a 24 V alarm output (N/O contact function) with stop category 0 accord- ing to EN 60204-1/VDE 0113-1. Observe the safety instructions on page 4. Make sure you always use the latest documentation. It can be downloaded at www.download.phoenixcontact.com . A conversion table is available on the Internet at http://www.download.phoenixcontact.com/general/7000_en_00.pdf. This data sheet is valid for all products listed on the following page: Safety Relay for Emergency Stop and Safety Door Circuits

PSR-SCP- 24DC/SDC4/2X1/B PSR-SPP- 24DC/SDC4/2X1/B · PSR-...- 24DC/SDC4/2X1/B 102858en_02_ PHOENIX CONTACT 2 Ordering Data Technical Data Safety Relays Description Type Order No

  • Upload
    others

  • View
    35

  • Download
    0

Embed Size (px)

Citation preview

Page 1: PSR-SCP- 24DC/SDC4/2X1/B PSR-SPP- 24DC/SDC4/2X1/B · PSR-...- 24DC/SDC4/2X1/B 102858en_02_ PHOENIX CONTACT 2 Ordering Data Technical Data Safety Relays Description Type Order No

© PHOENIX CONTACT - 12/2006102858_02_en

INTERFACE

PSR-SCP- 24DC/SDC4/2X1/BPSR-SPP- 24DC/SDC4/2X1/B

Data Sheet

DescriptionThe PSR-...- 24DC/SDC4/2X1/B safety relay can be used in safety circuits according to DIN EN 60204-1/VDE 0113-1 and EN 954-1.

Control is implemented via single or two-channel switches with N/O/N/C or N/C/N/C contacts (mechanical or elec-tronic) or via light grids. The device has an interface for the T-BUS DIN rail connector. This interface can be used for single-channel control and monitoring of extension units. For this function, a T-BUS connector with switchable con-tacts is required.

Depending on the external wiring, the maximum safety cat-egory that can be achieved is safety category 2 or 4.

The device has two enable current paths and a 24 V alarm output (N/O contact function) with stop category 0 accord-ing to EN 60204-1/VDE 0113-1.

Observe the safety instructions on page 4.

Make sure you always use the latest documentation. It can be downloaded at www.download.phoenixcontact.com.

A conversion table is available on the Internet at http://www.download.phoenixcontact.com/general/7000_en_00.pdf.

This data sheet is valid for all products listed on the following page:

Safety Relay for Emergency Stop and Safety Door Circuits

Page 2: PSR-SCP- 24DC/SDC4/2X1/B PSR-SPP- 24DC/SDC4/2X1/B · PSR-...- 24DC/SDC4/2X1/B 102858en_02_ PHOENIX CONTACT 2 Ordering Data Technical Data Safety Relays Description Type Order No

PSR-...- 24DC/SDC4/2X1/B

102858en_02_ PHOENIX CONTACT 2

Ordering Data

Technical Data

Safety RelaysDescription Type Order No. Pcs./Pkt.Safety relay for emergency stop and safety door circuits, with screw connection

PSR-SCP- 24DC/SDC4/2X1/B 2981486 1

Safety relay for emergency stop and safety door circuits, with spring-cage connection

PSR-SPP- 24DC/SDC4/2X1/B 2981499 1

AccessoriesDescription Type Order No. Pcs./Pkt.DIN rail connector, yellow, for PSR applications PSR-TBUS 2890425 50Dummy plug PSR-TBUS-TP 2981716 50

DocumentationDescription Type Order No. Pcs./Pkt.Application manual for PSR safety relays UM EN SAFETY RELAY APPLICATION 2888712 1

Input DataNominal input voltage UN 24 V DCPermissible range 0.85 - 1.1 x UN

Typical current consumption at UN 70 mATypical response time

Monitored/manual startAutomatic start

20 ms150 ms

Typical release time 10 msSimultaneity between channel 1 and channel 2 when using the restart inhibit in the event of a mains failure

3 seconds, approximately

Status indicators Green LED

Alarm Output Y30Switching voltage 24 V DCLimiting continuous current 100 mA

Output Data Contact type 2 enable current pathsContact material Silver tin oxide (AgSnO2)Maximum switching voltage 250 V AC/DCMinimum switching voltage 15 V AC/DCLimiting continuous current (N/O contact) 6 AMaximum inrush current (N/O contact) 6 AMinimum switching current 25 mAMaximum shutdown power

24 V DC48 V DC

110 V DC220 V DC250 V AC

Ohmic load τ = 0 ms144 W288 W77 W88 W1500 VA

Inductive load τ = 40 ms48 W40 W35 W33 W

Minimum switching power 0.4 WMechanical service life 107 cycles, approximately

Page 3: PSR-SCP- 24DC/SDC4/2X1/B PSR-SPP- 24DC/SDC4/2X1/B · PSR-...- 24DC/SDC4/2X1/B 102858en_02_ PHOENIX CONTACT 2 Ordering Data Technical Data Safety Relays Description Type Order No

PSR-...- 24DC/SDC4/2X1/B

102858en_02_ PHOENIX CONTACT 3

Switching capacity according to DIN EN 60947-5-1/VDE 0660-200 Cycles DC13 AC15360/h: 24 V: 6 A –

230 V: – 5 A3600/h: 24 V: 3 A –

230 V: – 3 AShort-circuit protection of the output circuits, external NEOZED 10 A gL/gG

Output Data (Continued)

General DataPermissible ambient operating temperature -20°C to +55°CNominal operating mode 100% operating factorDegree of protection according to VDE 0470-1

HousingConnection terminal blocksInstallation location

IP20IP20IP54, minimum

Mounting position AnyAir and creepage distances between circuits

Basic insulation According to DIN EN 50178:1998-04 1

Impulse voltage withstand level 4 kV 1

Pollution degree 2Surge voltage category IIIDimensions (W x H x D)

PSR-SCP- 24DC/SDC4/2X1/BPSR-SPP- 24DC/SDC4/2X1/B

22.5 mm x 99 mm x 114.5 mm22.5 mm x 112 mm x 114.5 mm

Conductor cross sectionPSR-SCP- 24DC/SDC4/2X1/BPSR-SPP- 24DC/SDC4/2X1/B

0.2 mm2 ... 2.5 mm2

0.2 mm2 ... 1.5 mm2

Housing material Polyamide PA, not reinforced1 Safe isolation, reinforced insulation, and 6 kV between the input circuit/N/C contacts and the enable contact current paths.

Tests/ApprovalsBG/GS

UL applied for

Page 4: PSR-SCP- 24DC/SDC4/2X1/B PSR-SPP- 24DC/SDC4/2X1/B · PSR-...- 24DC/SDC4/2X1/B 102858en_02_ PHOENIX CONTACT 2 Ordering Data Technical Data Safety Relays Description Type Order No

PSR-...- 24DC/SDC4/2X1/B

102858en_02_ PHOENIX CONTACT 4

Safety Instructions

– During operation, parts of electrical switching devices carry hazardous voltages.– Before working on the device, disconnect the power.– Please observe the safety regulations of electrical engineering and industrial safety and liability

associations.Disregarding these safety regulations may result in death, serious personal injury or damage to equipment.

– Startup, assembly, modifications, and upgrades may only be carried out by a skilled electrical engineer.

– For emergency stop applications, the machine must be prevented from restarting automatically by a higher-level control system.

– Protective covers must not be removed when operating electrical switching devices.

– In the event of an error, replace the device immediately.– Repairs, especially if the housing must be opened, may only be carried out by the manufacturer or

authorized persons. Otherwise the warranty is invalidated.

When operating relay modules the operator must meet the requirements for noise emission for electrical and electronic equipment (EN 61000-6-4) on the contact side and, if required, take appropriate measures.

Page 5: PSR-SCP- 24DC/SDC4/2X1/B PSR-SPP- 24DC/SDC4/2X1/B · PSR-...- 24DC/SDC4/2X1/B 102858en_02_ PHOENIX CONTACT 2 Ordering Data Technical Data Safety Relays Description Type Order No

PSR-...- 24DC/SDC4/2X1/B

102858en_02_ PHOENIX CONTACT 5

Structure

Figure 1 Structure

1 Metal lock for mounting on the DIN rail2 Plug-in COMBICON screw terminal blocks3 Plug-in COMBICON spring-cage terminal blocks4 13-14, 23-24: Enable current paths5 S33, S34, S35: Start circuit (activating circuit)6 Y1: Activating circuit7 A1, A2: Supply voltage connection8 Y30: 24 V alarm output9 S10, S11, S12, S13: Input circuits

Block Diagram

Figure 2 Block diagram

2324

1314

2324

S34 S33 S35Y1

A1 Y30 S22A2

S11 S10 S12 S13

PS

R-S

PP

-24D

C/S

DC

4/2

X1/B

Ord

er

No

.:2

981

49

9

AP

PR

OV

AL

Seria

lN

o.

13

23

14

24

S34

24

S11

S12S

13

Y30

S22

A2

A1

S10

13

S35

23 Y

1

14

S33

Pow

er

IN1IN

2K1K

2

PS

R-S

DC

4

2324

1314

S35Y1

S34 S33

PS

R-S

CP

-24D

C/S

DC

4/2

X1/B

Ord

er

No

.:2

98

14

86

AP

PR

OV

AL

Seria

lN

o.

13

23

14

24

S34

24

S11

S12S

13

Y30

S22

A2

A1

S10

13

S35

23 Y

1

14

S33

Pow

er

IN1IN

2K1K

2

PS

R-S

DC

4

1

3

1

PSR-SCP- 24DC/SDC4/2X1/B PSR-SPP- 24DC/SDC4/2X1/B

2

6

4

8

9

75 6

4

8

9

75

S12

Y3

0

K1

IN2

IN1

K2

14

13

A1

T-B

US

T-B

US

T-BUSK1/K2

T-B

US

T-B

US

A2

24VDC

POWER24VDC

24

23

S11

Y1

S33

S34

S3

5

S1

0

S1

3

S2

2

+24V

RESET&

FEEDBACK

LOGIC

Page 6: PSR-SCP- 24DC/SDC4/2X1/B PSR-SPP- 24DC/SDC4/2X1/B · PSR-...- 24DC/SDC4/2X1/B 102858en_02_ PHOENIX CONTACT 2 Ordering Data Technical Data Safety Relays Description Type Order No

PSR-...- 24DC/SDC4/2X1/B

102858en_02_ PHOENIX CONTACT 6

FunctionWhen the operating voltage (24 V DC) is applied at A1 and A2, the "Power" LED lights up. Depending on the two N/C contacts connected, e.g., for the emergency stop button, the positive potential is at S11 and the negative potential at A2.

There must be a flow of current via contacts S33 and S34 (activating circuit) in order to activate the module. Contacts S33, Y1, and S35 must be jumpered for automatic activa-tion. In this state, relays K1 and K2 are excited.

If one of the emergency stop N/C contacts opens, the re-lays drop and cannot be switched on again. They can only be switched back on when both N/C contacts are open.

In the event of a cross circuit between terminal blocks S11 and A2, this is detected and the relays drop. Operation without cross-circuit detection is also possible.

For additional connection examples, see page 7.

Connection Notes

When using T-BUS DIN rail connectors, connect together the required number of T-BUS connectors and push them onto the DIN rail. When attaching the safety relay to the DIN rail, ensure that it is aligned correctly with the T-BUS connector (see Figure 3).

Figure 3 Using the T-BUS DIN rail connector

– For PSR applications, only yellow PSR-TBUS connectors (Order No. 2890425) may be used. Con-nection with another T-BUS is not permitted.

– Devices may only be mounted on/removed from the T-BUS when the power is switched off.– A T-BUS unit can contain a basic device (PSR-...-SDC...) and a maximum of 10 extension units

(PSR-UR...). Extension units must be mounted to the right of the basic device.– The feedback circuit must be closed at the last extension unit (on the right) by a cable jumper or

by the PSR-TBUS-TP dummy plug (Order No. 2981716).– The voltage supply can be provided at any PSR device or using a system power supply via the

T-BUS.

��

DPSR-TBUS

3

Page 7: PSR-SCP- 24DC/SDC4/2X1/B PSR-SPP- 24DC/SDC4/2X1/B · PSR-...- 24DC/SDC4/2X1/B 102858en_02_ PHOENIX CONTACT 2 Ordering Data Technical Data Safety Relays Description Type Order No

PSR-...- 24DC/SDC4/2X1/B

102858en_02_ PHOENIX CONTACT 7

In order to comply with UL approval, use copper cables that are designed for operating temperatures > 75°C.

For reliable and safe-to-touch contacts, strip the cable ends as follows:

Figure 4 PSR-SCP- 24DC/SDC4/2X1/B Figure 5 PSR-SPP- 24DC/SDC4/2X1/B

Connection Examples

Circuits

Figure 6 Two-channel emergency stop circuit (2 N/C contacts) with cross-circuit detection

– Manual activation (monitored reset button at S33-S34)– Automatic activation (jumper at Y1-S33-S35)– Suitable up to safety category 4

7 mm

2324

1314

S35Y1

S34 S33

24

S35

23 Y

1

14

3

8 mm

2324

1314

2324

S34 S33 S35Y1

24

S35

23 Y

1

14

3

102858B001

+24 V DC

0 V

EM

ER

GE

NC

YS

TO

P

A1 S33 S34 S35

A2

-K2

S22 S10 S12S11

Y1

2313

13 23

14 24

14 24

PSR-SDC4

S13

Re

se

t

... TBUS ...

... TBUS ...

Y30

Page 8: PSR-SCP- 24DC/SDC4/2X1/B PSR-SPP- 24DC/SDC4/2X1/B · PSR-...- 24DC/SDC4/2X1/B 102858en_02_ PHOENIX CONTACT 2 Ordering Data Technical Data Safety Relays Description Type Order No

PSR-...- 24DC/SDC4/2X1/B

102858en_02_ PHOENIX CONTACT 8

Figure 7 Two-channel emergency stop circuit without cross-circuit detection

– Manual activation (monitored reset button at S33-S34)– Automatic activation (jumper at Y1-S33-S35)– Suitable up to safety category 3

102858B002

+24 V DC

0 V

EM

ER

GE

NC

YS

TO

P

A1 S33 S34 S35

A2

-K2

S22 S10 S12S11 S13

Y1

2313

13 23

14 24

14 24

PSR-SDC4

Re

se

t... TBUS ...

... TBUS ...

Y30

Page 9: PSR-SCP- 24DC/SDC4/2X1/B PSR-SPP- 24DC/SDC4/2X1/B · PSR-...- 24DC/SDC4/2X1/B 102858en_02_ PHOENIX CONTACT 2 Ordering Data Technical Data Safety Relays Description Type Order No

PSR-...- 24DC/SDC4/2X1/B

102858en_02_ PHOENIX CONTACT 9

Figure 8 Two-channel safety door monitoring without cross-circuit detection, one N/C contact and one N/O contact

– Manual activation (monitored reset button at S33-S34)– Automatic activation (jumper at Y1-S33-S35)– Suitable up to safety category 2

102858B003

+24 V DC

0 V

Sa

fety

do

or

A1 S33 S34 S35

A2

-K2

S22 S10 S12S11 S13

Y1

2313

13 23

14 24

14 24

PSR-SDC4

Re

se

t... TBUS ...

... TBUS ...

Y30

Page 10: PSR-SCP- 24DC/SDC4/2X1/B PSR-SPP- 24DC/SDC4/2X1/B · PSR-...- 24DC/SDC4/2X1/B 102858en_02_ PHOENIX CONTACT 2 Ordering Data Technical Data Safety Relays Description Type Order No

PSR-...- 24DC/SDC4/2X1/B

102858en_02_ PHOENIX CONTACT 10

Figure 9 Monitoring with encoded magnetic switch without cross-circuit detection, with closed safety door

– Manual activation (monitored reset button at S33-S34)– Automatic activation (jumper at Y1-S33-S35)– Suitable up to safety category 3*

102858A006

+24 V DC

0 V

Magneticswitch

A1 S33 S34 S35

A2

-K2

S22 S10 S12S11 S13

Y1

2313

13 23

14 24

14 24

PSR-SDC4

Re

se

t... TBUS ...

... TBUS ...

Y30

* Due to the high level of protection from errors and manipulation offered by magnetic switches, unlike monitoring using safety doors with position switches, only one switch is required for safety category 3 according to EN 954-1.

Page 11: PSR-SCP- 24DC/SDC4/2X1/B PSR-SPP- 24DC/SDC4/2X1/B · PSR-...- 24DC/SDC4/2X1/B 102858en_02_ PHOENIX CONTACT 2 Ordering Data Technical Data Safety Relays Description Type Order No

PSR-...- 24DC/SDC4/2X1/B

102858en_02_ PHOENIX CONTACT 11

Figure 10 Connection for safety category 3 according to EN 954-1: Example with three magnetic switches with 2-pos. control switch (N/C contact and N/O contact), with open safety door

Comparison of Safety Categories According to EN 954-1 and Product Standard EN 60947-5-3

The machine manufacturer must carry out a risk analysis according to the Machinery Directive.

The assignment of safety categories according to EN 954-1 for proximity switches is somewhat difficult because it is not fully congruent with product standard EN 60947-5-3.

The proximity switches (magnetic switches) are classified as PDFs (Proximity Devices with Defined Behavior under Fault Conditions):

102858A007

S3

S10 S11 S12 S13

S2

S1

Class DescriptionPDF-D Reliability due to special designPDF-T Test capabilityPDF-S Single-fault tolerancePDF-M Self monitoring

Categories acc. toEN 954-1

PDF classes acc. toEN 60947-5-3

B D1 T2

S3

M4

Page 12: PSR-SCP- 24DC/SDC4/2X1/B PSR-SPP- 24DC/SDC4/2X1/B · PSR-...- 24DC/SDC4/2X1/B 102858en_02_ PHOENIX CONTACT 2 Ordering Data Technical Data Safety Relays Description Type Order No

PSR-...- 24DC/SDC4/2X1/B

102858en_02_ PHOENIX CONTACT 12

Figure 11 Single-channel emergency stop circuit with monitored contact extension

– Manual activation (monitored reset button at S33-S34)– Automatic activation (jumper at Y1-S33-S35)– Suitable up to safety category 2

102858B004

+24 V DC

0 V

EM

ER

GE

NC

YS

TO

P

A1 S33 S34 S35

A2

-K2

S22 S10 S12S11 S13

Y1

2313

13 23

14 24

14 24

PSR-SDC4

Re

se

t

K3

K4

K3

K4

N

L

... TBUS ...

... TBUS ...

Y30

Page 13: PSR-SCP- 24DC/SDC4/2X1/B PSR-SPP- 24DC/SDC4/2X1/B · PSR-...- 24DC/SDC4/2X1/B 102858en_02_ PHOENIX CONTACT 2 Ordering Data Technical Data Safety Relays Description Type Order No

PSR-...- 24DC/SDC4/2X1/B

102858en_02_ PHOENIX CONTACT 13

Figure 12 Two-channel light grid monitoring with cross-circuit detection

– Manual activation (monitored reset button at S33-S35)– Automatic activation (jumper at Y1-S33-S35)– Suitable up to safety category 4

102858B005

+24 V DC

0 V

A1 S33 S34 S35

A2

-K2

S22 S10 S12S11 S13

Y1

2313

13 23

14 24

14 24

PSR-SDC4

Re

se

t

Light

grid

OSSD1 OSSD2... TBUS ...

... TBUS ...

Y30

Page 14: PSR-SCP- 24DC/SDC4/2X1/B PSR-SPP- 24DC/SDC4/2X1/B · PSR-...- 24DC/SDC4/2X1/B 102858en_02_ PHOENIX CONTACT 2 Ordering Data Technical Data Safety Relays Description Type Order No

PSR-...- 24DC/SDC4/2X1/B

102858en_02_ PHOENIX CONTACT 14

Start and Feedback Circuits

Figure 13 Monitored reset Figure 14 Automatic activation with monitored contact extension (K3 ext., K4 ext.) via T-BUS DIN rail connector

Figure 15 Monitored reset with monitored contact ex-tension (K3 ext., K4 ext.) via T-BUS DIN rail connector

Figure 16 Automatic activation with monitored contact extension (K3 ext., K4 ext.)

Figure 17 Monitored reset with monitored contact ex-tension (K3 ext., K4 ext.)

Figure 18 Automatic activation with restart inhibit in the event of mains failure (E-S1, E-S2)Not fault-proof

Figure 19 Automatic activation Figure 20 Automatic activation with restart inhibit in the event of mains failure (E-S1, E-S2) with monitored contact extension (K3 ext., K4 ext.) Not fault-proof

S33

Reset

Y1 S34 S35

K4

ext.

K3

ext.

T-BUS

S33 Y1 S34 S35

K4

ext.

K3

ext.

Reset

S33 Y1 S34 S35

T-BUS

K4 ext.

K3 ext.

S33 Y1 S34 S35

K4 ext.

K3 ext.Reset

S33 Y1 S34 S35 S11

E-S 1

E-S 2

S33 Y1 S34 S35

S33 Y1 S34 S35 S11

E-S 1

E-S 2

K4 ext.

K3 ext.

S33 Y1 S34 S35

Page 15: PSR-SCP- 24DC/SDC4/2X1/B PSR-SPP- 24DC/SDC4/2X1/B · PSR-...- 24DC/SDC4/2X1/B 102858en_02_ PHOENIX CONTACT 2 Ordering Data Technical Data Safety Relays Description Type Order No

PSR-...- 24DC/SDC4/2X1/B

102858_02_en 15PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • GermanyPhone: +49-(0) 5235-3-00 • Fax: +49-(0) 5235-3-4 12 00

www.phoenixcontact.com

Emergency Stop Circuits

© PHOENIX CONTACT 12/2006

Figure 21 Two-channel with cross-circuit detection, two N/C contacts

Figure 22 Single-channel

Figure 23 Two-channel without cross-circuit detection, two N/C contacts

Figure 24 Semiconductor outputs

Figure 25 Two-channel without cross-circuit detection, one N/C contact and one N/O contact

S11

E-S 1 E-S 2

S12 S13 S10 A2 S22 S11

E-S 1

S12 S13 S10 A2 S22

S11

E-S 1 E-S 2

S12 S13 S10 A2 S22S11

+24V Output

1 2

S12 S13 S10 A2 S22

S11

E-S 1 E-S 2

S12 S13 S10 A2 S22