80
2 - 213 R2 SERIES YKB/YLM OUTDOOR UNITS MEE14K035 I.R2 SERIES 1. SPECIFICATIONS ........................................................................................................................................... 2 - 214 2. EXTERNAL DIMENSIONS .............................................................................................................................. 2 - 229 3. CENTER OF GRAVITY ................................................................................................................................... 2 - 240 4. ELECTRICAL WIRING DIAGRAMS ................................................................................................................ 2 - 241 5. SOUND LEVELS ............................................................................................................................................. 2 - 243 6. VIBRATION LEVEL ......................................................................................................................................... 2 - 249 7. OPERATION TEMPERATURE RANGE.......................................................................................................... 2 - 250 8. CAPACITY TABLES ........................................................................................................................................ 2 - 251 8-1. Selection of Cooling/Heating Units .......................................................................................................... 2 - 252 8-2. Correction by temperature ....................................................................................................................... 2 - 254 8-3. Correction by total indoor ......................................................................................................................... 2 - 274 8-4. Correction by refrigerant piping length..................................................................................................... 2 - 283 8-5. Correction by port counts of the BC controller ......................................................................................... 2 - 286 8-6. Correction at frost and defrost ................................................................................................................. 2 - 286 9. OPTIONAL PARTS.......................................................................................................................................... 2 - 287 9-1. JOINT ...................................................................................................................................................... 2 - 287 9-2. OUTDOOR TWINNING KIT..................................................................................................................... 2 - 288 9-3. JOINT KIT "CMY-R160-J1" FOR BC CONTROLLER ............................................................................. 2 - 290 9-4. RELAY BOX ............................................................................................................................................ 2 - 291 9-5. BASE HEATER........................................................................................................................................ 2 - 292

R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

  • Upload
    lekhanh

  • View
    232

  • Download
    0

Embed Size (px)

Citation preview

Page 1: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 213

R2 SERIES YKB/YLM

OUTDOOR UNITS

MEE14K035

I.R2 SERIES

1. SPECIFICATIONS........................................................................................................................................... 2 - 214

2. EXTERNAL DIMENSIONS .............................................................................................................................. 2 - 229

3. CENTER OF GRAVITY ................................................................................................................................... 2 - 240

4. ELECTRICAL WIRING DIAGRAMS ................................................................................................................ 2 - 241

5. SOUND LEVELS ............................................................................................................................................. 2 - 243

6. VIBRATION LEVEL ......................................................................................................................................... 2 - 249

7. OPERATION TEMPERATURE RANGE.......................................................................................................... 2 - 250

8. CAPACITY TABLES ........................................................................................................................................ 2 - 251

8-1. Selection of Cooling/Heating Units .......................................................................................................... 2 - 2528-2. Correction by temperature ....................................................................................................................... 2 - 2548-3. Correction by total indoor......................................................................................................................... 2 - 2748-4. Correction by refrigerant piping length..................................................................................................... 2 - 2838-5. Correction by port counts of the BC controller ......................................................................................... 2 - 2868-6. Correction at frost and defrost ................................................................................................................. 2 - 286

9. OPTIONAL PARTS.......................................................................................................................................... 2 - 287

9-1. JOINT ...................................................................................................................................................... 2 - 2879-2. OUTDOOR TWINNING KIT..................................................................................................................... 2 - 2889-3. JOINT KIT "CMY-R160-J1" FOR BC CONTROLLER ............................................................................. 2 - 2909-4. RELAY BOX ............................................................................................................................................ 2 - 2919-5. BASE HEATER........................................................................................................................................ 2 - 292

0000003483.BOOK 213 ページ 2015年1月14日 水曜日 午前11時12分

Page 2: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 214

R2

MEE14K035

1. SPECIFICATIONS YKB/YLM

I.R2 SERIES1. SPECIFICATIONS

Model PURY-P200YLM-A1 (-BS) PURY-P250YLM-A1 (-BS)

Power source 3-phase 4-wire 380-400-415 V 50/60 Hz 3-phase 4-wire 380-400-415 V 50/60 Hz

Cooling capacity *1 kW 22.4 28.0

(Nominal) kcal/h 20,000 25,000

*1 BTU/h 76,400 95,500

Power input kW 5.29 6.98

Current input A 8.9-8.4-8.1 11.7-11.1-10.7

EER kW/kW 4.23 4.01

Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F) 15.0~24.0°C (59~75°F)

cooling *3 Outdoor D.B. -5.0~46.0°C (23~115°F) -5.0~46.0°C (23~115°F)

Heating capacity *2 kW 25.0 31.5

(Nominal) kcal/h 21,500 27,100

*2 BTU/h 85,300 107,500

Power input kW 5.49 7.32

Current input A 9.2-8.8-8.4 12.3-11.7-11.3

COP kW/kW 4.55 4.30

Temp. range of Indoor D.B. 15.0~27.0°C (59~81°F) 15.0~27.0°C (59~81°F)

heating *3 Outdoor W.B. -20.0~15.5°C (-4~60°F) -20.0~15.5°C (-4~60°F)

Indoor unit Total capacity 50~150% 50~150% of outdoor unit capacity

connectable Model/Quantity P15~P250/1~20 P15~P250/1~25

Sound pressure level (measured in anechoic room) dB <A> 59 60

Sound power level (measured in anechoic room) dB <A> 82.5 83.5

Refrigerant High pressure mm (in.) 15.88 (5/8) Brazed 19.05 (3/4) Brazed

piping diameter Low pressure mm (in.) 19.05 (3/4) Brazed 22.2 (7/8) Brazed

FAN Type x Quantity Propeller fan x 1 Propeller fan x 1

Air flow rate m3/min 185 185

L/s 3,083 3,083

cfm 6,532 6,532

Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor

Motor output kW 0.92 x 1 0.92 x 1

*4 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)

Compressor Type x Quantity Inverter scroll hermetic compressor Inverter scroll hermetic compressor

Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION AC&R Works, MITSUBISHI ELECTRIC CORPORATION

Starting method Inverter Inverter

Motor output kW 5.6 6.9

Case heater kW - (- V) - (- V)

Lubricant MEL32 MEL32

External finishPre-coated galvanized steel sheets (+powder coating for -BS

type)Pre-coated galvanized steel sheets (+powder coating for -BS

type)

<MUNSELL 5Y 8/1 or similar> <MUNSELL 5Y 8/1 or similar>

External dimension H x W x D mm 1,710 (1,650 without legs) x 920 x 740 1,710 (1,650 without legs) x 920 x 740

in. 67-3/8 (65 without legs) x 36-1/4 x 29-3/16 67-3/8 (65 without legs) x 36-1/4 x 29-3/16

Protection devices High pressure protectionHigh pressure sensor, High pressure switch at 4.15 MPa (601

psi)High pressure sensor, High pressure switch at 4.15 MPa (601

psi)

Inverter circuit (COMP./FAN) Over-heat protection, Over-current protection Over-heat protection, Over-current protection

Compressor Over-heat protection Over-heat protection

Fan motor Over-current protection Over-current protection

Refrigerant Type x original charge R410A x 9.5 kg (21 lbs) R410A x 9.5 kg (21 lbs)

Control Indoor LEV and BC controller Indoor LEV and BC controller

Net weight kg (lbs) 205 (452) 205 (452)

Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube

HIC circuit (HIC: Heat Inter-Changer) - -

Defrosting method Auto-defrost mode (Reversed refrigerant cycle, Hot gas) Auto-defrost mode (Reversed refrigerant cycle, Hot gas)

Drawing External WKJ94T176 WKJ94T176

Wiring WKE94G041 WKE94G041

Standard attachment Document Installation Manual Installation Manual

Accessory Refrigerant conn. pipe Refrigerant conn. pipe

Optional parts Joint: CMY-Y102SS-G2,CMY-Y102LS-G2,CMY-R160-J1 Joint: CMY-Y102SS-G2,CMY-Y102LS-G2,CMY-R160-J1

BC controller: CMB-P104,105,106,108,1010,1013,1016V-G1 BC controller: CMB-P104,105,106,108,1010,1013,1016V-G1

Main BC controller: CMB-P108,1010,1013,1016V-GA1 Main BC controller: CMB-P108,1010,1013,1016V-GA1

Sub BC controller: CMB-P104,108V-GB1,CMB-P1016V-HB1 Sub BC controller: CMB-P104,108V-GB1,CMB-P1016V-HB1

Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual.Due to continuing improvement, above specifications may be subject to change without notice.

Notes: Unit converter

1.Nominal cooling conditions (subject to JIS B8615-2) Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B./24°CW.B. (95°FD.B./75°FW.B.) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.) 2.Nominal heating conditions (subject to JIS B8615-2) Indoor: 20°CD.B. (68°FD.B.), Outdoor: 7°CD.B./6°CW.B. (45°FD.B./43°FW.B.) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.) 3.-5°CD.B. (23°FD.B.)/-6°CW.B. (21°FW.B.) to 21°CD.B. (70°FD.B.)/15.5°CW.B. (60°FW.B.) with cooling/heating mixed operation. 4.External static pressure option is available (30 Pa, 60 Pa/3.1 mmH2O, 6.1 mmH2O).

BTU/h =kW x 3,412

cfm =m3/min x 35.31

lbs =kg/0.4536

*Above specification data is

subject to rounding variation.

0000003483.BOOK 214 ページ 2015年1月14日 水曜日 午前11時12分

Page 3: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 215

R2

MEE14K035

1. SPECIFICATIONS YKB/YLM

Model PURY-P300YLM-A1 (-BS) PURY-P350YLM-A1 (-BS)

Power source 3-phase 4-wire 380-400-415 V 50/60 Hz 3-phase 4-wire 380-400-415 V 50/60 Hz

Cooling capacity *1 kW 33.5 40.0

(Nominal) kcal/h 30,000 35,000

*1 BTU/h 114,300 136,500

Power input kW 9.10 11.76

Current input A 15.3-14.5-14.0 19.8-18.8-18.1

EER kW/kW 3.68 3.40

Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F) 15.0~24.0°C (59~75°F)

cooling *3 Outdoor D.B. -5.0~46.0°C (23~115°F) -5.0~46.0°C (23~115°F)

Heating capacity *2 kW 37.5 45.0

(Nominal) kcal/h 32,300 40,000

*2 BTU/h 128,000 153,500

Power input kW 9.37 11.59

Current input A 15.8-15.0-14.4 19.5-18.5-17.9

COP kW/kW 4.00 3.88

Temp. range of Indoor D.B. 15.0~27.0°C (59~81°F) 15.0~27.0°C (59~81°F)

heating *3 Outdoor W.B. -20.0~15.5°C (-4~60°F) -20.0~15.5°C (-4~60°F)

Indoor unit Total capacity 50~150% of outdoor unit capacity 50~150% of outdoor unit capacity

connectable Model/Quantity P15~P250/1~30 P15~P250/1~35

Sound pressure level (measured in anechoic room) dB <A> 62.5 62.5

Sound power level (measured in anechoic room) dB <A> 86 86

Refrigerant High pressure mm (in.) 19.05 (3/4) Brazed 19.05 (3/4) Brazed

piping diameter Low pressure mm (in.) 22.2 (7/8) Brazed 28.58 (1-1/8) Brazed

FAN Type x Quantity Propeller fan x 1 Propeller fan x 1

Air flow rate m3/min 230 230

L/s 3,833 3,833

cfm 8,121 8,121

Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor

Motor output kW 0.92 x 1 0.92 x 1

*4 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)

Compressor Type x Quantity Inverter scroll hermetic compressor Inverter scroll hermetic compressor

Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION AC&R Works, MITSUBISHI ELECTRIC CORPORATION

Starting method Inverter Inverter

Motor output kW 8.1 10.5

Case heater kW - (- V) - (- V)

Lubricant MEL32 MEL32

External finishPre-coated galvanized steel sheets (+powder coating for -BS

type)Pre-coated galvanized steel sheets (+powder coating for -BS

type)

<MUNSELL 5Y 8/1 or similar> <MUNSELL 5Y 8/1 or similar>

External dimension H x W x D mm 1,710 (1,650 without legs) x 1,220 x 740 1,710 (1,650 without legs) x 1,220 x 740

in. 67-3/8 (65 without legs) x 48-1/16 x 29-3/16 67-3/8 (65 without legs) x 48-1/16 x 29-3/16

Protection devices High pressure protectionHigh pressure sensor, High pressure switch at 4.15 MPa (601

psi)High pressure sensor, High pressure switch at 4.15 MPa (601

psi)

Inverter circuit (COMP./FAN) Over-heat protection, Over-current protection Over-heat protection, Over-current protection

Compressor Over-heat protection Over-heat protection

Fan motor Over-current protection Over-current protection

Refrigerant Type x original charge R410A x 10.3 kg (23 lbs) R410A x 10.3 kg (23 lbs)

Control Indoor LEV and BC controller Indoor LEV and BC controller

Net weight kg (lbs) 248 (547) 248 (547)

Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube

HIC circuit (HIC: Heat Inter-Changer) - -

Defrosting method Auto-defrost mode (Reversed refrigerant cycle, Hot gas) Auto-defrost mode (Reversed refrigerant cycle, Hot gas)

Drawing External WKJ94T177 WKJ94T177

Wiring WKE94G041 WKE94G041

Standard attachment Document Installation Manual Installation Manual

Accessory Refrigerant conn. pipe Refrigerant conn. pipe

Optional parts Joint: CMY-Y102SS-G2,CMY-Y102LS-G2,CMY-R160-J1 Joint: CMY-Y102SS-G2,CMY-Y102LS-G2,CMY-R160-J1

BC controller: CMB-P104,105,106,108,1010,1013,1016V-G1 BC controller: CMB-P104,105,106,108,1010,1013,1016V-G1

Main BC controller: CMB-P108,1010,1013,1016V-GA1 Main BC controller: CMB-P108,1010,1013,1016V-GA1

Sub BC controller: CMB-P104,108V-GB1,CMB-P1016V-HB1 Sub BC controller: CMB-P104,108V-GB1,CMB-P1016V-HB1

Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual.Due to continuing improvement, above specifications may be subject to change without notice.

Notes: Unit converter

1.Nominal cooling conditions (subject to JIS B8615-2) Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B./24°CW.B. (95°FD.B./75°FW.B.) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.) 2.Nominal heating conditions (subject to JIS B8615-2) Indoor: 20°CD.B. (68°FD.B.), Outdoor: 7°CD.B./6°CW.B. (45°FD.B./43°FW.B.) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.) 3.-5°CD.B. (23°FD.B.)/-6°CW.B. (21°FW.B.) to 21°CD.B. (70°FD.B.)/15.5°CW.B. (60°FW.B.) with cooling/heating mixed operation. 4.External static pressure option is available (30 Pa, 60 Pa/3.1 mmH2O, 6.1 mmH2O).

BTU/h =kW x 3,412

cfm =m3/min x 35.31

lbs =kg/0.4536

*Above specification data is

subject to rounding variation.

0000003483.BOOK 215 ページ 2015年1月14日 水曜日 午前11時12分

Page 4: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 216

R2

MEE14K035

1. SPECIFICATIONS YKB/YLM

Model PURY-P400YLM-A1 (-BS) PURY-P450YLM-A1 (-BS)

Power source 3-phase 4-wire 380-400-415 V 50/60 Hz 3-phase 4-wire 380-400-415 V 50/60 Hz

Cooling capacity *1 kW 45.0 50.0

(Nominal) kcal/h 40,000 45,000

*1 BTU/h 153,500 170,600

Power input kW 13.71 14.32

Current input A 23.1-21.9-21.1 24.1-22.9-22.1

EER kW/kW 3.28 3.49

Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F) 15.0~24.0°C (59~75°F)

cooling *3 Outdoor D.B. -5.0~46.0°C (23~115°F) -5.0~46.0°C (23~115°F)

Heating capacity *2 kW 45.0 56.0

(Nominal) kcal/h 40,000 50,000

*2 BTU/h 153,500 191,100

Power input kW 11.42 14.93

Current input A 19.2-18.3-17.6 25.2-23.9-23.0

COP kW/kW 3.94 3.75

Temp. range of Indoor D.B. 15.0~27.0°C (59~81°F) 15.0~27.0°C (59~81°F)

heating *3 Outdoor W.B. -20.0~15.5°C (-4~60°F) -20.0~15.5°C (-4~60°F)

Indoor unit Total capacity 50~150% of outdoor unit capacity 50~150% of outdoor unit capacity

connectable Model/Quantity P15~P250/1~40 P15~P250/1~45

Sound pressure level (measured in anechoic room) dB <A> 62.5 62.5

Sound power level (measured in anechoic room) dB <A> 86 86

Refrigerant High pressure mm (in.) 22.2 (7/8) Brazed 22.2 (7/8) Brazed

piping diameter Low pressure mm (in.) 28.58 (1-1/8) Brazed 28.58 (1-1/8) Brazed

FAN Type x Quantity Propeller fan x 1 Propeller fan x 2

Air flow rate m3/min 230 320

L/s 3,833 5,333

cfm 8,121 11,299

Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor

Motor output kW 0.92 x 1 0.92 x 2

*4 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)

Compressor Type x Quantity Inverter scroll hermetic compressor Inverter scroll hermetic compressor

Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION AC&R Works, MITSUBISHI ELECTRIC CORPORATION

Starting method Inverter Inverter

Motor output kW 10.9 12.4

Case heater kW - (- V) - (- V)

Lubricant MEL32 MEL32

External finishPre-coated galvanized steel sheets (+powder coating for -BS

type)Pre-coated galvanized steel sheets (+powder coating for -BS

type)

<MUNSELL 5Y 8/1 or similar> <MUNSELL 5Y 8/1 or similar>

External dimension H x W x D mm 1,710 (1,650 without legs) x 1,220 x 740 1,710 (1,650 without legs) x 1,750 x 740

in. 67-3/8 (65 without legs) x 48-1/16 x 29-3/16 67-3/8 (65 without legs) x 68-15/16 x 29-3/16

Protection devices High pressure protectionHigh pressure sensor, High pressure switch at 4.15 MPa (601

psi)High pressure sensor, High pressure switch at 4.15 MPa (601

psi)

Inverter circuit (COMP./FAN) Over-heat protection, Over-current protection Over-heat protection, Over-current protection

Compressor Over-heat protection Over-heat protection

Fan motor Over-current protection Over-current protection

Refrigerant Type x original charge R410A x 10.3 kg (23 lbs) R410A x 11.8 kg (27 lbs)

Control Indoor LEV and BC controller Indoor LEV and BC controller

Net weight kg (lbs) 246 (543) 321 (708)

Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube

HIC circuit (HIC: Heat Inter-Changer) - -

Defrosting method Auto-defrost mode (Reversed refrigerant cycle, Hot gas) Auto-defrost mode (Reversed refrigerant cycle, Hot gas)

Drawing External WKJ94T177 WKJ94T178

Wiring WKE94G041 WKE94G042

Standard attachment Document Installation Manual Installation Manual

Accessory Refrigerant conn. pipe Refrigerant conn. pipe

Optional parts Joint: CMY-Y102SS-G2,CMY-Y102LS-G2,CMY-R160-J1 Joint: CMY-Y102SS-G2,CMY-Y102LS-G2,CMY-R160-J1

Main BC controller: CMB-P108,1010,1013,1016V-GA1 Main BC controller: CMB-P108,1010,1013,1016V-GA1

Sub BC controller: CMB-P104,108V-GB1,CMB-P1016V-HB1 Sub BC controller: CMB-P104,108V-GB1,CMB-P1016V-HB1

Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual.Due to continuing improvement, above specifications may be subject to change without notice.

Notes: Unit converter

1.Nominal cooling conditions (subject to JIS B8615-2) Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B./24°CW.B. (95°FD.B./75°FW.B.) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.) 2.Nominal heating conditions (subject to JIS B8615-2) Indoor: 20°CD.B. (68°FD.B.), Outdoor: 7°CD.B./6°CW.B. (45°FD.B./43°FW.B.) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.) 3.-5°CD.B. (23°FD.B.)/-6°CW.B. (21°FW.B.) to 21°CD.B. (70°FD.B.)/15.5°CW.B. (60°FW.B.) with cooling/heating mixed operation. 4.External static pressure option is available (30 Pa, 60 Pa/3.1 mmH2O, 6.1 mmH2O).

BTU/h =kW x 3,412

cfm =m3/min x 35.31

lbs =kg/0.4536

*Above specification data is

subject to rounding variation.

0000003483.BOOK 216 ページ 2015年1月14日 水曜日 午前11時12分

Page 5: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 217

R2

MEE14K035

1. SPECIFICATIONS YKB/YLM

Model PURY-P500YLM-A1 (-BS)

Power source 3-phase 4-wire 380-400-415 V 50/60 Hz

Cooling capacity *1 kW 56.0

(Nominal) kcal/h 50,000

*1 BTU/h 191,100

Power input kW 17.77

Current input A 29.9-28.4-27.4

EER kW/kW 3.15

Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F)

cooling *3 Outdoor D.B. -5.0~46.0°C (23~115°F)

Heating capacity *2 kW 58.0

(Nominal) kcal/h 50,000

*2 BTU/h 197,900

Power input kW 16.06

Current input A 27.1-25.7-24.8

COP kW/kW 3.61

Temp. range of Indoor D.B. 15.0~27.0°C (59~81°F)

heating *3 Outdoor W.B. -20.0~15.5°C (-4~60°F)

Indoor unit Total capacity 50~150% of outdoor unit capacity

connectable Model/Quantity P15~P250/1~50

Sound pressure level (measured in anechoic room) dB <A> 63.5

Sound power level (measured in anechoic room) dB <A> 87

Refrigerant High pressure mm (in.) 22.2 (7/8) Brazed

piping diameter Low pressure mm (in.) 28.58 (1-1/8) Brazed

FAN Type x Quantity Propeller fan x 2

Air flow rate m3/min 380

L/s 6,333

cfm 13,418

Control, Driving mechanism Inverter-control, Direct-driven by motor

Motor output kW 0.92 x 2

*4 External static press. 0 Pa (0 mmH2O)

Compressor Type x Quantity Inverter scroll hermetic compressor

Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION

Starting method Inverter

Motor output kW 13.4

Case heater kW - (- V)

Lubricant MEL32

External finishPre-coated galvanized steel sheets (+powder coating for -BS

type)

<MUNSELL 5Y 8/1 or similar>

External dimension H x W x D mm 1,710 (1,650 without legs) x 1,750 x 740

in. 67-3/8 (65 without legs) x 68-15/16 x 29-3/16

Protection devices High pressure protectionHigh pressure sensor, High pressure switch at 4.15 MPa (601

psi)

Inverter circuit (COMP./FAN) Over-heat protection, Over-current protection

Compressor Over-heat protection

Fan motor Over-current protection

Refrigerant Type x original charge R410A x 11.8 kg (27 lbs)

Control Indoor LEV and BC controller

Net weight kg (lbs) 321 (708)

Heat exchanger Salt-resistant cross fin & copper tube

HIC circuit (HIC: Heat Inter-Changer) -

Defrosting method Auto-defrost mode (Reversed refrigerant cycle, Hot gas)

Drawing External WKJ94T178

Wiring WKE94G042

Standard attachment Document Installation Manual

Accessory Refrigerant conn. pipe

Optional parts Joint: CMY-Y102SS-G2,CMY-Y102LS-G2,CMY-R160-J1

Main BC controller: CMB-P108,1010,1013,1016V-GA1

Sub BC controller: CMB-P104,108V-GB1,CMB-P1016V-HB1

Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual.Due to continuing improvement, above specifications may be subject to change without notice.

Notes: Unit converter

1.Nominal cooling conditions (subject to JIS B8615-2) Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B./24°CW.B. (95°FD.B./75°FW.B.) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.) 2.Nominal heating conditions (subject to JIS B8615-2) Indoor: 20°CD.B. (68°FD.B.), Outdoor: 7°CD.B./6°CW.B. (45°FD.B./43°FW.B.) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.) 3.-5°CD.B. (23°FD.B.)/-6°CW.B. (21°FW.B.) to 21°CD.B. (70°FD.B.)/15.5°CW.B. (60°FW.B.) with cooling/heating mixed operation. 4.External static pressure option is available (30 Pa, 60 Pa/3.1 mmH2O, 6.1 mmH2O).

BTU/h =kW x 3,412

cfm =m3/min x 35.31

lbs =kg/0.4536

*Above specification data is

subject to rounding variation.

0000003483.BOOK 217 ページ 2015年1月14日 水曜日 午前11時12分

Page 6: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 218

R2

MEE14K035

1. SPECIFICATIONS YKB/YLM

Model PURY-P400YSLM-A1 (-BS)

Power source 3-phase 4-wire 380-400-415 V 50/60 Hz

Cooling capacity *1 kW 45.0

(Nominal) kcal/h 40,000

*1 BTU/h 153,500

Power input kW 10.97

Current input A 18.5-17.5-16.9

EER kW/kW 4.10

Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F)

cooling *3 Outdoor D.B. -5.0~46.0°C (23~115°F)

Heating capacity *2 kW 50.0

(Nominal) kcal/h 45,000

*2 BTU/h 170,600

Power input kW 10.98

Current input A 18.5-17.6-16.9

COP kW/kW 4.55

Temp. range of Indoor D.B. 15.0~27.0°C (59~81°F)

heating *3 Outdoor W.B. -20.0~15.5°C (-4~60°F)

Indoor unit Total capacity 50~150% of outdoor unit capacity

connectable Model/Quantity P15~P250/1~40

Sound pressure level (measured in anechoic room) dB <A> 62

Sound power level (measured in anechoic room) dB <A> 85.5

Refrigerant High pressure mm (in.) 22.2 (7/8) Brazed

piping diameter Low pressure mm (in.) 28.58 (1-1/8) Brazed

Set Model

Model PURY-P200YLM-A1 (-BS) PURY-P200YLM-A1 (-BS)

FAN Type x Quantity Propeller fan x 1 Propeller fan x 1

Air flow rate m3/min 185 185

L/s 3,083 3,083

cfm 6,532 6,532

Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor

Motor output kW 0.92 x 1 0.92 x 1

*4 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)

Compressor Type x Quantity Inverter scroll hermetic compressor Inverter scroll hermetic compressor

Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION AC&R Works, MITSUBISHI ELECTRIC CORPORATION

Starting method Inverter Inverter

Motor output kW 5.6 5.6

Case heater kW - (- V) - (- V)

Lubricant MEL32 MEL32

External finishPre-coated galvanized steel sheets (+powder coating for -BS

type)Pre-coated galvanized steel sheets (+powder coating for -BS

type)

<MUNSELL 5Y 8/1 or similar> <MUNSELL 5Y 8/1 or similar>

External dimension H x W x D mm 1,710 (1,650 without legs) x 920 x 740 1,710 (1,650 without legs) x 920 x 740

in. 67-3/8 (65 without legs) x 36-1/4 x 29-3/16 67-3/8 (65 without legs) x 36-1/4 x 29-3/16

Protection devices High pressure protectionHigh pressure sensor, High pressure switch at 4.15 MPa (601

psi)High pressure sensor, High pressure switch at 4.15 MPa (601

psi)

Inverter circuit (COMP./FAN) Over-heat protection, Over-current protection Over-heat protection, Over-current protection

Compressor Over-heat protection Over-heat protection

Fan motor Over-current protection Over-current protection

Refrigerant Type x original charge R410A x 9.5 kg (21 lbs) R410A x 9.5 kg (21 lbs)

Control Indoor LEV and BC controller

Net weight kg (lbs) 205 (452) 205 (452)

Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube

HIC circuit (HIC: Heat Inter-Changer) - -

Pipe between unit and High pressure mm (in.) 15.88 (5/8) Brazed 15.88 (5/8) Brazed

distributor Low pressure mm (in.) 19.05 (3/4) Brazed -

Defrosting method Auto-defrost mode (Reversed refrigerant cycle, Hot gas)

Drawing External WKJ94T179

Wiring WKE94G041 WKE94G041

Standard attachment Document Installation Manual

Accessory Refrigerant conn. pipe

Optional parts Outdoor Twinning kit: CMY-R100VBK-A

Joint: CMY-Y102S-G2,CMY-Y102L-G2,CMY-R160-J1

Main BC controller: CMB-P108,1010,1013,1016V-GA1

Sub BC controller: CMB-P104,108V-GB1,CMB-P1016V-HB1

Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual.Due to continuing improvement, above specifications may be subject to change without notice.

Notes: Unit converter

1.Nominal cooling conditions (subject to JIS B8615-2) Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B./24°CW.B. (95°FD.B./75°FW.B.) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.) 2.Nominal heating conditions (subject to JIS B8615-2) Indoor: 20°CD.B. (68°FD.B.), Outdoor: 7°CD.B./6°CW.B. (45°FD.B./43°FW.B.) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.) 3.-5°CD.B. (23°FD.B.)/-6°CW.B. (21°FW.B.) to 21°CD.B. (70°FD.B.)/15.5°CW.B. (60°FW.B.) with cooling/heating mixed operation. 4.External static pressure option is available (30 Pa, 60 Pa/3.1 mmH2O, 6.1 mmH2O).

BTU/h =kW x 3,412

cfm =m3/min x 35.31

lbs =kg/0.4536

*Above specification data is

subject to rounding variation.

0000003483.BOOK 218 ページ 2015年1月14日 水曜日 午前11時12分

Page 7: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 219

R2

MEE14K035

1. SPECIFICATIONS YKB/YLM

Model PURY-P450YSLM-A1 (-BS)

Power source 3-phase 4-wire 380-400-415 V 50/60 Hz

Cooling capacity *1 kW 50.0

(Nominal) kcal/h 45,000

*1 BTU/h 170,600

Power input kW 12.50

Current input A 21.1-20.0-19.3

EER kW/kW 4.00

Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F)

cooling *3 Outdoor D.B. -5.0~46.0°C (23~115°F)

Heating capacity *2 kW 56.0

(Nominal) kcal/h 48,200

*2 BTU/h 191,100

Power input kW 12.64

Current input A 21.3-20.2-19.5

COP kW/kW 4.43

Temp. range of Indoor D.B. 15.0~27.0°C (59~81°F)

heating *3 Outdoor W.B. -20.0~15.5°C (-4~60°F)

Indoor unit Total capacity 50~150% of outdoor unit capacity

connectable Model/Quantity P15~P250/1~45

Sound pressure level (measured in anechoic room) dB <A> 62.5

Sound power level (measured in anechoic room) dB <A> 86

Refrigerant High pressure mm (in.) 22.2 (7/8) Brazed

piping diameter Low pressure mm (in.) 28.58 (1-1/8) Brazed

Set Model

Model PURY-P200YLM-A1 (-BS) PURY-P250YLM-A1 (-BS)

FAN Type x Quantity Propeller fan x 1 Propeller fan x 1

Air flow rate m3/min 185 185

L/s 3,083 3,083

cfm 6,532 6,532

Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor

Motor output kW 0.92 x 1 0.92 x 1

*4 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)

Compressor Type x Quantity Inverter scroll hermetic compressor Inverter scroll hermetic compressor

Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION AC&R Works, MITSUBISHI ELECTRIC CORPORATION

Starting method Inverter Inverter

Motor output kW 5.6 6.9

Case heater kW - (- V) - (- V)

Lubricant MEL32 MEL32

External finishPre-coated galvanized steel sheets (+powder coating for -BS

type)Pre-coated galvanized steel sheets (+powder coating for -BS

type)

<MUNSELL 5Y 8/1 or similar> <MUNSELL 5Y 8/1 or similar>

External dimension H x W x D mm 1,710 (1,650 without legs) x 920 x 740 1,710 (1,650 without legs) x 920 x 740

in. 67-3/8 (65 without legs) x 36-1/4 x 29-3/16 67-3/8 (65 without legs) x 36-1/4 x 29-3/16

Protection devices High pressure protectionHigh pressure sensor, High pressure switch at 4.15 MPa (601

psi)High pressure sensor, High pressure switch at 4.15 MPa (601

psi)

Inverter circuit (COMP./FAN) Over-heat protection, Over-current protection Over-heat protection, Over-current protection

Compressor Over-heat protection Over-heat protection

Fan motor Over-current protection Over-current protection

Refrigerant Type x original charge R410A x 9.5 kg (21 lbs) R410A x 9.5 kg (21 lbs)

Control Indoor LEV and BC controller

Net weight kg (lbs) 205 (452) 205 (452)

Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube

HIC circuit (HIC: Heat Inter-Changer) - -

Pipe between unit and High pressure mm (in.) 15.88 (5/8) Brazed 19.05 (3/4) Brazed

distributor Low pressure mm (in.) 19.05 (3/4) Brazed -

Defrosting method Auto-defrost mode (Reversed refrigerant cycle, Hot gas)

Drawing External WKJ94T179

Wiring WKE94G041 WKE94G041

Standard attachment Document Installation Manual

Accessory Refrigerant conn. pipe

Optional parts Outdoor Twinning kit: CMY-R100VBK-A

Joint: CMY-Y102S-G2,CMY-Y102L-G2,CMY-R160-J1

Main BC controller: CMB-P108,1010,1013,1016V-GA1

Sub BC controller: CMB-P104,108V-GB1,CMB-P1016V-HB1

Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual.Due to continuing improvement, above specifications may be subject to change without notice.

Notes: Unit converter

1.Nominal cooling conditions (subject to JIS B8615-2) Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B./24°CW.B. (95°FD.B./75°FW.B.) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.) 2.Nominal heating conditions (subject to JIS B8615-2) Indoor: 20°CD.B. (68°FD.B.), Outdoor: 7°CD.B./6°CW.B. (45°FD.B./43°FW.B.) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.) 3.-5°CD.B. (23°FD.B.)/-6°CW.B. (21°FW.B.) to 21°CD.B. (70°FD.B.)/15.5°CW.B. (60°FW.B.) with cooling/heating mixed operation. 4.External static pressure option is available (30 Pa, 60 Pa/3.1 mmH2O, 6.1 mmH2O).

BTU/h =kW x 3,412

cfm =m3/min x 35.31

lbs =kg/0.4536

*Above specification data is

subject to rounding variation.

0000003483.BOOK 219 ページ 2015年1月14日 水曜日 午前11時12分

Page 8: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 220

R2

MEE14K035

1. SPECIFICATIONS YKB/YLM

Model PURY-P500YSLM-A1 (-BS)

Power source 3-phase 4-wire 380-400-415 V 50/60 Hz

Cooling capacity *1 kW 56.0

(Nominal) kcal/h 50,000

*1 BTU/h 191,100

Power input kW 14.39

Current input A 24.2-23.0-22.2

EER kW/kW 3.89

Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F)

cooling *3 Outdoor D.B. -5.0~46.0°C (23~115°F)

Heating capacity *2 kW 63.0

(Nominal) kcal/h 54,200

*2 BTU/h 215,000

Power input kW 14.65

Current input A 24.7-23.4-22.6

COP kW/kW 4.30

Temp. range of Indoor D.B. 15.0~27.0°C (59~81°F)

heating *3 Outdoor W.B. -20.0~15.5°C (-4~60°F)

Indoor unit Total capacity 50~150% of outdoor unit capacity

connectable Model/Quantity P15~P250/1~50

Sound pressure level (measured in anechoic room) dB <A> 63

Sound power level (measured in anechoic room) dB <A> 86.5

Refrigerant High pressure mm (in.) 22.2 (7/8) Brazed

piping diameter Low pressure mm (in.) 28.58 (1-1/8) Brazed

Set Model

Model PURY-P250YLM-A1 (-BS) PURY-P250YLM-A1 (-BS)

FAN Type x Quantity Propeller fan x 1 Propeller fan x 1

Air flow rate m3/min 185 185

L/s 3,083 3,083

cfm 6,532 6,532

Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor

Motor output kW 0.92 x 1 0.92 x 1

*4 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)

Compressor Type x Quantity Inverter scroll hermetic compressor Inverter scroll hermetic compressor

Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION AC&R Works, MITSUBISHI ELECTRIC CORPORATION

Starting method Inverter Inverter

Motor output kW 6.9 6.9

Case heater kW - (- V) - (- V)

Lubricant MEL32 MEL32

External finishPre-coated galvanized steel sheets (+powder coating for -BS

type)Pre-coated galvanized steel sheets (+powder coating for -BS

type)

<MUNSELL 5Y 8/1 or similar> <MUNSELL 5Y 8/1 or similar>

External dimension H x W x D mm 1,710 (1,650 without legs) x 920 x 740 1,710 (1,650 without legs) x 920 x 740

in. 67-3/8 (65 without legs) x 36-1/4 x 29-3/16 67-3/8 (65 without legs) x 36-1/4 x 29-3/16

Protection devices High pressure protectionHigh pressure sensor, High pressure switch at 4.15 MPa (601

psi)High pressure sensor, High pressure switch at 4.15 MPa (601

psi)

Inverter circuit (COMP./FAN) Over-heat protection, Over-current protection Over-heat protection, Over-current protection

Compressor Over-heat protection Over-heat protection

Fan motor Over-current protection Over-current protection

Refrigerant Type x original charge R410A x 9.5 kg (21 lbs) R410A x 9.5 kg (21 lbs)

Control Indoor LEV and BC controller

Net weight kg (lbs) 205 (452) 205 (452)

Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube

HIC circuit (HIC: Heat Inter-Changer) - -

Pipe between unit and High pressure mm (in.) 19.05 (3/4) Brazed 19.05 (3/4) Brazed

distributor Low pressure mm (in.) 22.2 (7/8) Brazed -

Defrosting method Auto-defrost mode (Reversed refrigerant cycle, Hot gas)

Drawing External WKJ94T179

Wiring WKE94G041 WKE94G041

Standard attachment Document Installation Manual

Accessory Refrigerant conn. pipe

Optional parts Outdoor Twinning kit: CMY-R100VBK-A

Joint: CMY-Y102S-G2,CMY-Y102L-G2,CMY-R160-J1

Main BC controller: CMB-P108,1010,1013,1016V-GA1

Sub BC controller: CMB-P104,108V-GB1,CMB-P1016V-HB1

Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual.Due to continuing improvement, above specifications may be subject to change without notice.

Notes: Unit converter

1.Nominal cooling conditions (subject to JIS B8615-2) Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B./24°CW.B. (95°FD.B./75°FW.B.) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.) 2.Nominal heating conditions (subject to JIS B8615-2) Indoor: 20°CD.B. (68°FD.B.), Outdoor: 7°CD.B./6°CW.B. (45°FD.B./43°FW.B.) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.) 3.-5°CD.B. (23°FD.B.)/-6°CW.B. (21°FW.B.) to 21°CD.B. (70°FD.B.)/15.5°CW.B. (60°FW.B.) with cooling/heating mixed operation. 4.External static pressure option is available (30 Pa, 60 Pa/3.1 mmH2O, 6.1 mmH2O).

BTU/h =kW x 3,412

cfm =m3/min x 35.31

lbs =kg/0.4536

*Above specification data is

subject to rounding variation.

0000003483.BOOK 220 ページ 2015年1月14日 水曜日 午前11時12分

Page 9: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 221

R2

MEE14K035

1. SPECIFICATIONS YKB/YLM

Model PURY-P550YSLM-A1 (-BS)

Power source 3-phase 4-wire 380-400-415 V 50/60 Hz

Cooling capacity *1 kW 63.0

(Nominal) kcal/h 54,200

*1 BTU/h 215,000

Power input kW 16.89

Current input A 28.5-27.0-26.1

EER kW/kW 3.73

Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F)

cooling *3 Outdoor D.B. -5.0~46.0°C (23~115°F)

Heating capacity *2 kW 69.0

(Nominal) kcal/h 59,300

*2 BTU/h 235,400

Power input kW 16.62

Current input A 28.0-26.6-25.6

COP kW/kW 4.15

Temp. range of Indoor D.B. 15.0~27.0°C (59~81°F)

heating *3 Outdoor W.B. -20.0~15.5°C (-4~60°F)

Indoor unit Total capacity 50~150% of outdoor unit capacity

connectable Model/Quantity P15~P250/2~50

Sound pressure level (measured in anechoic room) dB <A> 64.5

Sound power level (measured in anechoic room) dB <A> 88

Refrigerant High pressure mm (in.) 28.58 (1-1/8) Brazed

piping diameter Low pressure mm (in.) 28.58 (1-1/8) Brazed

Set Model

Model PURY-P250YLM-A1 (-BS) PURY-P300YLM-A1 (-BS)

FAN Type x Quantity Propeller fan x 1 Propeller fan x 1

Air flow rate m3/min 185 230

L/s 3,083 3,833

cfm 6,532 8,121

Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor

Motor output kW 0.92 x 1 0.92 x 1

*4 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)

Compressor Type x Quantity Inverter scroll hermetic compressor Inverter scroll hermetic compressor

Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION AC&R Works, MITSUBISHI ELECTRIC CORPORATION

Starting method Inverter Inverter

Motor output kW 6.9 8.1

Case heater kW - (- V) - (- V)

Lubricant MEL32 MEL32

External finishPre-coated galvanized steel sheets (+powder coating for -BS

type)Pre-coated galvanized steel sheets (+powder coating for -BS

type)

<MUNSELL 5Y 8/1 or similar> <MUNSELL 5Y 8/1 or similar>

External dimension H x W x D mm 1,710 (1,650 without legs) x 920 x 740 1,710 (1,650 without legs) x 1,220 x 740

in. 67-3/8 (65 without legs) x 36-1/4 x 29-3/16 67-3/8 (65 without legs) x 48-1/16 x 29-3/16

Protection devices High pressure protectionHigh pressure sensor, High pressure switch at 4.15 MPa (601

psi)High pressure sensor, High pressure switch at 4.15 MPa (601

psi)

Inverter circuit (COMP./FAN) Over-heat protection, Over-current protection Over-heat protection, Over-current protection

Compressor Over-heat protection Over-heat protection

Fan motor Over-current protection Over-current protection

Refrigerant Type x original charge R410A x 9.5 kg (21 lbs) R410A x 10.3 kg (23 lbs)

Control Indoor LEV and BC controller

Net weight kg (lbs) 205 (452) 248 (547)

Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube

HIC circuit (HIC: Heat Inter-Changer) - -

Pipe between unit and High pressure mm (in.) 19.05 (3/4) Brazed 19.05 (3/4) Brazed

distributor Low pressure mm (in.) 22.2 (7/8) Brazed -

Defrosting method Auto-defrost mode (Reversed refrigerant cycle, Hot gas)

Drawing External WKJ94T180

Wiring WKE94G041 WKE94G041

Standard attachment Document Installation Manual

Accessory Refrigerant conn. pipe

Optional parts Outdoor Twinning kit: CMY-R100VBK2

Joint: CMY-Y102SS-G2,CMY-Y102LS-G2,CMY-R160-J1

Main BC controller: CMB-P108,1010,1013,1016V-GA1

Sub BC controller: CMB-P104,108V-GB1,CMB-P1016V-HB1

Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual.Due to continuing improvement, above specifications may be subject to change without notice.

Notes: Unit converter

1.Nominal cooling conditions (subject to JIS B8615-2) Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B./24°CW.B. (95°FD.B./75°FW.B.) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.) 2.Nominal heating conditions (subject to JIS B8615-2) Indoor: 20°CD.B. (68°FD.B.), Outdoor: 7°CD.B./6°CW.B. (45°FD.B./43°FW.B.) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.) 3.-5°CD.B. (23°FD.B.)/-6°CW.B. (21°FW.B.) to 21°CD.B. (70°FD.B.)/15.5°CW.B. (60°FW.B.) with cooling/heating mixed operation. 4.External static pressure option is available (30 Pa, 60 Pa/3.1 mmH2O, 6.1 mmH2O).

BTU/h =kW x 3,412

cfm =m3/min x 35.31

lbs =kg/0.4536

*Above specification data is

subject to rounding variation.

0000003483.BOOK 221 ページ 2015年1月14日 水曜日 午前11時12分

Page 10: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 222

R2

MEE14K035

1. SPECIFICATIONS YKB/YLM

Model PURY-P600YSLM-A1 (-BS)

Power source 3-phase 4-wire 380-400-415 V 50/60 Hz

Cooling capacity *1 kW 69.0

(Nominal) kcal/h 59,300

*1 BTU/h 235,400

Power input kW 19.32

Current input A 32.6-30.9-29.8

EER kW/kW 3.57

Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F)

cooling *3 Outdoor D.B. -5.0~46.0°C (23~115°F)

Heating capacity *2 kW 76.5

(Nominal) kcal/h 65,800

*2 BTU/h 261,000

Power input kW 19.12

Current input A 32.2-30.6-29.5

COP kW/kW 4.00

Temp. range of Indoor D.B. 15.0~27.0°C (59~81°F)

heating *3 Outdoor W.B. -20.0~15.5°C (-4~60°F)

Indoor unit Total capacity 50~150% of outdoor unit capacity

connectable Model/Quantity P15~P250/2~50

Sound pressure level (measured in anechoic room) dB <A> 65.5

Sound power level (measured in anechoic room) dB <A> 89

Refrigerant High pressure mm (in.) 28.58 (1-1/8) Brazed

piping diameter Low pressure mm (in.) 28.58 (1-1/8) Brazed

Set Model

Model PURY-P300YLM-A1 (-BS) PURY-P300YLM-A1 (-BS)

FAN Type x Quantity Propeller fan x 1 Propeller fan x 1

Air flow rate m3/min 230 230

L/s 3,833 3,833

cfm 8,121 8,121

Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor

Motor output kW 0.92 x 1 0.92 x 1

*4 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)

Compressor Type x Quantity Inverter scroll hermetic compressor Inverter scroll hermetic compressor

Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION AC&R Works, MITSUBISHI ELECTRIC CORPORATION

Starting method Inverter Inverter

Motor output kW 8.1 8.1

Case heater kW - (- V) - (- V)

Lubricant MEL32 MEL32

External finishPre-coated galvanized steel sheets (+powder coating for -BS

type)Pre-coated galvanized steel sheets (+powder coating for -BS

type)

<MUNSELL 5Y 8/1 or similar> <MUNSELL 5Y 8/1 or similar>

External dimension H x W x D mm 1,710 (1,650 without legs) x 1,220 x 740 1,710 (1,650 without legs) x 1,220 x 740

in. 67-3/8 (65 without legs) x 48-1/16 x 29-3/16 67-3/8 (65 without legs) x 48-1/16 x 29-3/16

Protection devices High pressure protectionHigh pressure sensor, High pressure switch at 4.15 MPa (601

psi)High pressure sensor, High pressure switch at 4.15 MPa (601

psi)

Inverter circuit (COMP./FAN) Over-heat protection, Over-current protection Over-heat protection, Over-current protection

Compressor Over-heat protection Over-heat protection

Fan motor Over-current protection Over-current protection

Refrigerant Type x original charge R410A x 10.3 kg (23 lbs) R410A x 10.3 kg (23 lbs)

Control Indoor LEV and BC controller

Net weight kg (lbs) 248 (547) 248 (547)

Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube

HIC circuit (HIC: Heat Inter-Changer) - -

Pipe between unit and High pressure mm (in.) 19.05 (3/4) Brazed 19.05 (3/4) Brazed

distributor Low pressure mm (in.) 22.2 (7/8) Brazed -

Defrosting method Auto-defrost mode (Reversed refrigerant cycle, Hot gas)

Drawing External WKJ94T181

Wiring WKE94G041 WKE94G041

Standard attachment Document Installation Manual

Accessory Refrigerant conn. pipe

Optional parts Outdoor Twinning kit: CMY-R100VBK2

Joint: CMY-Y102SS-G2,CMY-Y102LS-G2,CMY-R160-J1

Main BC controller: CMB-P108,1010,1013,1016V-GA1

Sub BC controller: CMB-P104,108V-GB1,CMB-P1016V-HB1

Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual.Due to continuing improvement, above specifications may be subject to change without notice.

Notes: Unit converter

1.Nominal cooling conditions (subject to JIS B8615-2) Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B./24°CW.B. (95°FD.B./75°FW.B.) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.) 2.Nominal heating conditions (subject to JIS B8615-2) Indoor: 20°CD.B. (68°FD.B.), Outdoor: 7°CD.B./6°CW.B. (45°FD.B./43°FW.B.) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.) 3.-5°CD.B. (23°FD.B.)/-6°CW.B. (21°FW.B.) to 21°CD.B. (70°FD.B.)/15.5°CW.B. (60°FW.B.) with cooling/heating mixed operation. 4.External static pressure option is available (30 Pa, 60 Pa/3.1 mmH2O, 6.1 mmH2O).

BTU/h =kW x 3,412

cfm =m3/min x 35.31

lbs =kg/0.4536

*Above specification data is

subject to rounding variation.

0000003483.BOOK 222 ページ 2015年1月14日 水曜日 午前11時12分

Page 11: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 223

R2

MEE14K035

1. SPECIFICATIONS YKB/YLM

Model PURY-P650YSLM-A1 (-BS)

Power source 3-phase 4-wire 380-400-415 V 50/60 Hz

Cooling capacity *1 kW 73.0

(Nominal) kcal/h 62,800

*1 BTU/h 249,100

Power input kW 21.28

Current input A 35.9-34.1-32.8

EER kW/kW 3.43

Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F)

cooling *3 Outdoor D.B. -5.0~46.0°C (23~115°F)

Heating capacity *2 kW 81.5

(Nominal) kcal/h 70,100

*2 BTU/h 278,100

Power input kW 20.68

Current input A 34.9-33.1-31.9

COP kW/kW 3.94

Temp. range of Indoor D.B. 15.0~27.0°C (59~81°F)

heating *3 Outdoor W.B. -20.0~15.5°C (-4~60°F)

Indoor unit Total capacity 50~150% of outdoor unit capacity

connectable Model/Quantity P15~P250/2~50

Sound pressure level (measured in anechoic room) dB <A> 65.5

Sound power level (measured in anechoic room) dB <A> 89

Refrigerant High pressure mm (in.) 28.58 (1-1/8) Brazed

piping diameter Low pressure mm (in.) 28.58 (1-1/8) Brazed

Set Model

Model PURY-P300YLM-A1 (-BS) PURY-P350YLM-A1 (-BS)

FAN Type x Quantity Propeller fan x 1 Propeller fan x 1

Air flow rate m3/min 230 230

L/s 3,833 3,833

cfm 8,121 8,121

Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor

Motor output kW 0.92 x 1 0.92 x 1

*4 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)

Compressor Type x Quantity Inverter scroll hermetic compressor Inverter scroll hermetic compressor

Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION AC&R Works, MITSUBISHI ELECTRIC CORPORATION

Starting method Inverter Inverter

Motor output kW 8.1 10.5

Case heater kW - (- V) - (- V)

Lubricant MEL32 MEL32

External finishPre-coated galvanized steel sheets (+powder coating for -BS

type)Pre-coated galvanized steel sheets (+powder coating for -BS

type)

<MUNSELL 5Y 8/1 or similar> <MUNSELL 5Y 8/1 or similar>

External dimension H x W x D mm 1,710 (1,650 without legs) x 1,220 x 740 1,710 (1,650 without legs) x 1,220 x 740

in. 67-3/8 (65 without legs) x 48-1/16 x 29-3/16 67-3/8 (65 without legs) x 48-1/16 x 29-3/16

Protection devices High pressure protectionHigh pressure sensor, High pressure switch at 4.15 MPa (601

psi)High pressure sensor, High pressure switch at 4.15 MPa (601

psi)

Inverter circuit (COMP./FAN) Over-heat protection, Over-current protection Over-heat protection, Over-current protection

Compressor Over-heat protection Over-heat protection

Fan motor Over-current protection Over-current protection

Refrigerant Type x original charge R410A x 10.3 kg (23 lbs) R410A x 10.3 kg (23 lbs)

Control Indoor LEV and BC controller

Net weight kg (lbs) 248 (547) 248 (547)

Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube

HIC circuit (HIC: Heat Inter-Changer) - -

Pipe between unit and High pressure mm (in.) 19.05 (3/4) Brazed 19.05 (3/4) Brazed

distributor Low pressure mm (in.) 22.2 (7/8) Brazed -

Defrosting method Auto-defrost mode (Reversed refrigerant cycle, Hot gas)

Drawing External WKJ94T181

Wiring WKE94G041 WKE94G041

Standard attachment Document Installation Manual

Accessory Refrigerant conn. pipe

Optional parts Outdoor Twinning kit: CMY-R100VBK2

Joint: CMY-Y102SS-G2,CMY-Y102LS-G2,CMY-R160-J1

Main BC controller: CMB-P108,1010,1013,1016V-GA1

Sub BC controller: CMB-P104,108V-GB1,CMB-P1016V-HB1

Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual.Due to continuing improvement, above specifications may be subject to change without notice.

Notes: Unit converter

1.Nominal cooling conditions (subject to JIS B8615-2) Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B./24°CW.B. (95°FD.B./75°FW.B.) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.) 2.Nominal heating conditions (subject to JIS B8615-2) Indoor: 20°CD.B. (68°FD.B.), Outdoor: 7°CD.B./6°CW.B. (45°FD.B./43°FW.B.) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.) 3.-5°CD.B. (23°FD.B.)/-6°CW.B. (21°FW.B.) to 21°CD.B. (70°FD.B.)/15.5°CW.B. (60°FW.B.) with cooling/heating mixed operation. 4.External static pressure option is available (30 Pa, 60 Pa/3.1 mmH2O, 6.1 mmH2O).

BTU/h =kW x 3,412

cfm =m3/min x 35.31

lbs =kg/0.4536

*Above specification data is

subject to rounding variation.

0000003483.BOOK 223 ページ 2015年1月14日 水曜日 午前11時12分

Page 12: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 224

R2

MEE14K035

1. SPECIFICATIONS YKB/YLM

Model PURY-P700YSLM-A1 (-BS)

Power source 3-phase 4-wire 380-400-415 V 50/60 Hz

Cooling capacity *1 kW 80.0

(Nominal) kcal/h 68,800

*1 BTU/h 273,000

Power input kW 24.24

Current input A 40.9-38.8-37.4

EER kW/kW 3.30

Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F)

cooling *3 Outdoor D.B. -5.0~46.0°C (23~115°F)

Heating capacity *2 kW 88.0

(Nominal) kcal/h 75,700

*2 BTU/h 300,300

Power input kW 22.68

Current input A 38.2-36.3-35.0

COP kW/kW 3.88

Temp. range of Indoor D.B. 15.0~27.0°C (59~81°F)

heating *3 Outdoor W.B. -20.0~15.5°C (-4~60°F)

Indoor unit Total capacity 50~150% of outdoor unit capacity

connectable Model/Quantity P15~P250/2~50

Sound pressure level (measured in anechoic room) dB <A> 65.5

Sound power level (measured in anechoic room) dB <A> 89

Refrigerant High pressure mm (in.) 28.58 (1-1/8) Brazed

piping diameter Low pressure mm (in.) 34.93 (1-3/8) Brazed

Set Model

Model PURY-P350YLM-A1 (-BS) PURY-P350YLM-A1 (-BS)

FAN Type x Quantity Propeller fan x 1 Propeller fan x 1

Air flow rate m3/min 230 230

L/s 3,833 3,833

cfm 8,121 8,121

Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor

Motor output kW 0.92 x 1 0.92 x 1

*4 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)

Compressor Type x Quantity Inverter scroll hermetic compressor Inverter scroll hermetic compressor

Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION AC&R Works, MITSUBISHI ELECTRIC CORPORATION

Starting method Inverter Inverter

Motor output kW 10.5 10.5

Case heater kW - (- V) - (- V)

Lubricant MEL32 MEL32

External finishPre-coated galvanized steel sheets (+powder coating for -BS

type)Pre-coated galvanized steel sheets (+powder coating for -BS

type)

<MUNSELL 5Y 8/1 or similar> <MUNSELL 5Y 8/1 or similar>

External dimension H x W x D mm 1,710 (1,650 without legs) x 1,220 x 740 1,710 (1,650 without legs) x 1,220 x 740

in. 67-3/8 (65 without legs) x 48-1/16 x 29-3/16 67-3/8 (65 without legs) x 48-1/16 x 29-3/16

Protection devices High pressure protectionHigh pressure sensor, High pressure switch at 4.15 MPa (601

psi)High pressure sensor, High pressure switch at 4.15 MPa (601

psi)

Inverter circuit (COMP./FAN) Over-heat protection, Over-current protection Over-heat protection, Over-current protection

Compressor Over-heat protection Over-heat protection

Fan motor Over-current protection Over-current protection

Refrigerant Type x original charge R410A x 10.3 kg (23 lbs) R410A x 10.3 kg (23 lbs)

Control Indoor LEV and BC controller

Net weight kg (lbs) 248 (547) 248 (547)

Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube

HIC circuit (HIC: Heat Inter-Changer) -

Pipe between unit and High pressure mm (in.) 19.05 (3/4) Brazed 19.05 (3/4) Brazed

distributor Low pressure mm (in.) 28.58 (1-1/8) Brazed -

Defrosting method Auto-defrost mode (Reversed refrigerant cycle, Hot gas)

Drawing External WKJ94T181

Wiring WKE94G041 WKE94G041

Standard attachment Document Installation Manual

Accessory Refrigerant conn. pipe

Optional parts Outdoor Twinning kit: CMY-R200VBK2

Joint: CMY-Y102SS-G2,CMY-Y102LS-G2,CMY-R160-J1

Main BC controller: CMB-P1016V-HA1

Sub BC controller: CMB-P104,108V-GB1,CMB-P1016V-HB1

Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual.Due to continuing improvement, above specifications may be subject to change without notice.

Notes: Unit converter

1.Nominal cooling conditions (subject to JIS B8615-2) Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B./24°CW.B. (95°FD.B./75°FW.B.) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.) 2.Nominal heating conditions (subject to JIS B8615-2) Indoor: 20°CD.B. (68°FD.B.), Outdoor: 7°CD.B./6°CW.B. (45°FD.B./43°FW.B.) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.) 3.-5°CD.B. (23°FD.B.)/-6°CW.B. (21°FW.B.) to 21°CD.B. (70°FD.B.)/15.5°CW.B. (60°FW.B.) with cooling/heating mixed operation. 4.External static pressure option is available (30 Pa, 60 Pa/3.1 mmH2O, 6.1 mmH2O).

BTU/h =kW x 3,412

cfm =m3/min x 35.31

lbs =kg/0.4536

*Above specification data is

subject to rounding variation.

0000003483.BOOK 224 ページ 2015年1月14日 水曜日 午前11時12分

Page 13: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 225

R2

MEE14K035

1. SPECIFICATIONS YKB/YLM

Model PURY-P750YSLM-A1 (-BS)

Power source 3-phase 4-wire 380-400-415 V 50/60 Hz

Cooling capacity *1 kW 85.0

(Nominal) kcal/h 73,100

*1 BTU/h 290,000

Power input kW 26.23

Current input A 44.2-42.0-40.5

EER kW/kW 3.24

Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F)

cooling *3 Outdoor D.B. -5.0~46.0°C (23~115°F)

Heating capacity *2 kW 90.0

(Nominal) kcal/h 77,400

*2 BTU/h 307,100

Power input kW 23.01

Current input A 38.8-36.9-35.5

COP kW/kW 3.91

Temp. range of Indoor D.B. 15.0~27.0°C (59~81°F)

heating *3 Outdoor W.B. -20.0~15.5°C (-4~60°F)

Indoor unit Total capacity 50~150% of outdoor unit capacity

connectable Model/Quantity P15~P250/2~50

Sound pressure level (measured in anechoic room) dB <A> 65.5

Sound power level (measured in anechoic room) dB <A> 89

Refrigerant High pressure mm (in.) 28.58 (1-1/8) Brazed

piping diameter Low pressure mm (in.) 34.93 (1-3/8) Brazed

Set Model

Model PURY-P350YLM-A1 (-BS) PURY-P400YLM-A1 (-BS)

FAN Type x Quantity Propeller fan x 1 Propeller fan x 1

Air flow rate m3/min 230 230

L/s 3,833 3,833

cfm 8,121 8,121

Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor

Motor output kW 0.92 x 1 0.92 x 1

*4 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)

Compressor Type x Quantity Inverter scroll hermetic compressor Inverter scroll hermetic compressor

Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION AC&R Works, MITSUBISHI ELECTRIC CORPORATION

Starting method Inverter Inverter

Motor output kW 10.5 10.9

Case heater kW - (- V) - (- V)

Lubricant MEL32 MEL32

External finishPre-coated galvanized steel sheets (+powder coating for -BS

type)Pre-coated galvanized steel sheets (+powder coating for -BS

type)

<MUNSELL 5Y 8/1 or similar> <MUNSELL 5Y 8/1 or similar>

External dimension H x W x D mm 1,710 (1,650 without legs) x 1,220 x 740 1,710 (1,650 without legs) x 1,220 x 740

in. 67-3/8 (65 without legs) x 48-1/16 x 29-3/16 67-3/8 (65 without legs) x 48-1/16 x 29-3/16

Protection devices High pressure protectionHigh pressure sensor, High pressure switch at 4.15 MPa (601

psi)High pressure sensor, High pressure switch at 4.15 MPa (601

psi)

Inverter circuit (COMP./FAN) Over-heat protection, Over-current protection Over-heat protection, Over-current protection

Compressor Over-heat protection Over-heat protection

Fan motor Over-current protection Over-current protection

Refrigerant Type x original charge R410A x 10.3 kg (23 lbs) R410A x 10.3 kg (23 lbs)

Control Indoor LEV and BC controller

Net weight kg (lbs) 248 (547) 246 (543)

Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube

HIC circuit (HIC: Heat Inter-Changer) - -

Pipe between unit and High pressure mm (in.) 19.05 (3/4) Brazed 22.2 (7/8) Brazed

distributor Low pressure mm (in.) 28.58 (1-1/8) Brazed -

Defrosting method Auto-defrost mode (Reversed refrigerant cycle, Hot gas)

Drawing External WKJ94T181

Wiring WKE94G041 WKE94G041

Standard attachment Document Installation Manual

Accessory Refrigerant conn. pipe

Optional parts Outdoor Twinning kit: CMY-R200VBK2

Joint: CMY-Y102SS-G2,CMY-Y102LS-G2,CMY-R160-J1

Main BC controller: CMB-P1016V-HA1

Sub BC controller: CMB-P104,108V-GB1,CMB-P1016V-HB1

Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual.Due to continuing improvement, above specifications may be subject to change without notice.

Notes: Unit converter

1.Nominal cooling conditions (subject to JIS B8615-2) Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B./24°CW.B. (95°FD.B./75°FW.B.) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.) 2.Nominal heating conditions (subject to JIS B8615-2) Indoor: 20°CD.B. (68°FD.B.), Outdoor: 7°CD.B./6°CW.B. (45°FD.B./43°FW.B.) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.) 3.-5°CD.B. (23°FD.B.)/-6°CW.B. (21°FW.B.) to 21°CD.B. (70°FD.B.)/15.5°CW.B. (60°FW.B.) with cooling/heating mixed operation. 4.External static pressure option is available (30 Pa, 60 Pa/3.1 mmH2O, 6.1 mmH2O).

BTU/h =kW x 3,412

cfm =m3/min x 35.31

lbs =kg/0.4536

*Above specification data is

subject to rounding variation.

0000003483.BOOK 225 ページ 2015年1月14日 水曜日 午前11時12分

Page 14: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 226

R2

MEE14K035

1. SPECIFICATIONS YKB/YLM

Model PURY-P800YSLM-A1 (-BS)

Power source 3-phase 4-wire 380-400-415 V 50/60 Hz

Cooling capacity *1 kW 90.0

(Nominal) kcal/h 77,400

*1 BTU/h 307,100

Power input kW 28.30

Current input A 47.7-45.3-43.7

EER kW/kW 3.18

Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F)

cooling *3 Outdoor D.B. -5.0~46.0°C (23~115°F)

Heating capacity *2 kW 90.0

(Nominal) kcal/h 77,400

*2 BTU/h 307,100

Power input kW 22.84

Current input A 38.5-36.6-35.3

COP kW/kW 3.94

Temp. range of Indoor D.B. 15.0~27.0°C (59~81°F)

heating *3 Outdoor W.B. -20.0~15.5°C (-4~60°F)

Indoor unit Total capacity 50~150% of outdoor unit capacity

connectable Model/Quantity P15~P250/2~50

Sound pressure level (measured in anechoic room) dB <A> 65.5

Sound power level (measured in anechoic room) dB <A> 89

Refrigerant High pressure mm (in.) 28.58 (1-1/8) Brazed

piping diameter Low pressure mm (in.) 34.93 (1-3/8) Brazed

Set Model

Model PURY-P400YLM-A1 (-BS) PURY-P400YLM-A1 (-BS)

FAN Type x Quantity Propeller fan x 1 Propeller fan x 1

Air flow rate m3/min 230 230

L/s 3,833 3,833

cfm 8,121 8,121

Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor

Motor output kW 0.92 x 1 0.92 x 1

*4 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)

Compressor Type x Quantity Inverter scroll hermetic compressor Inverter scroll hermetic compressor

Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION AC&R Works, MITSUBISHI ELECTRIC CORPORATION

Starting method Inverter Inverter

Motor output kW 10.9 10.9

Case heater kW - (- V) - (- V)

Lubricant MEL32 MEL32

External finishPre-coated galvanized steel sheets (+powder coating for -BS

type)Pre-coated galvanized steel sheets (+powder coating for -BS

type)

<MUNSELL 5Y 8/1 or similar> <MUNSELL 5Y 8/1 or similar>

External dimension H x W x D mm 1,710 (1,650 without legs) x 1,220 x 740 1,710 (1,650 without legs) x 1,220 x 740

in. 67-3/8 (65 without legs) x 48-1/16 x 29-3/16 67-3/8 (65 without legs) x 48-1/16 x 29-3/16

Protection devices High pressure protectionHigh pressure sensor, High pressure switch at 4.15 MPa (601

psi)High pressure sensor, High pressure switch at 4.15 MPa (601

psi)

Inverter circuit (COMP./FAN) Over-heat protection, Over-current protection Over-heat protection, Over-current protection

Compressor Over-heat protection Over-heat protection

Fan motor Over-current protection Over-current protection

Refrigerant Type x original charge R410A x 10.3 kg (23 lbs) R410A x 10.3 kg (23 lbs)

Control Indoor LEV and BC controller

Net weight kg (lbs) 246 (543) 246 (543)

Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube

HIC circuit (HIC: Heat Inter-Changer) - -

Pipe between unit and High pressure mm (in.) 22.2 (7/8) Brazed 22.2 (7/8) Brazed

distributor Low pressure mm (in.) 28.58 (1-1/8) Brazed -

Defrosting method Auto-defrost mode (Reversed refrigerant cycle, Hot gas)

Drawing External WKJ94T181

Wiring WKE94G041 WKE94G041

Standard attachment Document Installation Manual

Accessory Refrigerant conn. pipe

Optional parts Outdoor Twinning kit: CMY-R200VBK2

Joint: CMY-Y102SS-G2,CMY-Y102LS-G2,CMY-R160-J1

Main BC controller: CMB-P1016V-HA1

Sub BC controller: CMB-P104,108V-GB1,CMB-P1016V-HB1

Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual.Due to continuing improvement, above specifications may be subject to change without notice.

Notes: Unit converter

1.Nominal cooling conditions (subject to JIS B8615-2) Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B./24°CW.B. (95°FD.B./75°FW.B.) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.) 2.Nominal heating conditions (subject to JIS B8615-2) Indoor: 20°CD.B. (68°FD.B.), Outdoor: 7°CD.B./6°CW.B. (45°FD.B./43°FW.B.) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.) 3.-5°CD.B. (23°FD.B.)/-6°CW.B. (21°FW.B.) to 21°CD.B. (70°FD.B.)/15.5°CW.B. (60°FW.B.) with cooling/heating mixed operation. 4.External static pressure option is available (30 Pa, 60 Pa/3.1 mmH2O, 6.1 mmH2O).

BTU/h =kW x 3,412

cfm =m3/min x 35.31

lbs =kg/0.4536

*Above specification data is

subject to rounding variation.

0000003483.BOOK 226 ページ 2015年1月14日 水曜日 午前11時12分

Page 15: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 227

R2

MEE14K035

1. SPECIFICATIONS YKB/YLM

Model PURY-P850YSLM-A1 (-BS)

Power source 3-phase 4-wire 380-400-415 V 50/60 Hz

Cooling capacity *1 kW 96.0

(Nominal) kcal/h 82,600

*1 BTU/h 327,600

Power input kW 29.26

Current input A 49.3-46.9-45.2

EER kW/kW 3.28

Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F)

cooling *3 Outdoor D.B. -5.0~46.0°C (23~115°F)

Heating capacity *2 kW 101.0

(Nominal) kcal/h 86,900

*2 BTU/h 344,600

Power input kW 26.23

Current input A 44.2-42.0-40.5

COP kW/kW 3.85

Temp. range of Indoor D.B. 15.0~27.0°C (59~81°F)

heating *3 Outdoor W.B. -20.0~15.5°C (-4~60°F)

Indoor unit Total capacity 50~150% of outdoor unit capacity

connectable Model/Quantity P15~P250/2~50

Sound pressure level (measured in anechoic room) dB <A> 65.5

Sound power level (measured in anechoic room) dB <A> 89

Refrigerant High pressure mm (in.) 28.58 (1-1/8) Brazed

piping diameter Low pressure mm (in.) 41.28 (1-5/8) Brazed

Set Model

Model PURY-P400YLM-A1 (-BS) PURY-P450YLM-A1 (-BS)

FAN Type x Quantity Propeller fan x 1 Propeller fan x 2

Air flow rate m3/min 230 320

L/s 3,833 5,333

cfm 8,121 11,299

Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor

Motor output kW 0.92 x 1 0.92 x 2

*4 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)

Compressor Type x Quantity Inverter scroll hermetic compressor Inverter scroll hermetic compressor

Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION AC&R Works, MITSUBISHI ELECTRIC CORPORATION

Starting method Inverter Inverter

Motor output kW 10.9 12.4

Case heater kW - (- V) - (- V)

Lubricant MEL32 MEL32

External finishPre-coated galvanized steel sheets (+powder coating for -BS

type)Pre-coated galvanized steel sheets (+powder coating for -BS

type)

<MUNSELL 5Y 8/1 or similar> <MUNSELL 5Y 8/1 or similar>

External dimension H x W x D mm 1,710 (1,650 without legs) x 1,220 x 740 1,710 (1,650 without legs) x 1,750 x 740

in. 67-3/8 (65 without legs) x 48-1/16 x 29-3/16 67-3/8 (65 without legs) x 68-15/16 x 29-3/16

Protection devices High pressure protectionHigh pressure sensor, High pressure switch at 4.15 MPa (601

psi)High pressure sensor, High pressure switch at 4.15 MPa (601

psi)

Inverter circuit (COMP./FAN) Over-heat protection, Over-current protection Over-heat protection, Over-current protection

Compressor Over-heat protection Over-heat protection

Fan motor Over-current protection Over-current protection

Refrigerant Type x original charge R410A x 10.3 kg (23 lbs) R410A x 11.8 kg (27 lbs)

Control Indoor LEV and BC controller

Net weight kg (lbs) 246 (543) 321 (708)

Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube

HIC circuit (HIC: Heat Inter-Changer) - -

Pipe between unit and High pressure mm (in.) 22.2 (7/8) Brazed 22.2 (7/8) Brazed

distributor Low pressure mm (in.) 28.58 (1-1/8) Brazed -

Defrosting method Auto-defrost mode (Reversed refrigerant cycle, Hot gas)

Drawing External WKJ94T182

Wiring WKE94G041 WKE94G042

Standard attachment Document Installation Manual

Accessory Refrigerant conn. pipe

Optional parts Outdoor Twinning kit: CMY-R200XLVBK

Joint: CMY-Y102SS-G2,CMY-Y102LS-G2,CMY-R160-J1

Main BC controller: CMB-P1016V-HA1

Sub BC controller: CMB-P104,108V-GB1,CMB-P1016V-HB1

Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual.Due to continuing improvement, above specifications may be subject to change without notice.

Notes: Unit converter

1.Nominal cooling conditions (subject to JIS B8615-2) Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B./24°CW.B. (95°FD.B./75°FW.B.) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.) 2.Nominal heating conditions (subject to JIS B8615-2) Indoor: 20°CD.B. (68°FD.B.), Outdoor: 7°CD.B./6°CW.B. (45°FD.B./43°FW.B.) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.) 3.-5°CD.B. (23°FD.B.)/-6°CW.B. (21°FW.B.) to 21°CD.B. (70°FD.B.)/15.5°CW.B. (60°FW.B.) with cooling/heating mixed operation. 4.External static pressure option is available (30 Pa, 60 Pa/3.1 mmH2O, 6.1 mmH2O).

BTU/h =kW x 3,412

cfm =m3/min x 35.31

lbs =kg/0.4536

*Above specification data is

subject to rounding variation.

0000003483.BOOK 227 ページ 2015年1月14日 水曜日 午前11時12分

Page 16: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 228

R2

MEE14K035

1. SPECIFICATIONS YKB/YLM

Model PURY-P900YSLM-A1 (-BS)

Power source 3-phase 4-wire 380-400-415 V 50/60 Hz

Cooling capacity *1 kW 101.0

(Nominal) kcal/h 86,900

*1 BTU/h 344,600

Power input kW 29.79

Current input A 50.2-47.7-46.0

EER kW/kW 3.39

Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F)

cooling *3 Outdoor D.B. -5.0~46.0°C (23~115°F)

Heating capacity *2 kW 113.0

(Nominal) kcal/h 97,200

*2 BTU/h 385,600

Power input kW 30.13

Current input A 50.8-48.3-46.5

COP kW/kW 3.75

Temp. range of Indoor D.B. 15.0~27.0°C (59~81°F)

heating *3 Outdoor W.B. -20.0~15.5°C (-4~60°F)

Indoor unit Total capacity 50~150% of outdoor unit capacity

connectable Model/Quantity P15~P250/2~50

Sound pressure level (measured in anechoic room) dB <A> 65.5

Sound power level (measured in anechoic room) dB <A> 89

Refrigerant High pressure mm (in.) 28.58 (1-1/8) Brazed

piping diameter Low pressure mm (in.) 41.28 (1-5/8) Brazed

Set Model

Model PURY-P450YLM-A1 (-BS) PURY-P450YLM-A1 (-BS)

FAN Type x Quantity Propeller fan x 2 Propeller fan x 2

Air flow rate m3/min 320 320

L/s 5,333 5,333

cfm 11,299 11,299

Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor

Motor output kW 0.92 x 2 0.92 x 2

*4 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)

Compressor Type x Quantity Inverter scroll hermetic compressor Inverter scroll hermetic compressor

Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION AC&R Works, MITSUBISHI ELECTRIC CORPORATION

Starting method Inverter Inverter

Motor output kW 12.4 12.4

Case heater kW - (- V) - (- V)

Lubricant MEL32 MEL32

External finishPre-coated galvanized steel sheets (+powder coating for -BS

type)Pre-coated galvanized steel sheets (+powder coating for -BS

type)

<MUNSELL 5Y 8/1 or similar> <MUNSELL 5Y 8/1 or similar>

External dimension H x W x D mm 1,710 (1,650 without legs) x 1,750 x 740 1,710 (1,650 without legs) x 1,750 x 740

in. 67-3/8 (65 without legs) x 68-15/16 x 29-3/16 67-3/8 (65 without legs) x 68-15/16 x 29-3/16

Protection devices High pressure protectionHigh pressure sensor, High pressure switch at 4.15 MPa (601

psi)High pressure sensor, High pressure switch at 4.15 MPa (601

psi)

Inverter circuit (COMP./FAN) Over-heat protection, Over-current protection Over-heat protection, Over-current protection

Compressor Over-heat protection Over-heat protection

Fan motor Over-current protection Over-current protection

Refrigerant Type x original charge R410A x 11.8 kg (27 lbs) R410A x 11.8 kg (27 lbs)

Control Indoor LEV and BC controller

Net weight kg (lbs) 321 (708) 321 (708)

Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube

HIC circuit (HIC: Heat Inter-Changer) - -

Pipe between unit and High pressure mm (in.) 22.2 (7/8) Brazed 22.2 (7/8) Brazed

distributor Low pressure mm (in.) 28.58 (1-1/8) Brazed -

Defrosting method Auto-defrost mode (Reversed refrigerant cycle, Hot gas)

Drawing External WKJ94T183

Wiring WKE94G042 WKE94G042

Standard attachment Document Installation Manual

Accessory Refrigerant conn. pipe

Optional parts Outdoor Twinning kit: CMY-R200XLVBK

Joint: CMY-Y102SS-G2,CMY-Y102LS-G2,CMY-R160-J1

Main BC controller: CMB-P1016V-HA1

Sub BC controller: CMB-P104,108V-GB1,CMB-P1016V-HB1

Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual.Due to continuing improvement, above specifications may be subject to change without notice.

Notes: Unit converter

1.Nominal cooling conditions (subject to JIS B8615-2) Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B./24°CW.B. (95°FD.B./75°FW.B.) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.) 2.Nominal heating conditions (subject to JIS B8615-2) Indoor: 20°CD.B. (68°FD.B.), Outdoor: 7°CD.B./6°CW.B. (45°FD.B./43°FW.B.) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.) 3.-5°CD.B. (23°FD.B.)/-6°CW.B. (21°FW.B.) to 21°CD.B. (70°FD.B.)/15.5°CW.B. (60°FW.B.) with cooling/heating mixed operation. 4.External static pressure option is available (30 Pa, 60 Pa/3.1 mmH2O, 6.1 mmH2O).

BTU/h =kW x 3,412

cfm =m3/min x 35.31

lbs =kg/0.4536

*Above specification data is

subject to rounding variation.

0000003483.BOOK 228 ページ 2015年1月14日 水曜日 午前11時12分

Page 17: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 229

R2

MEE14K035

2. EXTERNAL DIMENSIONS YKB/YLM

2. EXTERNAL DIMENSIONS

1650303 1347

681(678~684) 29.5

(740)

29.5

8076

080

177

150

222

121196

2020

586

5757

201

222

140

5875

150600=150×4 70

881

920

19.5

19.5

740

217

77 89

54

9484

145

186

1710(60)

(60)

6060

251

83

146262 (60)

262

63

7

245

8 1

Ref

riger

ant s

ervi

ce v

alve

<Low

pre

ssur

e>R

efrig

eran

t ser

vice

val

ve<H

igh

pres

sure

>

2×5-

ø4.6

Hol

e(M

ake

hole

at t

he p

last

ic fa

n gu

ard

for s

now

hoo

d at

tach

men

t)<S

now

hoo

d at

tach

men

t hol

e>

Con

trol b

ox

Inta

ke

air

Inta

ke

air

Inta

ke

air

Serv

ice

pane

l

Dis

char

ge a

ir

Left

side

vie

wFr

ont v

iew

Slin

g ho

le

Det

acha

ble

leg

(fron

t and

bac

k,2

poin

ts)

Not

e 2*

Top

view

(Mounting pitch)

2×2-

14×3

1 O

val h

ole

2×2-

14×2

0 Ov

al ho

le(wi

thou

t det

acha

ble le

g)

A

Mod

elD

iam

eter

Ref

riger

ant p

ipe

Serv

ice

valv

e

PURY

-P250

YLM-

A1(-B

S)ø2

5.4

ø19.0

5 Braz

ed *1

ø15.8

8 Braz

ed *1

ø25.

4PU

RY-P2

00YL

M-A1

(-BS)

Con

nect

ing

pipe

spe

cific

atio

ns

High

pre

ssur

eLo

w pr

essu

re

*1 U

se th

e in

clud

ed c

onne

ctin

g pi

pe a

nd c

onne

ct to

the

refri

gera

nt s

ervi

ceva

lve

pipi

ng.

High

pre

ssur

eLo

w pr

essu

re

For tr

ansm

ission

cable

s

For w

ires

For p

ipes

NO

.U

sage

Spec

ifica

tions

Fr

ont t

hrou

gh h

ole

Botto

m th

roug

h ho

leFr

ont t

hrou

gh h

ole

Fron

t thr

ough

hol

e

Botto

m th

roug

h ho

leBo

ttom

thro

ugh

hole

Fron

t thr

ough

hol

e

140

× 77

Kno

ckou

t hol

e

ø65

or ø

40 K

nock

out h

ole

ø52

or ø

27 K

nock

out h

ole

ø65

Knoc

kout

hol

e ø5

2 Kn

ocko

ut h

ole

ø34

Knoc

kout

hol

e

150

× 94

Kno

ckou

t hol

e

ø45

Knoc

kout

hol

e

Fron

t thr

ough

hol

e(U

ses

when

twin

ning

kit

(opt

iona

l p

arts

) is

mou

nted

.)

<Acc

esso

ries>

●Con

nect

ing

pipe

<Lo

w p

ress

ure>

Not

e1.P

leas

e re

fer t

o th

e ne

xt p

age

for i

nfor

mat

ion

rega

rdin

g ne

cess

ary

spac

ing

arou

nd th

e

un

it an

d fo

unda

tion

wor

k.

2.Th

e de

tach

able

leg

can

be re

mov

ed a

t site

.

3.At

bra

zing

of p

ipes

,wra

p th

e re

frige

rant

ser

vice

val

ve

w

ith w

et c

loth

and

kee

p th

e te

mpe

ratu

re o

f

re

frige

rant

ser

vice

val

ve u

nder

120

°C.

·Pip

e (ID

ø25.

4×O

Dø1

9.05

) ···

P20

0 1

pc.

·Pip

e (ID

ø25.

4×ID

ø22.

2)

··· P

250

1pc

.

<H

igh

pres

sure

>·P

ipe

(IDø2

5.4×

OD

ø15.

88)

··· P

200

1pc

.·P

ipe

(IDø1

5.88

×ID

ø15.

88)

··· P

200

1pc

.

·Elbo

w(ID

ø19.

05×O

Dø1

9.05

) ···

P200

1pc

.

·Pip

e (ID

ø25.

4×O

Dø1

9.05

) ···

P25

0 1

pc.

·Elbo

w(ID

ø19.

05×O

Dø1

9.05

) ···

P250

1pc

.

ø22.2

Braz

ed *1

ø19.0

5 Braz

ed *1

1 2 3 4 5 6 7 8

(

) A

Serv

ice

valv

e Fr

ont v

iew

(

) Se

rvic

e va

lve

Botto

m v

iew

Botto

m v

iew

(Mou

ntin

g pi

tch)

PURY-P200, 250YLM-A1 (-BS)Unit : mm

0000003483.BOOK 229 ページ 2015年1月14日 水曜日 午前11時12分

Page 18: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 230

R2

MEE14K035

2. EXTERNAL DIMENSIONS YKB/YLM

PURY-P200, 250YLM-A1 (-BS)Unit : mm

Unit heighthH

500h

H

30mm max.

15 m

in.*

50 m

in.*

50 m

in.*

100 min.* 450 min.*

300min.*

100

min

.30

min

.45

0 m

in.

450

min

.*45

0 m

in.

100

min

.*

450 min.*100 min.*

450 min.*

1000

min

.*

900min.300min.*

900min.300min.* 300min.*

15min.*

450m

in.

450m

in.

450 min.* 300 min.*15

min

.*

30mm max.

Fron

tFr

ont

<Top

vie

w>

<Uni

t:mm

>

<Top

vie

w>

<Wal

l hei

ght l

imit>

Fro

nt:U

p to

the

unit

heig

ht

B

ack

:Up

to 5

00m

m fr

om

the

unit

botto

m

S

ide

:Up

to th

e un

it he

ight

<Sid

e vi

ew>

M10

anc

hor b

olt

<fie

ld s

uppl

y re

quire

d>

Fixin

g pl

ate

<fie

ld s

uppl

y re

quire

d>

<To be left open>

Fron

t

Wal

l <H

>

<To

be le

ft op

en>

Front

<Uni

t:mm

>

Front

Fixi

ng p

late

<fie

ld s

uppl

y re

quire

d>

M10

anc

hor b

olt

<fie

ld s

uppl

y re

quire

d>

Wal

l <H

>

<To be left open>

<To be left open>

<To be left open>

Fron

t

Wal

l <H

>

Wal

l <H

>

Wall <H>

Wall <H>

Front

Front

<To

be le

ft op

en>

Wal

l <H

>

Fron

t

Wal

l <H

>

<To be left open>

<To be left open>

Front

Front

Front

Wal

l <H

>W

all <

H>

Fron

t

<To be left open>

<To

be le

ft op

en>

Deta

chab

le le

g

Fig.

A (w

ithou

t det

acha

ble

legs

)

Fig.

B (w

ith d

etac

habl

e le

gs)

Fig.

C (w

ithou

t det

acha

ble

legs

)Fi

g.D

(with

det

acha

ble

legs

)De

tach

able

leg

1. R

equi

red

spac

e ar

ound

the

unit

●In

case

of s

ingl

e in

stal

latio

n 1

Sec

ure

enou

gh s

pace

aro

und

the

unit

as s

how

n in

the

figur

e be

low.

· With

a s

pace

of a

t lea

st

2 W

hen

the

heig

ht o

f the

wal

ls o

n th

e fro

nt,b

ack

or o

n th

e si

des<

H>

2. F

ound

atio

n w

ork

1 T

ake

into

con

side

ratio

n th

e su

rface

stre

ngth

,wat

er d

rain

age

rout

e,

pip

ing

rout

e,an

d w

iring

rout

e w

hen

prep

arin

g th

e in

stal

latio

n si

te.

<

Not

e th

at th

e dr

ain

wat

er c

omes

out

of t

he u

nit d

urin

g op

erat

ion.

>2

Bui

ld th

e fo

unda

tion

in s

uch

way

that

the

corn

er o

f the

inst

alla

tion

leg

is

sec

urel

y su

ppor

ted

as s

how

n in

the

right

figu

re.(F

ig.A

,B)

W

hen

usin

g a

rubb

er is

olat

ing

cush

ion,

ple

ase

ensu

re it

is la

rge

enou

gh

to c

over

the

entir

e w

idth

of e

ach

of th

e un

it's

legs

.3

The

pro

trusi

on le

ngth

of t

he a

ncho

r bol

t mus

t not

exc

eed

30m

m.(F

ig.A

,B)

4 U

se fo

ur fi

xing

pla

tes

as s

how

n in

the

right

figu

re <

field

sup

ply

requ

ired>

w

hen

usin

g po

st-in

stal

led

anch

or b

olts

.(Fig

.C,D

)5

To

prev

ent s

mall

anim

als a

nd w

ater

and

snow

from

ent

ering

the

unit a

nd d

amag

ing its

par

ts,

clo

se th

e ga

p ar

ound

the

edge

s of

thro

ugh

hole

s fo

r pip

es a

nd w

ires

with

fi

ller p

late

s <f

ield

sup

ply

requ

ired>

.6

Whe

n th

e pi

pes

or c

able

s ar

e ro

uted

at t

he b

otto

m o

f the

uni

t,

mak

e su

re th

at th

e th

roug

h ho

le a

t the

bas

e of

the

unit

does

not

get

blo

cked

w

ith th

e in

stal

latio

n ba

se.

7 R

efer

to th

e In

stal

latio

n M

anua

l whe

n in

stal

ling

units

on

an in

stal

latio

n ba

se.

●In

case

of c

olle

ctiv

e in

stal

latio

n 1

Whe

n m

ultip

le u

nits

are

inst

alle

d ad

jace

nt to

eac

h ot

her,

secu

re e

noug

h sp

ace

to a

llow

fo

r air

circ

ulat

ion

and

wal

kway

bet

wee

n gr

oups

of u

nits

as

show

n in

the

figur

es b

elow

.2

At l

east

two

side

s m

ust b

e le

ft op

en.

3 A

s w

ith th

e si

ngle

inst

alla

tion,

add

the

heig

ht th

at e

xcee

ds th

e he

ight

lim

it<h>

to

the

figur

es th

at a

re m

arke

d w

ith a

n as

teris

k.4

If th

ere

is a

wal

l at b

oth

the

front

and

the

rear

of t

he u

nit,

inst

all u

p to

six

uni

ts

con

secu

tivel

y in

the

side

dire

ctio

n an

d pr

ovid

e a

spac

e of

100

0mm

or m

ore

as in

let s

pace

/

pas

sage

spa

ce fo

r eac

h si

x un

its.

300m

m to

the

wal

l on

the

back

of t

he u

nit

· With

a s

pace

of a

t lea

st

100m

m to

the

wal

l on

the

back

of t

he u

nit

exc

eeds

the

wal

l hei

ght l

imit

as d

efin

ed b

elow

add

the

heig

ht th

at e

xcee

ds th

e he

ight

lim

it <h

> to

the

figur

es th

at a

re m

arke

d w

ith a

n as

teris

k.

0000003483.BOOK 230 ページ 2015年1月14日 水曜日 午前11時12分

Page 19: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 231

R2

MEE14K035

2. EXTERNAL DIMENSIONS YKB/YLM

6

Slin

g ho

le

184 2 7

3

4×5-

ø4.6

Hol

e(M

ake

hole

at t

he p

last

ic fa

n gu

ard

<Sno

w h

ood

atta

chm

ent h

ole>

Ref

riger

ant s

ervi

ce v

alve

Con

trol b

ox

(Mou

ntin

g pi

tch)

(Mounting pitch)

pane

l

Disc

harg

e ai

r

Inta

keai

r

Inta

keai

rIn

take

air

for s

now

hoo

d at

tach

men

t)

Serv

ice

Det

acha

ble

leg

(fron

t and

bac

k,2

poin

ts)

Not

e 2*

<Low

pre

ssur

e>

Fron

t vie

w

Botto

m v

iew

Left

side

vie

w

5Top

view

2×2-

14×3

1 O

val h

ole

2×2-1

4×20

Ova

l hole

(with

out d

etach

able

leg)

Ref

riger

ant s

ervi

ce v

alve

<Hig

h pr

essu

re>

A

Mod

elD

iam

eter

Ref

riger

ant p

ipe

Serv

ice

valv

e

PURY

-P350

YLM-

A1(-B

S)ø2

5.4

ø25.

4PU

RY-P3

00YL

M-A1

(-BS)

Con

nect

ing

pipe

spe

cific

atio

ns

High

pre

ssur

eLo

w pr

essu

re

*1 U

se th

e in

clud

ed c

onne

ctin

g pi

pe a

nd c

onne

ct to

the

refri

gera

nt s

ervi

ceva

lve

pipi

ng.

1 2 3 4 5 6 7 8

High

pre

ssur

eLo

w pr

essu

re

For t

rans

miss

ion ca

bles

For w

ires

For p

ipes

NO

.U

sage

Spec

ifica

tions

Fr

ont t

hrou

gh h

ole

Botto

m th

roug

h ho

leFr

ont t

hrou

gh h

ole

Fron

t thr

ough

hole

Botto

m th

roug

h ho

leBo

ttom

thro

ugh

hole

Fron

t thr

ough

hole

140

× 77

Kno

ckou

t hole

ø65

or ø

40 K

nock

out h

ole

ø52

or ø

27 K

nock

out h

ole

ø65

Knoc

kout

hole

ø5

2 Kn

ocko

ut h

ole

ø34

Knoc

kout

hole

150

× 94

Kno

ckou

t hole

ø45

Knoc

kout

hole

Fron

t thr

ough

hole

(Use

s whe

n tw

inning

kit (

optio

nal

par

ts) is

mou

nted

.)

ø19.0

5 Braz

ed *1

<Acc

esso

ries>

●Con

nect

ing

pipe

<Lo

w p

ress

ure>

Not

e1.P

leas

e re

fer t

o th

e ne

xt p

age

for i

nfor

mat

ion

rega

rdin

g ne

cess

ary

spac

ing

arou

nd th

e

un

it an

d fo

unda

tion

wor

k.

2.Th

e de

tach

able

leg

can

be re

mov

ed a

t site

.

3.At

bra

zing

of p

ipes

,wra

p th

e re

frige

rant

ser

vice

val

ve

w

ith w

et c

loth

and

kee

p th

e te

mpe

ratu

re o

f

re

frige

rant

ser

vice

val

ve u

nder

120

°C.

·Pip

e (ID

ø25.

4×ID

ø22.

2)

··· P

300

1pc

.

<H

igh

pres

sure

>·P

ipe

(IDø2

5.4×

OD

ø19.

05)

··· P

300,

P350

1pc

.·P

ipe

(IDø2

5.4×

IDø2

2.2)

···

P40

0 1

pc.

·Elbo

w(ID

ø19.

05×O

Dø1

9.05

) ···

P300

,P35

0 1

pc.

·Pip

e (ID

ø28.

58×I

Dø2

5.4)

···

P35

0,P4

00 1

pc.

PURY

-P400

YLM-

A1(-B

S)ø2

2.2 Br

azed

*1

ø22.2

Braz

ed *1

ø28.5

8 Braz

ed *1

ø28.5

8 Braz

ed *1

ø19.0

5 Braz

ed *1

600=150×4

150

70

19.5

1181

19.5

1220

740

303 1347

1650

77 895875

251

272

140

217

681(678~684) 29.529.5

8010

6080121

196

54 5720

586

2057

(740)

227

272

150

84 94

(60)

6060

236

145

1710

(60)

146

301

83

262 (60)

262

(

) Se

rvic

e va

lve

Botto

m v

iew

(

) A

Serv

ice

valv

e Fr

ont v

iew

PURY-P300, 350, 400YLM-A1 (-BS)Unit : mm

0000003483.BOOK 231 ページ 2015年1月14日 水曜日 午前11時12分

Page 20: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 232

R2

MEE14K035

2. EXTERNAL DIMENSIONS YKB/YLM

Unit : mm

Fron

tFr

ont

<Top

vie

w>

<Uni

t:mm

> <T

op v

iew

>

50 m

in.*

<Wal

l hei

ght l

imit>

Fro

nt :U

p to

the

unit

heig

ht

Back

:Up

to 5

00m

m fr

om

th

e un

it bo

ttom

Si

de :

Up

to th

e un

it he

ight

<Sid

e vi

ew>

M10

anc

hor b

olt

<fie

ld s

uppl

y re

quire

d>

Fixi

ng p

late

<fie

ld s

uppl

y re

quire

d>

<To be left open>

Fron

t

Wal

l <H

>

<To

be le

ft op

en>

Front

<Uni

t:mm

>

Front

Fixi

ng p

late

<fie

ld s

uppl

y re

quire

d>

M10

anc

hor b

olt

<fie

ld s

uppl

y re

quire

d>

Wal

l <H

>

<To be left open>

<To be left open>

<To be left open>

Fron

t

Wal

l <H

>

Wal

l <H

>

Wall <H>

Wall <H>

Front

Front

<To

be le

ft op

en>

Wal

l <H

>

Fron

t

Wal

l <H

>

<To be left open>

<To be left open>

Front

Front

Front

Wal

l <H

>W

all <

H>

Fron

t

<To be left open>

<To

be le

ft op

en>

Det

acha

ble

leg

Fig.

A (w

ithou

t det

acha

ble

legs

)

Fig.

B (w

ith d

etac

habl

e le

gs)

Fig.

C (w

ithou

t det

acha

ble

legs

)Fi

g.D

(with

det

acha

ble

legs

)De

tach

able

leg

1. R

equi

red

spac

e ar

ound

the

unit

●In

case

of s

ingl

e in

stal

latio

n 1

Sec

ure

enou

gh s

pace

aro

und

the

unit

as s

how

n in

the

figur

e be

low.

·With

a s

pace

of a

t lea

st

2 W

hen

the

heig

ht o

f the

wal

ls o

n th

e fro

nt,b

ack

or o

n th

e si

des<

H>

2. F

ound

atio

n w

ork

●In

case

of c

olle

ctiv

e in

stal

latio

n 1

Whe

n m

ultip

le u

nits

are

inst

alle

d ad

jace

nt to

eac

h ot

her,

secu

re e

noug

h sp

ace

to a

llow

fo

r air

circ

ulat

ion

and

wal

kway

bet

wee

n gr

oups

of u

nits

as

show

n in

the

figur

es b

elow

.2

At l

east

two

side

s m

ust b

e le

ft op

en.

3 A

s w

ith th

e si

ngle

inst

alla

tion,

add

the

heig

ht th

at e

xcee

ds th

e he

ight

lim

it<h>

to

the

figur

es th

at a

re m

arke

d w

ith a

n as

teris

k.4

If th

ere

is a

wal

l at b

oth

the

front

and

the

rear

of t

he u

nit,

inst

all u

p to

six

uni

ts

con

secu

tivel

y in

the

side

dire

ctio

n an

d pr

ovid

e a

spac

e of

100

0mm

or m

ore

as in

let s

pace

/

pas

sage

spa

ce fo

r eac

h si

x un

its.

300m

m to

the

wal

l on

the

back

of t

he u

nit

·With

a s

pace

of a

t lea

st

100m

m to

the

wal

l on

the

back

of t

he u

nit

e

xcee

ds th

e w

all h

eigh

t lim

it as

def

ined

bel

ow

add

the

heig

ht th

at e

xcee

ds th

e he

ight

lim

it <h

> to

the

figur

es th

at

are

mar

ked

with

an

aste

risk.

Unit heighthH

500h

H

30mm max.

15 m

in.*

50 m

in.*

100 min.* 450 min.*

300min.*

100

min

.30

min

.45

0 m

in.

450

min

.*45

0 m

in.

100

min

.*

450 min.*100 min.*

450 min.*

1000

min

.*

900min.300min.*

900min.300min.* 300min.*

15min.*

450m

in.

450m

in.

450 min.*300 min.*15

min

.*

30mm max.

1 T

ake

into

con

side

ratio

n th

e su

rface

stre

ngth

,wat

er d

rain

age

rout

e,

pip

ing

rout

e,an

d w

iring

rout

e w

hen

prep

arin

g th

e in

stal

latio

n si

te.

<

Not

e th

at th

e dr

ain

wat

er c

omes

out

of t

he u

nit d

urin

g op

erat

ion.

>2

Bui

ld th

e fo

unda

tion

in s

uch

way

that

the

corn

er o

f the

inst

alla

tion

leg

is

sec

urel

y su

ppor

ted

as s

how

n in

the

right

figu

re.(F

ig.A

,B)

W

hen

usin

g a

rubb

er is

olat

ing

cush

ion,

ple

ase

ensu

re it

is la

rge

enou

gh

to c

over

the

entir

e w

idth

of e

ach

of th

e un

it's

legs

.3

The

pro

trusi

on le

ngth

of t

he a

ncho

r bol

t mus

t not

exc

eed

30m

m.(F

ig.A

,B)

4 U

se fo

ur fi

xing

pla

tes

as s

how

n in

the

right

figu

re <

field

sup

ply

requ

ired>

w

hen

usin

g po

st-in

stal

led

anch

or b

olts

.(Fig

.C,D

)5

To

prev

ent s

mall

anim

als a

nd w

ater

and

snow

from

ent

ering

the

unit a

nd d

amag

ing its

par

ts,

clo

se th

e ga

p ar

ound

the

edge

s of

thro

ugh

hole

s fo

r pip

es a

nd w

ires

with

fi

ller p

late

s <f

ield

sup

ply

requ

ired>

.6

Whe

n th

e pi

pes

or c

able

s ar

e ro

uted

at t

he b

otto

m o

f the

uni

t,

mak

e su

re th

at th

e th

roug

h ho

le a

t the

bas

e of

the

unit

does

not

get

blo

cked

w

ith th

e in

stal

latio

n ba

se.

7 R

efer

to th

e In

stal

latio

n M

anua

l whe

n in

stal

ling

units

on

an in

stal

latio

n ba

se.

PURY-P300, 350, 400YLM-A1 (-BS)

0000003483.BOOK 232 ページ 2015年1月14日 水曜日 午前11時12分

Page 21: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 233

R2

MEE14K035

2. EXTERNAL DIMENSIONS YKB/YLM

150

600=150×4 70

19.5

831

4983

119

.5

740

1750

57

20

586

20

5754

303 13471650

77 89

587554

156

214

0

217

516

561

150

84

121196

8079

579

580

29.5 29.5

(740)

94

(60)

1710

(60)

6060

145

526

146

590

83

262 (60)

262

for s

now

hoo

d at

tach

men

t)

Disc

harg

e ai

r

Inta

ke

air

Con

trol b

ox

pane

l

8

1

54

63

7

(Mou

ntin

g pi

tch)

Fan

box

(Mak

e ho

le a

t the

pla

stic

fan

guar

d

<Sno

w h

ood

atta

chm

ent h

ole>

2×7-

ø4.6

Hol

e

Inta

ke

air

Inta

ke

air

Serv

ice

Left

side

vie

wFr

ont v

iew (Mou

ntin

g pi

tch)

Bo

ttom

vie

w

681(678~684)(Mounting pitch)

pane

l Se

rvic

e

Slin

g ho

le

Det

acha

ble

leg

(fron

t and

bac

k,3

poin

ts)

Not

e 2*

Top

view

2

2×3-

14×3

1 O

val h

ole

2×3-

14×2

0 O

val h

ole(

with

out d

etac

habl

e le

g)

<Low

pre

ssur

e>R

efrig

eran

t ser

vice

val

ve

<Hig

h pr

essu

re>

Ref

riger

ant s

ervi

ce v

alve

A

Con

nect

ing

pipe

spe

cific

atio

ns

*1 U

se th

e in

clud

ed c

onne

ctin

g pi

pe a

nd c

onne

ct to

the

refri

gera

nt s

ervi

ceva

lve

pipi

ng.

For tr

ansm

ission

cable

s

For w

ires

For p

ipes

NO

.U

sage

Spec

ifica

tions

Fr

ont th

roug

h hole

Botto

m thr

ough

hole

Fron

t thro

ugh h

ole

Fron

t thro

ugh h

ole

Botto

m thr

ough

hole

Botto

m thr

ough

hole

Fron

t thro

ugh h

ole

140

× 77

Kno

ckou

t hol

e

ø65

or ø

40 K

nock

out h

ole

ø52

or ø

27 K

nock

out h

ole

ø65

Knoc

kout

hol

e ø5

2 Kn

ocko

ut h

ole

ø34

Knoc

kout

hol

e

150

× 94

Kno

ckou

t hol

e

ø45

Knoc

kout

hol

e

Fron

t thro

ugh h

ole(U

ses w

hen t

winn

ing ki

t (op

tiona

l pa

rts) is

mou

nted.)

Mod

elD

iam

eter

Ref

riger

ant p

ipe

Serv

ice

valv

e Hi

gh p

ress

ure

Low

pres

sure

High

pre

ssur

eLo

w pr

essu

rePU

RY-P

450Y

LM-A

1(-BS

)ø2

8.58

ø2

2.2 Br

azed

*1ø2

8.58 B

razed

*1ø2

5.4

PURY

-P50

0YLM

-A1(-

BS)

Not

e1. P

leas

e re

fer t

o th

e ne

xt p

age

for i

nfor

mat

ion

rega

rdin

g ne

cess

ary

spac

ing

arou

nd th

e

un

it an

d fo

unda

tion

wor

k.

2.Th

e de

tach

able

leg

can

be re

mov

ed a

t site

.

3.At

bra

zing

of p

ipes

,wra

p th

e re

frige

rant

ser

vice

val

ve

w

ith w

et c

loth

and

kee

p th

e te

mpe

ratu

re o

f

re

frige

rant

ser

vice

val

ve u

nder

120

°C.

<Acc

esso

ries>

●Con

nect

ing

pipe

<Lo

w p

ress

ure>

<H

igh

pres

sure

>·P

ipe

(IDø2

5.4×

IDø2

2.2)

···

P450

,P50

0 1

pc.

·Elbo

w(ID

ø28.

58×O

Dø2

8.58

) ··· P

450,

P500

1pc

.

1 2 3 4 5 6 7 8

(

) Se

rvic

e va

lve

Botto

m v

iew

(

) A

Serv

ice

valv

e Fr

ont v

iew

PURY-P450, 500YLM-A1 (-BS)Unit : mm

0000003483.BOOK 233 ページ 2015年1月14日 水曜日 午前11時12分

Page 22: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 234

R2

MEE14K035

2. EXTERNAL DIMENSIONS YKB/YLM

Unit : mm

Wal

l <H

>

<Uni

t:mm

>

Fron

t

<Sid

e vi

ew>

<Top

vie

w>

<Uni

t:mm

>

· With

a s

pace

of a

t lea

st

Fron

t

●In

case

of c

olle

ctiv

e in

stal

latio

n1

Whe

n m

ultip

le u

nits

are

inst

alle

d ad

jace

nt to

eac

h ot

her,

secu

re e

noug

h sp

ace

to a

llow

fo

r air

circ

ulat

ion

and

wal

kway

bet

wee

n gr

oups

of u

nits

as

show

n in

the

figur

es b

elow

.2

At l

east

two

side

s m

ust b

e le

ft op

en.

3 A

s w

ith th

e si

ngle

inst

alla

tion,

add

the

heig

ht th

at e

xcee

ds th

e he

ight

lim

it<h>

to

the

figur

es th

at a

re m

arke

d w

ith a

n as

teris

k.4

If th

ere

is a

wal

l at b

oth

the

front

and

the

rear

of t

he u

nit,

inst

all u

p to

thre

e un

its

con

secu

tivel

y in

the

side

dire

ctio

n an

d pr

ovid

e a

spac

e of

100

0mm

or m

ore

as in

let s

pace

/

pas

sage

spa

ce fo

r eac

h th

ree

units

.

●In

case

of s

ingl

e in

stal

latio

n1

Sec

ure

enou

gh s

pace

aro

und

the

unit

as s

how

n in

the

figur

e be

low.

1. R

equi

red

spac

e ar

ound

the

unit

2 W

hen

the

heig

ht o

f the

wal

ls o

n th

e fro

nt,b

ack

or o

n th

e si

des<

H>

e

xcee

ds th

e w

all h

eigh

t lim

it as

def

ined

bel

ow

add

the

heig

ht th

at e

xcee

ds th

e he

ight

lim

it <h

> to

the

figur

es th

at

<Wal

l hei

ght l

imit>

Fro

nt :U

p to

the

unit

heig

ht

Back

:Up

to 5

00m

m fr

om

th

e un

it bo

ttom

1 T

ake

into

con

side

ratio

n th

e su

rface

stre

ngth

,wat

er d

rain

age

rout

e,

pip

ing

rout

e,an

d w

iring

rout

e w

hen

prep

arin

g th

e in

stal

latio

n si

te.

<

Not

e th

at th

e dr

ain

wat

er c

omes

out

of t

he u

nit d

urin

g op

erat

ion.

>2

Bui

ld th

e fo

unda

tion

in s

uch

way

that

the

corn

er o

f the

inst

alla

tion

leg

is

sec

urel

y su

ppor

ted

as s

how

n in

the

right

figu

re.(F

ig.A

,B)

W

hen

usin

g a

rubb

er is

olat

ing

cush

ion,

ple

ase

ensu

re it

is la

rge

enou

gh

to c

over

the

entir

e w

idth

of e

ach

of th

e un

it's

legs

.3

The

pro

trusi

on le

ngth

of t

he a

ncho

r bol

t mus

t not

exc

eed

30m

m.(F

ig.A

,B)

4 U

se fo

ur fi

xing

pla

tes

as s

how

n in

the

right

figu

re <

field

sup

ply

requ

ired>

w

hen

usin

g po

st-in

stal

led

anch

or b

olts

.(Fig

.C,D

)5

To

prev

ent s

mal

l ani

mal

s an

d w

ater

and

sno

w fr

om e

nter

ing

the

unit

and

dam

agin

g its

par

ts,

c

lose

the

gap

arou

nd th

e ed

ges

of th

roug

h ho

les

for p

ipes

and

wire

s w

ith

fille

r pla

tes

<fie

ld s

uppl

y re

quire

d>.

6 W

hen

the

pipe

s or

cab

les

are

rout

ed a

t the

bot

tom

of t

he u

nit,

m

ake

sure

that

the

thro

ugh

hole

at t

he b

ase

of th

e un

it do

es n

ot g

et b

lock

ed

with

the

inst

alla

tion

base

.7

Ref

er to

the

Inst

alla

tion

Man

ual w

hen

inst

allin

g un

its o

n an

inst

alla

tion

base

.

2. F

ound

atio

n w

ork

300m

m to

the

wal

l on

the

back

of t

he u

nit

· With

a s

pace

of a

t lea

st10

0mm

to th

e w

all o

nth

e ba

ck o

f the

uni

t

<Top

vie

w>

a

re m

arke

d w

ith a

n as

teris

k.

Si

de :

Up

to th

e un

it he

ight

Front

<To be left open>

Fron

t

<To be left open>

<To be left open>

Wal

l <H

>

Wal

l <H

>

Fron

t

Wal

l <H

>

Wall <H>

<To be left open>

Wall <H>

<To

be le

ft op

en>

<To

be le

ft op

en>

Front

Front

Front

Front

Front

Front

Wal

l <H

>

Wal

l <H

>

Fron

t

Wal

l <H

>

<To be left open>

<To be left open>

<To

be le

ft op

en>

Fron

t

Wal

l <H

>

<To be left open>

M10

anc

hor b

olt

<fie

ld s

uppl

y re

quire

d>

M10

anc

hor b

olt

<fie

ld s

uppl

y re

quire

d>

Deta

chab

le le

gFig.

A (w

ithou

t det

acha

ble

legs

)

Fig.

B (w

ith d

etac

habl

e le

gs)

Fixi

ng p

late

<fie

ld s

uppl

y re

quire

d>Fi

xing

pla

te<f

ield

sup

ply

requ

ired>

Fig.

C (w

ithou

t det

acha

ble

legs

)Fi

g.D

(with

det

acha

ble

legs

)

Det

acha

ble

leg

Unit heighth

500hH

H

30 m

in.

15 m

in.*

15 m

in.*

450 min.*

300 min.*

50 m

in.*

50 m

in.*

450 min.*

100 min.*

300 min.*450 min.*

100

min

.

450 min.*100 min.*

450

min

.*45

0 m

in.

450

min

.10

0 m

in.*

15 min.*

450

min

.45

0 m

in.

900 min.300 min.* 300 min.*

1000

min

.*

300 min.* 900 min.

30mm max. 30mm max.

PURY-P450, 500YLM-A1 (-BS)

0000003483.BOOK 234 ページ 2015年1月14日 水曜日 午前11時12分

Page 23: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 235

R2

MEE14K035

2. EXTERNAL DIMENSIONS YKB/YLM

PURY-P400, 450, 500YSLM-A1 (-BS)Unit : mm

1650

3092

074

0

(60)

1710

920

Left

view

Fron

t view

c

b

To B

C c

ontro

ller

aTw

inni

ng p

ipe(

Hig

h pr

essu

re)

e

Outd

oor u

nit 2

Deta

chab

le leg

Note

6*

f

To B

C c

ontro

ller

<opt

iona

l par

ts>

Outd

oor u

nit 1

Twin

ning

pip

e(Lo

w p

ress

ure)

<opt

iona

l par

ts> d

Disc

harg

e air

Inta

keai

rIn

take

air

Inta

keai

r

Not

e 1.

C

onne

ct th

e pi

pes

as s

how

n in

the

figur

e ab

ove.

Ref

er to

the

tabl

e ab

ove

for t

he p

ipe

size

.

2.

Twin

ning

pip

e (H

igh

pres

sure

) sho

uld

not b

e til

ted

mor

e th

an 1

5 de

gree

s fro

m th

e ho

rizon

tal p

lane

.

Be s

ure

to s

ee th

e In

stal

latio

n M

anua

l for

det

ails

of T

win

ning

pip

e in

stal

latio

n.

3.

The

pipe

sec

tion

befo

re th

e Tw

inni

ng p

ipe

(sec

tion

″a″in

the

figur

e) m

ust h

ave

at le

ast 5

00m

m o

f stra

ight

sec

tion

(*

incl

udin

g th

e st

raig

ht p

ipe

that

is s

uppl

ied

with

the

Twin

ning

pip

e).

4.

O

nly

use

the

Twin

ning

pip

e by

Mits

ubis

hi (o

ptio

nal p

arts

).

5.

Con

nect

the

outd

oor u

nit 1

with

the

Twin

ning

pip

e (L

ow p

ress

ure)

(sec

tion

″d″in

the

figur

e).

6.

Th

e de

tach

able

leg

can

be re

mov

ed a

t site

.

Twin

ning

pip

e co

nnec

tion

size

a bHi

gh p

ress

ure

Low

pres

sure

Com

pone

nt u

nit n

ame

Out

door

uni

t 1Pa

ckag

e un

it na

me

Out

door

Tw

inni

ng K

it(op

tiona

l par

ts)

BC co

ntroll

er~T

winn

ing pi

pe

PURY

-P40

0YSL

M-A1

(-BS)

Out

door

uni

t 2PU

RY-P

200Y

LM-A

1(-B

S)PU

RY-P

200Y

LM-A

1(-B

S)

ø22.

2

PURY

-P45

0YSL

M-A1

(-BS)

PURY

-P25

0YLM

-A1(

-BS)

PURY

-P20

0YLM

-A1(

-BS)

ø28.

58

CM

Y-R

100V

BK-A

ø15.

88c d

High

pre

ssur

eLo

w pr

essu

re

Com

pone

ntP4

00

unit

mod

elP2

00

- (No

te 5)

Twinn

ing K

it~O

utdo

or u

nitø1

5.88

e f

P200

ø19.

05

Uni

t mod

el

ø19.

05c d

P450

P250

- (No

te 5)

ø15.

88e f

P200

ø19.

05ø1

9.05

c d

P500

P250

- (No

te 5)

ø19.

05e f

P250

ø22.

2

PURY

-P50

0YSL

M-A1

(-BS)

PURY

-P25

0YLM

-A1(

-BS)

PURY

-P25

0YLM

-A1(

-BS)

0000003483.BOOK 235 ページ 2015年1月14日 水曜日 午前11時12分

Page 24: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 236

R2

MEE14K035

2. EXTERNAL DIMENSIONS YKB/YLM

PURY-P550YSLM-A1 (-BS)Unit : mm

Left

view

Fron

t view

Not

e 1.

C

onne

ct th

e pi

pes

as s

how

n in

the

figur

e ab

ove.

Ref

er to

the

tabl

e ab

ove

for t

he p

ipe

size

.

2.

Twin

ning

pip

e (H

igh

pres

sure

) sho

uld

not b

e til

ted

mor

e th

an 1

5 de

gree

s fro

m th

e ho

rizon

tal p

lane

.

Be s

ure

to s

ee th

e In

stal

latio

n M

anua

l for

det

ails

of T

win

ning

pip

e in

stal

latio

n.

3.

The

pipe

sec

tion

befo

re th

e Tw

inni

ng p

ipe

(sec

tion

″a″in

the

figur

e) m

ust h

ave

at le

ast 5

00m

m o

f stra

ight

sec

tion

(*

incl

udin

g th

e st

raig

ht p

ipe

that

is s

uppl

ied

with

the

Twin

ning

pip

e).

4.

O

nly

use

the

Twin

ning

pip

e by

Mits

ubis

hi (o

ptio

nal p

arts

).

5.

Con

nect

the

outd

oor u

nit 1

with

the

Twin

ning

pip

e (L

ow p

ress

ure)

(sec

tion

″d″in

the

figur

e).

6.

Th

e de

tach

able

leg

can

be re

mov

ed a

t site

.

Twin

ning

pip

e co

nnec

tion

size

ø28.

58a b

High

pre

ssur

eLo

w pr

essu

re

Com

pone

nt u

nit n

ame

Out

door

uni

t 1Pa

ckag

e un

it na

me

Out

door

Tw

inni

ng K

it(op

tiona

l par

ts)

BC co

ntroll

er~T

winn

ing pi

pe

PURY

-P55

0YSL

M-A1

(-BS)

Out

door

uni

t 2PU

RY-P

300Y

LM-A

1(-B

S)PU

RY-P

250Y

LM-A

1(-B

S)

ø28.

58ø1

9.05

c dHi

gh pr

essu

reLo

w pr

essu

re

Com

pone

ntP5

50

unit

mod

elP3

00

- (No

te 5)

Twinn

ing K

it~O

utdoo

r unit

ø19.

05P2

50

ø22.

2e f

Uni

t mod

el

CM

Y-R

100V

BK2

Disc

harg

e air

Inta

keai

r

Outd

oor u

nit 1

c

b

To B

C c

ontro

ller

aTw

inni

ng p

ipe<

Hig

h pr

essu

re>

e

Outd

oor u

nit 2

Deta

chab

le leg

Note

6*

f

Twinn

ing p

ipe(L

ow p

ress

ure)

<opt

iona

l par

ts>

To B

C c

ontro

ller

<opt

iona

l par

ts>

d

Inta

keai

rIn

take

air

740

1650

3092

012

20

(60)

1710

0000003483.BOOK 236 ページ 2015年1月14日 水曜日 午前11時12分

Page 25: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 237

R2

MEE14K035

2. EXTERNAL DIMENSIONS YKB/YLM

PURY-P600, 650, 700, 750, 800YSLM-A1 (-BS)Unit : mm

1650

3012

2074

0

(60)

1710

1220

c dHi

gh pr

essu

reLo

w pr

essu

re

Com

pone

ntun

it m

odel

- (No

te 5)

Twinn

ing K

it~O

utdoo

r unit

c de f

Uni

t mod

el

- (No

te 5)

ø19.

05P650

P350

ø19.

05ø2

2.2

ø19.

05P600

ø19.

05

P300

ø22.

2

P300

e f

P300

c d- (

Note

5)ø1

9.05P7

00P3

50

ø19.

05ø2

8.58

e f

P350

c d- (

Note 5

)ø2

2.2P7

50P4

00

ø19.

05ø2

8.58

e f

P350

c d- (

Note 5

)ø2

2.2P8

00P4

00

ø22.

2ø2

8.58

e f

P400

Twin

ning

pip

e co

nnec

tion

size a b

High

pres

sure

Low

pres

sure

Comp

onen

t unit

name

Out

door

uni

t 1Pa

ckag

e un

it na

me

Outd

oor T

winn

ing K

it(op

tiona

l par

ts)BC

con

trolle

r

Out

door

uni

t 2

PURY

-P70

0YSL

M-A1

(-BS)

PURY

-P35

0YLM

-A1(

-BS)

ø28.

58

PURY

-P75

0YSL

M-A1

(-BS)

PURY

-P40

0YLM

-A1(

-BS)

PURY

-P35

0YLM

-A1(

-BS)

ø28.

58

PURY

-P80

0YSL

M-A1

(-BS)

PURY

-P40

0YLM

-A1(

-BS)

PURY

-P40

0YLM

-A1(

-BS)

ø34.

93

PURY

-P35

0YLM

-A1(

-BS)

ø34.

93ø2

8.58

ø34.

93

CM

Y-R

200V

BK2

CM

Y-R

200V

BK2

CM

Y-R

200V

BK2

PURY

-P65

0YSL

M-A1

(-BS)

PURY

-P35

0YLM

-A1(

-BS)

PURY

-P30

0YLM

-A1(

-BS)

ø28.

58

PURY

-P60

0YSL

M-A1

(-BS)

PURY

-P30

0YLM

-A1(

-BS)

PURY

-P30

0YLM

-A1(

-BS)

ø28.

58ø2

8.58

CM

Y-R

100V

BK2

CM

Y-R

100V

BK2

ø28.

58 ~

Twin

ning

pip

e

Left

view

Outd

oor u

nit 1

Fron

t view

c

bae

Outd

oor u

nit 2

Detac

hable

leg

Note

6*

Twinn

ing p

ipe(L

ow p

ress

ure)

<opt

ional

parts

>

d

Twin

ning

pip

e<Hi

gh p

ress

ure>

To B

C co

ntro

ller

<opt

iona

l par

ts>

fTo

BC

cont

rolle

r

Note

1.

Conn

ect t

he p

ipes

as

show

n in

the

figur

e ab

ove.

Ref

er to

the

tabl

e ab

ove

for t

he p

ipe

size.

2.

Twi

nnin

g pi

pe (H

igh

pres

sure

) sho

uld

not b

e tilt

ed m

ore

than

15

degr

ees

from

the

horiz

onta

l pla

ne.

Be

sur

e to

see

the

Inst

alla

tion

Man

ual f

or d

etai

ls of

Twi

nnin

g pi

pe in

stal

latio

n.

3. T

he p

ipe

sect

ion

befo

re th

e Tw

inni

ng p

ipe

(sec

tion

″a″in

the

figur

e) m

ust h

ave

at le

ast 5

00m

m o

f stra

ight

sec

tion

(*i

nclu

ding

the

stra

ight

pip

e th

at is

sup

plie

d wi

th th

e Tw

inni

ng p

ipe)

.

4. O

nly

use

the

Twin

ning

pip

e by

Mits

ubish

i (op

tiona

l par

ts).

5.

Con

nect

the

outd

oor u

nit 1

with

the

Twin

ning

pip

e

(Low

pre

ssur

e) (s

ectio

n ″d

″in th

e fig

ure)

.

6. T

he d

etac

habl

e le

g ca

n be

rem

oved

at s

ite.

Disc

harg

e air

Inta

keai

rIn

take

air

Inta

keai

r

0000003483.BOOK 237 ページ 2015年1月14日 水曜日 午前11時12分

Page 26: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 238

R2

MEE14K035

2. EXTERNAL DIMENSIONS YKB/YLM

PURY-P850YSLM-A1 (-BS)Unit : mm

1750

3012

2074

0

1650 (60)

1710

d

f

ea b

cTw

inni

ng p

ipe<

Hig

h pr

essu

re>

<opt

iona

l par

ts> To

BC

con

trolle

r

To B

C c

ontro

ller

Twin

ning

pip

e(Lo

w p

ress

ure)

<o

ptio

nal p

arts

>

Inta

keai

r

Outd

oor u

nit 1

Ou

tdoo

r unit

2

Left

view

Fron

t view

Inta

keai

rIn

take

air

Not

e 1.

C

onne

ct th

e pi

pes

as s

how

n in

the

figur

e ab

ove.

Ref

er to

the

tabl

e ab

ove

for t

he p

ipe

size

.

2.

Twin

ning

pip

e (H

igh

pres

sure

) sho

uld

not b

e til

ted

mor

e th

an 1

5 de

gree

s fro

m th

e ho

rizon

tal p

lane

.

Be s

ure

to s

ee th

e In

stal

latio

n M

anua

l for

det

ails

of T

win

ning

pip

e in

stal

latio

n.

3.

The

pipe

sec

tion

befo

re th

e Tw

inni

ng p

ipe

(sec

tion

″a″in

the

figur

e) m

ust h

ave

at le

ast 5

00m

m o

f stra

ight

sec

tion

(*

incl

udin

g th

e st

raig

ht p

ipe

that

is s

uppl

ied

with

the

Twin

ning

pip

e).

4.

O

nly

use

the

Twin

ning

pip

e by

Mits

ubis

hi (o

ptio

nal p

arts

).

5.

Con

nect

the

outd

oor u

nit 1

with

the

Twin

ning

pip

e (L

ow p

ress

ure)

(sec

tion

″d″in

the

figur

e).

6.

Th

e de

tach

able

leg

can

be re

mov

ed a

t site

.

Twin

ning

pip

e co

nnec

tion

size

ø28.

58a b

High

pre

ssur

eLo

w pr

essu

re

Com

pone

nt u

nit n

ame

Out

door

uni

t 1Pa

ckag

e un

it na

me

Out

door

Tw

inni

ng K

it(op

tiona

l par

ts)

BC co

ntro

ller~

Twinn

ing p

ipe

PURY

-P85

0YSL

M-A

1(-B

S)

Out

door

uni

t 2PU

RY-P

450Y

LM-A

1(-B

S)PU

RY-P

400Y

LM-A

1(-B

S)

ø41.

28ø2

2.2

c dHi

gh p

ress

ure

Low

pres

sure

Com

pone

ntP8

50

unit

mod

elP4

50

- (No

te 5

)Tw

inni

ng K

it~O

utdo

or u

nit

ø22.

2e f

P400

ø28.

58

Detac

hable

leg

Note

6 *

Uni

t mod

el

Disc

harg

e air

CM

Y-R

200X

LVBK

0000003483.BOOK 238 ページ 2015年1月14日 水曜日 午前11時12分

Page 27: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 239

R2

MEE14K035

2. EXTERNAL DIMENSIONS YKB/YLM

PURY-P900YSLM-A1 (-BS)Unit : mm

1750

3074

0

1650 (60)1710

1750

d

f

ea b

cTw

inni

ng p

ipe<

Hig

h pr

essu

re>

<opt

iona

l par

ts> To

BC

con

trolle

r

To B

C c

ontro

ller

Twin

ning

pip

e(Lo

w p

ress

ure)

<o

ptio

nal p

arts

>

Inta

keai

r

Outd

oor u

nit 1

Left

view

Fron

t view

Inta

keai

rIn

take

air

Deta

chab

le leg

No

te 6

*

Outd

oor u

nit 2

Not

e 1.

C

onne

ct th

e pi

pes

as s

how

n in

the

figur

e ab

ove.

Ref

er to

the

tabl

e ab

ove

for t

he p

ipe

size

.

2.

Twin

ning

pip

e (H

igh

pres

sure

) sho

uld

not b

e til

ted

mor

e th

an 1

5 de

gree

s fro

m th

e ho

rizon

tal p

lane

.

Be s

ure

to s

ee th

e In

stal

latio

n M

anua

l for

det

ails

of T

win

ning

pip

e in

stal

latio

n.

3.

The

pipe

sec

tion

befo

re th

e Tw

inni

ng p

ipe

(sec

tion

″a″in

the

figur

e) m

ust h

ave

at le

ast 5

00m

m o

f stra

ight

sec

tion

(*

incl

udin

g th

e st

raig

ht p

ipe

that

is s

uppl

ied

with

the

Twin

ning

pip

e).

4.

O

nly

use

the

Twin

ning

pip

e by

Mits

ubis

hi (o

ptio

nal p

arts

).

5.

Con

nect

the

outd

oor u

nit 1

with

the

Twin

ning

pip

e (L

ow p

ress

ure)

(sec

tion

″d″in

the

figur

e).

6.

Th

e de

tach

able

leg

can

be re

mov

ed a

t site

.

ø22.

2c d

High

pre

ssur

eLo

w pr

essu

re

Com

pone

ntP9

00

unit

mod

elP4

50

- (No

te 5)

Twin

ning

Kit

~Out

door

uni

te f

P450

ø28.

58

Uni

t mod

el

ø22.

2

Twin

ning

pip

e co

nnec

tion

size

ø28.

58a b

High

pre

ssur

eLo

w pr

essu

re

Com

pone

nt u

nit n

ame

Out

door

uni

t 1Pa

ckag

e un

it na

me

Out

door

Tw

inni

ng K

it(op

tiona

l par

ts)

BC co

ntroll

er~T

winn

ing pi

pe

PURY

-P90

0YSL

M-A

1(-B

S)

Out

door

uni

t 2PU

RY-P

450Y

LM-A

1(-B

S)PU

RY-P

450Y

LM-A

1(-B

S)

ø41.

28

Disc

harg

e air

CM

Y-R

200X

LVBK

0000003483.BOOK 239 ページ 2015年1月14日 水曜日 午前11時12分

Page 28: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 240

R2

MEE14K035

3. CENTER OF GRAVITY YKB/YLM

3. CENTER OF GRAVITY

Y

681

740

1407

Z

1060 80

1220

X

1750

795

X

80795

Y

681

740

1407

Z

PURY-P300, 350, 400YLM-A1 (-BS)

Model X Y ZUnit : mm

455

455

455

314

314

314

650

650

650

PURY-P300YLM-A1(-BS)

PURY-P400YLM-A1(-BS)

PURY-P350YLM-A1(-BS)

60

Y

681

740

1407

Z

1710

760 80

920

X

PURY-P200, 250YLM-A1 (-BS)

Model X Y ZUnit : mm

344 309 691PURY-P200YLM-A1(-BS)

344 309 691PURY-P250YLM-A1(-BS)

1710

60

PURY-P450, 500YLM-A1 (-BS)

Unit : mm

718 327 710

Model X Y Z

PURY-P500YLM-A1(-BS)

718 327 710PURY-P450YLM-A1(-BS)

60

1710

0000003483.BOOK 240 ページ 2015年1月14日 水曜日 午前11時12分

Page 29: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 241

R2

MEE14K035

4. ELECTRICAL WIRING DIAGRAMS YKB/YLM

4. ELECTRICAL WIRING DIAGRAMS

Line

ar e

xpan

sion

val

ve (f

or th

e co

ntro

l of

evap

orat

ing

tem

pera

ture

)

RSH0

1/02,R

SH1

For c

urre

nt d

etec

tion

C30

~C37

Cap

acito

r (in

verte

r mai

n ci

rcui

t)

LC

hoke

coi

l (fo

r hig

h fre

quen

cy n

oise

redu

ctio

n)

SV4a

,b,d

Hea

t exc

hang

er c

apac

ity c

ontro

l

R1,

5R

esis

tor

For i

nrus

h cu

rrent

pre

vent

ion

Subc

oole

d liq

uid

refri

gera

ntte

mpe

ratu

re

Pipe

tem

pera

ture

Out

door

uni

t hea

t exc

hang

erca

paci

ty c

ontro

lSV

5b

SV1a

21S4

aSy

mbo

l

<Sym

bol e

xpla

natio

n>

63H

1

63H

S163

LS72

C

CT12

,CT2

2,CT3

LEV5

a

DC

L

Sole

noid

valv

eFo

r ope

ning

/clo

sing

the

bypa

ssci

rcui

t und

er th

e O

/S

4-w

ay v

alve

(Coo

ling/

Hea

ting

switc

hing

)Ex

plan

atio

n

Pres

sure

sens

or

Pres

sure

switc

hH

igh

pres

sure

pro

tect

ion

for t

heou

tdoo

r uni

tD

isch

arge

pre

ssur

eLo

w p

ress

ure

Mag

netic

rela

y(in

verte

r mai

n ci

rcui

t)

Cur

rent

sen

sor(A

C)

DC

reac

tor

Z25

THH

S

TH7

TH6

TH5

TH4

TH3

TB7

TB3

TB1

SV7,

SV9

Ther

mis

tor

Dis

char

ge p

ipe

tem

pera

ture

ACC

inle

t pip

e te

mpe

ratu

re

OA

tem

pera

ture

IPM

tem

pera

ture

Func

tion

setti

ng c

onne

ctor

Pow

er s

uppl

yIn

door

/Out

door

tran

smis

sion

cabl

eC

entra

l con

trol t

rans

mis

sion

cabl

e

Term

inal

bloc

k

For o

peni

ng/c

losi

ng th

e by

pass

circ

uit

*1.S

ingl

e-do

tted

lines

indi

cate

wiri

ng n

ot s

uppl

ied

with

the

unit.

*2.D

ot-d

ash

lines

indi

cate

the

cont

rol b

ox b

ound

arie

s.*3

.Ref

er to

the

Dat

a bo

ok fo

r con

nect

ing

inpu

t/out

put

si

gnal

con

nect

ors.

*4.D

aisy

-cha

in te

rmin

als

(TB3

) on

the

outd

oor u

nits

in th

e

sam

e re

frige

rant

sys

tem

toge

ther

.*5

.Fas

ton

term

inal

s ha

ve a

lock

ing

func

tion.

M

ake

sure

the

term

inal

s ar

e se

cure

ly lo

cked

in p

lace

af

ter i

nser

tion.

Pre

ss th

e ta

b on

the

term

inal

s to

re

mov

ed th

em.

*6.C

ontro

l box

hou

ses

high

-vol

tage

par

ts.

Be

fore

insp

ectin

g th

e in

side

of t

he c

ontro

l box

,turn

off

th

e po

wer

,kee

p th

e un

it of

f for

at l

east

10

min

utes

, and

co

nfirm

that

the

volta

ge b

etw

een

FT-P

and

FT-

N o

n

INV

Boar

d ha

s dr

oppe

d to

DC

20V

or le

ss.

SV10

,SV1

1Fo

r ope

ning

/clo

sing

the

defro

stci

rcui

t

TH9,

TH11

Heat

exc

hang

er o

utlet

pipe

tem

pera

ture

*7.D

iffer

ence

of a

pplia

nce.

P200

/250

/300

/350

/400

Mod

el n

ame

*7 d

o no

t exi

stap

plia

nce

EP20

0/25

0/30

0/35

0*7

exi

st

F121

DC

700V

4A T

C151

,C15

2

RSH0

1/02

12

L3N

red

CN

PS

1 321 TP

1TP2

TB3

23

TB7

M1

M2

M1

M2

S

1

512

34

12

12

132

346

36

1

53

1

2 2

CN

82bl

ue

13 4C

N83

blac

k

L1L2

31

Fan

mot

or(H

eat e

xcha

nger

)

U V W

CN

INV

7 14

34

CN

4bl

ack

1

13

231

3

SW00

1

14

CN

2

1

12

1

3

31

432

23

1

1

CN

SNR

TH4

4

1

1

1

CN

211

gree

n

2312

332

1

U

5

2

54321

1

32

1

23

123

1

CN

6

21

2

yello

wCN

POW

1

654

X10

X12

ON

X08

Uni

t add

ress

setti

ng

CT1

2

CN5

red

D1R4

-Z5

1

+

3 16

whi

te

12

34

3gr

een

CN

62

CN

990

gree

n

CN

213

gree

n

CN

TYP4

F4 AC25

0V6.3

A T

R5

CN

201

Z25

TH5

TH6

SWU2

LED

1

SW6

10

Con

trol B

oard

TH3

CN

40

63H

S1

CN

41

TH7

15

234

1

SW4

LED

3

5

LEV5

a

33

SET

UP(

SW6-

10)

SC-V

CT2

2

SC-U

V

CN4

blue

red

M

OFF

t

blac

k

CN

506

red

CN

TYP2

blac

k

6

yello

wC

N3K

*3

Com

pres

sor O

N/O

FF o

utpu

tEr

ror d

etec

tion

outp

ut

TB21

DC12

VCN

51

SV5b

CN1A

U

CN

2

blue

CN

3N

1 3

+

3

4

TB1

CN

1B

TB7

Pow

erse

lect

ing

conn

ecto

r

CNVD

C

1

IPM

2

5

6

L3N

DC

L

blac

k

72C

white

red

26

ON

OFF

M-N

ET p

ower

supp

ly c

ircui

t

12

M-N

ET B

oard

Indo

or/O

utdo

ortra

nsm

issio

nca

ble

INV

Boar

dre

dTB

23TB

24

L2L1

+

ON1'

sdi

git

THHS

CN

102

C31,

C33,

C35,

C37

14

11

W

10's

digi

t

OFF

LED2

:Nor

mal

ope

ratio

n(Li

t)/ E

rror(B

link)

CN

S2ye

llow

CN

DC

red

red

MS 3~

22

C10

0*5

LED

1:Po

wer

sup

ply

toIn

door

/Out

door

trans

mis

sion

line

+

blac

k

Cent

ral c

ontro

ltra

nsm

issio

nca

ble

*6

SC-L

1

ONOF

F

FT-N

R30,

R32,

R34

Mot

or(C

ompr

esso

r)

red

CN

3S

1

CN04

red

CN

43ye

llow

1

SC-P

2

P

CN

61gr

een

CN

202

red

C30

,C32

,C

34,C

36

6

N

CN1

LED1

:Nor

mal

ope

ratio

n(Li

t)

/ Er

ror(B

link)

*4

SC-W

SC-L

3

2

CN

RYB

P

63H

1

4

1

SW5

10

5

CN

3D

1

CPU

pow

ersu

pply

circ

uit

blac

kC

NAC

2

1 *3

ONOF

F

10

SWU1

whi

te

CN

212

red

SC-L

2

62

CN

80

CN

TYP5

gree

n

LED4

:CPU

in op

eratio

n

LED1

:Norm

al op

eratio

n(Lit)

/ Er

ror(B

link)

CN

801

red

5

˚IP

M4

SC-P

1

FT-P

blac

kre

d

DB1

CT3

C1

CNTY

Pbl

ack

blac

k

TB22

SWP1

RSH

1

R6

C11

FAN

Boa

rd

63LS

ZNR

1U

L

Noi

seFi

lter

2

CN

507

blac

k

CN

508

blue

3 3

3

6 6

4

CN3

gree

n

SV9

Func

tion

setti

ng

LED

1D

ispl

ayse

tting

/Fu

nctio

nse

tting

72C

Noi

se fi

lter

Noi

se fi

lter

67

red

Surg

eab

sorb

er

12

1 1

CN

LVA

1

F01

AC25

0V3.1

5A T

MS 3~

white

blac

k

1

CN

ITre

dL1

L2L3

N

R31,

R33,

R35

3

4 1

R1,R

5

X05

X13

X06

X14

3 35 51 16 6

CN

505

CN

509

yello

w

13

CN

AC

CN

81gr

een

12

534

4

4C

N2

SV1a

SV4b

SV4d

SV4a

21S4

a

Pow

er S

ourc

e

3N~

50

/60H

z

380/

400/

415V

t ˚ t ˚ t ˚ t ˚ t ˚ t ˚t ˚

TH11

CN

TYP1

blac

k12

TH9

5

X09

SV7

*7

3 1C

N50

4SV

11

3 1C

N50

3SV

10

X03

yello

w

gree

n

X04

CN

110

blac

k

12

Pow

er fa

ilure

dete

ctio

n ci

rcui

tUZN

R40

0

1

PURY-P200, 250, 300, 350, 400YLM-A1(-BS)

0000003483.BOOK 241 ページ 2015年1月14日 水曜日 午前11時12分

Page 30: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 242

R2

MEE14K035

4. ELECTRICAL WIRING DIAGRAMS YKB/YLM

FT2-

NF1

01D

C70

0V4A

T

FT2-

P

C10

2

R10

4~R

106

R10

1~R

103

C10

1+

+

F121

DC

700V

4A T

C15

1,C

152

F121

DC

700V

4A T

C15

1,C

152

RSH0

1/02

FAN

Boa

rd

CN3

green1 3

CONN

ECT

Boar

d

54321

11

23

CN2A

12

3C

N2

M2

CPU

pow

ersu

pply

circ

uit

M1

CN33

2bl

ue12

12

X05

X06

35 16

CN

505

13

WVU

Fan

mot

or(H

eat e

xcha

nger

)

CN

4bl

ack

M1

LED1

:Norm

al op

eratio

n(Lit)

/ Erro

r(Blin

k)LE

D4:C

PU in

opera

tion

3

IPM

CN

VDC

1

CN

81gr

een

CN

80

SW00

1

42

L3N

23

6 5 4 3 2 1 211 6OF

FON

4 1 4 17

CN

INV

14

red

CN

PS

1 321

TP1

TP2

TB3

23

CN

201

blue

CN

4Abl

ack

TB7

S

CN

AC5

1234

CN

81gr

een

5431

12

LEV5

b

M

123461234

1 2

6

36 53

1

CN

202

gree

n3

L1L2

31

3 4

blac

kC

N10

3

Fan

mot

or(H

eat e

xcha

nger

)

U V WC

NIN

V

7 14

34

1

13

3

SW00

1

14

12

CN

2

1

5

1

134

12

1

3

31

432

23

1

1

CN

SNR

M2

TH4

44

1

1

1

CN

211

gree

n

23

123

32

1

SV1a

U

CN

83bl

ack

21S4

a

Pow

er S

ourc

e3N

~50

/60H

z38

0/40

0/41

5V

5

2

CN

104

4 4

1 1

1

32N

oise

filte

r

1

23

Surg

eab

sorb

er

red

blac

k

MS 3~

2

123

1

CN

6

1

21

MS 3~

3

2

CN

82bl

ue

yello

wCN

POW

1

654

X10

ON

X08

X12

X14

X07

X11

X13

Uni

t add

ress

setti

ng

CT1

2

C31

,C33

,C

35,C

37

CN

5re

dD

1R

4

-Z5

1

3 3 35 5 51 1 16 6 6

whi

te

12

34

3gr

een

CN

62

SET

UP(

SW6-

10)

LED

1D

ispl

ayse

tting

/Fu

nctio

nse

tting

CN51

DC12

V

Func

tion

setti

ng

CN

990

gree

n

CN

213

gree

n

CN

TYP4

F4 AC25

0V6.

3A T

R5

*3 Com

pres

sor O

N/O

FF o

utpu

tEr

ror d

etec

tion

outp

utC

N20

1

Z25

TH5

TH6

SWU2

LED

1

R31

,R33

,R

35R

30,R

32,

R34

SW6

10

Con

trol B

oard

TH3

CN

40

63H

S1

CN

41

TH7

15

234

1

SW4

LED

3

5

LEV5

a

33

SC-V

CT2

2

SC-U

V

+

CN4

blue

red

M

+

OFF

blac

k

CN

506

red

CN

508

blue

CN

509

yello

w

CN

TYP2

blac

k

6

yello

wC

N3K

*3

TB21

SV5b

SV4d

SV4c

SV4b

SV4a

CN1A

U

CN

2

blue

CN

3N

+

3

21S4

b

TB1

CN

1B

TB7

Pow

erse

lect

ing

conn

ecto

r

CN

VDC

1

IPM

2

6

L3N

DC

L

blac

k

72C

white

red

26

ON

OFF

M-N

ET p

ower

supp

ly c

ircui

t

12

M-N

ET B

oard

Indo

or/O

utdo

ortra

nsm

issi

onca

ble

INV

Boar

dre

dTB

23TB

24

L2L1

+

ON1'

sdi

git

THH

S

CN

102

14

11

W

10's

digi

t

OFF

LED

2:No

rmal

ope

ratio

n(Li

t)/ E

rror(B

link)

CN

S2ye

llow

CN

DC

red

red

MS 3~

22

C10

0 *5

LED

1:Po

wer

sup

ply

toIn

door

/Out

door

trans

mis

sion

line

6

blac

k

Cen

tral c

ontro

ltra

nsm

issi

onca

ble

*6

SC-L

1

ONOF

F

FT-N

Mot

or(C

ompr

esso

r)

red

CN

3S

1

CN

04re

d

CN

43ye

llow

1

SC-P

2

P

CN

61gr

een

CN

202

red

6

N

CN

1

1 2

LED

1:N

orm

al o

pera

tion(

Lit)

/ Er

ror(B

link)

*4

SC-W

SC-L

3

2

CN

RYB

P

63H

1

4

1

SW5

10

5

CN

3D

1

blac

kCN

AC2

1ON

OFF

10

SWU1

whi

te

CN

212

red

SC-L

2

3

6

2

CN

80

4

CN

TYP5

gree

n

LED4

:CPU

in op

eratio

n

LED1

:Norm

al op

eratio

n(Lit)

/ Erro

r(Blin

k)

5

CN80

1re

d

CN

SNR

5

IPM4

SC-P

1

FT-P

blac

k

C30

,C32

,C

34,C

36

red

DB1

CT3

C1

CNTY

Pbl

ack

R1,

R5

blac

k

TB22

SWP1

RSH

1

R6

C11

FAN

Boa

rd

63LS

ZNR

1U

L

Noi

seFi

lter

2

CN

507

blac

k3

3

6

4

SV9

Noi

se fi

lter

72C

67

red

12

1

CN

LVA

CN

LVB

red

1

F01

AC25

0V3.1

5A T

whi

tebl

ack

1

CN

ITre

dL1

L2L3

N

4 1X0

9

SV7

*75

TH12

2

t ˚

t ˚

t ˚ t ˚ t ˚ t ˚ t ˚ t ˚ t ˚

CN

TYP1

blac

kTH

912

TH11

3 1C

N50

4SV

11

3 1C

N50

3SV

10

RSH0

1/02

X03

X04

gree

n

yello

w

CN

110

blac

k

12

Pow

er fa

ilure

dete

ctio

n ci

rcui

tUZN

R40

0

R1,

5R

esis

tor

For i

nrus

h cu

rrent

pre

vent

ion

RSH0

1/02,R

SH1

For c

urre

nt d

etec

tion

Indo

or/O

utdo

or tr

ansm

issi

on c

able

Line

ar e

xpan

sion

val

ve (f

or th

e co

ntro

l of

evap

orat

ing

tem

pera

ture

)

Cen

tral c

ontro

l tra

nsm

issi

on c

able

Subc

oole

d liq

uid

refri

gera

ntte

mpe

ratu

re

SV4a

,b,c

,d

Pipe

tem

pera

ture

Out

door

uni

t hea

t exc

hang

erca

paci

ty c

ontro

lSV

5b

C30

~C37

Cap

acito

r (in

verte

r mai

n ci

rcui

t)

LC

hoke

coi

l (fo

r hig

h fre

quen

cy n

oise

redu

ctio

n)

SV1a

Hea

t exc

hang

er c

apac

ity c

ontro

l

21S4

aSy

mbo

l

<Sym

bol e

xpla

natio

n>

63H

1

63H

S163

LS72

C

21S4

b

CT12

,CT2

2,CT3

LEV5

a,b

DC

L

Sole

noid

valv

eFo

r ope

ning

/clo

sing

the

bypa

ssci

rcui

t und

er th

e O

/S

Hea

t exc

hang

er c

apac

ity c

ontro

l4-

way

val

veEx

plan

atio

n

Pres

sure

sens

or

Coo

ling/

Hea

ting

switc

hing

Pres

sure

switc

hH

igh

pres

sure

pro

tect

ion

for t

heou

tdoo

r uni

tD

isch

arge

pre

ssur

eLo

w p

ress

ure

Mag

netic

rela

y(in

verte

r mai

n ci

rcui

t)

Cur

rent

sen

sor(A

C)

DC

reac

tor

Z25

THH

S

TH7

TH6

TH5

TH4

TH3

TB7

TB3

TB1

SV7,

SV9

Ther

mis

tor

Dis

char

ge p

ipe

tem

pera

ture

ACC

inle

t pip

e te

mpe

ratu

re

OA

tem

pera

ture

IPM

tem

pera

ture

Func

tion

setti

ng c

onne

ctor

Pow

er s

uppl

yTe

rmin

albl

ock

For o

peni

ng/c

losi

ng th

e by

pass

circ

uit

*1.S

ingle-

dotte

d lin

es in

dicat

e wi

ring

not s

uppli

ed

with

the

unit.

*2.D

ot-d

ash

lines

indic

ate

the

cont

rol b

ox b

ound

aries

.*3

.Ref

er to

the

Data

boo

k for

conn

ectin

g inp

ut/o

utpu

t

signa

l con

necto

rs.

*4.D

aisy-

chain

term

inals

(TB3

) on

the

outd

oor u

nits i

n

the

sam

e re

frige

rant

syste

m to

geth

er.

*5.F

asto

n te

rmina

ls ha

ve a

lock

ing fu

nctio

n.

Mak

e su

re th

e te

rmina

ls ar

e se

cure

ly loc

ked

in pla

ce

afte

r ins

ertio

n. P

ress

the

tab

on th

e te

rmina

ls to

re

mov

ed th

em.

*6.C

ontro

l box

hou

ses h

igh-v

oltag

e pa

rts. B

efor

e

inspe

cting

the

inside

of t

he co

ntro

l box

,turn

off

th

e po

wer,

keep

the

unit o

ff fo

r at le

ast 1

0 m

inute

s,

and

conf

irm th

at th

e vo

ltage

bet

ween

FT-

P an

d FT

-N o

n

INV

Boar

d ha

s dro

pped

to D

C20V

or l

ess.

*7.D

iffere

nce

of a

pplia

nce.

P450

/500

Mod

el n

ame

*7 d

o no

t exi

stap

plia

nce

EP40

0/45

0*7

exi

st

SV10

,SV1

1Fo

r ope

ning

/clo

sing

the

defro

stci

rcui

t

TH9,T

H11,T

H12

Heat

exc

hang

er o

utle

t pip

e te

mpe

ratu

re

PURY-P450, 500YLM-A1(-BS)

0000003483.BOOK 242 ページ 2015年1月14日 水曜日 午前11時12分

Page 31: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 243

R2

MEE14K035

5. SOUND LEVELS YKB/YLM

5. SOUND LEVELS

Depending on the operation conditions, the unit generates noise caused by valve actuation, refrigerant flow, and pressure changes when operating normally. Please consider to avoid location where quietness is required.For BC controller, it is recommended to be installed in places such as ceilings of corridor, rest rooms and plant rooms.

Measurementlocation

1m

1m

Measurement conditionPURY-P200, 250YLM-A1(-BS)

Measurementlocation

1m

1m

Measurement conditionPURY-P300, 350, 400YLM-A1(-BS)

63 125 250 500 1k 2k 4k 8k dB(A)Standard 50/60HzLow noise mode 50/60HzWhen Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operationfrom Low noise mode automatically in the case that the operation condition is severe.

10

20

30

40

50

60

70

80

90

63 125 250 500 1k 2k 4k 8k

NC-40

NC-30

NC-20

NC-60

NC-50

NC-70

Octave band central frequency (Hz)

Oct

ave

band

sou

nd le

vel (

dB)

Approximate minimumaudible limit oncontinuous noise

Standard 50/60HzLow 50/60Hz

75.0 65.0 61.5 57.5 51.0 45.0 38.5 32.5 59.054.5 50.0 46.5 43.0 32.0 31.5 32.5 28.0 44.0

Sound level of PURY-P200YLM-A1(-BS)

63 125 250 500 1k 2k 4k 8k dB(A)Standard 50/60HzLow noise mode 50/60HzWhen Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operationfrom Low noise mode automatically in the case that the operation condition is severe.

10

20

30

40

50

60

70

80

90

63 125 250 500 1k 2k 4k 8k

NC-40

NC-30

NC-20

NC-60

NC-50

NC-70

Octave band central frequency (Hz)

Oct

ave

band

sou

nd le

vel (

dB)

Approximate minimumaudible limit oncontinuous noise

Standard 50/60HzLow 50/60Hz

73.5 68.5 65.0 61.5 55.5 48.0 41.0 37.0 62.561.0 57.5 50.0 47.5 43.5 40.0 34.0 36.0 50.0

Sound level of PURY-P300YLM-A1(-BS)

63 125 250 500 1k 2k 4k 8k dB(A)Standard 50/60HzLow noise mode 50/60HzWhen Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operationfrom Low noise mode automatically in the case that the operation condition is severe.

10

20

30

40

50

60

70

80

90

63 125 250 500 1k 2k 4k 8k

NC-40

NC-30

NC-20

NC-60

NC-50

NC-70

Octave band central frequency (Hz)

Oct

ave

band

sou

nd le

vel (

dB)

Approximate minimumaudible limit oncontinuous noise

Sound level of PURY-P250YLM-A1(-BS)

Standard 50/60HzLow 50/60Hz

76.0 66.0 62.5 58.5 52.0 46.0 41.5 34.0 60.056.0 52.5 48.5 43.0 33.5 32.0 33.0 28.0 45.0

63 125 250 500 1k 2k 4k 8k dB(A)Standard 50/60HzLow noise mode 50/60HzWhen Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operationfrom Low noise mode automatically in the case that the operation condition is severe.

10

20

30

40

50

60

70

80

90

63 125 250 500 1k 2k 4k 8k

NC-40

NC-30

NC-20

NC-60

NC-50

NC-70

Octave band central frequency (Hz)

Oct

ave

band

sou

nd le

vel (

dB)

Approximate minimumaudible limit oncontinuous noise

Standard 50/60HzLow 50/60Hz

73.5 68.5 64.5 61.5 55.5 48.0 43.0 37.5 62.561.0 57.5 50.0 47.5 43.5 40.0 34.5 36.0 50.0

Sound level of PURY-P350YLM-A1(-BS)

0000003483.BOOK 243 ページ 2015年1月14日 水曜日 午前11時12分

Page 32: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 244

R2

MEE14K035

5. SOUND LEVELS YKB/YLM

Depending on the operation conditions, the unit generates noise caused by valve actuation, refrigerant flow, and pressure changes when operating normally. Please consider to avoid location where quietness is required.For BC controller, it is recommended to be installed in places such as ceilings of corridor, rest rooms and plant rooms.

63 125 250 500 1k 2k 4k 8k dB(A)Standard 50/60Hz 73.5 68.5 64.5 61.5 55.5 48.0 43.0 37.5 62.5Low noise mode 50/60Hz 64.0 60.5 53.0 50.5 46.5 43.0 38.0 38.5 53.0When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operationfrom Low noise mode automatically in the case that the operation condition is severe.

10

20

30

40

50

60

70

80

90

63 125 250 500 1k 2k 4k 8k

NC-40

NC-30

NC-20

NC-60

NC-50

NC-70

Octave band central frequency (Hz)

Oct

ave

band

sou

nd le

vel (

dB)

Approximate minimumaudible limit oncontinuous noise

Stand 50/60HzLow 50/60Hz

Sound level of PURY-P400YLM-A1(-BS)

Measurementlocation

1m

1m

Measurement conditionPURY-P450, 500YLM-A1(-BS)

63 125 250 500 1k 2k 4k 8k dB(A)Standard 50/60Hz 72.5 69.5 64.5 60.5 55.5 50.5 47.0 41.0 62.5Low noise mode 50/60Hz 64.5 61.0 51.5 50.0 46.5 44.0 38.5 39.5 53.0When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operationfrom Low noise mode automatically in the case that the operation condition is severe.

10

20

30

40

50

60

70

80

90

63 125 250 500 1k 2k 4k 8k

NC-40

NC-30

NC-20

NC-60

NC-50

NC-70

Octave band central frequency (Hz)

Oct

ave

band

sou

nd le

vel (

dB)

Approximate minimumaudible limit oncontinuous noise

Stand 50/60HzLow 50/60Hz

Sound level of PURY-P450YLM-A1(-BS)

63 125 250 500 1k 2k 4k 8k dB(A)Standard 50/60Hz 72.5 69.5 66.0 62.0 56.0 51.5 46.5 39.5 63.5Low noise mode 50/60Hz 64.5 61.0 52.5 50.0 46.5 43.5 39.0 37.5 53.0When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operationfrom Low noise mode automatically in the case that the operation condition is severe.

10

20

30

40

50

60

70

80

90

63 125 250 500 1k 2k 4k 8k

NC-40

NC-30

NC-20

NC-60

NC-50

NC-70

Octave band central frequency (Hz)

Oct

ave

band

sou

nd le

vel (

dB)

Approximate minimumaudible limit oncontinuous noise

Stand 50/60HzLow 50/60Hz

Sound level of PURY-P500YLM-A1(-BS)

0000003483.BOOK 244 ページ 2015年1月14日 水曜日 午前11時12分

Page 33: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 245

R2

MEE14K035

5. SOUND LEVELS YKB/YLM

Depending on the operation conditions, the unit generates noise caused by valve actuation, refrigerant flow, and pressure changes when operating normally. Please consider to avoid location where quietness is required.For BC controller, it is recommended to be installed in places such as ceilings of corridor, rest rooms and plant rooms.

Measurementlocation

1m

1m

Measurement conditionPURY-P400, 450, 500YSLM-A1(-BS)

63 125 250 500 1k 2k 4k 8k dB(A)Standard 50/60HzLow noise mode 50/60HzWhen Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operationfrom Low noise mode automatically in the case that the operation condition is severe.

10

20

30

40

50

60

70

80

90

63 125 250 500 1k 2k 4k 8k

NC-40

NC-30

NC-20

NC-60

NC-50

NC-70

Octave band central frequency (Hz)

Oct

ave

band

sou

nd le

vel (

dB)

Approximate minimumaudible limit oncontinuous noise

Standard 50/60HzLow 50/60Hz

79.0 69.0 65.5 61.5 55.0 49.0 44.5 37.0 63.059.0 55.5 51.5 46.0 36.5 35.0 36.0 31.0 48.0

Sound level of PURY-P500YSLM-A1(-BS)

63 125 250 500 1k 2k 4k 8k dB(A)Standard 50/60HzLow noise mode 50/60HzWhen Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operationfrom Low noise mode automatically in the case that the operation condition is severe.

10

20

30

40

50

60

70

80

90

63 125 250 500 1k 2k 4k 8k

NC-40

NC-30

NC-20

NC-60

NC-50

NC-70

Octave band central frequency (Hz)

Oct

ave

band

sou

nd le

vel (

dB)

Approximate minimumaudible limit oncontinuous noise

Standard 50/60HzLow 50/60Hz

78.0 68.5 64.5 60.5 53.5 48.0 41.5 35.5 62.057.5 53.0 49.5 46.0 35.0 34.0 36.0 31.0 47.0

Sound level of PURY-P400YSLM-A1(-BS)

63 125 250 500 1k 2k 4k 8k dB(A)Standard 50/60HzLow noise mode 50/60HzWhen Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operationfrom Low noise mode automatically in the case that the operation condition is severe.

10

20

30

40

50

60

70

80

90

63 125 250 500 1k 2k 4k 8k

NC-40

NC-30

NC-20

NC-60

NC-50

NC-70

Octave band central frequency (Hz)

Oct

ave

band

sou

nd le

vel (

dB)

Approximate minimumaudible limit oncontinuous noise

Standard 50/60HzLow 50/60Hz

78.5 68.5 65.0 61.0 54.5 48.5 43.5 36.5 62.558.0 54.5 50.5 46.0 36.0 34.5 36.0 31.0 47.5

Sound level of PURY-P450YSLM-A1(-BS)

0000003483.BOOK 245 ページ 2015年1月14日 水曜日 午前11時12分

Page 34: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 246

R2

MEE14K035

5. SOUND LEVELS YKB/YLM

Depending on the operation conditions, the unit generates noise caused by valve actuation, refrigerant flow, and pressure changes when operating normally. Please consider to avoid location where quietness is required.For BC controller, it is recommended to be installed in places such as ceilings of corridor, rest rooms and plant rooms.

Measurementlocation

1m

1m

Measurement conditionPURY-P550YSLM-A1(-BS)

Measurementlocation

1m

1m

Measurement conditionPURY-P600, 650, 700, 750, 800YSLM-A1(-BS)

63 125 250 500 1k 2k 4k 8k dB(A)Standard 50/60HzLow noise mode 50/60HzWhen Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operationfrom Low noise mode automatically in the case that the operation condition is severe.

10

20

30

40

50

60

70

80

90

63 125 250 500 1k 2k 4k 8k

NC-40

NC-30

NC-20

NC-60

NC-50

NC-70

Octave band central frequency (Hz)

Oct

ave

band

sou

nd le

vel (

dB)

Approximate minimumaudible limit oncontinuous noise

Standard 50/60HzLow 50/60Hz

78.0 71.0 67.0 63.0 57.0 50.5 44.5 39.0 64.562.5 59.0 52.5 49.5 44.0 41.0 36.5 36.5 51.5

Sound level of PURY-P550YSLM-A1(-BS)

63 125 250 500 1k 2k 4k 8k dB(A)Standard 50/60HzLow noise mode 50/60HzWhen Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operationfrom Low noise mode automatically in the case that the operation condition is severe.

10

20

30

40

50

60

70

80

90

63 125 250 500 1k 2k 4k 8k

NC-40

NC-30

NC-20

NC-60

NC-50

NC-70

Octave band central frequency (Hz)

Oct

ave

band

sou

nd le

vel (

dB)

Approximate minimumaudible limit oncontinuous noise

Standard 50/60HzLow 50/60Hz

76.5 72.0 67.5 64.5 58.5 51.0 44.5 40.0 65.564.0 60.5 53.0 50.5 46.5 43.0 36.5 39.0 53.0

Sound level of PURY-P600YSLM-A1(-BS)

63 125 250 500 1k 2k 4k 8k dB(A)Standard 50/60HzLow noise mode 50/60HzWhen Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operationfrom Low noise mode automatically in the case that the operation condition is severe.

10

20

30

40

50

60

70

80

90

63 125 250 500 1k 2k 4k 8k

NC-40

NC-30

NC-20

NC-60

NC-50

NC-70

Octave band central frequency (Hz)

Oct

ave

band

sou

nd le

vel (

dB)

Approximate minimumaudible limit oncontinuous noise

Standard 50/60HzLow 50/60Hz

72.0 67.5 64.5 58.5 51.0 45.5 40.0 65.560.5

76.564.0 53.0 50.5 46.5 43.0 37.0 39.0 53.0

Sound level of PURY-P650YSLM-A1(-BS)

0000003483.BOOK 246 ページ 2015年1月14日 水曜日 午前11時12分

Page 35: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 247

R2

MEE14K035

5. SOUND LEVELS YKB/YLM

Depending on the operation conditions, the unit generates noise caused by valve actuation, refrigerant flow, and pressure changes when operating normally. Please consider to avoid location where quietness is required.For BC controller, it is recommended to be installed in places such as ceilings of corridor, rest rooms and plant rooms.

63 125 250 500 1k 2k 4k 8k dB(A)Standard 50/60HzLow noise mode 50/60HzWhen Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operationfrom Low noise mode automatically in the case that the operation condition is severe.

10

20

30

40

50

60

70

80

90

63 125 250 500 1k 2k 4k 8k

NC-40

NC-30

NC-20

NC-60

NC-50

NC-70

Octave band central frequency (Hz)

Oct

ave

band

sou

nd le

vel (

dB)

Approximate minimumaudible limit oncontinuous noise

Standard 50/60HzLow 50/60Hz

76.5 72.0 67.5 64.5 58.5 51.0 46.0 40.5 65.564.0 60.5 53.0 50.5 46.5 43.0 37.5 39.0 53.0

Sound level of PURY-P700YSLM-A1(-BS)

Measurementlocation

1m

1m

Measurement conditionPURY-P850YSLM-A1(-BS)

63 125 250 500 1k 2k 4k 8k dB(A)Standard 50/60HzLow noise mode 50/60HzWhen Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operationfrom Low noise mode automatically in the case that the operation condition is severe.

10

20

30

40

50

60

70

80

90

63 125 250 500 1k 2k 4k 8k

NC-40

NC-30

NC-20

NC-60

NC-50

NC-70

Octave band central frequency (Hz)

Oct

ave

band

sou

nd le

vel (

dB)

Approximate minimumaudible limit oncontinuous noise

Standard 50/60HzLow 50/60Hz

76.5 72.0 67.5 64.5 58.5 51.0 46.0 40.5 65.566.0 62.5 55.0 53.0 48.0 45.0 39.5 40.5 55.0

Sound level of PURY-P750YSLM-A1(-BS)

63 125 250 500 1k 2k 4k 8k dB(A)Standard 50/60HzLow noise mode 50/60HzWhen Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operationfrom Low noise mode automatically in the case that the operation condition is severe.

10

20

30

40

50

60

70

80

90

63 125 250 500 1k 2k 4k 8k

NC-40

NC-30

NC-20

NC-60

NC-50

NC-70

Octave band central frequency (Hz)

Oct

ave

band

sou

nd le

vel (

dB)

Approximate minimumaudible limit oncontinuous noise

Standard 50/60HzLow 50/60Hz

76.0 72.0 67.5 64.0 58.5 52.5 48.5 42.5 65.567.5 64.0 55.0 53.5 49.5 46.5 41.0 42.0 56.0

Sound level of PURY-P850YSLM-A1(-BS)

63 125 250 500 1k 2k 4k 8k dB(A)Standard 50/60HzLow noise mode 50/60HzWhen Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operationfrom Low noise mode automatically in the case that the operation condition is severe.

10

20

30

40

50

60

70

80

90

63 125 250 500 1k 2k 4k 8k

NC-40

NC-30

NC-20

NC-60

NC-50

NC-70

Octave band central frequency (Hz)

Oct

ave

band

sou

nd le

vel (

dB)

Approximate minimumaudible limit oncontinuous noise

Standard 50/60HzLow 50/60Hz

76.5 72.0 67.5 64.5 58.5 51.0 46.0 40.5 65.567.0 63.5 56.0 53.5 49.5 46.0 41.0 40.5 56.0

Sound level of PURY-P800YSLM-A1(-BS)

0000003483.BOOK 247 ページ 2015年1月14日 水曜日 午前11時12分

Page 36: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 248

R2

MEE14K035

5. SOUND LEVELS YKB/YLM

Depending on the operation conditions, the unit generates noise caused by valve actuation, refrigerant flow, and pressure changes when operating normally. Please consider to avoid location where quietness is required.For BC controller, it is recommended to be installed in places such as ceilings of corridor, rest rooms and plant rooms.

Measurementlocation

1m

1m

Measurement conditionPURY-P900YSLM-A1(-BS)

63 125 250 500 1k 2k 4k 8k dB(A)Standard 50/60HzLow noise mode 50/60HzWhen Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operationfrom Low noise mode automatically in the case that the operation condition is severe.

10

20

30

40

50

60

70

80

90

63 125 250 500 1k 2k 4k 8k

NC-40

NC-30

NC-20

NC-60

NC-50

NC-70

Octave band central frequency (Hz)

Oct

ave

band

sou

nd le

vel (

dB)

Approximate minimumaudible limit oncontinuous noise

Standard 50/60HzLow 50/60Hz

75.5 72.5 67.5 63.5 58.5 53.5 50.0 44.0 65.567.5 64.0 55.0 53.0 49.5 47.0 41.5 42.5 56.0

Sound level of PURY-P900YSLM-A1(-BS)

0000003483.BOOK 248 ページ 2015年1月14日 水曜日 午前11時12分

Page 37: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 249

R2

MEE14K035

6. VIBRATION LEVEL YKB/YLM

6. VIBRATION LEVEL[PURY-P200-500YLM, PURY-P400-900YSLM]

* Vibration level varies depending on the conditions of actual installation site.

20cm10cm

Concrete

Service panel side

Measurement point

Measurement condition

Measurement frequency: 1 Hz-80 Hz

Measurement point: Ground surface 20 cm away from the unit leg

Installation condition: Direct installation on the concrete floor

Power source: 3-phase 4-wire 380-400-415 V 50/60 Hz

Operation condition: JIS condition (cooling, heating)

Measurement device: Vibration level meter for vibration pollution VM-1220C (JIS-compliant product)

Vibration level

Model Vibration level (dB)

PURY-P200YLM-A1 (-BS) 45

PURY-P250YLM-A1 (-BS) 46

PURY-P300YLM-A1 (-BS) 47

PURY-P350YLM-A1 (-BS) 47

PURY-P400YLM-A1 (-BS) 47

PURY-P450YLM-A1 (-BS) 47

PURY-P500YLM-A1 (-BS) 48

PURY-P400YSLM-A1 (-BS) 48

PURY-P450YSLM-A1 (-BS) 48.5

PURY-P500YSLM-A1 (-BS) 49

PURY-P550YSLM-A1 (-BS) 49.5

PURY-P600YSLM-A1 (-BS) 50

PURY-P650YSLM-A1 (-BS) 50

PURY-P700YSLM-A1 (-BS) 50

PURY-P750YSLM-A1 (-BS) 50

PURY-P800YSLM-A1 (-BS) 50

PURY-P850YSLM-A1 (-BS) 50

PURY-P900YSLM-A1 (-BS) 50

0000003483.BOOK 249 ページ 2015年1月14日 水曜日 午前11時12分

Page 38: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 250

R2

MEE14K035

7. OPERATION TEMPERATURE RANGE YKB/YLM

7. OPERATION TEMPERATURE RANGE

Indo

or te

mpe

ratu

re

Outdoor temperature

Outdoor temperature

15 to 24 CWB (59 to 75 FWB)

15 to 27 CDB (59 to 81 FDB)

Indoor temperature

Cooling Heating

-11 to 15.5 CWB (12.2 to 60 FWB)

-10 to 21 CDB (14 to 70 FDB)

Combination of cooling/heating operation (Cooling main or Heating main)

30

25

20

15

5

0-20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50

10

Range for continuous operation

Continuous operation not recommended

40

25

20

15

10

0

35

30

5

-20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50

Indo

or te

mpe

ratu

re

Outdoor temperature

Range for continuous operation

Continuous operation not recommended

Continuous operation not recommended

Cooling only

Heating only

0000003483.BOOK 250 ページ 2015年1月14日 水曜日 午前11時12分

Page 39: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 251

R2

MEE14K035

8. CAPACITY TABLES YKB/YLM

8. CAPACITY TABLES

Section 8-1.Shows an example of how to select the indoor and outdoor units according to the required heating/cooling load.

Section 8-2. through 8-6.Show the actual correction data of indoor and outdoor units.

0000003483.BOOK 251 ページ 2015年1月14日 水曜日 午前11時12分

Page 40: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 252

R2

MEE14K035

8. CAPACITY TABLES YKB/YLM

8-1. Selection of Cooling/Heating Units

Indoor Temperature [°CW.B.]

Rat

io o

f coo

ling

capa

city

15 16 17 18 19 20 21 22 23 240.8

0.9

1.0

1.1

1.2

1.2

1.0

0.9

0.8

0.7

0.6

1.1

1.3

Rat

io o

f coo

ling

capa

city

-523

032

541

1050

1559

2068

2577

3086

3595

40104

45113

°CD.B.°FD.B.

Indoor Temperature

Outdoor Temperature

19°CW.B.66°FW.B.

<Cooling>

Design ConditionOutdoor Design Dry Bulb Temperature 43 ºCTotal Cooling Load 18.0 kWRoom1

Indoor Design Dry Bulb Temperature 27 ºCIndoor Design Wet Bulb Temperature 20 ºCCooling Load 8.0 kW

Room2Indoor Design Dry Bulb Temperature 24 ºCIndoor Design Wet Bulb Temperature 17 ºCCooling Load 10.0 kW

<Other>Indoor/Outdoor Equivalent Piping Length 50 m

1. Cooling Calculation(1) Temporary Selection of Indoor Units

Room1PEFY-P80 9 kW (Rated)

Room2PEFY-P100 11.2 kW (Rated)

(2) Total Indoor Units CapacityP80 + P100 = P180

(3) Selection of Outdoor UnitThe P200 outdoor unit is selected as total indoor units capacity is P180PUHY-P200 22.4 kW

(4) Total Indoor Units Capacity Correction CalculationRoom1

Indoor Design Wet Bulb Temperature Correction (20ºC) 1.04 (Refer to Fig.1)

Fig.1 Indoor unit temperature correction To be used to correct indoor unit only

Fig.2 Outdoor unit temperature correction To be used to correct outdoor unit only

Fig.3 Correction of refrigerant piping length

Room2Indoor Design Wet Bulb Temperature Correction (17ºC) 0.95 (Refer to Fig.1)

CTi = Σ (Indoor Unit Rating × Indoor Design Temperature Correction)= 9.0 × 1.04 + 11.2 × 0.95= 20.0 kW

(5) Outdoor Unit Correction CalculationOutdoor Design Dry Bulb Temperature Correction (43ºC) 0.94 (Refer to Fig.2)Piping Length Correction (50 m) 0.94 (Refer to Fig.3)

Total Outdoor Unit Capacity (CTo)

Total Indoor Units Capacity (CTi)

CTo = Outdoor Rating × Outdoor Design Temperature Correction × Piping Length Correction= 22.4 × 0.94 × 0.94= 19.9 kW

(6) Determination of Maximum System CapacityComparison of Capacity between Total Indoor Units Capacity (CTi) and Total Outdoor Unit Capacity (CTo)

CTi = 20.0 > CTo = 19.9, thus, select CTo. CTx = CTo = 19.9 kW

(7) Comparison with Essential LoadAgainst the essential load 18.0kW, the maximum system capacity is 19.9kW: Proper outdoor units have been selected.

(8) Calculation of Maximum Indoor Unit Capacity of Each RoomCTx = CTo, thus, calculate by the calculation below

Room1Maximum Capacity × Room1 Capacity after the Temperature Correction/(Room1,2 Total Capacity after the Temperature Correction

= 19.9 × (9.0 × 1.04)/(9.0 × 1.04 + 11.2 × 0.95)= 9.3 kW OK: fulfills the load 8.0kW

Room2Maximum Capacity × Room2 Capacity after the Temperature Correction/(Room1,2Total Capacity after the Temperature Correction)

= 19.9 × (11.20 × 0.95)/(9.0 × 1.04 + 11.2 × 0.95)= 10.6 kW OK: fulfills the load 10.0kW

Go on to the heating trial calculation since the selected units fulfill the cooling loads of Room 1, 2.

Piping equivalent length (m)

1

0.90

0.80

0.95

0.85

0.75

0.65

0.70

Coo

ling

capa

city

cor

rect

ion

fact

or

0 20 40 60 80 100 120 140 160 180

Total capacity of indoor unit100

150

200260

0000003483.BOOK 252 ページ 2015年1月14日 水曜日 午前11時12分

Page 41: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 253

R2

MEE14K035

8. CAPACITY TABLES YKB/YLM

Indoor Temperature [°CD.B.]

Rat

io o

f hea

ting

capa

city

15 16 17 18 19 20 21 22 23 272625240.6

0.7

0.8

0.9

1.0

1.1

1.1

0.9

0.8

0.7

0.6

0.5

1.0

1.2

Rat

io o

f hea

ting

capa

city

-20-4

-155

-1014

-523

032

541

1050

1559

°CW.B.°FW.B.

Indoor Temperature

Outdoor Temperature

20°CD.B.68°FD.B.

<Heating>

Design ConditionOutdoor Design Wet Bulb Temperature -3 ºCTotal Heating Load 20.5 kWRoom1

Indoor Design Dry Bulb Temperature 21 ºCHeating Load 9.5 kW

Room2Indoor Design Dry Bulb Temperature 23 ºCHeating Load 11.0 kW

<Other>Indoor/Outdoor Equivalent Piping Length 50 m

2. Heating Calculation(1) Temporary Selection of Indoor Units

Room1PEFY-P80 10 kW (Rated)

Room2PEFY-P100 12.5 kW (Rated)

(2) Total Indoor Units CapacityP80 + P100 = P180

(3) Selection of Outdoor UnitThe P200 outdoor unit is selected as total indoor units capacity is P180PUHY-P200 25.0 kW

(4) Total Indoor Units Capacity Correction CalculationRoom1

Indoor Design Dry Bulb Temperature Correction (21ºC) 0.97 (Refer to Fig.4)

Tbl.1 Table of correction factor at frost and defrost

Room2Indoor Design Dry Bulb Temperature Correction (23ºC) 0.90 (Refer to Fig.4)

CTi = Σ (Indoor Unit Rating × Indoor Design Temperature Correction)= 10.0 × 0.97 + 12.5 × 0.90= 21.0 kW

(5) Outdoor Unit Correction CalculationOutdoor Design Wet Bulb Temperature Correction (-3ºC) 0.98 (Refer to Fig.5)Piping Length Correction (50 m)Defrost Correction

0.97 (Refer to Fig.6)0.89 (Refer to Tbl.1)

Total Outdoor Unit Capacity (CTo)

Total Indoor Units Capacity (CTi)

CTo = Outdoor Unit Rating × Outdoor Design Temperature Correction × Piping Length Correction × Defrost Correction

= 25.0 × 0.98 × 0.97 × 0.89= 21.1 kW

(6) Determination of Maximum System CapacityComparison of Capacity between Total Indoor Units Capacity (CTi) and Total Outdoor Unit Capacity (CTo)

CTi = 21.0 < CTo = 21.1, thus, select CTi. CTx = CTi = 21.0 kW

(7) Comparison with Essential LoadAgainst the essential load 20.5kW, the maximum system capacity is 21.0kW: Proper outdoor units have been selected.

(8) Calculation of Maximum Indoor Unit Capacity of Each RoomCTx = CTi, thus, calculate by the calculation below

Room1Indoor Unit Rating × Indoor Design Temperature Correction

= 10.0 × 0.97= 9.7 kW OK: fulfills the load 9.5kW

Room2Indoor Unit Rating × Indoor Design Temperature Correction

= 12.5 × 0.90= 11.3 kW OK: fulfills the load 11.0kW

Completed selecting units since the selected units fulfill the heating loads of Room 1, 2.

Outdoor inlet air temp. °C 6 4 2 1 0 -2 -4 -6 -8 -10 -20Outdoor inlet air temp. °F 43 39 36 34 32 28 25 21 18 14 -4PUHY-P200 1.00 0.95 0.84 0.825 0.83 0.87 0.90 0.95 0.95 0.95 0.95PUHY-P250 1.00 0.95 0.84 0.825 0.83 0.87 0.90 0.95 0.95 0.95 0.95PUHY-P300 1.00 0.93 0.82 0.80 0.82 0.86 0.90 0.90 0.95 0.95 0.95PUHY-P350 1.00 0.93 0.85 0.83 0.84 0.86 0.90 0.90 0.95 0.95 0.95PUHY-P400 1.00 0.93 0.85 0.83 0.84 0.86 0.90 0.90 0.95 0.95 0.95

Fig.4 Indoor unit temperature correction To be used to correct indoor unit only

Fig.5 Outdoor unit temperature correction To be used to correct outdoor unit only

Fig.6 Correction of refrigerant piping length

0.900 20 40 60 80 100 120 140 160 180

Hea

ting

capa

city

cor

rect

ion

fact

or

0.95

1.00

Piping equivalent length (m)

0000003483.BOOK 253 ページ 2015年1月14日 水曜日 午前11時12分

Page 42: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 254

R2

MEE14K035

8. CAPACITY TABLES YKB/YLM

8-2. Correction by temperature

P200YLM-A122.4

76,4005.29

P250YLM-A128.0

95,5006.98

PURY- Indoor unit temperature correctionNominalCoolingCapacityInput

kWBTU/hkW

Indoor Temperature [°CW.B.]

Rat

io o

f coo

ling

capa

city

To be used to correct indoor unit capacity only

15 16 17 18 19 20 21 22 23 240.8

0.9

1.0

1.1

1.2

Outdoor unit temperature correction

1.2

1.0

0.9

0.8

0.7

0.6

1.1

1.3

Rat

io o

f coo

ling

capa

city

-523

032

541

1050

1559

2068

2577

3086

3595

40104

45113

°CD.B.°FD.B.

0.8

0.9

1.0

1.2

1.1

1.3

0.7

0.6

0.5

0.3

0.4

Rat

io o

f pow

er in

put

-523

032

541

1050

1559

2068

2577

3086

3595

40104

45113

°CD.B.°FD.B.

Indoor Temperature

Indoor Temperature

Outdoor Temperature

Outdoor Temperature

19°CW.B.66°FW.B.

24°CW.B.75°FW.B.

22°CW.B.72°FW.B.

20°CW.B.68°FW.B.

To be used to correct outdoor unit only

Outdoor unit power input is affected by the indoor and outdoor temperatures as shown in the graph above. Please consult the sales office for details.

18°CW.B.64°FW.B.

19°CW.B.66°FW.B.

16°CW.B.61°FW.B.

15°CW.B.59°FW.B.

0000003483.BOOK 254 ページ 2015年1月14日 水曜日 午前11時12分

Page 43: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 255

R2

MEE14K035

8. CAPACITY TABLES YKB/YLM

P200YLM-A125.0

85,3005.49

P250YLM-A131.5

107,5007.32

PURY- Indoor unit temperature correctionNominalHeatingCapacityInput

kWBTU/hkW

To be used to correct indoor unit capacity only

Indoor Temperature [°CD.B.]

Rat

io o

f hea

ting

capa

city

15 16 17 18 19 20 21 22 23 272625240.6

0.7

0.8

0.9

1.0

1.1

Outdoor unit temperature correction

1.1

0.9

0.8

0.7

0.6

0.5

1.0

1.2

Rat

io o

f hea

ting

capa

city

0.9

1.0

1.1

1.3

1.2

1.4

0.8

0.7

0.6

0.4

0.5

Rat

io o

f pow

er in

put

-20-4

-155

-1014

-523

032

541

1050

1559

°CW.B.°FW.B.

Indoor Temperature

Indoor Temperature

Outdoor Temperature

-20-4

-155

-1014

-523

032

541

1050

1559

°CW.B.°FW.B.

Outdoor Temperature

20°CD.B.68°FD.B.

27°CD.B.81°FD.B.

25°CD.B.77°FD.B.

20°CD.B.68°FD.B.

To be used to correct outdoor unit only

Outdoor unit power input is affected by the indoor and outdoor temperatures as shown in the graph above. Please consult the sales office for details.

15°CD.B.59°FD.B.

0000003483.BOOK 255 ページ 2015年1月14日 水曜日 午前11時12分

Page 44: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 256

R2

MEE14K035

8. CAPACITY TABLES YKB/YLM

P300YLM-A133.5

114,3009.10

P350YLM-A140.0

136,50011.76

P400YLM-A145.0

153,50013.71

PURY- Indoor unit temperature correctionNominalCoolingCapacityInput

kWBTU/hkW

Indoor Temperature [°CW.B.]

Rat

io o

f coo

ling

capa

city

To be used to correct indoor unit capacity only

15 16 17 18 19 20 21 22 23 240.8

0.9

1.0

1.1

1.2

Outdoor unit temperature correction

1.2

1.0

0.9

0.8

0.7

0.6

1.1

1.3

Rat

io o

f coo

ling

capa

city

-523

032

541

1050

1559

2068

2577

3086

3595

40104

45113

°CD.B.°FD.B.

0.8

0.9

1.0

1.2

1.1

1.3

0.7

0.6

0.5

0.3

0.4

Rat

io o

f pow

er in

put

-523

032

541

1050

1559

2068

2577

3086

3595

40104

45113

°CD.B.°FD.B.

Indoor Temperature

Indoor Temperature

Outdoor Temperature

Outdoor Temperature

19°CW.B.66°FW.B.

24°CW.B.75°FW.B.

22°CW.B.72°FW.B.

20°CW.B.68°FW.B.

To be used to correct outdoor unit only

Outdoor unit power input is affected by the indoor and outdoor temperatures as shown in the graph above. Please consult the sales office for details.

18°CW.B.64°FW.B.

19°CW.B.66°FW.B.

16°CW.B.61°FW.B.

15°CW.B.59°FW.B.

P400YSLM-A145.0

153,50010.97

PURY-NominalCoolingCapacityInput

kWBTU/hkW

0000003483.BOOK 256 ページ 2015年1月14日 水曜日 午前11時12分

Page 45: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 257

R2

MEE14K035

8. CAPACITY TABLES YKB/YLM

P300YLM-A137.5

128,0009.37

P350YLM-A145.0

153,50011.59

PURY- Indoor unit temperature correctionNominalHeatingCapacityInput

kWBTU/hkW

To be used to correct indoor unit capacity only

Indoor Temperature [°CD.B.]

Rat

io o

f hea

ting

capa

city

15 16 17 18 19 20 21 22 23 272625240.6

0.7

0.8

0.9

1.0

1.1

Outdoor unit temperature correction

1.1

0.9

0.8

0.7

0.6

0.5

1.0

1.2

Rat

io o

f hea

ting

capa

city

0.9

1.0

1.1

1.3

1.2

1.4

0.8

0.7

0.6

0.4

0.5

Rat

io o

f pow

er in

put

-20-4

-155

-1014

-523

032

541

1050

1559

°CW.B.°FW.B.

Indoor Temperature

Indoor Temperature

Outdoor Temperature

-20-4

-155

-1014

-523

032

541

1050

1559

°CW.B.°FW.B.

Outdoor Temperature

20°CD.B.68°FD.B.

27°CD.B.81°FD.B.

25°CD.B.77°FD.B.

20°CD.B.68°FD.B.

To be used to correct outdoor unit only

Outdoor unit power input is affected by the indoor and outdoor temperatures as shown in the graph above. Please consult the sales office for details.

15°CD.B.59°FD.B.

P400YLM-A145.0

153,50011.42

P400YSLM-A150.0

170,60010.98

PURY-NominalHeatingCapacityInput

kWBTU/hkW

0000003483.BOOK 257 ページ 2015年1月14日 水曜日 午前11時12分

Page 46: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 258

R2

MEE14K035

8. CAPACITY TABLES YKB/YLM

P450YLM-A150.0

170,60014.32

P500YLM-A156.0

191,10017.77

P450YSLM-A150.0

170,60012.50

PURY- Indoor unit temperature correctionNominalCoolingCapacityInput

kWBTU/hkW

Indoor Temperature [°CW.B.]

Rat

io o

f coo

ling

capa

city

To be used to correct indoor unit capacity only

15 16 17 18 19 20 21 22 23 240.8

0.9

1.0

1.1

1.2

Outdoor unit temperature correction

1.2

1.0

0.9

0.8

0.7

0.6

1.1

1.3

Rat

io o

f coo

ling

capa

city

-523

032

541

1050

1559

2068

2577

3086

3595

40104

45113

°CD.B.°FD.B.

0.8

0.9

1.0

1.2

1.1

1.3

0.7

0.6

0.5

0.3

0.4

Rat

io o

f pow

er in

put

-523

032

541

1050

1559

2068

2577

3086

3595

40104

45113

°CD.B.°FD.B.

Indoor Temperature

Indoor Temperature

Outdoor Temperature

Outdoor Temperature

19°CW.B.66°FW.B.

24°CW.B.75°FW.B.

22°CW.B.72°FW.B.

20°CW.B.68°FW.B.

To be used to correct outdoor unit only

Outdoor unit power input is affected by the indoor and outdoor temperatures as shown in the graph above. Please consult the sales office for details.

18°CW.B.64°FW.B.

19°CW.B.66°FW.B.

16°CW.B.61°FW.B.

15°CW.B.59°FW.B.

P500YSLM-A156.0

191,10014.39

P550YSLM-A163.0

215,00016.89

P600YSLM-A169.0

235,40019.32

PURY-

P650YSLM-A173.0

249,10021.28

PURY-

NominalCoolingCapacityInput

kWBTU/hkW

NominalCoolingCapacityInput

kWBTU/hkW

0000003483.BOOK 258 ページ 2015年1月14日 水曜日 午前11時12分

Page 47: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 259

R2

MEE14K035

8. CAPACITY TABLES YKB/YLM

Indoor unit temperature correctionTo be used to correct indoor unit capacity only

Indoor Temperature [°CD.B.]

Rat

io o

f hea

ting

capa

city

15 16 17 18 19 20 21 22 23 272625240.6

0.7

0.8

0.9

1.0

1.1

Outdoor unit temperature correction

1.1

0.9

0.8

0.7

0.6

0.5

1.0

1.2

Rat

io o

f hea

ting

capa

city

0.9

1.0

1.1

1.3

1.2

1.4

0.8

0.7

0.6

0.4

0.5

Rat

io o

f pow

er in

put

-20-4

-155

-1014

-523

032

541

1050

1559

°CW.B.°FW.B.

Indoor Temperature

Indoor Temperature

Outdoor Temperature

-20-4

-155

-1014

-523

032

541

1050

1559

°CW.B.°FW.B.

Outdoor Temperature

20°CD.B.68°FD.B.

27°CD.B.81°FD.B.

25°CD.B.77°FD.B.

20°CD.B.68°FD.B.

To be used to correct outdoor unit only

Outdoor unit power input is affected by the indoor and outdoor temperatures as shown in the graph above. Please consult the sales office for details.

15°CD.B.59°FD.B.

P450YLM-A156.0

191,10014.93

P500YLM-A158.0

197,90016.06

P450YSLM-A156.0

191,10012.64

PURY-NominalHeatingCapacityInput

kWBTU/hkW

P500YSLM-A163.0

215,00014.65

P550YSLM-A169.0

235,40016.62

P600YSLM-A176.5

261,00019.12

PURY-

P650YSLM-A181.5

278,10020.68

PURY-

NominalHeatingCapacityInput

kWBTU/hkW

NominalHeatingCapacityInput

kWBTU/hkW

0000003483.BOOK 259 ページ 2015年1月14日 水曜日 午前11時12分

Page 48: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 260

R2

MEE14K035

8. CAPACITY TABLES YKB/YLM

P700YSLM-A180.0

273,00024.24

P750YSLM-A185.0

290,00026.23

P800YSLM-A190.0

307,10028.30

PURY- Indoor unit temperature correctionNominalCoolingCapacityInput

kWBTU/hkW

Indoor Temperature [°CW.B.]

Rat

io o

f coo

ling

capa

city

To be used to correct indoor unit capacity only

15 16 17 18 19 20 21 22 23 240.8

0.9

1.0

1.1

1.2

Outdoor unit temperature correction

1.2

1.0

0.9

0.8

0.7

0.6

1.1

1.3

Rat

io o

f coo

ling

capa

city

-523

032

541

1050

1559

2068

2577

3086

3595

40104

45113

°CD.B.°FD.B.

0.8

0.9

1.0

1.2

1.1

1.3

0.7

0.6

0.5

0.3

0.4

Rat

io o

f pow

er in

put

-523

032

541

1050

1559

2068

2577

3086

3595

40104

45113

°CD.B.°FD.B.

Indoor Temperature

Indoor Temperature

Outdoor Temperature

Outdoor Temperature

19°CW.B.66°FW.B.

24°CW.B.75°FW.B.

22°CW.B.72°FW.B.

20°CW.B.68°FW.B.

To be used to correct outdoor unit only

Outdoor unit power input is affected by the indoor and outdoor temperatures as shown in the graph above. Please consult the sales office for details.

18°CW.B.64°FW.B.

19°CW.B.66°FW.B.

16°CW.B.61°FW.B.

15°CW.B.59°FW.B.

0000003483.BOOK 260 ページ 2015年1月14日 水曜日 午前11時12分

Page 49: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 261

R2

MEE14K035

8. CAPACITY TABLES YKB/YLM

P700YSLM-A188.0

300,30022.68

P750YSLM-A190.0

307,10023.01

PURY- Indoor unit temperature correctionNominalHeatingCapacityInput

kWBTU/hkW

To be used to correct indoor unit capacity only

Indoor Temperature [°CD.B.]

Rat

io o

f hea

ting

capa

city

15 16 17 18 19 20 21 22 23 272625240.6

0.7

0.8

0.9

1.0

1.1

Outdoor unit temperature correction

1.1

0.9

0.8

0.7

0.6

0.5

1.0

1.2

Rat

io o

f hea

ting

capa

city

0.9

1.0

1.1

1.3

1.2

1.4

0.8

0.7

0.6

0.4

0.5

Rat

io o

f pow

er in

put

-20-4

-155

-1014

-523

032

541

1050

1559

°CW.B.°FW.B.

Indoor Temperature

Indoor Temperature

Outdoor Temperature

-20-4

-155

-1014

-523

032

541

1050

1559

°CW.B.°FW.B.

Outdoor Temperature

20°CD.B.68°FD.B.

27°CD.B.81°FD.B.

25°CD.B.77°FD.B.

20°CD.B.68°FD.B.

To be used to correct outdoor unit only

Outdoor unit power input is affected by the indoor and outdoor temperatures as shown in the graph above. Please consult the sales office for details.

15°CD.B.59°FD.B.

P800YSLM-A190.0

307,10022.84

0000003483.BOOK 261 ページ 2015年1月14日 水曜日 午前11時12分

Page 50: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 262

R2

MEE14K035

8. CAPACITY TABLES YKB/YLM

P850YSLM-A196.0

327,60029.26

P900YSLM-A1101.0

344,60029.79

PURY- Indoor unit temperature correctionNominalCoolingCapacityInput

kWBTU/hkW

Indoor Temperature [°CW.B.]

Rat

io o

f coo

ling

capa

city

To be used to correct indoor unit capacity only

15 16 17 18 19 20 21 22 23 240.8

0.9

1.0

1.1

1.2

Outdoor unit temperature correctionOutdoor unit temperature correction

1.2

1.0

0.9

0.8

0.7

0.6

1.1

1.3

Rat

io o

f coo

ling

capa

city

-523

032

541

1050

1559

2068

2577

3086

3595

40104

45113

°CD.B.°FD.B.

0.8

0.9

1.0

1.2

1.1

1.3

0.7

0.6

0.5

0.3

0.4

Rat

io o

f pow

er in

put

-523

032

541

1050

1559

2068

2577

3086

3595

40104

45113

°CD.B.°FD.B.

Indoor Temperature

Indoor Temperature

Outdoor Temperature

Outdoor Temperature

19°CW.B.66°FW.B.

24°CW.B.75°FW.B.

22°CW.B.72°FW.B.

20°CW.B.68°FW.B.

To be used to correct outdoor unit only

Outdoor unit power input is affected by the indoor and outdoor temperatures as shown in the graph above. Please consult the sales office for details.

18°CW.B.64°FW.B.

19°CW.B.66°FW.B.

16°CW.B.61°FW.B.

15°CW.B.59°FW.B.

0000003483.BOOK 262 ページ 2015年1月14日 水曜日 午前11時12分

Page 51: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 263

R2

MEE14K035

8. CAPACITY TABLES YKB/YLM

P850YSLM-A1101.0

344,60026.23

P900YSLM-A1113.0

385,60030.13

PURY- Indoor unit temperature correctionNominalHeatingCapacityInput

kWBTU/hkW

To be used to correct indoor unit capacity only

Indoor Temperature [°CD.B.]

Rat

io o

f hea

ting

capa

city

15 16 17 18 19 20 21 22 23 272625240.6

0.7

0.8

0.9

1.0

1.1

Outdoor unit temperature correction

1.1

0.9

0.8

0.7

0.6

0.5

1.0

1.2

Rat

io o

f hea

ting

capa

city

0.9

1.0

1.1

1.3

1.2

1.4

0.8

0.7

0.6

0.4

0.5

Rat

io o

f pow

er in

put

-20-4

-155

-1014

-523

032

541

1050

1559

°CW.B.°FW.B.

Indoor Temperature

Indoor Temperature

Outdoor Temperature

-20-4

-155

-1014

-523

032

541

1050

1559

°CW.B.°FW.B.

Outdoor Temperature

20°CD.B.68°FD.B.

27°CD.B.81°FD.B.

25°CD.B.77°FD.B.

20°CD.B.68°FD.B.

To be used to correct outdoor unit only

Outdoor unit power input is affected by the indoor and outdoor temperatures as shown in the graph above. Please consult the sales office for details.

15°CD.B.59°FD.B.

0000003483.BOOK 263 ページ 2015年1月14日 水曜日 午前11時12分

Page 52: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 264

R2

MEE14K035

8. CAPACITY TABLES YKB/YLM

Correction by temperature (COP Priority Mode)CITY MULTI could have various capacities at different designing temperatures. Using the nominal cooling/heating capacity values and the ratios below, the capacity can be found for various temperatures.To select COP priority mode, DipSW 6-2 must be set to ON.

P200YLM-A122.4

76,4005.29

P250YLM-A128.0

95,5006.98

PURY- Indoor unit temperature correctionNominalCoolingCapacityInput

kWBTU/hkW

Indoor Temperature [°CW.B.]R

atio

of c

oolin

g ca

paci

ty

To be used to correct indoor unit capacity only

15 16 17 18 19 20 21 22 23 240.8

0.9

1.0

1.1

1.2

Outdoor unit temperature correction

1.2

1.0

0.9

0.8

0.7

0.6

1.1

1.3

Rat

io o

f coo

ling

capa

city

-523

032

541

1050

1559

2068

2577

3086

3595

40104

45113

°CD.B.°FD.B.

0.8

0.9

1.0

1.2

1.1

1.3

0.7

0.6

0.5

0.3

0.4

Rat

io o

f pow

er in

put

-523

032

541

1050

1559

2068

2577

3086

3595

40104

45113

°CD.B.°FD.B.

Indoor Temperature

Indoor Temperature

Outdoor Temperature

Outdoor Temperature

19°CW.B.66°FW.B.

24°CW.B.75°FW.B.

22°CW.B.72°FW.B.

20°CW.B.68°FW.B.

To be used to correct outdoor unit only

Outdoor unit power input is affected by the indoor and outdoor temperatures as shown in the graph above. Please consult the sales office for details.

18°CW.B.64°FW.B.

19°CW.B.66°FW.B.

16°CW.B.61°FW.B.

15°CW.B.59°FW.B.

0000003483.BOOK 264 ページ 2015年1月14日 水曜日 午前11時12分

Page 53: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 265

R2

MEE14K035

8. CAPACITY TABLES YKB/YLM

P200YLM-A125.0

85,3005.49

P250YLM-A131.5

107,5007.32

PURY- Indoor unit temperature correctionNominalHeatingCapacityInput

kWBTU/hkW

To be used to correct indoor unit capacity only

Indoor Temperature [°CD.B.]

Rat

io o

f hea

ting

capa

city

15 16 17 18 19 20 21 22 23 272625240.6

0.7

0.8

0.9

1.0

1.1

Outdoor unit temperature correction

1.1

0.9

0.8

0.7

0.6

0.5

1.0

1.2

Rat

io o

f hea

ting

capa

city

0.9

1.0

1.1

1.3

1.2

1.4

0.8

0.7

0.6

0.4

0.5

Rat

io o

f pow

er in

put

-20-4

-155

-1014

-523

032

541

1050

1559

°CW.B.°FW.B.

Indoor Temperature

Indoor Temperature

Outdoor Temperature

-20-4

-155

-1014

-523

032

541

1050

1559

°CW.B.°FW.B.

Outdoor Temperature

20°CD.B.68°FD.B.

27°CD.B.81°FD.B.

25°CD.B.77°FD.B.

20°CD.B.68°FD.B.

To be used to correct outdoor unit only

Outdoor unit power input is affected by the indoor and outdoor temperatures as shown in the graph above. Please consult the sales office for details.

15°CD.B.59°FD.B.

0000003483.BOOK 265 ページ 2015年1月14日 水曜日 午前11時12分

Page 54: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 266

R2

MEE14K035

8. CAPACITY TABLES YKB/YLM

P300YLM-A133.5

114,3009.10

P350YLM-A140.0

136,50011.76

P400YLM-A145.0

153,50013.71

PURY- Indoor unit temperature correctionNominalCoolingCapacityInput

kWBTU/hkW

Indoor Temperature [°CW.B.]

Rat

io o

f coo

ling

capa

city

To be used to correct indoor unit capacity only

15 16 17 18 19 20 21 22 23 240.8

0.9

1.0

1.1

1.2

Outdoor unit temperature correction

1.2

1.0

0.9

0.8

0.7

0.6

1.1

1.3

Rat

io o

f coo

ling

capa

city

-523

032

541

1050

1559

2068

2577

3086

3595

40104

45113

°CD.B.°FD.B.

0.8

0.9

1.0

1.2

1.1

1.3

0.7

0.6

0.5

0.3

0.4

Rat

io o

f pow

er in

put

-523

032

541

1050

1559

2068

2577

3086

3595

40104

45113

°CD.B.°FD.B.

Indoor Temperature

Indoor Temperature

Outdoor Temperature

Outdoor Temperature

19°CW.B.66°FW.B.

24°CW.B.75°FW.B.

22°CW.B.72°FW.B.

20°CW.B.68°FW.B.

To be used to correct outdoor unit only

Outdoor unit power input is affected by the indoor and outdoor temperatures as shown in the graph above. Please consult the sales office for details.

18°CW.B.64°FW.B.

19°CW.B.66°FW.B.

16°CW.B.61°FW.B.

15°CW.B.59°FW.B.

P400YSLM-A145.0

153,50010.97

PURY-NominalCoolingCapacityInput

kWBTU/hkW

0000003483.BOOK 266 ページ 2015年1月14日 水曜日 午前11時12分

Page 55: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 267

R2

MEE14K035

8. CAPACITY TABLES YKB/YLM

Indoor unit temperature correctionTo be used to correct indoor unit capacity only

Indoor Temperature [°CD.B.]

Rat

io o

f hea

ting

capa

city

15 16 17 18 19 20 21 22 23 272625240.6

0.7

0.8

0.9

1.0

1.1

Outdoor unit temperature correction

1.1

0.9

0.8

0.7

0.6

0.5

1.0

1.2

Rat

io o

f hea

ting

capa

city

0.9

1.0

1.1

1.3

1.2

1.4

0.8

0.7

0.6

0.4

0.5

Rat

io o

f pow

er in

put

-20-4

-155

-1014

-523

032

541

1050

1559

°CW.B.°FW.B.

Indoor Temperature

Indoor Temperature

Outdoor Temperature

-20-4

-155

-1014

-523

032

541

1050

1559

°CW.B.°FW.B.

Outdoor Temperature

20°CD.B.68°FD.B.

27°CD.B.81°FD.B.

25°CD.B.77°FD.B.

20°CD.B.68°FD.B.

To be used to correct outdoor unit only

Outdoor unit power input is affected by the indoor and outdoor temperatures as shown in the graph above. Please consult the sales office for details.

15°CD.B.59°FD.B.

P300YLM-A137.5

128,0009.37

P350YLM-A145.0

153,50011.59

PURY-NominalHeatingCapacityInput

kWBTU/hkW

P400YLM-A145.0

153,50011.42

P400YSLM-A150.0

170,60010.98

PURY-NominalHeatingCapacityInput

kWBTU/hkW

0000003483.BOOK 267 ページ 2015年1月14日 水曜日 午前11時12分

Page 56: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 268

R2

MEE14K035

8. CAPACITY TABLES YKB/YLM

P450YLM-A150.0

170,60014.32

P500YLM-A156.0

191,10017.77

P450YSLM-A150.0

170,60012.50

PURY- Indoor unit temperature correctionNominalCoolingCapacityInput

kWBTU/hkW

Indoor Temperature [°CW.B.]

Rat

io o

f coo

ling

capa

city

To be used to correct indoor unit capacity only

15 16 17 18 19 20 21 22 23 240.8

0.9

1.0

1.1

1.2

Outdoor unit temperature correction

1.2

1.0

0.9

0.8

0.7

0.6

1.1

1.3

Rat

io o

f coo

ling

capa

city

-523

032

541

1050

1559

2068

2577

3086

3595

40104

45113

°CD.B.°FD.B.

0.8

0.9

1.0

1.2

1.1

1.3

0.7

0.6

0.5

0.3

0.4

Rat

io o

f pow

er in

put

-523

032

541

1050

1559

2068

2577

3086

3595

40104

45113

°CD.B.°FD.B.

Indoor Temperature

Indoor Temperature

Outdoor Temperature

Outdoor Temperature

19°CW.B.66°FW.B.

24°CW.B.75°FW.B.

22°CW.B.72°FW.B.

20°CW.B.68°FW.B.

To be used to correct outdoor unit only

Outdoor unit power input is affected by the indoor and outdoor temperatures as shown in the graph above. Please consult the sales office for details.

18°CW.B.64°FW.B.

19°CW.B.66°FW.B.

16°CW.B.61°FW.B.

15°CW.B.59°FW.B.

P500YSLM-A156.0

191,10014.39

P550YSLM-A163.0

215,00016.89

P600YSLM-A169.0

235,40019.32

PURY-

P650YSLM-A173.0

249,10021.28

PURY-

NominalCoolingCapacityInput

kWBTU/hkW

NominalCoolingCapacityInput

kWBTU/hkW

0000003483.BOOK 268 ページ 2015年1月14日 水曜日 午前11時12分

Page 57: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 269

R2

MEE14K035

8. CAPACITY TABLES YKB/YLM

Indoor unit temperature correctionTo be used to correct indoor unit capacity only

Indoor Temperature [°CD.B.]

Rat

io o

f hea

ting

capa

city

15 16 17 18 19 20 21 22 23 272625240.6

0.7

0.8

0.9

1.0

1.1

Outdoor unit temperature correction

1.1

0.9

0.8

0.7

0.6

0.5

1.0

1.2

Rat

io o

f hea

ting

capa

city

0.9

1.0

1.1

1.3

1.2

1.4

0.8

0.7

0.6

0.4

0.5

Rat

io o

f pow

er in

put

-20-4

-155

-1014

-523

032

541

1050

1559

°CW.B.°FW.B.

Indoor Temperature

Indoor Temperature

Outdoor Temperature

-20-4

-155

-1014

-523

032

541

1050

1559

°CW.B.°FW.B.

Outdoor Temperature

20°CD.B.68°FD.B.

27°CD.B.81°FD.B.

25°CD.B.77°FD.B.

20°CD.B.68°FD.B.

To be used to correct outdoor unit only

Outdoor unit power input is affected by the indoor and outdoor temperatures as shown in the graph above. Please consult the sales office for details.

15°CD.B.59°FD.B.

P450YLM-A156.0

191,10014.93

P500YLM-A158.0

197,90016.06

P450YSLM-A156.0

191,10012.64

PURY-NominalHeatingCapacityInput

kWBTU/hkW

P500YSLM-A163.0

215,00014.65

P550YSLM-A169.0

235,40016.62

P600YSLM-A176.5

261,00019.12

PURY-

P650YSLM-A181.5

278,10020.68

PURY-

NominalHeatingCapacityInput

kWBTU/hkW

NominalHeatingCapacityInput

kWBTU/hkW

0000003483.BOOK 269 ページ 2015年1月14日 水曜日 午前11時12分

Page 58: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 270

R2

MEE14K035

8. CAPACITY TABLES YKB/YLM

P700YSLM-A180.0

273,00024.24

P750YSLM-A185.0

290,00026.23

P800YSLM-A190.0

307,10028.30

PURY- Indoor unit temperature correctionNominalCoolingCapacityInput

kWBTU/hkW

Indoor Temperature [°CW.B.]

Rat

io o

f coo

ling

capa

city

To be used to correct indoor unit capacity only

15 16 17 18 19 20 21 22 23 240.8

0.9

1.0

1.1

1.2

Outdoor unit temperature correction

1.2

1.0

0.9

0.8

0.7

0.6

1.1

1.3

Rat

io o

f coo

ling

capa

city

-523

032

541

1050

1559

2068

2577

3086

3595

40104

45113

°CD.B.°FD.B.

0.8

0.9

1.0

1.2

1.1

1.3

0.7

0.6

0.5

0.3

0.4

Rat

io o

f pow

er in

put

-523

032

541

1050

1559

2068

2577

3086

3595

40104

45113

°CD.B.°FD.B.

Indoor Temperature

Indoor Temperature

Outdoor Temperature

Outdoor Temperature

19°CW.B.66°FW.B.

24°CW.B.75°FW.B.

22°CW.B.72°FW.B.

20°CW.B.68°FW.B.

To be used to correct outdoor unit only

Outdoor unit power input is affected by the indoor and outdoor temperatures as shown in the graph above. Please consult the sales office for details.

18°CW.B.64°FW.B.

19°CW.B.66°FW.B.

16°CW.B.61°FW.B.

15°CW.B.59°FW.B.

0000003483.BOOK 270 ページ 2015年1月14日 水曜日 午前11時12分

Page 59: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 271

R2

MEE14K035

8. CAPACITY TABLES YKB/YLM

Indoor unit temperature correctionTo be used to correct indoor unit capacity only

Indoor Temperature [°CD.B.]

Rat

io o

f hea

ting

capa

city

15 16 17 18 19 20 21 22 23 272625240.6

0.7

0.8

0.9

1.0

1.1

Outdoor unit temperature correction

1.1

0.9

0.8

0.7

0.6

0.5

1.0

1.2

Rat

io o

f hea

ting

capa

city

0.9

1.0

1.1

1.3

1.2

1.4

0.8

0.7

0.6

0.4

0.5

Rat

io o

f pow

er in

put

-20-4

-155

-1014

-523

032

541

1050

1559

°CW.B.°FW.B.

Indoor Temperature

Indoor Temperature

Outdoor Temperature

-20-4

-155

-1014

-523

032

541

1050

1559

°CW.B.°FW.B.

Outdoor Temperature

20°CD.B.68°FD.B.

27°CD.B.81°FD.B.

25°CD.B.77°FD.B.

20°CD.B.68°FD.B.

To be used to correct outdoor unit only

Outdoor unit power input is affected by the indoor and outdoor temperatures as shown in the graph above. Please consult the sales office for details.

15°CD.B.59°FD.B.

P700YSLM-A188.0

300,30022.68

P750YSLM-A190.0

307,10023.01

PURY-NominalHeatingCapacityInput

kWBTU/hkW

P800YSLM-A190.0

307,10022.84

0000003483.BOOK 271 ページ 2015年1月14日 水曜日 午前11時12分

Page 60: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 272

R2

MEE14K035

8. CAPACITY TABLES YKB/YLM

P850YSLM-A196.0

327,60029.26

P900YSLM-A1101.0

344,60029.79

PURY- Indoor unit temperature correctionNominalCoolingCapacityInput

kWBTU/hkW

Indoor Temperature [°CW.B.]

Rat

io o

f coo

ling

capa

city

To be used to correct indoor unit capacity only

15 16 17 18 19 20 21 22 23 240.8

0.9

1.0

1.1

1.2

Outdoor unit temperature correctionOutdoor unit temperature correction

1.2

1.0

0.9

0.8

0.7

0.6

1.1

1.3

Rat

io o

f coo

ling

capa

city

-523

032

541

1050

1559

2068

2577

3086

3595

40104

45113

°CD.B.°FD.B.

0.8

0.9

1.0

1.2

1.1

1.3

0.7

0.6

0.5

0.3

0.4

Rat

io o

f pow

er in

put

-523

032

541

1050

1559

2068

2577

3086

3595

40104

45113

°CD.B.°FD.B.

Indoor Temperature

Indoor Temperature

Outdoor Temperature

Outdoor Temperature

19°CW.B.66°FW.B.

24°CW.B.75°FW.B.

22°CW.B.72°FW.B.

20°CW.B.68°FW.B.

To be used to correct outdoor unit only

Outdoor unit power input is affected by the indoor and outdoor temperatures as shown in the graph above. Please consult the sales office for details.

18°CW.B.64°FW.B.

19°CW.B.66°FW.B.

16°CW.B.61°FW.B.

15°CW.B.59°FW.B.

0000003483.BOOK 272 ページ 2015年1月14日 水曜日 午前11時12分

Page 61: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 273

R2

MEE14K035

8. CAPACITY TABLES YKB/YLM

Indoor unit temperature correctionTo be used to correct indoor unit capacity only

Indoor Temperature [°CD.B.]

Rat

io o

f hea

ting

capa

city

15 16 17 18 19 20 21 22 23 272625240.6

0.7

0.8

0.9

1.0

1.1

Outdoor unit temperature correction

1.1

0.9

0.8

0.7

0.6

0.5

1.0

1.2

Rat

io o

f hea

ting

capa

city

0.9

1.0

1.1

1.3

1.2

1.4

0.8

0.7

0.6

0.4

0.5

Rat

io o

f pow

er in

put

-20-4

-155

-1014

-523

032

541

1050

1559

°CW.B.°FW.B.

Indoor Temperature

Indoor Temperature

Outdoor Temperature

-20-4

-155

-1014

-523

032

541

1050

1559

°CW.B.°FW.B.

Outdoor Temperature

20°CD.B.68°FD.B.

27°CD.B.81°FD.B.

25°CD.B.77°FD.B.

20°CD.B.68°FD.B.

To be used to correct outdoor unit only

Outdoor unit power input is affected by the indoor and outdoor temperatures as shown in the graph above. Please consult the sales office for details.

15°CD.B.59°FD.B.

P850YSLM-A1101.0

344,60026.23

P900YSLM-A1113.0

385,60030.13

PURY-NominalHeatingCapacityInput

kWBTU/hkW

0000003483.BOOK 273 ページ 2015年1月14日 水曜日 午前11時12分

Page 62: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 274

R2

MEE14K035

8. CAPACITY TABLES YKB/YLM

8-3. Correction by total indoor

Total capacity of indoor units

Rat

io o

f cap

acity

Rat

io o

f pow

er in

put

Total capacity of indoor units

Rat

io o

f cap

acity

Rat

io o

f pow

er in

put

PURY-P250YLM-A1

PURY-P200YLM-A1

CoolingHeating

50 100 200 300150 250 350

0.2

1.2

1.0

0.8

0.6

0.4

1.0

0.8

0.6

0.4

0.2

1.2

CoolingHeating

100 150 250 350200 300 400

0.2

1.2

1.0

0.8

0.6

0.4

1.0

0.8

0.6

0.4

0.2

1.2

NominalCoolingCapacityInput

kWBTU/hkW

PURY-P250YLM-A128.0

95,5006.98

NominalHeatingCapacityInput

kWBTU/hkW

PURY-P250YLM-A131.5

107,5007.32

NominalCoolingCapacityInput

kWBTU/hkW

PURY-P200YLM-A122.4

76,4005.29

NominalHeatingCapacityInput

kWBTU/hkW

PURY-P200YLM-A125.0

85,3005.49

0000003483.BOOK 274 ページ 2015年1月14日 水曜日 午前11時12分

Page 63: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 275

R2

MEE14K035

8. CAPACITY TABLES YKB/YLM

Total capacity of indoor units100 200 300 400 500

Rat

io o

f cap

acity

Rat

io o

f pow

er in

put

0.2

1.2

1.0

0.8

0.6

0.4

1.0

0.8

0.6

0.4

0.2

1.2

Total capacity of indoor units100 200 400300 500 600

0.2

1.2

1.0

0.8

0.6

0.4

1.0

0.8

0.6

0.4

0.2

1.2

Rat

io o

f cap

acity

Rat

io o

f pow

er in

put

PURY-P300YLM-A1

PURY-P350YLM-A1

CoolingHeating

CoolingHeating

NominalCoolingCapacityInput

kWBTU/hkW

PURY-P300YLM-A133.5

114,3009.10

NominalHeatingCapacityInput

kWBTU/hkW

PURY-P300YLM-A137.5

128,0009.37

NominalCoolingCapacityInput

kWBTU/hkW

PURY-P350YLM-A140.0

136,50011.76

NominalHeatingCapacityInput

kWBTU/hkW

PURY-P350YLM-A145.0

153,50011.59

0000003483.BOOK 275 ページ 2015年1月14日 水曜日 午前11時12分

Page 64: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 276

R2

MEE14K035

8. CAPACITY TABLES YKB/YLM

Total capacity of indoor units

Rat

io o

f cap

acity

Rat

io o

f pow

er in

put

Total capacity of indoor units

Rat

io o

f cap

acity

Rat

io o

f pow

er in

put

PURY-P450YLM-A1

CoolingHeating

100 200 400 600300 500 700

0.2

1.2

1.0

0.8

0.6

0.4

1.0

0.8

0.6

0.4

0.2

1.2

CoolingHeating

200 300 500 700400 600 800

0.2

1.2

1.0

0.8

0.6

0.4

1.0

0.8

0.6

0.4

0.2

1.2

PURY-P400YLM-A1NominalCoolingCapacityInput

kWBTU/hkW

PURY-P400YLM-A145.0

153,50013.71

NominalHeatingCapacityInput

kWBTU/hkW

PURY-P400YLM-A145.0

153,50011.42

NominalCoolingCapacityInput

kWBTU/hkW

PURY-P450YLM-A150.0

170,60014.32

NominalHeatingCapacityInput

kWBTU/hkW

PURY-P450YLM-A156.0

191,10014.93

0000003483.BOOK 276 ページ 2015年1月14日 水曜日 午前11時12分

Page 65: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 277

R2

MEE14K035

8. CAPACITY TABLES YKB/YLM

Total capacity of indoor units

Rat

io o

f cap

acity

Rat

io o

f pow

er in

put

Total capacity of indoor units

Rat

io o

f cap

acity

Rat

io o

f pow

er in

put

CoolingHeating

200 300 500 700400 600 800

0.2

1.2

1.0

0.8

0.6

0.4

1.0

0.8

0.6

0.4

0.2

1.2

PURY-P500YLM-A1

PURY-P400YSLM-A1

CoolingHeating

100 200 400 600300 500 700

0.2

1.2

1.0

0.8

0.6

0.4

1.0

0.8

0.6

0.4

0.2

1.2

NominalHeatingCapacityInput

kWBTU/hkW

PURY-P500YLM-A158.0

197,90016.06

NominalCoolingCapacityInput

kWBTU/hkW

PURY-P400YSLM-A145.0

153,50010.97

NominalHeatingCapacityInput

kWBTU/hkW

PURY-P400YSLM-A150.0

170,60010.98

NominalCoolingCapacityInput

kWBTU/hkW

PURY-P500YLM-A156.0

191,10017.77

0000003483.BOOK 277 ページ 2015年1月14日 水曜日 午前11時12分

Page 66: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 278

R2

MEE14K035

8. CAPACITY TABLES YKB/YLM

Total capacity of indoor units

Rat

io o

f cap

acity

Rat

io o

f pow

er in

put

Total capacity of indoor units

Rat

io o

f cap

acity

Rat

io o

f pow

er in

put

PURY-P450YSLM-A1

CoolingHeating

200 300 500 700400 600 800

0.2

1.2

1.0

0.8

0.6

0.4

1.0

0.8

0.6

0.4

0.2

1.2

CoolingHeating

200 300 500 700400 600 800

0.2

1.2

1.0

0.8

0.6

0.4

1.0

0.8

0.6

0.4

0.2

1.2

PURY-P500YSLM-A1

NominalCoolingCapacityInput

kWBTU/hkW

PURY-P450YSLM-A150.0

170,60012.50

NominalHeatingCapacityInput

kWBTU/hkW

PURY-P450YSLM-A156.0

191,10012.64

NominalHeatingCapacityInput

kWBTU/hkW

PURY-P500YSLM-A163.0

215,00014.65

NominalCoolingCapacityInput

kWBTU/hkW

PURY-P500YSLM-A156.0

191,10014.39

0000003483.BOOK 278 ページ 2015年1月14日 水曜日 午前11時12分

Page 67: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 279

R2

MEE14K035

8. CAPACITY TABLES YKB/YLM

Total capacity of indoor units200 500400300 600 700 900800

Rat

io o

f cap

acity

Rat

io o

f pow

er in

put

1.2

1.0

0.8

0.6

0.2

0.4

1.0

0.8

0.6

0.2

0.4

1.2

Total capacity of indoor units200 400 600 800 1000

Rat

io o

f cap

acity

Rat

io o

f pow

er in

put

0.2

1.2

1.0

0.8

0.6

0.4

1.0

0.8

0.6

0.4

0.2

1.2

PURY-P550YSLM-A1

CoolingHeating

PURY-P600YSLM-A1

CoolingHeating

NominalCoolingCapacityInput

kWBTU/hkW

PURY-P550YSLM-A163.0

215,00016.89

NominalHeatingCapacityInput

kWBTU/hkW

PURY-P550YSLM-A169.0

235,40016.62

NominalCoolingCapacityInput

kWBTU/hkW

PURY-P600YSLM-A169.0

235,40019.32

NominalHeatingCapacityInput

kWBTU/hkW

PURY-P600YSLM-A176.5

261,00019.12

0000003483.BOOK 279 ページ 2015年1月14日 水曜日 午前11時12分

Page 68: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 280

R2

MEE14K035

8. CAPACITY TABLES YKB/YLM

Total capacity of indoor units200 400 600 800 1000

Rat

io o

f cap

acity

Rat

io o

f pow

er in

put

0.2

1.2

1.0

0.8

0.6

0.4

1.0

0.8

0.6

0.4

0.2

1.2

Total capacity of indoor units200 400 800600 1000 1200

Rat

io o

f cap

acity

Rat

io o

f pow

er in

put

0.2

1.2

1.0

0.8

0.6

0.4

1.0

0.8

0.6

0.4

0.2

1.2

PURY-P650YSLM-A1

CoolingHeating

PURY-P700YSLM-A1

CoolingHeating

NominalCoolingCapacityInput

kWBTU/hkW

PURY-P650YSLM-A173.0

249,10021.28

NominalHeatingCapacityInput

kWBTU/hkW

PURY-P650YSLM-A181.5

278,10020.68

NominalCoolingCapacityInput

kWBTU/hkW

PURY-P700YSLM-A180.0

273,00024.24

NominalHeatingCapacityInput

kWBTU/hkW

PURY-P700YSLM-A188.0

300,30022.68

0000003483.BOOK 280 ページ 2015年1月14日 水曜日 午前11時12分

Page 69: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 281

R2

MEE14K035

8. CAPACITY TABLES YKB/YLM

Total capacity of indoor units200 400 800600 1000 1200

Rat

io o

f cap

acity

Rat

io o

f pow

er in

put

0.2

1.2

1.0

0.8

0.6

0.4

1.0

0.8

0.6

0.4

0.2

1.2

Total capacity of indoor units

Rat

io o

f cap

acity

Rat

io o

f pow

er in

put

PURY-P750YSLM-A1

CoolingHeating

PURY-P800YSLM-A1

CoolingHeating

200 400 800 1200600 1000 1400

0.2

1.2

1.0

0.8

0.6

0.4

1.0

0.8

0.6

0.4

0.2

1.2

NominalCoolingCapacityInput

kWBTU/hkW

PURY-P750YSLM-A185.0

290,00026.23

NominalHeatingCapacityInput

kWBTU/hkW

PURY-P750YSLM-A190.0

307,10023.01

NominalCoolingCapacityInput

kWBTU/hkW

PURY-P800YSLM-A190.0

307,10028.30

NominalHeatingCapacityInput

kWBTU/hkW

PURY-P800YSLM-A190.0

307,10022.84

0000003483.BOOK 281 ページ 2015年1月14日 水曜日 午前11時12分

Page 70: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 282

R2

MEE14K035

8. CAPACITY TABLES YKB/YLM

Total capacity of indoor units

Rat

io o

f cap

acity

Rat

io o

f pow

er in

put

Total capacity of indoor units

Rat

io o

f cap

acity

Rat

io o

f pow

er in

put

PURY-P850YSLM-A1

CoolingHeating

200 400 800600

0.2

1.2

1.0

0.8

0.6

0.4

1.0

0.8

0.6

0.4

0.2

1.2

12001000 1400

PURY-P900YSLM-A1

CoolingHeating

200 400 800 1200600 1000 1400

0.2

1.2

1.0

0.8

0.6

0.4

1.0

0.8

0.6

0.4

0.2

1.2

NominalCoolingCapacityInput

kWBTU/hkW

PURY-P850YSLM-A196.0

327,60029.26

NominalHeatingCapacityInput

kWBTU/hkW

PURY-P850YSLM-A1101.0

344,60026.23

NominalCoolingCapacityInput

kWBTU/hkW

PURY-P900YSLM-A1101.0

344,60029.79

NominalHeatingCapacityInput

kWBTU/hkW

PURY-P900YSLM-A1113.0

385,60030.13

0000003483.BOOK 282 ページ 2015年1月14日 水曜日 午前11時12分

Page 71: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 283

R2

MEE14K035

8. CAPACITY TABLES YKB/YLM

8-4. Correction by refrigerant piping lengthCITY MULTI system can extend the piping flexibly within its limitation for the actual situation. However, a decrease of cooling/heating capacity could happen correspondently. Using following correction factor according to the equivalent length of the piping shown at 8-4-1 and 8-4-2, the capacity can be observed. 8-4-3 shows how to obtain the equivalent length of piping.

8-4-1. Cooling capacity correction

Piping equivalent length (m)

1

0.90

0.80

0.95

0.85

0.75

0.65

0.70

Co

olin

g c

ap

aci

ty c

orr

ect

ion

fa

cto

r

PURY-P200YLM-A1(-BS) Total capacity of indoor unit100

150

200300

0 20 40 60 80 100 120 140 160 180Piping equivalent length (m)

1

0.90

0.80

0.95

0.85

0.75

0.65

0.70

Co

olin

g c

ap

aci

ty c

orr

ect

ion

fa

cto

r

0 20 40 60 80 100 120 140 160 180

PURY-P400Y(S)LM-A1(-BS) Total capacity of indoor unit200

300

400

600

Piping equivalent length (m)

1

0.90

0.80

0.95

0.85

0.75

0.65

0.70

Coo

ling

capa

city

cor

rect

ion

fact

or

PURY-P250YLM-A1(-BS) Total capacity of indoor unit125

188

250375

0 20 40 60 80 100 120 140 160 180Piping equivalent length (m)

1

0.90

0.80

0.95

0.85

0.75

0.65

0.70

Coo

ling

capa

city

cor

rect

ion

fact

or

PURY-P450Y(S)LM-A1(-BS)225

338

450

675

Total capacity of indoor unit

0 20 40 60 80 100 120 140 160 180

Piping equivalent length (m)

1

0.90

0.80

0.95

0.85

0.75

0.65

0.70

Co

olin

g c

ap

aci

ty c

orr

ect

ion

fa

cto

r

PURY-P300YLM-A1(-BS) Total capacity of indoor unit150

225

300

4500 20 40 60 80 100 120 140 160 180 0 20 40 60 80 100 120 140 160 180

Piping equivalent length (m)

1

0.90

0.80

0.95

0.85

0.75

0.65

0.70

Co

olin

g c

ap

aci

ty c

orr

ect

ion

fa

cto

r

PURY-P500Y(S)LM-A1(-BS) Total capacity of indoor unit250

375

500

750

Piping equivalent length (m)

1

0.90

0.80

0.95

0.85

0.75

0.65

0.70

Co

olin

g c

ap

aci

ty c

orr

ect

ion

fa

cto

r

0 20 40 60 80 100 120 140 160 180

PURY-P350YLM-A1(-BS) Total capacity of indoor unit175

263

350

525

Piping equivalent length [m]

1

0.90

0.80

0.95

0.85

0.75

0.65

0.70

Coo

ling

capa

city

cor

rect

ion

fact

or

PURY-P550YSLM-A1(-BS)275

413

550

825

Total capacity of indoor unit

0 20 40 60 80 100 120 140 160 180

0000003483.BOOK 283 ページ 2015年1月14日 水曜日 午前11時12分

Page 72: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 284

R2

MEE14K035

8. CAPACITY TABLES YKB/YLM

Piping equivalent length (m)

1

0.90

0.80

0.95

0.85

0.75

0.65

0.70

Co

olin

g c

ap

aci

ty c

orr

ect

ion

fa

cto

r

0 20 40 60 80 100 120 140 160 180

PURY-P600YSLM-A1(-BS) Total capacity of indoor unit300

450

600900

Piping equivalent length (m)

1

0.90

0.80

0.95

0.85

0.75

0.65

0.70

Co

olin

g c

ap

aci

ty c

orr

ect

ion

fa

cto

r

PURY-P800YSLM-A1(-BS) Total capacity of indoor unit400

600

800

1200

0 20 40 60 80 100 120 140 160 180

Piping equivalent length (m)

1

0.90

0.80

0.95

0.85

0.75

0.65

0.70

Co

olin

g c

ap

aci

ty c

orr

ect

ion

fa

cto

r

PURY-P650YSLM-A1(-BS) Total capacity of indoor unit325

488

650

975

0 20 40 60 80 100 120 140 160 180Piping equivalent length (m)

1

0.90

0.80

0.95

0.85

0.75

0.65

0.70

Co

olin

g c

ap

aci

ty c

orr

ect

ion

fa

cto

r

0 20 40 60 80 100 120 140 160 180

PURY-P850YSLM-A1(-BS) Total capacity of indoor unit425

638

850

1275

Piping equivalent length (m)

1

0.90

0.80

0.95

0.85

0.75

0.65

0.70

Co

olin

g c

ap

aci

ty c

orr

ect

ion

fa

cto

r

PURY-P700YSLM-A1(-BS) Total capacity of indoor unit350

525

700

1050

0 20 40 60 80 100 120 140 160 180Piping equivalent length (m)

1

0.90

0.80

0.95

0.85

0.75

0.65

0.70

Coo

ling

capa

city

cor

rect

ion

fact

or

PURY-P900YSLM-A1(-BS)450

675

900

1350

Total capacity of indoor unit

0 20 40 60 80 100 120 140 160 180

Piping equivalent length (m)

1

0.90

0.80

0.95

0.85

0.75

0.65

0.70

Coo

ling

capa

city

cor

rect

ion

fact

or

PURY-P750YSLM-A1(-BS) Total capacity of indoor unit375

563

750

1125

0 20 40 60 80 100 120 140 160 180

0000003483.BOOK 284 ページ 2015年1月14日 水曜日 午前11時12分

Page 73: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 285

R2

MEE14K035

8. CAPACITY TABLES YKB/YLM

8-4-2. Heating capacity correction

0.800 20 40 60 80 100 120 140 160

Hea

ting

capa

city

cor

rect

ion

fact

or

0.90

1.00

Piping equivalent length (m)

PURY-P200YLM-A1(-BS)

0.800 20 40 60 80 100 120 140 160

Hea

ting

capa

city

cor

rect

ion

fact

or

0.90

1.00PURY-P550, 600, 650, 700, 750, 800, 850, 900YSLM-A1(-BS)

Piping equivalent length (m)

0.800 20 40 60 80 100 120 140 160

Hea

ting

capa

city

cor

rect

ion

fact

or

0.90

1.00

Piping equivalent length (m)

PURY-P250, 300YLM-A1(-BS)

0.800 20 40 60 80 100 120 140 160

Hea

ting

capa

city

cor

rect

ion

fact

or

0.90

1.00PURY-P350YLM-A1(-BS)

Piping equivalent length (m)

0.800 20 40 60 80 100 120 140 160

Hea

ting

capa

city

cor

rect

ion

fact

or

0.90

1.00PURY-P400, 450, 500Y(S)LM-A1(-BS)

Piping equivalent length (m)

0000003483.BOOK 285 ページ 2015年1月14日 水曜日 午前11時12分

Page 74: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 286

R2

MEE14K035

8. CAPACITY TABLES YKB/YLM

8-4-3. How to obtain the equivalent piping length

8-5. Correction by port counts of the BC controllerIndoor unit sizes P200 and P250 must be connected to 2 ports on the BC controller.Indoor unit sizes from P100 to P140 should normally be connected to 2 ports on the BC controller (set BC controller DIP-SW 4-6 to its ON position).In cases whereby indoor unit sizes from P100 to P140 are connected to only 1port on the BC controller (set BC controller DIP-SW 4-6 to its OFF position), the cooling capacity of the indoor unit should be multiplied by a correction factor of 0.97.

8-6. Correction at frost and defrostDue to frost at the outdoor heat exchanger and the automatic defrost operation, the heating capacity of the outdoor unit can be calculated by multiplying the correction factor shown in the table below.

1 PURY-P200YLM-A1(-BS)Equivalent length = (Actual piping length to the farthest indoor unit) + (0.35 x number of bends in the piping) m

2 PURY-P250, 300YLM-A1(-BS)Equivalent length = (Actual piping length to the farthest indoor unit) + (0.42 x number of bends in the piping) m

3 PURY-P350YLM-A1(-BS)Equivalent length = (Actual piping length to the farthest indoor unit) + (0.47 x number of bends in the piping) m

4 PURY-P400, 450, 500, 550, 600, 650Y(S)LM-A1(-BS)Equivalent length = (Actual piping length to the farthest indoor unit) + (0.50 x number of bends in the piping) m

5 PURY-P700, 750, 800YSLM-A1(-BS)Equivalent length = (Actual piping length to the farthest indoor unit) + (0.70 x number of bends in the piping) m

6 PURY-P850, 900YSLM-A1(-BS)Equivalent length = (Actual piping length to the farthest indoor unit) + (0.80 x number of bends in the piping) m

PURY-P200YLM-A1(-BS)PURY-P250YLM-A1(-BS)PURY-P300YLM-A1(-BS)PURY-P350YLM-A1(-BS)PURY-P400Y(S)LM-A1(-BS)PURY-P450Y(S)LM-A1(-BS)PURY-P500Y(S)LM-A1(-BS)PURY-P550YSLM-A1(-BS)PURY-P600YSLM-A1(-BS)PURY-P650YSLM-A1(-BS)

PURY-P750YSLM-A1(-BS)PURY-P800YSLM-A1(-BS)PURY-P850YSLM-A1(-BS)PURY-P900YSLM-A1(-BS)

PURY-P700YSLM-A1(-BS)

1.001.001.001.001.001.001.001.001.001.001.001.001.001.001.00

0.950.950.930.930.950.980.980.940.940.940.980.980.980.980.98

0.840.840.820.850.900.890.890.870.840.840.890.890.890.890.89

0.830.830.800.830.870.870.860.860.860.860.880.880.880.880.88

0.830.830.820.840.880.890.890.870.870.870.890.890.890.890.89

0.870.870.860.860.890.900.900.880.880.880.900.900.900.900.90

0.900.900.900.900.900.920.920.900.900.900.920.920.920.920.92

0.950.950.900.900.950.950.950.900.900.900.950.950.950.950.95

0.950.950.950.950.950.950.950.930.930.930.950.950.950.950.95

0.950.950.950.950.950.950.950.930.930.930.950.950.950.950.95

0.950.950.950.950.950.950.950.930.930.930.950.950.950.950.95

0000003483.BOOK 286 ページ 2015年1月14日 水曜日 午前11時12分

Page 75: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 287

R2

MEE14K035

9. OPTIONAL PARTS YKB/YLM

9. OPTIONAL PARTS9-1. JOINTCITY MULTI units can be easily connected by using Joint sets and Header sets provided by Mitsubishi Electric. Three kinds of Joint sets are available for use. Refer to section 3 in "System Design" or the Installation Manual that comes with the Joint set for how to install the Joint set.

For Gas pipe:

*Pipe diameter is indicated by inside diameter.

CMY-Y102SS-G2<Deformed pipe(Accessory)>

ø15.88

ø19.05ø19.05

30

58 (2 Pcs.)

(Outside diameter)

(Outside diameter)

(Outside diameter)

ø19.05

ø19.05

ø12.7ø15.88

ø15.88

ø12.7

28

30

37

36

18

ø9.52

ø9.52

ø9.52(Outside diameter)

ø9.52

(2 Pcs.)

ø6.35

20

For Liquid pipe:mm

<Deformed pipe(Accessory)>

For Gas pipe: For Liquid pipe:

*Pipe diameter is indicated by inside diameter.

mmCMY-Y102LS-G2

<Deformed pipe(Accessory)>

<Deformed pipe(Accessory)>

ø25.4 ø25.4

ø19.05

76

39

(2 Pcs.)

(2 Pcs.)

(2 Pcs.)

(Outside diameter)

(Outside diameter)

(Outside diameter)

(Outside diameter)

(Outside diameter)

(Outside diameter)

(Outside diameter)

54

41

45

42

54

30

37

ø22.2ø25.4

ø25.4 ø28.58

ø19.05ø25.4

ø15.88ø25.4ø19.05

ø19.05

ø12.7ø19.05

ø15.88

ø22.2ø9.52

ø12.7 ø12.7

40

20

(2 Pcs.)

(Outside diameter)

(Outside diameter)

ø12.7

ø9.52

23

20

ø9.52

ø6.35

For Gas pipe:

*Pipe diameter is indicated by inside diameter.

mmCMY-Y202S-G2

<Deformed pipe(Accessory)>

<Deformed pipe(Accessory)>

ø15.88(Outside diameter)

ø12.7(Outside diameter)

(Outside diameter)

(Outside diameter)

ø12.7

ø15.88

28

23

28

23

ø9.52

ø6.35

ø9.52

ø12.7

ø12.7ø15.88 ø15.88

49

23

ø25.4 ø25.4ø19.05

76

39

(3 Pcs.)

(Outside diameter)

(Outside diameter)

(Outside diameter)

(Outside diameter)

(Outside diameter)

(Outside diameter)

54

54

42

54

30

37

ø22.2ø25.4

ø25.4 ø28.58

ø25.4ø19.05

ø19.05

ø19.05

ø12.7ø19.05

ø15.88

ø22.2

For Liquid pipe:

0000003483.BOOK 287 ページ 2015年1月14日 水曜日 午前11時12分

Page 76: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 288

R2

MEE14K035

9. OPTIONAL PARTS YKB/YLM

9-2. OUTDOOR TWINNING KITThe following optional Outdoor Twinning Kit is needed to use to combine multiple refrigerant pipes. Refer to the chapter entitled System Design Section for the details of selecting a proper twinning kit.

50

50

36

36

62

62

80

35

214 16

191

58

115

62

1007 30

407

14635

62

17117

85

ø25.4

ø28.58

ø28.58ø28.58

ø22.2ø22.2

ø19.05

ø22.2

ø22.2

ø19.05

ø22.2

ø25.4ø19.05

±15°

ø19.05

ø19.05

ø22.2

ø19.05 ø15.88

ø19.05

ø19.05ø15.88

ø25.4

(Outside diameter)

(Outside diameter)

<Deformed pipe(Accessory)>

<Elbow pipe(Accessory)> <Accessory> Fixing screw ……1 Pipe cover ……1 Cable tie ……2 Insulation cover ……1 Buffer ……1

(Outside diameter)

(Outside diameter)

<Pipe for routing through the bottom (Accessory)>

(Outside diameter) high-pressure side

Slope of the twinning pipe is at an anglewithin ±15° to the horizontal plane.

Note 1:Refer to the figure below for the installation position of the twinning pipe.

2:Pipe diameter is indicated by inside diameter.

<Deformed pipe(Accessory)>

(Outside diameter)

(3Pcs.)

<Pipe for routing through the front (Accessory)>

Twinning pipe on the

(Outside diameter)

High-pressure twinning pipe

Low-pressure pipe twinning kitCMY-R100VBK-A

<Deformed pipe(Accessory)><Low-pressure pipe twinning kit(Accessory)>

High-pressure twinning pipe

Low-pressure pipe twinning kit

<Deformed pipe(Accessory)> <Pipe for routing through the bottom (Accessory)>

<Pipe for routing through the front (Accessory)>

<Elbow pipe(Accessory)>

25.4

19.05

15.88

15.88

15.88(Outside diameter) 15.88

19.05(Outside diameter)

25.4

(Outside diameter)

(Outside diameter)

(Outside diameter)

(Outside diameter)

(3Pcs.)

19.05

19.05

(Outside diameter)

(Outside diameter)

(Outside diameter)

19.05

25.4

25.4

25.4

25.4

22.2

22.2 28.58

19.05 15.88 19.05

19.05

22.2

28.58

19.05 22.2

22.2 22.2

28.58

28.58

19.05 19.05

2725

60

191115

16214

192 16

115

58

191

19193

58

60

8080

60

8933

106

62

62

80

35

13316

176

432

62

36

36

50

50

16214

85

(Outside diameter) 15.88 19.05

(Outside diameter) 19.05 22.2

62

CMY-R100VBK2

Slope of the twinning pipe is at an angle within to the horizontal plane.

2. Use the attached pipe to braze the port-opening of the distributer.3. Pipe diameter is indicated by inside diameter.

Note 1. Refer to the figure below for the installation position of the twinning pipe. Twinning pipe on the

high-pressure side

15

15

4. Only use the Twinning pipe by Mitsubishi (optional parts) .

0000003483.BOOK 288 ページ 2015年1月14日 水曜日 午前11時12分

Page 77: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 289

R2

MEE14K035

9. OPTIONAL PARTS YKB/YLM

(Outside diameter)

(Outside diameter)

(Outside diameter)

(Outside diameter)

<Elbow pipe(Accessory)>

<Deformed pipe(Accessory)>

<Deformed pipe(Accessory)>

<Pipe for routing through the bottom (Accessory)>

<Pipe for routing through the front (Accessory)>

(2Pcs.)

(Outside diameter)

(Outside diameter)

<Accessory> Fixing screw ……1 Pipe cover ……1 Cable tie ……2 Insulation cover ……1

(Outside diameter)high-pressure side

Slope of the twinning pipe is at an anglewithin ±15° to the horizontal plane.

Note 1:Refer to the figure below for the installation position of the twinning pipe.

2:Pipe diameter is indicated by inside diameter.

Twinning pipe on the

108

32

26

6217

6

427

62

160

50

50

35

80

53

53

62

62

190117

60

217 14

ø31.75

ø28.58

ø25.4

ø22.2

ø28.58

ø19.05

ø28.58ø28.58

ø19.05

ø19.05ø28.58

ø31.75ø31.75

ø19.05 ø22.2

ø34.93ø31.75

ø22.2

ø25.4

ø22.2

ø25.4ø22.2

±15°

25136

35

High-pressure twinning pipe

Low-pressure pipe twinning kitCMY-R200VBK2

High-pressure twinning pipe

Low-pressure pipe twinning kit

CMY-R200XLVBK

<Deformed pipe (Accessory)>

<Elbow pipe (Accessory)>

<Deformed pipe (Accessory)>

<Pipe for routing through the bottom (Accessory)>

<Pipe for routing through the front (Accessory)>

(3Pcs.)

(Outside diameter)31.75

28.58(Outside diameter)

28.58

41.2834.93(Outside diameter)

22.2 19.05(Outside diameter)

25.4

19.05

25.4(Outside diameter)

(Outside diameter)

(Outside diameter)31.75 34.93

28.58

28.58

19.05

19.0528.58

19.05

31.75

31.75

19.05 22.2

108

32

26

62

176

42725 35

136

69

62

214 16

191

58

115

160

50

50

35

80

53

53

62

±15º

High-pressure twinning pipe

On-site pipes

Inclination tolerance of thehigh-pressure twinning pipe is ±15ºrelative to the ground.

2. Pipe diameter is indicated by inside diameter.

<Accessory> Fixing screwPipe coverCable tieInsulation cover

• • • 1• • • 1• • • 2• • • 1

Note 1. Refer to the figure below for the installation position of the high-pressure twinning pipe.

Slope of the twinning pipe is at an angle within to the horizontal plane.

2. Use the attached pipe to braze the port-opening of the distributer.3. Pipe diameter is indicated by inside diameter.

Note 1. Refer to the figure below for the installation position of the twinning pipe. Twinning pipe on the

high-pressure side

15

15

4. Only use the Twinning pipe by Mitsubishi (optional parts) .

0000003483.BOOK 289 ページ 2015年1月14日 水曜日 午前11時12分

Page 78: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 290

R2

MEE14K035

9. OPTIONAL PARTS YKB/YLM

9-3. JOINT KIT "CMY-R160-J1" FOR BC CONTROLLER

2 Joint pipe (for liquid side) 3 Joint pipe (for gas side) mm(in.)

PURY-(E)P-Y(S)LM-A(1)

Joint kitCMY-R160-J1

CMY-Y102SS-G2Joint BC controller

Fig.1. CMY-R160-J1 applying scheme

IU IU IU

IU IU IU IU

Group1Total Indoor Capacity<=P80

Group2Total Indoor CapacityP81 to P250

Group3Indoor CapacityP100 to P250

Piping to indoor unit(Non-oxidized brazing)

Joint pipe (for liquid side)2

Joint pipe(for gas side)3

Fig.2. Connecting CMY-R160-J1

1. Designing CMY-R160-J1 to a PURY-(E)P-Y(S)LM-A(1) systemThe maximum down-stream Indoor capacity for 1 port of BCcontroller is P80. When the down-stream Indoor capacity isabove P80, Joint kit CMY-R160-J1 is needed to combined 2ports of BC controller to enlarge the capacity, like Group 2 and3 in Fig. 1.Maximum 3 Indoor units are allowed to connect to 1 port of BCcontroller or 2 combined ports of BC controller using CMY-R160-J1.When connecting Indoor units to 1 port of BC controller or 2combined ports of BC controller using CMY-R160-J1 or CMY-Y102SS-G2 is applicable, like Group 1 and 2 in Fig. 1

Caution: Mixed cooling and heating mode at the same time forIndoor units connecting to 1 port or 2 combined ports is notavailable.

2. Piping at the installation siteThe connection of CMY-R160-J1 to BC controller and pipe leading to Indoor units is referable to Fig. 2. Non-oxidized brazing isnecessary. All piping must be careful to avoid foreign material getting inside.After piping and air-tight testing, insulation work to the Joint and pipe should be done. Details is available at the Installation Manual.

Joint kit "CMY-R160-J1" for BC controller is used to combine 2 ports of the BC controller at a PURY-(E)P-Y(S)LM-A(1) system so as to enable down-stream Indoor capacity above P80 as shown in Fig. 1.

ø15.88(5/8")ø9.52(3/8")

ø19.

05(3

/4")

ø9.5

2(3/

8")

ø15.88(5/8")ø9.52(3/8")

226(8-29/32")226(8-29/32")

60(2

-3/8

")

60(2

-3/8

")

Instruction

This sheet

Please prepare the following items in the field. Tape for insulation material sealing Extension pipe for refrigerant circuit1pc 1pc 1pc 1pc for gas side 1pc for Iiquid side 8pcs 1pc 1pc2pcs

Cover 1 Cover 2 Cover 3 Band Reducer 2Joint pipe(Small) Joint pipe(Large) 7 9Reducer 1865432

2

1

1

OD19.05-ID22.2 OD19.05-ID15.88

The Joint kit include following items:

Cutting point

Have pipe expansion of indoor unit connecting port by cutting the piping at the cutting point.Remove burr after cutting the piping to prevent entering the piping.Check that there is no crack at the pipe expansion part.

0000003483.BOOK 290 ページ 2015年1月14日 水曜日 午前11時12分

Page 79: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 291

R2

MEE14K035

9. OPTIONAL PARTS YKB/YLM

9-4. RELAY BOXIf there is a risk that the drain water will freeze inside the outdoor unit, the installation of a base heater is recommended. PAC-BH02KTY-E is a relay box for controlling the electric base heater. For details, refer to the relay box Installation Manual.

172(

6-3/

4)

147(5-3/4) 72(2-7/8)

0000003483.BOOK 291 ページ 2015年1月14日 水曜日 午前11時12分

Page 80: R2 SERIES YKB/YLM - mitsubishitech.co.ukmitsubishitech.co.uk/Data/City-Multi_Outdoor/PURY_Standard/2016... · 2 - 213 r2 series ykb/ylm outdoor units mee14k035 i.r2 series 1. specifications

2 - 292

R2

MEE14K035

9. OPTIONAL PARTS YKB/YLM

9-5. BASE HEATERIf there is a risk that the drain water will freeze inside the outdoor unit, the installation of a base heater is recommended. For details, refer to the base heater Installation Manual.

Base heaterPAC-BH04EHT-E (for S module)

PAC-BH05EHT-E (for L module)Right base heater(right side of the unit)

Left base heater(left side of the unit)

PAC-BH06EHT-E (for XL module)

Right base heater(right side of the unit)

Left base heater(left side of the unit)

0000003483.BOOK 292 ページ 2015年1月14日 水曜日 午前11時12分