Oleh: Ribut Sugiharto
PENDAHULUAN
455
Temperature plays an important role in maintaining the quality of
stored food products. Lowering the temperature retards the rates of
reactions that cause quality deterioration. It is generally agreed
that the reaction rate is reduced by half by lowering the
temperature by 10°C.
In earlier days, a lower temperature was obtained by the use of
ice. Ice was allowed to melt in an insulated chamber that contained
food prod- ucts ( Fig. 6.1 ). During melting, ice requires latent
heat (333.2 kJ/kg) to be converted from the solid phase to liquid
water. This heat was extracted from the product that was kept next
to ice in an insulated chamber.
Today, the cooling process is achieved by the use of a mechanical
refrigeration system. Refrigeration systems allow transfer of heat
from the cooling chamber to a location where the heat can easily be
dis- carded. The transfer of heat is accomplished by using a
refrigerant, which like water changes state—from liquid to vapor.
Unlike water, a refrigerant has a much lower boiling point. For
example, ammonia, a commonly used refrigerant in industrial plants,
has a boiling point of !33.3°C. This is a much lower temperature
compared with 100°C, the boiling point of water at atmospheric
pressure. Similar to water, ammonia needs latent heat to change its
phase from liquid to gas at its boiling point. The boiling point of
a refrigerant can be varied by changing the pressure. Thus, to
increase the boiling point of ammo- nia to 0°C, its pressure must
be raised to 430.43 kPa.
A very simple refrigeration system that utilizes a refrigerant is
shown in Figure 6.2 . The only drawback in this illustration is the
onetime use of the refrigerant. Because refrigerants are expensive,
they must
6 Refrigeration
Chapter
All icons in this chapter refer to the author’s web site, which is
independently owned and operated. Academic Press is not responsible
for the content or operation of the author’s web site. Please
direct your web site comments and questions to the author:
Professor R. Paul Singh, Department of Biological and Agricultural
Engineering, University of California, Davis, CA 95616, USA. Email:
[email protected].
Ice
Jurusan Teknologi Hasil Pertanian Fakultas Pertanian Universitas
Lampung
Ribut Sugiharto
Evaporator Condenser
Jenis Media Penyerap Panas 1. Air (Es)
• Es mencair memerlukan panas latent (333,2 kJ/kg). • Panas diserap
dari lingkungannya.
2. Refrigenant • Mechanical refrigeration system. • mempunyai titik
didih sangat rendah (<15oC) dan
suhu kondensasi tinggi (>30oC). • Contoh: freon (12, 22, 30,
134a), amonia.
Jurusan Teknologi Hasil Pertanian Fakultas Pertanian Universitas
Lampung
SYARAT REFRIGERANT a. Panas latent penguapan besar. b. Tekanan
kondesasi rendah. c. Suhu pembekuan dibawah suhu penguapan. d. Suhu
kritis tinggi, lebih tinggi suhu kamar. e. Tidak beracun. f. Tidak
mudah terbakar. g. Tidak menyebabkan korosi. h. Secara kimia
stabil. i. Mudah dideteksi bila terjadi kebocoran. j. Murah. k.
Tidak merusak lingkungan.
ASHRAE Standard No. 34-1978
458 CHAPTER 6 Refrigeration
A number of refrigerants used in commercial practice are halocar-
bons, although their use is being severely curtailed as described
later in this section. Refrigerant-12, also called Freon 12, is a
dichlorodi- fl uoromethane. Its latent heat of vaporization is low
compared with ammonia (R-717); therefore, considerably more weight
of the refrig- erant must be circulated to achieve the same
refrigeration capacity.
Table 6.1 Comparison between Commonly Used Refrigerants
(Performance Based on !15°C Evaporator Temperature and 30°C
Condenser Temperature)
Chemical formula
CHClF2) HFC 134a (CH2FCF3)
Boiling point (°C) at 101.3 kPa !29.8 !40.8 !26.16 !33.3
Evaporator pressure at !15°C (kPa) 182.7 296.4 164.0 236.5
Condensing pressure at 30°C (kPa) 744.6 1203.0 770.1 1166.5
Freezing point (°C) at 101.3 kPa !157.8 !160.0 !96.6 !77.8
Critical temperature (°C) 112.2 96.1 101.1 132.8
Critical pressure (kPa) 4115.7 4936.1 4060 11423.4
Compressor discharge temperature (°C)
37.8 55.0 43 98.9
Latent heat of vaporization at !15°C (kJ/kg)
161.7 217.7 209.5 1314.2
Refrigerant circulated/ton refrigeration (kg/s), ideal
2.8 " 10!2 2.1 " 10!2 2.38 " 10!2 0.31 " 10!2
Compressor displacement/ton refrigeration (m3/s)
Stability (toxic decomposition products)
No
JENIS REFRIGERANT
KOMPONEN SISTEM REFRIGERASI
EVAPORATOR Fungsi: • Tempat refrigerant berubah fase dari cair
menjadi uap/
gas. • Memerlukan panas latent dan menyerap panas dari
lingkungannya. Jenis: 1. Direct expansion,
• Refrigerant menguap pada koil, dan koil menyerap panas langung
dari lingkungannya.
2. Indirect expansion, • Refrigerant mendinginkan medium (air,
brine, glycol),
yang kemudian dipompakan ke bahan yang didinginkan.
Jurusan Teknologi Hasil Pertanian Fakultas Pertanian Universitas
Lampung
EVAPORATOR
EVAPORATOR
COMPRESSOR
COMPRESSOR
CONDENSER Fungsi: • Transfer panas dari
refrigerant ke sekelilingnya (udara, air).
• Mengubah fase uap refrigerant menjadi fase cair.
Jenis: 1. Berpendingin udara. 2. Berpendingin air. 3. Evaporasi
(udara + air)
Jurusan Teknologi Hasil Pertanian Fakultas Pertanian Universitas
Lampung
CONDENSER 467
Air-cooled condensers can be either tube-and-fi n type or plate
type, as shown in Figure 6.10 . Fins on tubes allow a large heat
transfer area in a compact case. The plate condensers have no fi
ns, so they require considerably larger surface areas. However,
they are cheaper to con- struct and require little maintenance.
Both these types of condensers can be found in household
refrigerators.
Air-cooled condensers can also employ artifi cial movement of air
by using a fan. The fan helps in obtaining higher convective
heat-transfer coeffi cients at the surface of the condenser.
Water
Water
Water
Water
Water
Hot gas
Liquid refrigerant
Figure 6.9 An open shell-and-tube condenser and double-pipe
condenser. (Courtesy of Carrier Co.)
Figure 6.10 A plate and tube-and-fi n condenser. (Courtesy of
Carrier Co.)
6.2 Components of a Refrigeration System
Jenis berpendingin air: 1. Open shell and tube. 2. Double pipe. 3.
Plate. 4. Tube and Fin.
Jenis berpendingin udara: 1. Plate. 2. Tube and Fin
Jurusan Teknologi Hasil Pertanian Fakultas Pertanian Universitas
Lampung
CONDENSER
EXPANSION VALVE Fungsi: • Menurunkan tekanan refrigerant •
Menentukan laju alir (jumlah) refrigerant cair masuk ke
dalam evaporator.
468 CHAPTER 6 Refrigeration
In evaporative condensers, a circulating water pump draws water
from a pan at the base of the condenser and sprays the water onto
the coils. In addition, a large amount of air is drawn over the
condenser coils. Evaporation of water requires latent heat, which
is extracted from the refrigerant. Figure 6.11 shows an evaporative
condenser. These units can be quite large.
6.2.4 Expansion Valve An expansion valve is essentially a metering
device that controls the fl ow of liquid refrigerant to an
evaporator. The valve can be operated either manually or by sensing
pressure or temperature at another desired location in the
refrigeration system.
The common type of metering devices used in the refrigeration sys-
tem include (1) manually operated expansion valve, (2) automatic
low-side fl oat valve, (3) automatic high-side fl oat valve, (4)
automatic expansion valve, and (5) thermostatic expansion
valve.
A simple, manually operated expansion valve is shown in Figure 6.12
. The valve, manually adjusted, allows a desired amount of fl ow of
refrigerant from the high-pressure liquid side to the low-pressure
gas/ liquid side. The refrigerant cools as it passes through the
valve. The heat given up by the liquid refrigerant is absorbed to
convert some of
Moist air exit
Hot gas inlet Air inlet
Figure 6.11 An evaporative condenser. (From Jennings, 1970.
Copyright © 1939, 1944, 1949, 1956 , 1958 , 1970 by Harper and Row,
Publishers, Inc. Reprinted with permission of the publisher.)
Low-pressure gas and liquid
High-pressure liquid
Figure 6.12 A manually operated expansion valve. (Courtesy of
Carrier Co.)
w
470 CHAPTER 6 Refrigeration
fl oat consequently rises and opens the orifi ce, allowing the
refrigerant to fl ow to the evaporator.
The automatic expansion valve maintains a constant pressure in the
evaporator. As shown in Figure 6.15 , an increase in evaporator
pres- sure causes the diaphragm to rise against the spring
pressure, which results in the valve closing. The valve opens when
the evaporator pressure decreases. This valve is used in
applications that require a constant refrigeration load and
constant evaporator temperature—for example, in a household
refrigerator.
Thermal expansion valves contain a thermostatic bulb clamped to the
side of the suction pipe to the compressor ( Fig. 6.16 ). The
thermo- static bulb senses the temperature of the superheated gas
leaving the evaporator. The relatively high temperature of the
thermostatic bulb causes the fl uid in the bulb (usually the same
refrigerant) to increase in pressure. The increased pressure is
transmitted via the thermo- static tube to the bellows and the
diaphragm chamber. The valve consequently opens to allow more
liquid refrigerant to fl ow through. Thermostatic valves are the
most widely used of all metering devices in the refrigeration
industry.
6.3 PRESSURE–ENTHALPY CHARTS Both pressure and enthalpy of the
refrigerant change as the refrigerant is conveyed through various
components of a refrigeration system. In both the evaporator and
the condenser, the enthalpy of the refriger- ant changes and the
pressure remains constant. During the compres- sion step, work is
done by the compressor, resulting in an increase in the enthalpy of
the refrigerant along with an increase in pressure. The expansion
valve is a constant-enthalpy process that allows the liquid
refrigerant under high pressure to pass at a controlled rate into
the low-pressure section of the refrigeration system.
Charts or diagrams have been used extensively in the literature to
present thermodynamic properties of refrigerants. These charts are
particularly useful during the early, conceptual stages of a
refrigera- tion system design. Looking at a chart, we can easily
comprehend a standard process, as well as any deviations from the
standard. Most commonly used charts depict enthalpy and pressure
values on the x and y axes, respectively. Another type of chart
involves entropy and temperature values plotted along x and y axes,
respectively. The entire
Bulb pressure
Figure 6.16 A thermostatic expansion valve. (Courtesy of Carrier
Co.)
Spring pressure
Evaporator pressure
Figure 6.15 An automatic expansion valve. (Courtesy of Carrier
Co.)
w
470 CHAPTER 6 Refrigeration
fl oat consequently rises and opens the orifi ce, allowing the
refrigerant to fl ow to the evaporator.
The automatic expansion valve maintains a constant pressure in the
evaporator. As shown in Figure 6.15 , an increase in evaporator
pres- sure causes the diaphragm to rise against the spring
pressure, which results in the valve closing. The valve opens when
the evaporator pressure decreases. This valve is used in
applications that require a constant refrigeration load and
constant evaporator temperature—for example, in a household
refrigerator.
Thermal expansion valves contain a thermostatic bulb clamped to the
side of the suction pipe to the compressor ( Fig. 6.16 ). The
thermo- static bulb senses the temperature of the superheated gas
leaving the evaporator. The relatively high temperature of the
thermostatic bulb causes the fl uid in the bulb (usually the same
refrigerant) to increase in pressure. The increased pressure is
transmitted via the thermo- static tube to the bellows and the
diaphragm chamber. The valve consequently opens to allow more
liquid refrigerant to fl ow through. Thermostatic valves are the
most widely used of all metering devices in the refrigeration
industry.
6.3 PRESSURE–ENTHALPY CHARTS Both pressure and enthalpy of the
refrigerant change as the refrigerant is conveyed through various
components of a refrigeration system. In both the evaporator and
the condenser, the enthalpy of the refriger- ant changes and the
pressure remains constant. During the compres- sion step, work is
done by the compressor, resulting in an increase in the enthalpy of
the refrigerant along with an increase in pressure. The expansion
valve is a constant-enthalpy process that allows the liquid
refrigerant under high pressure to pass at a controlled rate into
the low-pressure section of the refrigeration system.
Charts or diagrams have been used extensively in the literature to
present thermodynamic properties of refrigerants. These charts are
particularly useful during the early, conceptual stages of a
refrigera- tion system design. Looking at a chart, we can easily
comprehend a standard process, as well as any deviations from the
standard. Most commonly used charts depict enthalpy and pressure
values on the x and y axes, respectively. Another type of chart
involves entropy and temperature values plotted along x and y axes,
respectively. The entire
Bulb pressure
Figure 6.16 A thermostatic expansion valve. (Courtesy of Carrier
Co.)
Spring pressure
Evaporator pressure
Figure 6.15 An automatic expansion valve. (Courtesy of Carrier
Co.)
w
KOMPONEN SISTEM REFRIGERASI