24
Rotronic goes CO2!

Rotronic goes CO2!

  • Upload
    meriel

  • View
    58

  • Download
    0

Embed Size (px)

DESCRIPTION

Rotronic goes CO2!. CO2. Topics: CO2 in general CO2 transmitter CO2 & Temp. transmitter CO2 special transmitter . CO2 in general. Big topic over the last year, everybody has it.. e.g. Green house effect and environment … . CO2 in general. CO2 in general. Photosynthesis : - PowerPoint PPT Presentation

Citation preview

Rotronic goes CO2!

CO2Topics:• CO2 in general• CO2 transmitter• CO2 & Temp. transmitter• CO2 special transmitter

CO2 in general

Big topic over the last year, everybody has it.. e.g. Green house effect and environment …

CO2 in general

CO2 in general

Photosynthesis:Chemical recation CO2 + H2O --> CHO + O2 + H2O

Carbon dioxide, water using light and chlorophyll, oxygen and glucose

CO2 in general

CO2 in generalIndoor air quality in offices leads to high or low levels of gases:

Since CO2 is exhaled by people at predictable levels the content of Carbon Dioxide - CO2 – in air may be a significant indication of air quality.

A measure of CO2 indicates the amount of fresh air supply:15 cfm = 7.0l/s ventilation rate per occupant

corresponds to 1000 ppm CO2

20 cfm = 9.2l/s ventilation rate per occupant corresponds to 800 ppm CO2

Normal CO2 LevelsThe effects of increased CO2 summarized:

•  normal outdoor level: 350 - 450 ppm• acceptable levels: < 600 ppm• complaints of stiffness and odors: 600 - 1000 ppm• ASHRAE and OSHA standards: 1000 ppm• general drowsiness: 1000 - 2500 ppm• adverse health effects expected: 2500 - 5000 ppm• maximum allowed concentration within a 8 hour working period:

5000 ppm 

CO2 in general

CO2 in general

Extreme and Dangerous CO2 Levels

• slightly intoxicating, breathing and pulse rate increase, nausea: 30,000 ppm

• above plus headaches and sight impairment: 50,000 ppm

• unconscious, further exposure death: 100.000 ppm

Rotronic CO2 transmitter Portfolio

CO2 transmitter

CO2 transmitter for climate control• EU/US electrical junction box• Selectable with and without display• for fixed installation

“decreasing your energy consumption while creating a healthier indoor air climate”

CO2 transmitter

Specification EU:• Measurement range : 0…2000 ppm• Method infrared (NDIR) w. Auto calibration • Accuracy : ± 30 ppm• Supply : 24 VDC/AC• Output 1 : 0…10 VDC (CO2)• Output 2: 4…20 mA (CO2)• Operation temperature : 0…50 °C• Dimensions (H x W x D): 100 x 80 x 25 mm

CF3-W-EU

CF3-W-EU-Dips

CO2 transmitter

Specification US:• Measurement range : 0…2000 ppm• Measurement method:

Infrared (NDIR) w. Auto calibration • Accuracy : ± 30 ppm• Supply : 24 VDC/AC• Output 1 : 0…10 VDC (CO2)• Output 2: 4…20 mA (CO2)• Operation temperature : 0…50 °C• Dimensions (H x W x D): 130 x 85 x 30 mm

CF3-W-US

CF3-W-US-Dips

CO2 transmitter

Specification for duct version:• Measurement range : 0…2000 ppm• Method infrared (NDIR) w. Auto calibration • Accuracy : ± 30 ppm• Supply : 24 VDC/AC• Output 1 : 0…10 VDC (CO2)• Output 2: 4…20 mA (CO2)• Operation temperature : 0…50 °C

CF3-D

CF3-D-Dips

CO2 & Temperature transmitter

CO2 & temperature transmitter for:• BMS• Controlling Ventilation, Air flaps &

valves “decreasing your energy consumption while creating a healthier indoor air climate”

DuctWall

Specification for wall mount:• Measurement range : 0…2000 ppm• Measurement Temperature: 0.. 50 °C• Method infrared (NDIR) w. Auto calibration • Accuracy : ± 30 ppm• Supply : 24 VDC/AC• Output 1 : 0…10 VDC (CO2)• Output 2: 4…20 mA (CO2)• Operation temperature : 0…50 °C• Dimensions (H x W x D): 120 x 82 x 30 mm

CF5-W

CF5-W-Dips

CO2 & Temperature transmitter

Specification for duct mount:• Measurement range : 0…2000 ppm• Measurement Temperature: 0.. 50 °C• Method infrared (NDIR) w. auto calibration • Accuracy : ± 30 ppm• Supply : 24 VDC/AC• Output 1 : 0…10 VDC (CO2)• Output 2: 4…20 mA (CO2)• Operation temperature : 0…50 °C• Dimensions (H x W x D): 142 x 84 x 46 mm• Ductprobe: 245 mm

CF5-D

CF5-D-Dips

CO2 & Temperature transmitter

CO2 special transmitter

Special CO2 transmitters:• „Fresh Air Indication“• Carbon dioxide alarm • Sound & light indication• relays out’s • bigger ranges • for classrooms , offices , controllers

and more“decreasing your energy consumption while creating a healthier indoor air climate”

CO2 special transmitter

CF3-W-EU-Displ-FLI

Special CO2 transmitters wall mount:• Measurement range : 0…2000 ppm• Method Infrared (NDIR) w. Auto calibration • Accuracy : ± 30 ppm• Supply : 24 VDC/AC• Output 1 : 0…10 VDC (CO2)• Sound & light indication• Operation temperature : 0…50 °C• Dimensions (H x W x D): EU: 100x 80 x 28 mm // US: 130x 85 x 30 mm

CF3-W-US-Displ-FLI

CO2 special transmitterSpecial CO2 transmitters alarm and relays:• Measurement range : 0..4% CO2• Accuracy : ± 200 ppm

• Supply : 24 VDC/AC• Output 1 : 0 … 20mA or 0/2 ... 10 VDC (CO2)• Output 2: 0 … 20mA or 0/2 ... 10 VDC (CO2)• Output 3 (relay 1): Open > 1.4% closed >1.5% (CO2)• Output 4 (relay 2): Open > 2.9% closed >3.0% (CO2)

• Operation temperature : 0…50 °C• Dimensions (H x W x D): 142 x 84 x 46mm

CF8-W-Disp-AL

CO2 special transmitterSpecial CO2 transmitters for Green House:• Measurement range : 0…4000 ppm• Accuracy : ± 200 ppm

• Supply : 24 VDC/AC• Output 1 : 0 … 20mA or 0/2 ... 10 VDC (CO2)• Output 2: 0 … 20mA or 0/2 ... 10 VDC (°C)• Output 3 (relay): Open > 2.0% closed >1.9% (CO2)

• Operation temperature : 0…50 °C• Dimensions (H x W x D): 142 x 84 x 46mm CF8-W-Disp-GH

CO2 special transmitterSpecial CO2 transmitters for incubators:• Measurement range : 0…3000 ppm• Accuracy : ± 200 ppm

• Supply : 24 VDC/AC• Output 1 : 0... 5 VDC, 0…2% (CO2)• Output 2: 0… 5 VDC, 0…3 % (CO2)

• Operation temperature : 0…50 °C• Dimensions (H x W x D): 142 x 84 x 46mm

CF8-D_W-Disp-IN

Thanks for your attention!