Mendenhall Water Treatment Plant July 24, 2017 D-45473.00
Section 16915 Flow Monitoring
1. General
1.1 Description
.1 For all instrumentation, the Equipment Supplier shall furnish all labour, materials,
components, and programming, and shall provide all design, assembly, and start-up
services required to provide a complete and workable system.
.2 Provide assistance to the Owner and Engineer for the testing and commissioning of the
instrumentation.
1.2 Operation and Maintenance Manuals
.1 Provided for insertion within the general project operation and maintenance manuals shall
be at least four copies of original equipment manufacturer printed manuals. These shall
include at a minimum:
Full User Manual
Installation Instructions
Full list of Parameters/Programming Manual
Troubleshooting/Maintenance Manual
.2 A complete list of all parameters programmed into each instrument at the end of
commissioning shall be provided for insertion within the general project operation and
maintenance manuals. These lists shall be clearly sorted by instrument tag number.
1.3 Submittals
.1 Submit shop drawings for all flowmeters and flow switches providing full details on make,
pipe size, measuring range, instrumentation tag number, full model number (with options
clearly indicated), dimensions, wiring and power requirements, digital communication
addresses (Modbus, Profibus, Foundation Fieldbus, etc.), and all installation accessories
for each flowmeter.
.2 Shop drawing submittals for flowmeters shall be clearly identified by tag number. For
example: “50mm Flowmeter A - FIT-123” and “150mm Flowmeter B – FIT-456”. Like
flowmeters can be combined for example: “100mm Flowmeter C – FIT-123/FIT-456/FIT-
789”.
Section 16915
Flow Monitoring
Page 2 of 3
Regional District of North Okanagan July 2017
Duteau Creek WTP UV Upgrades
2. Products
2.1 Magnetic Flowmeter (Chlorine Flow Measurement)
.1 Flowmeter shall be magnetic type and suitable for 0.8 Sodium Hypochlorite solution water
flow.
.2 Acceptable flow range shall be from 0.1 to 1350 L/Hr, with meter accuracy of within 2%
of scale down to 40 L/hr.
.3 The sensor tube shall inherently meet NEMA 4X requirements and be provided with two
316L grounding rings, complete with straps. Grounding ring thickness shall be as follows:
Up to and including 300mm: minimum 3.2mm thick
Above 300mm: minimum 6.4mm thick
.4 Provided with the meter shall be a remote wall mounted transmitter with display board
capable of providing bidirectional rate of flow and totalization. Operating parameters and
units of measurement shall be operator definable.
.5 Flowmeter should support PROFIBUS PA protocol.
.6 Flowmeters and controller shall be:
- Siemens SITRANS F M MAGFLOW Mag 1100 7ME6110-1RA20-2AA2 +
FDK-083G0686 (Grounding rings)
- Siemens MAG 6000 7ME6920-1AA10-1AA0 + FDK-085U0236 (Profibus PA
Module) + FDK-083F3058 (Cable) + FDK-085U1053 (Wall mounting unit) +
FDK-085U0220 (USM Potting Kit) as available from EB Horsman & Son (1-
888-467-7626)
2.2 Ultrasonic Flowmeter (UV Flow Measurement)
.1 Flowmeter shall be four channel, includes two sensors, shall be capable of expanding to
four sensors if required, and clamp-on ultrasonic type with mounting hardware for UV
flow measurement.
.2 Acceptable flow velocity range shall be from 0.3 to 12 m/s, with meter accuracy of within
0.5% of scale down to 0.3 m/s.
.3 The flowmeter shall be powered by 120VAC. The 4-20mA flow output shall be wired to
the Plant PLC.
.4 The enclosure shall inherently meet NEMA 4x/IP65 requirements, and be provided with
mounting hardware for 1200mm diameter pipe line.
.5 Provided with the meter shall be an integral transmitter with display board capable of
providing bidirectional rate of flow and totalization. Operating parameters and units of
measurement shall be operator definable.
Section 16915
Flow Monitoring
Page 3 of 3
Regional District of North Okanagan July 2017
Duteau Creek WTP UV Upgrades
.6 Meters located in areas where accessibility is limited or the area has potential for flooding
shall have a remote transmitter with display board capable of providing bidirectional rate
of flow and totalization. Operating parameters and units of measurement shall be operator
definable. Remote transmitters shall be installed at locations shown on drawings.
.7 Flowmeters shall be:
- Siemens SITRANS FUS 1010 Standard Clamp-on (7ME3530-9CA60-0QA1-
ZH1A-K01-K01-T01-Y19) as available from EB Horsman & Son (1888-467-
7626).
2.3 Flow Switch (FSL831/832/833)
.1 Flow switch shall be FLT93 series FlexSwitch. Provided with dual, independent SPDT
relays signal to wire to the Plant PLC, the output relay rating configurable 6A resistive at
115VAC.
.2 Accuracy 2% of the setpoint velocity at -40C to +40 C range; Repeatability of 0.5 %
reading.
.3 The enclosure shall inherently meet NEMA 4x/IP66 requirements.
.4 The switch shall be powered by 120VAC.
.5 The process connection would be 1” MNPT.
.6 Flow switch shall be:
- FCI – FLT93L-4B1A1BC4B00000 as available from EB Horsman & Son
(1888-467-7626).
3. Execution
3.1 Process Magnetic Flowmeter Installation
.1 Flowmeter tube flanges, adjacent flanges, and grounding rings shall all be electrically
bonded together using minimum #8 AWG green insulated grounding conductors.
.2 The Magnetic flowmeter shall be configured to use PROFIBUS PA protocol to
communicate with the Plant PLC.
.3 Support stand shall be provided if required.
End of Section