21
Seite 1 1 Professor Bjarne W. Olesen, PhD Director International Centre for Indoor Environment and Energy Department of Civil Engineering Technical University of Denmark Possibilities and limitations for using water based radiant heating and cooling systems. International Centre for Indoor Environment and Energy The 20-20-20 EU policy by 2020 Greenhouse gas levels Energy consumption Renewables in energy mix -20% -20% 100% 20% 8,5% Comprehensive set of legislation to enhance energy efficiency . Directive for the taxation of energy products and electricity Revision in 2008 . Energy end-use efficiency and energy services Directive Services . Directive on the promotion of cogeneration Generation Buildings . Energy performance of buildings Directive (EPBD) . Directive establishing a framework for the setting of eco-design requirements for energy-using products (implementing directives for e.g. boilers, refrigerators, freezers and ballasts for fluorescent lighting Eco-Design . Directives for labelling of e.g. electric ovens, air-conditioners, refrigerators and other domestic appliances . Regulation of Energy Star labelling for office equipment Product Labelling Taxation 3/14 Energy Performance of Buildings Directive – EPBD (2002/91/EC) Requirements - for Member States to specify and implement: An integrated methodology to rate the energy performance of buildings Minimum energy performance standards for new and for existing buildings that undergo major renovation Energy performance certificates for buildings Regular inspections of boilers and air-conditioning systems 4/14

Seite 1 - SyracuseCoE · 2015. 6. 16. · Seite 7 7 ISO/TC 205/WG 8 Radiant Heating & Cooling System ISO/DIS 11855-1 ISO/DIS 11855-2 ISO/DIS 11855-3 (July) ISO/DIS 11855-4 ISO/CD

  • Upload
    others

  • View
    11

  • Download
    0

Embed Size (px)

Citation preview

  • Seite 1 1

    Professor Bjarne W. Olesen, PhD Director

    International Centre for Indoor Environment and Energy Department of Civil Engineering Technical University of Denmark

    Possibilities and limitations for using water based radiant heating and cooling systems.

    International Centre for Indoor Environment and Energy

    The 20-20-20 EU policy by 2020

    Greenhouse gas levels

    Energy consumption

    Renewables in energy mix

    -20% -20% 100%

    20%

    8,5%

    Comprehensive set of legislation to enhance energy efficiency

    l

    . Directive for the taxation of energy products and electricity

    Revision in 2008 . Energy end-use efficiency and energy services Directive Services

    . Directive on the promotion of cogeneration Generation Buildings . Energy performance of buildings Directive (EPBD)

    . Directive establishing a framework for the setting of eco-design requirements for energy-using products (implementing directives for e.g. boilers, refrigerators, freezers and ballasts for fluorescent lighting

    Eco-Design

    . Directives for labelling of e.g. electric ovens, air-conditioners, refrigerators and other domestic appliances . Regulation of Energy Star labelling for office equipment Product Labelling

    Taxation 3/14

    Energy Performance of Buildings Directive – EPBD (2002/91/EC) l

    Requirements - for Member States to specify and implement:

    §  An integrated methodology to rate the energy performance of

    buildings

    §  Minimum energy performance standards for new and for

    existing buildings that undergo major renovation

    §  Energy performance certificates for buildings

    §  Regular inspections of boilers and

    air-conditioning systems

    4/14

  • Seite 2 2

    EPBD – Energy Performance Certificate lExample for Member States’ room for manoeuvre:

    5/14

    Achieving Excellence in Indoor Environmental Quality

    •  Physical factors –  Thermal Comfort –  Air quality (ventilation) –  Noise-Acoustic –  Illumination

    •  Personal factors –  Activity –  Clothing –  Adaptation –  Expectation –  Exposure time

    Energy Efficient Technologies

    •  Indoor air quality –  Pollution sources –  Air distribution (contaminant removal) effectiveness –  Personal ventilation –  Air cleaning

    •  Thermal comfort –  Low Temperature Heating- and High Temperature Cooling Systems –  Thermo-Active-Building-Systems (TABS) –  Drifting temperatures

     No cooling – decreased performance  Low energy costs  Low operation costs

     Full Air-Conditioning  Constant temperature  Draught, Noise, SBS  High energy costs  High operation costs

     Thermo-Active-Building-Systems  Temperature ramps  Reasonable energy costs  Low operation costs

    COMFORT-PERFORMANCE

  • Seite 3 3

    CONCEPTS OF RADIANT HEATING AND COOLING SYSTEMS

    •  Heating - cooling panels •  Surface systems •  Embedded systems

    HISTORY Frank Lloyd Wright's Usonian Houses 1930’s

    A lightweight floor slab was used and the traditional basement was dispensed with. By using steam or hot water piping, it became possible to heat the floor, therefore eliminating the need for radiators. The overall result was heat without a draft or temperature variation of the most comfort - cool head and warm feet.

    c. 10,000 B.C., China, the word “kang,” can be traced back to the 11th century B.C. and originally meant, “to dry” before it became known as a heated bed. c. 5,000 B.C., evidence of baked floors are found foreshadowing early forms of “kang” and “dikang” (heated floor) later “ondol” (warm stone) in China and Korea, respectively.

    c. 10,000 B.C., China

    HISTORY

    Hypocausts were used from the third century B.C. in ancient Europe.

    c. 1904, Liverpool Cathedral heated with system based on the hypocaust principles.

    Suspended cooled ceilings

  • Seite 4 4

    Radiant surface heating!and cooling systems!

    Floor! Wall!

    Thermo Active Building Systems!

    Ceiling!

    The image cannot be displayed. Your computer may not have Reinforcement!

    Floor!

    Concrete! Pipes!

    Room!

    Room!

    Window!

    Embedded piping systems

    •  Free use of space •  No cleaning •  Safety •  Comfort •  Energy

    6/24/11 Bjarne W. Olesen, ICIEE-DTU 15

    Low-Temperature heating High-Temperature Cooling

    •  Higher efficiency of boilers and chillers •  Lower distribution losses •  Better use of renewable energy sources •  Low energy consumption for circulation •  Future flexibility •  Low Exergy

    THERMAL COMFORT

    •  -0,5 < PMV < +0,5 ; PPD < 10 %

    •  Spaces with sedentary work : –  Summer clothing 0,5 clo – Winter clothing 1,0 clo – Activity level 1,2 met

    •  OPERATIVE TEMPERATURE •  WINTER 20 °C (68F)< to < 24 °C(75.2F) •  SUMMER 23 °C (73.4F) < to < 26 °C (78.8F).

  • Seite 5 5

    OPERATIVE TEMPERATURE

    –  to = (hcta + hrtr)/(hc + hr) –  to = 0.5ta + 0.5tr ( low air velocity)

    »  ta = Air temperature »  tr = Mean radiant temperature »  hc = Convective heat exchange coefficient »  hr = Radiative heat exchange coefficient

    Mean Radiant Temperature

    •  tr = ΣFp-i tsi –  Fp-i = Angle factor from person to surface i –  tsi = Surface temperature of surface i –  ΣFp-i = 1

  • Seite 6 6

    Angle factor

    00,050,10,150,20,250,30,350,40,45

    Gulv Loft Vindue Brystning Bagväg SidevägFloor Ceiling Window Out. Wall Back Wall Side Wall

    SURFACE HEATING AND COOLING Heat transfer coefficient

    8,08,0

    6,0

    11,011,0

    7,0

    5,56,5

    7,5

    8,5

    9,5

    10,5

    11,5

    Floor

    Ceiling

    Wall

    W/m2K

    Heating Cooling

    6/24/11 23

    SURFACE HEATING AND COOLING Max. - Min. Surface temperature

    40

    17

    27

    17

    35

    20

    29

    20

    15

    20

    25

    30

    35

    40

    45

    Floor

    Ceiling Wall

    oC

    Heating Cooling

    Perimeter

    6/24/11 24

    MAXIMUM HEATING AND COOLING CAPACITY

    160

    72

    42

    99

    165

    42

    99

    42

    020406080100120140160180200

    Floor

    Ceiling Wall

    Heating Cooling

    Perimeter

    W/m2

  • Seite 7 7

    ISO/TC 205/WG 8 Radiant Heating & Cooling System

    ISO/DIS 11855-1 ISO/DIS 11855-2 ISO/DIS 11855-3 (July) ISO/DIS 11855-4 ISO/CD 11855-5 ISO/CD 11855-6 (July)

    1. Screed 2. Pipes 3. Plastic foil 4. Insulation 5. Levelling 6. Concrete

    ALUMINUM HC device: Floor Heating & Cooling (type B), R=0.01~0.1, T=150 & 300

    0

    20

    40

    60

    80

    100

    120

    140

    160

    -15 -10 -5 0 5 10 15 20 25 30Heating/cooling medium differential temperature ΔθH=θH-θi [°C]

    Hea

    t exc

    hang

    e [W

    /m2]

    T=150, R=0.01T=150, R=0.1T=300, R=0.01T=300, R=0.1

    Figure 4.17 Heat exchange between the surface (with ceramic tiles, wooden

    parquets or carpet R?B=0.1 and no covering R?B=0) and the space when aluminium heat conductive device used

    Heating/ cooling capacity, EN1264 and EN 15377

  • Seite 8 8

    Wood constructions

    6/24/11 30

    Finite Element Method

    Radiant Floor Cooling

    Radiant Floor Cooling

    OPERA HOUSE

    SHOPPING CENTER MUSEUM

    AIRPORT

  • Seite 9 9

    Slide 33

    Opera House in Copenhagen Cooling

    •  2,5 MW cooling capacity •  2 systems – 10/15°C and 15/18 °C •  Free cooling from sea water •  Combined radiant floor heating + radiant

    floor cooling •  18 km underfloor cooling tubing •  Quiet cooling walls •  De-humidification Condensing coils for

    ventilation

    BBI airport, Berlin, Germany. 76,750 m² to be heated/cooled with floor system

    •  The in-city airports in Berlin will be closed and replaced by the new BBI

    •  In future, up to 6,500 persons will be starting or landing at the new airport in a typical hour.

    •  There will be a floor heating/cooling realized in 2010

    Airport Bangkok HEAT LOADS

    •  Once the heat load to the space had been determined, the conditioning system was being developed.

    •  The loads for the concourse were 97 W/m2 •  The conditioning systems to remove this heat from the

    space was divided as follows: – Radiant Floor 80 W/m2 – Ventilation Air 17 W/m2

  • Seite 10 10

    Airport Bangkok Airport Bangkok

    VENTILATION

    •  The outdoor air AHU will supply variable outdoor air quantities at a constant temperature to the zone AHU’s.

    •  The volume of outdoor air will be varied depending upon the CO2 levels metered in each zone, down to a fixed minimum position

    •  Each zone AHU can supply air at 16 C to the space via the displacement diffusers

    Ta = 16 oC Td = 10 oC

    TsupplyW = 13 oC

  • Seite 11 11

    Airport Bangkok TABS Thermo Active Building Systems

    Insulation!Floor!

    Concrete!

    Reinforcement!

    Pipe!

    Room!

    Room!

    Window!

    Concept of Thermo Active Building Systems

  • Seite 12 12

    The analysed building

    West room

    Width of the room: 3.6 m

    Window portion of the outside wall: 50%

    Office building

    Slab used in simulation Convegno Internazionale AICARR

    Prof. Bjarne W. Olesen, International Centre for Indoor Environment and Energy, DTU

    Sun protection

    Sun protection: Only during occupation and direct exposure of sunlight and operative temperature above 23 °C, reduction factor 0.5

    ®VENTILATION RATES

    During time of occupancy: 1.5 ach

    Outside time of occupancy:1.5 ach

  • Seite 13 13

    CONTROL OF WATERTEMPERATURE •  Supply water temperature is a function of outside

    temperature according to the equation:

    •  Average water temperature is a function of outside

    temperature according to:

    •  Average water temperature is constant and equal to: 22°C in summer and 25°C in winter.

    •  Supply water temperature is a function of outside temperature according to the equation:

    ( ) )22(*6,12020*52,0sup −−+−= oexternalply ttt °C (case 801)

    ( ) )22(*6,12020*52,0 −−+−= oexternalaverage ttt °C (case 901)

    ( ) 1818*35,0sup +−= externalply tt °C summer (case 1401) ( ) 1818*45,0sup +−= externalply tt °C winter (case 1401)

    PERFORMANCE EVALUATION

    •  Range of operative temperature •  Pump running time •  Energy consumption

    Operative temperature range, May to September Different control concepts for water temperature, Time of operation 18:00 - 6:00 Uhr

    33

    14

    54 54 52

    38

    0

    10

    20

    30

    40

    50

    60

    70

    80

    90

    100

    Tsup =Tdp

    Pump Tsup =F(ext)

    Pump Tavg =F(ext)

    Pump Tavg =22 °C

    Pump Tavg =20 °C

    Pump Tavg =18 °C

    Pump

    Control of water temperature

    Ope

    rativ

    e te

    mpe

    ratu

    re ra

    nge

    [%]

    >27

    26-27

    25-26

    22-25

    20-22

  • Seite 14 14

    Comparison with the norm DIN 1946-part 2

    19

    20

    21

    22

    23

    24

    25

    26

    27

    28

    -12 -10 -8 -6 -4 -2 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32

    Outdoor Temperature [°C]

    Indo

    or O

    pera

    tive

    Tem

    pera

    ture

    [°C

    ]

    Venezia fall16

    Comparison with the norm DIN 1946-part 2

    19

    20

    21

    22

    23

    24

    25

    26

    27

    28

    -12 -10 -8 -6 -4 -2 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32

    Outdoor Temperature [°C]

    Indo

    or O

    pera

    tive

    Tem

    pera

    ture

    [°C]

    Venezia fall17

    Circulation pump on at 18:00 Sunday

    Circulation pump on 10:00 Sunday

    CONTROL OF WATER TEMPERATURE SUMMER

    Operative temperature May to September

    Water temperature control. Time of operation 6 pm to 6 am

    26 36

    26 30 33 39

    32 34

    0 10 20 30 40 50 60 70 80 90

    100

    Tsup= f(Ti,Te) Tave= f(Ti,Te) Tave=

    22 °C Tsup= f(Te) Tsup= f(Ti,Te) Tave=

    f(Ti,Te) Tave= 22 °C Tsup= f(Te) Control methods

    Ran

    ge o

    f ope

    rativ

    e te

    mpe

    ratu

    re %

    >27 26-27 25-26 22-25 20-22

  • Seite 15 15

    ART MUSEUM IN BREGENZ

    •  Design requirements – Air temperature variations during a day within 4 K – Relative humidity variations less than 6 % during a day. –  Seasonal variations between 48 and 58 % – Room temperature in winter 18 oC to 22 oC – Room temperature in summer 22 oC to 26 oC, occasional up to 28 oC

    •  Design load 250 persons pr. day, 2 hours •  Displacement ventilation < 0,2 h-1 •  Floor area 2.800 m² , 4 floors •  28.000 m plastic pipes embedded in walls and floor slabs

    ART MUSEUM BREGENZ

    •  3.750 m² floor area •  4.725 m² embedded pipes

    •  Condensing boiler

    •  Ventilation 750 m3/h per floor (first design was 25.000 m3/h

    ART MUSEUM IN BREGENZ ART MUSEUM BREGENZ

  • Seite 16 16

    ART MUSEUM BREGENZ

    Offices M+W Zander Stuttgart, Germany -  TABS –

    - in 6.500 m2

    MW-Zander Measurements during normal operation

    Operative temperature sensor

    Air temperature sensor

    Transmitters

  • Seite 17 17

    Stuttgart

    Stuttgart 24.07. - 28.07, 2000

    20

    21

    22

    23

    24

    25

    26

    24. J

    ul

    24. J

    ul

    25. J

    ul

    25. J

    ul

    26. J

    ul

    26. J

    ul

    27. J

    ul

    27. J

    ul

    28. J

    ul

    28. J

    ul

    29. J

    ul

    Zeit

    Tem

    pera

    tur [

    °C]

    O1-Operative Büro 4. Stock Fenster-Ost F1-Fläche 4. Stock RucklaufO-Operative Büro 5. Stock Fenster-West O6-Operative Büro 5. Stock Fenster-Ost

    Energy concept in BOB.1 Temperatures for one year in BOB.1

  • Seite 18 18

    cooling period in BOB.1 Heating period in BOB.1

    0

    5000

    10000

    15000

    20000

    25000

    30000

    35000

    Heizung Kühlung Lüftung Beleuchtung Pumpen Warmwasser Summe

    Yea

    rly e

    nerg

    ie c

    osts

    [€/m²a

    ]

    BestandBOB.1

    Energy efficiency

    94 % energy saving compared with conventional cooling

    60 % energy saving for lighting by daylight steering

    The need of energy for heating, cooling, air-ventilation lighting and warm water is 27,8 kWh/m² per year

    Energy costs per m², per year: 2,7 EUR, per month 22,5 Cent

    Heat pump

    Free Cooling and line up to a reversible Heat Pump, A - free cooling by means of ground coupling (cca 10-25 W/m) B - possibel to obtain much higher cooling

    capacity by using reversible heat pump

  • Seite 19 19

    Influence of condensing temperature on COP

    0.0

    0.5

    1.0

    1.5

    2.0

    2.5

    3.0

    3.5

    4.0

    4.5

    5.0

    30 40 50 60Temperature, condenser (°C)

    COP

    Evaporation - 5°C

    Absorption Heat Pump

    Cooling by using Absorption Heat Pump supported by Solar Heat, 1 - cooling tower, 2 - control system unit, 3 - Solar collector, 4 - buffer tank, 5 - additional heating, 6 –

    absorptive heat pump, 7 - floor heating system

    Ground Heat Exchanger

    a - ground well (hole), b - , c - gap wall,

    d - ground collector, e - plate floor cooler, f- soil cooler

    BoilerChiller

    Temperature-Humidity

    Outsidetemperature

    Floor temp.

    Supply Limiter

    ReturnMixing valve

    Shut off valves

    Control

    Room sensor Control unit

    Valve

    Manifold

    Pump

    Control of a combined floor heating-cooling system

    with individual room control

  • Seite 20 20

    SELF CONTROL

    80W/m?

    40W/m?

    20W/m?

    10W/m?

    Heat load

    FloortemperatureHeat. level temp. tiles

    Heat. level temp. carpet

    38,4

    29,4

    24,922,5

    31,9

    26,2

    23,321,7

    27,3

    23,922,1

    21,12022242628303234363840

    Floortemperature at 20 °C RoomtemperaturedegC F18 64,419 66,220 6821 69,822 71,623 73,424 75,225 7726 78,827 80,628 82,429 84,230 86

    PRE- FABRICATION

    Low Exergy Hydronic Radiant Heating and Cooling Why?

    •  Water based systems

    •  Low temperature heating - High temperature cooling •  More economical to move heat by water:

    – Greater heat capacity than air – Much smaller diameter pipes than air-ducts –  Electrical consumption for circulation pump is lower than for fans

    •  Lower noise level •  Less risk for draught •  Lower building height •  Higher efficiency of energy plant •  But

    –  Reduced capacity? –  Acoustic? –  Latent load?

  • Seite 21 21

    International Centre for Indoor Environment And Energy

    THANK YOU